Name of Project: RVL OFFICE Job ref./Enquiry No.

: -
Address: Coimbatore Estimated by: Heat load for: Summer
Space used for: OFFICE Peak load at: 4.00 PM
Area in sq.ft = 4900.0 Length in Ft. 70.0 Height in ft.= 15.0 DESIGN CONDITIONS
Volume in cu.ft 73500 Width in Ft. 70.0 Contact factor : 0.85 (British Units) DBT % RH WBT Gr/lb
Bypass factor : 0.15 Btu/hour Outside 102.2 37 79.2 114
Area x Temp.diff. x Factor = Sensible Load Latent Load Inside 75 50 62.5 65
SOLAR GAIN-GLASS Difference 27.2 xxxx xxxx 49
Glass (N) 11 0.56 0 - Eq. Temp.correction factor 0
Glass (E) 11 0.56 0 - OUTDOOR AIR (CFM)
Glass (S) 11 0.56 0 - 84 People x 8.50 CFM/Person = 714.00
Glass (W) 165 0.56 0 - 2 No. of air changes/hr = 2450.00
Glass (NE) 11 0.56 0 - Selected Outdoor Air CFM = 2450.00
Glass (SW) 113 0.56 0 -
Glass (NW) 118 0.56 0 - APPARATUS DEW POINT
Glass (SE) 11 0.56 0 -
SOLAR & TRANSMISSION GAIN-WALLS & ROOF Effective Sens. Heat Factor (ESHF) = ERSH/ERTH = 0.96
Wall (N) 4 0.35 0 -
Wall (E) 18 0.35 0 - INDICATED ADP = 54 SELECT.ADP= 54
Wall (S) 16 0.35 0 -
Wall (W) 12 0.35 0 - DEHUMIDIFIED AIR QUANTITY
Wall (NE) 10 0.35 0 -
Wall (SW) 14 0.35 0 - Dehum. Rise = Contact Factor x (Rm Temp. - ADP)= 17.8
Wall (NW) 6 0.35 0 - Dehum. CFM = ERSH/1.08/Dehum. Rise = 15614
Wall (SE) 18 0.35 0 - Dehum CFM /400 = 39.035
Exposed Roof 4900 35 0.48 82320 - U-factors: Roof Insl 0.12
TRANSMISSION GAIN-EXCEPT WALLS & ROOF Exposed Walls 0.35 Roof Non Insl 0.48
All Glass 0 27.2 1.13 0 - Partition Walls 0.40 Ceiling 0.48
Partition Wall 4200 22.2 0.40 37296 - Partition Glass 0.43 Floor 0.48
Partition Glass 22.2 0.43 0 - Factors for Glass: Solar gain 0.56
Ceiling 4900.00 22.2 0.48 52214 - Transm. Gain 1.13
Floor 4900.00 22.2 0.48 52214 - Some typical inside design conditions:
INTERNAL HEAT DBT % RH WBT Gr/lb
People 2 245 205 490 410 70 50 58.5 54.8
DESIGN CONDITIONS

Lights (I) - W 9800 3.41 1.0 33418 - 70 55 59.7 60.1


Lights (F) - W 1.512 3.41 1.25 6 - 72 50 60.1 58.8
Equip.Load -W 2 3.41 1.0 7 - 72 55 61.4 64.4
-do- in HP 0 2545 1.0 0 0 74 50 61.8 62.0
Others 0 0 74 55 63.0 68.0
Subtotals 257966 410 75 50 62.6 65.0
Safety Factors (12.5% & 5% respectively) 32246 21 75 55 64.0 71.5
Room Sensible & Latent Loads 290212 431 76 55 64.9 74.0
77 55 65.6 76.6
Outdoor Air cfm = 2450 10796 12245 90 88 86 184.0
Effective Room Sensible Heat (ERSH) 301008 - 104 45 83 138.0
Effective Room Latent Heat (ERLH) - 12676 105 40 83 136.0
Effective Room Total Heat (ERTH) 313683 110 25 78 94.0
OUTDOOR AIR (O.A.)
Sensible Load 61176 - Air on Coil in deg F: Check figures:
Latent Load - 69389 DBT : 79 sq.ft/TR = 129
Effective Room Total Heat + O.A Heat 444248 WBT : 65 cfm/sq.ft = 3.2
Other Heat Gains @ 3% 13327 cfm/TR = 409

GRAND TOTAL HEAT 457575 TMBH = 457.6

TR 38.13 SMBH = 362.2 Sheet No.