TECHNICAL SUBMITTAL

PROJECT

CUSTOMER:
Project: AL-HADETHA CUSTOMS - CHILLER PLANT

Location: TABOUK

Title: Technical Submittal

Item: Supply of AC UNITS - Chillers, AHU,FCU,Split

Usage: HVAC

Supplier: Zamil Air conditioners


-P.O.Box 7504
-Jeddah – 23523
-Tel # (012) 234 3640

Manufacturer: Zamil Air conditioners


-P.O.Box 1440
-Dammam-31424,
-K.S.A Tel# (013) 8574444
INDEX

1. SPECIFICATIONS COMPLIANCE
a. Chillers
b. AHU
c. FCU

2. TECHNICAL DATASHEET WITH DRAWING


a. Chillers Plant
b. AHU + FCU + Split (each Building)

3. CERTIFICATES
a. Chillers
b. AHU
c. FCU
d. Split

4. CATALOGUES
1. SPECIFICATIONS COMPLIANCE
1.a - Chillers
Noted
Noted

Noted

Comply, refer to attached


Comply, refer to attached

Comply, refer to attached


Comply, attached Manual
Comply, attached Manual

ir Conditioners Noted

Noted
Noted

Comply

Comply

Comply

Comply

Comply

Comply
Comply
Please refer to datasheet

Comply

Comply ir Conditioners
with Rubber
Isolators
Comply

Comply, 3
compressors

Comply

Comply

Comply

Comply, disconnect switch to be installed at site next to unit by contractor.

ir Conditioners
Noted

Noted

Noted

ir Conditioners
1.b - AHU
ir Conditioners

Comply, AHU are AHRI certified as per attached certificates


Comply

Comply, Double skin 50mm insulation

Comply, Insulated GI painted Drain Pan

ir Conditioners
Comply, Backward curved fan is provided
Comply, TEFC motor provided
Comply

Comply, Spring isolators


1"provided under fan

Comply
Not required

Not required

Comply

Comply,
copper
tubes
with AL
ir Conditioners
fins

Comply, UL heater provided


Comply

Comply, with 2" AL washable filter and 15"


Bag filter

Comply, Mixing box provided With AL dampers

ir Conditioners
1.c - FCU
Comply

ir Conditioners

Comply

NA

NA

Comply, number of rows as per selection


Noted
Noted

Noted

Noted

Noted
Noted
Noted

Noted

Noted

Noted ir Conditioners

Noted
Comply

Comply, FCU units are cool only

Comply

Comply

Comply

Heater Not required for FCU

Comply
Comply

GI panels not painted, units are ceiling concealed

Valve package to be installed at site by contractor

ir Conditioners
Comply

ir Conditioners
2. TECHNICAL DATA WITH
DRAWING
2.a Chillers Plant
Chillers Design Data

Ambient Water in Temp Water out Temp


S.NO UNITS TR location Coil Compressor Power Supply QTY
(°C) (°C) (°C)

Aluminum fins /
0.1 chillers 322 46 11 5.5 outside Rotary Screw 380V-3Ph-60Hz 3
copper tubes

Zamil Selection Chillers Data

Ambient Water in Temp Water out Temp


S.NO UNITS TR location Coil Compressor Power Supply QTY
(°C) (°C) (°C)

Aluminum fins /
0.1 chillers 324.5 46 11 5.5 outside Rotary Screw 380V-3Ph-60Hz 3
copper tubes
ChillZAC

Chiller Unit 1.1.82.0

Customer: WATANCO Done By: AB


General Info

Project: AL-HADETHA CUSTOMS - CHILLER PLANTLocation: TABOUK

Ref/Tag: CH 1 TO 3 Quantity: 3

Revision: 0 Date: Tuesday, November 29, 2022

Required Capacity Required Outside Required Inlet and Leaving


Conditions Water Temperatures

Total Ambient Altitude Inlet Outlet

TR °C ft °C °C
Input Conditions

322.0 46.00 0.000 11.00 5.50

Auxiliary Required Options Required Power Supply

Evaporator Fouling Factor Refrigerant Compressor Type Voltage Phases Frequency

m²°C/kW Volts Phase Hertz


0.017610 R134a Semi Hermetic Screw 380V 3 60Hz

Selected Unit Model


ASC390B

Performance @ 46 °C Ambient Condenser Coil and Fan


Total Cooling Capacity 324.5 TR Coil Type Cu/Al
Total Power Input 536.2 kW Coil Face Area 57.49 m²
Compressor Power Input 488.5 kW Number of Rows 4-3
Water Flow Rate 49.63 LPS Fins per Inch 14
Water Pressure Drop 44.35 kPa Coil Tube Dia 9.5 mm
Entering Water Temperature 11.00 °C Fan Diameter 800 mm
Leaving Water Temperature 5.50 °C Fan Quantity 24
IPLV.IP (EER) 14.20 Btu/W.h Total Fan Airflow 143,860.91 LPS
IPLV.SI (COP) 4.161 Kw/Kw
COP 2.128 Kw/Kw Crankcase Heater
Compressor Data Supply Voltage 230 Volts
Total Capacity 900 W
Total Amperes 3.9 Amps
Output Performance

Comp 1 Comp 2 Units

Type Screw Screw


No of Compressors 2 1 Physical Data
Locked Rotor Ampere (each) 823 627 Amps
Rated Load Ampere (each) 304.1 268.1 Amps Length 12325 mm
Circuit Breaker Poles 3 3 Width 2200 mm
Circuit Breaker 1 486.6 429.0 Amps Height 2585 mm
Circuit Breaker 1 Quantity 2.0 1.0 Shipping Weight 11064 kg
Circuit Breaker 2 0.0 0.0 Amps Operating Weight 11914 kg
Circuit Breaker 2 Quantity 0.0 0.0
Water Inlet Diameter 250 mm
Water Outlet Diameter 250 mm
Condenser Fan Motor Number of Coolers 1
Fan FLA (each) 3.8 Amps
RPM 1030 Electrical Data
Total Fan Motor Power Input 47.76 kW
Circuit Breaker Quantity 12 Supply Voltage (Nominal) 380V-3Ph-60Hz
Minimum 342 Volts
Maximum 418 Volts
Sound Data Minimum Circuit Ampacity 1,043.0 Amps
Maximum Over Current Protection 1,300.0 Amps
Sound Pressure Level 79.6 dBA @ 3 m
AHRI Rating
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor
Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P)
and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at
www.ahridirectory.org
Certificates

1 of 2
PacZAC

Chiller Unit 1.1.82.0

Customer: WATANCO Done By: AB


General Info

Project: Location: TABOUK

Ref/Tag: CH 1 TO 3 Quantity: 3

Revision: Date: Tuesday, November 29, 2022

Selected Unit Model


ASC390B
Output Performance

2 of 2
2.b AHU + FCU
Building-A
A-BUILDING

Design Data

Supply Fan Return Fan ESP for each Electric Heater


Item TAG# TYPE Total Capacity (Tons) GPM Fresh Air (CFM) FLOOR Power Supply Qty
AirFlow (CFM) AirFlow (CFM) Fan (Pa) (kW)

1 A-AHU-GF-1 Chilled water AHU 38 91.2 16000 4225 16000 500 36 R.F 380V-3Ph-60Hz 2

2 A-AHU-GF-2 Chilled water AHU 20 48 7000 1750 7000 500 18 R.F 380V-3Ph-60Hz 2

3 FCU-01-1 TO 06 Chilled water FCU 1.0 2.4 420 - - 50 1 G.F 230V-1Ph-60Hz 6

4 FCU-02-1 TO 04 Chilled water FCU 3.0 7.2 1,350 - - 50 3 G.F 230V-1Ph-60Hz 4

Zamil Selection Data

Total Capacity Sensible Capacity Supply Fan Return Fan ESP for each Electric Heater
Item TAG# TYPE Model GPM Fresh Air (CFM) FLOOR Power Supply Qty
(Tons) (Tons) AirFlow (CFM) AirFlow (CFM) Fan (Pa) (kW)

1 A-AHU-GF-1 Chilled water TW26P5BD 38 32.56 91.66 16,000 4225 16000 500 36 / 2 Stages R.F 380V-3Ph-60Hz 2

2 A-AHU-GF-2 Chilled water TW11P5BD 20 16.32 48.25 7,000 1750 7000 500 27 / 2 Stages R.F 380V-3Ph-60Hz 2

3 FCU-01-1 TO 06 Chilled water DWX06 1.0 0.74 2.4 420 - - 50 1 G.F 230V-1Ph-60Hz 6

4 FCU-02-1 TO 04 Chilled water DWX18 4.1 2.92 9.8 1,466 - - 50 3 G.F 230V-1Ph-60Hz 4
239 311 311

120
82.5

675
1,995
1,830
2,075
1 2 1 2 3 4 5

801
519
82.5
80

1,290 550 590 590 600 700 1,340


2,430 3,230
L1 L2
5,660
112.5
82.5

552
801
1,995
1,770
1,830

642
112.5
82.5

SURFACE CASING TOLERANCE


Supply air TW26P5BD P5 Exhaust air TW26P5BD P5 Type of unit External unit
Panel outside GI-P AL-HADETHA WN
Project:
Panel inside GI AJD-26234-R1* 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 16-Jan-23 user CW
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: A-AHUGF-1
VER: 3.8.33
DRAWING NO. Office
Classic
A-BUILDING Air Conditioners
TEL. EMail
+966 3 847 3333 [email protected]

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer AJD-26234-R1*
Phone +966 3 847 3333 From date 16-Jan-23
Fax Position A-AHUGF-1
LV CW
web www.zamilac.com

Office / Agent user Print data 16-Jan-23

POINT LOAD DISTRIBUTION

SECTION 1 SECTION 2
o o o o o o

o o o o o o

93

Delivery sections No. Points Each load (kg)

1 Delivery Section 6 228


2 Delivery Section 6 345

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/7
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer AJD-26234-R1*
Phone +966 3 847 3333 From date 16-Jan-23
Fax Position A-AHUGF-1
LV CW
web www.zamilac.com

Office / Agent user Print data 16-Jan-23


Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class E 2016 Model box as declared on the Eurovent Certified Performance website
CAL(R) L3/L3.

Serie TW Sealevel [m] 0


Execution Standard Design Outdoor Temperature 46 °C
Type of unit External unit Unit design NRVU - BVU

Unit definition General data

Unit size TW26P5BD Casing:


Type Supply air Thickness P5
Panel inside GI Thick [mm] 0.7
Airflow [cfm] 16,000 Length [mm] 3,820.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [inWG] 1.999 Width [mm] 1,995.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [inWG] 4.573 Height [mm] 1,995.0
Profiles AL

1 Double mixing section 590.0 mm 0.265 inW

Recircle air [cfm] 11,775 Humidity 64.05 Mixed air Temp. 84.38 Humidity [%] 66.30
Fresh air [cfm] 4,225 Humidity 72.00 total air 16,000 Mixing Ratio [%] 74

Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 4,800
Total Qta. Levers 1 air velocity [m/s] 4.12
Each Torque [Nm] 3.03

Damper: Dimensions [mm] 1,770.0 x 412.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 12,800
Total Qta. Levers 1 air velocity [m/s] 8.28
Each Torque [Nm] 4.04

1 Pcs Measuring Opening

16-Jan-23 12:14
Offer AJD-26234-R1* Page 2/7
Position A-AHUGF-1 From date 16-Jan-23

Unit size TW26 AirCalc++ Vers. 3.8.33

2 Bag Filter section with prefilter 590.0 mm 0.976 inW

Type 2" Aluminum


Cells pcs x size [mm] 9 x 592.0 x 592.0
Class G3 ISO ePM Coarse 55%
Clean dP [inWG] 0.153
Dirty dP [inWG] 0.458
Airflow [cfm] 16,000 Cross section velocity [m/s] AEC [kWh] N/A
2.1

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 9 x 592.0 x 592.0
Clean dP [inWG] 0.470
Dirty dP [inWG] 0.871
Airflow [cfm] 16,000 Cross section velocity [m/s] 2.1
1 Pcs Measuring Opening
1 Pcs Differential Pressure switch

3 Cooling coil 600.0 mm 0.466 inW

Medium Water
Airflow [cfm] 16,000
Med. Flow [Gpm] 91.66
air velocity [m/s] 2.67
Med. velocity [m/s] 0.85
Air in [gF] 84.38 Humidity [gF] 66.3
Med. in [gF] 41.88
Air out [gF] 61.51 Humidity [gF] 57.28
Med. out [gF] 51.78
total capacity [RT] 38.00
Med. pres. drop [inWG] 40.71
Sens. capacity 32.56
SHR 0.86
Air press. drop (wet) [inWG] 0.466
Air press. drop (dry) [inWG] 0.419

No. of Rows 4 Materials:

Fins AL
Fin space [mm] 2.5
RRows CU
Connection in NPT 2 1/2
Header CU
Connection out NPT 2 1/2
Frames GI
CW-1/2"-2.5 4R - RH
Water content (KG) 60.4
1 set Coating for End Plates

Drain pan Quality galvanized painted Drain connection 1 1/4

1 Pcs Measuring Opening


1 Pcs Drain second wall (for doubl wall drain)

4 Electric heater 700.0 mm 0.201 inW

HTRD-TW26-36-02-Q-C-WX Heat capacity [KW] 36.00


Entering [gF] 41.00 Voltage [V] 3x400
Leaving [gF] 48.19 Steps 2

Air volume [cfm] 16,000 Kw: Equally Divided

16-Jan-23 12:14
Offer AJD-26234-R1* Page 3/7
Position A-AHUGF-1 From date 16-Jan-23

Unit size TW26 AirCalc++ Vers. 3.8.33

5 Centrifugal fan / belt driven Supply 1,340.0 mm 0.666 inW

Backward Inclined Fan Error Motor


Air volume [cfm] 16,000 Protection IP55
External press [inWG] 1.999
Dyn. pres. [inWG] 0.333 Power [kW] 15.000
Tot. pres. [inWG] 4.573 Speed [1/m] 1,765
Speed [1/m] 1,359
Fan shaft power [kW] 10.548 Supply 3x400 / 60
efficiency % 81.53
Total Real Power Input [kW] 14.0

Fan pulley SPB280 Bush 2517-50 Axle distance ca. [mm] 419
Motor pulley SPB212 Bush 2517-42
Belt 2x 1600
System effect pressure drop included
Pulleys & Belts selected with service factor 150%

Note: Fan discharge opening cutout location may vary by +-50 mm

1 Pcs Fan with motor on side


Lamp LAMP -220V - 100W Equivalent

switch SWITCH (Mounted Externally) Nominal data 220 V

16-Jan-23 12:14
Offer AJD-26234-R1* Page 4/7
Position A-AHUGF-1 From date 16-Jan-23

Unit size TW26 AirCalc++ Vers. 3.8.33

1 Pcs Lighting wired incl. switch


1 Pcs Measuring Opening

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 76.9 77.9 85.9 83.9 84.9 79.9 72.9 61.9 88.0
Outlet (db) 87.9 85.9 89.9 86.9 86.9 80.9 75.9 66.9 94.9
Casing (db) 74.2 72.9 72.0 69.9 58.4 53.0 42.4 31.4 69.2
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 62.9 63.9 71.9 69.9 70.9 65.9 58.9 47.9 74.0
Outlet (db) 73.9 71.9 75.9 72.9 72.9 66.9 61.9 52.9 80.9
Casing (db) 60.2 58.9 58.0 55.9 44.4 39.0 28.4 17.4 55.2

Unit definition General data

Unit size TW26P5BD Casing:


Type Exhaust air Thickness P5
Panel inside GI Thick [mm] 0.7
Airflow [cfm] 16,000 Length [mm] 1,840.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [inWG] 1.999 Width [mm] 1,995.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [inWG] 2.738 Height [mm] 1,995.0
Profiles AL

16-Jan-23 12:14
Offer AJD-26234-R1* Page 5/7
Position A-AHUGF-1 From date 16-Jan-23

Unit size TW26 AirCalc++ Vers. 3.8.33

1 Centrifugal fan / belt driven Return 1,290.0 mm 0.666 inW

Backward Inclined Fan Error Motor


Air volume [cfm] 16,000 Protection IP55
External press [inWG] 1.999
Dyn. pres. [inWG] 0.333 Power [kW] 11.000
Tot. pres. [inWG] 2.738 Speed [1/m] 1,765
Speed [1/m] 1,154
Fan shaft power [kW] 6.765 Supply 3x400 / 60
efficiency % 76.13
Total Real Power Input [kW] 9.4

Fan pulley SPB280 Bush 2517-50 Axle distance ca. [mm] 407
Motor pulley SPB180 Bush 2517-42
Belt 2x 1500
System effect pressure drop included
Pulleys & Belts selected with service factor 150%

Note: Fan discharge opening cutout location may vary by +-50 mm

1 Pcs Fan with motor on side


Lamp LAMP -220V - 100W Equivalent

switch SWITCH (Mounted Externally) Nominal data 220 V

16-Jan-23 12:14
Offer AJD-26234-R1* Page 6/7
Position A-AHUGF-1 From date 16-Jan-23

Unit size TW26 AirCalc++ Vers. 3.8.33

1 Pcs Lighting wired incl. switch


1 Pcs Measuring Opening

2 Double mixing section 550.0 mm 0.072 inW

Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 4,800
Total Qta. Levers 1 air velocity [m/s] 4.12
Each Torque [Nm] 3.03

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 75.0 78.0 86.0 85.0 86.0 81.0 75.0 64.0 89.1
Outlet (db) 86.0 84.0 88 85 85 79 74.0 65.0 93
Casing (db) 72.3 71.0 70.1 68.0 56.5 51.1 40.5 29.5 67.3
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 61.0 64.0 72.0 71.0 72.0 67.0 61.0 50.0 75.1
Outlet (db) 72.0 70.0 74 71 71 65 60.0 51.0 79
Casing (db) 58.3 57.0 56.1 54.0 42.5 37.1 26.5 15.5 53.3

Baseframe H80-4 Material GI isolated No


Height [mm] 80.0 Welded No

1 set Roof top-weather proof

SFP (int) 0 Specific Fan Power (Internal) MCA : 107.54 MOCP : 150 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no. Width [mm] Height [mm] Length [mm] Weight [kg]

1 1,995.0 1,995.0 2,430.0 915.00


2 1,995.0 1,995.0 3,230.0 1,380.00

16-Jan-23 12:14
Offer AJD-26234-R1* Page 7/7
Position A-AHUGF-1 From date 16-Jan-23

Unit size TW26 AirCalc++ Vers. 3.8.33

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C


P1 CML(1) 104.99 20 9.57 65.43 22.42 77.00 50 9.88 50.31 17.87
17.87 MIX 84.38 39 9.80 54.31 19.15 19.1519.15 19.15 19.15 19.15
P2 CML(2) 104.99 20 9.57 65.43 22.42 77.00 50 9.88 50.31 17.87
17.87 MIX 84.38 39 9.80 54.31 19.15 19.1519.15 19.15 19.15 19.15
P3 CK1 84.36 39 9.80 54.28 19.15 61.52 78 9.06 39.43 14.07
P4 CEE 41.00 0 0.00 5.03 -2.61 48.20 0 0.00 9.05 -0.25

16-Jan-23 12:14
239 311 311

120

484
569.5
1,385
1,465

311

507
1 2 1 2 3 4 5

504.5

394
80

1,090 550 590 590 750 700 1,090


2,230 3,130
L1 L2
5,360
82.5
112.5

255
507
1,385
1,160
1,220

623
112.5
82.5

SURFACE CASING TOLERANCE


Supply air TW11P5BD P5 Exhaust air TW11P5BD P5 Type of unit External unit
Panel outside GI-P AL-HADETHA WN
Project:
Panel inside GI AJD-26234-R1* 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 16-Jan-23 user CW
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: A-AHUGF-2
VER: 3.8.33
DRAWING NO. Office
Classic
A-BUILDING Air Conditioners
TEL. EMail
+966 3 847 3333 [email protected]

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer AJD-26234-R1*
Phone +966 3 847 3333 From date 16-Jan-23
Fax Position A-AHUGF-2
LV CW
web www.zamilac.com

Office / Agent user Print data 16-Jan-23

POINT LOAD DISTRIBUTION

SECTION 1 SECTION 2
o o o o o o

o o o o o o

93

Delivery sections No. Points Each load (kg)

1 Delivery Section 6 129


2 Delivery Section 6 226.5

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/7
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer AJD-26234-R1*
Phone +966 3 847 3333 From date 16-Jan-23
Fax Position A-AHUGF-2
LV CW
web www.zamilac.com

Office / Agent user Print data 16-Jan-23


Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class E 2016 Model box as declared on the Eurovent Certified Performance website
CAL(R) L3/L3.

Serie TW Sealevel [m] 0


Execution Standard Design Outdoor Temperature 46 °C
Type of unit External unit Unit design NRVU - BVU

Unit definition General data

Unit size TW11P5BD Casing:


Type Supply air Thickness P5
Panel inside GI Thick [mm] 1.00
Airflow [cfm] 7,000 Length [mm] 3,720.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [inWG] 1.999 Width [mm] 1,385.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [inWG] 4.789 Height [mm] 1,385.0
Profiles AL

1 Double mixing section 590.0 mm 0.209 inW

Recircle air [cfm] 5,250 Humidity 64.05 Mixed air Temp. 84.01 Humidity [%] 66.17
Fresh air [cfm] 1,750 Humidity 72.00 total air 7,000 Mixing Ratio [%] 75

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 2,100
Total Qta. Levers 1 air velocity [m/s] 2.75
Each Torque [Nm] 2.32

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 5,600
Total Qta. Levers 1 air velocity [m/s] 7.33
Each Torque [Nm] 2.32

1 Pcs Measuring Opening

16-Jan-23 12:14
Offer AJD-26234-R1* Page 2/7
Position A-AHUGF-2 From date 16-Jan-23

Unit size TW11 AirCalc++ Vers. 3.8.33

2 Bag Filter section with prefilter 590.0 mm 0.972 inW

Type 2" Aluminum


Cells pcs x size [mm] 4 x 592.0 x 592.0
Class G3 ISO ePM Coarse 55%
Clean dP [inWG] 0.153
Dirty dP [inWG] 0.458
Airflow [cfm] 7,000 Cross section velocity [m/s] AEC [kWh] N/A
2

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 4 x 592.0 x 592.0
Clean dP [inWG] 0.466
Dirty dP [inWG] 0.867
Airflow [cfm] 7,000 Cross section velocity [m/s] 2
1 Pcs Measuring Opening

3 Cooling coil 750.0 mm 0.614 inW

Medium Water
Airflow [cfm] 7,000
Med. Flow [Gpm] 48.25
air velocity [m/s] 2.67
Med. velocity [m/s] 1.36
Air in [gF] 84.01 Humidity [gF] 66.1
Med. in [gF] 41.88
Air out [gF] 57.79 Humidity [gF] 55.10
Med. out [gF] 51.78
total capacity [RT] 20.00
Med. pres. drop [inWG] 110.88
Sens. capacity 16.34
SHR 0.82
Air press. drop (wet) [inWG] 0.562
Air press. drop (dry) [inWG] 0.506

No. of Rows 4 Materials:

Fins AL
Fin space [mm] 2.1
RRows CU
Connection in NPT 2
Header CU
Connection out NPT 2
Frames GI
CW-1/2"-2.1 4R - RH
Water content (KG) 27.1
1 set Coating for End Plates

Drain pan Quality galvanized painted Drain connection 1 1/4

Drip eliminator

1 Pcs Measuring Opening


1 Pcs Drain second wall (for doubl wall drain)

4 Electric heater 700.0 mm 0.201 inW

HTRD-TW11-27-02-Q-C-WX Heat capacity [KW] 27.00


Entering [gF] 41.00 Voltage [V] 3x400
Leaving [gF] 53.24 Steps 2

Air volume [cfm] 7,000 Kw: Equally Divided

16-Jan-23 12:14
Offer AJD-26234-R1* Page 3/7
Position A-AHUGF-2 From date 16-Jan-23

Unit size TW11 AirCalc++ Vers. 3.8.33

5 Centrifugal fan / belt driven Supply 1,090.0 mm 0.794 inW

Backward Inclined Fan Error Motor


Air volume [cfm] 7,000 Protection IP55
External press [inWG] 1.999
Dyn. pres. [inWG] 0.397 Power [kW] 7.500
Tot. pres. [inWG] 4.789 Speed [1/m] 1,750
Speed [1/m] 2,284
Fan shaft power [kW] 5.108 Supply 3x400 / 60
efficiency % 77.16
Total Real Power Input [kW] 7.1

Fan pulley SPB178V Bush 2012-35 Axle distance ca. [mm] (338)
Motor pulley SPB212 Bush 2517-38
Belt 2x 1250
No. of turns 1.5 System effect pressure drop included
Pulleys & Belts selected with service factor 150%

Note: Fan discharge opening cutout location may vary by +-50 mm

1 Pcs Fan with motor on side


1 Pcs Fan with motor on side
1 Pcs Fan with motor on side

16-Jan-23 12:14
Offer AJD-26234-R1* Page 4/7
Position A-AHUGF-2 From date 16-Jan-23

Unit size TW11 AirCalc++ Vers. 3.8.33

Lamp LAMP -220V - 100W Equivalent

switch SWITCH (Mounted Externally) Nominal data 220 V

1 Pcs Lighting wired incl. switch


1 Pcs Measuring Opening

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 84.9 80.9 84.9 85.9 81.9 81.9 73.9 68.9 88.0
Outlet (db) 92.9 89.9 87.9 86.9 85.9 83.9 76.9 68.9 94.9
Casing (db) 79.5 76.7 70.4 71.0 56.4 55.4 43.4 36.4 69.9
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 70.9 66.9 70.9 71.9 67.9 67.9 59.9 54.9 74.0
Outlet (db) 78.9 75.9 73.9 72.9 71.9 69.9 62.9 54.9 80.9
Casing (db) 65.5 62.7 56.4 57.0 42.4 41.4 29.4 22.4 55.9

Unit definition General data

Unit size TW11P5BD Casing:


Type Exhaust air Thickness P5
Panel inside GI Thick [mm] 1.00
Airflow [cfm] 7,000 Length [mm] 1,640.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [inWG] 1.999 Width [mm] 1,385.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [inWG] 2.830 Height [mm] 1,385.0
Profiles AL

16-Jan-23 12:14
Offer AJD-26234-R1* Page 5/7
Position A-AHUGF-2 From date 16-Jan-23

Unit size TW11 AirCalc++ Vers. 3.8.33

1 Centrifugal fan / belt driven Return 1,090.0 mm 0.794 inW

Backward Inclined Fan Error Motor


Air volume [cfm] 7,000 Protection IP55
External press [inWG] 1.999
Dyn. pres. [inWG] 0.397 Power [kW] 4.000
Tot. pres. [inWG] 2.830 Speed [1/m] 1,745
Speed [1/m] 1,972
Fan shaft power [kW] 3.375 Supply 3x400 / 60
efficiency % 69.01
Total Real Power Input [kW] 4.8

Fan pulley SPB187V Bush 2012-35 Axle distance ca. [mm] (348)
Motor pulley SPB190 Bush 2012-28
Belt 1x 1250
No. of turns 2 System effect pressure drop included
Pulleys & Belts selected with service factor 150%

Note: Fan discharge opening cutout location may vary by +-50 mm

1 Pcs Fan with motor on side


1 Pcs Fan with motor on side
Lamp LAMP -220V - 100W Equivalent

16-Jan-23 12:14
Offer AJD-26234-R1* Page 6/7
Position A-AHUGF-2 From date 16-Jan-23

Unit size TW11 AirCalc++ Vers. 3.8.33

switch SWITCH (Mounted Externally) Nominal data 220 V

1 Pcs Lighting wired incl. switch


1 Pcs Measuring Opening

2 Double mixing section 550.0 mm 0.036 inW

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 2,100
Total Qta. Levers 1 air velocity [m/s] 2.75
Each Torque [Nm] 2.32

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 83.8 79.8 82.8 87.8 81.8 81.8 76.8 70.8 88.7
Outlet (db) 91.8 86.8 83.8 85.8 82.8 80.8 75.8 66.8 92.8
Casing (db) 78.4 73.6 66.3 69.9 53.3 52.3 42.3 34.3 68.1
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 69.8 65.8 68.8 73.8 67.8 67.8 62.8 56.8 74.7
Outlet (db) 77.8 72.8 69.8 71.8 68.8 66.8 61.8 52.8 78.8
Casing (db) 64.4 59.6 52.3 55.9 39.3 38.3 28.3 20.3 54.1

Baseframe H80-4 Material GI isolated No


Height [mm] 80.0 Welded No

1 set Roof top-weather proof


1 Pcs UL name plate

SFP (int) 0 Specific Fan Power (Internal) MCA : 64.315 MOCP : 80 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no. Width [mm] Height [mm] Length [mm] Weight [kg]

16-Jan-23 12:14
Offer AJD-26234-R1* Page 7/7
Position A-AHUGF-2 From date 16-Jan-23

Unit size TW11 AirCalc++ Vers. 3.8.33

1 1,385.0 1,385.0 2,230.0 515.00


2 1,385.0 1,385.0 3,130.0 907.00

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C


P1 CML(1) 104.99 20 9.57 65.43 22.42 77.00 50 9.88 50.31 17.87
17.87 MIX 84.02 39 9.79 54.07 19.08 19.0819.08 19.08 19.08 19.08
P2 CML(2) 104.99 20 9.57 65.43 22.42 77.00 50 9.88 50.31 17.87
17.87 MIX 84.02 39 9.79 54.07 19.08 19.0819.08 19.08 19.08 19.08
P3 CK1 84.00 39 9.78 54.04 19.07 57.79 85 8.64 36.25 12.86
P4 CEE 41.00 0 0.00 5.03 -2.61 53.24 0 0.00 11.87 1.38

16-Jan-23 12:14
GCC GULF
GCC GULF
DIMENSIONS
MODELS: DWX02 - DWX20

A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H

0.5"
2
E
B

6
1

1.0"
7
END VIEW TOP VIEW END VIEW

F 3.5"

3
G
C

7.0"

FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

DIMENSIONS NO. OF NO. OF


MODEL MOTORS BLOWERS
A B C D E F G H I
DWX02 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX03 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX04 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX06 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX08 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX10 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX12 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX14 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX16 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX18 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX20 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
2.b AHU + FCU
Building-E
E-BUILDING

Design Data

Supply Fan Return Fan ESP for each Electric Heater


Item TAG# TYPE Total Capacity (Tons) GPM Fresh Air (CFM) FLOOR Power Supply Qty
AirFlow (CFM) AirFlow (CFM) Fan (Pa) (kW)

1 AHU-04 Chilled water AHU 18.6 44.64 11,386 1500 11386 500 15 R.F 380V-3Ph-60Hz 2

2 AHU-05 Chilled water AHU 15.3 36.72 9,000 1000 9000 500 15 R.F 380V-3Ph-60Hz 2

3 FCU-01-1 TO 04 Chilled water FCU 1 2.4 420 - - 50 1 G.F 230V-1Ph-60Hz 4

4 FCU-02-1 TO 10 Chilled water FCU 1.5 3.6 650 - - 50 2 M.F 230V-1Ph-60Hz 10

5 FCU-03-1 TO 02 Chilled water FCU 2 4.8 840 - - 50 2 M.F 230V-1Ph-60Hz 2

6 FCU-05-1 TO 06 Chilled water FCU 3 7.2 1,350 - - 50 3 G.F 230V-1Ph-60Hz 6

Zamil Selection Data

Total Capacity Sensible Capacity Supply Fan Return Fan ESP for each Electric Heater
Item TAG# TYPE Model GPM Fresh Air (CFM) FLOOR Power Supply Qty
(Tons) (Tons) AirFlow (CFM) AirFlow (CFM) Fan (Pa) (kW)

1 AHU-04 Chilled water TW17P5BD 25.11 20.98 60.6 11,386 1500 11386 500 18 / 1 Stages R.F 380V-3Ph-60Hz 2

2 AHU-05 Chilled water TW14P5BD 19.51 16.58 47.0 9,000 1000 9000 500 18 / 1 Stages R.F 380V-3Ph-60Hz 2

3 FCU-01-1 TO 04 Chilled water DWX06 1.00 0.74 2.4 421 - - 50 1 G.F 230V-1Ph-60Hz 4

4 FCU-02-1 TO 10 Chilled water DWX10 1.71 1.24 4.1 727 - - 50 2 M.F 230V-1Ph-60Hz 10

5 FCU-03-1 TO 02 Chilled water DWX12 2.01 1.45 4.9 886 - - 50 2 M.F 230V-1Ph-60Hz 2

6 FCU-05-1 TO 06 Chilled water DWX18 4.08 2.92 9.9 1,466 - - 50 3 G.F 230V-1Ph-60Hz 6
239 311 311

120

302
569.5

638
1,385
1,465

311
1 2 1 2 3 4 5

504.5

445
80
1,140 550 590 590 750 700 1,190
2,280 3,230
L1 L2
5,510
112.5
82.5

678.5
1,995
1,770
1,830

638
678.5
112.5
82.5

SURFACE CASING TOLERANCE


Supply air TW17P5BD P5 Exhaust air TW17P5BD P5 Type of unit External unit
Panel outside GI-P AL-HADETHA WN
Project:
Panel inside GI AJD-26234-R1* 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 16-Jan-23 user CW
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: AHU-04
VER: 3.8.33
DRAWING NO. Office
Classic
E-BUILDING Air Conditioners
TEL. EMail
+966 3 847 3333 [email protected]

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer AJD-26234-R1*
Phone +966 3 847 3333 From date 16-Jan-23
Fax Position AHU-04
LV CW
web www.zamilac.com

Office / Agent user Print data 16-Jan-23

POINT LOAD DISTRIBUTION

SECTION 1 SECTION 2
o o o o o o

o o o o o o

93

Delivery sections No. Points Each load (kg)

1 Delivery Section 6 195


2 Delivery Section 6 313.5

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/7
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer AJD-26234-R1*
Phone +966 3 847 3333 From date 16-Jan-23
Fax Position AHU-04
LV CW
web www.zamilac.com

Office / Agent user Print data 16-Jan-23


Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class E 2016 Model box as declared on the Eurovent Certified Performance website
CAL(R) L3/L3.

Serie TW Sealevel [m] 0


Execution Standard Design Outdoor Temperature 46 °C
Type of unit External unit Unit design NRVU - BVU

Unit definition General data

Unit size TW17P5BD Casing:


Type Supply air Thickness P5
Panel inside GI Thick [mm] 1.00
Airflow [cfm] 11,386 Length [mm] 3,820.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [inWG] 1.999 Width [mm] 1,995.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [inWG] 5.006 Height [mm] 1,385.0
Profiles AL

1 Double mixing section 590.0 mm 0.237 inW

Recircle air [cfm] 9,886 Humidity 64.05 Mixed air Temp. 80.60 Humidity [%] 65.18
Fresh air [cfm] 1,500 Humidity 72.00 total air 11,386 Mixing Ratio [%] 85

Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 3,416
Total Qta. Levers 1 air velocity [m/s] 2.93
Each Torque [Nm] 3.03

Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 9,109
Total Qta. Levers 1 air velocity [m/s] 7.81
Each Torque [Nm] 3.03

1 Pcs Measuring Opening

16-Jan-23 12:15
Offer AJD-26234-R1* Page 2/7
Position AHU-04 From date 16-Jan-23

Unit size TW17 AirCalc++ Vers. 3.8.33

2 Bag Filter section with prefilter 590.0 mm 1.160 inW

Type 2" Washable MERV8


Cells pcs x size [mm] 6 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
Clean dP [inWG] 0.257
Dirty dP [inWG] 0.658
Airflow [cfm] 11,386 Cross section velocity [m/s] AEC [kWh] N/A
2.21

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 6 x 592.0 x 592.0
Clean dP [inWG] 0.502
Dirty dP [inWG] 0.903
Airflow [cfm] 11,386 Cross section velocity [m/s] 2.21
1 Pcs Measuring Opening

3 Cooling coil 750.0 mm 0.566 inW

Medium Water
Airflow [cfm] 11,386
Med. Flow [Gpm] 60.56
air velocity [m/s] 2.80
Med. velocity [m/s] 1.71
Air in [gF] 80.60 Humidity [gF] 65.1
Med. in [gF] 41.88
Air out [gF] 59.99 Humidity [gF] 56.63
Med. out [gF] 51.78
total capacity [RT] 25.11
Med. pres. drop [inWG] 231.80
Sens. capacity 20.98
SHR 0.84
Air press. drop (wet) [inWG] 0.506
Air press. drop (dry) [inWG] 0.455

No. of Rows 4 Materials:

Fins AL
Fin space [mm] 2.5
RRows CU
Connection in NPT 2
Header CU
Connection out NPT 2
Frames GI
CW-1/2"-2.5 4R - RH
Water content (KG) 37.5
1 set Coating for End Plates

Drain pan Quality galvanized painted Drain connection 1 1/4

Drip eliminator

1 Pcs Measuring Opening


1 Pcs Drain second wall (for doubl wall drain)

4 Electric heater 700.0 mm 0.201 inW

HTRD-TW17-18-01-Q-C-WX Heat capacity [KW] 18.00


Entering [gF] 41.00 Voltage [V] 3x400
Leaving [gF] 46.03 Steps 1

Air volume [cfm] 11,386 Kw: Equally Divided

16-Jan-23 12:15
Offer AJD-26234-R1* Page 3/7
Position AHU-04 From date 16-Jan-23

Unit size TW17 AirCalc++ Vers. 3.8.33

5 Centrifugal fan / belt driven Supply 1,190.0 mm 0.844 inW

Backward Inclined Fan Error Motor


Air volume [cfm] 11,386 Protection IP55
External press [inWG] 1.999
Dyn. pres. [inWG] 0.422 Power [kW] 11.000
Tot. pres. [inWG] 5.006 Speed [1/m] 1,765
Speed [1/m] 1,846
Fan shaft power [kW] 8.324 Supply 3x400 / 60
efficiency % 80.48
Total Real Power Input [kW] 11.0

Fan pulley SPB180 Bush 2517-40 Axle distance ca. [mm] (353)
Motor pulley SPB190 Bush 2517-42
Belt 2x 1250
System effect pressure drop included
Pulleys & Belts selected with service factor 150%

Note: Fan discharge opening cutout location may vary by +-50 mm

1 Pcs Fan with motor on side


1 Pcs Fan with motor on side
1 Pcs Fan with motor on side

16-Jan-23 12:15
Offer AJD-26234-R1* Page 4/7
Position AHU-04 From date 16-Jan-23

Unit size TW17 AirCalc++ Vers. 3.8.33

Lamp LAMP -220V - 100W Equivalent

switch SWITCH (Mounted Externally) Nominal data 220 V

1 Pcs Lighting wired incl. switch


1 Pcs Measuring Opening

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 86.3 83.3 93.3 87.3 82.3 79.3 72.3 66.3 89.4
Outlet (db) 94.3 91.3 93.3 88.3 88.3 83.3 77.3 69.3 97.3
Casing (db) 80.9 78.3 77.4 72.4 58.1 53.8 42.8 34.8 72.8
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 72.3 69.3 79.3 73.3 68.3 65.3 58.3 52.3 75.4
Outlet (db) 80.3 77.3 79.3 74.3 74.3 69.3 63.3 55.3 83.3
Casing (db) 66.9 64.3 63.4 58.4 44.1 39.8 28.8 20.8 58.8

Unit definition General data

Unit size TW17P5BD Casing:


Type Exhaust air Thickness P5
Panel inside GI Thick [mm] 1.00
Airflow [cfm] 11,386 Length [mm] 1,690.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [inWG] 1.999 Width [mm] 1,995.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [inWG] 2.883 Height [mm] 1,385.0
Profiles AL

16-Jan-23 12:15
Offer AJD-26234-R1* Page 5/7
Position AHU-04 From date 16-Jan-23

Unit size TW17 AirCalc++ Vers. 3.8.33

1 Centrifugal fan / belt driven Return 1,140.0 mm 0.844 inW

Backward Inclined Fan Error Motor


Air volume [cfm] 11,386 Protection IP55
External press [inWG] 1.999
Dyn. pres. [inWG] 0.422 Power [kW] 7.500
Tot. pres. [inWG] 2.883 Speed [1/m] 1,750
Speed [1/m] 1,576
Fan shaft power [kW] 5.356 Supply 3x400 / 60
efficiency % 71.99
Total Real Power Input [kW] 7.4

Fan pulley SPA170 Bush 2012-40 Axle distance ca. [mm] 315
Motor pulley SPA164V Bush 1615-38
Belt 2x 1107
No. of turns 1 System effect pressure drop included
Pulleys & Belts selected with service factor 150%

Note: Fan discharge opening cutout location may vary by +-50 mm

1 Pcs Fan with motor on side


1 Pcs Fan with motor on side
Lamp LAMP -220V - 100W Equivalent

16-Jan-23 12:15
Offer AJD-26234-R1* Page 6/7
Position AHU-04 From date 16-Jan-23

Unit size TW17 AirCalc++ Vers. 3.8.33

switch SWITCH (Mounted Externally) Nominal data 220 V

1 Pcs Lighting wired incl. switch


1 Pcs Measuring Opening

2 Double mixing section 550.0 mm 0.040 inW

Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 3,416
Total Qta. Levers 1 air velocity [m/s] 2.93
Each Torque [Nm] 3.03

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 85.3 81.3 93.3 88.3 83.3 81.3 76.3 69.3 90.3
Outlet (db) 93.3 87.3 91.3 86.3 86.3 82.3 77.3 68.3 95.3
Casing (db) 79.9 74.3 75.4 70.4 56.1 52.8 42.8 33.8 70.6
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 71.3 67.3 79.3 74.3 69.3 67.3 62.3 55.3 76.3
Outlet (db) 79.3 73.3 77.3 72.3 72.3 68.3 63.3 54.3 81.3
Casing (db) 65.9 60.3 61.4 56.4 42.1 38.8 28.8 19.8 56.6

Baseframe H80-4 Material GI isolated No


Height [mm] 80.0 Welded No

1 set Roof top-weather proof


1 Pcs UL name plate

SFP (int) 0 Specific Fan Power (Internal) MCA : 65.695 MOCP : 90 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no. Width [mm] Height [mm] Length [mm] Weight [kg]

16-Jan-23 12:15
Offer AJD-26234-R1* Page 7/7
Position AHU-04 From date 16-Jan-23

Unit size TW17 AirCalc++ Vers. 3.8.33

1 1,995.0 1,385.0 2,280.0 782.00


2 1,995.0 1,385.0 3,230.0 1,253.00

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C


P1 CML(1) 104.99 20 9.57 65.43 22.42 77.00 50 9.88 50.31 17.87
17.87 MIX 80.60 44 9.85 52.29 18.51 18.5118.51 18.51 18.51 18.51
P2 CML(2) 104.99 20 9.57 65.43 22.42 77.00 50 9.88 50.31 17.87
17.87 MIX 80.60 44 9.85 52.29 18.51 18.5118.51 18.51 18.51 18.51
P3 CK1 80.58 44 9.85 52.26 18.51 59.99 82 9.02 38.46 13.71
P4 CEE 41.00 0 0.00 5.03 -2.61 46.04 0 0.00 7.85 -0.94

16-Jan-23 12:15
239 311 311

120

302
569.5

638
1,385
1,465

311
1 2 1 2 3 4 5

504.5

445
80

1,140 550 590 590 750 700 1,140


2,280 3,180
L1 L2
5,460
82.5
265

426
638
1,690
1,160
1,525

626
265
82.5

SURFACE CASING TOLERANCE


Supply air TW14P5BD P5 Exhaust air TW14P5BD P5 Type of unit External unit
Panel outside GI-P AL-HADETHA WN
Project:
Panel inside GI AJD-26234-R1* 95001
Profiles AL
Date Name
Location:
ALL RIGHTS RESERVED WITH RESPECT DRAWN 16-Jan-23 user CW
TO THE INFORMATION AND DESIGN
DISCLOSED HEREIN. CHK. Sheet
no. OF
STD. Tag-no: AHU-05
VER: 3.8.33
DRAWING NO. Office
Classic
E-BUILDING Air Conditioners
TEL. EMail
+966 3 847 3333 [email protected]

ISSUE. CHANGE DATE/NAME REP.FOR REP.BY


Classic Page 1/1
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer AJD-26234-R1*
Phone +966 3 847 3333 From date 16-Jan-23
Fax Position AHU-05
LV CW
web www.zamilac.com

Office / Agent user Print data 16-Jan-23

POINT LOAD DISTRIBUTION

SECTION 1 SECTION 2
o o o o o o

o o o o o o

93

Delivery sections No. Points Each load (kg)

1 Delivery Section 6 183


2 Delivery Section 6 277.5

Points to be distributed evenly at intervals of 2 meters.


Classic Page 1/7
P.O.Box 14440 AirCalc++ Vers. 3.8.33
Dammam Offer AJD-26234-R1*
Phone +966 3 847 3333 From date 16-Jan-23
Fax Position AHU-05
LV CW
web www.zamilac.com

Office / Agent user Print data 16-Jan-23


Zamil Air Conditioners is participating in the Eurovent Certification Programme for Air Handling Units. The range TW & TW (H) is
certified under the number 07.04.233 and presented in the Directory of Certified Air Handling Units. www.eurovent-certification.com
EUROVENT – AHU Energy Efficiency Class E 2016 Model box as declared on the Eurovent Certified Performance website
CAL(R) L3/L3.

Serie TW Sealevel [m] 0


Execution Standard Design Outdoor Temperature 46 °C
Type of unit External unit Unit design NRVU - BVU

Unit definition General data

Unit size TW14P5BD Casing:


Type Supply air Thickness P5
Panel inside GI Thick [mm] 1.00
Airflow [cfm] 9,000 Length [mm] 3,770.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [inWG] 1.999 Width [mm] 1,690.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [inWG] 4.701 Height [mm] 1,385.0
Profiles AL

1 Double mixing section 590.0 mm 0.333 inW

Recircle air [cfm] 8,000 Humidity 64.05 Mixed air Temp. 80.05 Humidity [%] 65.01
Fresh air [cfm] 1,000 Humidity 72.00 total air 9,000 Mixing Ratio [%] 83

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 2,700
Total Qta. Levers 1 air velocity [m/s] 3.53
Each Torque [Nm] 2.32

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 7,200
Total Qta. Levers 1 air velocity [m/s] 9.42
Each Torque [Nm] 2.32

1 Pcs Measuring Opening

16-Jan-23 12:18
Offer AJD-26234-R1* Page 2/7
Position AHU-05 From date 16-Jan-23

Unit size TW14 AirCalc++ Vers. 3.8.33

2 Bag Filter section with prefilter 590.0 mm 1.124 inW

Type 2" Washable MERV8


Cells pcs x size [mm] 4 x 592.0 x 592.0
Class F5 ISO ePM Coarse 55%
2 x 592.0 x 287.0
Clean dP [inWG] 0.245
Dirty dP [inWG] 0.646
Airflow [cfm] 9,000 Cross section velocity [m/s] AEC [kWh] N/A
2.08

Type Bag Filter 15"


Class F9 ISO ePM1 85% Cells pcs x size [mm] 4 x 592.0 x 592.0
Clean dP [inWG] 0.478 2 x 592.0 x 287.0
Dirty dP [inWG] 0.879
Airflow [cfm] 9,000 Cross section velocity [m/s] 2.08
1 Pcs Measuring Opening

3 Cooling coil 750.0 mm 0.522 inW

Medium Water
Airflow [cfm] 9,000
Med. Flow [Gpm] 47.08
air velocity [m/s] 2.68
Med. velocity [m/s] 1.33
Air in [gF] 81.60 Humidity [gF] 65.4
Med. in [gF] 41.88
Air out [gF] 60.99 Humidity [gF] 57.19
Med. out [gF] 51.78
total capacity [RT] 19.51
Med. pres. drop [inWG] 126.90
Sens. capacity 16.58
SHR 0.85
Air press. drop (wet) [inWG] 0.466
Air press. drop (dry) [inWG] 0.419

No. of Rows 4 Materials:

Fins AL
Fin space [mm] 2.5
RRows CU
Connection in NPT 2
Header CU
Connection out NPT 2
Frames GI
CW-1/2"-2.5 4R - RH
Water content (KG) 32.5
1 set Coating for End Plates

Drain pan Quality galvanized painted Drain connection 1 1/4

Drip eliminator

1 Pcs Measuring Opening


1 Pcs Drain second wall (for doubl wall drain)

4 Electric heater 700.0 mm 0.201 inW

HTRD-TW14-18-01-Q-C-WX Heat capacity [KW] 18.00


Entering [gF] 41.00 Voltage [V] 3x400
Leaving [gF] 47.30 Steps 1

Air volume [cfm] 9,000 Kw: Equally Divided

16-Jan-23 12:18
Offer AJD-26234-R1* Page 3/7
Position AHU-05 From date 16-Jan-23

Unit size TW14 AirCalc++ Vers. 3.8.33

5 Centrifugal fan / belt driven Supply 1,140.0 mm 0.522 inW

Backward Inclined Fan Error Motor


Air volume [cfm] 9,000 Protection IP55
External press [inWG] 1.999
Dyn. pres. [inWG] 0.261 Power [kW] 7.500
Tot. pres. [inWG] 4.701 Speed [1/m] 1,750
Speed [1/m] 1,691
Fan shaft power [kW] 6.050 Supply 3x400 / 60
efficiency % 82.23
Total Real Power Input [kW] 8.2

Fan pulley SPA170 Bush 2012-40 Axle distance ca. [mm] 314
Motor pulley SPA160 Bush 2012-38
Belt 2x 1107
System effect pressure drop included
Pulleys & Belts selected with service factor 150%

Note: Fan discharge opening cutout location may vary by +-50 mm

1 Pcs Fan with motor on side


Lamp LAMP -220V - 100W Equivalent

switch SWITCH (Mounted Externally) Nominal data 220 V

16-Jan-23 12:18
Offer AJD-26234-R1* Page 4/7
Position AHU-05 From date 16-Jan-23

Unit size TW14 AirCalc++ Vers. 3.8.33

1 Pcs Lighting wired incl. switch


1 Pcs Measuring Opening

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 83.2 80.2 90.2 84.2 79.2 76.2 69.2 63.2 86.3
Outlet (db) 91.2 88.2 90.2 85.2 85.2 80.2 74.2 66.2 94.2
Casing (db) 77.8 75.2 74.3 69.3 55.0 50.7 39.7 31.7 69.7
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 69.2 66.2 76.2 70.2 65.2 62.2 55.2 49.2 72.3
Outlet (db) 77.2 74.2 76.2 71.2 71.2 66.2 60.2 52.2 80.2
Casing (db) 63.8 61.2 60.3 55.3 41.0 36.7 25.7 17.7 55.7

Unit definition General data

Unit size TW14P5BD Casing:


Type Exhaust air Thickness P5
Panel inside GI Thick [mm] 1.00
Airflow [cfm] 9,000 Length [mm] 1,690.0
Panel outside GI-P Thick [mm] 0.7
Ext. pressure [inWG] 1.999 Width [mm] 1,690.0
Panel inside bottom GI Thick [mm] 1.25
Tot. pressure [inWG] 2.577 Height [mm] 1,385.0
Profiles AL

16-Jan-23 12:18
Offer AJD-26234-R1* Page 5/7
Position AHU-05 From date 16-Jan-23

Unit size TW14 AirCalc++ Vers. 3.8.33

1 Centrifugal fan / belt driven Return 1,140.0 mm 0.522 inW

Backward Inclined Fan Error Motor


Air volume [cfm] 9,000 Protection IP55
External press [inWG] 1.999
Dyn. pres. [inWG] 0.261 Power [kW] 5.500
Tot. pres. [inWG] 2.577 Speed [1/m] 1,760
Speed [1/m] 1,373
Fan shaft power [kW] 3.516 Supply 3x400 / 60
efficiency % 77.61
Total Real Power Input [kW] 5.2

Fan pulley SPB236 Bush 2012-40 Axle distance ca. [mm] 348
Motor pulley SPB180 Bush 1610-38
Belt 1x 1320
System effect pressure drop included
Pulleys & Belts selected with service factor 150%

Note: Fan discharge opening cutout location may vary by +-50 mm

1 Pcs Fan with motor on side


1 Pcs Fan with motor on side
Lamp LAMP -220V - 100W Equivalent

16-Jan-23 12:18
Offer AJD-26234-R1* Page 6/7
Position AHU-05 From date 16-Jan-23

Unit size TW14 AirCalc++ Vers. 3.8.33

switch SWITCH (Mounted Externally) Nominal data 220 V

1 Pcs Lighting wired incl. switch


1 Pcs Measuring Opening

2 Double mixing section 550.0 mm 0.056 inW

Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 2,700
Total Qta. Levers 1 air velocity [m/s] 3.53
Each Torque [Nm] 2.32

noise calculation measureing point at 2 m Distance


sound power
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 80.7 76.7 88.7 83.7 78.7 76.7 71.7 64.7 85.7
Outlet (db) 88.7 82.7 86.7 81.7 81.7 77.7 72.7 63.7 90.7
Casing (db) 75.3 69.7 70.8 65.8 51.5 48.2 38.2 29.2 66.0
sound pressure level
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum (dbA)
Inlet (db) 66.7 62.7 74.7 69.7 64.7 62.7 57.7 50.7 71.7
Outlet (db) 74.7 68.7 72.7 67.7 67.7 63.7 58.7 49.7 76.7
Casing (db) 61.3 55.7 56.8 51.8 37.5 34.2 24.2 15.2 52.0

Baseframe H80-4 Material GI isolated No


Height [mm] 80.0 Welded No

1 set Roof top-weather proof


1 Pcs UL name plate

SFP (int) 0 Specific Fan Power (Internal) MCA : 53.595 MOCP : 70 of complete unit.

Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.

* Control box location will vary based on design.


* Horizontal blower orientation may change as per design.
* Fan location and Damper locations dimension may vary as per design.
* Internal section length may change during design but total unit length dimension remain.
* 400V Power Supply (04 wires 3P+1N)

Delivery sections no. Width [mm] Height [mm] Length [mm] Weight [kg]

16-Jan-23 12:18
Offer AJD-26234-R1* Page 7/7
Position AHU-05 From date 16-Jan-23

Unit size TW14 AirCalc++ Vers. 3.8.33

1 1,690.0 1,385.0 2,280.0 735.00


2 1,690.0 1,385.0 3,180.0 1,111.00

t °C r % x g/kg h kJ/kg tw °C t °C r % x g/kg h kJ/kg tw °C


P1 CML(1) 104.99 20 9.57 65.43 22.42 77.00 50 9.88 50.31 17.87
17.87 MIX 80.06 45 9.86 51.99 18.42 18.4218.42 18.42 18.42 18.42
P2 CML(2) 104.99 20 9.57 65.43 22.42 77.00 50 9.88 50.31 17.87
17.87 MIX 81.68 43 9.81 52.80 18.68 18.6818.68 18.68 18.68 18.68
P3 CK1 81.59 43 9.83 52.79 18.68 61.00 80 9.12 39.29 14.02
P4 CEE 41.00 0 0.00 5.03 -2.61 47.30 0 0.00 8.55 -0.53

16-Jan-23 12:18
GCC GULF
GCC GULF
GCC GULF
GCC GULF
DIMENSIONS
MODELS: DWX02 - DWX20

A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H

0.5"
2
E
B

6
1

1.0"
7
END VIEW TOP VIEW END VIEW

F 3.5"

3
G
C

7.0"

FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

DIMENSIONS NO. OF NO. OF


MODEL MOTORS BLOWERS
A B C D E F G H I
DWX02 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX03 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX04 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX06 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX08 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX10 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX12 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX14 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX16 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX18 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX20 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
2.b FCU & SPLIT
Building-F
F-BUILDING

Design Data

Supply AirFlow
Item TAG# TYPE Total Capacity (Tons) GPM ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty
(CFM)
1 FCU-01 TO 14 Chilled water FCU 2.5 6 1,050 50 1 G.F 230V-1Ph-60Hz 14

2 FCU-04 TO 02 Chilled water FCU 2 4.8 840 50 2 G.F 230V-1Ph-60Hz 2

3 FCU-02 Chilled water FCU 1.5 3.6 650 50 2 G.F 230V-1Ph-60Hz 1

4 FCU-05 Chilled water FCU 1 2.4 420 50 3 G.F 230V-1Ph-60Hz 2

5 SPLIT UNIT 01 DX-HighWall 1.5 - 700 - Heat-Pump G.F 230V-1Ph-60Hz 1

Zamil Selection Data

Total Capacity Sensible Supply AirFlow


Item TAG# TYPE Model GPM ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty
(Tons) Capacity (Tons) (CFM)
1 FCU-01 TO 14 Chilled water DWX14 2.75 1.93 6.7 1,064 50 3 G.F 230V-1Ph-60Hz 14

2 FCU-04 TO 02 Chilled water DWX12 2.01 1.45 4.9 886 50 2 M.F 230V-1Ph-60Hz 2

3 FCU-02 Chilled water DWX10 1.71 1.24 4.1 727 50 2 M.F 230V-1Ph-60Hz 1

4 FCU-05 Chilled water DWX06 1.00 0.74 2.4 421 50 1 G.F 230V-1Ph-60Hz 2

5 SPLIT UNIT 01 DX-HighWall MAZ18CH/MRZ18CD 1.50 - - 700 - Heat-Pump G.F 230V-1Ph-60Hz 1


Chilled Water Fan Coil Unit
fcZAC

Customer: GCC GULF Done By: AB


General Info

Project: AL-HADETHA Location: QURAYAT

Ref/Tag: FCU-01 TO 14 Quantity: 14

Revision: 0 Date: 2023-01-16 13:09

External
Air Flow Static Pressure Altitude
Input Conditions

1,050.0 50.00 300.00 Total Entering Entering Water Entering Delta

Cooling Data
CFM Pa ft Capacity Dry Bulb Wet Bulb Flowrate Water Temp

2.500 78.00 65.00 6.061 41.90 9.90


Voltage Phases Frequency TR °F °F GPM °F °F
Volts Phase Hertz
230V 1 60Hz

Selected Unit Model


DWX14

Cooling Performance Data


Total Cooling Capacity 2.748 TR
Total Sensible Capacity 1.932 TR
SHR 0.7
Air Flowrate 1,063.4 CFM
Fan Speed MED
Entering Water Temp 41.90 °F
Leaving Water Temp 51.80 °F
Water Flowrate 6.648 GPM
Water Pressure Drop 1.63 ft H2O

Psychrometric Data
Entering (On Coil) Leaving (Off Coil)
Output Performance

Dry Bulb 78.00 °F Dry Bulb 57.66 °F


Wet Bulb 65.00 °F Wet Bulb 53.90 °F

Cooling Coil Data


Coil Tube Diameter 3/8 Inch
Rows 4
Fins Per Inch 12

Electrical Data General Data


Blower Motor 353 W Weight 55 kg
Blower Motor FLA 2.35 A Pipe Connection In/Out - Cooling 5 / 8 - 5 / 8 in
MCA 19.24 A Unit Length See Drawings
MOCP 25 A Unit Width See Drawings
Electric Heater 3 kW Unit Height See Drawings
Heater FLA 13.04 A

Sound Power Data

Frequency (Hz) 125 250 500 1000 2000 4000 8000

dB 72 67 66 69 64 63 62
Products Certifications

of
GCC GULF

FCU-04 TO 02 2
GCC GULF

FCU-02 1
GCC GULF

FCU-05 2
DIMENSIONS
MODELS: DWX02 - DWX20

A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H

0.5"
2
E
B

6
1

1.0"
7
END VIEW TOP VIEW END VIEW

F 3.5"

3
G
C

7.0"

FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

DIMENSIONS NO. OF NO. OF


MODEL MOTORS BLOWERS
A B C D E F G H I
DWX02 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX03 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX04 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX06 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX08 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX10 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX12 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX14 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX16 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX18 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX20 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b FCU
Building-G1
(G1) -STAFF BUILDING

Design Data

Item TAG# TYPE Total Capacity (Tons) GPM Supply AirFlow (CFM) ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty

1 FCU-1 Chilled water FCU 1 2.4 420 50 1 G.F 230V-1Ph-60Hz 2

2 FCU-2 Chilled water FCU 2 4.8 840 50 2 G.F 230V-1Ph-60Hz 1

3 FCU-5 Chilled water FCU 4 7.2 1,350 50 2 G.F 230V-1Ph-60Hz 4

Zamil Selection Data

Total Capacity Sensible


Item TAG# TYPE Model GPM Supply AirFlow (CFM) ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty
(Tons) Capacity (Tons)

1 FCU-1 Chilled water DWX06 1.00 0.74 2.4 421 50 1 G.F 230V-1Ph-60Hz 2

2 FCU-2 Chilled water DWX12 2.01 1.45 4.9 886 50 2 M.F 230V-1Ph-60Hz 1

3 FCU-5 Chilled water DWX18 4.08 2.92 9.9 1,466 50 3 G.F 230V-1Ph-60Hz 4
GCC GULF

FCU-01 2
GCC GULF

FCU-02 1
GCC GULF

FCU-5 4
DIMENSIONS
MODELS: DWX02 - DWX20

A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H

0.5"
2
E
B

6
1

1.0"
7
END VIEW TOP VIEW END VIEW

F 3.5"

3
G
C

7.0"

FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

DIMENSIONS NO. OF NO. OF


MODEL MOTORS BLOWERS
A B C D E F G H I
DWX02 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX03 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX04 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX06 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX08 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX10 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX12 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX14 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX16 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX18 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX20 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
2.b FCU
Building-K1
(K1) -BUS WORKSHOP - OUTBOUND

Design Data

Item TAG# TYPE Total Capacity (Tons) GPM Supply AirFlow (CFM) ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty

1 FCU-03 Chilled water FCU 1.5 3.6 650 50 1 G.F 230V-1Ph-60Hz 1

2 FCU-04 Chilled water FCU 2 4.8 1,350 50 2 G.F 230V-1Ph-60Hz 1

3 FCU-02 Chilled water FCU 3 7.2 1,350 50 2 G.F 230V-1Ph-60Hz 2

Zamil Selection Data

Total Capacity Sensible


Item TAG# TYPE Model GPM Supply AirFlow (CFM) ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty
(Tons) Capacity (Tons)
1 FCU-3 Chilled water DWX10 1.71 1.24 4.1 727 50 2 G.F 230V-1Ph-60Hz 1

2 FCU-4 Chilled water DWX18 4.08 2.92 9.9 1,466 50 3 G.F 230V-1Ph-60Hz 1

3 FCU-2 Chilled water DWX18 4.08 2.92 9.9 1,466 50 3 G.F 230V-1Ph-60Hz 2
GCC GULF

FCU-03 1
GCC GULF

FCU-4 1
GCC GULF

FCU-2 2
DIMENSIONS
MODELS: DWX02 - DWX20

A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H

0.5"
2
E
B

6
1

1.0"
7
END VIEW TOP VIEW END VIEW

F 3.5"

3
G
C

7.0"

FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

DIMENSIONS NO. OF NO. OF


MODEL MOTORS BLOWERS
A B C D E F G H I
DWX02 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX03 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX04 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) 1 1
DWX06 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX08 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) 1 2
DWX10 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX12 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX14 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) 1 2
DWX16 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX18 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
DWX20 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1 2
2.b Split
Building-D1
BUILDING - 1 (CONFORMITY-D1)
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 D1-SU-01-1 TO 02 DX-High Wall Split MMZ36CH/MRZ36DGH 3 950 Heat Pump G.F Building-D1 2

2 D1-SU-02-1 TO 02 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-D1 2

3 D1-SU-03-1 TO 02 DX-High Wall Split MAZ12CH/MRZ12CD 1 415 Heat Pump G.F Building-D1 2
SPECIFICATIONS
INDOOR UNIT MAZ30CCXAD MAZ30CHXAD MMZ36CCXAD MMZ36CHXAD
MODEL NUMBER
OUTDOOR UNIT KRZ30CDACIAD KRZ30CDAHIAD MRZ36CDGCIAD MRZ36CDGHIAD
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 27000 / 24000 27000 / 24000 31400 / 26800 31400 / 26800
COOLING CAPACITY ( T1 & T3 ) watts 7900 / 7020 7900 / 7020 9202 / 7854 9202 / 7854
HEATING CAPAICTY watts -- 7,500 -- 9,000
POWER INPUT ( T1 & T3 ) watts 2195 / 2824 2195 / 2824 2614 / 3135 2614 / 3135
POWER INPUT ( Heating ) watts -- 2,150 -- 2,455
EER ( T1 & T3 ) Btuh/W 12.3 / 8.50 12.3 / 8.50 12.0 / 8.55 12.0 / 8.55
COP ( Heating ) W/W -- 3.49 -- 3.65
SEER Btuh/W 10.35 10.35 10.17 10.17
ANNUAL ENERGY CONSUMPTION kWh 9,200 9,200 10,469 10,469
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 850 / 790 / 640 / 550 850 / 790 / 640 / 550 950 / 850 / 750 950 / 850 / 750
SOUND PRESSURE LEVEL (1M) dBA 52 / 48 / 45 52 / 48 / 45 50.5/47.5/44.5 51 /48 / 45
BLOWER MOTOR FLA/POWER INPUT watts 0.4 / 89 0.4 / 89 0.35 / 73 0.35 / 73
COMPRESSOR RLA/LRA A 10.6 / 56 10.6 / 56 12.0 / 79 12.0 / 79
CONDENSER FAN MOTOR FLA/LRA A 0.87 / 200 0.87 / 200 0.70 / 150 0.70 / 150
COMPRESSOR TYPE ROTARY ROTARY ROTARY ROTARY
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 14.12 0.5 / 14.12 0.6 / 16 0.6 / 16
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 25 5 / 25 5 / 25 5 / 25
REFRIGERANT TYPE R410a R410a R410a R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 25 / 30 25 / 30 21.3 / 27.3 21.3 / 27.3
NET WEIGHT, KG
OUTDOOR UNIT kg 69 / 74 72 / 77 68.4 / 73 69.8 / 74.5
INDOOR UNIT mm 1259 X 282 X 362 1259 X 282 X 362 1350 X 272 X 365 1350 X 272 X 365
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 1000 X 390 X 860 1000 X 390 X 860 946 X 410 X 810 946 X 410 X 810

CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ12CHX
MODEL NUMBER
OUTDOOR UNIT MRZ12CDGH
MODE OF OPERATION Cool only / Heal pump HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60
ENERGY CLASS ( SEER ) D
COOLING CAPACITY ( T1 & T3 ) Btuh 11800 / 10300
COOLING CAPACITY ( T1 & T3 ) watts 3458 / 3019
HEATING CAPAICTY watts 3,300
POWER INPUT ( T1 & T3 ) watts 951 / 1177
POWER INPUT ( Heating ) watts 916
EER ( T1 & T3 ) Btuh/W 12.4 / 8.75
COP ( Heating ) W/W 3.60
SEER Btuh/W 10.50
ANNUAL ENERGY CONSUMPTION kWh
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 415 / 365 / 315
SOUND PRESSURE LEVEL (1M) dBA 40.5 / 37 / 34.5
BLOWER MOTOR FLA/POWER INPUT watts 59
COMPRESSOR RLA/LRA A 4.75 / 27
CONDENSER FAN MOTOR FLA/LRA A 78
COMPRESSOR TYPE Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.3 / 6.39
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 15
REFRIGERANT TYPE R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 1/2, 5/8
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 20 / 8
INDOOR UNIT kg 11.6 / 14.9
NET WEIGHT, KG
OUTDOOR UNIT kg 33.8 / 36.5
INDOOR UNIT mm 965x215x319
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 805x330x554
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-D2
BUILDING - D2
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 D2-SU-01 DX-High Wall Split MMZ36CH/MRZ36DGH 3 950 Heat Pump G.F Building-D2 2

2 D2-SU-02 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-D2 2

3 D2-SU-03 DX-High Wall Split MAZ12CH/MRZ12CD 1 415 Heat Pump G.F Building-D2 2
SPECIFICATIONS
INDOOR UNIT MAZ30CCXAD MAZ30CHXAD MMZ36CCXAD MMZ36CHXAD
MODEL NUMBER
OUTDOOR UNIT KRZ30CDACIAD KRZ30CDAHIAD MRZ36CDGCIAD MRZ36CDGHIAD
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 27000 / 24000 27000 / 24000 31400 / 26800 31400 / 26800
COOLING CAPACITY ( T1 & T3 ) watts 7900 / 7020 7900 / 7020 9202 / 7854 9202 / 7854
HEATING CAPAICTY watts -- 7,500 -- 9,000
POWER INPUT ( T1 & T3 ) watts 2195 / 2824 2195 / 2824 2614 / 3135 2614 / 3135
POWER INPUT ( Heating ) watts -- 2,150 -- 2,455
EER ( T1 & T3 ) Btuh/W 12.3 / 8.50 12.3 / 8.50 12.0 / 8.55 12.0 / 8.55
COP ( Heating ) W/W -- 3.49 -- 3.65
SEER Btuh/W 10.35 10.35 10.17 10.17
ANNUAL ENERGY CONSUMPTION kWh 9,200 9,200 10,469 10,469
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 850 / 790 / 640 / 550 850 / 790 / 640 / 550 950 / 850 / 750 950 / 850 / 750
SOUND PRESSURE LEVEL (1M) dBA 52 / 48 / 45 52 / 48 / 45 50.5/47.5/44.5 51 /48 / 45
BLOWER MOTOR FLA/POWER INPUT watts 0.4 / 89 0.4 / 89 0.35 / 73 0.35 / 73
COMPRESSOR RLA/LRA A 10.6 / 56 10.6 / 56 12.0 / 79 12.0 / 79
CONDENSER FAN MOTOR FLA/LRA A 0.87 / 200 0.87 / 200 0.70 / 150 0.70 / 150
COMPRESSOR TYPE ROTARY ROTARY ROTARY ROTARY
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 14.12 0.5 / 14.12 0.6 / 16 0.6 / 16
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 25 5 / 25 5 / 25 5 / 25
REFRIGERANT TYPE R410a R410a R410a R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 25 / 30 25 / 30 21.3 / 27.3 21.3 / 27.3
NET WEIGHT, KG
OUTDOOR UNIT kg 69 / 74 72 / 77 68.4 / 73 69.8 / 74.5
INDOOR UNIT mm 1259 X 282 X 362 1259 X 282 X 362 1350 X 272 X 365 1350 X 272 X 365
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 1000 X 390 X 860 1000 X 390 X 860 946 X 410 X 810 946 X 410 X 810

CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ12CHX
MODEL NUMBER
OUTDOOR UNIT MRZ12CDGH
MODE OF OPERATION Cool only / Heal pump HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60
ENERGY CLASS ( SEER ) D
COOLING CAPACITY ( T1 & T3 ) Btuh 11800 / 10300
COOLING CAPACITY ( T1 & T3 ) watts 3458 / 3019
HEATING CAPAICTY watts 3,300
POWER INPUT ( T1 & T3 ) watts 951 / 1177
POWER INPUT ( Heating ) watts 916
EER ( T1 & T3 ) Btuh/W 12.4 / 8.75
COP ( Heating ) W/W 3.60
SEER Btuh/W 10.50
ANNUAL ENERGY CONSUMPTION kWh
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 415 / 365 / 315
SOUND PRESSURE LEVEL (1M) dBA 40.5 / 37 / 34.5
BLOWER MOTOR FLA/POWER INPUT watts 59
COMPRESSOR RLA/LRA A 4.75 / 27
CONDENSER FAN MOTOR FLA/LRA A 78
COMPRESSOR TYPE Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.3 / 6.39
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 15
REFRIGERANT TYPE R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 1/2, 5/8
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 20 / 8
INDOOR UNIT kg 11.6 / 14.9
NET WEIGHT, KG
OUTDOOR UNIT kg 33.8 / 36.5
INDOOR UNIT mm 965x215x319
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 805x330x554
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-G2
Building (G2) - STAFF BREAK-21
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 G2-SU-01-1 TO 07 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-G02 7
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-I
BUILDING (I) - CAR PASSENGERS CHECKING & BREAK
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 I-SU-01-1 TO 04 DX-High Wall Split MAZ12CH/MRZ12CD 1 415 Heat Pump G.F Building-I 4

2 I-SU-02-1 TO 03 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-I 3

3 I-SU-03-01 TO 05 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-I 5

4 I-SU-05-1 TO 11 DX-High Wall Split MMZ36CH/MRZ36DGH 3 950 Heat Pump G.F Building-I 11
SPECIFICATIONS
INDOOR UNIT MAZ12CHX
MODEL NUMBER
OUTDOOR UNIT MRZ12CDGH
MODE OF OPERATION Cool only / Heal pump HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60
ENERGY CLASS ( SEER ) D
COOLING CAPACITY ( T1 & T3 ) Btuh 11800 / 10300
COOLING CAPACITY ( T1 & T3 ) watts 3458 / 3019
HEATING CAPAICTY watts 3,300
POWER INPUT ( T1 & T3 ) watts 951 / 1177
POWER INPUT ( Heating ) watts 916
EER ( T1 & T3 ) Btuh/W 12.4 / 8.75
COP ( Heating ) W/W 3.60
SEER Btuh/W 10.50
ANNUAL ENERGY CONSUMPTION kWh
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 415 / 365 / 315
SOUND PRESSURE LEVEL (1M) dBA 40.5 / 37 / 34.5
BLOWER MOTOR FLA/POWER INPUT watts 59
COMPRESSOR RLA/LRA A 4.75 / 27
CONDENSER FAN MOTOR FLA/LRA A 78
COMPRESSOR TYPE Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.3 / 6.39
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 15
REFRIGERANT TYPE R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 1/2, 5/8
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 20 / 8
INDOOR UNIT kg 11.6 / 14.9
NET WEIGHT, KG
OUTDOOR UNIT kg 33.8 / 36.5
INDOOR UNIT mm 965x215x319
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 805x330x554
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ30CCXAD MAZ30CHXAD MMZ36CCXAD MMZ36CHXAD
MODEL NUMBER
OUTDOOR UNIT KRZ30CDACIAD KRZ30CDAHIAD MRZ36CDGCIAD MRZ36CDGHIAD
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 27000 / 24000 27000 / 24000 31400 / 26800 31400 / 26800
COOLING CAPACITY ( T1 & T3 ) watts 7900 / 7020 7900 / 7020 9202 / 7854 9202 / 7854
HEATING CAPAICTY watts -- 7,500 -- 9,000
POWER INPUT ( T1 & T3 ) watts 2195 / 2824 2195 / 2824 2614 / 3135 2614 / 3135
POWER INPUT ( Heating ) watts -- 2,150 -- 2,455
EER ( T1 & T3 ) Btuh/W 12.3 / 8.50 12.3 / 8.50 12.0 / 8.55 12.0 / 8.55
COP ( Heating ) W/W -- 3.49 -- 3.65
SEER Btuh/W 10.35 10.35 10.17 10.17
ANNUAL ENERGY CONSUMPTION kWh 9,200 9,200 10,469 10,469
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 850 / 790 / 640 / 550 850 / 790 / 640 / 550 950 / 850 / 750 950 / 850 / 750
SOUND PRESSURE LEVEL (1M) dBA 52 / 48 / 45 52 / 48 / 45 50.5/47.5/44.5 51 /48 / 45
BLOWER MOTOR FLA/POWER INPUT watts 0.4 / 89 0.4 / 89 0.35 / 73 0.35 / 73
COMPRESSOR RLA/LRA A 10.6 / 56 10.6 / 56 12.0 / 79 12.0 / 79
CONDENSER FAN MOTOR FLA/LRA A 0.87 / 200 0.87 / 200 0.70 / 150 0.70 / 150
COMPRESSOR TYPE ROTARY ROTARY ROTARY ROTARY
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 14.12 0.5 / 14.12 0.6 / 16 0.6 / 16
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 25 5 / 25 5 / 25 5 / 25
REFRIGERANT TYPE R410a R410a R410a R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 25 / 30 25 / 30 21.3 / 27.3 21.3 / 27.3
NET WEIGHT, KG
OUTDOOR UNIT kg 69 / 74 72 / 77 68.4 / 73 69.8 / 74.5
INDOOR UNIT mm 1259 X 282 X 362 1259 X 282 X 362 1350 X 272 X 365 1350 X 272 X 365
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 1000 X 390 X 860 1000 X 390 X 860 946 X 410 X 810 946 X 410 X 810

CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-K2
BUILDING (K2) - CAR CHECK BUILDING
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 K2-SU-02-01 TO 06 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-K2 6
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-K18
BUILDING (K18) - BUS WORKSHOP - INBOUND
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 K18-SU-01-01 TO 03 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-K18 3
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-K22
BUILDING (K22) - CAR WORKSHOP - OUTBOUND
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 K22-SU-02-01 TO 06 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-K22 6
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-H
BUILDING (K3) 09 - BUILDING
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 B09-SU-01-01 TO 09 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-K3 9

2 B09-SU-02-01 TO 03 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-K3 3

3 B09-SU-03-01 TO 04 DX-High Wall Split MAZ30CH/KRZ30CD 2.5 850 Heat Pump G.F Building-K3 4
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ30CCXAD MAZ30CHXAD MMZ36CCXAD MMZ36CHXAD
MODEL NUMBER
OUTDOOR UNIT KRZ30CDACIAD KRZ30CDAHIAD MRZ36CDGCIAD MRZ36CDGHIAD
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 27000 / 24000 27000 / 24000 31400 / 26800 31400 / 26800
COOLING CAPACITY ( T1 & T3 ) watts 7900 / 7020 7900 / 7020 9202 / 7854 9202 / 7854
HEATING CAPAICTY watts -- 7,500 -- 9,000
POWER INPUT ( T1 & T3 ) watts 2195 / 2824 2195 / 2824 2614 / 3135 2614 / 3135
POWER INPUT ( Heating ) watts -- 2,150 -- 2,455
EER ( T1 & T3 ) Btuh/W 12.3 / 8.50 12.3 / 8.50 12.0 / 8.55 12.0 / 8.55
COP ( Heating ) W/W -- 3.49 -- 3.65
SEER Btuh/W 10.35 10.35 10.17 10.17
ANNUAL ENERGY CONSUMPTION kWh 9,200 9,200 10,469 10,469
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 850 / 790 / 640 / 550 850 / 790 / 640 / 550 950 / 850 / 750 950 / 850 / 750
SOUND PRESSURE LEVEL (1M) dBA 52 / 48 / 45 52 / 48 / 45 50.5/47.5/44.5 51 /48 / 45
BLOWER MOTOR FLA/POWER INPUT watts 0.4 / 89 0.4 / 89 0.35 / 73 0.35 / 73
COMPRESSOR RLA/LRA A 10.6 / 56 10.6 / 56 12.0 / 79 12.0 / 79
CONDENSER FAN MOTOR FLA/LRA A 0.87 / 200 0.87 / 200 0.70 / 150 0.70 / 150
COMPRESSOR TYPE ROTARY ROTARY ROTARY ROTARY
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 14.12 0.5 / 14.12 0.6 / 16 0.6 / 16
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 25 5 / 25 5 / 25 5 / 25
REFRIGERANT TYPE R410a R410a R410a R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 25 / 30 25 / 30 21.3 / 27.3 21.3 / 27.3
NET WEIGHT, KG
OUTDOOR UNIT kg 69 / 74 72 / 77 68.4 / 73 69.8 / 74.5
INDOOR UNIT mm 1259 X 282 X 362 1259 X 282 X 362 1350 X 272 X 365 1350 X 272 X 365
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 1000 X 390 X 860 1000 X 390 X 860 946 X 410 X 810 946 X 410 X 810

CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-B04
BUILDING B04-EMPLOYEE'S ADMIN AND RECEPTION BUILDING
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 B04-SU-01-01 TO 04 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-B04 4

2 B04-SU-02-01 TO12 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-B04 12
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-DL
BUILDING DL-BUILDING OF CONFORMITY CABINET BUILDING
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 DL-SU-01-01 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-DL 1
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-GT
BUILDIONG (GT)-GATE BUILDING
SUMMARY SHEET - AC UNITS

Total Capacity Electric Heater


Item TAG# TYPE Model Air Flow (CFM) Floor Building Qty
(Tons) (kW)

1 GT-SU-01-01 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-GT 1
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
3. CERTIFICATES
3.a CHILLERS CERTIFICATES
Certificate of Product Ratings
AHRI Certified Reference Number : 10324726 Date : 12-11-2022 Model Status : Active

Brand Name : ZAMIL

Model Designation : ASC390B

Ratings generated using the following shall be in accordance with the latest edition of ANSI/AHRI Standards 550/590 (I-P) with Addendum
3 and 551/591 (SI) with Addendum 3 for Performance Rating of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor
Compression Cycle and subject to rating accuracy by AHRI-sponsored, independent, third party testing.

Refrigerant Used per ASHRAE 34 : R-134a

Compressor Model Series Information : RC2 / CSH / CSVH / RE

Compressor Type : Screw

Primary Catalog or Selection Rating Application Name : ChillZAC

Primary Catalog or Selection Rating Application Version : 1.1.82.0

Hertz : 60

Country of Origin : Saudi Arabia

Certified by AHRI to EN 14511 and EN14825 : No

Nominal Cooling Capacity Units : Tons

Nominal Cooling Capacity Range - Low : 377.2

Nominal Cooling Capacity Range - High : 415.9

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133152388953761644
Certificate
For
Energy Efficiency Label

The Saudi Standards, Metrology and Quality Org. (SASO)


has certified: ZAMIL CENTRAL AIR CONDITIONERS CO. (L.L.C.)
to use the energy efficiency label According to SASO 2874/2016, for the following product (s): -

Large AC Type Out Door Model Mark's Name License Number Cooling Capacity Power EER/SCOP
Chillers – air cooled ZAMIL AIR
ASC390B LAC051802943 4755000 445.9 10.65
CONDITIONERS

Expiry Date: 16/11/1444 H, (04-06-2023 A.D.)


This certificate is subject during its validation to the related Rules & Regulations of the Kingdom of
Saudi Arabia, and any Instructions or Amendments issued by SASO.

Certificate No.: E02943/2018


CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20150430
Issue Date 2019-FEBRUARY-11

Issued to: Zamil Air Conditioners & Home Appliances Co. Ltd
PO BOX 14440
1ST INDUSTRIAL CITY
DAMMAM 31424 SAUDI ARABIA

This certificate confirms that HEATING AND COOLING EQUIPMENT


representative samples of See Addendum Page

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 1995, Heating and Cooling Equipment


Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20150430
Issue Date 2019-FEBRUARY-11

This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.

Liquid Chillers – Self Contained Units

Type or Model Designation

For 60Hz Model:

ASC followed by 060 to 510 followed by B followed by H or M or F followed by xxxxxxx followed by UL

ASY followed by 060 to 510 followed by B followed by H or M or F followed by xxxxxxx followed by ULh

For 50Hz Model:

ASC followed by 055 to 445 followed by B followed by L followed by xxxxxxx followed by UL

ASY followed by 055 to 445 followed by B followed by L followed by xxxxxxx followed by ULh

Note – x can be any letter indicating options

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 2
3.b AHU CERTIFICATES
Certificate of Product Ratings
AHRI Certified Reference Number : 200096144 Date : 12-20-2022 Model Status : Active

Old AHRI Reference Number : 8296623

Brand Name : ZAMIL

Model Number : TW26

Ratings generated using the following shall be in accordance with the latest editions of AHRI Standard 430 (I-P) and AHRI Standard 431
(SI) for Central Station Air-Handling Unit Supply Fans and subject to rating accuracy by AHRI-sponsored, independent, third party
testing.

Configuration : Ducted Fan Discharge

Supply Fan Type : Housed Fan

Geometry : Airfoil/Backwards-Inclined

Drive Type : Belt-drive

Fan Array Included : No

Fan Array Type : Contained

Casing Design Pressure : 10.00

Units >= 10 in H2O Casing Design Pressure optionally certified : No

Units >= 50000 cfm optionally certified : Yes

Rating Method : Measured

Software Name : AirCalc++(Climcalc)

Software Version : 3.8.33

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160007333276033
Certificate of Product Ratings
AHRI Certified Reference Number : 200096122 Date : 01-16-2023 Model Status : Active

Old AHRI Reference Number : 8296601

Brand Name : ZAMIL

Model Number : TW17

Ratings generated using the following shall be in accordance with the latest editions of AHRI Standard 430 (I-P) and AHRI Standard 431
(SI) for Central Station Air-Handling Unit Supply Fans and subject to rating accuracy by AHRI-sponsored, independent, third party
testing.

Configuration : Ducted Fan Discharge

Supply Fan Type : Housed Fan

Geometry : Airfoil/Backwards-Inclined

Drive Type : Belt-drive

Fan Array Included : No

Fan Array Type : Contained

Casing Design Pressure : 10.00

Units >= 10 in H2O Casing Design Pressure optionally certified : No

Units >= 50000 cfm optionally certified : Yes

Rating Method : Measured

Software Name : AirCalc++(Climcalc)

Software Version : 3.8.33

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2023 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133183490167914406
Certificate of Product Ratings
AHRI Certified Reference Number : 200096112 Date : 12-20-2022 Model Status : Active

Old AHRI Reference Number : 8296591

Brand Name : ZAMIL

Model Number : TW14

Ratings generated using the following shall be in accordance with the latest editions of AHRI Standard 430 (I-P) and AHRI Standard 431
(SI) for Central Station Air-Handling Unit Supply Fans and subject to rating accuracy by AHRI-sponsored, independent, third party
testing.

Configuration : Ducted Fan Discharge

Supply Fan Type : Housed Fan

Geometry : Airfoil/Backwards-Inclined

Drive Type : Belt-drive

Fan Array Included : No

Fan Array Type : Contained

Casing Design Pressure : 10.00

Units >= 10 in H2O Casing Design Pressure optionally certified : No

Units >= 50000 cfm optionally certified : Yes

Rating Method : Measured

Software Name : AirCalc++(Climcalc)

Software Version : 3.8.33

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160007019364775
Certificate of Product Ratings
AHRI Certified Reference Number : 200096090 Date : 01-16-2023 Model Status : Active

Old AHRI Reference Number : 8296569

Brand Name : ZAMIL

Model Number : TW11

Ratings generated using the following shall be in accordance with the latest editions of AHRI Standard 430 (I-P) and AHRI Standard 431
(SI) for Central Station Air-Handling Unit Supply Fans and subject to rating accuracy by AHRI-sponsored, independent, third party
testing.

Configuration : Ducted Fan Discharge

Supply Fan Type : Housed Fan

Geometry : Airfoil/Backwards-Inclined

Drive Type : Belt-drive

Fan Array Included : No

Fan Array Type : Contained

Casing Design Pressure : 10.00

Units >= 10 in H2O Casing Design Pressure optionally certified : No

Units >= 50000 cfm optionally certified : Yes

Rating Method : Measured

Software Name : AirCalc++(Climcalc)

Software Version : 3.8.33

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2023 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133183490049943893
CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20140605
Issue Date 2019-FEBRUARY-11

Issued to: Zamil Air Conditioners & Home Appliances Co. Ltd
PO BOX 14440
1ST INDUSTRIAL CITY
DAMMAM 31424 SAUDI ARABIA

This certificate confirms that HEATING AND COOLING EQUIPMENT


representative samples of See Addendum Page

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL1995/CSA C22.2 No. 236, Heating and Cooling
Equipment
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20140605
Issue Date 2019-FEBRUARY-11

This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.

Air Handling units

Type or Model Designation:

Series TW or TWH, may be followed by S, followed by 2/3/4/6/8/11/14/17/22/26/35/47/60/73/90/105


/120, followed by P3/P5/P5E, followed by B/V/S, followed by D.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 2
CERTIFICATE
N° 07.04.233
Air Handling Unit / Centrales de traitement d'air
Range Name / Nom de Gamme :
TW&TW(H)
Granted on April 27, 2007 - Date 1ère admission 27 avril 2007

This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com

Participant/Titulaire

ZAMIL Central Air Conditioners


PO Box 41015 - Street 106, 2nd industrial city
31521 Dammam, Saudi Arabia

This product performance certificate is issued by Ce certificat de performance produit est délivré par Eurovent
Eurovent Certita Certification according to the Certita Certification dans les conditions fixées par le
certification rules: référentiel :

ECP AHU - « Air Handling Unit » in force at ECP AHU – « Centrales de traitement d'air » en vigueur à
established date. date d’édition.

Pursuant to the decision notified by Eurovent Certita En vertu de la décision notifiée par Eurovent Certita
Certification, the right to use the mark ECP shall be Certification, le droit d'usage de la marque ECP, est accordé à
granted to the beneficiary company for the above Range la société qui en est bénéficiaire pour la gamme visée ci-
in the conditions defined by the certification program dessus, dans les conditions définies par le programme de
mentioned. certification mentionné.

Unless withdrawn or suspended, this certificate remains Sauf retrait ou suspension, ce certificat demeure valide tant
valid as long as the requirements for the certification que les conditions du référentiel du programme de certification
program framework are met. The validity of the sont respectées. La validité du certificat est à vérifier sur le site
certificate is to be verified on www.eurovent- Internet www.eurovent-certification.com
certification.com
CE CERTIFICAT A ÉTÉ EMIS LE 14/12/2021
THIS CERTIFICATE HAS BEEN ISSUED ON 14/12/2021 CE CERTIFICAT EST VALIDE JUSQU’AU 31/12/2022
THIS CERTIFICATE IS VALID UNTIL 31/12/2022

Paris, 14 décembre 2021


Organisme accrédité n° 5-0517
Certification Produits et Services selon la
norme NF EN ISO/CEI 17065:2012
Portée disponible sur www.cofrac.fr
MANAGING BOARD MEMBER / MEMBRE DIRECTOIRE
Accreditation #5-0517 Products and
Services Certification according to NF EN
ISO/CEI 17065:2012 –
Scope available on www.cofrac.fr

COFRAC est signataire des accords MLA


d’EA et MLA d’IAF,
COFRAC is signatory of EA MLA and IAF
MLA,
list of EA members is available on
www.european-accreditation.org/ea-members
list of IAF members is available on
www.iaf.nu//articles/IAF_MEMBERS_SIGNATORIES/4

1/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06D06 TEMPLATE_ECP_RANGE_REV1.1
CERTIFICATE
N° 07.04.233

Appendix / Annexe

Granted on April 27, 2007 - Date 1ère admission 27 avril 2007

This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com

List of certified products and characteristics is displayed on:


La liste des références et caractéristiques certifiées est disponible sur le site :
www.eurovent-certification.com
This product performance certificate is valid for the following trade names:
Ce certificat de performance produit est valide pour les marques commerciales suivantes:
Trade Name / Marque Commerciale

COOLINE
ZAMIL

This product performance certificate is valid for the following manufacturing places:
Ce certificat de performance produit est valide pour les sites de production suivants:
Manufacturing Place / Site de Production

Dammam, Saudi Arabia

This product performance certificate is valid for the following software:


Ce certificat de performance produt est valide pour les logiciels de sélection suivants:
Software / Logiciel de sélection

Aircalc++ 3.8.32

2/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06D06 TEMPLATE_ECP_RANGE_REV1.1
3.c FCU CERTIFICATES
Certificate of Product Ratings
AHRI Certified Reference Number : 8075204 Date : 12-20-2022 Model Status : Active

Brand Name : ZAMIL AIR CONDITIONERS

Model Number : DWX06

Series Name : DWX

Motor Type : PSC

Rated as follows in accordance with the latest edition of ANSI/AHRI 440 with Addendum 1: Performance Rating of Room Fan-Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:

Air Flow Rating, scfm : 680

Total Capacity, btuh : 18700

Sensible Capacity, btuh : 14700

Power Input, W : 190

Water Temperature Rise, deg F : 10

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160005382921012
Certificate of Product Ratings
AHRI Certified Reference Number : 8075205 Date : 12-20-2022 Model Status : Active

Brand Name : ZAMIL AIR CONDITIONERS

Model Number : DWX08

Series Name : DWX

Motor Type : PSC

Rated as follows in accordance with the latest edition of ANSI/AHRI 440 with Addendum 1: Performance Rating of Room Fan-Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:

Air Flow Rating, scfm : 740

Total Capacity, btuh : 19400

Sensible Capacity, btuh : 15400

Power Input, W : 215

Water Temperature Rise, deg F : 10

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160005551047631
Certificate of Product Ratings
AHRI Certified Reference Number : 8075206 Date : 12-20-2022 Model Status : Active

Brand Name : ZAMIL AIR CONDITIONERS

Model Number : DWX10

Series Name : DWX

Motor Type : PSC

Rated as follows in accordance with the latest edition of ANSI/AHRI 440 with Addendum 1: Performance Rating of Room Fan-Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:

Air Flow Rating, scfm : 1200

Total Capacity, btuh : 30600

Sensible Capacity, btuh : 23600

Power Input, W : 485

Water Temperature Rise, deg F : 10

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160005641515683
Certificate of Product Ratings
AHRI Certified Reference Number : 8075207 Date : 12-20-2022 Model Status : Active

Brand Name : ZAMIL AIR CONDITIONERS

Model Number : DWX12

Series Name : DWX

Motor Type : PSC

Rated as follows in accordance with the latest edition of ANSI/AHRI 440 with Addendum 1: Performance Rating of Room Fan-Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:

Air Flow Rating, scfm : 1370

Total Capacity, btuh : 33800

Sensible Capacity, btuh : 26100

Power Input, W : 590

Water Temperature Rise, deg F : 10

†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being

marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160006044803749
CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20140909
Issue Date 2019-FEBRUARY-11

Issued to: Zamil Air Conditioners & Home Appliances Co. Ltd
PO BOX 14440
1ST INDUSTRIAL CITY
DAMMAM 31424 SAUDI ARABIA

This certificate confirms that HEATING AND COOLING EQUIPMENT


representative samples of FAN-COIL UNITS, Models DWX and CWX

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL1995/CSA C22.2 No. 236, Heating and Cooling
Equipment
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 1
3.d SPLIT CERTIFICATES
Certificate
For
Energy Efficiency Label

The Saudi Standards, Metrology and Quality Org. (SASO)


has certified : GD Midea Air‐Conditioning Equipment Co., Ltd.
to use the energy efficiency label According to SASO 2663/2021, for the following product:‐

Device Type Model's number Brand name SEER value Class Licence number

AC Single Split System MAZ12CHXAD1 ZAMIL 10.50 D AC122135202


MRZ12CDGHIAD1

* Expiry Date: 1444‐05‐22 AH, 16‐Dec‐2022 AD


This certificate is subject during its validation to the related Rules & Regulations of the Kingdom of
Saudi Arabia, and any Instructions or Amendments issued by SASO.

Application No: E35202/2021


+966 11 2529999
Certificate
For
Energy Efficiency Label

The Saudi Standards, Metrology and Quality Org. (SASO)


has certified : ZAMIL AIRCONDITIONERS
to use the energy efficiency label According to SASO 2663/2021, for the following product:‐

Device Type Model's number Brand name SEER value Class Licence number

AC Single Split System MAZ18CHXAD1 ZAMIL 10.55 D AC012200783


MRZ18CDGHIAD1

* Expiry Date: 1444‐05‐07 AH, 01‐Dec‐2022 AD


This certificate is subject during its validation to the related Rules & Regulations of the Kingdom of
Saudi Arabia, and any Instructions or Amendments issued by SASO.

Application No: E14308/2019


+966 11 2529999
Certificate
For
Energy Efficiency Label

The Saudi Standards, Metrology and Quality Org. (SASO)


has certified : ZAMIL AIRCONDITIONERS
to use the energy efficiency label According to SASO 2663/2021, for the following product:‐

Device Type Model's number Brand name SEER value Class Licence number

AC Single Split System MAZ24CHXAD1 ZAMIL 10.45 D AC012200784


MRZ24CDGHIAD1

* Expiry Date: 1444‐04‐23 AH, 17‐Nov‐2022 AD


This certificate is subject during its validation to the related Rules & Regulations of the Kingdom of
Saudi Arabia, and any Instructions or Amendments issued by SASO.

Application No: E14363/2019


+966 11 2529999
Certificate
For
Energy Efficiency Label

The Saudi Standards, Metrology and Quality Org. (SASO)


has certified : ZAMIL AIRCONDITIONERS
to use the energy efficiency label According to SASO 2663/2021, for the following product:‐

Device Type Model's number Brand name SEER value Class Licence number

AC Single Split System MMZ36CHXAD ZAMIL 10.20 D AC042204027


MRZ36CDGHIAD

* Expiry Date: 1444‐09‐29 AH, 20‐Apr‐2023 AD


This certificate is subject during its validation to the related Rules & Regulations of the Kingdom of
Saudi Arabia, and any Instructions or Amendments issued by SASO.

Application No: E04027/2022


+966 11 2529999