Zamil Technical Submittal - AL-HADETHA CUSTOMS - Chillers, AHU, FCU, SPLIT - R1
Zamil Technical Submittal - AL-HADETHA CUSTOMS - Chillers, AHU, FCU, SPLIT - R1
PROJECT
CUSTOMER:
Project: AL-HADETHA CUSTOMS - CHILLER PLANT
Location: TABOUK
Usage: HVAC
1. SPECIFICATIONS COMPLIANCE
a. Chillers
b. AHU
c. FCU
3. CERTIFICATES
a. Chillers
b. AHU
c. FCU
d. Split
4. CATALOGUES
1. SPECIFICATIONS COMPLIANCE
1.a - Chillers
Noted
Noted
Noted
ir Conditioners Noted
Noted
Noted
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Please refer to datasheet
Comply
Comply ir Conditioners
with Rubber
Isolators
Comply
Comply, 3
compressors
Comply
Comply
Comply
ir Conditioners
Noted
Noted
Noted
ir Conditioners
1.b - AHU
ir Conditioners
ir Conditioners
Comply, Backward curved fan is provided
Comply, TEFC motor provided
Comply
Comply
Not required
Not required
Comply
Comply,
copper
tubes
with AL
ir Conditioners
fins
ir Conditioners
1.c - FCU
Comply
ir Conditioners
Comply
NA
NA
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted ir Conditioners
Noted
Comply
Comply
Comply
Comply
Comply
Comply
ir Conditioners
Comply
ir Conditioners
2. TECHNICAL DATA WITH
DRAWING
2.a Chillers Plant
Chillers Design Data
Aluminum fins /
0.1 chillers 322 46 11 5.5 outside Rotary Screw 380V-3Ph-60Hz 3
copper tubes
Aluminum fins /
0.1 chillers 324.5 46 11 5.5 outside Rotary Screw 380V-3Ph-60Hz 3
copper tubes
ChillZAC
Ref/Tag: CH 1 TO 3 Quantity: 3
TR °C ft °C °C
Input Conditions
1 of 2
PacZAC
Ref/Tag: CH 1 TO 3 Quantity: 3
2 of 2
2.b AHU + FCU
Building-A
A-BUILDING
Design Data
1 A-AHU-GF-1 Chilled water AHU 38 91.2 16000 4225 16000 500 36 R.F 380V-3Ph-60Hz 2
2 A-AHU-GF-2 Chilled water AHU 20 48 7000 1750 7000 500 18 R.F 380V-3Ph-60Hz 2
Total Capacity Sensible Capacity Supply Fan Return Fan ESP for each Electric Heater
Item TAG# TYPE Model GPM Fresh Air (CFM) FLOOR Power Supply Qty
(Tons) (Tons) AirFlow (CFM) AirFlow (CFM) Fan (Pa) (kW)
1 A-AHU-GF-1 Chilled water TW26P5BD 38 32.56 91.66 16,000 4225 16000 500 36 / 2 Stages R.F 380V-3Ph-60Hz 2
2 A-AHU-GF-2 Chilled water TW11P5BD 20 16.32 48.25 7,000 1750 7000 500 27 / 2 Stages R.F 380V-3Ph-60Hz 2
3 FCU-01-1 TO 06 Chilled water DWX06 1.0 0.74 2.4 420 - - 50 1 G.F 230V-1Ph-60Hz 6
4 FCU-02-1 TO 04 Chilled water DWX18 4.1 2.92 9.8 1,466 - - 50 3 G.F 230V-1Ph-60Hz 4
239 311 311
120
82.5
675
1,995
1,830
2,075
1 2 1 2 3 4 5
801
519
82.5
80
552
801
1,995
1,770
1,830
642
112.5
82.5
SECTION 1 SECTION 2
o o o o o o
o o o o o o
93
Recircle air [cfm] 11,775 Humidity 64.05 Mixed air Temp. 84.38 Humidity [%] 66.30
Fresh air [cfm] 4,225 Humidity 72.00 total air 16,000 Mixing Ratio [%] 74
Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 4,800
Total Qta. Levers 1 air velocity [m/s] 4.12
Each Torque [Nm] 3.03
Damper: Dimensions [mm] 1,770.0 x 412.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 12,800
Total Qta. Levers 1 air velocity [m/s] 8.28
Each Torque [Nm] 4.04
16-Jan-23 12:14
Offer AJD-26234-R1* Page 2/7
Position A-AHUGF-1 From date 16-Jan-23
Medium Water
Airflow [cfm] 16,000
Med. Flow [Gpm] 91.66
air velocity [m/s] 2.67
Med. velocity [m/s] 0.85
Air in [gF] 84.38 Humidity [gF] 66.3
Med. in [gF] 41.88
Air out [gF] 61.51 Humidity [gF] 57.28
Med. out [gF] 51.78
total capacity [RT] 38.00
Med. pres. drop [inWG] 40.71
Sens. capacity 32.56
SHR 0.86
Air press. drop (wet) [inWG] 0.466
Air press. drop (dry) [inWG] 0.419
Fins AL
Fin space [mm] 2.5
RRows CU
Connection in NPT 2 1/2
Header CU
Connection out NPT 2 1/2
Frames GI
CW-1/2"-2.5 4R - RH
Water content (KG) 60.4
1 set Coating for End Plates
16-Jan-23 12:14
Offer AJD-26234-R1* Page 3/7
Position A-AHUGF-1 From date 16-Jan-23
Fan pulley SPB280 Bush 2517-50 Axle distance ca. [mm] 419
Motor pulley SPB212 Bush 2517-42
Belt 2x 1600
System effect pressure drop included
Pulleys & Belts selected with service factor 150%
16-Jan-23 12:14
Offer AJD-26234-R1* Page 4/7
Position A-AHUGF-1 From date 16-Jan-23
16-Jan-23 12:14
Offer AJD-26234-R1* Page 5/7
Position A-AHUGF-1 From date 16-Jan-23
Fan pulley SPB280 Bush 2517-50 Axle distance ca. [mm] 407
Motor pulley SPB180 Bush 2517-42
Belt 2x 1500
System effect pressure drop included
Pulleys & Belts selected with service factor 150%
16-Jan-23 12:14
Offer AJD-26234-R1* Page 6/7
Position A-AHUGF-1 From date 16-Jan-23
Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 4,800
Total Qta. Levers 1 air velocity [m/s] 4.12
Each Torque [Nm] 3.03
SFP (int) 0 Specific Fan Power (Internal) MCA : 107.54 MOCP : 150 of complete unit.
Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.
Delivery sections no. Width [mm] Height [mm] Length [mm] Weight [kg]
16-Jan-23 12:14
Offer AJD-26234-R1* Page 7/7
Position A-AHUGF-1 From date 16-Jan-23
16-Jan-23 12:14
239 311 311
120
484
569.5
1,385
1,465
311
507
1 2 1 2 3 4 5
504.5
394
80
255
507
1,385
1,160
1,220
623
112.5
82.5
SECTION 1 SECTION 2
o o o o o o
o o o o o o
93
Recircle air [cfm] 5,250 Humidity 64.05 Mixed air Temp. 84.01 Humidity [%] 66.17
Fresh air [cfm] 1,750 Humidity 72.00 total air 7,000 Mixing Ratio [%] 75
Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 2,100
Total Qta. Levers 1 air velocity [m/s] 2.75
Each Torque [Nm] 2.32
Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 5,600
Total Qta. Levers 1 air velocity [m/s] 7.33
Each Torque [Nm] 2.32
16-Jan-23 12:14
Offer AJD-26234-R1* Page 2/7
Position A-AHUGF-2 From date 16-Jan-23
Medium Water
Airflow [cfm] 7,000
Med. Flow [Gpm] 48.25
air velocity [m/s] 2.67
Med. velocity [m/s] 1.36
Air in [gF] 84.01 Humidity [gF] 66.1
Med. in [gF] 41.88
Air out [gF] 57.79 Humidity [gF] 55.10
Med. out [gF] 51.78
total capacity [RT] 20.00
Med. pres. drop [inWG] 110.88
Sens. capacity 16.34
SHR 0.82
Air press. drop (wet) [inWG] 0.562
Air press. drop (dry) [inWG] 0.506
Fins AL
Fin space [mm] 2.1
RRows CU
Connection in NPT 2
Header CU
Connection out NPT 2
Frames GI
CW-1/2"-2.1 4R - RH
Water content (KG) 27.1
1 set Coating for End Plates
Drip eliminator
16-Jan-23 12:14
Offer AJD-26234-R1* Page 3/7
Position A-AHUGF-2 From date 16-Jan-23
Fan pulley SPB178V Bush 2012-35 Axle distance ca. [mm] (338)
Motor pulley SPB212 Bush 2517-38
Belt 2x 1250
No. of turns 1.5 System effect pressure drop included
Pulleys & Belts selected with service factor 150%
16-Jan-23 12:14
Offer AJD-26234-R1* Page 4/7
Position A-AHUGF-2 From date 16-Jan-23
16-Jan-23 12:14
Offer AJD-26234-R1* Page 5/7
Position A-AHUGF-2 From date 16-Jan-23
Fan pulley SPB187V Bush 2012-35 Axle distance ca. [mm] (348)
Motor pulley SPB190 Bush 2012-28
Belt 1x 1250
No. of turns 2 System effect pressure drop included
Pulleys & Belts selected with service factor 150%
16-Jan-23 12:14
Offer AJD-26234-R1* Page 6/7
Position A-AHUGF-2 From date 16-Jan-23
Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 2,100
Total Qta. Levers 1 air velocity [m/s] 2.75
Each Torque [Nm] 2.32
SFP (int) 0 Specific Fan Power (Internal) MCA : 64.315 MOCP : 80 of complete unit.
Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.
Delivery sections no. Width [mm] Height [mm] Length [mm] Weight [kg]
16-Jan-23 12:14
Offer AJD-26234-R1* Page 7/7
Position A-AHUGF-2 From date 16-Jan-23
16-Jan-23 12:14
GCC GULF
GCC GULF
DIMENSIONS
MODELS: DWX02 - DWX20
A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H
0.5"
2
E
B
6
1
1.0"
7
END VIEW TOP VIEW END VIEW
F 3.5"
3
G
C
7.0"
FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector
Design Data
1 AHU-04 Chilled water AHU 18.6 44.64 11,386 1500 11386 500 15 R.F 380V-3Ph-60Hz 2
2 AHU-05 Chilled water AHU 15.3 36.72 9,000 1000 9000 500 15 R.F 380V-3Ph-60Hz 2
Total Capacity Sensible Capacity Supply Fan Return Fan ESP for each Electric Heater
Item TAG# TYPE Model GPM Fresh Air (CFM) FLOOR Power Supply Qty
(Tons) (Tons) AirFlow (CFM) AirFlow (CFM) Fan (Pa) (kW)
1 AHU-04 Chilled water TW17P5BD 25.11 20.98 60.6 11,386 1500 11386 500 18 / 1 Stages R.F 380V-3Ph-60Hz 2
2 AHU-05 Chilled water TW14P5BD 19.51 16.58 47.0 9,000 1000 9000 500 18 / 1 Stages R.F 380V-3Ph-60Hz 2
3 FCU-01-1 TO 04 Chilled water DWX06 1.00 0.74 2.4 421 - - 50 1 G.F 230V-1Ph-60Hz 4
4 FCU-02-1 TO 10 Chilled water DWX10 1.71 1.24 4.1 727 - - 50 2 M.F 230V-1Ph-60Hz 10
5 FCU-03-1 TO 02 Chilled water DWX12 2.01 1.45 4.9 886 - - 50 2 M.F 230V-1Ph-60Hz 2
6 FCU-05-1 TO 06 Chilled water DWX18 4.08 2.92 9.9 1,466 - - 50 3 G.F 230V-1Ph-60Hz 6
239 311 311
120
302
569.5
638
1,385
1,465
311
1 2 1 2 3 4 5
504.5
445
80
1,140 550 590 590 750 700 1,190
2,280 3,230
L1 L2
5,510
112.5
82.5
678.5
1,995
1,770
1,830
638
678.5
112.5
82.5
SECTION 1 SECTION 2
o o o o o o
o o o o o o
93
Recircle air [cfm] 9,886 Humidity 64.05 Mixed air Temp. 80.60 Humidity [%] 65.18
Fresh air [cfm] 1,500 Humidity 72.00 total air 11,386 Mixing Ratio [%] 85
Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 3,416
Total Qta. Levers 1 air velocity [m/s] 2.93
Each Torque [Nm] 3.03
Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 9,109
Total Qta. Levers 1 air velocity [m/s] 7.81
Each Torque [Nm] 3.03
16-Jan-23 12:15
Offer AJD-26234-R1* Page 2/7
Position AHU-04 From date 16-Jan-23
Medium Water
Airflow [cfm] 11,386
Med. Flow [Gpm] 60.56
air velocity [m/s] 2.80
Med. velocity [m/s] 1.71
Air in [gF] 80.60 Humidity [gF] 65.1
Med. in [gF] 41.88
Air out [gF] 59.99 Humidity [gF] 56.63
Med. out [gF] 51.78
total capacity [RT] 25.11
Med. pres. drop [inWG] 231.80
Sens. capacity 20.98
SHR 0.84
Air press. drop (wet) [inWG] 0.506
Air press. drop (dry) [inWG] 0.455
Fins AL
Fin space [mm] 2.5
RRows CU
Connection in NPT 2
Header CU
Connection out NPT 2
Frames GI
CW-1/2"-2.5 4R - RH
Water content (KG) 37.5
1 set Coating for End Plates
Drip eliminator
16-Jan-23 12:15
Offer AJD-26234-R1* Page 3/7
Position AHU-04 From date 16-Jan-23
Fan pulley SPB180 Bush 2517-40 Axle distance ca. [mm] (353)
Motor pulley SPB190 Bush 2517-42
Belt 2x 1250
System effect pressure drop included
Pulleys & Belts selected with service factor 150%
16-Jan-23 12:15
Offer AJD-26234-R1* Page 4/7
Position AHU-04 From date 16-Jan-23
16-Jan-23 12:15
Offer AJD-26234-R1* Page 5/7
Position AHU-04 From date 16-Jan-23
Fan pulley SPA170 Bush 2012-40 Axle distance ca. [mm] 315
Motor pulley SPA164V Bush 1615-38
Belt 2x 1107
No. of turns 1 System effect pressure drop included
Pulleys & Belts selected with service factor 150%
16-Jan-23 12:15
Offer AJD-26234-R1* Page 6/7
Position AHU-04 From date 16-Jan-23
Damper: Dimensions [mm] 1,770.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 3,416
Total Qta. Levers 1 air velocity [m/s] 2.93
Each Torque [Nm] 3.03
SFP (int) 0 Specific Fan Power (Internal) MCA : 65.695 MOCP : 90 of complete unit.
Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.
Delivery sections no. Width [mm] Height [mm] Length [mm] Weight [kg]
16-Jan-23 12:15
Offer AJD-26234-R1* Page 7/7
Position AHU-04 From date 16-Jan-23
16-Jan-23 12:15
239 311 311
120
302
569.5
638
1,385
1,465
311
1 2 1 2 3 4 5
504.5
445
80
426
638
1,690
1,160
1,525
626
265
82.5
SECTION 1 SECTION 2
o o o o o o
o o o o o o
93
Recircle air [cfm] 8,000 Humidity 64.05 Mixed air Temp. 80.05 Humidity [%] 65.01
Fresh air [cfm] 1,000 Humidity 72.00 total air 9,000 Mixing Ratio [%] 83
Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 2,700
Total Qta. Levers 1 air velocity [m/s] 3.53
Each Torque [Nm] 2.32
Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 7,200
Total Qta. Levers 1 air velocity [m/s] 9.42
Each Torque [Nm] 2.32
16-Jan-23 12:18
Offer AJD-26234-R1* Page 2/7
Position AHU-05 From date 16-Jan-23
Medium Water
Airflow [cfm] 9,000
Med. Flow [Gpm] 47.08
air velocity [m/s] 2.68
Med. velocity [m/s] 1.33
Air in [gF] 81.60 Humidity [gF] 65.4
Med. in [gF] 41.88
Air out [gF] 60.99 Humidity [gF] 57.19
Med. out [gF] 51.78
total capacity [RT] 19.51
Med. pres. drop [inWG] 126.90
Sens. capacity 16.58
SHR 0.85
Air press. drop (wet) [inWG] 0.466
Air press. drop (dry) [inWG] 0.419
Fins AL
Fin space [mm] 2.5
RRows CU
Connection in NPT 2
Header CU
Connection out NPT 2
Frames GI
CW-1/2"-2.5 4R - RH
Water content (KG) 32.5
1 set Coating for End Plates
Drip eliminator
16-Jan-23 12:18
Offer AJD-26234-R1* Page 3/7
Position AHU-05 From date 16-Jan-23
Fan pulley SPA170 Bush 2012-40 Axle distance ca. [mm] 314
Motor pulley SPA160 Bush 2012-38
Belt 2x 1107
System effect pressure drop included
Pulleys & Belts selected with service factor 150%
16-Jan-23 12:18
Offer AJD-26234-R1* Page 4/7
Position AHU-05 From date 16-Jan-23
16-Jan-23 12:18
Offer AJD-26234-R1* Page 5/7
Position AHU-05 From date 16-Jan-23
Fan pulley SPB236 Bush 2012-40 Axle distance ca. [mm] 348
Motor pulley SPB180 Bush 1610-38
Belt 1x 1320
System effect pressure drop included
Pulleys & Belts selected with service factor 150%
16-Jan-23 12:18
Offer AJD-26234-R1* Page 6/7
Position AHU-05 From date 16-Jan-23
Damper: Dimensions [mm] 1,160.0 x 311.0 x 120.0 x 1 Type ZAC Airfoil AL/AL
Actuated by Lever Airflow [cfm] 2,700
Total Qta. Levers 1 air velocity [m/s] 3.53
Each Torque [Nm] 2.32
SFP (int) 0 Specific Fan Power (Internal) MCA : 53.595 MOCP : 70 of complete unit.
Note:
* Consider extra height for wood pc. under unit for shipping = 150mm & extra height for baserail of lower deck sections.
* Consider extra section for Energy Recovery section in TW11 & above " Whenever applicable".
* Fan outlet position subject to change during design.
* Pulleys & Belts may change without notice keeping similar RPM's.
Delivery sections no. Width [mm] Height [mm] Length [mm] Weight [kg]
16-Jan-23 12:18
Offer AJD-26234-R1* Page 7/7
Position AHU-05 From date 16-Jan-23
16-Jan-23 12:18
GCC GULF
GCC GULF
GCC GULF
GCC GULF
DIMENSIONS
MODELS: DWX02 - DWX20
A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H
0.5"
2
E
B
6
1
1.0"
7
END VIEW TOP VIEW END VIEW
F 3.5"
3
G
C
7.0"
FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector
Design Data
Supply AirFlow
Item TAG# TYPE Total Capacity (Tons) GPM ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty
(CFM)
1 FCU-01 TO 14 Chilled water FCU 2.5 6 1,050 50 1 G.F 230V-1Ph-60Hz 14
2 FCU-04 TO 02 Chilled water DWX12 2.01 1.45 4.9 886 50 2 M.F 230V-1Ph-60Hz 2
3 FCU-02 Chilled water DWX10 1.71 1.24 4.1 727 50 2 M.F 230V-1Ph-60Hz 1
4 FCU-05 Chilled water DWX06 1.00 0.74 2.4 421 50 1 G.F 230V-1Ph-60Hz 2
External
Air Flow Static Pressure Altitude
Input Conditions
Cooling Data
CFM Pa ft Capacity Dry Bulb Wet Bulb Flowrate Water Temp
Psychrometric Data
Entering (On Coil) Leaving (Off Coil)
Output Performance
dB 72 67 66 69 64 63 62
Products Certifications
of
GCC GULF
FCU-04 TO 02 2
GCC GULF
FCU-02 1
GCC GULF
FCU-05 2
DIMENSIONS
MODELS: DWX02 - DWX20
A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H
0.5"
2
E
B
6
1
1.0"
7
END VIEW TOP VIEW END VIEW
F 3.5"
3
G
C
7.0"
FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b FCU
Building-G1
(G1) -STAFF BUILDING
Design Data
Item TAG# TYPE Total Capacity (Tons) GPM Supply AirFlow (CFM) ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty
1 FCU-1 Chilled water DWX06 1.00 0.74 2.4 421 50 1 G.F 230V-1Ph-60Hz 2
2 FCU-2 Chilled water DWX12 2.01 1.45 4.9 886 50 2 M.F 230V-1Ph-60Hz 1
3 FCU-5 Chilled water DWX18 4.08 2.92 9.9 1,466 50 3 G.F 230V-1Ph-60Hz 4
GCC GULF
FCU-01 2
GCC GULF
FCU-02 1
GCC GULF
FCU-5 4
DIMENSIONS
MODELS: DWX02 - DWX20
A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H
0.5"
2
E
B
6
1
1.0"
7
END VIEW TOP VIEW END VIEW
F 3.5"
3
G
C
7.0"
FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector
Design Data
Item TAG# TYPE Total Capacity (Tons) GPM Supply AirFlow (CFM) ESP (Pa) Electric Heater (kW) FLOOR Power Supply Qty
2 FCU-4 Chilled water DWX18 4.08 2.92 9.9 1,466 50 3 G.F 230V-1Ph-60Hz 1
3 FCU-2 Chilled water DWX18 4.08 2.92 9.9 1,466 50 3 G.F 230V-1Ph-60Hz 2
GCC GULF
FCU-03 1
GCC GULF
FCU-4 1
GCC GULF
FCU-2 2
DIMENSIONS
MODELS: DWX02 - DWX20
A
4 3/4" NPT(14TPI)
I DRAIN TUBE.
5 H
0.5"
2
E
B
6
1
1.0"
7
END VIEW TOP VIEW END VIEW
F 3.5"
3
G
C
7.0"
FRONT VIEW
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector
1 D1-SU-01-1 TO 02 DX-High Wall Split MMZ36CH/MRZ36DGH 3 950 Heat Pump G.F Building-D1 2
2 D1-SU-02-1 TO 02 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-D1 2
3 D1-SU-03-1 TO 02 DX-High Wall Split MAZ12CH/MRZ12CD 1 415 Heat Pump G.F Building-D1 2
SPECIFICATIONS
INDOOR UNIT MAZ30CCXAD MAZ30CHXAD MMZ36CCXAD MMZ36CHXAD
MODEL NUMBER
OUTDOOR UNIT KRZ30CDACIAD KRZ30CDAHIAD MRZ36CDGCIAD MRZ36CDGHIAD
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 27000 / 24000 27000 / 24000 31400 / 26800 31400 / 26800
COOLING CAPACITY ( T1 & T3 ) watts 7900 / 7020 7900 / 7020 9202 / 7854 9202 / 7854
HEATING CAPAICTY watts -- 7,500 -- 9,000
POWER INPUT ( T1 & T3 ) watts 2195 / 2824 2195 / 2824 2614 / 3135 2614 / 3135
POWER INPUT ( Heating ) watts -- 2,150 -- 2,455
EER ( T1 & T3 ) Btuh/W 12.3 / 8.50 12.3 / 8.50 12.0 / 8.55 12.0 / 8.55
COP ( Heating ) W/W -- 3.49 -- 3.65
SEER Btuh/W 10.35 10.35 10.17 10.17
ANNUAL ENERGY CONSUMPTION kWh 9,200 9,200 10,469 10,469
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 850 / 790 / 640 / 550 850 / 790 / 640 / 550 950 / 850 / 750 950 / 850 / 750
SOUND PRESSURE LEVEL (1M) dBA 52 / 48 / 45 52 / 48 / 45 50.5/47.5/44.5 51 /48 / 45
BLOWER MOTOR FLA/POWER INPUT watts 0.4 / 89 0.4 / 89 0.35 / 73 0.35 / 73
COMPRESSOR RLA/LRA A 10.6 / 56 10.6 / 56 12.0 / 79 12.0 / 79
CONDENSER FAN MOTOR FLA/LRA A 0.87 / 200 0.87 / 200 0.70 / 150 0.70 / 150
COMPRESSOR TYPE ROTARY ROTARY ROTARY ROTARY
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 14.12 0.5 / 14.12 0.6 / 16 0.6 / 16
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 25 5 / 25 5 / 25 5 / 25
REFRIGERANT TYPE R410a R410a R410a R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 25 / 30 25 / 30 21.3 / 27.3 21.3 / 27.3
NET WEIGHT, KG
OUTDOOR UNIT kg 69 / 74 72 / 77 68.4 / 73 69.8 / 74.5
INDOOR UNIT mm 1259 X 282 X 362 1259 X 282 X 362 1350 X 272 X 365 1350 X 272 X 365
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 1000 X 390 X 860 1000 X 390 X 860 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ12CHX
MODEL NUMBER
OUTDOOR UNIT MRZ12CDGH
MODE OF OPERATION Cool only / Heal pump HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60
ENERGY CLASS ( SEER ) D
COOLING CAPACITY ( T1 & T3 ) Btuh 11800 / 10300
COOLING CAPACITY ( T1 & T3 ) watts 3458 / 3019
HEATING CAPAICTY watts 3,300
POWER INPUT ( T1 & T3 ) watts 951 / 1177
POWER INPUT ( Heating ) watts 916
EER ( T1 & T3 ) Btuh/W 12.4 / 8.75
COP ( Heating ) W/W 3.60
SEER Btuh/W 10.50
ANNUAL ENERGY CONSUMPTION kWh
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 415 / 365 / 315
SOUND PRESSURE LEVEL (1M) dBA 40.5 / 37 / 34.5
BLOWER MOTOR FLA/POWER INPUT watts 59
COMPRESSOR RLA/LRA A 4.75 / 27
CONDENSER FAN MOTOR FLA/LRA A 78
COMPRESSOR TYPE Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.3 / 6.39
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 15
REFRIGERANT TYPE R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 1/2, 5/8
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 20 / 8
INDOOR UNIT kg 11.6 / 14.9
NET WEIGHT, KG
OUTDOOR UNIT kg 33.8 / 36.5
INDOOR UNIT mm 965x215x319
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 805x330x554
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-D2
BUILDING - D2
SUMMARY SHEET - AC UNITS
1 D2-SU-01 DX-High Wall Split MMZ36CH/MRZ36DGH 3 950 Heat Pump G.F Building-D2 2
2 D2-SU-02 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-D2 2
3 D2-SU-03 DX-High Wall Split MAZ12CH/MRZ12CD 1 415 Heat Pump G.F Building-D2 2
SPECIFICATIONS
INDOOR UNIT MAZ30CCXAD MAZ30CHXAD MMZ36CCXAD MMZ36CHXAD
MODEL NUMBER
OUTDOOR UNIT KRZ30CDACIAD KRZ30CDAHIAD MRZ36CDGCIAD MRZ36CDGHIAD
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 27000 / 24000 27000 / 24000 31400 / 26800 31400 / 26800
COOLING CAPACITY ( T1 & T3 ) watts 7900 / 7020 7900 / 7020 9202 / 7854 9202 / 7854
HEATING CAPAICTY watts -- 7,500 -- 9,000
POWER INPUT ( T1 & T3 ) watts 2195 / 2824 2195 / 2824 2614 / 3135 2614 / 3135
POWER INPUT ( Heating ) watts -- 2,150 -- 2,455
EER ( T1 & T3 ) Btuh/W 12.3 / 8.50 12.3 / 8.50 12.0 / 8.55 12.0 / 8.55
COP ( Heating ) W/W -- 3.49 -- 3.65
SEER Btuh/W 10.35 10.35 10.17 10.17
ANNUAL ENERGY CONSUMPTION kWh 9,200 9,200 10,469 10,469
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 850 / 790 / 640 / 550 850 / 790 / 640 / 550 950 / 850 / 750 950 / 850 / 750
SOUND PRESSURE LEVEL (1M) dBA 52 / 48 / 45 52 / 48 / 45 50.5/47.5/44.5 51 /48 / 45
BLOWER MOTOR FLA/POWER INPUT watts 0.4 / 89 0.4 / 89 0.35 / 73 0.35 / 73
COMPRESSOR RLA/LRA A 10.6 / 56 10.6 / 56 12.0 / 79 12.0 / 79
CONDENSER FAN MOTOR FLA/LRA A 0.87 / 200 0.87 / 200 0.70 / 150 0.70 / 150
COMPRESSOR TYPE ROTARY ROTARY ROTARY ROTARY
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 14.12 0.5 / 14.12 0.6 / 16 0.6 / 16
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 25 5 / 25 5 / 25 5 / 25
REFRIGERANT TYPE R410a R410a R410a R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 25 / 30 25 / 30 21.3 / 27.3 21.3 / 27.3
NET WEIGHT, KG
OUTDOOR UNIT kg 69 / 74 72 / 77 68.4 / 73 69.8 / 74.5
INDOOR UNIT mm 1259 X 282 X 362 1259 X 282 X 362 1350 X 272 X 365 1350 X 272 X 365
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 1000 X 390 X 860 1000 X 390 X 860 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ12CHX
MODEL NUMBER
OUTDOOR UNIT MRZ12CDGH
MODE OF OPERATION Cool only / Heal pump HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60
ENERGY CLASS ( SEER ) D
COOLING CAPACITY ( T1 & T3 ) Btuh 11800 / 10300
COOLING CAPACITY ( T1 & T3 ) watts 3458 / 3019
HEATING CAPAICTY watts 3,300
POWER INPUT ( T1 & T3 ) watts 951 / 1177
POWER INPUT ( Heating ) watts 916
EER ( T1 & T3 ) Btuh/W 12.4 / 8.75
COP ( Heating ) W/W 3.60
SEER Btuh/W 10.50
ANNUAL ENERGY CONSUMPTION kWh
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 415 / 365 / 315
SOUND PRESSURE LEVEL (1M) dBA 40.5 / 37 / 34.5
BLOWER MOTOR FLA/POWER INPUT watts 59
COMPRESSOR RLA/LRA A 4.75 / 27
CONDENSER FAN MOTOR FLA/LRA A 78
COMPRESSOR TYPE Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.3 / 6.39
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 15
REFRIGERANT TYPE R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 1/2, 5/8
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 20 / 8
INDOOR UNIT kg 11.6 / 14.9
NET WEIGHT, KG
OUTDOOR UNIT kg 33.8 / 36.5
INDOOR UNIT mm 965x215x319
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 805x330x554
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-G2
Building (G2) - STAFF BREAK-21
SUMMARY SHEET - AC UNITS
1 G2-SU-01-1 TO 07 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-G02 7
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-I
BUILDING (I) - CAR PASSENGERS CHECKING & BREAK
SUMMARY SHEET - AC UNITS
1 I-SU-01-1 TO 04 DX-High Wall Split MAZ12CH/MRZ12CD 1 415 Heat Pump G.F Building-I 4
2 I-SU-02-1 TO 03 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-I 3
3 I-SU-03-01 TO 05 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-I 5
4 I-SU-05-1 TO 11 DX-High Wall Split MMZ36CH/MRZ36DGH 3 950 Heat Pump G.F Building-I 11
SPECIFICATIONS
INDOOR UNIT MAZ12CHX
MODEL NUMBER
OUTDOOR UNIT MRZ12CDGH
MODE OF OPERATION Cool only / Heal pump HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60
ENERGY CLASS ( SEER ) D
COOLING CAPACITY ( T1 & T3 ) Btuh 11800 / 10300
COOLING CAPACITY ( T1 & T3 ) watts 3458 / 3019
HEATING CAPAICTY watts 3,300
POWER INPUT ( T1 & T3 ) watts 951 / 1177
POWER INPUT ( Heating ) watts 916
EER ( T1 & T3 ) Btuh/W 12.4 / 8.75
COP ( Heating ) W/W 3.60
SEER Btuh/W 10.50
ANNUAL ENERGY CONSUMPTION kWh
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 415 / 365 / 315
SOUND PRESSURE LEVEL (1M) dBA 40.5 / 37 / 34.5
BLOWER MOTOR FLA/POWER INPUT watts 59
COMPRESSOR RLA/LRA A 4.75 / 27
CONDENSER FAN MOTOR FLA/LRA A 78
COMPRESSOR TYPE Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.3 / 6.39
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 15
REFRIGERANT TYPE R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 1/2, 5/8
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 20 / 8
INDOOR UNIT kg 11.6 / 14.9
NET WEIGHT, KG
OUTDOOR UNIT kg 33.8 / 36.5
INDOOR UNIT mm 965x215x319
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 805x330x554
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ30CCXAD MAZ30CHXAD MMZ36CCXAD MMZ36CHXAD
MODEL NUMBER
OUTDOOR UNIT KRZ30CDACIAD KRZ30CDAHIAD MRZ36CDGCIAD MRZ36CDGHIAD
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 27000 / 24000 27000 / 24000 31400 / 26800 31400 / 26800
COOLING CAPACITY ( T1 & T3 ) watts 7900 / 7020 7900 / 7020 9202 / 7854 9202 / 7854
HEATING CAPAICTY watts -- 7,500 -- 9,000
POWER INPUT ( T1 & T3 ) watts 2195 / 2824 2195 / 2824 2614 / 3135 2614 / 3135
POWER INPUT ( Heating ) watts -- 2,150 -- 2,455
EER ( T1 & T3 ) Btuh/W 12.3 / 8.50 12.3 / 8.50 12.0 / 8.55 12.0 / 8.55
COP ( Heating ) W/W -- 3.49 -- 3.65
SEER Btuh/W 10.35 10.35 10.17 10.17
ANNUAL ENERGY CONSUMPTION kWh 9,200 9,200 10,469 10,469
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 850 / 790 / 640 / 550 850 / 790 / 640 / 550 950 / 850 / 750 950 / 850 / 750
SOUND PRESSURE LEVEL (1M) dBA 52 / 48 / 45 52 / 48 / 45 50.5/47.5/44.5 51 /48 / 45
BLOWER MOTOR FLA/POWER INPUT watts 0.4 / 89 0.4 / 89 0.35 / 73 0.35 / 73
COMPRESSOR RLA/LRA A 10.6 / 56 10.6 / 56 12.0 / 79 12.0 / 79
CONDENSER FAN MOTOR FLA/LRA A 0.87 / 200 0.87 / 200 0.70 / 150 0.70 / 150
COMPRESSOR TYPE ROTARY ROTARY ROTARY ROTARY
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 14.12 0.5 / 14.12 0.6 / 16 0.6 / 16
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 25 5 / 25 5 / 25 5 / 25
REFRIGERANT TYPE R410a R410a R410a R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 25 / 30 25 / 30 21.3 / 27.3 21.3 / 27.3
NET WEIGHT, KG
OUTDOOR UNIT kg 69 / 74 72 / 77 68.4 / 73 69.8 / 74.5
INDOOR UNIT mm 1259 X 282 X 362 1259 X 282 X 362 1350 X 272 X 365 1350 X 272 X 365
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 1000 X 390 X 860 1000 X 390 X 860 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-K2
BUILDING (K2) - CAR CHECK BUILDING
SUMMARY SHEET - AC UNITS
1 K2-SU-02-01 TO 06 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-K2 6
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-K18
BUILDING (K18) - BUS WORKSHOP - INBOUND
SUMMARY SHEET - AC UNITS
1 K18-SU-01-01 TO 03 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-K18 3
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-K22
BUILDING (K22) - CAR WORKSHOP - OUTBOUND
SUMMARY SHEET - AC UNITS
1 K22-SU-02-01 TO 06 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-K22 6
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-H
BUILDING (K3) 09 - BUILDING
SUMMARY SHEET - AC UNITS
1 B09-SU-01-01 TO 09 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-K3 9
2 B09-SU-02-01 TO 03 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-K3 3
3 B09-SU-03-01 TO 04 DX-High Wall Split MAZ30CH/KRZ30CD 2.5 850 Heat Pump G.F Building-K3 4
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
SPECIFICATIONS
INDOOR UNIT MAZ30CCXAD MAZ30CHXAD MMZ36CCXAD MMZ36CHXAD
MODEL NUMBER
OUTDOOR UNIT KRZ30CDACIAD KRZ30CDAHIAD MRZ36CDGCIAD MRZ36CDGHIAD
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 27000 / 24000 27000 / 24000 31400 / 26800 31400 / 26800
COOLING CAPACITY ( T1 & T3 ) watts 7900 / 7020 7900 / 7020 9202 / 7854 9202 / 7854
HEATING CAPAICTY watts -- 7,500 -- 9,000
POWER INPUT ( T1 & T3 ) watts 2195 / 2824 2195 / 2824 2614 / 3135 2614 / 3135
POWER INPUT ( Heating ) watts -- 2,150 -- 2,455
EER ( T1 & T3 ) Btuh/W 12.3 / 8.50 12.3 / 8.50 12.0 / 8.55 12.0 / 8.55
COP ( Heating ) W/W -- 3.49 -- 3.65
SEER Btuh/W 10.35 10.35 10.17 10.17
ANNUAL ENERGY CONSUMPTION kWh 9,200 9,200 10,469 10,469
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 850 / 790 / 640 / 550 850 / 790 / 640 / 550 950 / 850 / 750 950 / 850 / 750
SOUND PRESSURE LEVEL (1M) dBA 52 / 48 / 45 52 / 48 / 45 50.5/47.5/44.5 51 /48 / 45
BLOWER MOTOR FLA/POWER INPUT watts 0.4 / 89 0.4 / 89 0.35 / 73 0.35 / 73
COMPRESSOR RLA/LRA A 10.6 / 56 10.6 / 56 12.0 / 79 12.0 / 79
CONDENSER FAN MOTOR FLA/LRA A 0.87 / 200 0.87 / 200 0.70 / 150 0.70 / 150
COMPRESSOR TYPE ROTARY ROTARY ROTARY ROTARY
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 14.12 0.5 / 14.12 0.6 / 16 0.6 / 16
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 25 5 / 25 5 / 25 5 / 25
REFRIGERANT TYPE R410a R410a R410a R410a
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 25 / 30 25 / 30 21.3 / 27.3 21.3 / 27.3
NET WEIGHT, KG
OUTDOOR UNIT kg 69 / 74 72 / 77 68.4 / 73 69.8 / 74.5
INDOOR UNIT mm 1259 X 282 X 362 1259 X 282 X 362 1350 X 272 X 365 1350 X 272 X 365
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 1000 X 390 X 860 1000 X 390 X 860 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-B04
BUILDING B04-EMPLOYEE'S ADMIN AND RECEPTION BUILDING
SUMMARY SHEET - AC UNITS
1 B04-SU-01-01 TO 04 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-B04 4
2 B04-SU-02-01 TO12 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-B04 12
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-DL
BUILDING DL-BUILDING OF CONFORMITY CABINET BUILDING
SUMMARY SHEET - AC UNITS
1 DL-SU-01-01 DX-High Wall Split MAZ24CH/MRZ24CD 2 735 Heat Pump G.F Building-DL 1
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
2.b Split
Building-GT
BUILDIONG (GT)-GATE BUILDING
SUMMARY SHEET - AC UNITS
1 GT-SU-01-01 DX-High Wall Split MAZ18CH/MRZ18CD 1.5 710 Heat Pump G.F Building-GT 1
SPECIFICATIONS
INDOOR UNIT MAZ18CCXAD2 MAZ18CHXAD1 MAZ24CCXAD1 MAZ24CHXAD1
MODEL NUMBER
OUTDOOR UNIT MRZ18CDGCIAD2 MRZ18CDGHIAD1 MRZ24CDGCIAD1 MRZ24CDGHIAD1
MODE OF OPERATION Cool only / Heal pump COOL ONLY HEAT PUMP COOL ONLY HEAT PUMP
POWER SUPPLY Volts-Ph-Hz 230-1-60 230-1-60 230-1-60 230-1-60
ENERGY CLASS ( SEER ) D D D D
COOLING CAPACITY ( T1 & T3 ) Btuh 18000 / 15500 18000 / 15900 22000 / 18200 22000 / 18400
COOLING CAPACITY ( T1 & T3 ) watts 5275 / 4542 5275 / 4660 6450 / 5334 6450 / 5393
HEATING CAPAICTY watts -- 5,100 -- 6,450
POWER INPUT ( T1 & T3 ) watts 1469 / 1802 1452 / 1797 1781 / 2128 1781 / 2114
POWER INPUT ( Heating ) watts -- 1,645 -- 1,792
EER ( T1 & T3 ) Btuh/W 12.25 / 8.6 12.40 / 8.85 12.35 / 8.55 12.35 / 8.70
COP ( Heating ) W/W -- 3.10 -- 3.60
SEER Btuh/W 10.34 10.54 10.37 10.51
ANNUAL ENERGY CONSUMPTION kWh 5,940 5,986 6,985 7,024
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 710 / 680 / 570 / 520 700 / 640 / 590 / 520 735 / 680 / 570 / 510 735 / 680 / 570 / 510
SOUND PRESSURE LEVEL (1M) dBA 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40 51/50 /45 /40
BLOWER MOTOR FLA/POWER INPUT watts 0.40 / 89 0.3 / 60 0.3 / 60 0.3 / 60
COMPRESSOR RLA/LRA A 6.6 / 40 6.6 / 40 8.25 / 50 8.25 / 50
CONDENSER FAN MOTOR FLA/LRA A 0.66 / 150 0.66 / 150 0.66 / 150 0.66 / 150
COMPRESSOR TYPE Rotary Rotary Rotary Rotary
MINIMUM CIRCUIT AMPACITY, AMPS (IDU/ODU) 0.5 / 9.33 0.5 / 9.33 0.5 / 17 0.5 / 17
MAXIMUM FUSE SIZE/CIRCUIT BREAKER, AMPS (IDU/ODU) 5 / 20 5 / 20 5 / 25 5 / 25
REFRIGERANT TYPE R410A R410A R410A R410A
LIQUID - SUCTION - DRAIN PIPE DIA., INCHES inch 1/4, 5/8, 3/4 1/4, 5/8, 3/4 3/8, 5/8, 3/4 3/8, 5/8, 3/4
MAX ALLOWED CONNECTION PIPE LENGTH ( Total / vertical ) meter 25 / 10 25 / 10 25 / 10 25 / 10
INDOOR UNIT kg 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1 15.3 / 19.1
NET WEIGHT, KG
OUTDOOR UNIT kg 43.7 / 47.1 49.2 / 52.5 60.9 / 65.5 62.5 / 67.3
INDOOR UNIT mm 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335 1080 X 226 X 335
DIMENSIONS (LxWxH), MM
OUTDOOR UNIT mm 890 X 342 X 673 890 X 342 X 673 946 X 410 X 810 946 X 410 X 810
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.
3. CERTIFICATES
3.a CHILLERS CERTIFICATES
Certificate of Product Ratings
AHRI Certified Reference Number : 10324726 Date : 12-11-2022 Model Status : Active
Ratings generated using the following shall be in accordance with the latest edition of ANSI/AHRI Standards 550/590 (I-P) with Addendum
3 and 551/591 (SI) with Addendum 3 for Performance Rating of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor
Compression Cycle and subject to rating accuracy by AHRI-sponsored, independent, third party testing.
Hertz : 60
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133152388953761644
Certificate
For
Energy Efficiency Label
Large AC Type Out Door Model Mark's Name License Number Cooling Capacity Power EER/SCOP
Chillers – air cooled ZAMIL AIR
ASC390B LAC051802943 4755000 445.9 10.65
CONDITIONERS
Issued to: Zamil Air Conditioners & Home Appliances Co. Ltd
PO BOX 14440
1ST INDUSTRIAL CITY
DAMMAM 31424 SAUDI ARABIA
This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.
Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20150430
Issue Date 2019-FEBRUARY-11
This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
ASY followed by 060 to 510 followed by B followed by H or M or F followed by xxxxxxx followed by ULh
ASY followed by 055 to 445 followed by B followed by L followed by xxxxxxx followed by ULh
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 2 of 2
3.b AHU CERTIFICATES
Certificate of Product Ratings
AHRI Certified Reference Number : 200096144 Date : 12-20-2022 Model Status : Active
Ratings generated using the following shall be in accordance with the latest editions of AHRI Standard 430 (I-P) and AHRI Standard 431
(SI) for Central Station Air-Handling Unit Supply Fans and subject to rating accuracy by AHRI-sponsored, independent, third party
testing.
Geometry : Airfoil/Backwards-Inclined
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160007333276033
Certificate of Product Ratings
AHRI Certified Reference Number : 200096122 Date : 01-16-2023 Model Status : Active
Ratings generated using the following shall be in accordance with the latest editions of AHRI Standard 430 (I-P) and AHRI Standard 431
(SI) for Central Station Air-Handling Unit Supply Fans and subject to rating accuracy by AHRI-sponsored, independent, third party
testing.
Geometry : Airfoil/Backwards-Inclined
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2023 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133183490167914406
Certificate of Product Ratings
AHRI Certified Reference Number : 200096112 Date : 12-20-2022 Model Status : Active
Ratings generated using the following shall be in accordance with the latest editions of AHRI Standard 430 (I-P) and AHRI Standard 431
(SI) for Central Station Air-Handling Unit Supply Fans and subject to rating accuracy by AHRI-sponsored, independent, third party
testing.
Geometry : Airfoil/Backwards-Inclined
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160007019364775
Certificate of Product Ratings
AHRI Certified Reference Number : 200096090 Date : 01-16-2023 Model Status : Active
Ratings generated using the following shall be in accordance with the latest editions of AHRI Standard 430 (I-P) and AHRI Standard 431
(SI) for Central Station Air-Handling Unit Supply Fans and subject to rating accuracy by AHRI-sponsored, independent, third party
testing.
Geometry : Airfoil/Backwards-Inclined
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2023 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133183490049943893
CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20140605
Issue Date 2019-FEBRUARY-11
Issued to: Zamil Air Conditioners & Home Appliances Co. Ltd
PO BOX 14440
1ST INDUSTRIAL CITY
DAMMAM 31424 SAUDI ARABIA
Standard(s) for Safety: UL1995/CSA C22.2 No. 236, Heating and Cooling
Equipment
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.
This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.
Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20140605
Issue Date 2019-FEBRUARY-11
This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 2 of 2
CERTIFICATE
N° 07.04.233
Air Handling Unit / Centrales de traitement d'air
Range Name / Nom de Gamme :
TW&TW(H)
Granted on April 27, 2007 - Date 1ère admission 27 avril 2007
This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com
Participant/Titulaire
This product performance certificate is issued by Ce certificat de performance produit est délivré par Eurovent
Eurovent Certita Certification according to the Certita Certification dans les conditions fixées par le
certification rules: référentiel :
ECP AHU - « Air Handling Unit » in force at ECP AHU – « Centrales de traitement d'air » en vigueur à
established date. date d’édition.
Pursuant to the decision notified by Eurovent Certita En vertu de la décision notifiée par Eurovent Certita
Certification, the right to use the mark ECP shall be Certification, le droit d'usage de la marque ECP, est accordé à
granted to the beneficiary company for the above Range la société qui en est bénéficiaire pour la gamme visée ci-
in the conditions defined by the certification program dessus, dans les conditions définies par le programme de
mentioned. certification mentionné.
Unless withdrawn or suspended, this certificate remains Sauf retrait ou suspension, ce certificat demeure valide tant
valid as long as the requirements for the certification que les conditions du référentiel du programme de certification
program framework are met. The validity of the sont respectées. La validité du certificat est à vérifier sur le site
certificate is to be verified on www.eurovent- Internet www.eurovent-certification.com
certification.com
CE CERTIFICAT A ÉTÉ EMIS LE 14/12/2021
THIS CERTIFICATE HAS BEEN ISSUED ON 14/12/2021 CE CERTIFICAT EST VALIDE JUSQU’AU 31/12/2022
THIS CERTIFICATE IS VALID UNTIL 31/12/2022
1/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06D06 TEMPLATE_ECP_RANGE_REV1.1
CERTIFICATE
N° 07.04.233
Appendix / Annexe
This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com
COOLINE
ZAMIL
This product performance certificate is valid for the following manufacturing places:
Ce certificat de performance produit est valide pour les sites de production suivants:
Manufacturing Place / Site de Production
Aircalc++ 3.8.32
2/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06D06 TEMPLATE_ECP_RANGE_REV1.1
3.c FCU CERTIFICATES
Certificate of Product Ratings
AHRI Certified Reference Number : 8075204 Date : 12-20-2022 Model Status : Active
Rated as follows in accordance with the latest edition of ANSI/AHRI 440 with Addendum 1: Performance Rating of Room Fan-Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160005382921012
Certificate of Product Ratings
AHRI Certified Reference Number : 8075205 Date : 12-20-2022 Model Status : Active
Rated as follows in accordance with the latest edition of ANSI/AHRI 440 with Addendum 1: Performance Rating of Room Fan-Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160005551047631
Certificate of Product Ratings
AHRI Certified Reference Number : 8075206 Date : 12-20-2022 Model Status : Active
Rated as follows in accordance with the latest edition of ANSI/AHRI 440 with Addendum 1: Performance Rating of Room Fan-Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160005641515683
Certificate of Product Ratings
AHRI Certified Reference Number : 8075207 Date : 12-20-2022 Model Status : Active
Rated as follows in accordance with the latest edition of ANSI/AHRI 440 with Addendum 1: Performance Rating of Room Fan-Coils and
subject to rating accuracy by AHRI-sponsored, independent, third party testing:
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
†
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
©2022 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 133160006044803749
CERTIFICATE OF COMPLIANCE
Certificate Number 20190211-SA13167
Report Reference SA13167-20140909
Issue Date 2019-FEBRUARY-11
Issued to: Zamil Air Conditioners & Home Appliances Co. Ltd
PO BOX 14440
1ST INDUSTRIAL CITY
DAMMAM 31424 SAUDI ARABIA
Standard(s) for Safety: UL1995/CSA C22.2 No. 236, Heating and Cooling
Equipment
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.
This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.
Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 1
3.d SPLIT CERTIFICATES
Certificate
For
Energy Efficiency Label
Device Type Model's number Brand name SEER value Class Licence number
Device Type Model's number Brand name SEER value Class Licence number
Device Type Model's number Brand name SEER value Class Licence number
Device Type Model's number Brand name SEER value Class Licence number