0% found this document useful (0 votes)
197 views

C-051-080-SPC-0004 - c1 - Specification For Fire and Gas Detectors Rev. 003

Uploaded by

MGHIRBI HAYKEL
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
197 views

C-051-080-SPC-0004 - c1 - Specification For Fire and Gas Detectors Rev. 003

Uploaded by

MGHIRBI HAYKEL
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

SUPPLIER DOCUMENT FRONT SHEET

Supplier Name: PETROJET

Equipment Tag
No(s):

Supplier Supplier Document


C-051-080-SPC-0004 1
Document No.: Revision No.:

Document Title: Specification for Fire and Gas Detectors

COMPANY Document Number

Purchase Order/ Contract Number SDDRL Code Sequence No. Sheet No.

Alternative Document Number (if applicable):

2015-C-051-0000-DG10-SPC-0005

Rev Description Date Orig Chk’d App’d

001 Issued for Review/ Comments 21.07.15 VMK HVS JSD/PTJ


002 Issued for Review/ Comments 08.09.15 NVP HVS JSD/PTJ
003 Issued for Review/ Comments 30.09.15 NVP HVS JSD/PTJ

Review of Supplier document

Code Description of Code Signature Date

1 Reviewed – no comment.

Revise and re-submit. Work may proceed subject


2
to incorporation of comments.

3 Revise and re-submit. Work shall NOT proceed.

4 Review not required – for information only. By sinol.dsouza at 4:44:19 PM, 10/1/2015

M0015K-0000-CD10-FRM-0001 Page 1 of 1
SIBA Field Development Project

Client:
Kuwait Energy,
P.O.Box. 5614, Salmiya, Kuwait

PMC:
Touchstone.
P.O.Box. 72129, Sharjah, UAE

EPC Contractor: Engineering Consultant


PETROJET Mott MacDonald
P.O. Box. 2048,Horreya-Heliopolice
Cairo, EGY

Project Title:
SIBA FIELD DEVELOPMENT PROJECT
Contract No:
KEIL/SIBA/2015/C-051-REV-CPF EPC

Document Title:

Specification For Fire And Gas Detectors

Re-Issued for
1 27.09.15 NVP HVS JSD WME
Implementation
Prepared Checked Approved Approved
Rev. Date Rev. Description PMC Rep. Client Rep.
By By By PTJ

Document No: C-051-080-SPC-0004

Format Pages

A4 1 Of 33

Page 1 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 2 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

Amendment Summary

Revision No Date Description

ZZ 12-July-2015 Issued for IDC / IFR

A 19-July-2015 Issued for Review / Comments

0 07-Sep-2015 Issued for Implementation

1 27-Sep-2015 Re-Issued for Implementation

Disclaimer:- “This document is issued for the party which commissioned it and for specific purposes connected with the captioned project only. It
should not be relied upon by any other party or used for any other purpose.
We accept no responsibility for the consequences of this document being relied upon by any other party, or being used for any other purpose, or
containing any error or omission which is due to an error or omission in data supplied to us by other parties.”

Page2 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 3 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

TABLE OF CONTENTS

1. Introduction ................................................................................ 6
2. Scope .......................................................................................... 8
3. Definitions ................................................................................... 9
4. Abbreviations ............................................................................ 10
5. Standards and Specifications .................................................. 12
5.1 Document Reference ......................................................................... 12
5.2 National and International Codes and Standards............................ 12
6. Reference .................................................................................. 15
6.1 Order of Precedence .......................................................................... 15
7. Units of Measurement .............................................................. 16
8. Environmental Condition .......................................................... 17
9. Area Classification ................................................................... 18
10. EMC Compliance ....................................................................... 19
11. Fire and Gas Detectors – Technical Requirements................. 20
11.1 General ................................................................................................ 20
11.2 Flame Detector – UV/IR / Triple IR Type ........................................... 21
11.3 Deleted. ............................................................................................... 21
11.4 Flammable Gas Detector – Point Type ............................................. 21
11.5 Flammable Gas Detector – Open path Type .................................... 22
11.6 Toxic (H2S) Gas Detector .................................................................. 23
11.7 Hydrogen (H2) Detector ..................................................................... 23
11.8 Deleted ................................................................................................ 24
11.9 Linear Heat Detector / Heat Sensing Wire loop / Fire wire.............. 24
11.10 Deleted ................................................................................................ 25
11.11 Manual Call Point ............................................................................... 25
11.12 Alarms and Notification Devices ...................................................... 25
11.13 Addressable Detectors ...................................................................... 27
11.14 Air Sampling Detection System (ASDS) ........................................... 28
11.15 Building Fire Alarm Control Panel (FACP) ....................................... 29
Page 3 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 4 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

11.16 Name Plates ........................................................................................ 29


12. Inspection and Testing ............................................................. 31
13. Special Parts and Special Tools .............................................. 32
14. Spares ....................................................................................... 33
15. Painting and Coating ................................................................ 34
16. Documentation ......................................................................... 35

Page 4 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 5 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

List of Figures
Figure 1-1 – Siba Field Location ................................................................................... 6

Figure 1-2 – Google Map for CPF and Possible Export Pipeline Route ......................... 7

Page 5 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 6 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

1. Introduction
The SIBA gas field was discovered in 1969 and is located in Southern Iraq, in the Basra
Governorate, some 30 km southeast of Basra City extending east to the Shatt Al-Arab River as
illustrated in Figure1-1.
Kuwait Energy Iraq Limited (KEIL), a wholly owned subsidiary of Kuwait Energy Plc, in partnership
with Turkish Petroleum (TPAO) and Missan Oil COMPANY signed with South Oil COMPANY
(SOC) in Iraq a Gas Development and Production Service Contract (GDPSC) for the Siba Field.
KEIL has been appointed the Operator for the field.
The Siba Field will be developed to produce 100 mmscfd of sales gas (annual average) as per the
terms within the GDPSC. The field is virgin land at this point in time, located in Basra, Governorate
of Iraq.

Figure 1-1 – Siba Field Location

Page 6 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 7 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

Figure 1-2–Google Map for CPF and Possible Export Pipeline Route

KEIL is committed to developing the Siba field in a staged manner, with an initial Early Production
Facility (EPF) subsequently expanded to a higher capacity Full Production Facility (FPF). The EPF
shall comprise of:

x Installation of gathering system to tie-in the available production wells.


x Installation of the EPF gas process plant (minimum capacity 55 mmscfd).
x Installation of export pipeline system for sales gas, LPG and condensate.
x Second stage development of the facilities, expansion to the FPF, will include:
x Installation of the remainder of the gathering system to connect all new, existing and future
wells to the Central Processing Facilities (CPF).
x Installation of the remainder of the gas processing facilities at the CPF to meet the
commitments specified within the GDPSC.

Page 7 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 8 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

2. Scope
This document describes the minimum requirement for the specification of Fire and Gas Detectors
to be installed at Siba Gas Plant Central Processing Facilities (CPF) and associated facilities.
The Devices Controlling/Monitoring other Services are not covered in this documents.

Page 8 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 9 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

3. Definitions
CLIENT/COMPANY Kuwait Energy Iraq Limited (KEIL)
CONTRACTOR The Petroleum Project & Technical Consultation Co. - Petrojet
PMC Touchstone LLC
CONSULTANT Mott MacDonald Pvt. Ltd.
SUPPLIER/VENDOR The party(s) which carry out all or part of the design, procurement,
installation support and testing of the equipment as specified by the
CONTRACTOR.
MAY Alternatives are equally acceptable
SHOULD Preferred or recommended
SHALL Provision is mandatory or is a statutory requirement
MUST Provision is deemed essential

Page 9 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 10 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

4. Abbreviations

ATEX Atmosphere Explosive

ASDS Air Sampling Detection System

BOPD Barrels of Oil Per Day

BS British Standard

BWPD Barrels of Water Per Day

CCR Central Control Room

CPF Central Processing Facility

EMI Electro Magnetic Interference

EPC Engineering, Procurement, Construction

EPF Early Production Facility

F&G Fire and Gas

FAP Fire Alarm Panel

FM Factory Mutual

FPF Full Production Facility

HVAC Heating, Ventilating and Air-Conditioning

IP Ingress Protection

IR Infrared

ISO International Standards Organization

KEIL Kuwait Energy Iraq Limited

LEL Lower Explosive Limit

LPG Liquefied Petroleum Gas

MCP Manual Call Point

NFPA National Fire Protection Association

OEM Original Equipment Manufacturer

RFI Radio Frequency Interference

Page 10 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 11 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

RHO Radiant Heat Output

SPIR Spare Parts Interchangeability Records

UL Underwriters Laboratories

Page 11 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 12 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

5. Standards and Specifications


The design and application of all Fire and Gas detectors shall comply with the latest revision of the
following codes, standard, and reference.

5.1 Document Reference


Refer Material Requisition relevant appendices for various discipline related project documents
and drawings.

5.2 National and International Codes and Standards


The following standards shall be considered in the design of the Gas Plant as applicable:

ATEX 94/9/EC Equipment and Protective Systems intended for


use in Potentially Explosive Atmospheres.

ATEX 99/92/EC Safety of Installation.

BS5839 Part 1 Fire detection and fire alarm systems for buildings

BS 5308 Instrument Cables

BS 6020 Part 1 & 4 Instruments for the detection of combustible


gases

EN 10204 Metallic Products Type of Inspection Documents

IEC 60079 Electrical Apparatus for Potentially Explosive


Atmospheres.

IEC 60079-1 Electrical Apparatus for Explosive Gas


Atmospheres Pt 1: Construction And Verification
Test of Flameproof Enclosures of Electrical
Apparatus

IEC 60079-11 Electrical Apparatus for Explosive Gas


Atmospheres, Part 11:
Construction and Test of Intrinsically Safe and
Associated Apparatus.

IEC 60079-14 Electrical Apparatus for Explosive Gas


Atmospheres. Electrical installations in hazardous
areas.

Page 12 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 13 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

IEC 60079-7 Electrical Apparatus for Explosive Gas


Atmospheres, Part 7: Increased Safety “e”.

IEC 60331 Test for Electric and Optical Fiber Cables Under
Fire Conditions – Circuit Integrity

IEC 60529 Classification for degree of protection provided by


enclosures. (IP rating)

IEC 60534.4 Inspection and routine testing.

IEC 61000 Electro Magnetic Compatibility

ISO 10474 Materials Traceability & Inspection

ISO 9000 Quality Management and Quality Assurance


Standards

NACE MR-0175/ISO Sulphide stress cracking resistant metallic


15156 materials for oil field equipment.

NFPA 72 National Fire Alarm and Signalling Code from


National Fire Protection Association

NFPA 12 Standards on Carbon Dioxide Extinguishing


Systems

NFPA 2001 Standard for Clean Agent Fire Extinguishing


Systems

BS EN54 Part-1-12 Fire detection and fire alarm systems in and


around buildings.

IEC-61511 Safety Instrumented Systems for the Process


Industry

NFPA 329 Recommended Practice for Handling Releases of


Flammable and Combustible Liquids and Gases

NFPA 75 Protection of Electronic/Computer Data


Processing Equipment

UL 268 Smoke Detectors For Fire Protective System.

Page 13 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 14 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

UL 521 Heat Detectors For Fire Protective System.

Page 14 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 15 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

6. Reference
6.1 Order of Precedence
In case of any conflict between this specification, related data sheets and diagrams, codes and
standards and any other specifications noted herein, the most stringent of the requirements shall
govern. The SUPPLIER or CONTRACTOR shall refer any such conflict and any other matter,
which requires further interpretation to the attention of COMPANY, and COMPANY representative
interpretation, shall be final.
The following is the order of precedence for Requisition, Specifications and Codes:

x Requisition, purchase order or change order


x This document
x Relevant project documents
x Referenced international codes and standards

Page 15 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 16 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

7. Units of Measurement
Units of Measurement shall be SI system unless otherwise stated in the datasheets with the
following few exceptions:

x Gas flow MMscfd


x Oil flow STBOPD
x Pressure bar g
x Valve and Pipe size inches (Nominal Bore)

Page 16 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 17 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

8. Environmental Condition
Instrumentation shall be designed to be located outdoors under direct sunlight.
The atmosphere is extreme harsh desert environment with air borne fine penetrating dust and
sand. Traces of sour gas (H2S, SO2) will be present in the air. All electronic boards and
component shall be designed to withstand such an environment.

Page 17 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 18 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

9. Area Classification
Siba Gas Plant hazardous area classification shall be Zone 2, Gas Group IIA, T3. However all field
instruments associated with F&G detection/control shall be rated for Zone1, Gas Group IIA, IIB
temperature Class T3 as a minimum.

Page 18 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 19 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

10. EMC Compliance


The design and installation of all electrical and electronic equipment shall meet the radio frequency
interference (RFI) or electromagnetic interference (EMI)(IEC61000), emission (IEC61000 6-4) and
immunity (IEC61000 6-2) requirements for an industrial environment.

Page 19 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 20 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

11. Fire and Gas Detectors – Technical Requirements


11.1 General
The early detection of a developing fire or gas release, and an early warning to operations and fire-
fighting personnel form an important aspect in the basic concept of fire and gas detection.
All F&G detectors to be supplied shall be suitable for operating at 24 VDC.
All field detectors, both indoor and outdoor shall be weatherproof to IP65 (minimum) in accordance
with IEC 60529. Detectors for indoor safe area use may be general purpose and addressable type.
The field Fire and Gas detectors shall preferably be SMART type field devices suitable for
interfacing with the F&G safeguarding system (part of ICSS) and should have local LCD/LED
indication, where practical. All electronic components and associated assemblies shall be
tropicalized.
The detectors shall be fast, reliable and designed to meet the functionality and safety requirements
they intend to carry out. Speed of response and accuracy shall be taken into consideration during
detailed design by CONTRACTOR.
General purpose indoor addressable detectors, which are not normally visible, as in ceiling void or
under floor, shall provide an output to an LED located within the room being covered. This LED will
light when the associated detector is in alarm.
Sensors and enclosure material shall be corrosion resistant, suitable for site environmental
conditions. Field detectors shall be weatherproof, designed to meet the conditions as stated in
project specifications. Field detectors and enclosure material shall be 316SS and ATEX rated
EEx’d’ for hazardous area Zone 1, Gr. IIA/IIB, Temperature class T3. Field F&G detectors shall be
SIL-2 certified.
Analogue detector shall have 0–20 mA current output (sink or source configurable, or option).
Required output modes shall be in accordance with the following table:

Current Signal
(mA) meaning

0 Common
fault

2 Optical
fault

4 No gas

20 Full scale
deflection

Page 20 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 21 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

All devices shall be supplied with a termination box with fixed screw type electrical connectors
(flying leads are not acceptable). Cable entries shall be M20 x 1.5mm ISO and shall be provided
with cable glands.
The SUPPLIER shall submit the following information:

x Power supply consumption (@ 24VDC).

x Maximum allowable distance between transmitter and F&G system panel according to
cable core section.

x Calibration requirements (schedule, detailed calibration procedure)


Detector shall be UL listed or FM Approved.
Detectors shall comply with NFPA 72.

11.2 Flame Detector – UV/IR / Triple IR Type


Triple Infrared (IR) shall be single frequency detectors that respond to infrared radiation equivalent
to the CO2 band.
For general use, equipment shall detect a fire of 10 kW radiant heat output (RHO) at 10 m (33 ft).
Response time shall be less than 10 seconds.
Detectors shall allow easy horizontal and vertical adjustment of ±π/4 radians (45 degrees).
Detectors shall lock in the desired position.
System shall contain diagnostics for checking that the detector is online.
Detectors or interface units shall have volt-free relay contacts for alarm and fault. Detectors shall
have 4 – 20 mA output with diagnostic capability.
A fire alarm simulation test source that can be used a minimum of 5 m (16 ft) from the detector
should be provided.
Detectors shall have at least a π/2 radian (90 degree) field of view in the horizontal axis.
Detector shall have range to detect fire of Methane 30 inch plume (0.8 m) from distance of 50 ft
(15 mtr). With the approval of the COMPANY/Contractor, longer distance detector may be
deployed.
Solar interference (sunlight), artificial lighting, or regularly modulated black body radiation shall not
cause false alarms.

11.3 Deleted
11.4 Flammable Gas Detector – Point Type
Flammable gas detectors should be Infrared point source type.
The time of response for the point type flammable gas detectors shall be as below

x t50 shall not be greater than 10secs for general application.

x t90 shall not be greater than 30secs for general application.


Page 21 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 22 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

x Less than 2 seconds for HVAC duct applications or any fast response applications.
Flammable Gas detectors shall be calibrated to provide two alarm signals considering the high
level at 20% LEL and High-High level at 50% LEL and for Flammable gas detectors at HVAC inlet
the set point shall be 15% LEL and 25%
Sensor life shall not be less than 3 years.
Detector and supporting electronic equipment shall detect and communicate any failure that might
prevent a response to hydrocarbon gas. Undetected failures in ability to respond correctly to
hazards are not acceptable.
Detectors shall have serial communication capability (or equivalent) for use with interrogation tools
or connection to smart control equipment.
Detectors shall have a full range of available accessories for commissioning and operational
activities such as Duct mounting kit, Field calibration and testing kit, Remote gas sampling
accessories and Weather protection/ splash guard.
The standard sensitivity range of the detector shall be 0–100% LEL.
Detector shall be calibrated so that it will never underestimate the flammability of any gas
compositions that it may see in the area it is installed. Detector shall be factory calibrated and shall
not be recalibrated in the field.
Detector shall not produce an alarm indication greater than 10% LEL in response to water or water
vapour in the optical path. Fouling of optical surfaces by common contaminants found in the area
of installation shall not cause unwanted alarms. Substantial fouling shall be communicated as an
optical fault. Optical test filters shall be provided to test function and accuracy of the detector. If
this is not available, calibration gas may be used.

11.5 Flammable Gas Detector – Open path Type


For open areas, open path gas detectors shall be the split transmitter and receiver type. Detectors
with combined transmitter/receivers using a reflector panel shall not be used.
Transmitters and receivers shall allow easy horizontal and vertical adjustment of ±π/4 radians
(45 degrees).
Transmitters and receivers shall lock in the desired position.
The system should be tolerant of misalignment of either or both the transmitter and the receiver of
4, 4E–3 radians (0, 25 degrees) without any effect on system operation.

Detector selection should be based on the Lower Explosive Limit (LEL) of the predominant
stream components to provide the earliest detector response considering high alarm at 1
LEL.m and High-High Alarm at 2.5 LEL.m.
Detector shall be calibrated so that the flammability of any gas compositions for the area where it
is installed shall not be underestimated.
System shall contain diagnostics for the following conditions:

x Improperly installed equipment shall be detected. Detection of either excess path length or
misalignment shall prevent equipment from going operational.
Page 22 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 23 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

x After initial setup, significant reduction in signal for more than 60 seconds shall
automatically indicate an optical fault.

x If system is in optical fault condition, gas shall be detectable without underestimation of


flammability.

x Reduction of signal strength to less than 5% of the initial setup value for more than 1 hour
detector shall indicate a common fault.
Solar interference (sunlight) shall not cause false alarms.
Detector shall not produce an alarm indication greater than 0,5 LEL in response to any
combination of obstructions, vibration, or external sources of infrared radiation (including solar and
hydrocarbon flare radiation) in the beam.
Fouling of optical surfaces by the common contaminants found in the area of installation shall not
cause unwanted alarms.
Substantial fouling shall be communicated as an optical fault.
Optical test filters to test function and accuracy of the detector shall be provided.
Using calibration gas to test these detectors is unacceptable due to the large volume of gas that
would need to be released into the optical path. OEM calibration test kit IR films set shall be
provided for field testing. Transmitter-Receiver alignment kit shall be provided.
Siting distance for open path detectors is up to 60 m (200 ft) for SIBA facilities. With the approval
of the COMPANY/Contractor, longer path-lengths may be deployed.

11.6 Toxic (H2S) Gas Detector


H2S detector shall be Electro-chemical point type. Metal Oxide Semi-conductor (MoS) or Catalytic
Type can be used as alternate subject to approval from EPC Contractor/COMPANY.
The sensitivity range of the detector should be from zero to no more than twice the Threshold Limit
Value (TLV) for the target gas. TLV for H2S should be 10 ppm. Short Term Exposure Limit (STEL)
is 15 ppm.
Detectors shall have a full range of available accessories for commissioning and operational
activities such as Duct mounting kit, Field calibration and testing kit, Remote gas sampling
accessories and Weather protection/ splash guard.
Detectors should be supplied with suitable calibration gas for site calibration.System shall contain
diagnostics for checking that the detector is online.
Sensor life shall not be less than 3 years
Gas detectors shall be calibrated to provide two alarm signals high level as 10 ppm and High-High
level at 15ppm.

11.7 Hydrogen (H2) Detector


Hydrogen gas detectors are required to detect flammable H2 Gas leaks from the batteries in the
Battery room.

Page 23 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 24 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

The Hydrogen gas detector shall be Electro-chemical point type (Catalytic typeshall not be
employed except in specific circumstances from approval by EPC CONTRACTOR/COMPANY).
Hydrogen gas detector shall be microprocessor based smart intelligent type with local read out.
The transmitter shall operate on 24V DC loop power supply and output shall be 4-20mA with
HART protocol. Hydrogen gas detector shall remain fully functional with a power supply between
18V DC to 30V DC.
Hydrogen gas detector and transmitter shall be EEx’d’ certified and shall be suitable for Zone 1,
Gas group IIC, T3 class area.
Hydrogen gas detector shall be calibrated and designed to operate from 0 – 100 % LEL,however
High level alarm limit shall be 10% LEL and High-High level alarm shall be 25% LEL.
The detector shall have a pre-warning feature that identifies the need for maintenance whilst
remaining full functional. This feature removes the need for routine maintenance.
The following shall be alarm settings:
Low Alarm – 10% LEL
High Alarm – 25% LEL
SUPPLIER shall advise the long term stability for zero and span.

11.8 Deleted
11.9 Linear Heat Detector / Heat Sensing Wire loop/Fire wire
The fire wire shall be a twin conductor cable with a temperature sensitive insulation protected by a
polythene braid outer sheath to meet the specific application requirements. Colour of outer sheath
shall be Red with Black ID tracer.
The fire wire shall fuse at a temperature range of 79 to 90 Deg C, following the concept of point of
risk detection. Each conductor shall be made of tinned copper – covered steel with a conductor
diameter of 0.9 mm.
The operating principle shall be such that in the case of a fire or acceptable operating temperature
levels are exceeded, the temperature sensitive insulation shall melt at 80 Deg C and short circuit
the twin conductors, to provide an instantaneous and reliable signal to the Fire and Gas System.
The fire wire shall be continuously monitored by the input card in Fire and Gas System so as to
detect open circuit and short circuit conditions. The necessary resistors for line monitoring shall be
supplied by SUPPLIER.The outer jacket shall be made of material to resist corrosion, chemicals,
moisture etc.
The heat detection cable shall be capable of returningto normal operating mode following an alarm
condition without the necessity ofreplacement.
In the event of cable being damaged by exposure to overheat, the cable shall be capable
ofreplacement of only damaged section

Page 24 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 25 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

11.10 Deleted
11.11 Manual Call Points
Addressable Manual Call Points
Manual call points at entry/exit of buildings in safe area shall be Addressable type looped with
Addressable Fire Alarm Control Panel of the building.
Manual call point shall be of lift flap “break glass” double action type. Lift flap is used for extra
protection against inadvertent operation. It shall have Key operated test facility.
The alarm contacts shall be opened under normal standby conditions, closing on alarm and come
complete with end of line resistors.
All units shall be surface mounted and tamper proof.
Colour shall be signal Red (or equal).
They shall be provided with a scoured glass and protective anti-splinter film. A means shall be
provided to test the call point without removing the cover.
Each break glass unit shall be clearly identified by a traffolyte label firmly attached. It shall have
the instrument tag number and the word FIRE, in white letters on red.
Field Manual Call Points
Manual Call points in process area and field shall be Non-addressable type connected with F&G
system.
Manual call points shall be of the break-glass, auto-release type.
The complete housing of manual call points installed outdoors shall be constructed in accordance
with requirements for the classified hazardous areas, shall be corrosion-resistant and fully
weather-proofed. For identification, they shall be coloured signal red to DIN Standard RAL 3000 or
equivalent.

11.12 Alarms and Notification Devices


The audio and visual alarm devices shall be addressable type when connected with building fire
alarm control panel.
Non-addressable audio and visual alarm devices installed outdoors shall be constructed in
accordance with requirements for the classified hazardous area, shall be corrosion-resistant and
fully weather-proofed.
The audio and visual alarm shall be compatible with fire and gas system panels from which it is
connected to have automatic initiation from the panel.
Local audible and visual alarms shall be provided within buildings and outside at the top
ofbuildings and at strategic locations of CPF areas to ensure that thealarms are audible at all
points in the facility.

Page 25 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 26 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

All audible and visual alarms for fire and gas system shall be distinguishable from audible and
visual alarms used for other purposes. The audiosignal shall be of different tones, as mentioned
below for fire, flammable gas, toxic (H2S) gas alarms.

x Tone 1 on fire detection

x Tone 2 on flammable gas detection

x Tone 3 on Toxic gas detection (H2S)


A manual operation should be required to silence the alarm. The alarm shall not beautomatically
silenced or cancelled.
Warning flashing fire alarm beacons provided for high noise level areas to compliment theaudio
alarm shall be complete with xenon strobe light and totally enclosed solid state circuitry
The colour of the transmitted light, power output and operation shall be such that it isclearly visible
from all areas it covers and readily discernible against artificial lighting andsunlight.
Visual alarms/beacons shall be capable of continuous operations without adverse effectsand shall
be colour as follows:

x Fire detection – Red;

x Combustible gas detection – Blue;

x Toxic Gas Detection– Amber (or Yellow beacon)


All audible and visual alarms to be installed in hazardous areas will be certified for use inthose
areas.
Emergency evacuation alarm (ESD-0) shall be completely separated from the fire and gas
alarmsand it is a separate facility interfaced to ESD system. A pushbutton (location shall be
finalised in consultation with COMPANY) shall be provided to actuate emergency evacuation
sirens andstrobe lights located strategically throughout the plant.
The F&G System shall be compatible with the PAGA system. An interface shall be
providedbetween the systems for operational coordination purpose. Alarms shall be
generatedeither manually from any one of the dedicated access panels or automatically from F&G
or Emergency Shutdown (ESD) System via dedicatedhardwired interfaces between the systems
for Public Address System.
The alarms and announcements of PAGA shall be individually configurable to differentvolume
levels to allow for clearly audible emergency broadcasts. An alarm in progress shallbe possible to
be attenuated or fully muted, while an emergency broadcast is made and isthen increased back to
its original level afterwards for Public Address System.This alarm control interface shall not be
permitted to turn off audible and visible notificationappliances for special suppression system (sect.
24.4.2. 25.1.3 of NFPA 72).
Plant Siren shall be provided in the CPF which shall be activated either manually or automatically
from the F&G system in case of major fire. It should have distinct tones for Fire, Flammable and
Toxic Gas.

11.12.1 Sounders

Page 26 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 27 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

Sounders for Gas Alarm:


Normally detection of gas (both toxic and flammable) shall be announced by audible means in
buildings and the Plant area (Field) using sounders.
The sounders' shall be by means of an on/off modulating tone, 4 seconds on and 4 seconds off, at
a frequency of 1000 Hz.
The sounders for the 'All Clear' shall be by means of a continuous tone, at a frequency of 1000 Hz.
Alarm sounders shall be of the electronic type, with an IP 65 rating and shall be certified for use in
the applicable hazardous area.
The sounders shall be supplied with 24V DC from the F&G safeguarding system.
The sounders shall operate a sound level of at least 110 dBA within a frequency range of 500-
1000Hz at a radius of one metre with in-built control to adjust the volume and facility to select the
tones.
The sounders for indoor requirements shall be generally as for outdoor but with a sound level of
85dBA (adjustable) and shall meet environmental requirements.
Sounders for Fire Alarm:
Fire detection shall be announced using sounders in outside locations. The sounders shall be
similar to those used for the gas alarm but shall operate in a continuous mode as opposed to the
on/off modulating mode for the gas alarm.

11.12.2 Beacons
The beacons consisting of a flashing beacon shall be installed to give warning of fire or gas
release.
The beacons shall be located so that they shall be visible in the area for which they are to provide
a warning and are accessible for maintenance.
The beacon shall have a flashing frequency of 60 flashes per minute. The effective luminous
intensity shall be 300 candela (cd) minimum. Lamp shall be Xenon -discharge type. The dome for
flash tube on the flashing beacons shall be made up of transparent toughened glass. A lens guard
/ cage shall also be provided for all the beacons.
The visual alarm shall be suitable for surface mounting on either walls or poles as required and
shall be readily visible under all probable lighting conditions.

11.13 Addressable Detectors


11.13.1 Heat Detector
The Heat Detectors shall be rate of rise temperature/rate compensated/fixed temperature type.
When heat detectors are installed indoors,they shall operate on the non fail-safe close to alarm
principle and come complete with end of line resistors. They shall be monitored by the building fire
alarm system for detector alarm and fault, and cable open and short circuit.

Page 27 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 28 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

Combination Detectors (Heat/Smoke) shall be used in kitchen areas, to detect heat during the day
and smoke during the night.

11.13.2 Smoke Detector – point type


Smoke detectors shall be addressable ionization type. Optical detectors shall also be considered
for non-process buildings for e.g. Substation/Equipment room.
Smoke detectors shall be equipped with lock-on base and integrated alarm light.
Detectors, which are not normally visible, as in ceiling void or under floor, shall provide an output
to an LED located within the room being covered. This LED will light when the associated detector
is in alarm.
Response time shall be 1 second for sensitive part response, with additional time delay (field
adjustable) against spurious detection (require field adjustable sensitivity).

11.13.3 Smoke Detector – beam type


Optical Beam Smoke Detectors shall be used to provide “wide area” smoke detection.
The Optical Beam Smoke Detector works on the principle of light obscuration.
The photosensitive element of the Optical Beam Smoke Detector sees light produced by the
Transmitter in a normal condition. The Receiver is calibrated to a preset sensitivity level based on
a percentage of total obscuration.
There are two general types of Optical Beam Smoke Detector - Projected and Reflective. The type
used will be dictated by the installation and environment conditions and constraints.

11.14 Air Sampling Detection System (ASDS)


The ASDsystem shall be used for smoke and combustion products detection using aspiration
method of sample handling.ASDS shall monitor the inside of each electrical equipment cabinet that
houses active electronic/electrical components and wire ways under raised floors.
The ASD system shall employ digital microprocessor based electronics to sequence, process,
execute logic from inputs and generate the desired outputs. All ASDS units supplied shall be low
power consumption type. Output signals shall be volt free contacts fitted with end of line resistors.
Separate contacts shall be available for two smoke level alarm points per sample line tested. Each
alarm point shall be fully configurable to any value within the obscuration range, and hardwired
directly to the building Fire alarm panel.
In addition to smoke alarm outputs, each ASDS unit shall be provided with a system status alarm
contact.
ASD system shall be powered with 24V DC power. The SUPPLIER shall provide supplies with the
system. ASD system shall be hardwired to building fire alarm system as part of their addressable
loop for further integration into the overall Fire and Gas detection system.
ASD system shall be aspirating, laser-based, digital smoke particle counting type. Detection shall
be made by the measurement of light scattered from air drawn into a sampling chamber.

Page 28 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 29 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

ASD system shall provide a sensitivity range of 0.005% to 20% obscuration per meter. This range
shall be fully configurable.
Components, equipment and assemblies shall be corrosion resistant.
SUPPLIER shall be responsible for the number of sample points provided, the number of ASDS
units provided, the detailed design layout of sample points and the generation of drawings for the
sampling system.
Sampling system shall employ a number of tubes of varying lengths. SUPPLIER shall design the
entire sampling network, pipe/tubing sizes, using appropriate software and submit to COMPANY
for review and approval. Multi-tube units, with automatic switching valves in the sample inlet
manifold to allow multiple sample lines to connect to a single aspirator / ASDSunit, can be
considered. In such case, the system component shall be redundant to avoid single point failure.
Output alarm contacts shall be provided individually per sample line.
SUPPLIER standard Teflon or other polymer tubing shall be used with COMPANY approval.
Sample system shall be under the false floor with branches up into various electronic cabinets.
The sampling system shall be protected against any mechanical damages. The tubing shall be
supported at regular interval to ensure stability of the tubing and reduce possibility of breaks. Any
points shall be airtight to prevent air leakage or infiltration. SUPPLIER shall label sampling system
tubing at branches, wall or floor penetrations, and at regular intervals of tubing runs.
SUPPLIER shall advise the maximum sampling time to alarm for each aspirated sample as a
function of the overall sample scan. It shall not exceed 120 seconds. Sampling system shall be
designed so it can be manually purged without pressurizing the aspirator unit.
ASDS units shall be supplied with local digital indicators. The main detector unit shall be immune
to dust and dirt build-up. It shall be capable of generating high signal to noise ratios, with immunity
from vibration and high humidity.
SUPPLIER shall design the equipment for 30 years design life.

11.15 Building Fire Alarm Control Panel (FACP)


Building Fire Alarmpanels shall be installed in all buildings. Major buildings shall have a dedicated
addressable fire system that are compatible with addressable smoke and heat detectors, gas
detectors, MCP, sounders, beacons and shall interface with fire suppression systemscontrol panel
and HVAC damper controls. The control panel (or slave panel) shall be wall mounted inside the
building (near staircase). Remote LCD HMI display shall be located in the main entrance area of
each building and shall provide the fire detectiondisplay mimic for annunciation of the building fire
alarms. The Building fire alarm systemincluding all components from detectors to the control panel
shall be in accordancewith the requirements of NFPA 72.
The Building Fire Alarm Panels in each building shall be networked over redundant fibreson the
same fibre optic cable and interfaced with the plant F&G systems.There shall be redundant serial
data links between the building fire alarm systems and the main plant Fire & Gas system which
shall provide status informationrelating to the building fire alarm systems in the Control Room.

11.16 Name Plates


All Fire and gas detectors shall be clearly and permanently identified by suitable nameplates.
The nameplates shall be stainless steel AISI 316 and affixed to the detectors.
Page 29 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 30 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

Information shall be engraved or stamped sufficiently deep to remain fully legible following several
years usage, inclusive of maltreatment such as scraping to remove paint.
Wire-on labels are not acceptable. The following information, where applicable, shall be shown on
the nameplate, as a minimum:

x Instrument Tag number in accordance with Data Sheets.


x Service
x Operating range
x Manufacturer's name, serial number
x UL Stamping

Page 30 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 31 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

12. Inspection and Testing


F&G detectors shall be subject to inspection by the CONTRACTOR / COMPANY or their
nominated third party as per the inspection and test plan of the respective items as applicable and
also as detailed on the material requisition / purchase order.
Integrated factory acceptance test shall be offered for the equipment and the detectors that are
intended for project use.
The SUPPLIER shall be responsible for preparing test procedures, co-ordination with third party
system suppliers and the testing of all interfaces to third party equipment.
It is a prior requirement to any final inspection that the drawings be certified / approved by the
CONTRACTOR / COMPANY.
Acceptance of shop tests shall not constitute a waiver of requirements to meet the service
requirements under specified conditions and final guarantee for material design, workmanship and
performance.
It shall be SUPPLIER’s responsibility to modify and / or replace any F&G detector component if the
specified functions are not completely and satisfactorily achieved during inspection and testing.

Page 31 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 32 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

13. Special Parts and Special Tools


SUPPLIER shall identify and supply any special installation, maintenance, tools and tackle
required for all F&G detectors supplied. SUPPLIER shall also provide special tools required for
configuration, calibration, diagnostics, and preventative maintenance including HART
communicator.

Page 32 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 33 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

14. Spares
SUPPLIER shall complete and submit an SPIR form for three-year operational period as a part of
required documentation.
The SUPPLIER shall provide:

x The spare parts for commissioning and start-up


x 3 years operation spares parts priced list

Page 33 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 34 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

15. Painting and Coating


Manufacturers’ standard painting suitable for sand laden desert environment is acceptable subject
to COMPANY review and approval.

Page 34 of 35
SIBA FIELD DEVELOPMENT PROJECT
KEIL/SIBA/2015/C-051-REV–CPF EPC

Document Number Document Title Page Page 35 of 35


Rev. 1
C-051-080-SPC-0004 Specification for Fire and Gas Detectors Date 27.09.2015

16. Documentation
SUPPLIER shall submit the documentation in accordance with the Supplier data Requirement list
(SDRL) of the Material Requisition and Purchase Order. All documents, drawings, dossiers
including third party certificates shall be in English.All reference to any system and field instrument
on any document shall be by referenced by its tag number.
SUPPLIER shall ensure that all the documents can be reproduced clearly and completely.
Wherever safety is involved, documents shall be approved by certifying authority prior to proceed
to fabrication.
Typical documents include:

x Specifications / data sheets

x Wiring Diagrams

x Schematic interface drawings

x Power consumption details

x Test Procedures

x Software documentation

x Operating and Maintenance Manuals

Page 35 of 35

You might also like