Current Structural Set 6.6.2023
Current Structural Set 6.6.2023
G. DOWELS FROM FOUNDATION OR SLABS TO WALLS SHALL MATCH WALL REINFORCING SIZE LOACTION AND SPACING, UNLESS NOTED
WIDE FLANGE SECTIONS: ASTM A992, GRADE 50 OTHERWISE. DOWELS SHALL BE PLACED BEFORE CONC. IS POURED. DOWELS SHALL NOT BE PUSHED INTO THE CONCRETE.
BUILDING CODES: ANGLES: ASTM A36 GENERAL NOTES:
2018 INTERNATIONAL BUILDING CODE (IBC) A. “REINFORCED CONCRETE NOTES” SHALL APPLY UNLESS NOTED OTHERWISE IN THIS SECTION
CHANNELS: ASTM A36
LOADING CRITERIA: H. WHERE GRADE BEAMS OR STRIP FOOTINGS INTERSECT COLUMNS FOUNDATIONS, EXTEND GRADE BEAM OR STRIP FOOTING B. POST TENSIONED CONCRETE SHALL CONFORM TO THE LATEST EDITION OF ACI 318 BUILDING CODE REQUIREMENT
PLATES AND BAR STOCK: ASTM A36 OR ASTM A572 (SEE PLANS) REINFORCEMENT CONTINUOUSLY THROUGH THE COLUMN FOUNDATION.
DEAD LOADS: (IN ADDITION TO SELF WEIGHT) FOR CONCRETE REFERENCED IN THE BUILDING CODE LISTED IN “DESIGN CRITERIA”
STEEL PIPES: ASTM A53, GRADE B OR ASTM A501
PARKING FLOORS B2-B1. FULL FLOOR 5 PSF I. WELDED WIRE FABRIC SHALL BE LAPPED A MINIMUM OF WIRE SPACING PLUS 6" AND TIED.
STEEL TUBES: ASTM A500, GRADE C K. SEQUENCE OF STRESSING SHALL BE AS FOLLOWS:
MVW
KJM
MEP & CEILING, FLOORING, 1ST FLOOR. FULL FLOOR 15 PSF J. WELDED WIRE FABRIC SHALL BE FABRICATED IN FLAT SHEETS. ROLLS ARE NOT ALLOWED.
K. UNLESS NOTED OTHERWISE, TENSION SPLICES IN REINFORCING, WHERE PERMITTED, SHALL BE: 1) ONE WAY PT SLABS
PORTE COCHERE / LOADING DOCK TOPPING SLABS 60 PSF D. METAL ROOF DECK, COMPOSITE AND NON-COMPOSITE FLOOR DECK:
CLASS B 2) PT BEAMS
Checked By:
MRI/ PT RECESS TOPPING SLABS 60 PSF DESIGN PER CURRENT EDITION OF: SDI
A. CONTINUOUS STRANDS
Drawn By:
MEP & CEILING FLOORS 2-6 & FUTURE 7,8. FULL FLOOR 10 PSF REINFORCING BAR LAP SCHEDULE:
SHALL CONFORM TO: ASTM A653 B. ADDED STRANDS
3rd FLOOR PATIO PAVERS 40 PSF MINIMUM YIELD STRENGTH: 55 KSI L. CONTRACTOR SHALL SHOW ALL OPENINGS AND SLEEVES IN SLAB ON POST TENSIONED SHOP DRAWINGS.
GREEN ROOF SYSTEM (FUTURE 9TH) FULL FLOOR 75 PSF #6 AND SMALLER #7 AND LARGER
E. LIGHT GAGE STEEL FRAMING (INCLUDING STRUCTURAL JOISTS AND WALL STUDS): ADDITIONAL OPENINGS NOT SHOWN ON THE SHOP DRAWINGS REQUIRE WRITTEN APPROVAL FROM THE ENGINEER
NOTE: ADDED DL INDICATED ABOVE ARE ADDITIVE DEPENDING ON THE AREA SEE PLAN F'c OTHER BARS TOP BARS OTHER BARS TOP BARS OF RECORD AND POST TENSION ENGINEER.
SHALL CONFORM TO: ASTM A1003 GreshamSmith.com
MINIMUM YIELD STRENGTH: 33 OR 50 KSI Class A Class B Class A Class B Class A Class B Class A Class B
M. ALL SUSPENDED MECHANICAL, PLUMBING AND ELECTRICAL EQUIPMENT TO BE SUSPENDED FROM THE POST
A. LIVE LOADS: F. STRUCTURAL INSULATION 3,000 PSI 44 db 57 db 57 db 74 db 55 db 72 db 72 db 93 db TENSIONS SLAB OR BEAMS SHALL BE MADE WITH PRE-INSTALLED ANCHOR SYSTEM CAST INTO THE SLAB.
REDUCIBLE PER IBC: 2018 FILL INSULATION BOARD SHALL CONFORM TO: ASTM C-578-01, TYPE IX 4,000 PSI 38 db 50 db 50 db 65 db 48 db 62 db 62 db 81 db COORDINATE ROUTING AND LOCATION OF ANCHORS WITH THE MEP SUB CONTRACTORS PRIOR TO POURING SLAB.
UNIFORM LIVE LOADS: MINIMUM COMPRESSIVE STRENGTH: 25 PSI PER ASTM D1621 5,000 PSI 34 db 45 db 45 db 58 db 43 db 56 db 56 db 72 db
UNIFORM LOADS CONCENTRATED LOADS G. FOUNDATIONS: 6,000 PSI 31 db 41 db 41 db 53 db 39 db 51 db 51 db 66 db
N. RECORDS OF ALL JACKING FORCES AND ELONGATIONS SHALL BE MADE AND KEPT BY THE INDEPENDENT TESTING
B3-B1 FLOORS FOUNDATION TYPES: SHALLOW FOUNDATIONS CONSISTING OF STRIP AND SPREAD FOOTINGS. 8,000 PSI 27 db 35 db 35 db 46 db 34 db 44 db 44 db 57 db AGENCY. THE RECORDS SHALL BE SUBMITTED TO THE ENGINEER OF RECORD AND POST TENSIONED ENGINEER OF
PARKING (NOT REDUCIBLE): 40 PSF 3000 LBS SOIL BEARING CAPACITIES: 10,000 PSI 24 db 32 db 32 db 41 db 30 db 39 db 39 db 51 db RECORD. THE FIELD APPLIED FORCES OR ELONGATIONS SHALL NOT VARY FROM THE CALCULATED VALUES BY 222 Second Avenue South
LIGHT STORAGE (NOT REDUCIBLE) : 125 PSF 2000 LBS MORE THAN 7%. IF TENDON ELONGATION IS OUT OF TOLERANCE A LETTER FROM THE POST TENSION ENGINEER OF Suite 1400
SPREAD FOOTINGS: 200,000 PSF (DESIGN MAXIMUM) NOTES: RECORD SHALL BE SUBMITTED WITH THE STRESSING RECORD INDICATING THE LONG TERM EFFECTIVE FORCE
CORRIDORS/ COMMON AREAS: 100 PSF 2000 LBS STRIP FOOTINGS: 200,000 PSF (DESIGN MAXIMUM) 1. ALL LAPS SHALL BE CLASS B UNLESS NOTED OTHERWISE (U.N.O.). INDICATED ON THE CONSTRUCTION DOCUMENTS WILL BE MET. Nashville, TN 37201
ELECTRICAL ROOM (NOT REDUCIBLE): 125 PSF 2000 LBS SOIL BEARING CAPACITIES LISTED ABOVE PER: GEOS (PER SUBSURFACE EXPLORATION) 2. BEAMS AND COLUMNS: INCREASE LAPS SHOWN BY 50% IF CLEAR SPACING OF BARS IS LESS THAN 2 db, OR IF CLEAR
615.770.8100
GEOTECHNICAL REPORT DATED: 1/20/2022 COVER OF BARS IS LESS THAN 1 db.
1ST FLOOR 3. WALLS, SLABS, AND FOOTINGS: INCREASE LAPS SHOWN BY 50% IF CLEAR SPACING OF BARS IS LESS THAN 2 db, OR IF O. THE TESTING AGENCY SHALL CONTINUOUSLY OBSERVE THE POST TENSIONED CONCRETE WORK INCLUDING THE
CORRIDORS: 100 PSF 2000 LBS SHALLOW FOUNDATIONS CLEAR COVER OF BARS IS LESS THAN 2 db.
4. INCREASE LAPS BY 25% FOR GRADE 75 REINFORCEMENT.
PLACEMENT AND SECURING OF TENDONS, THE PLACEMENT OF CONCRETE, THE STRESSING OF TENDONS, AND THE
REMOVAL OF THE PROJECTING STRANDS.
COMMON AREAS: 100 PSF 2000 LBS
STAIRS: 100 PSF GENERAL NOTES: 5. INCREASE LAPS BY 33% FOR LIGHTWEIGHT CONCRETE. P. PROJECTED ENDS OF STRANDS MAY ONLY BE REMOVED AFTER THE STRESSING HAS BEEN COMPLETED AND
CLINICAL SPACES: 100 PSF 2000 LBS A. FINISHED FLOOR ELEVATION SHALL BE TAKEN AS 0'-0". REFER TO CIVIL DRAWINGS FOR ACTUAL ELEVATION. MEASURED ELONGATIONS HAVE BEEN SUBMITTED AND APPROVED BY THE ENGINEER OF RECORD AND POST
TENSIONED ENGINEER OF RECORD. STRANDS SHALL BE CUT SO THAT THE END IS 1” CLEAR FROM THE EDGE OF
MECHANICAL ROOMS ( NOT REDUCIBLE): 150 PSF 3000 LBS B. SEE PLUMBING, ELECTRICAL, AND CIVIL DWGS. FOR REQUIRED UTILITIES UNDER FLOOR SLABS AND FOUNDATIONS. L. REINFORCING SPLICES SHALL OCCUR IN LOCATIONS AS INDICATED ON THE CONTRACT DOCUMENTS, SPLICES AT OTHER LOCATIONS
RETAIL SPACE: 100 PSF 2000 LBS C. BACKFILL FOR BASEMENT, CLOSURE AND RETAINING WALLS SHALL #57 UNIFORMLY GRADED STONE. SHALL BE APPORVED BY THE ENGINEER PRIOR TO CONSTRUCTION
CONCRETE. Smith
PORTE COCHERE / DRIVE THRU ( NOT REDUCIBLE): 125 PSF
Seckman
LOADING DOCK ( NOT REDUCIBLE): 125 PSF
D. FOOTINGS SHALL NOT BE POURED AGAINST SUB-GRADE CONTAINING ICE, STANDING WATER, OR LOOSE MATERIAL. Q. THE STRESSING POCKETS SHALL BE GROUTED WITHIN SEVEN DAYS OF APPROVAL OF THE MEASURED
ELONGATIONS.
Reid, Inc.
E. FOOTINGS SHALL BE CENTERED ON COLUMN LINES, AND CENTERLINES OF WALLS (U.N.O.). SLAB ON GRADE:
2995 Sidco Drive
SLAB-ON-GRADE: A. SAWN CONTROL JOINTS IN SLAB ON GRADE SHALL BE CUT IN ACCORDANCE WITH: ACI 302.1R R. IN THE CASE OF BROKEN TENDONS OR BLOWOUTS THE POST TENSIONED ENGINEER SHALL SUBMIT TO THE Nashville, TN 37204
2ND-5TH FLOORS A. SLAB-ON-GRADE SHALL BEAR PROPERLY AGAINST 15 MIL VAPOR BARRIER OVER 12" COMPACTED GRANULAR DRAINAGE LAYER. B. JOINTS SHALL BE CUT WITHIN 12 HOURS OF SLAB PLACEMENT. ENGINEER OF RECORD DETAILED CALCULATIONS AND PROCEDURES FOR REMEDIATION OF THE ISSUE. (615) 383-1113
CORRIDORS, LOBBIES, STAIRS & COMMON AREAS: 100 PSF 2000 LBS DRAINAGE LAYER SHALL BE UNIFORMLY GRADED GRANULAR MATERIAL EQUIVALENT TO #57 STONE.
C. CONTROL JOINTS MAXIMUM SPACING IS INDCATED IN SLAB ON GRADE DETAIL. THE CONTRACTOR SHALL SUBMIT CONTORL JOINT FAX: (615) 386-8469
S. CORING THE POST TENSIONED SLABS OR CONCRETE BEAMS OR USE OF DRILLED, POST INSTALLED, MECHANICAL
CLINICAL / OFFICE SPACE: 80 PSF (INCLUDES 15 PSF PARTITION LOAD) LAYOUT FOR APPORVAL PIOR TO CONSTRUCTION. THE SPACING OF THE JOINTS AND SUBMIT A REVISED SLAB CONTROL JOINT PLAN www.ssr-inc.com
OR ADHESIVE ANCHORS WITH AN EMBEDMENT GREATER THAT 3/4” SHALL NOT BE PERMITTED WITHOUT WRITTEN
MECHANICAL ROOMS ( NOT REDUCIBLE): 150 PSF 3000 LBS B. DESIGN OF SLAB-ON-GRADE IS BASED UPON THE FOLLOWING PER THE GEOTECHNICAL REPORT: TO THE ENGINEER FOR APPROVAL. THE LENGTH TO WIDTH RATIO BETWEEN JOINTS SHALL NOT EXCEED 1.5 AND THE AREA BOUNDED APPROVAL FROM THE ENGINEER OF RECORD. IF APPROVED, THE CONTRACTOR SHALL SCAN THE SLAB AND LOCATE
BY THE JOINTS SHALL NOT EXCEED 200 SF FOR 4” SLABS AND 400SF FOR 6” SLABS. ALL POST INSTALLED ANCHORS TO MISS THE POST TENSIONED TENDONS.
EXTERIOR TERRACE (3RD FLOOR): 100 PSF MODULUS OF SUB-GRADE REACTION: 200 PCI SSR Project #: 21640780
DESIGN INFORMATION:
A. FOUNDATION DESING IS BASED UPON THE RECOMMNEDATION CONTAINED INT THE FOLLOWING GEOTECHNICAL REPORT: D. ALL CONCRETE SLABS-ON-GRADE SHALL BE CURED USING A LIQUID MEMBRANE FORMING CURING COMPOUND WHERE PRACTICAL.
6TH FLOOR (PHASE 1/ROOF)
REFER TO THE SPECIFICATIONS FOR FURTHER INFORMATION.
GREEN ROOF ( UNREDUCIBLE)
ROOF:
75 PSF
20 PSF
GREEN ROOF IS LL FOR PHASE 1
GEOTECHNICAL REPORT:
E. SLAB-ON-GRADE VAPOR BARRIERS SHALL BE A MINIMUM OF 15 MILS THICK. OVERLAP SEAMS 6” AND TAPE. REINFORCED MASONRY
PREPARED BY: GEOS,INC F. PROVIDE 1/2" PRE-MOLDED EXPANSION JOINT MATERIAL WITH FLEXIBLE JOINT SEALANT WHERE SLAB ON GRADE IS POURED AROUND
COLUMNS AND AGAINST GRADE BEAMS OR WALLS, UNLESS OTHERWISE SHOWN OR NOTED. DESIGN CRITERIA:
6TH FLOOR (FUTURE) DATED: 1/20/2022
G. FOR FLATNESS AND LEVELNESS, CONCRETE SLABS SHALL CONFORM TO: ACI 117-90 A. DESIGN PER CURRENT EDITION OF: ACI 530
CORRIDORS, LOBBIES, STAIRS & COMMON AREAS: 100 PSF 2000 LBS B. FOOTINGS AND SLAB SUB-GRADE PREPARATION SHALL BE IN ACCORDANCE WITH THE RECOMMENDATIONS IN THE GEOTECHNICAL
REPORT AND IN COMPLIANCE WITH APPLICABLE REQUIREMENTS OF THE GOVERNING AUTHORITIES HAVING JURISDICTION. ACCORDING TO: ASTM E 1155 B. REFER TO THE ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ANY EMBEDDED ITEMS THAT SHALL
CLINICAL / OFFICE SPACE: 80 PSF (INCLUDES 15 PSF PARTITION LOAD) SPECIAL ATTENTION SHALL BE GIVEN TO RECOMMENDED BASTING DEPTH, OVEREXCAVATION AREAS, AND REQUIRED DRAINAGE BE CAST INTO MASONRY WALLS OR ANY OPENINGS REQUIRED THROUGH MASONRY WALLS.
MECHANICAL ROOMS ( NOT REDUCIBLE): 150 PSF 3000 LBS MAT UNDER BASEMENT SLAB ON GRADE. COMPOSITE FLATNESS (Ff) COMPOSITE LEVELNESS (Fl)
C. FOUNDATIONS SHALL BEAR ON COMPETENT BEAD ROCK OR 3000PSI LEAN CONCRETE AT OVEREXCAVATED AREAS. SPECIFIED OVERALL VALUE: 25 20
LOAD BEARING AND EXTERIOR WALLS:
A. COMPOSED OF HOLLOW CONCRETE MASONRY UNITS (CMU)
TENNESSEE
7TH FLOOR ( FUTURE FLOOR )
D. ALL FOOTING EXCAVATIONS HSALL BE OBSERVED AND A 2" DIA X 6-'0" LONG (MIN) PROBE HOLE SHALL BE ADVANCED UNDER THE
MINIMUM LOCAL VALUE: 17 15 B. CMU SHALL BE LAID IN A “FULL BEDDING” OF MORTAR.
PATTERN: RUNNING BOND
ONCOLOGY
FUTURE CORRIDORS, STAIRS & COMMON AREAS: 100 PSF 2000 LBS PROPOSED FOOTING PER THE GEOTECH REPORT TO DETERMING COMPETENCY OF THE UNDERLYING BEDROCK TO ACHIEVE THE ELEVATED CONCRETE FRAMING: CMU PER: ASTM C90
FUTURE CLINICAL / OFFICE SPACE( NOT REDUCIBLE): 85 PSF (INCLUDES 20 PSF PARTITION LOAD) REQUIRED BEARING CAPACITY.
A. CONSTRUCTION JOINTS IN FLOOR FRAMING SHALL OCCUR WITHIN THE MIDDLE 1/3 OF THE SPAN OF THE BEAM. JOINT IN GIRDERS TESTED IN ACCORDANCE WITH: ASTM C140
PHASE 1 ROOF: E. FOUNDATIONS SHALL BEAR ON COMPETENT BED ROCK WITH A BEARING CAPACITY PER THE GEOTECHNICAL REPORT OF THE SHALL OCCUR AWAY FROM INTERSECTING BEAMS AT A DISTANCE EQUAL
FOLLOWING: CMU TYPE: LIGHT WEIGHT
B. CONSTURCITON JOINT LOCATION SHALL BE APPROIVED BY THE THE STRUCUTRAL ENGINEER. CONTRACTOR SHALL SUBMIT
CONSTRUCTION DOCUMENTS
BASIC WIND SPEED (VASD): 81 MPH GENERAL: THIS IN FIGURING THE CONCRETE QUANTITIES C. REINFORCE CMU WALLS PER THE REINFORCING SCHEDULE OR AS INDICATED ON PLANS.
RISK CATEGORY: II A. ALL CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF ACI 318. D. REFER TO THE REINFORCEMENT SCHEDULE ON SHEET: 7/S410
WIND EXPOSURE CATEGORY: B B. PROVIDE 3/4" CHAMFER AT ALL EXPOSED CORNERS OF BEAMS, WALLS, SLABS, ETC. E. REINFORCE EA. CORNER, WALL END, WALL INTERSECTION, EACH SIDE OF CONTROL JOINTS AND EXPANSION JOINTS,
INTERNAL PRESSURE COEFFICIENT, Gcpi +/-0.18
COMPONENTS AND CLADDING PRESSURES: REFER TO FIGURE THIS SHEET.
C. ALL CONCRETE SHALL BE MECHANICALLY VIBRATED IN ACCORDANCE WITH:
D. ALL EXTERIOR CONC, PERMANENTLY EXPOSED TO WEATHER SHALL CONTAIN AN AIR ENTRAINING ADMIXTURE.
ACI 304 AND ACI 309
POST TENSIONED CONCRETE AND EA. SIDE OF OPENINGS (DOORS AND WINDOWS) WITH ONE (1) #5 VERTICAL, FULL HEIGHT OF WALL.
F. ALL REINFORCED CELLS SHALL BE GROUTED SOLID.
E. CONTRACTOR SHALL REFER TO AND COORDINATE WITH OTHER DISCIPLINES DRAWINGS AND OR VENDOR DRAWINGS FOR G. REINFORCE ALL CORNERS WITH CONTINUOUS CORNER BARS IN BOND BEAMS.
C. SNOW LOADS: EMBEDDED ITEMS AND OR RECESSES NOT SHOWN IN THE STRUCTURAL DRAWINGS. GENERAL NOTES: H. FOR CORNER REINFORCEMENT, REFER TO DETAIL: 8/S410
GROUND SNOW LOAD (Pg): 10 PSF A. “REINFORCED CONCRETE NOTES” SHALL APPLY UNLESS NOTED OTHERWISE IN THIS SECTION
HORIZONTAL JOINT REINFORCEMENT:
FLAT ROOF SNOW LOAD: 10 PSF CONCRETE MIXES: B. POST TENSIONED CONCRETE SHALL CONFORM TO THE LATEST EDITION OF ACI 318 BUILDING CODE REQUIREMENT FOR CONCRETE
REFERENCED IN THE BUILDING CODE LISTED IN “DESIGN CRITERIA” TYPE: LADDER ( 9 GAGE HORIZONTAL JOINT REINFORCEMENT)
EXPOSURE FACTOR (Ce): 1.0 STRENGTH (28 WATER/ CEMENT AIR ENTRAINMENT USE
DAY) RATIO (MAX.) SPACING: 16 INCHES ON CENTER, VERTICALLY, U.N.O.
IMPORTANCE FACTOR (Is): 1.0 C. POST TENSIONED CONCRETE SHALL CONFORM TO THE SPECIFICATIONS FOR UNBOUNDED SINGLE STRAND TENDONS BY THE A. INSTALL JOINT REINFORCING IN THE FIRST TWO MORTAR JOINTS ABOVE AND BELOW OPENINGS, EXTENDING AT
THERMAL FACTOR (Ct): 1.0 F'c = 4,000 PSI 0.48 NO INTERIOR SLAB-ON-GRADE POSTTENSIONED INSTITUTE, PTI LEAST 24" BEYOND THE OPENING, TYPICAL.
D. SEISMIC DESIGN CRITERIA: F'c = 4,500 PSI 0.45 YES EXTERIOR SLAB-ON-GRADE
D. TENDONS: POST TENSIONED TENDONS SHALL BE ASTM A416 LOW RELAXATION 1/2" DIA SEVEN WIRE STRANDS. ULTIMATE STRENGTH B. PROVIDE HORIZONTAL JOINT REINFORCEMENT IN PARAPETS AND FREE STANDING WALLS AT 8" O.C. VERTICALLY, LAP
IMPORTANCE FACTOR (Is): 1.0 F'c = 4,000 PSI 0.55 NO FOUNDATIONS F'pu=270 KSI. TENDONS SHALL BE AN ENCAPSULATED SYSTEM JOINT REINFORCEMENT 6" MIN.
RISK CATEGORY: II F'c = 4,500 PSI 0.45 YES FOUNDATION WALLS C. PROVIDE HORIZONTAL JOINT REINFORCING PREFABRICATED UNITS AT CORNERS AND T INTERSECTIONS.
E. DESIGN AND EXECUTION OF THE ALL POST TENSIONING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR IN ACCORDANCE WITH
SITE CLASSIFICATION: B F'c = 6,000 PSI 0.36 NO INTERIOR BEAMS & SLABS B2-6TH FLOOR THE SPECIFICATIONS AND DETAILS AS INDICATED ON THE DRAWINGS. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND
SEISMIC DESIGN CATEGORY: B F'c = 10,000 PSI 0.3 NO COLUMNS B3-2ND FLOOR CALCULATIONS SIGNED AND SEALED BY A STRUCTURAL ENGINEER REGISTER IN THE STATE OF THE PROJECT. VERTICAL REINFORCEMENT:
MAPPED SPECTRAL RESPONSE ACCELERATION: A. VERTICAL BAR POSITIONERS SHALL BE UTILIZED TO SECURELY HOLD VERTICAL BARS IN POSITION IN THE CENTER OF
F'c = 8,000 PSI 0.33 NO COLUMNS 2ND-6TH FLOOR
THE CORES. GROUT SHALL BE PLACED IN ALL REINFORCED CELLS, GROUT SHALL BE CONSOLIDATED, (VIBRATED),
Ss: 0.285 F'c = 4,500 PSI (LW) N/A NO TOPPING SLABS 1ST FLOOR DURING PLACEMENT. MAXIMUM GROUT LIFT SHALL BE 4’-0”. VERTICAL REINFORCING SHALL BE DETAILED AND LAPPED
S1: 0.142 F. CONTRACTOR AND POST TENSIONED SUPPLIER SHALL DESIGN AND PROVIDE ALL POST TENSIONED ANCHORAGE REINFORCING ACCORDINGLY.
F'c = 4,000 PSI (LW) N/A NO ELEVATED COMPOSITE SLABS
NECESSARY TO PROPERLY DEVELOP ANCHORAGE AND BEARING OF THE ANCHORAGE DEVISED. REINFORCING SHALL BE IN
MAPPED SPECTRAL DESIGN ACCELERATION:
F'c = 4,000 PSI 0.44 NO MISC CURBS AND PADS ADDITION OT REINFORCING SHOWN ON DRAWINGS. B. LAP VERTICAL BARS PER THE MASONRY LAP SCHEDULE. ALL LAPS SHALL BE SECURED WITH WIRE TIES.
SDS: 0.171
F'c = 3,000 PSI 0.55 NO ALL OTHER MISC CONCRETE C. REFER TO THE MASONRY LAP SCHEDULE ON SHEET: 4/S410
SD1 0.067 G. THE CONTRACTOR SHALL DETERMINE THE NUMBER OF STRANDS, TENDON LAYOUT, TENSIONED SEQUENCE, END ANCHORAGE
BASIC SEISMIC FORCE RESISTING SYSTEM: ORDINARY CONCRETE MOMENT FRAMES & ORDINARY STEEL DETAILS, LIVE AND DEAD ENDS, AND FINAL MINIMUM ELONGATION REQUIRED FOR EACH TENDON IN ORDER TO PROVIDE THE MINIMUM EXPANSION AND CONTROL JOINTS:
MOMENT FRAMES NOT SPECIFICALLY DETAILED FOR SEISMIC A. ALL CONCRETE MIXES SHALL CONFORM TO THE REQUIREMENTS OF CHAPTER 4 OF ACI 318. REFER TO SPECIFICATIONS FOR EFFECTIVE FORCE INDICATED ON THE DRAWINGS. POST TENSIONED FORCES INDICATED ON THE DRAWINGS ARE REQUIRED A. COORDINATE EXPANSION OR CONTROL JOINTS IN MASONRY WALLS WITH ARCHITECTURAL DRAWINGS. EXPANSION
RESISTANCE FURTHER MIX DESIGN REQUIRMENTS FOR EACH MIX INDICATED ABOVE. EFFECTIVE FORCES AFTER ALL LOSSES ARE ACCOUNTED FOR. CONTRACTOR SHALL SUBMIT CALCULATIONS INDICATING VALUE OF OR CONTROL JOINTS SHALL NOT OCCUR WITHIN MASONRY “SHEAR WALLS” AS INDICATED ON THE PLANS.
ALL LOSSES APPROPRIATE FOR THIS PROJECT. MAXIMUM EFFECTIVE FORCE PER 1/2” DIA STRAND IS 26.7 KIPS. STRESSED IN
B. LIGHWEIGHT CONCRETE SHALL HAVE A DRY UNIT WEIGHT NOT TO EXCEED 115 PCF.
TENDONS SHALL NOT EXCEED THE FOLLOWING:
RESPONSE MODIFICATION COEFFICIENT (R): 3.0
C. 8,0000, AND 10,000 PSI CONCRETE SHALL HAVE A 56 DAY STRENGTH IN LIEU OF THE 28 DAY STRENGTH LISTED ABOVE
DEFLECTION AMPLIFICATION FACTOR (Cd): 3.0
OVER STRENGTH (W): 3.0
D. 8,0000, AND 10,000 PSI CONCRETE MIXES SHALL CONTAIN A HIGH RANGE WATER REDUCER 216 KSI 0.8 F'pu
SEISMIC RESPONSE COEFFICIENT (Cs): 0.0100 1) TEMPORARY JACKING STRESSES
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
E. AIR ENTRAINMEnT LISTED ABOVE SHALL PROVIDE 5% MIN. AIR TO THE MIXTURE
DESIGN BASE SHEAR (V): 850 K 2) STRESSES AT IMMEDIATE TRANSFER 200 KSI 0.74 F'pu
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE 3) STRESSES AT I ANCHORAGE, AFTER ANCHORAGE 189 KSI 0.80 F'pu
REINFORCING:
A. UNLESS NOTED OTHERWISE (U.N.O.) ON THE DWGS, THE MIN. COVER FOR REINFORCING SHALL BE AS FOLLOWS:
DEFLECTION CRITERIA: CONSTRUCTION:
VERTICAL DEFLECTION CAST IN PLACE CONCRETE
A. PRESTRESSING OF CONCRETE SHALL NOT BEGIN UNTIL THE CONCRETE HAS ATTAINED A MINIMUM COMPRESSIVE STRESS OF 3000
LIVE LOAD DEAD LOAD +LIVE LOAD CAST AGAINST EARTH: 3.00 INCHES PSI.
FLOOR FRAMING: L/360 L/240 EXPOSED TO EARTH, LIQUID, OR WEATHER: Revision
#5 AND LARGER 2.00 INCHES B. TENDON SUPPORT SPACING SHALL NOT EXCEED 2'-6" ON CENTER IN ANY DIRECTION. SECURE TENDONS IN ACCORDANCE WITH THE
ROOF FRAMING: L/360 L/240 SPECIFICATIONS TO PREVENT MOVEMENT DURING CONCRETE PLACEMENT.
L= SPAN OF MEMBERS #5 AND SMALLER 1.50 INCHES No. Date Description
NOT EXPOSED TO EARTH, LIQUID, OR WEATHER:
HORIZONTAL DEFLECTION: (DRIFT) SLABS: 0.75 INCHES C. THE MINIMUM RADIUS OF CURVATURE FOR A HORIZONTAL TRANSITION IN A TENDON SHALL BE 60 IN.
MAXIMUM FLOOR TO FLOOR AND OVERALL DRIFT FOR WIND WALLS: 0.75 INCHES D. CONTRACTOR SHALL NOT VARY THE PROFILE OF TENDON PLACEMENT INDICATED MORE THAN 1/8” VERTICALLY.
50YR MRI WIND LOADS H/400
COLUMN TIES: 1.50 INCHES
H= HEIGHT OF BUILDING OR FLOOR BEAM STIRRUPS 1.50 INCHES E. UNLESS NOTED OTHERWISE PLACE THE TENDONS IN A SMOOTH PARABOLIC DRAPE BETWEEN HIGH AND LOW POINT AS INDICATE IN
FUTURE EXPANSION: THE DRAWINGS.
VERTICAL: A FUTURE 2 ADDITIONAL FLOORS, AND 1 ADDITIONAL ROOF POST TENSIONED CAST IN PLACE CONCRETE
F. CONTRACTOR TO COMPLETELY CONSOLIDATE CONCRETE BEHIND TENDON ANCHOR LOCATIONS.
HORIZONTAL: NO FUTURE HORIZONTAL EXPANSION HAS BEEN DESIGNED FOR AS PART OF THIS PROJECT CAST AGAINST EARTH: 3.00 INCHES
EXPOSED TO EARTH, LIQUID, OR WEATHER: G. CONTRACTOR SHALL MARK THE FORMS OR PROVIDE STRAND LOCATION INDICATORS IN THE SLAB AND BEAMS TO IDENTIFY THE
MATERIAL STRENGTHS: LOCATION OF THE STRAND AFTER THE CONCRETE IS POURED.
WALLS. SLABS 1.00 INCHES
A. CONCRETE: H. CONTRACTOR AND POST TENSIONED ENGINEER/ CONTRACTOR SHALL COORDINATE CONSTRUCTION JOINT LOCATIONS. JOINT
BEAMS AND OTHER MEMBERS 1.50 INCHES
DESIGN PER CURRENT EDITION OF: ACI 318-14 LOCATIONS SHALL BE SHOWN ON THE SUBMITTED POST TENSIONED SHOP DRAWINGS.
NOT EXPOSED TO EARTH, LIQUID, OR WEATHER:
INTERIOR SLAB-ON-GRADE: F'c = 4,000 PSI (MIN.)
PT GARAGE SLABS: 1.50 INCHES TOP COVER
EXTERIOR SLAB-ON-GRADE: F'c = 4,500 PSI (MIN.) I. CONTRACTOR AND POST TENSIONED ENGINEER SHALL COORDINATE LOCATION, DESIGN, AND PROVIDE DETAILS OF STRESSING
PT GARAGE SLABS: 0.75 INCHES BOTTOM COVER POCKETS AND BLOCK OUTS REQUIRED FOR CONSTRUCTION LOCATION AND DETAILS FOR POCKETS AND BLOCK OUTS SHALL BE
FOUNDATIONS F'c = 4,000 PSI
PT BEAM STIRRUPS 1.50 INCHES SHOWN OF THE SHOP DRAWINGS.
FOUNDATION WALLS: F'c = 4,000 PSI
INTERIOR BEAMS AND SLABS B2-6TH FLOOR: F'c = 6,000 PSI J. CONTRACTOR SHALL SUBMIT TO THE ENGINEER OF RECORD THE DETAILED PRE-STRESSING PROCEDURES AND SEQUENCES,
B. ALL REINFORCING SHALL BE HELD SECURELY IN POSITION WITH STANDARD ACCESSORIES IN CONFORMANCE WITH THE FOLLOWING
PRESTRESSING LOSS CALCULATIONS AND THE STATIC AND DYNAMIC TEST DATA.
DURING THE PLACING OF CONCRETE:
COLUMNS B3-2ND FLOOR: F'c = 10,000 PSI
CRSI MANUAL OF STANDARD PRACTICE
COLUMNS 2ND-6TH FLOOR: F'c = 8,000 PSI
ACI 315
TOPPING SLABS 1ST FLOOR: F'c = 4,500 PSI (LW)
C. ALL REINFORCING SHALL BE DETAILED SHOP DRAWINGS IN ACCORDANCE WITH THE FOLLOWING:
ELEVATED COMPOSITE SLABS: F'c = 4,000 PSI (LW)
CURBS... F'c = 4,000 PSI ACI DETAILING MANUAL, SP-66
CMU GROUT FILL: F'c = 2,000 PSI THE CRSI MANUAL OF CONCRETE PRACTICE
ACI 318
GENERAL NOTES
ALL OTHER MISC CONCRETE: F'c = 3,000 PSI
D. PROVIDE BAR SUPPORTS AND SPACERS IN ACCORDANCE WITH THE FOLLOWING:
REINFORCING STEEL: ASTM A615, GRADE 60 CRSI MANUAL OF STANDARD PRACTICE
4/25/2023 5:32:20 PM
S001
WELDED WIRE FABRIC: ASTM A1064 ACI 315
POST TENSIONED STRANDS: UNBONDED ASTM A416, F'pu=270ksi E. ALL BAR SUPPORTS IN AREA WHERE CONCRETE WILL BE EXPOSED SHALL HAVE PLASTIC TIPPED FEET. THE CONTRACTOR IS
B. CONCRETE MASONRY: CAUTIONED THAT CARE MUST BE EXERCISED TO PREVENT EXPOSURE OF THE TIE WIRE OR OTHER MATERIAL WHICH MAY CAUSE
STAINING OF EXPOSED CONCRETE. PROPER COVER AS INDICATED ABOVE SHALL BE MAINTAINED ON ALL REINFORCEMENT.
DESIGN PER CURRENT EDITION OF: ACI 530
COMPRESSIVE STRENGTH F'm = 2,000 PSI
C. STRUCTURAL STEEL: F. ALL 90, 135, & 180 HOOKS IN REINFORCING BARS SHALL BE ACI STANDARD HOOKS, U.N.O. 44791.01
DESIGN PER CURRENT EDITION OF: AISC
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
0.1A A B C D E
GreshamSmith.com
8' - 9" 15' - 0" 30' - 0" 30' - 0" 30' - 0"
Smith
2091 LBS.
Seckman
6 PB132 (36x21) Reid, Inc.
CB912 (36x36)
PB130 (36x21) PB131 (36x21) PB133 (36x21) PB134 (36x21) PB135 (36x21) 2995 Sidco Drive
Nashville, TN 37204
PB120 (36x21)
4" CONC. HOUSE (615) 383-1113
PB120 (36x21)
2091 LBS.
PB170 (48x21)
KEEPING PAD FAX: (615) 386-8469
4 4 4 3.5 1.5 6.25 1.25 6.25 1.25 6.25 1.25
15' - 9"
Fe = 34 www.ssr-inc.com
KIP / FT
MSB-A 6 MSB-B 19.5 KIP/FT.
PB164 (36x24)
4500 LBS. 4500 LBS. 4.0 SSR Project #: 21640780
T & S #4 @ 12" TERMINATE
B - TYP. 14.5 KIP/FT.
PB165 (42x24)
PB163 (20x24)
1
#4@12" B #4@12" B
#4@10" T #4@12" B
8" ONE WAY P.T.
TENNESSEE
PB169 (48x21)
SLAB - TYP. U.N.O.
8" ONE WAY P.T.
ONCOLOGY
29' - 3"
CB911 (36x48)
KIP / FT #4@12" B RAMP DOWN
PB119 (36x21)
PB119 (36x21)
-13' - 0"
4
Fe = 18 14 4 4 4 6 1.25 6.25 5.75 4 6.25 1 6.25 1
KIP / FT
4 4 4 4 1.25 6.25
Fe = 22 #4@12" T #4@12" B PLUMBING PIPE SLEEVE
KIP / FT #4 @ 12" T 4 THRU BEAM.
6
PB108 (36x21)
4 3.5 6.25 1 6.25 1
CB910 (36x48)
CONT. #4@12" B Fe = 18
PB105A (36x21)
PB124 (20x21)
PB102 (36x21)
Fe = 22 4 4 4 4 6 1 4
Fe = 18
CONSTRUCTION DOCUMENTS
12" CLOSURE 1' - 6" 9' - 0"
CABLE RAIL SYSTEM
WALL - TYP.
CB104 (16x21)
PLUMBING PIPE SLEEVE CABLE RAIL SYSTEM
THRU BEAM. #4@12" T ANCHOR WALL
#4@12" T
8' - 7"
8'-7"
Fe = 18 4 4 4 4 6 1 6.25 5.75 6.25 3.5 6.25 1 6.25 1
KIP / FT 3"
2
S404
3
1 PB145 (36x21) PB146 (36x21) PLUMBING PIPE SLEEVE PB147 (36x21)
PB143 (66x21) PB144 (66x21) THRU FLOOR
9' - 6"
458'-6"
8" ONE WAY P.T.
SLAB - TYP. U.N.O.
#4@12" T
CB909 (36x48)
PB111 (36x21)
PB111 (36x21)
#4@12" B #4@12" B #4@12" B #4@12" B
PB101 (36x21)
PB104 (36x21)
PB107 (36x21)
KIP / FT
45' - 0"
#4@12" T #4@12" T
1' - 7" EDGE OF
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
S403
OPEN
PB130 (36x21) PB131 (36x21) PB132 (36x21) PB133 (36x21) PB134 (36x21) PB135 (36x21)
Revision
1
No. Date Description
1 05.26.2023 Addendum No. 1
CB901 (36x36) CB902 (36x36) CB903 (36x36) CB903 (36x36) CB903 (36x36) CB904 (36x36)
1
S404
MATCHLINE - WEST
MATCHLINE - EAST
CONT. CLOSURE
BEAM TYP
12" CLOSURE
NOTES: WALL - TYP.
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM REINFORCING
SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS FOR POST
TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’
INDICATED DEPTH IN BEAM TAG A E M
6. REFER TO SHEETS S412, AND S413 FOR ONE WAY POST TENSIONED CONCRETE SLAB FRAMING AND CONSTRUCTION DETAILS
7. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND CONSTRUCTION DETAILS.
8. INDICATES TOPPING SLAB. REFER TO REFER TO 3/S422 FOR CONSTRUCTION DETAILS 6
9. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
10. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
11. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS. B1 FRAMING PLAN - WEST N
12. COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED ON PLANS
NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO DETAIL 1&2/S413 FOR SLEEVES
1 1/8" = 1'-0"
B1 FRAMING PLAN -
THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601 THROUGH CONCRETE BEAMS PART A
1
13. REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH ELECTRICAL
PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
PART A
14. REFER TO THE ARCHITECTURAL PLAN FOR BOLLARD LOCATION AND TYPE.
15. REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410, AND S411 FOR
5/25/2023 4:01:34 PM
KJM
E F H I J K L M M.1
Checked By:
Drawn By:
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0" 8' - 9"
GreshamSmith.com
3' - 0"
10"
6
PB136 (36x21) PB159 (36x21) PB139 (36x21) PB140 (36x21) PB141 (36x21) PB142 (36x21)
PB122 (42x21)
PB120 (36x21)
1.25 6.25 1.25 1 Seckman
15' - 9"
6.5 OPEN
12' - 10 5/8"
Reid, Inc.
Fe = 22 6
Fe = 19.5 KIP / FT #4@12" B 2995 Sidco Drive
S423
KIP / FT Nashville, TN 37204
T & S #4 @ 12" EDGE OF SLAB 8" ONE WAY P.T. (615) 383-1113
B - TYP. CB107 (30x72*) SLAB - TYP. U.N.O.
CB106 (30x42*) FAX: (615) 386-8469
www.ssr-inc.com
PB106 (36x21)
PB103 (36x21)
PB125 (20x21)
5
CB915 (36x48)
#4@12" T #4@10" T -13' - 0"
5
SSR Project #: 21640780
PB129 (36x21)
PB118 (36x21)
#4 @ 10" T 4 1 6.25 1.5 6.25 1.5 6
#4@12" B #4@12" B #4@10" B
Fe = 21
4 4 4 4 KIP/FT
8" ONE WAY P.T. 10" ONE WAY P.T. 10" ONE WAY P.T.
PB161 (36x21)
SLAB - TYP. U.N.O. SLAB SLAB AT RAMP 9' - 6" EDGE OF
PB121 (42x21)
1
29' - 3"
2
5
S423
#4@12" T #4@12" T
#4@12" B ONCOLOGY
S423 #4@12" B PB153 (66x21)
PB146 (36x21) CB237 (30X54*) CB107 (30x102*) PB160 (36x21) #4 @ 12" B PB151 (36x21) 3"
PB147 (36x21) PB155 (33x21) LO 5
PB152 (66x21)
2
4 #4@12" T
7' - 3"
Fe = 18 EDGE OF SLAB 4 1 6.25 4 6.25 5.00 6.25 1 6 4 4 4 4 Fe = 18
S8
S423
S7
KIP / FT KIP / FT
S8
PB117 (36x21)
#4 @ 12" T 4
PLUMBING PIPE SLEEVE S7 3
#4 @ 12" B CB102 (16x21) CB103 (16x21) S423 CB101 (16x21) #4 @ 12" T
THRU BEAM. S423 #4@12" B
OPEN
#4 @ 12" T 12" CLOSURE
CB104 (16x21)
Fe = 18 1 6.25 1 4 4 1 6.25 3.5 4 1 6
4 4 4 4 4 Fe = 22 WALL - TYP.
KIP / FT 14' - 2 3/4" Fe = 21
S7
PB128 (24x21)
PB105 (36x21)
PB102 (36x21)
PB124 (20x21)
PB115 (33x21)
PB108 (36x21)
3" PIPE, 5" SLEEVE FROM LEVEL B2 KIP / FT KIP / FT
#4 @ 12" T
PB113 (33x21)
14' - 4"
30' - 0"
CB914 (36x48)
PB166 (25x21)
19' - 6"
PB127 (24x21)
11' - 4" 1' - 6" 3'-0"
Fe = 18 1 6.25 1 4 6' - 11"
KIP / FT 4 #4 @ 12" T 1 6.25 1 3.5 4
HSS8x4x3/8 HSS8x4x3/8 Fe = 18
CABLE RAIL SYSTEM #4 @ 12" T KIP / FT
6.25 #4@12" B
HSS8x4x3/8
#4 @ 12" B S8 #4 @ 12" B #4@12" T 2
11' - 4"
CABLE RAIL SYSTEM
#4@12" B CB101 (16x21)
ANCHOR WALL 6' - 11" S403
4 1 6.25 1 1 6 4 4 4 4
8' - 5"
CONSTRUCTION DOCUMENTS
1 6.25 1 8" CONC. KIP / FT
Fe = 18 6.25 6.25
SLAB 6.25 3.75 5.00 PB153 (66x21)
KIP / FT
3"
3
PB146 (36x21) PLUMBING PIPE SLEEVE PB147 (36x21) PB149 (36x21) PB150 (36x21) PB151 (36x21) 1
PB148 (42x21) 1
THRU FLOOR PB152 (66x21) PLUMBING PIPE SLEEVE
PLUMBING PIPE SLEEVE THRU BEAM.
THRU BEAM
BOLLARD, SEE ARCH.
FOR TYPE.
#4@12" T #4@12" T T & S #4 @ 12"
1 B - TYP.
PB104 (36x21)
PB101 (36x21)
PB107 (36x21)
PB123(20x21)
PB111 (36x21)
PB112 (48x21)
PB114 (48x21)
#4@12" B #4@12" B
PB116 (36x21)
PB111 (36x21)
458'-6"
8" ONE WAY P.T.
SLAB - TYP. U.N.O.
1.25 6.25 1.25 6.5 1.0 6.5 1.25 6.25 1.25 6.25 1.25 6.25 1.25 6 4 4 4 4 Fe = 19.5
KIP / FT
45' - 0"
CB913 (36x48)
#4@12" T #4@12" T
#4@10" B
#4@12" T #4@12" T #4@12" T
PB134 (36x21) PB135 (36x21) PB136 (36x21) PB137 (36x21) PB138 (36x21) PB139 (36x21) PB140 (36x21) PB141 (36x21) PB142 (36x21) 1
1' - 7"
3"
6' - 7"
CB903 (36x36) CB904 (36x36) CB905 (36x48) CB906 (36x36) CB906 (36x36) CB906 (36x36) CB907 (36x36) CB908 (36x36)
Revision
1
1 S403 No. Date Description
12" CLOSURE
MATCHLINE - WEST
WALL - TYP.
LIMITS OF
EXCAVATION
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM REINFORCING
SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS FOR POST
TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’
INDICATED DEPTH IN BEAM TAG A E M
6. REFER TO SHEETS S412, AND S413 FOR ONE WAY POST TENSIONED CONCRETE SLAB FRAMING AND CONSTRUCTION DETAILS
7. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND CONSTRUCTION DETAILS.
8. INDICATES TOPPING SLAB. REFER TO REFER TO 3/S422 FOR CONSTRUCTION DETAILS
9. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES. 6
10. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
11. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
12. COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED ON PLANS B1 FRAMING PLAN - EAST N
NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO DETAIL 1&2/S413 FOR SLEEVES 1 1/8" = 1'-0"
B1 FRAMING PLAN -
THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601 THROUGH CONCRETE BEAMS
13. REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH ELECTRICAL PART B
1 PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
14. REFER TO THE ARCHITECTURAL PLAN FOR BOLLARD LOCATION AND TYPE.
PART B
15. REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410, AND S411 FOR
CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
5/25/2023 4:01:35 PM
1
16. ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE BY CONTRACTOR.
19.
REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR REQUIREMENTS DIFFER FROM WHAT IS SHOWN.
17. REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION DESIGN IS THE
RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR FRAMING WITH CONCRETE FRAMING.
18. WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT DIFFERS THAN WHAT IS SHOWN.
INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS.
S2B1B
20. INDICATES CONC. CRASH WALL BELOW CMU WALL. SEE DETAIL 6/S410.
KEYPLAN 44791.01
04/27/2023
1
KJM
0.1A A B C D E
GreshamSmith.com
8' - 9" 15' - 0" 30' - 0" 30' - 0" 30' - 0"
3' - 0"
MIN.
Smith
Seckman
1' - 7"
6 Reid, Inc.
2995 Sidco Drive
PB156 (36x21)
PB130 (36x21) PB131 (36x21) PB132 (36x21) Nashville, TN 37204
(615) 383-1113
PB110 (36x21)
4 4 4 3.5 6.25 1 6.25 1 4 FAX: (615) 386-8469
15' - 9"
Fe = 18 www.ssr-inc.com
KIP / FT
T & S #4 @ 12" 5" SLAB ON GRADE REINF WI #3 @12"O.C E.W. SSR Project #: 21640780
9 1/2"
B - TYP. OVER 15 MIL VAPOR BARRIER AND 12"
GRANULAR FILL
5
6' - 0" 448'-6"
1
PB103 (36x21)
PB106 (36x21)
9' - 8 1/2"
PB125 (20x21)
#4@12" B #4@12" B
#4@12" T #4@12" T
TENNESSEE
PB109 (36x21)
8
#4@12" T
9' - 6" EDGE RAMP5.26% S401
8" ONE WAY P.T. DOWN
ONCOLOGY
29' - 3"
Fe = 18 4 4 4 6.25 1 6.25 1 4
KIP / FT
4 #4 @ 12" T
7' - 0"
Fe = 18
KIP / FT
6.25 4.0
#4@12" T
14' - 11"
#4@12" B
4 4 4 4 1 9
6.25
S401
2" GAP
4 2.0 4 CABLE RAIL SYSTEM
#4@12" B
11' - 8 1/4"
Fe = 18
PB124 (20x21)
PB102 (36x21)
PB105 (36x21)
PB108 (36x21)
KIP / FT
PB158 (24x28 / 21
30' - 0"
Fe = 22 4 4 4 4 6.25 1 4
CONSTRUCTION DOCUMENTS
KIP / FT
UP DN #4@12" T
3' - 0" #4 @ 12" T
14' - 11"
EXCAVATED ROCK FACE 1' - 6" CB104 (16x21)
MIN. #4@12" T
11' - 4"
Fe = 18 4 4 4 4 6.25 1 6.25 5.25 6.25 4.0 6.25 1 6.25 1
KIP / FT
1 3"
2
3 S404
B2 ELEV.
8" ONE WAY P.T.
ESTIMATED LIMITS OF PERMANENT SHOTCRETE WALL
PB111 (36x21)
PB111 (36x21)
#4@12" B #4@12" B
APPROX. AREA 52' x 10' = 520 SQ.FT.
KIP / FT
45' - 0"
PB104 (36x21)
PB107 (36x21)
PB123 (20x21)
PB101 (36x21)
T & S #4 @ 12"
B - TYP.
6' - 0"
1
8' - 11"
S404
PB130 (36x21) PB131 (36x21) PB132 (36x21) PB133 (36x21) PB134 (36x21) PB135 (36x21)
Revision
1
No. Date Description
3' - 0"
MIN.
1' - 7"
MATCHLINE - WEST
MATCHLINE - EAST
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM REINFORCING
SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS FOR POST
TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’
INDICATED DEPTH IN BEAM TAG
6. REFER TO SHEETS S412, AND S413 FOR ONE WAY POST TENSIONED CONCRETE SLAB FRAMING AND CONSTRUCTION DETAILS
7. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND CONSTRUCTION DETAILS. A E M
8. INDICATES TOPPING SLAB. REFER TO REFER TO 3/S422 FOR CONSTRUCTION DETAILS
9. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
10. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
11. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS. 6
12. COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED ON PLANS
NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO DETAIL 1&2/S413 FOR SLEEVES
THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601 THROUGH CONCRETE BEAMS B2 FRAMING PLAN - WEST
13. REFER DETAIL 2/414 FOR REINFORCING ABOUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH ELECTRICAL 1 1/8" = 1'-0" N
B2 FRAMING PLAN -
1 PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
14. REFER TO THE ARCHITECTURAL PLAN FOR BOLLARD LOCATION AND TYPE. PART A
15. REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410, AND S411 FOR PART A
CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
16. ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE BY CONTRACTOR.
REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR REQUIREMENTS DIFFER FROM WHAT IS SHOWN.
5/25/2023 4:01:36 PM
1
17. REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION DESIGN IS THE
19.
20.
RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR FRAMING WITH CONCRETE FRAMING.
18. WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT DIFFERS THAN WHAT IS SHOWN.
INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS.
INDICATES CONC. CRASH WALL BELOW CMU WALL. SEE DETAIL 6/S410.
S2B2A
1
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
E F H I J K L M M.1
Checked By:
Drawn By:
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0" 8' - 9"
GreshamSmith.com
3' - 0"
MIN.
1' - 7"
1' - 7"
1' - 7"
6
PB136 (36x21) PB137 (36x21) PB138 (36x21) PB139 (36x21) PB140 (36x21) PB141 (36x21) PB142 (36x21)
8' - 11"
OPEN
10"5' - 3 1/8"
PB120 (36x21)
Smith
Seckman
15' - 9"
PB122 (42x21)
Reid, Inc.
2995 Sidco Drive
Nashville, TN 37204
10" ONE WAY P.T. SLAB (615) 383-1113
PB106 (36x21)
PB103 (36x21)
PB119 (36x21)
PB129 (36x21)
PB121 (42x21)
PB118 (36x21)
PB125 (20x21)
65' - 0"
5" SLAB ON GRADE REINF W/ #3 @12"O.C E.W.
OVER 15 MIL VAPOR BARRIER AND 12" 8" ONE WAY P.T.
RAMP UP
GRANULAR FILL SLAB TYP. U.N.O. 3' - 0"
29' - 3"
7' - 3"
PB154 (36x21) 4 1 6.25 1 6.25 4.25 6.25 5.75 6.25 1 6.25 4 4 4 4
S423 Fe = 18
S8
S7
KIP / FT
S8
S7 3
14' - 11"
14' - 11"
#4 @ 12" T #4 @ 12" T
CB102 (16x21) CB103 (16x21)
9 1' - 3" S423
#4 @ 12" B #4 @ 12" T CB101 (16x21)
CB104 (16x21)
S401 11' - 4"
10' - 5 1/4"
PB113 (33x21)
PB126 (24x21)
CABLE RAIL SYSTEM
PB127 (24x21)
4 6.25 1 6.25 4.25 4 4 1 6.25 4 4 4 4 Fe = 22
2" GAP
PB128 (24x21)
PB117 (36x21)
PB105 (36x21)
PB102 (36x21)
PB124 (20x21)
S7
PB108 (36x21)
Fe = 18 KIP / FT
1
12' - 5"
30' - 0"
PB115 (33x21)
#4 @ 12" T
HSS8x4x3/8
6.25 CB101 (16x21) #4@12" B
#4@12" B #4@12" T DN UP
14' - 11"
14' - 11"
#4 @ 12" B #4 @ 12" B
12' - 10"
1' - 6" 6' - 11" 8" CONC.
10' - 4"
4 1 6.25 1 6.25 4.25 5.75 6.25 1 6.25 4 4 4 4
CONSTRUCTION DOCUMENTS
1 6.25 1 4 KIP / FT
6.25 1' - 6" 1
1' - 6"
3"
1' - 6"
3
PB150 (36x21) 1
PB146 (36x21) PB147 (36x21) PB148 (42x21) PB149 (36x21) PB151 (36x21)
PLUMBING PIPE SLEEVE PB152 (66x21) PB153 (66x21)
PB111 (36x21)
PB111 (36x21)
PB112 (48x21)
PB114 (48x21)
PB116 (36x21)
PB107 (36x21)
PB104 (36x21)
PB101 (36x21)
PB123 (20x21)
10" ONE WAY P.T.
8" ONE WAY P.T.
65' - 0"
SLAB THIS BAY
SLAB TYP. U.N.O. 8" ONE WAY P.T.
SLAB TYP. U.N.O.
1.25 6.25 1.25 6.5 1 6.5 1.25 6.25 1.25 6.25 1.25 6.25 1.25 6.25 Fe = 19.5
KIP / FT
45' - 0"
PB134 (36x21) PB135 (36x21) PB136 (36x21) PB137 (36x21) PB138 (36x21) PB139 (36x21) PB141 (36x21) PB142 (36x21) 1
PB140 (36x21)
1' - 7"
3"
3' - 0"
6' - 7"
MIN.
CABLE RAIL SYSTEM
Revision
9' - 3"
1 No. Date Description
MATCHLINE - WEST
40' - 0"
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM REINFORCING
SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS FOR POST
TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’
INDICATED DEPTH IN BEAM TAG
6. REFER TO SHEETS S412, AND S413 FOR ONE WAY POST TENSIONED CONCRETE SLAB FRAMING AND CONSTRUCTION DETAILS
7. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND CONSTRUCTION DETAILS. A E M
8. INDICATES TOPPING SLAB. REFER TO REFER TO 3/S422 FOR CONSTRUCTION DETAILS
9. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
10. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
11. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS. 6
12. COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED ON PLANS
NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO DETAIL 1&2/S413 FOR SLEEVES
B2 FRAMING PLAN - EAST
THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601 THROUGH CONCRETE BEAMS
13. REFER DETAIL 2/414 FOR REINFORCING ABOUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH ELECTRICAL 1 1/8" = 1'-0" N
1 PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
14. REFER TO THE ARCHITECTURAL PLAN FOR BOLLARD LOCATION AND TYPE. PART B B2 FRAMING PLAN -
15. REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410, AND S411 FOR
CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
PART B
16. ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE BY CONTRACTOR.
REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR REQUIREMENTS DIFFER FROM WHAT IS SHOWN.
5/25/2023 4:01:38 PM
1
17. REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION DESIGN IS THE
19.
20.
RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR FRAMING WITH CONCRETE FRAMING.
18. WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT DIFFERS THAN WHAT IS SHOWN.
INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS.
INDICATES CONC. CRASH WALL BELOW CMU WALL. SEE DETAIL 6/S410.
S2B2B
1
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
0.1A A B C D E
GreshamSmith.com
8' - 9" 15' - 0" 30' - 0" 30' - 0" 30' - 0"
3'-0"
MIN.
W60
Smith
2"
2"
2"
2"
Seckman
2' - 6"
3' - 6"
F60 F60B
2"
F48 F60A F60A [437' - 0"] 2995 Sidco Drive
[437' - 0"]
[437' - 0"] [437' - 0"] [437' - 0"] Nashville, TN 37204
15' - 9"
18" THICK 6'-0"⌀ x 9'-6" www.ssr-inc.com
WALL DEEP SUMP
5' - 3" 9" PUMP. SEE
PLUMBING SSR Project #: 21640780
9 1/2"
36' - 6"
1' - 0"
W18 [438' - 6"]
10' - 6"
FOUNDATION F72C
12" THICK (-34'-6') [442' - 3"]
WALL 3"
W60
18" THICK WALL
GRANULAR FILL. F.F.E. = -33'-0"
ROCK FILL
1' - 3"
4 F72
F48 [437' - 0"]
[437' - 0"] 1
W18
1 [438' - 6"]
F24
F24
[438' - 6"] 9
W60
[438' - 6"]
S401
F24 W60
F24
[438' - 6"] [438' - 6"]
F24 FTG. FOR STAIR POSTS. [-34'-6"]
COORD. w/ STAIR SUPPLIER
30' - 0"
CONSTRUCTION DOCUMENTS
W18
W18
3' - 0" W18
[438' - 6"]
15' - 1"
MIN.
9
3" S410 W18
F60A [438' - 6"] F72
[437' - 0"] [437' - 0"]
3
F48
[437' - 0"] F72 F72
[437' - 0"] [437' - 0"]
1
FOUNDATION
[437' - 0"]
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
1' - 6"
7
S400
10' - 6"
4 F48
S402 [437' - 0"] F60A F60A F60 F60 F60
[437' - 0"] [437' - 0"] [437' - 0"] [437' - 0"] [437' - 0"]
Revision
1
2"
2"
2"
2"
2"
No. Date Description
1' - 0"
3' - 0"
MIN.
MATCHLINE - WEST
MATCHLINE - EAST
NOTES:
A E M
1. ALL FOUNDATIONS ARE CENTERED ON WALLS AND COLUMNS UNLESS NOTED OTHERWISE
ON THE PLANS AND DETAILS
2. F#, AND W# REFER TO SPREAD AND CONTINUOUS WALL FOUNDATIONS. REFER TO SHEET
S401 FOR FOUNDATION SCHEDULE AND FOUNDATION DETAILS. 6
3. REFER OT SHEET S400 FOR SLAB ON GRADE CONSTRUCTION DETAILS. B3 FOUNDATION PLAN - WEST
4. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
5. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
1 1/8" = 1'-0" N
6. EXCAVATION LIMITS SHOWN ARE MINIMUM CLEARANCES FOR POST TENSION INSTALLATION.
CONTRACTOR SHALL FIELD VERIFY EXCAVATION DIMENSIONS
AFTER EXCAVATION AND COORDINATE WITH ENGINEER PRIOR TO FABRICATION AND PART A B3 FOUNDATION
CONSTRUCTION OF CONCRETE COLUMNS OR WALLS. PLAN - PART A
7. COORDINATE DRAIN LOCATIONS, DRAIN LINE AND ANY UNDERGROUND DRAIN OR SANITARY
LINE WITH PLUMBING DRAWINGS.
8. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
5/25/2023 4:01:39 PM
1
9. REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS.
S2B3A
1
10. INDICATES CONC. CRASH WALL BELOW CMU WALL. SEE DETAIL 6/S410.
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
E F H I J K L M M.1
Checked By:
Drawn By:
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0" 8' - 9"
GreshamSmith.com
6
6 S402
S402 7
S402
222 Second Avenue South
Suite 1400
Nashville, TN 37201
615.770.8100
F48
[437' - 0"]
3'-0"
1' - 0"
MIN.
2"
2"
1' - 7"
6
2"
2"
2"
2' - 6"
3' - 6"
3' - 6"
3' - 6"
2"
2"
2"
F60 F60 F60A F60A
F60B 4
8' - 11"
F72C [437' - 0"] [437' - 0"] [437' - 0"] [437' - 0"]
F72C [438' - 6"] S402
[442' - 3"]
[442' - 3"]
7
F72C
[440' - 0"] EXCAVATED ROCK FACE
7 Smith
S400 Seckman
15' - 9"
1' - 0"
2995 Sidco Drive
Nashville, TN 37204
(615) 383-1113
5 FAX: (615) 386-8469
REINF. MAT W/ #6 @8"O.C www.ssr-inc.com
5 E.W. TOP AND BOTTOM
9" 6' - 3" S402
F72A 90° HOOK EACH END
F72C F72B F72B
SSR Project #: 21640780
[438' - 6"]
[442' - 3"] [442' - 3"] [440' - 0"] 5" SLAB ON GRADE REINF W/ #3 @12"O.C E.W.
OVER 15 MIL VAPOR BARRIER AND 4"
GRANULAR FILL.
9
S400
RAMP UP 5" SLAB ON GRADE REINF W/ #3 @12"O.C E.W.
OVER 15 MIL VAPOR BARRIER AND 4"
EXCAVATED ROCK FACE 3' - 0"
29' - 3"
19' - 6"
[438' - 6"]
[438' - 6"]
COORD. w/ STAIR SUPPLIER
ELEV. = -35' - 10"
W18
ELEV. = -35'-10"
ELEV. = -35'-10"
W18
ELEV. = -34' - 6"
ELEV. = -35'-10"
ELEV. = -37'-2"
ELEV. = -37'-2"
ELEV. = -37'-2"
ELEV. = -38'-6"
OF POST FOUNDATIONS
HSS8x4x3/8 1
19' - 5 7/8"
HSS8x4x3/8
S402 W18
15' - 1"
15' - 1"
15' - 1"
ELEVATOR ELEVATOR
PIT PITS [438' - 6"]
11' - 4"
2 9
CONSTRUCTION DOCUMENTS
8' - 4" FROM LEVEL B2 THRU LEVEL W18 3"
B1 FLOOR (SHOWN ON LEVEL [438' - 6"]
ABOVE AS WELL)
3
F48
F72 F72 F72 F72 [437' - 0"]
F84 F84 F60A
[437' - 0"] [437' - 0"] [437' - 0"] [437' - 0"]
[433' - 0"] [433' - 0"] [437' - 0"]
1
42" THICK MAT
UNDER ELEVATORS
BOLLARD
SEE ARCH. FOR
TYPE
1
5" SLAB ON GRADE REINF W/ #3 @12"O.C E.W.
OVER 15 MIL VAPOR BARRIER AND 4"
GRANULAR FILL. F.F.E. = -33'-0"
45' - 0"
SIM.
4
S402
7 1
EXCAVATED ROCK FACE F60A
S400 3"
F60A F60 [437' - 0"] F48
F60A F60 F60A
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
2"
2"
2"
2"
2"
1' - 0"
2"
2"
3' - 0"
MIN.
REINF W/ #6 @8" E.W.
1' - 0" T&B 90° HOOK EACH END Revision
18" THICK
WALL
1' - 0"
8' - 6" 9" No. Date Description
MATCHLINE - WEST
NOTES:
1. ALL FOUNDATIONS ARE CENTERED ON WALLS AND COLUMNS UNLESS NOTED OTHERWISE
ON THE PLANS AND DETAILS
2. F#, AND W# REFER TO SPREAD AND CONTINUOUS WALL FOUNDATIONS. REFER TO SHEET
S401 FOR FOUNDATION SCHEDULE AND FOUNDATION DETAILS.
3. REFER OT SHEET S400 FOR SLAB ON GRADE CONSTRUCTION DETAILS.
4. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
5. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
6. EXCAVATION LIMITS SHOWN ARE MINIMUM CLEARANCES FOR POST TENSION INSTALLATION.
CONTRACTOR SHALL FIELD VERIFY EXCAVATION DIMENSIONS A E M
AFTER EXCAVATION AND COORDINATE WITH ENGINEER PRIOR TO FABRICATION AND
CONSTRUCTION OF CONCRETE COLUMNS OR WALLS.
7. COORDINATE DRAIN LOCATIONS, DRAIN LINE AND ANY UNDERGROUND DRAIN OR SANITARY
6
LINE WITH PLUMBING DRAWINGS.
8. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
9. REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS.
10. INDICATES CONC. CRASH WALL BELOW CMU WALL. SEE DETAIL 6/S410.
1 B3 FOUNDATION PLAN - EAST N PART B B3 FOUNDATION
1 1/8" = 1'-0"
PLAN - PART B
5/25/2023 4:01:39 PM
S2B3B
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
STRUCTURAL STEEL SUPPLEMENTARY NOTES
DESIGN CRITERIA: A. PROVIDE ALL TEMPORARY BRACING, GUYING OR OTHER MEANS TO AVOID EXCESSIVE STRESSES AND TO HOLD
STRUCTURAL ELEMENTS IN PLACE DURING CONSTRUCTION. THE STRUCTURE SHOULD NOT BE CONSIDERED STABLE
A. STRUCTURAL STEEL FABRICATION, ERECTION, AND DETAILING SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
UNTIL ALL STRUCTURAL ELEMENTS HAVE BEEN CONSTRUCTED. CONTRACTOR IS RESPONSIBLE FOR ERECTION OF
AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES
AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION
THE STRUCTURE, THE SEQUENCE OF CONSTRUCTION, AND DESIGN OF SHORING, FALSEWORK, AND TEMPORARY
BRACING REQUIRED TO CONSTRUCT THE STRUCTURE.
SHEET GENERAL NOTES
GENERAL NOTES:
MVW
A. REFER TO OVERALL SHEET INDEX ON SHEET G001 FOR STRUCTURAL SHEET INDEX
KJM
B. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR CONSTRUCTION MEANS,
Approved By: DJS
A. STRUCTURAL STEEL FABRICATOR SHALL BE AISC CERTIFIED, CATEGORY Sbd, OR HAVE AN INDEPENDENT TESTING
LABORATORY APPROVED BY THE ARCHITECT OR ENGINEER CERTIFY THAT THE FABRICATION PROCEDURES USED METHODS, TECHNIQUES, PROCEDURES OR SEQUENCES. THIS IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
ARE IN ACCORDANCE WITH AISC SPECIFICATIONS AND THESE REQUIREMENTS. (USE THIS OPTION FOR SMALL THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR, OR
ANY OTHER PERSONS PERFORMING THE WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN
Checked By:
B. ALL STRUCTURAL STEEL AND LINTELS EXPOSED TO THE WEATHER SHALL BE HOT DIPPED GALVANIZED.
C. WHERE STEEL BEAMS ARE SHOWN CONTINUOUS OVER SUPPORTS, COLUMNS OR WALLS, PROVIDE 3/8” THICK FULL C. VERIFY ALL DIMENSIONS WITH THE ARCHITECTURAL DRAWINGS.
DEPTH WEB STIFFENERS ON EITHER SIDE OR WEB CENTERED OVER SUPPORT, COLUMN, OR WALL.
D. SEE THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR EMBEDS, OPENINGS, SLEEVES, GreshamSmith.com
D. ANGLE FRAME MEMBERS AROUND TRENCHES, PITS, OPENINGS, ETC. SHALL BE MITERED, WELDED, AND GROUND ETC. NOT SHOWN ON THE STRUCTURAL DRAWINGS.
SMOOTH. ALL ARCHITECTURALLY EXPOSED STEEL SHALL HAVE WELDS GROUND SMOOTH.
E. ALL STRUCTURAL OPENINGS AROUND OR AFFECTED BY MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT SHALL
E. PROVIDE MIN. 1 1/2" NON-METALLIC NON-SHRINK GROUT MEETING ASTM C-1107 UNDER COLUMN BASE PLATES, U.N.O. BE VERIFIED WITH EQUIPMENT PURCHASED BEFORE PROCEEDING WITH STRUCTURAL WORK AFFECTED.
LEVEL COLUMNS UTILIZING LEVELING NUT OR SHIM PLATES PRIOR TO GROUTING.
F. PROVIDE L3x3x1/4” ANGLE FRAMES ATTACHED TO THE SUPPORTING STRUCTURE AT ALL OPENINGS IN THE ROOF F. STRUCTURAL CONTRACTOR DOCUMENTS ARE BEING ISSUED IN ADVANCE OF OTHER DISCIPLINES( MEP,
UNLESS NOTED OTHERWISE. ARCHITECTURAL. THE CONTRACTOR SHALL COORDINATE STRUCTURAL PLANS WITH OTHER DISCIPLINES AS THEY
ARE ISSUED. NOTIFY ENI GINNER OF ANY DISCREPANCIES
G. PROVIDE C8x11.5 CHANNEL FRAMING ATTACHED TO THE SUPPORTED STRUCTURE AT ALL OPENINGS IN THE FLOOR
FRAMING UNLESS SHOWN OTHERWISE ON PLANS. 222 Second Avenue South
G. STRUCTURAL ENGINEER OF RECORD FOR THIS PROJECT IS NOT RESPONSIBLE FOR THE DESIGN OF STEEL STAIRS,
HANDRAILS, COLD FORMED METAL FRAMING, GLAZING, SHORING, FORMWORK, MEP ATTACHMENTS OR OTHER
Suite 1400
WELDS:
A. ALL WELDS SHALL BE MADE WITH ELECTRODES TYPE: E70XX SYSTEMS NOT INDICATED ON THE STRUCTURAL DOCUMENTS. REFER TO SPECIFICATIONS FOR THESE ITEMS FOR Nashville, TN 37201
DEFERRED DESIGN SUBMITTAL REQUIREMENTS. 615.770.8100
B. MINIMUM SIZE OF ALL FILLET WELDS SHALL BE 3/16” AND SHALL CONFORM TO SECTION J2 AISC SPECIFICATIONS EVEN
IF SHOWN OTHERWISE ON ARCHITECTURAL, MECHANICAL, OR STRUCTURAL DRAWINGS.
H. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE SEAL OF AN
C. ALL WELDS ALONG THE LENGTH OF MEMBERS INDICATED ON ARCHITECTURAL OR STRUCTURAL DRAWINGS, BUT NOT ENGINEER REGISTERED IN THE STATE OF THE PROJECT. REFER TO DEFERRED SUBMITTAL NOTES FOR FURTHER
SIZED SHALL BE A MINIMUM OF A 3" AT 12” O.C, 3/16" FILLET WELD EACH SIDE. REQUIREMENTS
D. ALL WELDS SHALL BE PERFORMED BY CERTIFIED WELDERS FOR THE TYPE OF WELDING PERFORMED IN ACCORDANCE
WITH THE WELDING CODE AWS D1.1, STRUCTURAL WELDING CODE. I. GENERAL CONTRACTOR MUST REVIEW AND APPROVE SHOP DRAWINGS PRIOR TO SUBMITTAL TO
ARCHITECT/ENGINEER. SUBMITTALS WHICH DO NOT CONTAIN THE CONTRACTORS SHOP DRAWING OR STAMP OR
CONNECTIONS: HAVE BEEN MERELY "RUBBER STAMPED" SHALL BE RETURNED WITHOUT REVIEW.
A. ALL BEAM TO BEAM AND BEAM TO COLUMN CONNECTIONS SHALL BE BEARING TYPE CONNECTIONS AND BOLTS SHALL
BE 3/4" OR 1" DIAMETER (ASTM F3125, GRADE A325 OR A490), UNLESS NOTED OTHERWISE (U.N.O.). ALL BOLTED
J. SUBMIT SHOP DRAWINGS THAT CONFORM TO THE REQUIREMENTS OF THE SPECIFICATIONS AND ADEQUATELY
Smith
CONNECTIONS SHALL BE INSTALLED USING EITHER TURN OF THE NUT METHOD OR DIRECT TENSION INDICATOR
INDICATE AND DETAIL THE STRUCTURAL ELEMENTS CONTAINED IN THE CONTRACT DOCUMENTS. REVIEW OF SHOP Seckman
METHOD, TYPICAL.
DRAWINGS/ SUBMITTALS BY THE ARCHITECT AND ENGINEER SHALL BE FOR GENERAL CONFORMANCE TO THE Reid, Inc.
CONTRACT DOCUMENTS INCLUDING REVIEW OF ARRANGEMENT, SIZES, AND DETAILS OF CONSTRUCTION. REVIEW OF
OTHER CONNECTIONS: SUBMITTALS AND SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THE REQUIREMENT OF THE CONTRACT 2995 Sidco Drive
ANCHOR BOLTS: ASTM F1554 ,GRADE 36 WITH HEAVY HEX NUTS DOCUMENTS. Nashville, TN 37204
(615) 383-1113
WELDED STUDS: ASTM A108, GRADE 1015 THRU 1020
FAX: (615) 386-8469
DEFORMED BAR ANCHORS: ASTM A706 K. DO NOT REPRODUCE STRUCTURAL ENGINEERS’ DRAWINGS. ERECTION AND SHOP DRAWINGS WILL NOT BE REVIEWED www.ssr-inc.com
IF ANY PORTION CONTAINS REPRODUCTIONS OF STRUCTURAL ENGINEERS’ DRAWINGS.
B. UNLESS NOTED OTHERWISE, BEAM TO BEAM AND BEAM TO COLUMN CONNECTIONS SHALL BE AISC SIMPLE FRAMING
CONNECTIONS UNLESS NOTED OTHERWISE.
L. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR SSR Project #: 21640780
C. FOR CONNECTION DETAILS, REFER TO DETAIL : 1/S430 OBTAINING CLARIFICATION FROM THE ARCHITECT BEFORE CONTINUING WITH CONSTRUCTION.
METAL DECKING
GENERAL NOTES:
A. ALL METAL DECKING SHALL BE INSTALLED WITH A MINIMUM OF THREE SPANS.
B. EACH DECKING PANEL SHALL BE CONNECTED TO SUPPORTING MEMBERS.
C. ADJACENT PANELS SHALL BE INTERCONNECTED WITH SIDE LAP FASTENERS AT EACH SPAN.
D. FOR CONNECTION DETAILS, REFER TO DETAIL: 3/S430
DESIGN CRITERIA:
A. DESIGN PER CURRENT EDITION OF: SDI
TENNESSEE
B. DECKING MATERIAL: G60 GALV. ,UNLESS NOTED OTHERWISE (U.N.O.)
METAL FLOOR DECKING
ONCOLOGY
MANUFACTURER: VULCRAFT (OR APPROVED EQUAL)
PROFILE: 3"
TYPE VLI
CONSTRUCTION DOCUMENTS
C. HEADED STUDS AND SHEAR STUDS SHALL NOT BE ARC (STICK) WELDED UNLESS APPROVED BY THE ENGINEER.
D. PRIOR TO POURING CONCRETE ON COMPOSITE DECK, ATTACHMENT OF SHEAR CONNECTORS TO STEEL BEAMS SHALL
BE TESTED, REFER TO SPECIFICATIONS.
E. ALL ARC SHIELDS (FERRULES) SHALL BE BROKEN OFF AND REMOVED.
F. WHERE NO SHEAR CONNECTORS ARE SHOWN FOR BEAMS WHOSE TOP FLANGE IS AGAINST DECK, PROVIDE SHEAR
CONNECTORS AT 12" O.C.
G. WHERE SHEAR STUDS ARE CALLED FOR, THEY SHALL BE CONSIDERED AS REPLACING PUDDLE WELDS ON A ONE FOR
ONE BASIS.
H. STEEL FLOOR DECK SHALL NOT BE LAPPED AT SUPPORTS.
I. GAGE AND WELDING FOR ALL EDGE ANGLE CLOSURES IS TO BE DETERMINED BY THE DECKING CONTRACTOR, AND
SHALL BE SUFFICIENT TO MAINTAIN STRAIGHT EDGE DURING CONCRETE POURING.
J. STEEL FABRICATOR SHALL PREPARE SHOP DRAWINGS SHOWING LOCATION OF ALL SHEAR CONNECTORS.
SAME MANNER AS DESCRIBED ABOVE. GIRDERS WITH DECK FLUTE PARALLEL TO THE SPAN SHALL HAVE STUDS
PLACED UNIFORMLY WITHIN THE ZONE INDICATED ON THE DRAWINGS.
H. AT COMPOSITE BEAMS PERPENDICULAR TO DECK SPAN, THE MAXIMUM SPACING OF STUDS SHALL BE 24" O.C.
I. AT COMPOSITE BEAMS OR GIRDERS PARALLEL TO DECK SPAN, THE MAX SPACING OF STUDS SHALL BE 32" O.C.
J. FOR MINIMUM TRAVERSE STUD SPACING, SHEAR STUDS IN GROUPS SHALL NOT BE SPACED CLOSER THAN 3".
K. STUDS WILL BE SPACED DIRECTLY OVER BEAM WEB FOR BEAMS HAVING A FLANGE THK. OF 0.300" OR LESS.
Revision
DEFERRED DESIGN SUBMITTALS No. Date Description
A. ALL DEFERRED SUBMITTALS SHALL BE DESIGNED AND ENGINEERED BY A 3RD PARTY ENGINEER HIRED BY THE
CONTRACTOR, VENDOR OR SUPPLIER. ALL DESIGN SUBMITTALS AND CALCULATIONS SHALL BE SIGNED AND SEALED
BY AN ENGINEER REGISTERED IN THE STATE OF THE PROJECT.
B. STRUCTURAL ENGINEER OF RECORD IS NOT RESPONSIBLE FOR THE DESIGN OF DEFERRED SUBMITTALS. DEFERRED
SUBMITTAL SPECIALTY ENGINEER SHALL BE RESPONSIBLE FOR THE DESIGN OF THE DEFERRED SUBMITTAL ELEMENTS
AND THERE CONNECTION TO THE SUPERSTRUCTURE.
C. DEFERRED DESIGN SUBMITTALS SHALL BE DESIGNED TO RESIST THE LOADS LISTED IN PROJECT "DESIGN CRITERIA"
ON THIS SHEET.
D. THE FOLLOWING IS A PARTIAL LIST OF THE DEFERRED DESIGN SUBMITTALS FOR THIS PROJECT. REFER TO
ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND CIVIL PLANS FOR OTHER DEFERRED DESIGN
SUBMITTALS.
1) TEMPORARY SHORING
2) PERMANENT SHORING - SHOTCRETE AND SOIL/ROCK NAILED
WALLS
3) POST TENSION DESIGN
4) CONCRETE FORMWORK
5) EXTERIOR WALL COLD FORMED METAL FRAMING
6) GLAZING SYSTEMS, STOREFRONT, CURTAIN WALL, ETC.
7) ANCHORAGE OF MECHANICAL, PLUMBING AND ELECTRICAL
COMPONENTS AND SYSTEMS INCLUDING ROOFTOP
EQUIPMENT TO SUPERSTRUCTURE
S002
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
IBC 2018 SPECIAL INSPECTIONS MASONRY INSPECTIONS STEEL INSPECTIONS
STATEMENT OF SPECIAL INSPECTIONS ***FOR OCCUPANCY CATEGORY I, II, III BUILDINGS***
THIS STATEMENT OF SPECIAL INSPECTIONS IS SUBMITTED AS REQUIRED FOR BUILDING PERMIT ISSUANCE IN ACCORDANCE WITH THE
SPECIAL INSPECTIONS AND STRUCTURAL TESTING REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE. THIS STATEMENT OF
ACI 530-13 TABLE 3.1.2: LEVEL B QUALITY ASSURANCE OTHER THAN STRUCTURAL STEEL
SPECIAL INSPECTIONS IS ONLY FOR THE STRUCTURAL PORTION OF THE WORK. REFER TO OTHER DISCIPLINES FOR OTHER SPECIAL MINIMUM TESTS
INSPECTION REQUIREMENTS FOR THIS PROJECT. REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE IN ACCORDANCE WITH ACI 530.1-13
THE OWNER OR REGISTERED DESIGN PROFESSIONAL IN CHARGE (ARCHITECT) ACTING AS THE OWNERS AGENT SHALL EMPLOY ONE OR ARTICLE 1.5.B.1.b.3 FOR SELF-CONSOLIDATING GROUT. REFERENCED
TYPE CONTINUOUS PERIODIC
MORE AGENCIES APPROVED BY THE BUILDING OFFICIAL TO PERFORM INSPECTIONS DURING CONSTRUCTION. THESE INSPECTIONS ARE STANDARD
MVW
VERIFICATION OF f'm AND f'AAC IN ACCORDANCE WITH ACI 530.1-13 ARTICLE 1.4 B PRIOR TO CONSTRUCTION, EXCEPT WHERE SPECIFICALLY
KJM
IN ADDITION TO SECTION 110 OF THE IBC. CONTRACTOR IS RESPONSIBLE TO ENSURE THE INSPECTOR IS PRESENT WHERE WORK EXEMPTED BY THIS CODE. 1. MATERIAL VERIFICATION OF COLD-FORMED DECK:
REQUIRES PERIODIC OR CONTINUOUS INSPECTION. 1A. IDENTIFICATION MARKINGS TO CONFORM TO ASTM
STANDARDS SPECIFIED IN THE APPROVED CONSTRUCTION
Checked By:
THE INSPECTOR SHALL KEEP RECORDS OF ALL INSPECTIONS AND SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL, REFERENCED
INSPECTION TASK CONTINUOUS PERIODIC
AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. DISCOVERED DISCREPANCIES SHALL BE BROUGHT TO THE STANDARD 1B. MANUFACTURER'S CERTIFIED TEST REPORTS. --- --- X
ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF SUCH DISCREPANCIES ARE NOT CORRECTED, THE DISCREPANCIES SHALL BE 1 VERIFY COMPLIANCE WITH THE APPROVED SUBMITTALS.
ACI 530.1: 1.5 --- X 2. COLD-FORMED STEEL DECK:
BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. A
FINAL REPORT DOCUMENTING ALL THE REQUIRED SPECIAL INSPECTIONS AND TESTING, AND CORRECTION OF ANY DISCREPANCIES 2. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE 2A. FLOOR AND ROOD DECK WELDS. AWS D1.3 --- X
NOTED PREVIOUSLY SHALL BE SUBMITTED TO THE BUILDING OFFICIAL PRIOR TO ISSUANCE OF A CERTIFICATE OF USE AND GreshamSmith.com
FOLLOWING ARE IN COMPLIANCE: 3. OPEN-WEB STEEL JOISTS AND JOIST GIRDERS
OCCUPANCY.
2A. PROPORTIONS OF SITE-PREPARED MORTAR. ACI 530.1: 2.1, 2.6A --- X 3A. INSTALLATION OF OPEN-WEB STEEL JOISTS AND JOIST
FABRICATIONS 2B. CONSTRUCTION OF MORTAR JOINTS. GIRDERS
ACI 530.1: 3.3B --- X
SPECIAL INSPECTIONS OF THE FABRICATION PROCESS SHALL NOT BE REQUIRED WHERE FABRICATION OF STRUCTURAL LOAD BEARING 3A.1 END CONNECTIONS - WELDING OR BOLTED IBC SECTION: 1705.2.3 --- X
2C. GRADE AND SIZE OF PRESTRESSING TENDONS AND
MEMBERS AND ASSEMBLIES IS BEING PERFORMED ON THE PREMISES OF A FABRICATOR IS REGISTERED AND APPROVED TO PERFORM ACI 530.1: 2.4B, 2.4H --- X
ANCHORAGES. 3A.2 BRIDGING - HORIZONTAL OR DIAGONAL
THE WORK WITHOUT SPECIAL INSPECTIONS. AT THE COMPLETION OF THE FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A
CERTIFICATE OF COMPLIANCE TO THE BUILDING OFFICIAL. 2D. LOCATION OF REINFORCEMENT, CONNECTORS, AND
PRESTRESSING TENDONS AND ANCHORAGES. ACI 530.1: 3.4, 3.6A --- X
THE SPECIAL INSPECTIONS ARE IN ADDITION TO THE MATERIAL TESTING AND INSPECTIONS LISTED IN THE CONTRACT SPECIFICATIONS. 3A.2.1 STANDARD BRIDGING IBC SECTION: 1705.2.3 --- X 222 Second Avenue South
CONTRACTOR IS TO COORDINATE SPECIAL INSPECTIONS, MATERIAL SPECIFIC TESTING AND INSPECTIONS WITH THE OWNER 2E. PRESTRESSING TECHNIQUE. ACI 530.1: 3.6B --- X 3A.2.2 BRIDGING THAT DIFFERS FROM THE SJI SPECIFICATIONS Suite 1400
FURNISHED SPECIAL INSPECTOR MATERIAL TESTING LABS. LISTED IN SECTION 2207.1 --- --- X
2F. PROPERTIES OF THIN-BED MORTAR FOR AAC MASONRY. Nashville, TN 37201
ACI 530.1: 2.1C X X
THE SPECIAL INSPECTIONS INDICATED HEREIN DO NOT RELIEVE THE CONTRACTOR FROM THEIR RESPONSIBILITIES. THE CONTRACTOR 4. COLD FORMED STEEL TRUSS SPANNING 60 FT OR GREATER 615.770.8100
SHALL PAY FOR ANY ADDITIONAL TESTING OR INSPECTION REQUIRED FROM WORK OR MATERIALS NOT IN CONFORMANCE WITH THE 3. PRIOR TO GROUTING, VERIFY THAT THE FOLLOWING ARE IN
CONTRACT DOCUMENTS. COMPLIANCE: 4A. VERIFY HE TEMPORARY INSTALLATION RESTRAINT / BRACING
THE STATEMENT OF SPECIAL INSPECTIONS INCLUDES REQUIRED VERIFICATION AND INSPECTION OF THE FOLLOWING: SECTIONS: 3A. GROUT SPACE. ACI 530.1: 3.2D, 3.2F --- X AND THE PERMANENT INDIVIDUAL TRUSS MEMBER RESTRAINT
/ BRACING ARE INSTALLED IN ACCORDANCE WITH THE IBC SECTION: 1705.2.4 --- X
3B. GRADE, TYPE, AND SIZE OF REINFORCEMENT AND ANCHOR APPROVED TRUSS SUBMITTAL PACKAGE.
1. CONCRETE INSPECTIONS BOLTS, AND PRESTRESSING TENDONS AND ANCHORAGES. ACI 530: 6.1 ACI
--- X
2. SOILS INSPECTIONS 530.1: 2.4, 3.4
6. MASONRY INSPECTIONS 3C. PLACEMENT OF REINFORCEMENT, CONNECTORS, AND ACI 530: 6.1, 6.2.1, 6.2.6, 6.2.7 ACI
PRESTRESSING TENDONS AND ANCHORAGES. --- X
8. STEEL INSPECTIONS OTHER THAN STRUCTURAL STEEL 530.1: 3.2E, 3.4, 3.6A
9. STRUCTURAL STEEL INSPECTIONS 3D. PROPORTIONS OF SITE-PREPARED GROUT AND Smith
PRESTRESSING GROUT FOR BONDED TENDONS ACI 530.1: 2.6B, 2.4G.1.b --- X Seckman
COMPONENTS PART OF THE MAIN WIND FORCE RESISTING SYSTEM AND SUBJECTED TO SPECIAL INSPECTIONS FOR WIND RESISTANCE: NONE
3E. CONSTRUCTION OF MORTAR JOINTS. ACI 530.1: 3.3B --- X Reid, Inc.
4. VERIFY DURING CONSTRUCTION: 2995 Sidco Drive
COMPONENTS PART OF THE MAIN SEISMIC FORCE RESISTING SYSTEM AND SUBJECTED TO SPECIAL INSPECTION FOR SEISMIC RESISTANCE:
NONE 4A. SIZE AND LOCATION OF STRUCTURAL ELEMENTS. ACI 530.1: 3.3F --- X Nashville, TN 37204
(615) 383-1113
4B. TYPE, SIZE, AND LOCATION OF ANCHORS, INCLUDING OTHER
FAX: (615) 386-8469
DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL
ACI 530: 1.2.1(e),6.1.4.3, 6.2.1 --- X www.ssr-inc.com
MEMBERS, FRAMES, OR OTHER CONSTRUCTION.
SOILS INSPECTIONS SSR Project #: 21640780
4C. WELDING OF REINFORCEMENT.
IBC 2018 TABLE 1705.6: REQUIRED SPECIAL INSPECTIONS AND TESTS OF SOILS ACI 530: 8.1.6.7.2, 9.3.3.4(c), 11.3.3.4(b) X ---
TYPE CONTINUOUS PERIODIC 4D. PREPARATION, CONSTRUCTION, AND PROTECTION OF
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE DESIGN MASONRY DURING COLD WEATHER (TEMPERATURE BELOW
BEARING CAPACITY. --- X 40⁰F (4.4⁰C)) OR HOT WEATHER (TEMPERATURE ABOVE 90⁰F ACI 530.1: 1.8C, 1.8D --- X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIAL. (32.2⁰C)).
--- X
4E. APPLICATION AND MEASUREMENT OF PRESTRESSING FORCE.
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS. ACI 530.1: 3.6B X ---
--- X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESSES DURING PLACEMENT AND 4F. PLACEMENT OF GROUT AND PRESTRESSING GROUT FOR
COMPACTION OF COMPACTED FILL. X --- BONDED TENDONS IS IN COMPLIANCE. ACI 530.1: 3.5, 3.6C X ---
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY THAT SITE HAS BEEN 4G. PLACEMENT OF AAC MASONRY UNITS AND CONSTRUCTION OF
PREPARED PROPERLY. --- X THIN-BED MORTAR JOINTS.
5. OBSERVE PREPARATION OF GROUT SPECIMENS, MORTAR
ACI 530.1: 3.3 B.9, 3.3 F.1.b
CONSTRUCTION DOCUMENTS
--- X
4B MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT 7B. CLEANLINESS (CONDITION OF STEEL SURFACES) --- X
DEFINED IN 4A. ACI 318: CH. 17.8.2 --- X
7C. TACKING (TACK WELD QUALITY AND LOCATION). --- X
5. VERIFY USE OF REQUIRED DESIGN MIX. ACI 318: CH. 19, 26.4.3, 26.4.4 8. CHECK WELDING EQUIPMENT --- X
IBC SECTION 1904.1, 1904.2, --- X
1908.2, 1908.3 TABLE N5.4-2 INSPECTION TASKS DURING WELDING
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS 1. USE OF QUALIFIED WELDERS --- X
ASTM C172
FOR STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT ASTM C31 2. CONTROL AND HANDLING OF WELDING CONSUMABLES:
TESTS, AND DETERMINE THE TEMPERATURE OF THE --- X
ACI 318: CH. 26.4, 26.12
CONCRETE. 2A. PACKING --- X
IBC SECTION 1908.10
2B. EXPOSURE CONTROL --- X
7. INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT FOR ACI 318: CH. 5.9, 5.10
PROPER APPLICATION TECHNIQUES. --- X 3. NO WELDING OVER CRACKED TACK WELDS --- X
IBC SECTION 1910.6 - 1910.8
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE ACI 318: 26.5.3-26.5.5 4. ENVIRONMENTAL CONDITIONS:
AND TECHNIQUES. --- X
IBC SECTION 1908.9 4A. WIND SPEED WITHIN LIMITS --- X
9. INSPECTION OF PRESTRESSED CONCRETE FOR:
4B. PRECIPITATION AND TEMPERATURE --- X
9A. APPLICATION OF PRESTRESSING FORCES. ACI 318: CH. 26.10 X --- 5. WPS FOLLOWED
9B. GROUTING OF BONDED PRESTRESSING TENDONS ACI 318: CH. 26.10 X --- 5A. SETTINGS ON WELDING EQUIPMENT --- X
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
ACI 318: CH. 26.8 --- X 5B. TRAVEL SPEED --- X
5C. SELECTED WELDING MATERIALS --- X
11. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING
OF TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO 5D. SHIELDING GAS TYPE/RATE FLOW --- X
REMOVAL OF SHORES AND FORMS FROM BEAMS AND ACI 318: CH. 26.11.2 --- X
5E. PREHEAT APPLIED --- X
STRUCTURAL SLABS.
5F. INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.) --- X
12. INSPECT FRAMEWORK FOR SHAPE, LOCATION, AND
DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED. 5G. PROPER POSITION (F, V, H, OH) --- X
ACI 318: CH. 21.11.1.2(b) --- X
6. WELDING TECHNIQUES:
6A. INTERPASS AND FINAL CLEANING --- X
6B. EACH PASS WITHIN PROFILE LIMITATIONS --- X
6C. EACH PASS MEETS QUALITY REQUIREMENTS --- X
TABLE N5.4-3 INSPECTION TASKS AFTER WELDING
1. WELDS CLEANED --- X
2. SIZE, LENGTH AND LOCATION OF WELDS X ---
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
7. PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS, AND OTHER FASTENER COMPONENTS.
--- X
3. FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM ROTATING --- X
4. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RSCS SPECIFICATION, PROGRESSING
SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE EDGES --- X
SPECIAL
TABLE N5.6-3 INSPECTION TASKS AFTER BOLTING
INSPECTIONS
1. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS X ---
4/25/2023 5:32:57 PM
TABLE N6.1 INSPECTION OF STEEL ELEMENTS OF COMPOSITE CONSTRUCTION PRIOR TO CONCRETE PLACEMENT
1. PLACEMENT AND INSTALLATION OF STEEL DECK
2. PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS
3. DOCUMENT ACCEPTANCE OR REJECTION OF STEEL ELEMENTS
X
X
X
---
---
---
S003
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
0.1A A B C D E
GreshamSmith.com
8' - 9" 15' - 0" 30' - 0" 30' - 0" 30' - 0"
1' - 7"
CB214 (37x48) CB215 (37x48) CB216 (37x48) CB217 (37x24) CB218 (37x24) CB219 (37x24) Smith
Seckman
1' - 7"
CMU WALL AT
6 Reid, Inc.
1' - 6"
GENERATOR ROOM HWB HWB
SHALL BE GROUTED 8" CONC. 4,200 LBS. 4,200 LBS. 2995 Sidco Drive
1' - 6"
SOLID FULL HEIGHT. SLAB
PB210 (36x60)
REINF. AS INDICATED
CB242A (54x24)
6" CONC. HOUSE KEEPING PAD
PB127 (36x42)
(615) 383-1113
SLOPE
SLOPE
IN SCHEDULE S421
9' - 6"
CB262 (16x24) CB269 (16x24) CB243A (16x24) FAX: (615) 386-8469
15' - 9"
GENERATOR www.ssr-inc.com
2 17,000 LBS. EMSB
3 5 468'-6" 4
S405 CB256 (16x24) CB257 (20x24) 3500 LBS
S424 S424 SSR Project #: 21640780
1' - 4"
S424
1' - 3"
PB203 (42x24)
AHU-1-2
1' - 6"
9' - 6"
1
S422 12,500 LBS. 8" CONC. 3
SLAB
CB257 (20x24) S300
S6
CB256 (16x24) CB258 (16x24) CB266 (16x24) CB267 (16x24) CB268 (16x24)
1' - 4"
PB206 (42x24)
PB245 (20x48)
8" CONC.
1' - 4"
4" CONC. HOUSE KEEPING
5' - 10"
S7 SLAB
PAD
TENNESSEE
PB209 (36x42)
9' - 6"
S6
PB216 (54x24)
CB266 (16x24) CB267 (16x24) CB268 (16x24)
PB213 (54x24)
ONCOLOGY
29' - 3"
1' - 4"
CB256 (16x24) CB257 (16x24) CB258 (16x24)
1' - 4"
1' - 2" S424
E.O.S.
CB266 (16x24) CB267 (16x24) CB268 (16x24)
8' - 3"
1
2' - 9"
S421 3 S424
PB248 (66x25.5) PB249 (66x25.5) SIM. S300
1 3" S301
CB234 (36x24) CB235 (36x24) CB236 (36x24)
.
M
SI
2
4
3' - 6"
S424 8
1
7' - 0"
11 S424
5' - 9" 1' - 4" 5' - 9" 1' - 4" 5' - 9" 1' - 4" 5' - 9"
S300
2' - 9"
6' - 10"
S424
6' - 11"
CB265 (16x24)
CB263 (16x24) CB264 (16x24)
PB215 (54x24)
1' - 4"
9" PLUMBING PIPE SLEEVE
THRU BEAM
PB257 (20x24)
PB244 (20x48)
PB202 (42x21)
PB205 (42x21)
PB208 (36x42)
CB265 (16x24)
PB212 (54x24)
CB263 (16x24) CB264 (16x24)
120' - 0"
30' - 0"
8' - 0"
CONSTRUCTION DOCUMENTS
2
1' - 4"
S424
S6
CB265 (16x24)
1' - 6" 9' - 1" CB263 (16x24) CB264 (16x24)
CB253 (16x21) CB254 (16x21) CB255 (16x21)
6' - 11"
7 471'-6" PLUMBING PIPE SLEEVE
CB293 (16x24)
2' - 9"
S421 THRU BEAM 6 8" CONC.
1' - 6"
SLAB
5' - 0"
1 3" S424 471'-6''
CB227 (36x24) CB228 (36x24) CB229 (36x24)
3
2' - 9"
1' - 6"
6' - 0" 1' - 4" 5' - 10" 1' - 4" 5' - 10" 1' - 4" 5' - 10" 1' - 4" 5' - 10" 1' - 4" 6' - 0"
PB246 (66x21) PB247 (66x21)
3
S425
8' - 3"
471'-6''
9" CB259 (16x24) CB261 (16x24)
PB211 (54x24)
E.O.S.
9' - 6"
1
CB260 (16x24)
S424
PB207 (36x42)
PB204 (42x21)
PB214 (54x24)
PB201 (42x21)
CB250 (16x21) CB251 (16x21) CB252 (16x21) CB259 (16x24) CB260 (16x24) CB261 (16x24)
45' - 0"
1' - 4"
PB243 (20x21)
8" CONCRETE
SLAB
9' - 6"
S6
S1
SLAB
1' - 4"
S424
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
9
S421
CB201 (37x21) CB202 (37x21) CB203 (37x21) CB204 (37x24) CB205 (37x24) CB206 (37x24)
5 ' - 3 " 1' - 6"
1' - 6"
Revision
1
2' - 9 1/2"
E.O.S.
5' - 3"
E.O.S.
E.O.S.
1' - 7"
F
CB247 (16x21) CB248 (16x21) CB249 (16x21) CB261A (16x24)
1 05.26.2023 Addendum No. 1
10" SLAB
2 6
1 S420 S300
S420
MATCHLINE - WEST
CLOUSURE CLOUSURE
MATCHLINE - EAST
WALL BELOW WALL BELOW
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS SLOPING TOPPING SLAB
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE. (6" L.W. CONC. OVER GEO-FOAM
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM REINFORCING AT DRIVE AISLE) AND
SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG AT CURBS / SIDEWALKS
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS FOR POST
TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES
WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND
CONSTRUCTION DETAILS.
7. INDICATES TOPPING SLAB. REFER TO REFER TO 3/S422 FOR CONSTRUCTION DETAILS
A E M
8. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
9. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
10.COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
11.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED 6
ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO
DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601
THROUGH CONCRETE BEAMS
12.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH
1ST FLOOR FRAMING - WEST N 1ST FLOOR FRAMING
1 ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
13.REFER TO THE ARCHITECTURAL PLAN FOR BOLLARD LOCATION AND TYPE. 1 1/8" = 1'-0" PART A
14.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410,
AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
PLAN - PART A
15.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE
BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR REQUIREMENTS
5/25/2023 4:01:40 PM
KJM
E F H I J K L M M.1
Checked By:
Drawn By:
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0" 8' - 9"
GreshamSmith.com
1' - 7"
1' - 7"
CB219 (37x24) CBB220 (37x24) CB221 (37x24) CB222 (37x24) CB223 (37x24) CB224 (37x24) CB225 (37x24) CB226 (37x24)
1' - 7"
F
1' - 6"
HWB HWB HWB
4,200 LBS. 4,200 LBS. 4,200 8" CONC.
LBS. SLAB
CB241A (42x24)
8" CONC. 472'-0" OPEN
SLAB
Smith
PB127 (36x42)
8
9' - 6"
CB246 (16x24) 6' - 11" +/-
S7
CB269 (16x24) CB243A (16x24) CB244A (16x24) CB245A (16x24) CB284 (16x24) S421 Seckman
S7
4
Reid, Inc.
PB225 (42x24)
468'-6" 2 470'-0" CB285 (16x24) CB286 (16x24) CB287 (16x24)
5 470'-6" 2995 Sidco Drive
S424
1' - 4"
S425 Peff= 22
S424 Nashville, TN 37204
KIP /FT 5
CB243 (36x24) FILL w/ (615) 383-1113
CB242 (33x26) CB244 (30x42*) CB245 (30x72*) CB246A (24x24) CB284 (16x24) S425 6" L.W. CONC. PROPOSED LOCATION OF MRI. FAX: (615) 386-8469
5' - 10" 1' - 4" 5' - 10" 1' - 4" 5' - 2" 2' - 0"
SLAB AT PROPOSED www.ssr-inc.com
5 COORDINATE LOCATION WITH
1' - 6"
PB228 (60x24)
9' - 6"
8" CONCRETE IMAGING AREA INTERIOR AND FINAL INSTALLATION
1' - 10 1/2"
5' - 10"
PB235 (42x24)
PB238 (42x24)
3 SLAB PLANS. ALL REINFORCING STEEL
SSR Project #: 21640780
S6
IN THE TOPPING SLAB, STRUCTURAL
PB231 (36x48)
S300
CB283 (16x24) CB284 (16x24) CB286 (16x24) CB287 (16x24)
4' - 7"
CB268 (16x24) CB285 (16x24) SLAB, BEAM TOP STEEL AND
PB241 (20x24)
CB267 (16x24)
6' - 0" 1' - 4" 5' - 10" 1' - 4" 5' - 10" 1' - 4"
1' - 4"
STIRRUPS IN A 10' X10' AREA
4 #4 @ 10" T. SHALL BE ASTM A995 SS 316LN.
8" CONC. S426 REINFORCING.
PB258 (42x24)
4" CONC. HOUSE KEEPING SLAB 10 8" CONCRETE
PAD 1
4 S425 SLAB
9' - 6"
T & S #4 B @ 10" 1' - 6"
S6
PB216 (54x24)
PB224 (42x24)
CB267 (16x24)
S7
S420
CB285 (16x24) CB286 (16x24) CB287 (16x24)
10" ONE WAY PT SLAB 8 7 9
1' - 4"
2 11
#4@10" B S425 S425 S425
S300
TENNESSEE
1' - 4"
S425 CB283 (16x24) CB284 (16x24)
CB267 (16x24) CB268 (16x24)
#4 @ 10" T. 6
9' - 1 1/2"
12 3
1' - 3" DN
470'-0"
S425
ONCOLOGY
5' - 7 1/2"
S424 S426
2' - 7 3/8"
CB237 (30"x54*) CB238 (30"x102*)
1'-10 1/2"
CB235 (36x24) CB236 (36x24) CB239 (43.5x54) CB240 (43.5x54) PB252 (43.5x30) PB253 (43.5x30)
1
4
1'-10 1/2"
7' - 3"
11 S424
S2
5' - 9" 1' - 4" 5' - 9" 1' - 4" 5' - 9" 1' - 4" 5' - 9"
472'-6"
S2
S2
7' - 11"
S1
S424 CB292 (16x21)
CB265 (16x24) S4
CB264 (16x24) CB291 (16x21) CB288 (16x21) CB277 (16x21) CB278 (16x21) CB279 (16x21)
1' - 4"
11' - 3"
CB280 (16x21) CB281 (16x21) CB282 (16x21)
PB215 (54x24)
7" CONC.
PB256 (24x21)
1' - 4"
S1
CB289 (16x21)
PLUMBING PIPE SLEEVE
PB240 (20x21)
SLAB
PB219 (36x54)
PB255 (24x21)
6' - 10"
THRU BEAM
PB234 (42x21)
PB237 (42x21)
PB223 (42x21)
PB227 (42x21)
PB254 (24x21)
PB230 (39x21)
6'-11" 10' - 5 1/4" 5" CONCRETE
CB265 (16x24)
19'-6" CLR.
CB264 (16x24) SLAB UNO
8' - 0"
CLR. CB290 (16x21) CB278 (16x21) CB279 (16x21)
PB221 (42x21)
S1
S424 HSS8x4x3/8 HSS8x4x3/8 1' - 6" CB280 (16x21) CB281 (16x21) CB282 (16x21)
1' - 4"
S6
CB265 (16x24)
HSS8x4x3/8
CB264 (16x24) CB294 (16x21) CB292 (16x21) 1' - 6"
1' - 6" 6' - 11" 2' - 0" 10' - 2 3/4" 2' - 0" CB278 (16x21) CB279 (16x21)
11' - 4"
6' - 11"
6
CLR.
2' - 9"
8" CONC.
8' - 6"
6 CLR.
CONSTRUCTION DOCUMENTS
PLUMBING PIPE SLEEVE
SLAB
1' - 6"
S424 THRU BEAM PB250 (66x21) PB251 (60x21)
471'-6''
CB229 (36x24) CB231 (36x21) CB232 (36x21) CB233 (36x21)
CB228 (36x24)
1' - 6"
1
3 3"
CB230 (36x26) 472'-6"
1' - 6"
2' - 9"
6' - 0" 1' - 4" 5' - 10" 1' - 4" 5' - 10" 1' - 4" 5' - 10" 1' - 4" 5' - 10" 1' - 4" 6' - 0"
9' - 6"
8' - 3"
CB260 (16x24) CB261 (16x24) RAMPS AND ELEVATION TO STAIRS AT
LV
THIS BAY.
TF
470'-0" CB270 (16x26) CB271 (16x21) CB272 (16x21) CB273 (16x21) CB274 (16x21) CB275 (16x21) CB276 (16x21)
1' - 4"
1' - 4"
10
471'-6''
S424 9"
CB261 (16x24)
E.O.S.
9' - 6"
9' - 6"
PB218 (36x54)
CB260 (16x24)
PB214 (54x24)
CB260 (16x24) CB261 (16x24) CB270 (16x26) CB271 (16x21) CB272 (16x21) CB273 (16x21) CB274 (16x21) CB275 (16x21) CB276 (16x21)
PB222 (42x21)
PB226 (42x21)
1' - 4"
1' - 4"
PB229 (42x21)
PB233 (42x21)
PB236 (42x21)
9 1' - 6" 5" CONCRETE
SLAB UNO
PB239 (20x21)
S424 6" CONCRETE
PB220 (48x26)
9' - 6"
9' - 6"
CB260 (16x24) CB261 (16x24) SLAB
S1
8" CONCRETE
S3
SLAB
CB270 (16x26) CB271 (16x21) CB272 (16x21) CB273 (16x21) CB274 (16x21) CB275 (16x21) CB276 (16x21)
7
1' - 4"
1' - 4"
S6
S424
CB260 (16x24) CB261 (16x24)
9' - 6"
THRU BEAM
1' - 6"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
CB205 (37x24) CB206 (37x24) CB207 (37x26) CB208 (37x21) CB209 (37x21) CB210 (37x21) CB211 (37x21) CB212 (37x21) CB213 (37x21) 1
1' - 6"
1
2' - 9 1/2"
E.O.S.
5' - 3"
E.O.S.
E.O.S.
E.O.S.
5' - 8"
5' - 8"
3"
E.O.S.
F
7'-6"
CB261A (16x24) CB270A (16x26) CB271A (16x21) CB272A (16x21) CB273A (16x21)
CB274A (16x21) CB275A (16x21) CB276A (16x21)
4
CLOSURE WALL BELOW Revision
6 3
S300
S420
S420
5 5 No. Date Description
S420
MATCHLINE - WEST
S300
GEO-FOAM FILL WITH 4" L.W. SLAB TO MAKE
RAMPS AND ELEVATION TO STAIRS AT
ALL INTERIOR SPACES THIS BAY.
2
S422
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM REINFORCING
SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS FOR POST
TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES
WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND
CONSTRUCTION DETAILS.
7. INDICATES TOPPING SLAB. REFER TO REFER TO 3/S422 FOR CONSTRUCTION DETAILS
8. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
9. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN A E M
10.COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
11.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED
ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO 6
DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601
THROUGH CONCRETE BEAMS
12.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH 1ST FLOOR FRAMING - EAST N
ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
13.REFER TO THE ARCHITECTURAL PLAN FOR BOLLARD LOCATION AND TYPE. 1 1/8" = 1'-0"
1ST FLOOR FRAMING
14.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410,
AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
PART B
15.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE PLAN - PART B
BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR REQUIREMENTS
DIFFER FROM WHAT IS SHOWN.
5/25/2023 4:01:42 PM
16.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION DESIGN 1
IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR FRAMING WITH CONCRETE FRAMING.
17.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT DIFFERS THAN WHAT IS SHOWN.
18. INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS. S201B
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
A B C D E
GreshamSmith.com
WALL SUPPORT 2
3
8" THK. CONC. SLAB FRAMING BELOW SEE S428
SECTIONS S428
1' - 6"
1' - 6"
Smith
E.O.S.
4' - 1"
Seckman
6 Reid, Inc.
CB314 (36x21) CB315 (36x21) CB316 (36x21) 2995 Sidco Drive
1' - 6"
1' - 6"
CB312 (36x21) CB313 (36x21)
Nashville, TN 37204
(615) 383-1113
9' - 4"
9' - 6"
FAX: (615) 386-8469
www.ssr-inc.com
PB350 (20x21) CB333 (16x21) CB334 (16x21) CB335 (16x21) SSR Project #: 21640780
1' - 8"
1' - 4"
CB354 (16x21)
PB303 (48x21)
PB309 (42x21)
PB312 (42x21)
PB306 (48x21)
9' - 2"
9' - 6"
7 PB350 (20x21)
45' - 0" CB333 (16x21) CB334 (16x21) CB335 (16x21)
1' - 8"
1' - 4"
S427
TENNESSEE
9' - 2"
9' - 6"
ONCOLOGY
PB350 (20x21) CB333 (16x21) CB334 (16x21) CB335 (16x21)
1' - 8"
1' - 4"
1
CB362B (16x21)
4
6' - 10"
9' - 6"
1' - 6"
1' - 6"
PB338 (36x21) CB323A (36x21) CB324 (36x21) CB325 (36x21)
4 3' - 9"
3' - 6"
5' - 10 1/2"
CB346 (16x21)
S1
6' - 11"
1' - 6"
1' - 6"
S1
8' - 0"
8' - 2"
CB362A (16x21)
PB351 (20x21) CB347 (16x21) CB348 (16x21)
1' - 8"
1' - 4"
1' - 5" 9' - 2" 2' - 0"
CB346A (29x21)
2' - 5"
30' - 0"
7' - 8"
8' - 0"
STAIRS
19' - 1"
CB353 (16x21)
PB302 (48x21)
PB308 (42x21)
PB311 (42x21)
PB334 (24x21)
CONSTRUCTION DOCUMENTS
PB305 (41x21)
PB351 (20x21) CB346 (16x21) CB347 (16x21) CB348 (16x21)
1' - 8"
1' - 4"
UP
AHU
8' - 2"
12,500 LBS.
8' - 0"
6" CONC. HOUSE
CB363 (16x21) KEEPING PAD
1' - 6"
1' - 6"
DN
4' - 0"
PPB337 (36x21) CB323 (36x21) CB324 (36x21) CB325 (36x21)
1' - 6"
1' - 6"
PLUMBING PIPE SLEEVE
9' - 4"
9' - 6"
9' - 11"
E.O.S.
PB350 (20x21) CB330 (16x21) CB331 (16x21) CB332 (16x21)
1' - 8"
1' - 4"
5" CONC. SLAB TYP.
WALL AND CANOPY 490'-6"
9' - 2"
9' - 6"
S1
SUPPORT FRAMING
BELOW SEE SECTIONS
CB352 (16x21)
PB301 (48x21)
PB307 (42x21)
PB310 (42x21)
PB304 (48x21)
PB350 (20x21) CB330 (16x21) CB331 (16x21) CB332 (16x21)
45' - 0"
1' - 8"
1' - 4"
8
S431 9
9' - 2"
9' - 6"
S431
1' - 4"
1
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
9' - 6"
9' - 4"
FRAMING BELOW
6 1
1' - 6"
1' - 6"
S427
CB301 (36x21) CB302 (36x21) CB303 (36x21) CB304 (36x21) CB305 (36x21)
Revision
1
No. Date Description
6' - 11"
1' - 6"
E.O.S.
1' - 6"
3' - 9"
4'-1"
1 05.26.2023 Addendum No. 1
1' - 4"
1' - 8"
MATCHLINE - WEST
MATCHLINE - EAST
S427 4 3
WALL AND CANOPY S427 S427
SUPPORT FRAMING
NOTES: BELOW SEE SECTIONS
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM
REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED
DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS
FOR POST TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS.
‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND A E M
CONSTRUCTION DETAILS.
7. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
8. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
6
9. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
10.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED
ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO
2ND FLOOR FRAMING - WEST
DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601
THROUGH CONCRETE BEAMS 1 1/8" = 1'-0" N 2ND FLOOR FRAMING
11.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH
ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
PART A
12.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410, PLAN - PART A
AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
13.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE
5/25/2023 4:01:44 PM
BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR 1
S202A
REQUIREMENTS DIFFER FROM WHAT IS SHOWN.
14.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION
DESIGN IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR
FRAMING WITH CONCRETE FRAMING.
15.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT
DIFFERS THAN WHAT IS SHOWN.
16. INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS. KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
E F H I J K L M
Checked By:
Drawn By:
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0"
GreshamSmith.com
5
S428 WALL AND CANOPY
SUPPORT FRAMING
BELOW SEE SECTIONS
222 Second Avenue South
WALL SUPPORT 4
4
Suite 1400
FRAMING BELOW SEE 8" THK. CONC. SLAB S428
SECTIONS 2 S428
Nashville, TN 37201
S428 615.770.8100
1' - 6"
1' - 6"
1' - 6"
E.O.S.
4' - 1"
6
1' - 6"
1' - 6"
CB315 (36x21) CB316 (36x21) CB317 (36X24.5) CB318 (36x21) CB319 (36x21) CB320 (36x21) CB321 (36x21)
1' - 6"
CB322 (36x21)
9 Smith
9' - 4"
9' - 6"
9' - 6"
S427 Seckman
Reid, Inc.
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB352 (20x21) 2995 Sidco Drive
1' - 4"
1' - 4"
1' - 8"
Nashville, TN 37204
PB324 (42x21)
PB327 (48x21)
PB315 (48x24.5)
PB318 (48x24.5)
(615) 383-1113
CB354 (16x21)
PB312 (42x21)
PB321 (42x21)
PB330 (48x21)
FAX: (615) 386-8469
www.ssr-inc.com
9' - 6"
9' - 6"
9' - 2"
SSR Project #: 21640780
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB352 (20x21)
45' - 0"
1' - 4"
1' - 4"
1' - 8"
490'-6"
9' - 6"
9' - 6"
9' - 2"
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB352 (20x21)
1' - 4"
1' - 4"
1' - 8"
5
TENNESSEE
S206C
ONCOLOGY
9' - 6"
9' - 6"
9' - 4"
S1
5" CONC. SLAB
TYP. UNO
1' - 6"
1' - 6"
1' - 6"
10' - 7"
CB324 (36x21) CB325 (36x21) CB326 (36X24.5) CB327 (36x21) CB328 (36x21) CB329 (36x21) PB340 (36x21)
1' - 6"
1' - 6"
1' - 6"
7' - 2"
7' - 2"
S1
6' - 2"
S1
6' - 2"
S1
8' - 0"
8' - 2"
1' - 4"
CB347 (16x21) CB348 (16x21) PB351 (20x21)
1' - 4"
1' - 8"
PB317 (42x21)
14' - 2"
1' - 6" 1' - 6"
CB359 (16x21)
AHU
PB333 (24x21)
PB332 (24x21)
6' - 10"
CB353 (16x21)
PB320 (42x21)
PB331 (24x21)
PB329 (48x21)
12,500 LBS.
S1
PB326 (41x21)
11' - 6" 6' - 11" 14' - 2 3/4" 6' - 11" 1 1' - 5"
30' - 0"
8' - 0"
18' - 0"
CB357 (16x21) CB350 (16x21) CB351 (16x21)
PB314 (36x21)
PB323 (42x21)
PB311 (42x21)
PB334 (24x21)
STAIRS STAIRS
S5 19' - 6"
1' - 4"
CB347 (16x21) CB348 (16x21) HSS8x4x3/8 HSS8x4x3/8
17' - 4"
1' - 4"
OPEN
HSS8x4x3/8
CB360 (16x21) CB350 (16x21) CB351 (16x21)
UP 1' - 6" UP
PLUMBING PIPE SLEEVE
8
8' - 2"
CONSTRUCTION DOCUMENTS
OPEN
1' - 6"
1' - 6"
DN
4' - 9 1/2"
1' - 6"
4' - 10"
CB324 (36x21) CB325 (36x21) CB330A (36X24.5) CB327 (36x21) CB328 (36x21) CB329 (36x21) PB339 (36x21)
3
1' - 6"
1' - 6"
1' - 6"
1' - 6"
E.O.S.
7' - 6"
9' - 4"
9' - 6"
9' - 6"
THRU BEAM
CB331 (16x21) CB332 (16x21) 8 CB340 (16x21) CB341 (16x21) CB342 (16x21) PB352 (20x21)
1' - 4"
1' - 4"
1' - 8"
S428
PB325 (30x30)
PB328 (48x21)
4' - 6 1/2"
CURTAIN WALL SUPPORT
9' - 6"
9' - 6"
9' - 2"
FRAMING BELOW 2' - 4 1/2"
E.O.S. 5" CONC. SLAB
S1
PB313 (52.5x24.5)
1
CB331 (16x21) CB332 (16x21) OPEN S428 CB340 (16x21) CB341 (16x21) CB342 (16x21) PB352 (20x21)
45' - 0"
1' - 4"
1' - 8"
9' - 11 3/4"
8" CONC. SLAB
9 AT CANTILEVER CB343 (16x21) CB344 (16x21) CB345 (16x21) E.O.S.
9' - 6"
9' - 2"
S431
7
1' - 4"
S428 1' - 3" E.O.S.
CB331 (16x21) CB332 (16x21) PB352 (20x21)
1' - 4"
1' - 8"
10
CB352 (16x21)
PB316 (30x30)
PB319 (30x30)
PB322 (30x30)
S428
OPEN OPEN OPEN
16' - 0"
E.O.S.
9' - 6"
9' - 4"
PLUMBING PIPE SLEEVE
THRU BEAM
1' - 6"
1' - 6"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
CB304 (36x21) CB305 (36x21) CB306 (30x30) CB307 (30x30) CB308 (30x30) CB309 (30x30) CB310 (36x21) CB311 (36x21)
1
E.O.S.
4' - 4"
1' - 6"
6' - 11"
E.O.S.
1' - 6"
3' - 9"
4'-1"
1' - 8"
1' - 4"
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM
REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED
DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS
FOR POST TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS.
‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND
CONSTRUCTION DETAILS. A E M
7. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
8. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
9. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
6
10.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED
ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO
DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601
THROUGH CONCRETE BEAMS
11.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH
2ND FLOOR FRAMING - EAST N PART B 2ND FLOOR FRAMING
ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
12.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410, 1 1/8" = 1'-0"
PLAN - PART B
AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
13.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE
BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR
5/25/2023 4:01:48 PM
S202B
14.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION
DESIGN IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR
FRAMING WITH CONCRETE FRAMING.
15.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT
DIFFERS THAN WHAT IS SHOWN.
16. INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS.
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
A B C D E
GreshamSmith.com
1
8" THK. CONC. SLAB S430
2' - 7"
Smith
E.O.S.
4' - 1"
Seckman
1' - 6"
6 Reid, Inc.
CB312 (36x21) CB 313 (36x21) CB314 (36x21) CB315 (36x21) CB316 (36x21) 2995 Sidco Drive
1' - 6"
Nashville, TN 37204
8" CONCRETE CURB
(615) 383-1113
9' - 4"
T/CURB 1'-4" ABOVE
3RD FLR. ELEVATION FAX: (615) 386-8469
T/CURB = 505'-10" www.ssr-inc.com
1' - 8"
CB354 (16x21)
PB303 (48x21)
PB306 (48x21)
PB309 (42x21)
PB312 (42x21)
9' - 2"
2' - 0"
1' - 8"
TENNESSEE
9' - 2"
ONCOLOGY
PB350 (20x21) CB333 (16x21) CB334 (16x21) CB335 (16x21)
1' - 8"
CB36B (16x21)
S1 504'-6"
1
1' - 6"
FOR SIM. CONNECTION
PB338 (36x21) TO CONC. BEAM CB323 (36x21) CB397 (36x21) CB325 (36x21)
1' - 6"
3' - 6"
S1
6' - 11"
1' - 6"
S1
8' - 6"
8' - 0"
8' - 2"
HSS8X4X1/4 CB370A (29x21)
PB351 (20x21) CB362A (16x21) CB371 (16x21) CB372 (16x21)
1' - 8"
1' - 4"
2' - 5"
1
PB305A (41x21)
PB334A (24x21)
PB308 (42x21)
CB353 (16x21)
PB302 (48x21)
PB311 (42x21)
15' - 4 3/4"
9' - 2" 2' - 0" 17' - 5"
120' - 0"
30' - 0"
7' - 8"
8' - 0"
1' - 5" STAIRS
1' - 8"
1' - 4"
CB363
UP (16x21) AHU
DN 12,500 LBS
8' - 2"
8' - 0"
9' - 11"
7' - 8 1/4"
6" CONC. HOUSE
1' - 6"
E.O.S. KEEPING PAD
PB337 (36x21) CB323 (36x21) CB397 (36x21) CB325 (36x21)
1' - 6"
3
1' - 6"
8" CONCRETE CURB
9' - 4"
PB301 (48x21)
PB304 (48x21)
PB307 (42x21)
PB310 (42x21)
S1
9' - 2"
1' - 8"
9' - 2"
4
S429 PB350 (20x21) CB333 (16x21) CB334 (16x21) CB335 (16x21)
1' - 8"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
9' - 4"
2' - 5 1/2"
3' - 3"
4' - 11 1/2"
1' - 6"
CB301 (36x21) CB302 (36x21) CB303 (36x21) CB304 (36x21) CB386 (36x21)
Revision
1
No. Date Description
6' - 11"
3' - 9"
E.O.S.
1' - 6"
5' - 5 1/2"
1 05.26.2023 Addendum No. 1
PB353 (20x21)
8" CONCRETE CURB CB355 (16x21) CB377 (16x21) CB378 (16x21)
1' - 8"
MATCHLINE - WEST
DETAILS
MATCHLINE - EAST
S429 S429
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM
REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED
DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS
FOR POST TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS.
‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND A E M
CONSTRUCTION DETAILS.
7. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
8. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
6
9. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
10.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED
ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO
3RD FLOOR FRAMING PLAN - WEST
DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601
THROUGH CONCRETE BEAMS 1 1/8" = 1'-0" N 3RD FLOOR FRAMING
11.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH
ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
PART A
12.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410, PLAN - PART A
AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
13.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE
5/25/2023 4:01:48 PM
BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR 1
S203A
REQUIREMENTS DIFFER FROM WHAT IS SHOWN.
14.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION
DESIGN IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR
FRAMING WITH CONCRETE FRAMING.
15.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT
DIFFERS THAN WHAT IS SHOWN.
16. INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS. KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
E F H I J K L M
Checked By:
Drawn By:
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0"
GreshamSmith.com
2' - 7"
10" CONC. SLAB
E.O.S.
E.O.S.
E.O.S.
4' - 1"
4' - 1"
AT DEPRESSED
6"- 6"
TERRACE SLAB
6
1' - 1'
CB315 (36x21) CB316 (36x21) CB317 (36X24.5) CB318 (36x21) CB319 (36x21) CB320 (36x21) CB394 (36x21) CB395 (36x21)
8" CONCRETE CURB
Smith
9' - 6"
SHALL BE 1'-4"
ABOVE 3RD F.F.E. 3 Seckman
T/CURB = 505'-10" S430 Reid, Inc.
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB360 (16x21) CB364 (16x21) CB365 (16x21) CB366 (16x21) 2995 Sidco Drive
1' - 4"
Nashville, TN 37204
PB381 (16.5X21)
PB360 (48x24.5)
PB363 (48x24.5)
(615) 383-1113
PB312 (42x21)
PB366 (42x21)
PB369 (42x21)
PB372 (42x21)
PB375 (42x33)
PB378 (42x21)
FAX: (615) 386-8469
5" CONCRETE www.ssr-inc.com
9' - 6"
S1
SLAB TYP. UNO
SSR Project #: 21640780
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB360 (16x21) CB364 (16x21) CB365 (16x21) CB366 (16x21)
1' - 4"
8" CONCRETE WALL 2' - 1" 12' - 11" 9' - 11 3/4"
504'-6"
9' - 6"
SHALL BE 4" ABOVE E.O.S.
3RD DEPRESSED F.F.E.
T/WALL EL. = 503'-10"
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB360 (16x21) CB364 (16x21) CB365 (16x21) CB366 (16x21)
1' - 4"
WALL SHALL BE 2'-4"
ABOVE 3RD FLR. DEPRESSED
TENNESSEE
F.F.E. - T/WALL EL. = 505'-10"
503'-6"
ONCOLOGY
9' - 6"
3' - 3"
PB382 (60x36.5 / 24.5)
CB397 (36x21) CB325 (36x21) CB326 (36X24.5) CB327 (36x21) CB398 (36x21) CB329 (36x21)
1' - 6"
4
1' - 6"
7' - 2"
7' - 8"
11' - 10" 1' - 4 1/2"
S1
9' - 0"
6' - 2"
9' - 8"
S1
S4 1' - 9" 6' - 2 3/4"
S1
8' - 2"
1' - 4"
1' - 4"
CB372 (16x21) 1' - 6" CB367 (16x21) CB368 (16x21) CB369 (16x21)
1' - 4"
1' - 4"
11' - 6" 2' - 0" CB376A (16x21) 11' - 6" 1' - 5"
AHU
6' - 10"
6' - 11" 10' - 2 1/4" 2' - 0" 2' - 0"
PB334A (24x21)
PB371 (38x21)
PB311 (42x21)
PB365 (42x21)
PB377 (42x21)
12,500 LBS
S1
14' - 4"
PB359 (36x21)
PB362 (42x21)
8' - 0"
8' - 0"
STAIRS CB373 (16x21) CB375 (16x21)
PB333 (24x21)
PB332 (24x21)
S5
PB380 (16.5X21)
STAIRS
PB331A (24x21)
PB368 (42x21)
PB374 (42x33)
19' - 6"
CB372 (16x21) HSS8x4x3/8 HSS8x4x3/8 CB376 (16x21) CB367 (16x21) CB368 (16x21) CB369 (16x21)
1' - 4"
1' - 4"
OPEN 1' - 6"
HSS8x4x3/8
CB363 (16x21) CB376B (24x21) CB363A (16x21)
CB349A (16x21) CB375 (16x21)
11' - 4"
DN UP OPEN DN UP
7' - 2"
S1
8' - 2"
CONSTRUCTION DOCUMENTS
OPEN
1' - 6"
PB382 (60x36.5 / 24.5) 5" CONCRETE
CB397 (36x21) CB325 (36x21) CB327 (36x21) CB398 (36x21) CB329 (36x21) SLAB TYP. UNO
2' - 6"
1' - 6"
1' - 6"
6
3 S430
1' - 6"
CB330A (36X24.5)
7" CONC. 6" CONC. HOUSE
SLAB KEEPING PAD
9' - 6"
5
S430
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB360 (16x21) CB364 (16x21) CB365 (16x21) CB366 (16x21)
1' - 4"
PB379 (16.5X21)
PB358 (48x24.5)
PB361 (48x24.5)
PB376 (42x21)
PB373 (42x33)
PB310 (42x21)
PB364 (42x21)
PB367 (42x21)
PB370 (42x21)
5" CONCRETE
S1
9' - 6"
SLAB TYP. UNO
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB360 (16x21) CB364 (16x21) CB365 (16x21) CB366 (16x21)
1' - 4"
8" CONC. WALL SHALL
BE 4" ABOVE 3RD
9' - 6"
DEPRESSED F.F.E.
T/WALL EL. = 504'-10"
CB334 (16x21) CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB360 (16x21) CB364 (16x21) CB365 (16x21) CB366 (16x21)
1' - 4"
4' - 11 1/2"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
1' - 6"
CB304 (36x21) CB386 (36x21) CB387 (36X24.5) CB388 (36x21) CB389 (36x21) CB390 (36x21) CB391 (36x21) CB392 (36x21)
1' - 4"4' - 1" 3' - 0"
3' - 5"
6' - 11"
6' - 11"
E.O.S.
E.O.S.
CB383 (16x21)
Revision
1' - 4 1/2"
CB377 (16x21) CB378 (16x21) CB379 (16x24.5) CB380 (16x21) CB381 (16x21) CB382 (16x21)
EYEBROW AND WINDOW 1 8" CONCRETE WALL SHALL
No. Date Description
3 2 4
WALL FRAMING BELOW BE 2'-4" ABOVE 3RD FLR.
MATCHLINE - WEST
S429
MATCHLINE - EAST
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM
REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED
DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS
FOR POST TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS.
‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND
CONSTRUCTION DETAILS. A E M
7. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
8. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
9. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
6
10.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED
ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO
DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601
THROUGH CONCRETE BEAMS
3RD FLOOR FRAMING PLAN - EAST
11.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH
ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT. 1 1/8" = 1'-0" N PART B 3RD FLOOR FRAMING
12.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410,
AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS. PLAN - PART B
13.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE
BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR
4/25/2023 5:33:21 PM
S203B
14.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION
DESIGN IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR
FRAMING WITH CONCRETE FRAMING.
15.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT
DIFFERS THAN WHAT IS SHOWN.
16. INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS.
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
A B C D E
GreshamSmith.com
CURTAIN WALL 3
8" THK. CONC. SLAB SUPPORT FRAMING S431
4th FLOOR ONLY
1' - 6"
1' - 6"
3' - 1"
E.O.S.
Smith
4' - 7"
CB313 (36x21) CB314 (36x21) CB315 (36x21) CB316 (36x21)
Seckman
6 Reid, Inc.
2995 Sidco Drive
1' - 6"
CB399 (36x21) PIPE PENETRATION
1' - 6"
Nashville, TN 37204
5th FLR. ONLY
(615) 383-1113
9' - 4"
9' - 6"
PIPE PENETRATION FAX: (615) 386-8469
5th FLR. ONLY www.ssr-inc.com
1' - 4"
1' - 8"
9' - 2"
9' - 6"
PB403 (50x21)
PB406 (48x21)
PB409 (42x21)
PB409 (42x21)
PB417 (20x21) CB333 (16x21) CB334 (16x21) CB335 (16x21)
45' - 0"
1' - 4"
1' - 8"
518'-6"
TENNESSEE
9' - 2"
9' - 6"
2' - 5"
E.O.S.
ONCOLOGY
PB417 (20x21) CB333 (16x21) CB334 (16x21) CB335 (16x21)
1' - 4"
1' - 8"
CB262B (16x21)
1
9' - 6"
1' - 6"
S431
1' - 6"
TO CONC. BEAMS
PB415 (36x21) CB323A (36x21) CB397 (36x21) CB325 (36x21)
3' - 6"
4
8' - 6 3/8"
S1
1' - 6"
6' - 11"
1' - 6"
S1
2' - 0" 10' - 8" 6' - 10"
8' - 0"
8' - 2"
HSS8X4X1/4 CB370A (29x21)
PB418 (20x21) CB362A (16x21) CB371 (16x21) CB372 (16x21)
1' - 4"
1
1' - 5" 9'-2"
1' - 8"
PB405 (41x21)
PB402 (50x21)
PB335 (24x21)
PB408 (42x21)
PB410 (42x21)
120' - 0"
STAIRS
30' - 0"
7' - 8"
8' - 0"
1' - 4"
CB363 (16x21) AHU
1' - 8"
12,500 LBS. 6" CONC. HOUSE
8' - 2"
8' - 0"
KEEPING PAD
7' - 9 1/4"
1' - 6"
1' - 6"
PB415 (36x21) CB323 (36x21) CB397 (36x21) CB325 (36x21)
1' - 6"
1' - 6"
PIPE PENETRATION
5th FLR. ONLY
11' - 0"
PIPE PENETRATION
9' - 4"
1' - 4"
5" CONCRETE SLAB TYP.
S1
9' - 2"
9' - 6"
1' - 8"
PB417 (20x21)
CB333 (16x21) CB334 (16x21) CB335 (16x21)
PB401 (50x21)
PB404 (48x21)
PB407 (42x21)
PB407 (42x21)
45' - 0"
1' - 4"
9' - 2"
9' - 6"
1' - 8"
1' - 4"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
9' - 6"
9' - 4"
1' - 6"
1' - 6"
CB401 (37.5x21) CB402 (37.5x21) CB403 (37.5x21) CB404 (37.5x21) CB405 (37.5x21)
Revision
1' - 7 1/2"
E.O.S.
1
No. Date Description
1' - 7 1/2"
1' - 7 1/2"
MATCHLINE - WEST
MATCHLINE - EAST
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM
REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED
DEPTH IN BEAM TAG NOTE:
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS
FOR POST TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS.
4th FLOOR ELEVATION = 518'-6"
‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG 5th FLOOR ELEVATION = 532'-6"
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND A E M
CONSTRUCTION DETAILS.
7. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
8. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
6
9. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
10.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED
ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO
DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601 4TH & 5TH FLOOR FRAMING PLAN - WEST 4TH & 5TH FLOOR
THROUGH CONCRETE BEAMS
11.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH 1 1/8" = 1'-0" N PART A
ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT. FRAMING PLAN -
12.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410,
AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS. PART A
13.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE
5/25/2023 4:01:49 PM
BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR 1
S204A
REQUIREMENTS DIFFER FROM WHAT IS SHOWN.
14.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION
DESIGN IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR
FRAMING WITH CONCRETE FRAMING.
15.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT
DIFFERS THAN WHAT IS SHOWN.
16. INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS. KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
E F H I J K L M
Checked By:
Drawn By:
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0"
GreshamSmith.com
1' - 6"
1' - 6"
E.O.S.
4' - 7"
CB316 (36x21) CB317 (36X24.5) CB318 (36x21) CB319 (36x21) CB320 (36x21) CB321 (36x21) CB400 (36x21)
1' - 6"
1' - 6"
2' - 5"
PIPE PENETRATION Smith
9' - 4"
9' - 6"
E.O.S.
AT 5th FLR. ONLY Seckman
Reid, Inc.
CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB419 (20x21) 2995 Sidco Drive
Nashville, TN 37204
(615) 383-1113
1' - 4"
1' - 8"
FAX: (615) 386-8469
518'-6" www.ssr-inc.com
AT 4th
9' - 6"
9' - 2"
5
FLR.
ONLY S431
PB413 (48x24.5)
PB413 (48x24.5)
SSR Project #: 21640780
PB409 (42x21)
PB409 (42x21)
PB409 (42x21)
PB406 (48x21)
PB403 (50x21)
CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB419 (20x21)
1' - 8"
1' - 4"
9' - 6"
9' - 2"
CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB419 (20x21)
TENNESSEE
1' - 4"
1' - 8"
ONCOLOGY
9' - 6"
9' - 4"
2
S431
1' - 6"
1' - 6"
1' - 6"
1' - 6"
1' - 6"
CB325 (36x21) CB326 (36X24.5) CB327 (36x21) CB398 (36x21) CB329 (36x21) PB416 (36x21)
1' - 6"
1' - 6"
7' - 2"
7' - 2"
8' - 0"
S1
6' - 2"
6' - 2"
PLUMBING PIPE SLEEVE
7' - 6"
S1
S4 S1
8' - 2"
1' - 4"
1' - 4"
6' - 11" 14' - 2 3/4" 6' - 11" 10' - 5 1/4" 2' - 0" 1' - 5"
PB412 (36x21)
PIPE PENETRATION
6' - 10"
1' - 6"
1' - 4"
1' - 8"
STAIRS
PB405A (41x21)
AT 5th FLR. ONLY.
PB410A (42x21)
PB335A (24x21)
CB359 (16x21)
PB408 (42x21)
PB402 (50x21)
PB331 (24x21)
14' - 4"
14' - 4"
S1
STAIRS
PB410 (42x21)
PB333 (24x21)
PB332 (24x21)
PB414 (42x21)
12' - 6"
8' - 0"
7' - 8"
OPEN OPEN
CB373 (16x21) CB375 (16x21) CB376 (16x21)
PLUMBING PIPE SLEEVE
AHU PB420 (20x21)
1' - 4"
CB372 (16x21) HSS8x4x3/8 HSS8x4x3/8
HSS8x4x3/8
CB376B (24x21) CB363A (16x21)
CB360 (16x21) CB375 (16x21)
1' - 8"
1' - 4"
CURTAIN WALL
OPEN OPEN OPEN
SUPPORT FRAMING
8' - 2"
CB363 (16x21)
8' - 0"
2' - 0"
8' - 6"
7" CONC.
5' - 0"
CONSTRUCTION DOCUMENTS
1' - 6"
1' - 6"
1' - 6"
1' - 6"
SLAB
CB325 (36x21) CB327 (36x21) CB398 (36x21) PB416 (36x21)
1' - 6"
1' - 6"
CB329 (36x21)
1' - 6"
CB330A (36X24.5)
1' - 6"
1' - 6"
1' - 6"
PIPE PENETRATION
AT 5th FLR. ONLY.
9' - 4"
9' - 6"
CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB419 (20x21)
1' - 8"
KEEPING PAD
518'-6"
9' - 6"
9' - 2"
S1 5" CONCRETE SLAB
TYP SLAB UNO.
PB411 (48x24.5)
PB411 (48x24.5)
CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB419 (20x21)
PB407 (42x21)
PB407 (42x21)
PB407 (42x21)
PB404 (48x21)
PB401 (50x21)
1' - 4"
1' - 8"
9' - 6"
9' - 2"
CB335 (16x21) CB336 (16x24.5) CB337 (16x21) CB338 (16x21) CB339 (16x21) PB419 (20x21)
1' - 4"
1' - 8"
PIPE PENETRATION
AT 5th FLR. ONLY.
PIPE PENETRATION
9' - 6"
9' - 4"
AT 5th FLR. ONLY.
1' - 6"
1' - 6"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
CB405 (37.5x21) CB406 (37.5x24.5) CB407 (37.5x21) CB408 (37.5x21) CB409 (37.5x21) CB410 (37.5x21) CB411 (37.5x21)
1' - 7 1/2"
E.O.S.
1' - 7 1/2"
1' - 7 1/2"
4
S431
AT 5th
FLR.
1 Revision
ONLY S431
No. Date Description
MATCHLINE - WEST
MATCHLINE - EAST
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND GRAPHICAL REINFORCING SCHEDULE.
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES SHEETS FOR CONCRETE BEAM
REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED
DEPTH IN BEAM TAG NOTE:
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET S620 AND 630 SERIES SHEETS 4th FLOOR ELEVATION = 518'-6"
FOR POST TENSIONED CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE BEAM FRAMING DETAILS.
‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG 5th FLOOR ELEVATION = 532'-6"
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING SCHEDULE AND
CONSTRUCTION DETAILS. A E M
7. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
8. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
9. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL AND M, E, P DRAWINGS.
6
10.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH BEAMS ARE INDICATED
ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED BEYOND WHAT IS SHOWN. REFER TO
DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414 THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601
THROUGH CONCRETE BEAMS
11.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB. COORDINATE WITH 4TH & 5TH FLOOR FRAMING PLAN - EAST N 4TH & 5TH FLOOR
ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
12.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS. REFER TO SHEETS S410,
1 1/8" = 1'-0" PART B FRAMING PLAN -
AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION DETAILS, AND BRACING REQUIREMENTS.
13.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR MANUFACTURE PART B
BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY ENGINEER ELEVATOR
4/25/2023 5:33:28 PM
S204B
14.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND CONNECTION
DESIGN IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE CONNECTIONS AND STAIR
FRAMING WITH CONCRETE FRAMING.
15.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF WEIGHT
DIFFERS THAN WHAT IS SHOWN.
16. INDICATES MECH OR ELECTRICAL/ HOUSEKEEPING REFER TO S443 FOR MECHANICAL EQUIPMENT PAD DETAILS.
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
A B C D E
GreshamSmith.com
1' - 6"
1' - 6"
11
45
45
45
E.O.S.
Smith
4' - 7"
x2
x1
x1
x1
CB539 (36x25) CB540 (36x25) CB541 (36x25) CB542 (36x25) CB543 (36x25)
14
14
14
14
Seckman
W
6 Reid, Inc.
2995 Sidco Drive
1' - 6"
45
1' - 6"
x1
Nashville, TN 37204
14
(615) 383-1113
W
9' - 3"
9' - 6"
FAX: (615) 386-8469
www.ssr-inc.com
PB521 (22x25)
CB509 (16x25) CB510 (16x25) CB511 (16x25)
1' - 10"
SSR Project #: 21640780
1' - 4"
548'-6"
5" CONCRETE SLAB
9' - 0"
9' - 6"
TYP UNO
PB506 (60x30.5)
PB512 (42x25)
S1
PB503 (50x25)
PB509 (42x25)
PB521 (22x25)
CB509 (16x25) CB510 (16x25) CB511 (16x25)
45' - 0"
1' - 10"
45' - 0"
1' - 4"
TENNESSEE
9' - 0"
9' - 6"
2' - 5"
E.O.S. PB521 (22x25) CB509 (16x25) CB510 (16x25) CB511 (16x25)
ONCOLOGY
1' - 10"
1' - 4"
CB563B (16x25)
2 T/ WEST SCREENWALL
S206C COLUMNS 14'-0" A.F.F.
6' - 10"
9' - 6"
11
32
32
1' - 6"
1' - 6"
S431
x2
X1
X1
CB550 (36x25) CB551 (36x25) CB552 (36x25)
14
14
PB525 (36x25)
14
W
W
4 2' - 0" 17' - 5"
3' - 6"
32
6' - 11"
S1
1' - 6"
1' - 6"
S1 1' - 9"
X1
8' - 7"
OPEN
14
7' - 11"
2" 18 GA. COMPOSITE DECK w/ 3 1/4"
8' - 2"
W
L.W. CONCRETE OVER FLUTES: TOTAL W12x26
THICKNESS = 5 1/4". REINF. w/
6x6: W2.9xW2.9 W.W.F. CB563A (16x25)
CB517 (16x25) CB518 (16x25)
5' - 6"
1' - 10"
1' - 5"
1' - 4"
2' - 6" W12x26
PB502 (50x25)
PB508 (42x25)
PB511 (42x25)
PB522 (22x25) CB516A (29x21)
PB505 (47x30.5)
120' - 0"
30' - 0"
9' - 2"
7' - 6"
8' - 0"
5' - 6"
PB516 (30x25)
3 5/8"
CONSTRUCTION DOCUMENTS
CB516 (16x25) CB517 (16x25) CB518 (16x25)
1' - 10"
4' - 0"
C6X8.2
6' - 10"
1' - 4"
C6X8.2 FUTURE STAIRWELL
7' - 11"
8' - 2"
OPENING
1' - 6"
W12x26
32
32
32
11
1' - 6"
X1
X1
X1
19' - 5"
x2
3' - 9"
14
14
14
14
W
W
W
1' - 6"
1' - 6"
1' - 6"
PB525 (36x25) CB550A (36x25) CB557 (36x25) CB558 (36x25)
9' - 3"
9' - 6"
S1
5" CONCRETE SLAB
TYP UNO
PB521 (22x25)
CB501 (16x25) CB502 (16x25) CB503 (16x25)
1' - 10"
1' - 4"
9' - 0"
9' - 6"
PB504 (60x30.5)
PB507 (42x25)
PB510 (42x25)
PB501 (50x25)
PB521 (22x25)
CB501 (16x25) CB502 (16x25) CB503 (16x25)
45' - 0"
1' - 10"
1' - 4"
9' - 0"
9' - 6"
PB521 (22x25) CB502 (16x25)
CB501 (16x25) CB503 (16x25)
1' - 10"
1' - 4"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
9' - 6"
9' - 3"
ANCHORAGE DETAILS
11
x2
45
1' - 6"
1' - 6"
14
45
x1
CB528 (37.5x25) CB529 (37.5x25) CB530 (37.5x25) CB531 (37.5x25) CB532 (37.5x25)
45
14
W
x1
45
x1
14
W
Revision
x1
14
W
1' - 7 1/2"
E.O.S.
14
W
1
W
No. Date Description
1' - 7 1/2"
1' - 7 1/2"
MATCHLINE - WEST
GRAPHICAL REINFORCING SCHEDULE.
MATCHLINE - EAST
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES
SHEETS FOR CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE
BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET
S620 AND 630 SERIES SHEETS FOR POST TENSIONED CONCRETE BEAM REINFORCING
SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’
INDICATED DEPTH IN BEAM TAG
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING
SCHEDULE AND CONSTRUCTION DETAILS.
7. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
8. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
9. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL
AND M, E, P DRAWINGS.
10.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH A E M
BEAMS ARE INDICATED ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED
BEYOND WHAT IS SHOWN. REFER TO DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414
THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601 THROUGH CONCRETE BEAMS 6
11.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB.
COORDINATE WITH ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
12.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS.
REFER TO SHEETS S410, AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION 6TH FLOOR FRAMING PLAN - WEST
DETAILS, AND BRACING REQUIREMENTS.
13.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR
1 1/8" = 1'-0" N PART A 6TH FLOOR FRAMING
MANUFACTURE BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY
ENGINEER ELEVATOR REQUIREMENTS DIFFER FROM WHAT IS SHOWN. PLAN - PART A
14.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND
CONNECTION DESIGN IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE
5/25/2023 4:01:49 PM
S206A
15.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF
WEIGHT DIFFERS THAN WHAT IS SHOWN.
16. INDICATES MOMENT FRAME CONNECTION REFER TO 7/S440 FOR DETAILS
17. REFER TO S440 FOR STD. STEEL BEAM AND METAL DECK CONNECTION DETAILS.
18. REFER TO S441 FOR FUTURE COLUMN ANCHOR BOLT AND BASEPLATE ARRANGEMENT TO BE EMBEDDED
IN THE CONCRETE STRUCTURE IN THIS PHASE FOR THE FUTURE EXPANSION.
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
E F H I J K L M
MVW
KJM
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0"
Drawn By:
GreshamSmith.com
7 PARAPET FRAMING
222 Second Avenue South
8" THK. CONC. SLAB S431 SEE DETAILS Suite 1400
Nashville, TN 37201
615.770.8100
1' - 6"
1' - 6"
E.O.S.
4' - 7"
CB542 (36x25) CB543 (36x25) CB544 (36x25) CB545 (36x25) CB546 (36x25) CB547 (36x25) CB548 (36x25) CB549 (36x25)
11
11
11
45
45
45
45
W1' - 6"
45
1' - 6"
x2
x2
x2
x1
x1
x1
x1
x1
14
14
14
14
14
14
14
14
W
W
W
W
9' - 3"
9' - 6"
Smith
Seckman
CB510 (16x25) CB511 (16x25) CB512 (16x25) CB513 (16x25) CB514 (16x25) CB515 (16x25) PB523 (22x25) Reid, Inc.
1' - 10"
1' - 4"
2995 Sidco Drive
Nashville, TN 37204
(615) 383-1113
5" SLAB FAX: (615) 386-8469
548'-6"
S1
9' - 6"
9' - 0"
CONCRETE TYP
PB515 (60x28.5)
PB506 (60x30.5)
www.ssr-inc.com
PB515 (60x28.5)
PB512 (42x25)
PB512 (42x25)
PB509 (42x25)
UNO
PB503 (50x25)
CB510 (16x25) CB511 (16x25) CB512 (16x25) CB513 (16x25) CB514 (16x25) CB515 (16x25) PB523 (22x25) SSR Project #: 21640780
45' - 0"
1' - 10"
1' - 4"
9' - 6"
9' - 0"
6
S431
CB510 (16x25) CB511 (16x25) CB512 (16x25) CB513 (16x25) CB514 (16x25) CB515 (16x25) PB523 (22x25)
1' - 10"
1' - 4"
2" 18 GA. COMPOSITE DECK
w/ 3 1/4" L.W. CONCRETE
T/ WEST SCREENWALL
COLUMNS 14'-0" A.F.F.
FUTURE
ELEVATOR
OVER FLUTES: TOTAL
THICKNESS = 5 1/4". REINF. w/ MECH. SHAFT
T/ EAST SCREENWALL
COLUMNS 24'-0" A.F.F.
TENNESSEE
9' - 6"
OPENING
9' - 3"
SHAFT
OPENINGS
6x6: 2.9xW2.9 W.W.F.
1
ONCOLOGY
32
11
32
11
1' - 6"
1' - 6"
CB554 (36x25) CB555 (36x25) CB556 (36x25) PB526 (36x25)
X1
x2
X1
x2
CB551 (36x25) CB552 (36x25) CB553 (36x28.5) S206C
14
14
14
14
W
W
W
W
4 2' - 0"
32
X1
11
1' - 6"
1' - 6"
7' - 2"
7' - 2"
14
7' - 8"
X1
x2
W
6' - 2"
S1
14
14
S1
S4 L.W. CONCRETE OVER FLUTES: TOTAL
7' - 7"
W
S1
W
CB522 (16x25) CB563 (16x25) 2' - 6" THICKNESS = 5 1/4". REINF. w/ 2' - 5"
CB526 (16x25) CB519 (16x25) S206C
CB520 (16x25) 6x6: W2.9xW2.9 W.W.F.
CB527 (16x25)
E.O.S.
1' - 4"
CB517 (16x25) PB524 (22x25)
4' - 9"
CB518 (16x25)
1' - 10"
5' - 4"
5' - 0 1/4"
CB524 (16x25) CB521A (16x25)
PB514A (48x28.5)
S1
PB505A (47x30.5)
6' - 10"
W12x26 W12x26
PB520 (24x25)
PB511 (42x25)
PB502 (50x25)
PB511 (42x25)
PB508 (42x25)
W12x26 W12x26
4' - 9"
30' - 0"
8' - 2"
10' - 5 1/4"
PB518 (30x28.5)
5' - 4"
PB517 (30x25)
S5
W12x26
W12x26 PB524 (22x25)
CB517 (16x25) CB518 (16x25) W12x26 W12x26 1' - 6" 7"
21' - 0"
W12x26
1' - 10"
C6X8.2
7' - 0"
5' - 4"
W12x26
H.B.
7' - 7"
5' - 8"
5' - 0 1/4"
H.B. W12x26
8' - 7"
4' - 10"
5' - 4"
FUTURE
32
1' - 6"
11
1' - 6"
8
32
1' - 6" 1' - 6"
32
X1
STAIR PB526 (36x25)
X1
CONSTRUCTION DOCUMENTS
x2
X1
X1
14
14
14
S442 OPENING
14
14
W
W
W
W
7' - 2 3/4"
3
1' - 6"
11
1' - 6"
1' - 6"
CB559 (36x28.5)
11
x2
CB557 (36x25) CB558 (36x25) CB560 (36x25) CB561 (36x25) CB556A (36x25)
x2
14
14
W
9' - 3"
W
9' - 6"
S1
FUTURE STAIR L.W. CONCRETE OVER FLUTES: TOTAL PARAPET FRAMING
OPENING THICKNESS = 5 1/4". REINF. w/ SEE DETAILS
6x6: W2.9xW2.9 W.W.F. PB523 (22x25)
CB502 (16x25) CB503 (16x25) CB505 (16x25) CB506 (16x25) CB507 (16x25)
CB504 (16x25)
1' - 10"
1' - 4"
5" SLAB
5" CONC. CONCRETE TYP
9' - 6"
9' - 0"
SLAB UNO
S1
PB510 (42x25)
PB513 (60x28.5)
PB513 (60x28.5)
PB504 (60x30.5)
PB523 (22x25)
PB501 (50x25)
CB504 (16x25) CB505 (16x25)
PB510 (42x25)
CB506 (16x25) CB507 (16x25)
PB507 (42x25)
CB502 (16x25) CB503 (16x25)
45' - 0"
1' - 10"
1' - 4"
9' - 6"
9' - 0"
CB502 (16x25) CB505 (16x25) CB506 (16x25) CB507 (16x25) PB523 (22x25)
CB503 (16x25) CB504 (16x25)
1' - 10"
1' - 4"
45 9' - 3"
ANCHORAGE DETAILS
45
1' - 6"
45
11
W
11
45
x1
CB533 (37.5x25) CB534 (37.5x25) CB535 (37.5x25) CB536 (37.5x25) CB537 (37.5x25)
x1
CB531 (37.5x25) CB532 (37.5x25)
14
x2
x2
x1
14
x1
45
14
14
x2
14
CB538 (37.5x25)
14
14
x1
W
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
11
W
W
14
W
1' - 7 1/2"
W
E.O.S.
1' - 6"
1' - 7 1/2"
1' - 7 1/2"
6
S431 PARAPET FRAMING
NOTES:
1. REFER TO S00 SHEETS FOR GENERAL NOTES.
SEE DETAILS
Revision
2. REFER TO S00 SHEETS SPECIAL INSPECTION REQUIREMENTS
3. REFER TO S500 SERIES SHEETS FOR CONCRETE COLUMNS DETAILS AND
No. Date Description
MATCHLINE - WEST
4. CB# (WxD), INDICATES CONCRETE BEAMS REFER TO SHEET S600 SERIES 1 05.26.2023 Addendum No. 1
SHEETS FOR CONCRETE BEAM REINFORCING SCHEDULES AND CONCRETE
BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’ INDICATED DEPTH IN BEAM TAG
5. PB # (WxD), INDICATES POST TENSIONED CONCRETE BEAMS REFER TO SHEET
S620 AND 630 SERIES SHEETS FOR POST TENSIONED CONCRETE BEAM REINFORCING
SCHEDULES AND CONCRETE BEAM FRAMING DETAILS. ‘W’ INDICATES WIDTH, ‘D’
INDICATED DEPTH IN BEAM TAG
6. S# INDICATES ONE WAY REINFORCED CONCRETE SLAB, REFER TO S414 FOR REINFORCING
SCHEDULE AND CONSTRUCTION DETAILS.
7. REFER TO S500 SERIES SHEETS FOR COLUMN DETAILS AND SCHEDULES.
8. REFER TO ARCHITECTURAL PLANS FOR ALL DIMENSIONS NOT SHOWN
9. COORDINATE ALL SLAB DEPRESSIONS AND EQUIPMENT PADS WITH ARCHITECTURAL
AND M, E, P DRAWINGS.
10.COORDINATE SLEEVE LOCATIONS WITH M,E,P DRAWINGS. REQUIRED SLEEVES THROUGH
BEAMS ARE INDICATED ON PLANS NOTIFY ENGINEER IF ADDITIONAL SLEEVES ARE REQUIRED
BEYOND WHAT IS SHOWN. REFER TO DETAIL 1&2/S413 FOR SLEEVES THROUGH PT SLABS, 1/S414
THROUGH REINF. CONCRETE SLABS, AND 2 &4/S601 THROUGH CONCRETE BEAMS
11.REFER DETAIL 2/S414 FOR REINFORCING AROUND CONDUIT EMBEDDED IN CONCRETE SLAB.
COORDINATE WITH ELECTRICAL PLANS FOR LOCATIONS, SIZE AND ROUTING OF EMBEDDED CONDUIT.
12.REFER TO ARCHITECTURAL PLANS FOR ALL NON- LOADBEARING CMU WALL LOCATIONS.
REFER TO SHEETS S410, AND S411 FOR CMU WALL REINFORCING SCHEDULE, CONSTRUCTION
A E M
DETAILS, AND BRACING REQUIREMENTS.
13.ELEVATOR RAIL SUPPORT AND BRACING REQUIREMENTS SHALL BE COORDINATED WITH ELEVATOR
MANUFACTURE BY CONTRACTOR. REFER TO SHEET S443 FOR TYPICAL RAIL SUPPORT DETAILS NOTIFY
ENGINEER ELEVATOR REQUIREMENTS DIFFER FROM WHAT IS SHOWN. 6
14.REFER TO S443 FOR STAIR LANDING AND HANGER CONNECTION TYPICAL DETAILS. STAIR DESIGN AND
CONNECTION DESIGN IS THE RESPONSIBILITY OF STAIR MANUFACTURER. CONTRACTOR TO COORDINATE
CONNECTIONS AND STAIR FRAMING WITH CONCRETE FRAMING.
6TH FLOOR FRAMING PLAN - EAST N
15.WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF
16.
WEIGHT DIFFERS THAN WHAT IS SHOWN.
INDICATES MOMENT FRAME CONNECTION REFER TO 7/S440 FOR DETAILS
1 1/8" = 1'-0"
PART B 6TH FLOOR FRAMING
17. REFER TO S440 FOR STD. STEEL BEAM AND METAL DECK CONNECTION DETAILS.
18. REFER TO S441 FOR FUTURE COLUMN ANCHOR BOLT AND BASEPLATE ARRANGEMENT TO BE EMBEDDED
PLAN - PART B
IN THE CONCRETE STRUCTURE IN THIS PHASE FOR THE FUTURE EXPANSION.
5/25/2023 4:01:50 PM
S206B
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
Approved By: Approver H I J K
Checker
Author
Checked By:
Drawn By:
MECH. SHAFT
OPENING
11' - 10" GreshamSmith.com
COOLING TOWER 2
S441 3
1 5/8" 11' - 6 3/4" 1 5/8" S206C
3'-0" CLR.
Suite 1400
MIN.
L4X4X Nashville, TN 37201
3/8
615.770.8100
2"
W16X36
6 3
S442 S441
SPRING ISOLATORS. COORD.
w/ MECHANICAL SUPPORT
8)
3/
SUBMITTAL.
15' - 0"
(L
Smith
11' - 11"
2' - 6" 11' - 6" 1' - 5" Seckman
4' - 9"
Reid, Inc.
W18X50
W18X50
2995 Sidco Drive
(L
W12x26 Nashville, TN 37204
4X
4X
COOLING TOWER (615) 383-1113
1 2" 18 GA. COMPOSITE
3/
30,000 LBS. FAX: (615) 386-8469
8)
2 DECK w/ 3 1/4" L.W.
COOLING TOWER
S442 www.ssr-inc.com
S442 CONCRETE OVER FLUTES
4' - 9"
TOTAL THICKNESS = 5 1/4".
24' - 2"
W16X36 REINF. w/ 6x6: W2.9xW2.9 W.W.F. SSR Project #: 21640780
W12x26
7
3 3"
5 S442
S441 7"
(L
8)
S441
4X
3/
4X
4X
C6X8.2
4X
3/
7' - 0"
8)
(L
2' - 0"
11' - 11"
T / COOLING TOWER
SUPPPORT STEEL
EL= 4'-1" A.F. 6TH FLR.
C6X8.2
TENNESSEE
3"
ROOF HATCH
S441
6
3
W12x26 SEE ARCH.
ONCOLOGY
S442
8' - 7"
MIN.
4' - 10"
9
W16X36
S442
(L4X4
2"
X3/8)
3'-0" CLR.
10' - 7 3/4"
3' - 4 1/2" 1' - 11 3/4"
2
S441
NOTES:
1. COOLING TOWER SUPPORT STRUCTURE HAS BEEN DESIGNED AROUND EVAPCO MODEL AT212-3M24
WEIGHING 30,000LBS. CONTRACTOR IS RESPONSIBLE FOR COORDINATING BEAM LOCATIONS AND DETAILING
OF SUPPORT STRUCTURE IF SUBMITTED AND APPROVED COOLING TOWER DOES NOT MATCH THE INDICATED
BASIS OF DESIGN LISTED ABOVE.
2. ALL EXPOSED STEEL SHALL BE HOT DIPPED GALVANIZED.
J
D D
3' - 3" 10' - 7"
10' - 7" 6' - 10"
1
J 4' - 9" 5' - 10"
2" 18 GA. COMPOSITE DECK w/ 3 1/4" 5' - 11" 4' - 8"
2' - 0" 17' - 5"
L.W. CONCRETE OVER FLUTES: TOTAL
THICKNESS = 5 1/4". REINF. w/
6x6: W2.9xW2.9 W.W.F.
4 4
S442 S442 4
4 4
.
M
4 4' - 9" 5' - 1" S442
1' - 6"
1' - 6"
SI
.
M
SI
7' - 6"
2' - 5"
4
4' - 0 1/2"
1' - 4" C6X8.2
4' - 0"
C6X8.2
3"
4' - 1"
C6X8.2
OPEN
C6X8.2
8' - 7"
7' - 0 1/4"
6' - 2"
5 5 C8X11.5
1' - 9" 1' - 10"
S442
C6X8.2
W10X15
W10X15
C6X8.2
7"
3' - 2"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
C6X8.2 5
7' - 8"
C6X8.2 C8X11.5
2' - 11 3/4"
2' - 2"
W10X15
W10X15
HSS6X2X1/4 S442
C6X8.2
3' - 0"
C8X11.5 C8X11.5
3' - 4 1/2"
C6X8.2
5
2' - 0"
S442
REFER TO 1&2/S402 FOR
SIM.S CONNECTION TO
6" CONC. BEAM 2" 18 GA. COMPOSITE DECK w/ 3 1/4"
L.W. CONCRETE OVER FLUTES: TOTAL
Revision
THICKNESS = 5 1/4". REINF. w/
2" 18 GA. COMPOSITE DECK w/ 3
1/4" L.W. CONCRETE OVER FLUTES:
6x6: W2.9xW2.9 W.W.F. No. Date Description
TOTAL THICKNESS = 5 1/4" . REINF. 2" 18 GA. COMPOSITE DECK w/ 3 1/4" 1 05.26.2023 Addendum No. 1
4 L.W. CONCRETE OVER FLUTES: TOTAL
w/ 6x6: W2.9xW2.9 W.W.F.
S442 THICKNESS = 5 1/4". REINF. w/
6x6: W2.9xW2.9 W.W.F.
2ND FLOOR WEST CHASE FRAMING PLAN 2ND FLOOR EAST CHASE FRAMING PLAN
4 1/4" = 1'-0" 5 1/4" = 1'-0"
6TH FLOOR WEST CHASE FRAMING PLAN 6TH FLOOR EAST CHASE FRAMING PLAN NOTES: NOTES:
2 1/4" = 1'-0" 3 1/4" = 1'-0" 1. CONTRACTOR TO COORDINATE SIZE AND LOCATION OF MECH EQUIPMENT PENETRATIONS THROUGH ROOF
SLAB WITH MECH SUBCONTRACTORS PRIOR TO FABRICATION OF STEEL COMPONENTS OR CONSTRUCTION
1. CONTRACTOR TO COORDINATE SIZE AND LOCATION OF MECH EQUIPMENT PENETRATIONS THROUGH ROOF
SLAB WITH MECH SUBCONTRACTORS PRIOR TO FABRICATION OF STEEL COMPONENTS OR CONSTRUCTION
NOTES: OF CONCRETE FLOOR AND BEAMS OF CONCRETE FLOOR AND BEAMS
1. CONTRACTOR TO COORDINATE SIZE AND LOCATION OF MECH EQUIPMENT PENETRATIONS THROUGH ROOF
SLAB WITH MECH SUBCONTRACTORS PRIOR TO FABRICATION OF STEEL COMPONENTS OR CONSTRUCTION NOTES:
OF CONCRETE FLOOR AND BEAMS 1. CONTRACTOR TO COORDINATE SIZE AND LOCATION OF MECH EQUIPMENT PENETRATIONS THROUGH ROOF
SLAB WITH MECH SUBCONTRACTORS PRIOR TO FABRICATION OF STEEL COMPONENTS OR CONSTRUCTION
OF CONCRETE FLOOR AND BEAMS A E M
S206C
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
A B C D E
GreshamSmith.com
Smith
Seckman
6 Reid, Inc.
2995 Sidco Drive
Nashville, TN 37204
(615) 383-1113
FAX: (615) 386-8469
www.ssr-inc.com
45' - 0"
TENNESSEE
ONCOLOGY
3" 18GA VL COMPOSITE DECK WITH 3-1/4"
L.W. CONCRETE OVER FLUTES: TOTAL
THICKNESS =6-1/4" - PHASE 1
HSS8x8x3/8 HSS8x8x3/8
HSS8x8x3/8
HSS8x8x3/8
120' - 0"
30' - 0"
4
9 S441
S442
3
HSS8x8x3/8 HSS8x8x3/8
HSS8x8x3/8" T/ STEEL
+3'-2" OVER 6TH FLOOR FFE
FUTURE 3" 18GA VL COMPOSITE DECK WITH +9'-2" OVER 6TH FLOOR FFE
3 1/4" L.W. CONCRETE OVER FLUTES: TOTAL +13'-2" OVER 6TH FLOOR FFE
THICKNESS =6-1/4" - PHASE 2 THIS BAY ONLY AT DOOR
45' - 0"
562'-6"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
Revision
1
No. Date Description
MATCHLINE - WEST
MATCHLINE - EAST
NOTES:
1. WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF
WEIGHT DIFFERS THAN WHAT IS SHOWN.
2. INDICATES MOMENT FRAME CONNECTION REFER TO 7/S440 FOR DETAILS
3. REFER TO S440 FOR STD. STEEL BEAM AND METAL DECK CONNECTION DETAILS. A E M
4. REFER TO S441 FOR FUTURE COLUMN ANCHOR BOLT AND BASEPLATE ARRANGEMENT TO BE EMBEDDED
IN THE CONCRETE STRUCTURE IN THIS PHASE FOR THE FUTURE EXPANSION.
5. ALL EXPOSED STEEL SHALL BE HOT DIPPED GALVANIZED.
6
S207A
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
MVW
KJM
E F H I J K L M
Checked By:
Drawn By:
30' - 0" 40' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 15' - 0"
GreshamSmith.com
Smith
Seckman
Reid, Inc.
2995 Sidco Drive
Nashville, TN 37204
(615) 383-1113
FAX: (615) 386-8469
www.ssr-inc.com
562'-6"
4 W24x68 W24x68
8' - 1 1/4"
8' - 1 1/4"
S441
4 5/8" T/STEEL=572'-6" TYP.
10' - 0"
HSS8x8x3/8
10"
10 3/4"
10"
HSS8x8x3/8
HSS8x8x3/8
W24x68
W24x68
W24x68
W24x68
30' - 0"
10"
T/STEEL= SEE BELOW
CONSTRUCTION DOCUMENTS
S441
1' - 6"
S441
1' - 6"
1' - 6"
W24x68 W24x68 W24x68
3
HSS8x8x3/8
HSS8x8x3/8 HSS8x8x3/8 HSS8x8x3/8
9
HSS8x8x3/8" T/ STEEL
+3'-2" OVER 6TH FLOOR FFE S442
+9'-2" OVER 6TH FLOOR FFE 3" 18GA VL COMPOSITE DECK WITH 3-1/4"
+13'-2" OVER 6TH FLOOR FFE L.W. CONCRETE OVER FLUTES: TOTAL
THIS BAY ONLY AT DOOR HSS8x8x3/8" T/ STEEL
THICKNESS =6-1/4" - PHASE 2
+3'-2" OVER 6TH FLOOR FFE
+9'-2" OVER 6TH FLOOR FFE
+13'-2" OVER 6TH FLOOR FFE
+18'-2" OVER 6TH FLOOR FFE
+23'-0" OVER 6THE FLOOR FFE
THIS BAY ONLY AT DOOR
45' - 0"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
Revision
No. Date Description
MATCHLINE - WEST
MATCHLINE - EAST
NOTES:
1. WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT IS SHOWN ON THE PLANS. NOTIFY ENGINEER IF
WEIGHT DIFFERS THAN WHAT IS SHOWN.
2. INDICATES MOMENT FRAME CONNECTION REFER TO 7/S440 FOR DETAILS
3. REFER TO S440 FOR STD. STEEL BEAM AND METAL DECK CONNECTION DETAILS.
4. REFER TO S441 FOR FUTURE COLUMN ANCHOR BOLT AND BASEPLATE ARRANGEMENT TO BE EMBEDDED
IN THE CONCRETE STRUCTURE IN THIS PHASE FOR THE FUTURE EXPANSION.
5. ALL EXPOSED STEEL SHALL BE HOT DIPPED GALVANIZED.
A E M
S207B
KEYPLAN 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
CONCRETE BEAM E
E
MVW
KJM
1" CLR.
Drawn By:
1 1/4"
1/2"x18"x7" BASE PLATE
1" CLR.
w/ (2) 3/4"x8" A.B. w/ 4.4" PROJECTION L5x3x5/16"x10" (LLV) 222 Second Avenue South
1' - 10 5/8"
3/16 3 @ 12
Suite 1400
CLOSURE WALL BOLT IN LONG Nashville, TN 37201
BELOW SLOTTED HOLE 615.770.8100
1' - 0 3/4"
HSS5x5x1/4" @ T/STL. 1' - 2"
EL. 472'-2", EL. 479'-6"
SLAB EDGE
1 1/4" HSS12x4x3/8" CONNECTION
AND EL. 487'-4 1/2" 3/16 3 @ 12 AT SECOND FLOOR
2 3/4"
CONCRETE WALL
SEE 2/S425
Smith
1'-10 1/2"
1/2"x2 1/2"x11 3/4" BENT PLATE.
BTM. OF COLUMN = 474'-0" EXTEND FROM TOPPING SLAB Seckman
3/16 UP 42" Reid, Inc.
1' - 8 3/4"
10 1/2"
0.1A
CLOSURE WALL
REINF.
3" CONC. LEDGE
BELOW
#5 VERT IN
CMU WALL T/CONC. CLOSURE
WALL BELOW 1
3' - 1 5/8"
EL. = 468'-6"
7' - 6 5/8"
REINIF. AND DETAILS
12" CONCRETE
WALL BELOW T/ CONC. WALL = 475'-6"
8"
5' - 8"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
8"
1' - 0" CONC. WALL AT DRIVE
6 SEE 2/S420
7' - 6"
T/CONC. CLOSURE 8" CONC. WALL
WALL BELOW
EL. = 468'-6" Revision
8"
1' - 3"
8"
7" 1' - 2" AT ENTRANCE
SEE 3/S420
7"
7 5/8"
T/ CONC. WALL = 476'-6"
T/ CONC. LEDGE
474'-6"
7 5/8" 8" 8" 7 5/8"
#4 @ 12"O.C. HORIZ.
1' - 0 3/4"
1' - 10 5/8" 5' - 5"
T/LEDGE = 470'-10"
8" CONC. WALL. T/WALL = 472'-6".
7"
PB214 BELOW AT
EL. 470'-0" REFER TO 8/S424 FOR REINF. 10" CONCRETE SLAB @470'-0". REINF.
AT SIM. WALL w/ #5 @6" O.C. T& B E.W. REFER
TO 2/S420 FOR SIM. DETAILS
1' - 2 3/4"
S300
1" = 1'-0" 1" = 1'-0"
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
M.1
I
1
MVW
KJM
2' - 1 5/8"
2" 18 GA. COMPOSITE DECK W/ 3 1/4"
12" CONCRETE L.W. CONCRETE OVER FLUTES:
WALL BELOW 7 1/4"x6" NOTCH FOR TOTAL THICKNESS = 5 1/4". REINF. W/
1' - 11"
BRICK LEDGE 6x6:W2.9xW2.9 W.W.F.
2 1/4"
2' - 10 3/8"
#5 @ 8"O.C. VERT.
Smith
3 1/4"
1/2"x5 1/2"x8 1/2"x2 1/2" Seckman
Reid, Inc.
3' - 6"
PROTECTION PLATE 4
S301
6 2995 Sidco Drive
1' - 0"
1/2"x8"x9" BASE PLATE Nashville, TN 37204
w/(3) 3/4"x6" EXPANSION (615) 383-1113
8"
ANCHORS FAX: (615) 386-8469
www.ssr-inc.com
7 5/8"
7 1/4"x6" NOTCH FOR
BRICK LEDGE SSR Project #: 21640780
TENNESSEE
ONCOLOGY
TYPICAL GARAGE DOOR JAMB DETAIL NORTHEAST BUILDING CORNER DETAIL 1ST FLOOR B1 & B2 KNOCK-OUT PANEL PLAN DETAIL
1 1" = 1'-0" 2 1" = 1'-0" 3 3/4" = 1'-0"
L2-1/2x2-1/2x5/16xCONT.
C8x11.5 CHANNEL W/ C8x11.5 CHANNEL W/ CONC. CRASH WALL
3/4"x5" H.S. @ 8" O.C. 3/4"x5" H.S. @ 8" O.C. L2-1/2x2-1/2x5/16xCONT.
3 1/4" L.W. CONC. SLAB (SEE DETAILS)
C8x11.5 CHANNEL W/
PT NON-STRESSING END
CONSTRUCTION DOCUMENTS
6x6:W2.9xW2.9 W.W.F.
8"
5 1/4"
8"
8"
2" VLI 18GA. DECK
PT STRESSING END
2" VLI 18GA. DECK (3)-#6 CONT.
3"@12" 3/16
CHANNEL DISCONTINUOUS @ TOP & BOTT.
3"@12" 3/16 STRESSING LOCATION. COORDINATE 3"@12" 3/16
REQUIRED ACCESS WIDTH &
LOCATION W/ PT CONTRACTOR. 3"@12" 3/16
Revision
No. Date Description
1 05.26.2023 Addendum No. 1
ENLARGED PLAN
DETAILS
5/25/2023 4:01:51 PM
S301
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
SLAB REINFORCING 1/8" SAW OR TROWEL CUT JOINT SLAB REINFORCING 1/8" SAW OR TROWEL CUT JOINT
TOP STEEL IF REQ'D.
(REFER TO PLANS FOR AT 1/4 DEPTH OF SLAB. FILL JOINT (REFER TO PLANS FOR AT 1/4 DEPTH OF SLAB. FILL JOINT
SEE CONT. WALL FTG. SIZE AND SPACING) WITH FLEXIBLE SEALANT SIZE AND SPACING) WITH FLEXIBLE SEALANT
SCHEDULE
2' - 4" MIN.
CLASS B LAP SPLICE BETWEEN STEPS
ADD CORNER BAR TO MATCH
EQ
ADD CORNER BAR TO MATCH FTG.
FTG. REINFORCING, LAP SPLICES REINFORCING, LAP SPLICES PER LAP
MVW
EQ
16" MAX
8" MIN.
FTG. STEP - SEE PLAN FOR
LOCATION & T/FTG. EL.
Checked By:
Drawn By:
VAPOR BARRIER FREE DRAINING VAPOR BARRIER DIAMOND DOWEL DIAMOND SHAPED
BOTTOM BAR GRANULAR MATERIAL 1/4"x4 1/2"x 4 1/2" DOWEL AT 18" O.C.
FREE DRAINING GreshamSmith.com
GRANULAR MATERIAL
MATCH BOTTOM BAR SIZE
& SPACING STD HOOK EACH
END
CONTROL JOINT CONSTRUCTION JOINT
NOTE: APPLIES TO SLABS-ON-GRADE GREATER THAN 6" THICK. NOTE: APPLIES TO ALL SLABS-ON-GRADE.
CONTINUOUS FOOTING, SLAB REINFORCING 1/8" SAW OR TROWEL CUT JOINT SLAB REINFORCING 1/2" EXPANSION JOINT
SEE PLAN AND SCHEDULE. CONTINUOUS FOOTING,
SEE PLAN AND SCHEDULE. 1' - 4" MIN. (REFER TO PLANS FOR AT 1/4 DEPTH OF SLAB. FILL JOINT (REFER TO PLANS FOR MATERIAL, FULL DEPTH
SIZE AND SPACING) WITH FLEXIBLE SEALANT SIZE AND SPACING) OF SLAB, CAULK AND 222 Second Avenue South
SEAL JOINT Suite 1400
Nashville, TN 37201
615.770.8100
AT 'T' INTERSECTION AT CORNER WALL / COLUMN
TYPICAL FOOTING STEP
2 3/4" = 1'-0"
# #
TENNESSEE
ONCOLOGY
C.J.
ROUGHEN CONCRETE #4 @ 12" O.C. AROUND PERIMETER. CONCRETE
C.J.
SURFACE FOR USE STD. 90 DEGREE HOOKS OR COLUMN
NOTE 2
BONDING AGENT EMBED 3" MIN. USING ADHESIVE
ANCHORING SYSTEM INSTALLED IN CONCRETE NOTE 2
ACCORDANCE W/MANFACTURER'S COLUMN
3"
NOTE 1 NOTE 1
.
IN
WRITTEN INSTRUCTIONS.
MI
M
N.
6"
.
IN
ELECTRICAL/MECHANICAL
M
NOTE 3
3"
CONTRACTOR
SLAB CONTROL EDGE OF SLAB
SLAB ON GRADE 3/4" CHAMFER (TYP.) JOINTS - TYP.
2" CLR.
SEE PLAN
SLAB ON GRADE EDGE OF SLAB
SEE PLAN ON GRADE
4"
C.J.
1' - 0"
(2) #4 x 3'-0"
4 1" = 1'-0"
SEE NOTE 1
6" MAX.
#4 CONT.
#4 @ 18"O.C.
1
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
W.W.F.
#4 @ 12" MAX. CONT.
SLAB ON GRADE (2 BAR MIN.) 3/4" N.M. N.S.
Revision
3'-0"
SLAB ON GRADE. SEE REINF. SLAB ON GRADE. SEE
PLAN FOR REINF. 24" PLAN FOR SIZE AND GROUT
(3) #5 CONT.
2' - 0"
#4 @ 12"O.C.
REINF.
#4 @ 12"O.C. 1/4 No. Date Description
SLAB ON GRADE. SEE
TOPPING SLAB 1 05.26.2023 Addendum No. 1
SEE NOTE 1
1' - 0"
1' - 0"
GRANULAR BASE
SEE PLAN
WATERSTOP 4" 8" 4" (3) #4 CONT. TOPPING SLABS - SEE ARCH.
GRANULAR SUB-BASE
SOUND ROCK STRUCTURAL SLAB
NOTES: 1' - 0" 1' - 0"
NOTE:
1' - 0" 1. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING AND 1. SEE ARCHITECTURAL DRAWINGS FOR REQUIRED BOLLARD LOCATIONS AT SLAB ON GRADE.
APPLICABLE EQUIPMENT MANUF. DRAWINGS FOR SLOPES 2. THIS DETAIL APPLIES TO B1 BOLLARD TYPE AS DICTATED ON THE ARCHITECTURAL PLANS.
AND / OR DRAINS IN SLAB AS WELL AS DEPTH OF THE
REQUIRED RECESS.
2. REFER TO PLANS FOR THICKNESS AND REINFORCING OF SECTION AT RAMP
CONCRETE SLAB ON GRADE. 9 1" = 1'-0" CONCRETE PIPE BOLLARD DETAIL
10
TURNED-DOWN SLAB ON GRADE SECTION TYPICAL SLAB STEP
1" = 1'-0"
FOUNDATION
7 1" = 1'-0"
8 SECTION AND
1" = 1'-0"
DETAILS
5/25/2023 4:01:53 PM
S400
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
COL. & FTG.
CLASS B LAP SPLICE
SEE PLAN AND SCHEDULE FOR
COLUMN SIZE AND REINF.
ISOLATED FOOTING SCHEDULE
DOWELS TO MATCH VERT.
CLASS B LAP
Approved By: Approver
SPLICE
SAME SIZE AND SPACING AS
MVW
STEEL
F48 4' - 0" 4' - 0" 36" (8) #7 BOTTOM E.W. A
SLAB REINF. - SEE PLAN F60 5' - 0" 5' - 0" 36" (9) #7 BOTTOM E.W. A SPLICE BARS SHALL BE
F60A 5' - 0" 6' - 0" 36" (9) #7 LONG WAY, (11) #7 SHORT WAY BOTTOM A SAME SIZE AND SPACING AS STANDARD HOOK. EXTEND
HORIZONTAL WALL STEEL BAR TO OUTSIDE FACCE OF
LAP SPLICE
F60B 5' - 0" 7' - 0" 36" (9) #7 LONG WAY, (13) #7 SHORT WAY TOP & BOTTOM A GreshamSmith.com
STEEL
T/SLAB F72 6' - 0" 6' - 0" 42" (10) #8 BOTTOM E.W. A
F72A 6' - 0" 6' - 0" 42" (10) #8 BOTTOM E.W. TOP & BOTTOM A
SEE PLAN
F72B 6' - 0" 7' - 0" 42" (10) #8 LONG WAY, (12) #8 SHORT WAY TOP & BOTTOM A
F72C 6' - 0" 8' - 0" 42" (10) #8 LONG WAY, (15) #8 SHORT WAY TOP & BOTTOM A
SEE PLAN
PROVIDE TIES @ 6" F84 7' - 0" 7' - 0" 42" (12) #8 BOTTOM E.W. A
IN FOOTING AROUND
3" MAX.
2" MIN.
2" CLR.
DOWELS. MATCH TIES ALTERNATE DIRECTION
SEE PLAN FOR FOOTING SIZE
IN CLOUMN SCHEDULE
AND SCHEDULE FOR REINF. OF HOOK 222 Second Avenue South
Suite 1400
TOP BARS - SEE PLAN AT INSIDE CORNER PLAN AT WALL TEE PLAN AT WALL END Nashville, TN 37201
SCHEDULE 615.770.8100
2" CLR.
NOTES:
3" CLR.
W18 1' - 6" 12" (2) #5 CONTINUOUS & #4 @ 24"O.C. TRANSVERSE
W42 3' - 6" 12" (4) #5 CONT. -T & B AND #5 @ 12"O.C. T & B TRANSVERSE Reid, Inc.
W60 5' - 0" 15" (6) #5 CONT. -T & B AND #5 @ 12"O.C. T & #6 @12" B 2995 Sidco Drive
T/ COMPETENT ROCK TRANSVERSE Nashville, TN 37204
(615) 383-1113
FAX: (615) 386-8469
www.ssr-inc.com
HSS COLUMN PER
STAIR SUPPLIER EMBED PLATE 5/8"x10"x0'-10"
SSR Project #: 21640780
w/ (4) 3/4"⌀ x 6" LONG HEADED
STUDS
1 1/2" ⌀ x 6'-0" TEST HOLE HORIZONTAL REINFORCING SHALL BE PROVIDE (2) ADDITIONAL VERT. STRINGER BY STAIR SUPPLIER
PER GEOTECHNICAL CONTINUOUS THROUGH CONSTRUCTION BARS EA. SIDE OF CONSTRUCTION SLAB ON GRADE
ENGINEER JOINT - SEE CORRESPONDING WALL JOINT. SIZE OF VERT. BARS TO L 3x3x1/4x0'-6" w/ 3/4"⌀ EXPANSION 3/16 SEE PLAN
SECTIONS FOR SIZE AND SPACING MATCH ADJACENT VERT. BARS. ANCHOR, 4" MIN. EMBED
2" 2" #4 @ 24"o.c.
WATERPROOFING AT BASEMENT
AT FTG. BEARING ON COMPETENT BEDROCK EXTERIOR SIDE WALLS AS REQ'D. - SEE ARCH. SLAB ON GRADE. SEE PLAN
FOR SIZE AND REINF.
1' - 0"
EQ
COL. & FTG. TENNESSEE
EQ
F24 FTG. SEE SCHEDULES FOR
1' - 0"
AT D < 5'-0", 2'-0" SIZE AND REINF.
ONCOLOGY
EQ
AT 5'-0" < D < 10'-0",
3'-0"
FOOTING - SEE ABOVE INTERIOR SIDE (2) #5 CONT. BOTTOM
#5 @ 12" O.C. E.W. CONTINUE THICKENED SLAB
2/3 D COORD. EXTENT TOP & BOTTOM 1'-0" PAST STAIR STRINGERS NOTE: COORDINATE LOCATION OF REQUIRED STAIR COLUMNS WITH
OF OVER EXCAVATION UNREINFORCED CONCRETE 1 1/2" EACH SIDE OF STAIR ARCHITECTURAL PLANS AND APPROVED STAIR SUPPLIER SHOP DRAWINGS
1' - 6"
T/ COMPETENT ROCK
CONSTRUCTION JOINT
CONSTRUCTION DOCUMENTS
SIDES
1 1/2" ⌀ x 6'-0" TEST HOLE #4 @ 12"O.C.
PER GEOTECHNICAL #4 @ 12"O.C. x 2'-0"
1/2" EXP. JOINT 5 1/2" 6"
ENGINEER MATERIAL
1' - 0"
2' - 0" SLAB ON GRADE.
SEE PLAN FOR SIZE AND REINF. SLAB ON GRADE
SEE PLAN FOR
SIZE & REINF. 2' - 0"
8"
(3) #4 CONT.
INTERIOR SIDE
8"
AT FTG. BEARING ON CONCRETE FILL AT OVER EXCAVATION 1. PROVIDE CONTROL JOINTS AT 20'-0" ON CENTER MAX. #5 @ 12"O.C.
2. CONTRACTOR SHALL SUBMIT PROPOSED CONTROL JOINTS PROVIDE 2 LAYERS OF BOND VERT. E.F.
FOR REVIEW PRIOR TO CONSTRUCTION. BREAKER ( 30LB FELT PAPER)
TROWEL T/ WALL SMOOTH WATER PROOFING
WATER PROOFING SEE ARCH.
TYPICAL COLUMN FOOTING SECTION CONTROL JOINT SEE ARCH.
1 3/4" = 1'-0"
#4 @ 12" O.C.
HORIZ. E.F.
#4 @ 12"O.C.
8"
8"
AND REINF. DRAIN. SEE
#4 @ 12"O.C.
8"
PLUMBING
VERT. E.F.
#4 @ 12" O.C. LEVEL B3 #5 @ 12" O.C. T KEYWAY
1' - 0"
(2) #4 CONT.
Revision
FOUNDATION HORIZ. E.F. #6 @12" O.C. B GRANULAR
WATER PROOFING 438' - 6"
DRAIN. SEE 1/2" EXP. JOINT MATERIAL 1/2" EXP. JOINT MATERIAL FILL
No. Date Description
8"
SEE ARCH.
PLUMBING
SLAB ON GRADE SEE PLAN FOR GRANULAR
GRANULAR SIZE & REINF. FREE DRAINING
1' - 3"
FOUNDATION SLAB ON GRADE SEE PLAN FOR 1' - 0"
FREE DRAINING #5 @ 12" O.C. T BACKFILL (6) #5 CONT. T & B
BACKFILL LEVEL B3 DRAIN. SEE SIZE & REINF. #6 @ 12" O.C. B KEYWAY
438' - 6" PLUMBING
LEVEL B3
8"
GRANULAR
GRANULAR 438' - 6" FILL
8"
FREE DRAINING
1' - 3"
1' - 0" BACKFILL (6) #5 CONT. T & B 2' - 9" 1' - 0" 1' - 3"
(2) #4 CONT. COMPETENT
1' - 0" BEDROCK
#5 @ 12"O.C. (2) #4 CONT.
T&B
1' - 3" 1' - 0" 2' - 9"
(4) #5 CONT. COMPETENT
SECTION AT RAMP WALL
1' - 0"
BEDROCK
9 3/4" = 1'-0"
GRANULAR GRANULAR
#5 @ 12"O.C. KEYWAY FILL FILL
T&B
COMPETENT 1' - 3" 1' - 0" 1' - 3"
BEDROCK KEYWAY
(4) #5 CONT.
SECTION AT BASEMENT RAMP WALL
8 3/4" = 1'-0"
1' - 0"
COMPETENT
BEDROCK
6
SECTION AT RAMP WALL
3/4" = 1'-0"
S401
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
10"
F 1/2" PLATE
3/4"x6” H.S.
1 1/2"
10"
10"
7"
6"
1 1/2"
CMU WALL. SEE ARCH. CMU WALL BEYOND CMU WALL. SEE ARCH.
Approved By: Approver
2"
Checker
SEE ELEVATOR
(4) 3/4"x6" H. S.
SEE ELEVATOR
HSS 8x4x3/8" EMBED PLATE EMBED PLATE
MANUF.
2' - 0" 2' - 0" 2' - 0"
Checked By:
MANUF.
DIVIDER BEAM
Drawn By:
8"
TO EMBED PLATE AT WALL 1' - 0"
CORNER KEYWAY
CMU WALL DWL. MATCH ELEVATOR SILL ANGLE. CMU WALL DWL. MATCH WATERSTOP
CONCRETE WALL
SPACING AND SIZE OF COORD. SIZE AND LOCATION BEYOND SPACING AND SIZE OF 1" GALVANIZED BAR GRATING
CMU REINF. w/ ELEVATOR MANUF. CMU REINF. TERMINATE MAT REINF.
ERECTION w/ STD. 90° HOOKS L2x2x1/4" x CONT. w/ (3) 5/8"⌀
BOLT 1' - 0" 1' - 0" 1' - 0" EXPANSION ANCHORS AT 12"O.C.
3/4" x 8" EPOXY ANCHOR
3/16 (3) MIN. PER SIDE
@ 12" O.C. AT ELEVATOR
SILL HSS8x4x3/8" 222 Second Avenue South
3/16 DIVIDER BEAM Suite 1400
2'-0" SQ.
Nashville, TN 37201
5' - 6"
5' - 6"
#4 @ 12" O.C. #4 @ 12" O.C. #4 @ 12" O.C. 615.770.8100
2' - 0"
VERT. E.F. VERT. E.F. VERT. E.F.
1' - 0"
ADD INTERRUPTED TOP BARS AT BOTTOM
(2) #4 CONT. OF SUMP PIT. EXTEND 4'-0" BEYOND Seckman
PIT / PROVIDE 90° HOOK AT EDGE OF Reid, Inc.
MAT AS REQUIRED.
2995 Sidco Drive
#8 @ 6" O.C. E.W. #8 @ 6" O.C. E.W. Nashville, TN 37204
T & B. HOOK EA. T & B. HOOK EA. (615) 383-1113
END w/ 90° HOOKS END w/ 90° HOOKS FAX: (615) 386-8469
www.ssr-inc.com
COMPETENT COMPETENT
3'-6"
3'-6"
SSR Project #: 21640780
BEDROCK BEDROCK
TENNESSEE
ONCOLOGY
SECTION AT ELEVATOR PIT SECTION AT MAINTENANCE ELEVATOR PIT SUMP PIT DETAIL
1 3/4" = 1'-0" 2 3/4" = 1'-0" 3 3/4" = 1'-0"
CONSTRUCTION DOCUMENTS
LEVEL B2
WALL VENTILATION SHAFT COLUMN SECTION
#4 TIES @ 9" O.C.
-23'-0"
3'-0" HAUNCH
1' - 6"
CONCRETE WALL
LAP SPLICE
BEYOND
CLASS B
#4 TIES @ 9"O.C.
2"
P.T. BEAM
WATERPROOF LAYER (14)#8VERT.
SEE FLOOR PLAN
BETWEEN ROCK AND
CMU WALL #5 @ 12"O.C. VERT. - E.F.
WALL. SEE ARCH.
SEE ARCH.
7
FOR SIZE
5
S402
1' - 0"
#5 @ 8"O.C.
HORIZ. E.F. 1' - 0"
SLAB ON GRADE. SEE
1' - 6"
TYP. TURNED PLAN FOR SIZE & REINF.
DOWN EDGE
LEVEL B3
#5 @ 12"O.C.
VERT. E.F. -33'-0" PLAN VIEW - VENTILATION SHAFT COLUMN SEE COLUMN
5 3/4" = 1'-0"
SCHEDULE FOR
REINF.
GRANULAR FILL
CMU WALL FOUNDATION
HAUNCH DETAIL AT FOUNDATION
EXTEND TIES
7 3/4" = 1'-0"
GRANULAR INTO FTG
FILL AROUND
1' - 6"
DOWELS
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
FOUNDATION
SECTION AND
DETAILS
4/25/2023 5:34:04 PM
S402
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
M.1
1' - 0"
6
1
1' - 0"
1' - 0" 3/4" CLR. 1 1/2" CLR.
MVW
TEMPORARY SHORING
KJM
LAP SPLICE
RETAINED SEE ARCH. EARTH
WATERPROOFING GRANULAR BACK FILL
SEE ARCH. EARTH
LAP SPLICE
WATER STOP SOUND ROCK FACE 222 Second Avenue South
LAP SPLICE
GRANULAR BACK FILL
GRANULAR BACK FILL ROUGHEN Suite 1400
SURFACE WATER STOP Nashville, TN 37201
DRAIN THRU BEAM. SEE PLUMB. AND SOUND ROCK FACE
2" CLR.
WATER STOP SOUND ROCK FACE ARCH. FOR SIZE AND LOCATION ROUGHEN 615.770.8100
ROUGHEN SURFACE
DRAIN THRU BEAM. SEE PLUMB. AND
2" CLR.
SURFACE
ARCH. FOR SIZE AND LOCATION
2" CLR.
1
2'-3" TOP OF
1'-3" TOP OF
1 1/2" CLR.
18" WITH STIRRUPS POST TENSIONED FLR. #4 U BARS @12" O.C LAP SSR Project #: 21640780
1 1/2" CLR.
POST TENSIONED FLR. #4 U BARS @12" O.C LAP BEAM - SEE PLAN 18" WITH STIRRUPS
1 1/2" CLR.
BEAM - SEE PLAN 18" WITH STIRRUPS POST TENSIONED FLR. SEE CLOSURE BEAM SCHEDULE
3'-0" SEE BEAM - SEE PLAN 3'-0" SEE #6 CONT. T & B
3'-0" SEE FOR SIZE AND REINF.
#6 CONT. T & B PROVIDE BOND
BEAM SCHEDULE #6 CONT. T & B BEAM SCHEDULE VARIES
PROVIDE BOND BEAM SCHEDULE BREAKER BTWN.
VARIES PROVIDE BOND BEAMS 0" MIN TO
BREAKER BTWN. VARIES
0" MIN TO BREAKER BTWN. 1'-0" MAX.
BEAMS 0" MIN TO
1'-0" MAX. BEAMS 1'-0" MAX. SEE CLOSURE BEAM SCHEDULE
SEE CLOSURE BEAM SCHEDULE FOR SIZE AND REINF.
FOR SIZE AND REINF.
NOTE: CLOSURE BEAM AND CLOSURE WALL SHALL BE PLACED AFTER
POST TENSIONED SLABS AND BEAMS ARE TENSIONED AND TENDONS CUT .
NOTE: CLOSURE BEAM AND CLOSURE WALL SHALL BE PLACED AFTER
POST TENSIONED SLABS AND BEAMS ARE TENSIONED AND TENDONS CUT .
NOTE: CLOSURE BEAM AND CLOSURE WALL SHALL BE PLACED AFTER
POST TENSIONED SLABS AND BEAMS ARE TENSIONED AND TENDONS CUT . TENNESSEE
ONCOLOGY
SECTION AT SOUTH CLOSURE BEAM SECTION AT EAST CLOSURE BEAM SECTION AT NORTH CLOSURE BEAM - TYP.
1 3/4" = 1'-0" 2 3/4" = 1'-0"
3
0.1A
CONSTRUCTION DOCUMENTS
3/4" CLR. 1 1/2" CLR.
TEMPORARY SHORING
#4 @ 12" O.C. SYSTEM ABOVE ROCK
E.F. HORIZ. FACE
#5 @ 12"O.C. VERT.
WATERPROOFING RETAINED
EARTH 3/4" CLR. 1 1/2" CLR.
SEE ARCH.
TEMPORARY SHORING
#4 @ 12" O.C. SYSTEM ABOVE ROCK
LAP SPLICE
#5 @ 12"O.C. VERT.
ARCH. FOR SIZE AND LOCATION RETAINED
WATERPROOFING
SEE ARCH. EARTH
LEVEL B1
1
LAP SPLICE
458' - 6"
GRANULAR BACK FILL
2'-3" TOP OF
2" CLR.
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
1'-3" TOP OF
Revision
POST TENSIONED FLR.
#4 U BARS @12" O.C LAP 1 1/2" CLR. No. Date Description
1 1/2" TYP.
BEAMS 1'-0" MAX. POST TENSIONED FLR. #4 U BARS @12" O.C LAP
BEAM - SEE PLAN 18" WITH STIRRUPS
3'-0" SEE
#6 CONT. T & B
BEAM SCHEDULE
PROVIDE BOND
NOTE: CLOSURE BEAM AND CLOSURE WALL SHALL BE PLACED AFTER BREAKER BTWN. VARIES
POST TENSIONED SLABS AND BEAMS ARE TENSIONED AND TENDONS CUT . BEAMS 0" MIN TO
1'-0" MAX.
SEE CLOSURE BEAM SCHEDULE
FOR SIZE AND REINF.
S403
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
1
1
M.1 1
6
Approved By: Approver
Checker
SEE 1-5 /S403 FOR TEMPORARY SHORING SEE 1-5 /S403 FOR
CLOSURE BEAM BACK FILL SYSTEM ABOVE ROCK CLOSURE BEAM SYSTEM ABOVE ROCK
SYSTEM ABOVE ROCK CLOSURE BEAM
AND WALL DETAILS FACE AND WALL DETAILS FACE
FACE AND WALL DETAILS
Checked By:
GreshamSmith.com
2' - 3"
SEE PLAN SEE PLAN SEE PLAN
615.770.8100
1'-0"
1' - 3"
1' - 3"
MAX.
Smith
3' - 0" Seckman
Reid, Inc.
2995 Sidco Drive
3" 3"
3"
PROVIDE (6) ADDITIONAL Nashville, TN 37204
1 #9's IN P.T. BEAM. (615) 383-1113
5' - 4"
5' - 4"
#4 TIES @ 4"O.C.
#4 TIES @ 6" O.C.
A A
C C
2' - 0"
(12) #9 VERT.
SEE COL. SCHEDULE
COLUMN SCHEDULE
COLUMN SCHEDULE
(10) #9 VERT. (11) #8 VERT.
SEE COLUMN SCHEDULE
1'-6" - SEE
1'-6" - SEE
2' - 6"
SECTION A-A
Revision
No. Date Description
1 05.26.2023 Addendum No. 1
TYP. 30" COLUMN HAUNCH AT GRID 1 AND 6 TYP. 18"x24" COLUMN HAUNCH AT GRID 0.1 AND M.1 TYP. 18" COLUMN HAUNCH AT GRID 0.1A/6, 0.1A/1, M.1/6
1 3/4" = 1'-0" 2 3/4" = 1'-0" 3 3/4" = 1'-0"
FOUNDATION
SECTIONS AND
DETAILS
5/25/2023 4:01:54 PM
S404
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
6 HANDRAIL
SEE ARCH.
Approved By: Approver
Checker
T/WALL
Author
477'-6"
1/2" EXP. JOINT #4 @ 12"O.C. E.W.
TEMPORARY SHORING MATERIAL
SEE 1/-4 /S403 FOR EL.= 471'-6"
Checked By:
CLOSURE BEAM
FACE
AND WALL DETAILS
8"
GRANULAR RETAINED EARTH
BACK FILL
(2) #4 CONT. SEE ARCH. AND GreshamSmith.com
CIVIL DRAWINGS
BLDG. WALL 1" TYP FOR SLOPES IN
SEE 4/S421 SLAB
#4 @ 12" O.C. HORIZ.
ADD #4 @ 12"TOP T/ STAIR
SEE CIVIL
SOLID GROUTED CMU WALL SEE PLAN FOR NUMBER
POST - TENSIONED REINF. w/ #5 @ 16"O.C. VERT. BACKFILL OF TREADS, ALL RISERS
BEAMS AND SLAB GRADE AND #5 @ 48"O.C. HORIZ. TO BE EQUAL U.N.O..
SEE PLAN SEE CIVIL #5 @ 8"O.C. VERT. 222 Second Avenue South
SOUND ROCK FACE Suite 1400
#4 CONTINUOUS Nashville, TN 37201
SLOPING RAMP 615.770.8100
FROM B1 - B2 GRADE - SEE CIVIL 12"Wx16"D THICKENED
EDGE W/ (2) #4 CONT.
(4) #4 CONT.
1/2" EXPANSION JOINT
1' - 3"
#4 @ 12"O.C. TOP & BTM.
#5 @ 12"O.C. MIN. 4" DEEP SLAB W/
4"
(3) #4 CONT. TOP & BTM. SIDEWALK - SEE CIVIL 6x6:W2.9xW2.9 W.W.F.
TOP & BTM.
EL.= 468'-10"
EL.=468'-0"
Smith
Seckman
1' - 0"
Reid, Inc.
1' - 0"
2995 Sidco Drive
Nashville, TN 37204
(615) 383-1113
3' - 6" FAX: (615) 386-8469
2' - 8" www.ssr-inc.com
A A
TENNESSEE
ONCOLOGY
SOUND ROCK FACE
SECTION A-A
TYPICAL 30" COLUMN HAUNCH AT GRIDE 6/D, 6/E, 6/F, 6/H, 6/I
1 3/4" = 1'-0"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
Revision
No. Date Description
FOUNDATION
SECTIONS AND
DETAILS
4/25/2023 5:34:12 PM
S405
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
Approved By: Approver REINF., SEE SCHEDULE
Checker
AS REQ'D
CMU, SEE PLAN 1 #5 @ 8" WALL FULL HEIGHT IN
FILL ALL CELLS WITH
WALL. CONT. REINF. THROUGH HORZ. REINF. IN GROUT FILLED CELL WHEN
CONCRETE HORIZ. BOND BM.
T/WALL CONTROL JOINTS BOND BEAM TYP. OPENING EXCEEDS 6'-0".
REINF. W/180° HOOK SEE GENERAL
Checked By:
NOTE 1
FILL W/CONC. REINF. SEE SCHEDULE
SPLICE
REINF. SEE SCHEDULE 1 #5 @ 8" WALL FULL HEIGHT IN
LAP
GROUT FILLED CELL WHEN
CMU U BLOCK CMU U BLOCK 8" CMU WALL
OPENING EXCEEDS 8'-0"
2' - 0" Sim Sim 1 #5 IN 8" WALL FULL HEIGHT IN
1 1 GROUT FILLED CELL
NOTE 1
MASONRY WALL MASONRY WINDOW SECTION Nashville, TN 37201
PLAN PLAN REINFORCING OPENING MASONRY
3 615.770.8100
SPLICE
SCHEDULE FOR DOOR 1" = 1'-0"
LAP
MASONRY OPENING MORE THAN 5'-0" MASONRY OPENING 5'-0" OR LESS. REINFORCING.
3 OPENING
(SEE SCHEDULE FOR SIZE AND REINFORCING) S410
3
S410
MASONRY LINTEL SCHEDULE
NOTE 1
JAMB REINF,
FULL HEIGHT 1ST COURSE CONTROL JOINT OR VERT. REINF.
CLEAR SPAN DEPTH BOTTOM REINFORCING TOP REINFORCING #3 TIE SPACING (1) BAR PER CELL EXPANSION JOINT,
MASONRY LAP SPLICE LENGTHS Smith
SPLICE
T/SLAB SEE PLANS AND
Seckman
LAP
SEE PLAN ARCHITECTURALS BAR SIZE MINIMUM LAP SPLICE LENGTH, in (mm)
< 5'-0" 8" 2 - #5 - - 1 - #5
Reid, Inc.
T/FOOTING #3 (#10) 12 (305)
5'-1" TO 5'-11" 1'-4" 2 - #5 2 - #5 - 2- #5 2995 Sidco Drive
SEE PLAN HORZ. REINF. IN #4 (#13) 15 (381) Nashville, TN 37204
BOND BEAM TYP. (615) 383-1113
#5 (#16) 23 (584)
6'-0" TO 7'-3" 2'-0" 2 - #5 2 - #5 8" 2- #5 DOWELS TO MATCH FAX: (615) 386-8469
FOOTING, ELEVATION PROVIDE (1) #4 HORZ. PROVIDE VERT. REINF. EACH SIDE SECTION DOWELS TO MATCH VERT. #6 (#19) 43 (1092)
VERTICAL REINFORCING www.ssr-inc.com
SEE PLAN. REINF. IN BOND BEAM OF OPENING FULL HEIGHT. SEE REINF. (TYP. U.N.O.).
7'-4" TO 9'-11" 2'-8" 2 - #5 2 - #5 8" 3- #5 SIZE AND SPACING. AT SILL. EXTEND 8" EA DETAIL AND LINTEL SCHEDULE FOR
SIDE SIZE AND QUANTITY.
MASONRY LAP SPLICE SCHEDULE SSR Project #: 21640780
NOTES: NOTES:
4 12" = 1'-0"
1. FOR OPENING LOCATIONS SEE ARCHITECTURAL DRAWINGS. 1. 4'-0" MAXIMUM POUR HEIGHT FOR GROUTING OF CMU WALLS.
2. PROVIDE 8" BEARING EACH SIDE OF OPENING. 2. DETAIL VERTICAL REINFORCING WITH LAP SPLICES AT MAX. GROUT POUR HEIGHT.
3. EXTEND MASONRY REINFORCING IN LINTEL 24" PAST OPENING, MIN . 3. VERTICAL LAP SPLICE LENGTH SHALL BE AS SHOWN IN THE MASONRY LAP SPLICE SCHEDULE 4/S4.10.
TYP. JOIST
MASONRY WALL REINFORCING SCHEDULE
TO L
1-#5 @ 4'-0" O.C. & STD. CONT. TRUSS REINFORCING @ 16" O.C.
8" EXT. CMU WALLS H < 12' 7 5/8" 3 13/16" #5 @ 32" O.C. VERTICAL @ REINFORCING
TYP. C TO
1-#5 @ 4'-0" O.C. & STD. CONT. TRUSS REINFORCING @ 16" O.C.
1/8 JOIST CMU WALL. SEE SCHEDULE CMU WALL. SEE SCHEDULE 8" EXT. CMU WALLS 12' > H < 20' 7 5/8" 3 13/16" #5 @ 24" O.C. VERTICAL @ REINFORCING
FOR REINF. FOR REINF.
L 5x3x1/4"x0'-6" L 5x3x1/4"x0'-6" 1-#5 @ 4'-0" O.C.
SPACE
@ EA. JOIST @ EA. JOIST 8" INT. CMU WALLS H < 12' 7 5/8" 3 13/16" #5 @ 48" O.C. VERTICAL @ REINFORCING
11_2"
8" INT. CMU WALLS 12' > H < 20' 7 5/8" 3 13/16" #5 @ 48" O.C. VERTICAL 1-#5 @ 4'-0" O.C., & STD. CONT. TRUSS REINFORCING @ 16" O.C. @ REINFORCING
BOND BEAM BOND BEAM TYP L TO C
3/16
CONC. CRASH WALL REINF. CONC. CRASH WALL REINF. HORIZONTAL BOND
FIRE SAFE AS REQ'D FIRE SAFE BETWEEN W/ #5 @ 8" O.C. VERT. AND W/ #5 @ 8" O.C. VERT. AND BEAM REINFORCING
CONSTRUCTION DOCUMENTS
2" FOR
6" WALL
'H'
40"
40"
VERT. REINF. HORIZONTAL BOND
GROUTING
'D'
SIDE CONT. COPE 24" W/3 1/4" MIN. EMBED. SLAB - SEE PLAN
WELD TO BEAM 8" WALL
'H'
AT BEAM AS REQ'D. BEYOND (TYP) W.W.F.
L4x3x3/16" LLV EACH
SIDE CONT.
VERT. REINF. HORIZONTAL BOND
BEAM REINFORCING
'D'
12" WALL
'H'
2' - 0" (2) #5 CONT.
WALL REINF.
SLAB - SEE PLAN
JOINT STABILIZATION SLAB ON GRADE. SEE
ANCHOR @32"O.C. SEALANT PLAN FOR SIZE AND
TYPICAL MASONRY PROVIDE PRE-FABRICATED
REINFORCING. CORNERS FOR JOINT REINFORCING.
HORIZ. REINF. W/180° REINF.
HOOKS AT
HORIZ. REINF. W/90° HOOKS
INTERSECTION TYP.
1' - 0"
@ EXP. CONTROL JT.
TYPICAL CONTROL MASONRY WALL INTERSECTION TYPICAL MASONRY WALL CORNER
TYPICAL CONTROL MASONRY WALL INTERSECTION TYPICAL CONTRTACTION JOINT IN MASONRY WALL
#4 @ 24"O.C.
(2) #5 CONT.
1' - 6"
BEAM - SEE PLAN
LOCATING ALL CONTROL JOINTS FOR ARCHITECTS AND ENGINEER'S APPROVAL PRIOR TO BEGINNING
S410
MASONRY CONSTRUCTION.
USUAL GUAGE
BEAM BOTTOM FLANGE
2 #3 TIES AROUND
Checked By:
3/16"
BRG. PLATE
EMBED PL. 5/8"x6"x2'-0" w/ GreshamSmith.com
REF. PLAN
BEARING PLATE BELOW (6) 3/4" ⌀ x 3/4" S.A.
WHEN BEAM FLANGE WIDTH IS = TO REF. PLAN
OR WIDER THAN BEARING PLATE
WELD A706 REBAR TO BEAM
GROUT SOLID 2-#5 VERT. IN GROUT 2' - 0" TO MATCH WALL REINF SIZE 2' - 0"
SCHED. DEPTH
REF. PLAN
FILLED CELLS FULL AND SPACING
HEIGHT OR MASONRY FILL POCKET WITH
COLUMNS, SEE PLANS 8" 8"
GROUT AFTER 222 Second Avenue South
1" CLEAR
INSTALLATION
ELEVATION Suite 1400
NOTE: BOLTED END SHOWN, WELDED END SIMILAR BEAM, SEE PLAN. Nashville, TN 37201
6"@ 8" CMU & 10" @12" CMU 8" U-BLOCK x 2'-0" 615.770.8100
6"@ 8" CMU & 10" @12" CMU
3/16" LONG. TYP.
1" CLEAR
FILL POCKET WITH GROUT REINF. BEAM PER SCHED.
AFTER ERECTION. 3/16"
PROVIDE 2 LAYERS OF
POLY BETWEEN BEAM AND L6x4x5/16x0'-4" (LLV) EMBED PL. 3/8" x 6" x 0'-8" EMBED PL. 3/8" x 6" x 0'-8"
BEAM, SEE PLAN. (2) #4x1'-9"
PLATE AT 3'-0" O.C.
"U" BARS TYP. w/ (2) 1/2"⌀ x 0'-4" H.S.A. w/ (2) 1/2"⌀ x 0'-4" H.S.A.
PROVIDE LONG SLOTTED 3/16" CONT. BOND BEAM
3" 3"
HOLE IN BEAM L5 x 3 x 3/8" x 0'-8" (LLV) w/ 1/2" L5 x 3 x 3/8" x 0'-8" (LLV) w/ 1/2"
3/16" 8" CMU 8" CMU VERTICALLY SLOTTED HOLE. PROVIDE VERTICALLY SLOTTED HOLE. PROVIDE
PROVIDE 2 LAYERS OF 5/8" x 7" x 0'-9" STEEL PLATE 5/8" x 7" x 0'-9" STEEL 1/2" DIA. THREADED HAS ROD w/ 1/2" DIA. THREADED HAS ROD w/ Smith
POLY BETWEEN BEAM AND W/(2) 3/4"ø x 9" F1554 PLATE W/(2) 3/4"ø x 5" HILTI HY-70 @ 4'-0" O.C. FOR 8" CMU HILTI HY-70 @ 4'-0" O.C. FOR 8" CMU Seckman
PLATE ANCHOR BOLTS W/3" PROJ. STUDS
12" CMU
BLOCK AND 2'-0" O.C. FOR 12 CMU BLOCK BLOCK AND 2'-0" O.C. FOR 12 CMU BLOCK Reid, Inc.
8" CMU 12" CMU
5/8" x 11" x 0'-9" STEEL PLATE 5/8" x 11" x 0'-9" STEEL 2995 Sidco Drive
8" CMU 5/8" x 7" x 0'-9" STEEL PLATE W/ (2) PLATE W/(2) 3/4"ø x 5" CONT. BOND BEAM CONT. BOND BEAM
3/4"ø x 5" STUDS W/(2) 3/4"ø x 9" F1554 Nashville, TN 37204
5/8" x 7" x 0'-9" STEEL PLATE GROUT SOLID STUDS
W/ (2) 3/4"øx9" F1554 12" CMU ANCHOR BOLTS W/3" PROJ. (615) 383-1113
5/8" x 11" x 0'-9" STEEL PLATE W/ (2) GROUT SOLID FAX: (615) 386-8469
ANCHOR BOLTS W/ 3" PROJ.
TYP. TYP. CMU WALL (TWO SIDED CONNECTION) CMU WALL (ONE SIDED CONNECTION @ BEAM OR EXT. WALL) TYP. CMU WALL (ONE SIDED CONNECTION @ SLAB) www.ssr-inc.com
12" CMU 3/4"ø x 5" STUDS
2-#5 VERT. IN GROUT
5/8" x 11" x 0'-9" STEEL PLATE
BOND BEAM W/ 2 #5 FILLED CELLS FULL
W/ (2) 3/4"øx9" F1554 SSR Project #: 21640780
HEIGHT OR MASONRY
ANCHOR BOLTS W/ 3" PROJ. 2-#5 VERT. IN GROUT
FILLED CELLS FULL
1' - 4"
COLUMNS SEE PLANS
1' - 4"
TYPICAL CMU WALL TOP ANCHORAGE AT CONCRETE FRAMING
BOLTED END HEIGHT OR MASONRY
COLUMNS SEE PLANS
WELDED END BOLTED END WELDED END 2 3/4" = 1'-0"
BEAM BEARING AT ANGLE OR PERPENDICULAR TO CMU WALL BEAM BEARING PARALLEL TO CMU WALL
NOTES:
1. STEEL BEAMS SPANNING LESS THAN 10'-0" IN LENGTH SHALL HAVE WELDED END BEARING PLATES ON EACH END.
2. STEEL BEAMS SPANNING GREATER THAN 10'-0" SHALL HAVE ONE WELDED END BEARING PLATE AND ONE BOLTED
END BEARING PLATE ON OPPOSITE ENDS OF THE BEAM.
Revision
No. Date Description
S411
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
EXTERIOR SUPPORT
LF1
OR BAR DEVELOPMENT
SEE PLAN
TEMP. & SHRINKAGE REINF TOP STEEL,
MVW
KJM
CGS OF TENDON
GreshamSmith.com
Smith
Seckman
"T" SLAB THICKNESS
GREATER OF 1/6 L1 LF GREATER OF 1/6 L1, 1/6 L2 GREATER OF 1/6 L1, 1/6 L2 GREATER OF 1/6 L2
PROVIDE MIN (3) #4 CONT. TOP Reid, Inc.
BARS EACH SIDE OF BEAM TOP
SEE PLAN
OF TENDON
CGS OF TENDON
CGS OF TENDON
OF TENDON
CGS OF TENDON
'LF' TENNESSEE
END SPAN INTERIOR SPAN CANTILEVER SPAN ONCOLOGY
CONSTRUCTION DOCUMENTS
KEYWAY CENTERED IN KEY
SLAB BETWEEN TENDON SELF RECESSING TYPE ANCHOR
BUNDLES. KEEP KEYWAY
3" CLEAR OF TENDONS
(2) #4 CONT. NON-SHRINK
1/2"⌀ -270 K.S.I. 7 WIRE STRANDS
STRAND PROFILE GROUT
#3 HAIRPINS. NUMBER GREASD AND PLASTIC WRAPPED
REQUIRED EQUALS
T/2 NUMBER OF STRANDS + 1
#4 x 4'-0" T & B @ 16"o.c.
T/2
SLAB THICKNESS
T
T/2
T/2
T
T/2
24"
#4 HAIRPINS 6" OR AS REQUIRED
CONTINUE BOTTOM STEEL
THRU JOINT BY P.T. SUPPLIER.
TYPICAL CONSTRUCTION JOINT AT STRESSING POINT TYP. POST-TENSION EXTERIOR SLAB STRESSING END DETAIL
2 1 1/2" = 1'-0" 3 1 1/2" = 1'-0"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
4"
@ 12" TO ENCLOSE ALL TENDONS
WITHIN CURVE. SEE PLAN. PROVIDE 2"
No. Date Description
#4
HAIRPIN ELEVATION
3 TENDONS IN
A GROUP (MAX.)
T/2
T/2
.
' MAX
T
1:12 SLOPE
T/2
T
IN, 20
T/2
12
.
MAX
1
10' M
#5 x 6'-0" T & B #3 HAIRPIN - TOTAL EQUAL TO
20'
PER ANCHOR NUMBER OF ANCHORS PLUS ONE
,
MIN
OR AS REQUIRED BY P.T. SUPPLIER
10'
TENDON ANCHOR. ROTATE
HORIZONTAL IF T<7" (2) #4 CONT. (MIN.)
3'-0"
HAIRPINS
TENDON ANCHOR. ROTATE
HORIZONTAL IF T<7"
SEE SCHEDULE
1- #4 HAIRPIN FOR
POST TENSIONED
EVERY 3 TENDON GROUP
MAX. PLACE HAIRPINS CONCRETE SLAB
AT A 1:12 SLOPE AS SHOWN.
DETAILS
PLAN VIEW AT < 3 TENDONS PER BUNDLE PLAN VIEW AT MULTIPLE TENDON BUNDLES
4/25/2023 5:34:20 PM
4
TYP. NON-STRESSING EXTERIOR END DETAIL
1 1/2" = 1'-0" 5
TYPICAL NON-STRESSING INTERIOR END DETAIL
1" = 1'-0" 6
TYPICAL DETAIL AT TENDON HORIZONTAL CURVE
3/4" = 1'-0"
S412
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
TENDON SHALL BE STRAIGHT FOR 2'-0" PAST
1 . DETAIL
KJM
AX
2' - 0"
M BLOCKOUT OR
OPENING
6"
Checked By:
1' - 6"
Drawn By:
6" MIN.
1/2 T & S. SPACING
GreshamSmith.com
45.
8" MAX.
2" SEE PLAN OF SLAB REINF.
2" CLR.
00°
OPENING DETAIL
P.T. TENDON 2'-0" MAX.
TENDON CGS AT FACE OF
1' - 6"
2" CLR.
BEAM. SEE PLAN FOR TENDON
2' - 0"
8" MAX
DIMENSION
6"
1' - 6"
Nashville, TN 37201
2' - 0"
#4 x 3'-0" MID DEPTH (2) #5 TOP & BTM. @ 2'-0" NO SLEEVE REQ'D. REFER TO PLACE 3 TEMP. AND SHRINKAGE BARS 615.770.8100
TENDONS TYP. SLEEVE 3" MIN. FROM PENETRATION DETAIL FOR CONT. AT THE TOP OF THE SLAB AT
MAX. OPENINGS
PENETRATION ALL PENETRATIONS IN ANCHORAGE TENDON REINFORCING EXTERIOR BEAMS. SEE SLAB OR
ZONE SHALL USE SCHEDULE 40 REINF. DETAILS FOR T&S BAR SIZE AND
PIPE SLEEVE, GALVANIZED IF SLAB TYP. SLAB STEEL. SEE SPACING.
IS EXPOSED. MAX. PENETRATION TENDON PLAN AND TYP. SLAB
NOTES: SIZE = 4" DIAMETER. DETAIL FOR SIZE,
NOTE: COORDINATE WITH STRUCTURAL ENGINEER WHEN SPACING, AND EXTENTS
1. FOR SLAB OPENINGS LARGER THAN 2'-0" x 2'-0", SUBMIT SIZE AND LOCATION
PENETRATION EXCEEDS 8" DIAMETER.
TO THE STRUCTURAL ENGINEER.
2. IF OPENING IS NEAR EDGE OF SLAB, PROVIDE 180° STD. HOOKS ON ADDED
REINFORCING. Smith
Seckman
Reid, Inc.
TYPICAL PT SLAB PENETRATION DETAIL TYPICAL PT SLAB OPENING DETAIL TYPICAL DETAIL AT ANCHORAGE ZONE TYPICAL EXTERIOR BEAM AT P.T. SLABS 2995 Sidco Drive
Revision
No. Date Description
POST TENSIONED
CONCRETE SLAB
DETAILS
4/25/2023 5:34:22 PM
S413
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
2' - 0"
KJM
2' - 0"
TYP.
OPENING - SQUARE, 3" (2)-#5x5'-0" AT CENTERLINE OF
Checked By:
2" CLR.
RECTANGULAR, OR ROUND SLAB - TYPICAL ADD #4 @ 12" (MIN.) EXTEND
Drawn By:
2" MIN.
16" PAST EACH SIDE OF
CONDUIT TOP OR BOTTOM
2' - 0"
MAX.
2" CLR.
MIN.
4" CLR.
MIN.
SLAB DEPTH
222 Second Avenue South
SEE PLAN
CROSSING CONDUIT 3 'D'
CLASS B LAP SPLICE ADD (1) @ 4 Suite 1400
CLASS B LAP SLICE INTERRUPTED SLAB STEEL IF PRESENT BETWEEN CONDUIT
Nashville, TN 37201
TOP OR BOTTOM
MAX HEIGHT OF CROSSING 615.770.8100
EXTEND BARS 2'-0" PAST SCHEDULED SLAB REINFORCING CONDUIT < 1/3 OF SLAB DEPTH
SHALL BE OFFSET TO MISS SLEEVES
PLACE 1/2 INTERRUPTED SLAB THE FURTHEST SLEEVE (TYP.) BUT CONTINUE THROUGH SLAB
STEEL ON EACH SIDE OF OPENING
NOTE:
1. REINFORCE EMBEDDED JUNCTION BOXES AS SLAB OPENINGS.
INTERRUPTED SLAB STEEL
TOP OR BOTTOM MULTIPLE PARALLEL PIPE/CONDUIT OPENINGS IN SLAB
SINGLE LARGE OR GROUPED OPENING Smith
Seckman
NOTES: NOTES: Reid, Inc.
1. DETAIL SHALL APPLY TO RECESSED BOXES, RECESSED,
DRAINS, BLOCK OUTS, PIPE SLEEVES, AND CONDUITS.
2. OPENINGS LARGER THAN LIMITS INDICATED ABOVE
1. IF CLEARANCE BETWEEN SLEEVES IS LESS THAN 4" THAN
TREAT ALL SLEEVES AS A LARGE COMBINED OPENING
EQUAL WITH DIMENSIONS EQUAL THE OVERALL WIDTH
TYPICAL SECTION AT EMBEDDED 2995 Sidco Drive
Nashville, TN 37204
CONSULT WITH ENGINEER. FROM 1ST TO LAST SLEEVE.
CONDUIT IN RC AND PT ELEVATED SLABS (615) 383-1113
2 3/4" = 1'-0"
FAX: (615) 386-8469
www.ssr-inc.com
TOPPING SLAB
TENNESSEE
500
0 LB
WINDOW WASH TIE-BACK ANCHOR BY 3RD
PARTY ENGINEER/MANUFACTURER.
WHERE REQUIRED
(SEE PLAN AND ARCH.) ONCOLOGY
LOA . W OR COORDINATE CONNECTION WITH FINAL
D (M KIN STRUCTURAL
AX. G DESIGN/INSTALLATION REQUIREMENTS
) POLYSTYRENE FILL AT
3/16
TOPPING SLABS
4" TOPPING SLAB 4" TOPPING SLAB CONNECTION APPLIES TO ELEVATED
(4)-#5 x8'-0" TOP E.W. (SEE PLAN FOR REINFORCING) GRADES - SEE CIVIL PT SLABS, ELEVATED NON-PT SLABS,
18" MAX.
1" CLR.
WASH TIE-BACK STRUCTURAL POLYSTYRENE FILL STRUCTURAL POLYSTYRENE FILL
MIN.
NEAT MIX ZONE (1/4"-2")
8"
BUILD INTEGRAL
@ COLD JOINT
SEE
COLD
JOINT
MIN.
3/4"x1'-0"x1'-0" STAINLESS
3"
WATERPROOFING AT EXT.
MIN.
1/4"
STEEL EMBED PLATE W/
2"
TOPPING SLABS (SEE ARCH.)
1"
(4)-3/4"⌀ x6" STAINLESS STEEL
HEADED STUDS AT 10" GAUGE (12)-ADD'L #5 BARS x6'-0"
EMBED PLATE BY WINDOW (3) EACH DIRECTION,
SHIFT MIDDLE BARS AS TOP & BTM.
WASH ENGINEER
REQUIRED TO AVOID CONDUIT
ADDITIONAL (4)-#3 CLOSED TIES @
FOR LIT BOLLARD LOCATIONS
6" O.C. AT WINDOW WASH TIE BACK
LOCATION. (2) EACH SIDE OF EMBED (6" MAX.) EXTENDED MIX SIKA 1000 OR
#4 BAR CONT. STRUCTURAL SLAB APPROVED EQUAL
ZONE (1'-6")
(SEE PLAN)
CONSTRUCTION DOCUMENTS
STRUCTURAL SLAB
(SEE PLAN) 1. SEE ARCHITECTURAL DRAWINGS FOR DECORATIVE BOLLARD LOCATIONS.
2. THIS DETAIL APPLIES TO B3 AND BL4 BOLLARD TYPES AS DICTATED ON
NOTE: THE ARCHITECTURAL PLANS.
1. ALL EXPOSED STEEL SHALL BE HOT DIPPED GALVANIZED 3. COORDINATE LIT AND UNLIT DECORATIVE BOLLARD (B3 & BL4) LOCATIONS
OPTION 1 OPTION 2 WITH ARCHITECTURAL DRAWINGS.
4. COORDINATE ALL INSTALLATION REQUIREMENTS WITH MANUFACTURER
SPECIFICATIONS.
TYPICAL WINDOW WASH ROOF TIE-BACK SECTION AT TOPPING SLAB BASE OF SLOPE TYPICAL DECORATIVE PIPE BOLLARD CONNECTION DETAIL
3 3/4" = 1'-0" 4 3/4" = 1'-0" 5 3/4" = 1'-0"
1/4 L1
1/2 T&S
SPACING T&S T&S
3/4" CLR.
6"
3/4" CLR.
3/4" CLR.
6" 6"
TEMPERATURE STEEL OPTION: BARS MAY BE CONTINUOUS
SEE SCHEDULE (SPLICE AT COLUMNS ONLY)
LAP TEMPERATURE
STEEL 16" Revision
No. Date Description
END SPAN CONTINUOUS SPAN
1 05.26.2023 Addendum No. 1
L1 L2
L 1/4 L 1/4
1/2 T&S
SPACING T&S T&S REINFORCED CONCRETE SLAB SCHEDULE
ADD 3 T&S BAR TOP @
SPACING SPACING T&S SPACING TOP BARS REINFORCING
ACI STD 90 HOOK PARALLEL TO BEAM MARK DEPTH TOP BARS TEMPERATURE STEEL NOTES
BOTTOM BARS
END SPAN CONTINUOUS END BOTTOM BARS
S1 5" #4 @ 12" O.C. #4 @ 12" O.C. #4 @ 11"o.c. #4 @ 18" O.C 1 1/2"x1 1/2" x6" LONG KEY
AT 2'-0" SPACING
S2 5" #4 @ 12" O.C. #4 @ 12" O.C. - #4 @ 18" O.C SINGLE SPAN CONSTRUCTION JOINT
S3 6" #4 @ 12" O.C. #4 @ 10" O.C. #4 @ 12"o.c. #4 @ 18" O.C CONT. TOP REINF. THRU
3/4" CLR.
SLAB DEPTH
SIMPLE SPAN S8 8" #5 @12" O.C. #5 @ 12" O.C. - #4 @ 10" O.C SINGLE SPAN REINFORCED
SEE PLAN
TEMP.
CONT. BOTTOM REINF. THRU REINFORCEMENT
L1
CONSTRUCTION JOINT CONCRETE SLAB
BOTTOM
REINFORCEMENT DETAILS
5/25/2023 4:01:56 PM
6
CONCRETE SLAB REINFORCING SCHEDULE AND DETAILS
3/4" = 1'-0" 7
TYPICAL DETAIL AT NON-PT SLAB CONSTRUCTION JOINT
3/4" = 1'-0"
S414
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
1 6" TOPPING SLAB - SEE 1 1
PLAN AND DETAILS FOR 4' - 4 1/2" 8" THK. CONC. 5' - 3"
5' - 3"
REINFORCING PAVING AREA
8" 8"
CURTAIN WALL #4 @ 12"o.c. HORIZ.
1' - 6" 1' - 7" 2' - 4"
Approved By: Approver
SEE ARCH. STRUCTURAL E.F. CONT. MIN. (2) ENTRY DOOR OR GLASS
Checker
POLYSTYRENE 4" L.W. TOPPING SLAB SEE PLAN MULLIONS - SEE ARCH.
MVW
8"
10"
SEE PLAN AND
2' - 6"
SCHEDULE FOR
2' - 0"
REINFORCING.
8"
2" CLR. FILL WITH #4 @ 10"o.c. 615.770.8100
COMPRESSIBLE TOP & BTM.
MATERIAL CONCRETE BEAM. SEE PLAN
2' - 0"
FOR SIZE AND SCHEDULE 1' - 7"
1' - 0" STRUCTURAL SLAB
REFER TO CLOSURE BEAM FOR REINFORCING #5 @ 6"o.c. TOP & BTM. SEE PLAN AND
DETAIL FOR CLOSURE SCHEDULE FOR
WALL REINFORCING BEDROCK BOND BREAKER REINFORCING.
GRANULAR BACKFILL 2" CLR. FILL WITH
CONCRETE BEAM. SEE PLAN CONCRETE BEAM. SEE PLAN
COMPRESSIBLE
BEDROCK FOR SIZE AND SCHEDULE FOR SIZE AND SCHEDULE
MATERIAL
FOR REINFORCING FOR REINFORCING Smith
REFER TO CLOSURE BEAM GRANULAR BACKFILL BOND BREAKER Seckman
DETAIL FOR CLOSURE
WALL REINFORCING 2" CLR. FILL WITH 1' - 0"
Reid, Inc.
COMPRESSIBLE 2995 Sidco Drive
SECTION AT SOUTH EDGE AT RETAIL SECTION AT SOUTH EDGE AT DRIVE MATERIAL Nashville, TN 37204
1' - 0"
#5 @ 8"o.c. GRADE - SEE CIVIL
#5 @ 8"o.c.
1' - 0"
GRADE, SEE
1' - 0"
CIVIL #5 @ 8"o.c.
#5 @ 8"o.c.
VARIES - SEE ARCH.
VERT. - E.F.
8"
LAP SPLICE
CLASS 'B'
CLASS 'B'
LAP SPLICE
CLASS 'B'
5"
SEE PLAN AND BIO RETENTION STRUCTURE
SEE CIVIL ELEV = 472'-6"
SCHEDULE FOR
REINFORCING.
5"
ROUGHEN SURFACE
4' - 7" 1' - 0 3/4"
STRUCTURAL SLAB
CONSTRUCTION DOCUMENTS
CONCRETE BEAM. SEE PLAN 1' - 6" 1' - 7" BOND BREAKER ROUGHEN SURFACE GRANULAR BACKFILL
SCHEDULE FOR
FOR SIZE AND SCHEDULE REINFORCING. BOND
FOR REINFORCING CONCRETE BEAM. SEE PLAN
FOR SIZE AND SCHEDULE BREAKER ROUGHEN SURFACE
2" CLR. FILL WITH 1' - 0"
FOR REINFORCING CONCRETE BEAM. SEE PLAN
COMPRESSIBLE 2" CLR. FILL WITH FOR SIZE AND SCHEDULE
MATERIAL COMPRESSIBLE FOR REINFORCING CONCRETE BEAM. SEE PLAN
MATERIAL 1' - 0"
REFER TO CLOSURE BEAM FOR SIZE AND SCHEDULE
DETAIL FOR CLOSURE REFER TO CLOSURE BEAM GRANULAR BACKFILL FOR REINFORCING 11" 9"
1' - 0"
WALL REINFORCING DETAIL FOR CLOSURE
WALL REINFORCING
1' - 9"
BEDROCK
REFER TO CLOSURE BEAM
GRANULAR DETAIL FOR CLOSURE
BACKFILL WALL REINFORCING
BEDROCK
GRADE
SECTION AT SOUTH EDGE WINDOW WALL SECTION AT SOUTH EDEGE AT STUD WALL
4 5 3/4" = 1'-0"
3/4" = 1'-0"
M.1
STONE VENEER, 6" L.W. TOPPING SLAB
SEE ARCH. SEE PLAN & DETAIL
METAL STUD WALL,
6 FOR REINFORCING 6
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
SEE ARCH.
STONE VENEER, SLOPING TOPPING SEE 4/S414 FOR SLAB
SEE ARCH. SLAB SEE ARCH. & SLOPE TRANSITION
#4 @ 12" E.F.
METAL STUD WALL, CIVIL FOR GRADES
CONT.
SEE ARCH.
6" L.W. TOPPING SLAB
SEE PLAN AND DETAIL STRUCTURAL
7" GRADE, SEE
VARIES - SEE ARCH.
FOR REINFORCING
GRADE, SEE
#4 @ 12" E.F.
CONT. 7 1/4"
GRADE, SEE
CIVIL
POLYSTYRENE
CIVIL Revision
CIVIL ELEV. 470'-0"
ELEV. 472'-6"
6" L.W. TOPPING SLAB No. Date Description
SEE PLAN AND DETAIL
8"
FOR REINFORCING ELEV. 472'-0"
8"
2' - 0"
8"
ELEV. 472'-6"
1"
1' - 4"
STRUCTURAL SLAB SEE
PLAN FOR REINFORCING
2' - 0"
1' - 0"
ELEV. 472'-0"
#5 @ 8" O.C.
1' - 4"
8"
BEDROCK
#4 @ 12" O.C. HORIZ. E.F.
CONT. (MIN. 2) CONCRETE BEAM SEE PLAN
FOR SIZE AND SCHEDULE
#5 @ 6" O.C. VERT. E.F. FOR REINFORCING #4 @ 8" O.C. CONCRETE BEAM SEE PLAN
1' - 4"
BOND BREAKER
GRANULAR BACKFILL
11" 9" 1' - 0"
SECTION AT NORTH WALL AT MRI SECTION AT NORTH WALL AT LOADING DOCK FRAMING SECTIONS
8 3/4" = 1'-0" 9 3/4" = 1'-0"
AND DETAILS
SECTION AT EAST WALL
7
4/25/2023 5:34:29 PM
S420
3/4" = 1'-0"
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
6 CMU WALL DWL. MATCH 6
6" L.W. TOPPING SLAB SIZE AND SPACING OF
6 SEE PLAN AND DETAIL
FOR REINFORCING
CMU WALL REINFORCING
8" CMU WALL SEE VENEER, SEE CIVIL PLAN AND DETAIL
POLYSTYRENE 7 1/2"
DETAIL FOR REINF. ARCH. GRADE, SEE FOR REINFORCING
GRADE, SEE CIVIL
Checked By:
CIVIL
7 1/2"
Drawn By:
ELEV. 471'-6"
BOND BREAKER
ELEV. 470'-0"
ELEV. 468'-6"
7 1/2" GreshamSmith.com
8"
#4 @ 12" E.F.
CONT.
3' - 0"
ROUGHEN SURFACE
2' - 0"
1' - 0"
1' - 4"
STRUCTURAL SLAB SEE
PLAN FOR REINFORCING BEDROCK #4 @ 12" O.C. EA. FACE
8"
615.770.8100
1' - 0"
#5 @ 12" O.C. VERT. GRANULAR FILL
CONCRETE BEAM SEE PLAN
REFER TO CLOSURE FOR SIZE AND SCHEDULE REFER TO CLOSURE
BEAM DETAILS FOR FOR REINFORCING (4) #4 CONT. STRUCTURAL SLAB SEE
BEAM DETAILS FOR
CLOSURE WALL PLAN FOR REINFORCING
CLOSURE WALL
1' - 6" 1' - 7" 1' - 0" 3" REINFORCING BOND BREAKER 1' - 6" 1' - 7" 1' - 0" REINFORCING #5 @ 12" O.C.
VERT.
CONCRETE BEAM SEE PLAN
REFER TO CLOSURE
FOR SIZE AND SCHEDULE Smith
FOR REINFORCING Seckman
SECTION AT NORTH WALL SECTION AT NORTH DRIVE BEAM DETAILS FOR
CLOSURE WALL BOND BREAKER Reid, Inc.
1 3/4" = 1'-0" 2 3/4" = 1'-0"
REINFORCING 3" 1' - 0" 1' - 7" 1' - 6"
2995 Sidco Drive
Nashville, TN 37204
(615) 383-1113
SECTION AT NORTH WALL FAX: (615) 386-8469
8"
DETAIL FOR REINF. ARCH.
ELEV. 471'-6"
ONCOLOGY
SEE PLAN AND
SCHEDULE FOR
8"
ELEV. 471'-6" REINFORCING
4' - 0"
5"
4' - 0"
3' - 0"
1' - 2"
REINFORCING
1' - 0"
AND SPACING
4' - 0"
#4 @ 9" O.C
GRADE, SEE
BOND BREAKER CIVIL
(4) #6 CONT.
1' - 2"
CONCRETE BEAM SEE PLAN
FOR SIZE AND SCHEDULE 1' - 2"
1' - 0"
FOR REINFORCING
11" 9" 1' - 0"
BEDROCK
CONSTRUCTION DOCUMENTS
#4 @ 8" O.C. 1' - 2" FOR SIZE AND SCHEDULE
2" CLEAR, FILL WITH
CONCRETE BEAM SEE PLAN COMPRESSIBLE FOR REINFORCING
FOR SIZE AND SCHEDULE MATERIAL 1' - 0" 9" 11"
(4) #4 CONT.
FOR REINFORCING 1' - 6" 1' - 7" 1' - 0" 3"
REFER TO CLOSURE REFER TO CLOSURE
BEAM DETAILS FOR BEAM DETAILS FOR 2" CLEAR, FILL WITH
CLOSURE WALL CLOSURE WALL COMPRESSIBLE
REINFORCING REINFORCING MATERIAL
REFER TO CLOSURE
SECTION AT NORTH WALL SECTION AT WEST CMU WALL BEAM DETAILS FOR
4 3/4" = 1'-0" 5 3/4" = 1'-0"
CLOSURE WALL
REINFORCING
8"
2" 4" 3" 1/2"x10"x9" PLATE W/4
3/16
0.1A
3/4"⌀ x 6" H.S.
0.1A EMBED PLATE
(2) 3/8"x3 1/2"x8" PLATE W/(2)
SEE ARCH. STORE FRONT
SLOPE T/ WALL AT 1"⌀ GALV. A325N BOLTS
STOREFRONT
EMBED PLATE M.1 MULLION
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
ELEV. 471'-6" #5 TOP BAR @ 8"O.C. CLOSE MESH ADA GALV. Revision
6' - 0" w/ STD. 180° HOOK BAR GRATING BY L 3X3X3/8" X CONT. GALV. W/ 3/4"⌀ SS
5"
MCNICHOLS OR EQUAL EPOXY ANCHORS @12" O.C. MIN No. Date Description
EMBED 4. 1/2" ENTIRE PERIMETER OF
VENTILATION SHAFT
#5 @ 8"o.c. VERT. 2' - 0" 2 3/4"
1' - 2 3/4" 7 1/4"
#4 @ 12"o.c. L1 1/2"X1 1/2"X1/4"X GRADE, SEE CIVIL
BOND BREAKER 11" 9" 1' - 0" 1 1/2", CMW-4-150A 11-W-4 L 3X3X3/8" X CONT. GALV. W/ 3/4"⌀ SS CONT. GALV.
HORIZ. - E.F. 5 3/4" ELEV. 471'-6"
MESH ADA GALV. BAR EPOXY ANCHORS @12" O.C. MIN
GRATING BY MCNICHOLS EMBED 4. 1/2" ENTIRE PERIMETER OF
5"
6" L.W. TOPPING SLAB, SEE
OR EQUAL
8"
PLAN AND DETAIL FOR 2 3/4" VENTILATION SHAFT
1' - 0"
REINFORCING
CONCRETE BEAM L1 1/2"X1 1/2"X1/4"X GRADE, SEE CIVIL
STRUCTURAL SLAB SEE
SEE PLAN FOR SIZE CONT. GALV.
PLAN AND SCHEDULE FOR 11" 9"
AND SCHEDULE FOR HSS8X4X1/4 GALVANIZED
REINFORCING
REINFORCING EMBED PLATE IN WALL
#4 @ 10"O.C. TOP & BTM.
1' - 0"
CLOSURE BEAM
WALL BEYOND WATER PROOFING
CMU WALL ANCHORAGE SEE 11" 1' - 4" VENTILATION SHAFT
#5 @ 8"o.c. TOP & BTM.
11" 9" STD DETAIL FOR EMBED AND WALL BEYOND
STRUCTURAL SLAB SEE ANCHORS
PLAN AND SCHEDULE FOR #4 @ 10"o.c. TOP & BTM.
REINFORCING BEDROCK
REFER TO VENTILATION SHAFT
VENTILATION SHAFT FOUNDATION DETAILS FOR SOIL
CONCRETE BEAM SEE PLAN
FOR SIZE AND SCHEDULE
WALL BEYOND WALL REINFORCING FRAMING SECTIONS
FOR REINFORCING AND DETAILS
SECTION AT WEST WALL AT GLASS CMU WALL ANCHORAGE SEE
7 STD DETAIL FOR EMBED AND
REFER TO VENTILATION SHAFT
4/25/2023 5:34:32 PM
S421
WALL REINFORCING
SECTION AT SOUTH WEST VENT SHAFT
9 3/4" = 1'-0"
REINF.
MVW
SEE ARCH
Drawn By:
8"
1 1/2", CMW-4-150A 11-W-4
CLOSE MESH ADA GALV.
BAR GRATING BY T/WALL SEE ARCH AND CIVIL
MCNICHOLS OR EQUAL 222 Second Avenue South
STRUCTURAL SLAB SEE 1' - 2"
PLAN AND SCHEDULE FOR Suite 1400
HSS8X4X1/4 GALVANIZED
#5 @ 8"O.C. 7 1/2" 3" EMBED PLATE IN WALL
BEYOND SEE 8/S421 FOR
EMBED PLATE AND
1' - 0"
CONNECTION DETAILS
TYP.
6"
REFER TO VENTILLATION
SHAFT FOUNDATION FOR WATER PROOFING Smith
WALL REINFORCING Seckman
CONCRETE BEAM SEE PLAN Reid, Inc.
FOR SIZE AND SCHEDULE (2) #6 CONT.
2995 Sidco Drive
FOR REINFORCING
Nashville, TN 37204
(615) 383-1113
VENTILATION SHAFT FAX: (615) 386-8469
11" 1' - 9" SOIL www.ssr-inc.com
CMU WALL ANCHORAGE SEE WALL BEYOND
STD DETAIL FOR EMBED AND
ANCHORS CLOSURE WALL
BEYOND SSR Project #: 21640780
BEDROCK
INTERMEDIATE
WALLS
TENNESSEE
ONCOLOGY
STONE VENEER
SEE ARCH
L 3X3X3/8" X CONT. GALV. W/ 3/4"⌀ SS METAL STUD WALL,
EPOXY ANCHORS @12" O.C. MIN SEE ARCH.
EMBED 4-1/2" ENTIRE PERIMETER OF POLYSTYRENE
VENTILATION SHAFT 1 1/2", CMW-4-150A 11-W-4 FILLER
CLOSE MESH ADA GALV.
BAR GRATING BY
T/WALL =+4.5' MCNICHOLS OR EQUAL
#5 @ 8" O.C.
GRADE, SEE CIVIL L1 1/2"X1 1/2"X1/4"X
CONT. GALV.
HSS8X4X1/4 GALVANIZED
EMBED PLATE IN WALL 7' - 6"
CONSTRUCTION DOCUMENTS
EMBED PLATE AND
CONNECTION DETAILS
6"
ROUGHEN SURFACE
VENTILATION SHAFT
WALL BEYOND ELEV. 472'-6"
5"
1' - 4"
#5 @12" O.C. VERTICAL
STRUCTURAL SLAB SEE
EACH FACE
PLAN AND SCHEDULE FOR
REINFORCING
GRANULAR BACKFILL
CONCRETE BEAM SEE CONCRETE BEAM SEE PLAN
PLAN FOR SIZE AND FOR SIZE AND SCHEDULE
SCHEDULE FOR FOR REINFORCING
REINFORCING
PLAN VIEW OF INTERMEDIATE WALLS AT RAISED SLABS
CMU WALL ANCHORAGE SEE
STD DETAIL FOR EMBED AND
#5 @ 8" O.C. HORIZONTAL ANCHORS PROVIDE REINF AS FOLLOWS:
EACH FACE 4" SLAB: INTERIOR 6x6 2.9xW2.9 WWF
6" SLAB EXTERIOR: #4@12"O.C. E. W. TOP #4 @ 12"o.c. CONT.
EXPRUDED POLYSTYRENE FILLER (2) MIN.
5' - 6"
PLAN
SEE
FOUNDATION DRAIN
T > 6"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
KEYWAY
WATERSTOP PROVIDE REINF AS FOLLOWS:
4" SLAB: INTERIOR 6x6 2.9xW2.9 WWF
6" SLAB EXTERIOR: #4@12"O.C. E. W.
APPLY BONDING AGENT AT TOP
OF STRUCTURAL SLAB
1/4 T
WATERSTOP
T ≤ 6"
CONCRETE FILL TO
COMPETENT
BEDROCK
BEDROCK
TOPPING SLAB LESS THAN OR EQUAL TO 6"
SINGLE SIDED CONCRETE
FORMED WALL
NOTES:
1. ALL TOPPING SLABS SHALL BE LIGHTWEIGHT STRUCTURAL CONCRETE.
2. PROVIDE SAWN CONTRACTION JOINTS SIMILAR TO SLAB ON GRADE CONTRACTION JOINTS FOR LARGE TOPPING
SLAB AREAS. SEE 3/S400 FOR CONTRATION JOINT DETAILS AND MAXIMUM SPACNIG.
2
SECTION AT SOUTH EAST VENT SHAFT
3/4" = 1'-0"
S422
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
F
4
H
Approved By: Approver
Checker
MVW
8"
458'-6" P.T.CONCRETE BEAM
LEVEL B1
8"
SEE PLAN FOR SIZE
1' - 9"
458'-6" AND SCHEDULE FOR
1' - 9"
8"
REINF.
2' - 9"
1' - 9"
3' - 0" CMU WALL ANCHORAGE
CMU WALL ANCHORAGE SEE STD. DETAILS FOR 222 Second Avenue South
SEE STD. DETAILS FOR 1' - 3" EMBED AND ANCHORS Suite 1400
EMBED AND ANCHORS
Nashville, TN 37201
P.T.CONCRETE BEAM CMU WALL - SEE DETAILS
P.T. CONCRETE BEAM
CMU WALL - SEE DETAILS FOR REINF. TYP. 615.770.8100
SEE PLAN FIR SIZE AND SEE PLAN FOR SIZE
FOR REINF. TYP. CMU WALL ANCHORAGE AND SCHEDULE FOR
SCHEDULE FOR REINF.
SEE STD. DETAILS FOR REINF.
CMU DWL. - MATCH WALL REINF. EMBED AND ANCHORS
SIZE AND SPACING
CMU WALL - SEE DETAILS
B2-B1 RAMP FOR REINF. TYP.
SLAB
1' - 3"
10" P.T. SLAB - SEE
SLOPE 8" SLAB - SEE PLAN PLAN FOR REINF. Smith
FOR REINF. Seckman
CMU DWL. - MATCH WALL REINF. Reid, Inc.
8"
SIZE AND SPACING
B2-B1 RAMP 2995 Sidco Drive
SLAB - ELEV. CMU DWL. - MATCH WALL REINF. Nashville, TN 37204
VARIES SIZE AND SPACING B2-B1 RAMP SLAB (615) 383-1113
8" P.T. SLAB - SEE FAX: (615) 386-8469
3' - 0" PLAN FOR REINF. www.ssr-inc.com
CMU WALL ANCHORAGE
SEE STD. DETAILS FOR SLOPE
10"
P.T. CONCRETE BEAM EMBED AND ANCHORS SSR Project #: 21640780
SEE PLAN FIR SIZE AND P.T.CONCRETE BEAM
SCHEDULE FOR REINF. SEE PLAN FOR SIZE
CMU WALL ANCHORAGE
8"
2' - 9" AND SCHEDULE FOR 1' - 3"
REINF. SEE STD. DETAILS FOR
EMBED AND ANCHORS
P.T.CONCRETE BEAM
CMU WALL ANCHORAGE SEE PLAN FOR SIZE
SEE STD. DETAILS FOR AND SCHEDULE FOR
CMU WALL - SEE DETAILS REINF.
FOR REINF. TYP. EMBED AND ANCHORS
8" SLAB - SEE PLAN 2' - 9"
8" SLAB - SEE PLAN CMU DWL. - MATCH WALL REINF. FOR REINF. CMU DWL. - MATCH WALL REINF.
FOR REINF. SIZE AND SPACING
CMU DWL. - MATCH WALL REINF.
8" SLAB - SEE PLAN
SIZE AND SPACING
TENNESSEE
LEVEL B2
SIZE AND SPACING
FOR REINF. LEVEL B2 ONCOLOGY
448'-6"
8"
448'-6"
LEVEL B2
8"
1' - 9"
448'-6"
8"
2' - 9" 2' - 9" P.T.CONCRETE BEAM
1' - 9"
CMU WALL ANCHORAGE 1' - 3" AND SCHEDULE FOR
SEE STD. DETAILS FOR 3' - 0" P.T.CONCRETE BEAM
REINF.
EMBED AND ANCHORS SEE PLAN FOR SIZE
AND SCHEDULE FOR
REINF.
P.T. CONCRETE BEAM CMU WALL ANCHORAGE CMU WALL ANCHORAGE
SEE PLAN FIR SIZE AND SEE STD. DETAILS FOR SEE STD. DETAILS FOR
SCHEDULE FOR REINF. EMBED AND ANCHORS EMBED AND ANCHORS
1' - 3"
I
I
3'-6"
10"
INTEGRAL WITH P.T. SLAB
LEVEL B1
458'-6" LEVEL B1
458'-6"
10" PT SLAB. SEE PLAN
FOR REINFORCING
Revision
I
No. Date Description
LEVEL B1
458'-6"
FRAMING SECTIONS
AND DETAILS
SECTION AT B1 RAMP TRANSITION
4/25/2023 5:34:38 PM
6 3/4" = 1'-0"
S423
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
INTERIOR EXTERIOR
E
EXTERIOR INTERIOR
8" CMU WALL - SEE
DETAILSFOR REINF. TYP. BRICK VENEER
SEE ARCH.
CMU DWL. - MATCH WALL REINF. BRICK VENEER
Approved By: Approver
Checker
6" L.W. CONCRETE TOPPING SLAB CMU DWL. - MATCH WALL REINF.
Drawn By:
E.O.S. GLASS WINDOW WALL 8" CMU WALL - SEE 4" L.W. TOPPING SLAB
SEE ARCH. SEE ARCH AND CIVIL FOR ELEVATIONS SIZE AND SPACING
DETAILS FOR REINF. TYP.
BRICK VENEER STRUCTURAL POLYSTYRENE AND FINISH
L.W. CONC. SEE ARCH. 6"x8" CONCRETE CURB
CURB 1/2" EXP. JOINT MAT'L. STRUCTURAL POLYSTYRENE
CMU DWL. - MATCH WALL REINF. ELEV. 471'-6" w/ (1) #4 CONT.
SIZE AND SPACING STRUCTURAL POLYSTYRENE STRUCTURAL POLYSTYRENE GreshamSmith.com
6" L.W. CONCRETE TOPPING SLAB
4"
#4 @ 12"O.C. SEE ARCH AND CIVIL FOR
6"
6" L.W. CONCRETE TOPPING SLAB
ELEVATIONS AND FINISH 6" L.W. CONCRETE TOPPING SLAB ELEV. 470'-0"
(3) #4 CONT. 4" L.W. TOPPING SLAB SEE ARCH AND CIVIL FOR ELEVATIONS
ELEV. 471'-6" SEE ARCH AND CIVIL FOR
6"
AND FINISH
ELEVATIONS AND FINISH
8"
5" STRUCTURAL POLYSTYRENE
6"
1' - 6"
3' - 0"
ELEV. 471'-6"
6"
STRUCTURAL POLYSTYRENE
1' - 6"
8" 7 1/2"
222 Second Avenue South
4"
ELEV. 468'-6" Suite 1400
1' - 6"
3' - 6"
Nashville, TN 37201
8"
615.770.8100
3' - 6"
8"
6"
ELEV. 470'-0" ELEV. 468'-6"
8"
8"
STRUCTURAL POLYSTYRENE
VARIES
STRUCTURAL POLYSTYRENE
STRUCTURAL POLYSTYRENE
8"
SLOPE
1' - 0"
ELEV. 471'-6"
1' - 6"
SLOPE LEVEL 01
ELEV. 471'-6"
2' - 2"
1' - 0"
471'-6"
2' - 6"
1' - 6"
2' - 6"
ELEV. 468'-6"
8"
6"
ELEV. 470'-0" T/CONC. WALL AT ENTRANCE
ELEV. 470'-0" DOOR 471'-6"
(3) #4 CONT. HORIZ. ELEV. 470'-0"
STRUCTURAL POLYSTYRENE
8"
8"
SEE SCHEDULE FOR SIZE AND (1) #4 CONT. HORIZ.
REINFORCING
1' - 3" 1' - 6" STRUCTURAL SLAB - SEE PLAN. 7 1/4" #4 @ 12"O.C. E.F. VERT. (4) #4 CONT. HORIZ.
SEE SCHEDULE FOR SIZE AND T/STRUCTURAL SLAB 470'-0" (4) #4 CONT. HORIZ.
REINFORCING T/STRUCTURAL SLAB 470'-0"
STRUCTURAL SLAB - SEE PLAN. CONCRETE BEAM. SEE PLAN FOR SIZE #5 @ 12"O.C. CTR'D.
1' - 3" STRUCTURAL SLAB - SEE PLAN. #5 @ 12"O.C. CTR'D.
SEE SCHEDULE FOR SIZE AND AND SCHEDULE FOR REINFORCING STRUCTURAL SLAB - SEE PLAN.
SEE SCHEDULE FOR SIZE AND
REINFORCING SEE SCHEDULE FOR SIZE AND
REINFORCING
REINFORCING
SECTION AT DRIVE NORTH AT GRID 5 SECTION AT DRIVE - EAST SIDE AT FIRE COMMAND SECTION AT DRIVE - EAST SIDE SECTION AT FIRE COMMAND EAST
5 3/4" = 1'-0" 6 3/4" = 1'-0" 7 3/4" = 1'-0" 8 3/4" = 1'-0"
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS SHALL BE LIGHTWEIGHT CONCRETE. AT MAIN ENTRANCE AND NORTH WALLS
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS
SHALL BE LIGHTWEIGHT CONCRETE.
SHALL BE LIGHTWEIGHT CONCRETE.
4
1' - 10 1/2"
BLOCK
VENEER
SEE ARCH. 1' - 0 5/8" METAL STUD WALL - SEE ARCH.
3' - 10"
TOPPING SLAB
ELEV. 472'-6" STRUCTURAL SLAB - SEE PLAN.
ELEV. 472'-6"
SEE SCHEDULE FOR SIZE AND
SEE ARCH.
REINFORCING Revision
1' - 0"
4"
ELEV. 471'-6" ELEV. 471'-6"
1"
4"
4' - 6"
ELEV. 470'-0"
1" ELEV. 470'-0"
8"
8"
STRUCTURAL
POLYSTYRENE
ELEV. 470'-0" ELEV. 470'-0"
8"
2' - 0"
(4) #4 CONT. HORIZ.
8"
8"
#5 @ 12"O.C. CTR'D.
SECTION AT LOBBY RAMP SECTION AT LOBBY STAIR SECTION AT HALLWAY STAIR SECTION AT GARAGE RAMP - SOUTH
9 3/4" = 1'-0" 10 3/4" = 1'-0" 11 3/4" = 1'-0" 12 3/4" = 1'-0"
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS
SHALL BE LIGHTWEIGHT CONCRETE. SHALL BE LIGHTWEIGHT CONCRETE. SHALL BE LIGHTWEIGHT CONCRETE. SHALL BE LIGHTWEIGHT CONCRETE.
FRAMING SECTIONS
AND DETAILS
4/25/2023 5:34:41 PM
S424
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
5
1
I
BLOCK
4 VENEER 8" CMU WALL - SEE
Approved By: Approver
SEE ARCH.
Checker
METAL STUD WALL - SEE ARCH. CONNECTION DETAILS SIZE AND SPACING
METAL STUD WALL
Drawn By:
3' - 10"
STRUCTURAL AND FINISH SEE ARCH AND CIVIL FOR
#4 @ 12"O.C. E.F. HORIZ. POLYSTYRENE STRUCTURAL POLYSTYRENE ELEVATIONS AND FINISH
L4x3x3/8"LLV CONT. w/ 3/4"⌀ EXP.
ANCHOR AT 12" O.C. MIN EMBED 6" 10 1/4" ELEV. 471'-6" STRUCTURAL POLYSTYRENE STRUCTURAL POLYSTYRENE
6" L.W. CONCRETE TOPPING SLAB.
SEE ARCH AND CIVIL FOR
4"
STRUCTURAL SLAB - SEE PLAN.
SEE SCHEDULE FOR SIZE AND ELEVATIONS AND FINISH #5 @ 8"O.C. 222 Second Avenue South
VERT. E.F. Suite 1400
1' - 4"
REINFORCING
1' - 6"
Nashville, TN 37201
3' - 10"
1' - 0 1/4"
ELEV. 472'-6" ELEV. 470'-0" 615.770.8100
6"
6"
#5 @ 8"O.C.
ELEV. 470'-0" VERT.
8"
5"
8"
1' - 10 1/2"
(3)-#4 CONT. E.F., HORIZ.
2' - 0"
8" 8"
2' - 0"
#4 @ 12" O.C. E.F., VERT. (3) #4 CONT.
CONCRETE BEAM -
1' - 4" 8" CONCRETE SLAB
SEE PLAN FOR SIZE
ELEV. 470'-0" AND SCHEDULE FOR
#5 @ 12"O.C. E.F. (1) #4 CONT.
REINFORCING Smith
Seckman
8"
STRUCTURAL SLAB -
1' - 3" 1' - 9" SEE PLAN. Reid, Inc.
CONCRETE BEAM - SEE PLAN FOR SIZE CONC. BEAM SEE SCHEDULE FOR
1' - 10 1/2" 1' - 9" (SEE PLAN) 2995 Sidco Drive
AND SCHEDULE FOR REINFORCING. SIZE AND REINFORCING
Nashville, TN 37204
(615) 383-1113
STRUCTURAL SLAB -
SEE PLAN. CONCRETE BEAM. SEE PLAN FOR SIZE SECTION AT AT WEST STAIR FAX: (615) 386-8469
www.ssr-inc.com
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS
SHALL BE LIGHTWEIGHT CONCRETE. SHALL BE LIGHTWEIGHT CONCRETE.
SECTION AT GARAGE RAMP NORTH SECTION AT LOADING DOCK EAST WALL
2 3/4" = 1'-0" 4 3/4" = 1'-0"
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS
SHALL BE LIGHTWEIGHT CONCRETE. SHALL BE LIGHTWEIGHT CONCRETE.
E
BLOCK VENEER TENNESSEE
SEE ARCH.
BLOCK VENEER
SEE ARCH. 6" L.W. CONCRETE TOPPING
LOADING ONCOLOGY
METAL STUD WALL SLAB - SEE PLAN 4 DOCK METAL STUD WALL
SEE ARCH.
INTERIOR
SEE ARCH.
6" L.W. CONCRETE 4
STRUCTURAL TOPPING SLAB
SLAB - SEE PLAN. HANDRAILS SEE ARCH. STRUCTURAL SLAB.
SEE SCHEDULE CONNECTION BY CONTRACTOR SEE PLAN SIZE
5"
REINFORCING H.S @12" O.C TYP ARMORING
AT ALL EDGES OF PIT 6" L.W. CONCRETE
STRUCTURAL POLYSTYRENE ELEV. 472'-0" 6" L.W. CONCRETE STRUCTURAL TOPPING SLAB
TOPPING SLAB
SEE ARCH AND
POLYSTYRENE LOADING SEE PLAN
8"
FINISH
5"
TOPPING SLAB
6"
1' - 7 1/2"
ELEV. 472'-0" SEE ARCH AND 63" LONGX74" WIDE 6X6 HK
1' - 8"
CIVIL FOR
6"
4' - 6"
2' - 6"
FINISH STRUCTURAL #5 @ 8"O.C.
ELEV. 470'-0"
4' - 0"
8"
8"
6"
CONSTRUCTION DOCUMENTS
STRUCTURAL SLAB 8"
(4) #4 @12"O.C. ELEV. 470'-0"
SEE PLAN. HORIZ. E.F.
STRUCTURAL SLAB - SEE PLAN. SEE SCHEDULE FOR
8"
SEE SCHEDULE FOR SIZE AND SIZE AND #5 @ 8"O.C.
REINFORCING REINFORCING VERT. E.F.
8"
CONCRETE BEAM - SEE PLAN FOR SIZE STRUCTURAL SLAB - SEE PLAN. (4) #4 #5 @ 8"O.C.
AND SCHEDULE FOR REINFORCING SEE SCHEDULE FOR SIZE AND HORIZ. E.F. E.F.
CONCRETE BEAM - SEE
REINFORCING
1' - 6" 1' - 6" PLAN FOR SIZE #5 @ 8"O.C.
AND SCHEDULE FOR STRUCTURAL SLAB - SEE PLAN.
CONCRETE BEAM. SEE PLAN FOR VERT. E.F. SEE SCHEDULE FOR SIZE AND
REINFORCING 1' - 10 1/2" 1' - 9"
SIZE AND SCHEDULE FOR REINFORCING REINFORCING
1' - 9" 1' - 9"
SECTION AT LOADING DOCK - EAST WALL SECTION AT MRI SUITE DEPRESSION SECTION AT LOADING DOCK SOUTH WALL SECTION AT DOCK LEVELER
5 3/4" = 1'-0" 6 3/4" = 1'-0" 7 3/4" = 1'-0" 8 3/4" = 1'-0"
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS
SHALL BE LIGHTWEIGHT CONCRETE. SHALL BE LIGHTWEIGHT CONCRETE.
COMPACTOR PAD
DIMENSIONS LOADING
23'-0"x11'-0" DOCK RAMP
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
ELEVATIONS AND CIVIL FOR SEE ARCH AND CIVIL FOR 471' - 6"
2' - 6"
1' - 6"
1 3/4"
ELEV. 470'-0"
ELEV. 470'-0"
8"
8"
10"
8"
10"
(4) #4 @12"O.C. 11'-0"
HORIZ. E.F. (4) #4 @12"O.C. 11'-0"
1' - 4"
HORIZ. E.F.
8" CONCRETE SLAB
#5 @ 8"O.C.
VERT. E.F. #5 @ 8"O.C.
VERT. E.F.
STRUCTURAL SLAB - SEE PLAN.
SEE SCHEDULE FOR SIZE AND STRUCTURAL SLAB - SEE PLAN.
SEE SCHEDULE FOR SIZE AND PB258 SEE PLAN
REINFORCING
REINFORCING
SECTION AT TRASH COMPACTOR PAD SECTION AT LOADING DOCK RAMP SECTION AT TOP OF SPEED RAMP
9 3/4" = 1'-0" 10 3/4" = 1'-0" 11 3/4" = 1'-0"
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS
SHALL BE LIGHTWEIGHT CONCRETE.
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS FRAMING SECTIONS
SHALL BE LIGHTWEIGHT CONCRETE. SHALL BE LIGHTWEIGHT CONCRETE.
AND DETAILS
5/25/2023 4:01:57 PM
S425
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
I H F
4
Approved By: Approver
Checker
BLOCK INTERIOR
VENEER
Checked By:
3 SEE ARCH.
Drawn By:
BEAM DEPTH
1' - 4"
10" RAMP SLAB "B" LA P
4' - 6"
T3 TOP BARS CALLS
T3 TOP BARS LEVEL 01 - PATTERSON
222 Second Avenue South
472' - 6" Suite 1400
Nashville, TN 37201
CB239
615.770.8100
LEVEL 01
471' - 6"
PB528
PB239 10" RAMP SLAB B1 BOTT BARS #5 @12" E.F.
LEVEL B1
458' - 6" #5 @12"O.C
TENNESSEE
ONCOLOGY
1 3/8" = 1'-0"
1' - 6"
8" CONC. SLAB BEYOND
CALL 'B
' LAP A
BEAM DEPTH
5' - 11 3 PLICE
/4"
3' - 6"
BLOCK
CMU DWL. - MATCH VENEER
PB224
5
CONSTRUCTION DOCUMENTS
CB 245,
30" CONC SIZE AND SPACING
WALL
T/CONC. WALL = 473'-10"
CB244(30x42) CB 245,
30" CONC
WALL
#5 @ 8"O.C. VERT. E.F.
PB258 L4x3x3/8"LLV CONT. w/ 3/4"⌀ EXP.
ANCHOR AT 12" O.C. MIN EMBED 6"
10"
CB 244,
30" CONC #4 @ 12"O.C. E.F. HORIZ.
BEAM
CB 244,
EXTERIOR
INTERIOR
3' - 10"
30" CONC 1' - 0 1/4"
WALL
LEVEL 01
471' - 6"
1' - 10 1/2"
1' - 6"
LEVEL B1
458' - 6"
FLOOR SLAB
PB161
@4 CLOSED TIES
SPACED PER
SCHEDULE ( 12" MAX)
#5 @12" E.F.
SECTION AT NORTH SPEED RAMP WALL
2 3/8" = 1'-0"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
BEAM BEYOND
2' - 6"
#5 @12"
NOTE: ALL CONCRETE WALLS AND TOPPING SLABS ABOVE STRUCTURAL SLABS
SHALL BE LIGHTWEIGHT CONCRETE.
FRAMING SECTIONS
AND DETAILS
4/25/2023 5:34:47 PM
S426
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
10"
CONTRACTOR SHALL
COORDINATE EMBEDS 1 1/2"
AND WINDOW WALL 3" 5 1/2"
CONNETIONS.
LOCATE CANOPY
LIGHT GAGE FRAMING
FRAMING EMBEDS AWAY
SEE ARCHITECT
9"
6"
FROM WINDOW WALL
H-B TBS BRICK SUPPORT 3 5/8" 4" CONNCETIONS
STOREFRONT WINDOW SYSTEM WITH
SEE ARCH SHARKTOOTH CONT.
Approved By: Approver
Checker
EMBED ANCHOR SYSTEM CONCRETE BEAM SEE WINDOW WALL EDGE EMBED PLATE
Author
3 5/8" 4" CONCRETE BEAM SEE PLAN OR APPROVED EQUAL. PLAN SEE ARCH
3/4"x10"x9" PLATE W/ (4) 3/4⌀ x4"
WINDOW WALL ANCHORAGE BY
LEVEL 02 H.S. SEE ABOVE FOR SPACING
Checked By:
1' - 9"
1' - 9"
EMBED ANCHOR SYSTEM #5@8"O.C TOP W/ #4 @10" O.C. 2' - 0" GreshamSmith.com
2' - 0"
2' - 0"
OR APPROVED EQUAL. 180° STD. HOOK T&B
LEVEL 02
490'-6"
8"
8"
CONTRACTOR IS RESPONSIBLE FOR
5"
THE DESIGN OF CUSTOM BRICK
LIGHT GAGE FRAMING SUPPORT SYSTEM. SYSTEM SHALL BE
AROUND PUNCHED H-B TBS SYSTEM OR EQUAL. SIZE OF LIGHT GAGE
FRAMING SEE 5/8" 222 Second Avenue South
BRICK VENEER WINDOWS SEE SYSTEM COMPONENTS, ANGLE,
ARCHITECT SPACING OF VERTICAL SUPPORTS ARCHITECT 6" Suite 1400
#5@8"O.C BOTT Nashville, TN 37201
AND SHARKTOOTH EMBEDDED
W/ 90° STD.
3' - 1 1/2"
CONTRACTOR IS RESPONSIBLE FOR
CHANNEL ANCHORS PER ENGINEER
HOOK 615.770.8100
RESPONSIBLE FOR DESIGN. SUBMIT
THE DESIGN OF CUSTOM BRICK LIGHT GAGE FRAMING
SIGNED AND SEALED CALCULATIONS
SUPPORT SYSTEM. SYSTEM SHALL BE SEE ARCHITECT
IN STATE OF PROJECT TO ENGINEER
H-B TBS SYSTEM OR EQUAL. SIZE OF OF RECORD FOR REVIEW.
L7x4x3/8" LLV LOOSE LINTEL SYSTEM COMPONENTS, ANGLE,
SPACING OF VERTICAL SUPPORTS CONCRETE BEAM SEE PLAN
AND SHARKTOOTH EMBEDDED
CHANNEL ANCHORS PER ENGINEER C6x8.2 @5'-0'
RESPONSIBLE FOR DESIGN. SUBMIT
SIGNED AND SEALED CALCULATIONS
SECTION AT SOUTH BRICK WALL 3/4"x9"x9" EMBED PLATE W/
Smith
IN STATE OF PROJECT TO ENGINEER
OF RECORD FOR REVIEW. 2 1" = 1'-0"
3/4"⌀x4" H.S. AT 6"
Seckman
Reid, Inc.
C6x8.2 @
5'-0'
10"
WINDOW WALL MANUF IS RESPONSIBLE 2995 Sidco Drive
FOR THE DESIGN OF ALL BRACING AND Nashville, TN 37204
C6x8.2 @5'-0' CONNECTIONS INCLUDING EMBEDS TO (615) 383-1113
HSS6x2x1/4" x CONT
CONCRETE STRUCTURE. SUBMIT FAX: (615) 386-8469
SECTION AT SOUTH STOREFRONT HSS6x2x1/4" x CONT CALCULATIONS FOR CONNECTIONS www.ssr-inc.com
1 1" = 1'-0"
SIGNED AND SEALED IN STATE OF
PROJECT TO ENGINEER OF RECORD
FOR REVIEW. SSR Project #: 21640780
SECTION AT ENTRANCE
3 1" = 1'-0"
1' - 0"
BRICK VENEER SEE ARCH. 1/2"x8"x8" EMBED PLATE
W (4) 3/4"⌀x4" H.S. @5"
BRICK VENEER
3/4"x9"x9" EMBED PLATE W/ SEE ARCH.
2' - 0"
2' - 0"
6" 3/4"⌀x4" H.S. AT 6" 3/4"x9"x9" EMBED PLATE W/
6" (4) 3/4"⌀x4" H.S. AT 6"
3' - 1 1/2"
3' - 1 1/2"
8"
8"
LIGHT GAGE
5/8" FRAMING SEE 5/8"
ARCHITECT C6x8.2 @5'-0"O.C.
4"
H-B TBS SYSTEM OR EQUAL. SIZE OF SUPPORT SYSTEM. SYSTEM SHALL BE STOREFRONT WINDOW
SYSTEM COMPONENTS, ANGLE, H-B TBS SYSTEM OR EQUAL. SIZE OF SEE ARCH
LIGHT GAGE
C6x8.2 CONT. SPACING OF VERTICAL SUPPORTS HSS6x2x1/4"xCONT. HSS6x2x1/4"xCONT. SYSTEM COMPONENTS, ANGLE,
FRAMING SEE
BETWEEN VERTICAL AND SHARKTOOTH EMBEDDED SPACING OF VERTICAL SUPPORTS 3 5/8"
ARCHITECT H-B TBS BRICK SUPPORT
SUPPORTS CHANNEL ANCHORS PER ENGINEER AND SHARKTOOTH EMBEDDED CONCRETE BEAM SEE PLAN
RESPONSIBLE FOR DESIGN. SUBMIT CHANNEL ANCHORS PER ENGINEER SYSTEM WITH
C6x8.2 @5'-0"O.C. SIGNED AND SEALED CALCULATIONS C6x8.2 @5'-0"O.C. C6x8.2 @5'-0"O.C. RESPONSIBLE FOR DESIGN. SUBMIT SHARKTOOTH CONT.
LEVEL 02
IN STATE OF PROJECT TO ENGINEER SIGNED AND SEALED CALCULATIONS EMBED ANCHOR SYSTEM
OF RECORD FOR REVIEW. IN STATE OF PROJECT TO ENGINEER OR APPROVED EQUAL. 490'-6"
OF RECORD FOR REVIEW.
1' - 9"
2' - 0"
4 1" = 1'-0"
SECTION AT SOUTH EYEBROW WITH BRICK
5 BRICK VENEER
8"
1" = 1'-0"
STOREFRONT
A ARCHITECT
WINDOW SEE
ARCH. L7x4x3/8" LLV LOOSE LINTEL CONTRACTOR IS RESPONSIBLE FOR
THE DESIGN OF CUSTOM BRICK
H-B TBS BRICK SUPPORT STOREFRONT SUPPORT SYSTEM. SYSTEM SHALL BE
3/4"x10"x9" PLATE W/ (4) 3/4⌀ x4" H-B TBS SYSTEM OR EQUAL. SIZE OF
SYSTEM WITH WINDOW SEE
H.S. SEE 3/S426 FOR DETAILS SYSTEM COMPONENTS, ANGLE,
SHARKTOOTH CONT. H-B TBS BRICK SUPPORT ARCH.
SYSTEM WITH SPACING OF VERTICAL SUPPORTS
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
SEE ARCH.
2' - 0" Revision
1' - 9" SECTION AT STORERONT No. Date Description
2' - 0"
LIGHT GAGE
8
2' - 0"
FRAMING SEE
1" = 1'-0"
ARCHITECT
3' - 1 1/2"
8"
8"
BRICK VENEER
SEE ARCH. CONTRACTOR IS RESPONSIBLE FOR STOREFRONT WINDOW
THE DESIGN OF CUSTOM BRICK SEE ARCH
C6x8.2 @5'-0'O.C
SUPPORT SYSTEM. SYSTEM SHALL BE
LIGHT GAGE H-B TBS SYSTEM OR EQUAL. SIZE OF
5/8" SYSTEM COMPONENTS, ANGLE,
FRAMING SEE
SPACING OF VERTICAL SUPPORTS 3 5/8" 4"
ARCHITECT L2 1/2"xL2 CONCRETE BEAM SEE PLAN
1/2"x1/4" AND SHARKTOOTH EMBEDDED
H-B TBS BRICK SUPPORT
BRACE @ LIGHT GAGE CHANNEL ANCHORS PER ENGINEER
1' - 5" SYSTEM WITH LEVEL 02
5'-0"O.C. FRAMING SEE RESPONSIBLE FOR DESIGN. SUBMIT
C6x8.2 @5'-0'O.C SHARKTOOTH CONT. 490'-6"
ARCHITECT SIGNED AND SEALED CALCULATIONS
EMBED ANCHOR SYSTEM
IN STATE OF PROJECT TO ENGINEER
CONTRACTOR IS RESPONSIBLE FOR OR APPROVED EQUAL.
OF RECORD FOR REVIEW.
THE DESIGN OF CUSTOM BRICK
SUPPORT SYSTEM. SYSTEM SHALL BE
1' - 9"
4"
2' - 0"
BRICK VENEER
C6x8.2 @5'-0'O.C SYSTEM COMPONENTS, ANGLE,
SPACING OF VERTICAL SUPPORTS
HSS6x2x1/4"x CONT. AND SHARKTOOTH EMBEDDED
SECTION AT STORERONT
8"
CHANNEL ANCHORS PER ENGINEER
STOREFRONT WINDOW SEE ARCH.
RESPONSIBLE FOR DESIGN. SUBMIT
SIGNED AND SEALED CALCULATIONS
7 1" = 1'-0" CONTRACTOR IS RESPONSIBLE FOR
IN STATE OF PROJECT TO ENGINEER THE DESIGN OF CUSTOM BRICK
OF RECORD FOR REVIEW. SUPPORT SYSTEM. SYSTEM SHALL BE
H-B TBS SYSTEM OR EQUAL. SIZE OF
SYSTEM COMPONENTS, ANGLE,
SPACING OF VERTICAL SUPPORTS
FRAMING SECTIONS
SECTION AT WEST EYEBROW AT BRICK LIGHT GAGE FRAMING
AND SHARKTOOTH EMBEDDED
CHANNEL ANCHORS PER ENGINEER
AND DETAILS
6 1" = 1'-0" SEE ARCHITECT RESPONSIBLE FOR DESIGN. SUBMIT
SIGNED AND SEALED CALCULATIONS
IN STATE OF PROJECT TO ENGINEER
4/25/2023 5:34:56 PM
SECTION AT STOREFRONT
S427
9 1" = 1'-0" 44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
6 6
WINDOW WALL
SEE ARCH 3/4"x10"x9" PLATE W/ (4) 3/4 WINDOW WALL
SEE ARCH
⌀ x4" H.S. SEE 3/S427
3/4"x10"x9" PLATE W/ (4) 3/4
STOREFRONT WINDOW ⌀ x4" H.S. SEE 3/S427
SEE ARCH
Approved By: Approver
3 5/8" 4" #5@8"O.C TOP W/ #4 @10" O.C. #5@8"O.C TOP W/ #4 @10" O.C.
Drawn By:
5/16" 180° STD. HOOK T&B 5/16" 180° STD. HOOK T&B
LEVEL 02
LEVEL 02 LEVEL 02
490'-6"
490'-6" 490'-6"
8"
8"
GreshamSmith.com
BRICK VENEER
BRICK VENEER
1' - 9"
1' - 9"
BRICK VENEER
2' - 0"
SEE ARCH 5/8"
6" SEE ARCH 6"
5/8" 6" 6"
#5@8"O.C BOTT W/
8"
CONTRACTOR IS RESPONSIBLE FOR CONCRETE BEAM SEE PLAN 90° STD. HOOK CONCRETE BEAM SEE PLAN
THE DESIGN OF CUSTOM BRICK #5@8"O.C BOTT
SUPPORT SYSTEM. SYSTEM SHALL BE W/ 90° STD. HOOK 222 Second Avenue South
3' - 8"
3' - 8"
H-B TBS SYSTEM OR EQUAL. SIZE OF Suite 1400
SYSTEM COMPONENTS, ANGLE, Nashville, TN 37201
SPACING OF VERTICAL SUPPORTS C6x8.2 @5'-0"O.C C6x8.2 @5'-0"O.C 615.770.8100
AND SHARKTOOTH EMBEDDED
LIGHT GAGE FRAMING CHANNEL ANCHORS PER ENGINEER 5/16" 5/16"
SEE ARCHITECT RESPONSIBLE FOR DESIGN. SUBMIT
SIGNED AND SEALED CALCULATIONS 5/16" 5/16"
3 5/8"4 5/8" 3/4"x9"x9" EMBED PLATE W/
IN STATE OF PROJECT TO ENGINEER 5/16" 3 5/8"4 5/8" 3/4"x9"x9" EMBED PLATE W/
5/16" 3/4"⌀x4" H.S. AT 6"
OF RECORD FOR REVIEW. C6x8.2 @5'-0"O.C 3/4"⌀x4" H.S. AT 6"
C6x8.2 @5'-0"O.C
Smith
4"
SECTION AT BRICK WALL L7x4x3/8" Seckman
1 1" = 1'-0"
CONT L7x4x3/8" CONT Reid, Inc.
HSS 6x6x1/4" 2995 Sidco Drive
L3x3x3/8"X7.5" BACK TO L3x3x3/8"X7.5" BACK TO
8" CMU WALL Nashville, TN 37204
BACK @ 4'-0"O.C. SEE BACK @ 4'-0"O.C. SEE
6/S428 FOR SUPPORT HSS 6x6x1/4" (615) 383-1113
6/S428 FOR SUPPORT
DETAILS DETAILS FAX: (615) 386-8469
www.ssr-inc.com
6 6
3/4"x10"x9" PLATE W/ (4) 3/4 3/4"x10"x9" PLATE W/ (4) 3/4
⌀ x4" H.S. SEE 3/S427 ⌀ x4" H.S. SEE 3/S427
7 1/2"
3' - 0 5/8" 3/16'
2"
BRICK VENEER 5/8"
5/8"
4"
SEE ARCH
6" 6" 6" 6"
3 5/8"
3 5/8"4 5/8" C6x8.2 4 5/8"
@5'-0" WELD
CONCRETE BEAM SEE PLAN CONCRETE BEAM SEE PLAN
O.C. AFTER
ERECTION 3/16" SECTION
C6x8.2 @
5'-0" O.C. VIEW
4' - 0"
4' - 0"
4' - 4"
HSS6x6x1/4"
CONT. BETWEEN 8 1/4"
5' - 0"
CONSTRUCTION DOCUMENTS
SEE ARCH. 3 3/4"
10"
2"
4"
SHELF ANGLE
3/16'
L2 1/2"x2 1/2"x1/4
5/16" BRACE @5'-0"
L7x4x3/8" CONT
SEE ARCHITECT
7 1/2" FOR GUTTER 5/16"
8"
SECTION AT LOADING DOCK OVER HEAD DOORS SECTION AT NORTH WALL CANOPY BRICK SHELF ANGLE SUPPORT DETAIL
4 1" = 1'-0" 5 1" = 1'-0" 6 1 1/2" = 1'-0"
F H
5"
5"
5"
5"
8"
4"
1/2"x6"xCONT. EMBED PLATE W/
3/4"⌀ x4" H.S. @8"O.C CONT. Revision
1' - 9"
2' - 0 1/2"
2' - 6"
COORDINATE CONNCETION
DETAIL WITH HANDRAIL MANUF. No. Date Description
#5@8"O.C BOTT W/ 2' - 6" METAL
90° STD. HOOK STUD WALL
SEE ARCH.
CONCRETE BEAM
METAL STUD WALL PT CONCRETE 1' - 4" SEE PLAN
SEE ARCH. BEAM SEE PLAN PT CONCRETE
1' - 4" BEAM SEE
PT CONCRETE BEAM SEE PALN PLAN
FRAMING SECTIONS
AND DETAILS
4/25/2023 5:35:04 PM
S428
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
1
1
6' - 11"
Approved By: Approver
Checker
Author
6' - 11"
WINDOW WALL 2' - 5 1/2"
SEE ARCH.
Checked By:
8"
Drawn By:
2' - 5 1/2"
WINDOW WALL WINDOW WALL ANCHORAGE 8"x8"x1/2" W/(2) 5/8" DIA. x 4" H.S. 5" SPACING, @ EACH
SEE ARCH. 8" BY WINDOW WALL MULLION CONNECTION COORDINATE LOCATION WITH
MANUFACTURER. WINDOW WALL MANUF.
WINDOW WALL ANCHORAGE 8"x8"x1/2" W/(2) 5/8" DIA. x 4" H.S. 5" SPACING, @ EACH
BY WINDOW WALL MULLION CONNECTION COORDINATE LOCATION WITH ROOFING - SEE ARCH. GreshamSmith.com
MANUFACTURER. WINDOW WALL MANUF. LIGHT GAGE PARAPET
FRAMING - SEE ARCH.
ROOFING - SEE ARCH. 3 5/8" 4"
LIGHT GAGE PARAPET #5 @ 12"O.C. VERT.
FRAMING - SEE ARCH.
3 5/8" 4" CONC. BEAM
#5 @ 12"O.C. VERT. SEE PLAN
2' - 0"
3/4"X10"X9" EMBED PLATE
(4) #4 x CONT.
BRICK VENEER
W/(4) 3/4" DIA x 4" H.S.
HORIZ. 222 Second Avenue South
SEE 3/S427
Suite 1400
2' - 0"
SEE ARCH. BRICK VENEER
(4) #4 x CONT. SEE ARCH. 1' - 4" 1/2"x8"x8" w( 4) 3/4" DIA x 4" Nashville, TN 37201
HORIZ. H.S AT 6"O.C. 615.770.8100
LEVEL 03
504' - 6"
5"
LEVEL 03
504' - 6" 1' - 6"
5"
8" MIN.
CONC. SLAB
1' - 9"
SEE PLAN
2' - 0"
CONCRETE SLAB Smith
1' - 9"
3' - 1 1/2"
2' - 0"
SEE PLAN
Seckman
Reid, Inc.
3' - 11 1/2"
MIN.
H-B TBS BRICK SUPPORT CONCRETE BEAM
SYSTEM WITH SHARKTOOTH 8" SEE PLAN 2995 Sidco Drive
5/8" Nashville, TN 37204
CONT. EMBED ANCHOR CONC. BEAM
2' - 9 1/2" (615) 383-1113
SYSTEM OR APPROVED H-B TBS BRICK SUPPORT C6x8.2 @ 5'-0"O.C. SEE PLAN
EQUAL. FAX: (615) 386-8469
SYSTEM WITH SHARKTOOTH www.ssr-inc.com
CONCRETE BEAM CONT. EMBED ANCHOR C6x8.2
SEE PLAN @ 5'-0"O.C. L2.5"x2.5"x1/4" BRACE
1' - 8" CONTRACTOR IS RESPONSIBLE FOR SYSTEM OR APPROVED
AT 5'-0"O.C.
THE DESIGN OF CUSTOM BRICK EQUAL. SSR Project #: 21640780
SUPPORT SYSTEM. SYSTEM SHALL BE
H-B TBS SYSTEM OR EQUAL. SIZE OF
SYSTEM COMPONENTS, ANGLE,
SPACING OF VERTICAL SUPPORTS CONTRACTOR IS RESPONSIBLE FOR
STORE FRONT HSS 6x2x1/4"
AND SHARKTOOTH EMBEDDED THE DESIGN OF CUSTOM BRICK
CONT.
4"
WINDOW - SEE CHANNEL ANCHORS PER ENGINEER
ARCH. SUPPORT SYSTEM. SYSTEM SHALL BE
RESPONSIBLE FOR DESIGN. SUBMIT 1' - 5" H-B TBS SYSTEM OR EQUAL. SIZE OF
SIGNED AND SEALED CALCULATIONS SYSTEM COMPONENTS, ANGLE,
IN STATE OF PROJECT TO ENGINEER SPACING OF VERTICAL SUPPORTS
OF RECORD FOR REVIEW. HSS6x2x1/4" CONT.
AND SHARKTOOTH EMBEDDED
L4x4x3/8"xCONT. CHANNEL ANCHORS PER ENGINEER
AT WINDOW WALL RESPONSIBLE FOR DESIGN. SUBMIT
C6x8.2 @ 5'-0"O.C.
WINDOW WALL ANCHORAGE SIGNED AND SEALED CALCULATIONS
IN STATE OF PROJECT TO ENGINEER
TENNESSEE
LIGHT GAGE FRAMING BY WINDOW WALL
SEE ARCH. DETAILS MANUFACTURER. OF RECORD FOR REVIEW.
ONCOLOGY
WINDOW WALL
SEE ARCH.
CONC. BEAM
SEE PLAN
2' - 0"
2' - 0"
1' - 4" 3/4"X10"X9" EMBED PLATE
W/(4) 3/4" DIA x 4" H.S. (4) #4 x CONT. (4) #4 x CONT.
SEE 3/S427 HORIZ. HORIZ.
BRICK VENEER 9' - 11"
BRICK VENEER SEE ARCH.
SEE ARCH. 1/2"x8"x8" w( 4) 3/4" DIA x 4" 1' - 4"
H.S AT 6"O.C.
LEVEL 03 LEVEL 03
504' - 6" 504' - 6"
5"
5"
3' - 4"
1' - 6"
2' - 0"
8" MIN.
CONC. SLAB
1' - 9"
1' - 9"
SEE PLAN CONC. SLAB
2' - 0"
2' - 0"
SEEE PLAN
3' - 1 1/2"
FRAMING SECTIONS
AND DETAILS
4/25/2023 5:35:09 PM
S429
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
6
Approved By: Approver 6
Checker
Author
M
Checked By:
Drawn By:
4'-1"
HANDRAIL - SEE ARCH.
WINDOW WALL 8" GreshamSmith.com
SEE ARCH.
WINDOW WALL ANCHORAGE 8"x8"x1/2" W/(2) 5/8" DIA. x 4" H.S. 5" SPACING, @ EACH 8"x8" x1/2" EMBED PLATE WITH
BY WINDOW WALL MULLION CONNECTION COORDINATE LOCATION WITH (4) 5/8"x 6" H.S. AT 5" SPACING.
MANUFACTURER. WINDOW WALL MANUF. PROVIDE AT VERTICAL POSTS. HANDRAIL - SEE ARCH. 6"x6" x1/2" EMBED PLATE WITH
3 5/8" 4" MAX SPACING 5'-0"O.C. (4) 5/8"x 6" H.S. AT 4" SPACING.
BRICK VENEER COORDINATE WITH SPACING PROVIDE AT VERTICAL POSTS.
#5 @ 8"O.C. TOP w/180° STD. HOOK
SEE ARCH. AND LOCATIONS WITH RAILING MAX SPACING 5'-0"O.C.
#5 @ 12"O.C. VERT. MANUF. AND DESIGNER. COORDINATE WITH SPACING 222 Second Avenue South
#4 @ 10"O.C. TOP AND BTM.
H-B TBS BRICK SUPPORT AND LOCATIONS WITH RAILING Suite 1400
MANUF. AND DESIGNER.
SYSTEM WITH SHARKTOOTH Nashville, TN 37201
1' - 4"
2' - 0"
CONT. EMBED ANCHOR 3 5/8" 4" 4' - 1" (2) #4 CONT. 615.770.8100
1' - 8"
7"
HORIZ. #4 @ 8"O.C. #5 @ 8"O.C. VERT.
#4 @ 8"O.C.
LEVEL 03
CONC. PAVERS - SEE ARCH.
504' - 6"
4"
5 1/2"
3 5/8" 4" 10"
8"
#5 @ 8"O.C. TOP w/180° STD. HOOK
CONC. PAVERS - SEE ARCH.
1' - 1"
5"
5 1/2"
1' - 9"
#4 @ 10"O.C. TOP AND BTM.
1' - 1"
#5 @ 8"O.C. TOP w/180° STD. HOOK Smith
1' - 6" 1' - 6"
ROOFING
SEE ARCH.
Seckman
Reid, Inc.
1' - 10 1/2"
ROOFING
3"
1' - 10 1/2"
LEVEL 03 #5 @ 8"O.C. VERT. SEE ARCH.
3"
504' - 6" LEVEL 03
2995 Sidco Drive
504' - 6"
3' - 4"
1' - 3"
1' - 3"
8" Nashville, TN 37204
1' - 0"
1' - 0"
8" (615) 383-1113
#5 @ 8"O.C. BTM. w/ 90° #4 @ 8"O.C. #4 @ 8"O.C.
STD. HOOK CONT. HORIZ. CONT. HORIZ. FAX: (615) 386-8469
CONCRETE BEAM www.ssr-inc.com
STUD WALL - SEE ARCH. SEE PLAN
5"
L7x4x3/8" LOOSE LINTEL
10"
SSR Project #: 21640780
10"
1' - 9"
1' - 9"
2' - 0"
8"
CONTRACTOR IS RESPONSIBLE FOR
THE DESIGN OF CUSTOM BRICK
BRICK VENEER 1' - 9"
1' - 9"
STORE FRONT WINDOW SUPPORT SYSTEM. SYSTEM SHALL BE
H-B TBS SYSTEM OR EQUAL. SIZE OF BRICK VENEER SEE ARCH.
SEE ARCH. SEE ARCH.
SYSTEM COMPONENTS, ANGLE, 1' - 6" 1' - 6"
SPACING OF VERTICAL SUPPORTS H-B TBS BRICK SUPPORT
AND SHARKTOOTH EMBEDDED SYSTEM WITH SHARKTOOTH #4 @ 10"O.C. TOP AND BTM.
H-B TBS BRICK SUPPORT CONT. EMBED ANCHOR
CHANNEL ANCHORS PER ENGINEER
SYSTEM WITH SHARKTOOTH SYSTEM OR APPROVED
RESPONSIBLE FOR DESIGN. SUBMIT
CONT. EMBED ANCHOR EQUAL.
SIGNED AND SEALED CALCULATIONS #5 @ 8"O.C. BTM. w/ 90°
SYSTEM OR APPROVED CONTRACTOR IS RESPONSIBLE FOR
IN STATE OF PROJECT TO ENGINEER STD. HOOK
OF RECORD FOR REVIEW.
EQUAL.
#5 @ 8"O.C. BTM. w/ 90°
CONCRETE BEAM
SEE PLAN
1' - 4 1/2"
THE DESIGN OF CUSTOM BRICK
SUPPORT SYSTEM. SYSTEM SHALL BE TENNESSEE
STD. HOOK H-B TBS SYSTEM OR EQUAL. SIZE OF
SYSTEM COMPONENTS, ANGLE,
SPACING OF VERTICAL SUPPORTS
ONCOLOGY
STORE FRONT WINDOW CONTRACTOR IS RESPONSIBLE FOR AND SHARKTOOTH EMBEDDED
SECTION AT NORTH WALL SEE ARCH. THE DESIGN OF CUSTOM BRICK STORE FRONT WINDOW
CHANNEL ANCHORS PER ENGINEER
1 1" = 1'-0"
SUPPORT SYSTEM. SYSTEM SHALL BE
H-B TBS SYSTEM OR EQUAL. SIZE OF
SYSTEM COMPONENTS, ANGLE,
SEE ARCH.
RESPONSIBLE FOR DESIGN. SUBMIT
SIGNED AND SEALED CALCULATIONS
IN STATE OF PROJECT TO ENGINEER
SPACING OF VERTICAL SUPPORTS
4"
LEVEL 03
5 1/2"
(1) #4 CONT.
#5 @ 8"O.C. TOP w/180° STD. HOOK 504' - 6"
2' - 1"
1' - 0"
#4 @ 12"O.C. T2 OR T5
5"
ROOFING PAVERS - SEE ARCH.
SEE ARCH.
ROOFING - SEE ARCH.
5"
#5 @ 8"O.C. VERT.
3' - 0 1/2"
4"
1' - 10 1/2"
LEVEL 03
1' - 0"
3"
5"
504' - 6"
2' - 0 1/2"
1' - 0"
5" SLAB T3 OR T6
BEYOND
1' - 0"
1' - 0"
8"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
1' - 9"
5"
10"
1' - 9"
FRAMING SECTIONS
AND DETAILS
4/25/2023 5:35:14 PM
S430
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
6
CURTAIN WALL 2" 4' - 7" 2' - 0"
M SEE ARCH.
1/2"x8"x8" w/ (4) 3/4"x4" H.S.
1 A WINDOW WALL ANCHORAGE AND
@ 5" SPACING. 4TH FLOOR
ONLY
2" 1' - 7 1/2" 2" 2' - 5"
EMBEDDED ANCHOR BY WINDOW 1
Approved By: Approver
AT EAST AND WEST EMBED CONCRETE ANCHOR BY HALFEN 90° STD. HOOK
WINDOW WALL ANCHORAGE AND EMBEDDED ANCHOR WALLS OR EQUAL. COORDINATE SPACING,
LENGTH OF CHANNEL, AND LOCATION #5@8"O.C TOP W/
BY WINDOW WALL MANUFACTURER. HTA-52/34-TA EMBED
WITH ANCHORAGE DESIGNER 180° STD. HOOK
CONCRETE ANCHOR BY HALFEN OR EQUAL. COORDINATE
Checked By:
3"
CONCRETE GROUT 2"x6"x8" RECESS FOR BY WINDOW WALL MANUFACTURER. HTA-52/34-TA EMBED
6" SPACING, LENGTH OF CHANNEL, AND LOCATION WITH
8"
CURTAIN WALL ANCHORAGE CONCRETE ANCHOR BY HALFEN OR EQUAL. COORDINATE
ANCHORAGE DESIGNER
3 1/2"
GROUT AFTER INSTALLATION SPACING, LENGTH OF CHANNEL, AND LOCATION WITH GreshamSmith.com
ANCHORAGE DESIGNER
6"
ADJUST STEEL CHANNEL EMBED 7'-6"O.C.
2"
6"
PLATE LOCATION AND WINDOW 4th FLR.
3' - 11 1/2"
WALL ANCHORAGE SO THEY DO ONLY
NOT CONFLICT. CONCRETE BEAM - SEE PLAN
2 1/2" FOR SIZE AND SCHEDULE
ADJUST BEAM STIRRUPS TO 4' - 1" 222 Second Avenue South
FOR REINFORCING
ALLOW FOR EMBED POCKET ADJUST BEAM STIRRUPS TO 2 1/2"
FOR CURTAIN WALL SYSTEM Suite 1400
ALLOW FOR EMBED POCKET
FOR CURTAIN WALL SYSTEM Nashville, TN 37201
1/2"x8"x8" w/ (4) 3/4"x4" H.S.
ADJUST BEAM STIRRUPS AND CONT. TOP
@ 5" SPACING. 4TH FLOOR 615.770.8100
STEEL TO ALLOW FOR EMBED POCKET
ONLY
FOR CURTAIN WALL SYSTEM
L2.5"x2.5"x1/4" @ 7'-6"O.C
CONCRETE BEAM - SEE PLAN CONCRETE BEAM - SEE PLAN 4th FLOOR ONLY
FOR SIZE AND SCHEDULE FOR SIZE AND SCHEDULE NOTE: ALL STEEL BRACES EMBED PLATES,
CURTAIN WALL CURTAIN WALL CONCRETE BEAM - SEE PLAN
FOR REINFORCING FOR REINFORCING CURTAIN WALL HSS6x4x1/4"xCONT. CHANNELS AND TUBES ARE FOR 4TH FLOOR
SEE ARCH. SEE ARCH. CURTAIN WALL FOR SIZE AND SCHEDULE
OFFSET AT 4th 4th FLOOR ONLY FRAMING ONLY
SEE ARCH. FOR REINFORCING
FLOOR ONLY
Smith
Seckman
Reid, Inc.
SECTION AT SOUTH WALL - 4th FLOOR SECTION AT EAST AND WEST WALLS SECTION AT NORTH WALL SECTION AT SOUTH WALL - 5th FLOOR 2995 Sidco Drive
1 3/4" = 1'-0" 2 3/4" = 1'-0" 3 3/4" = 1'-0" 4 3/4" = 1'-0" Nashville, TN 37204
(615) 383-1113
FAX: (615) 386-8469
www.ssr-inc.com
2' - 0"
& 6'-6" O.C AT 40' BAY.
2' - 0"
& 6'-6" O.C AT 40' BAY. WITH ANCHORAGE DESIGNER
2' - 4" SEE PLAN FOR POST LAYOUT
1/2"x8"x8" w/ (4) 3/4"x4" H.S. SEE PLAN FOR POST LAYOUT
2' - 0"
@ 5" SPACING AT EACH BEAM
#4 @10" O.C.
T&B
10" 10" 3/16
WINDOW WALL ANCHORAGE AND 3/16
5"
3"
EMBED CONCRETE ANCHOR BY HALFEN 548' - 6"
1' - 9"
8"
OR EQUAL. COORDINATE SPACING,
1' - 0"
LENGTH OF CHANNEL, AND LOCATION
WITH ANCHORAGE DESIGNER
3' - 11 1/2"
SECTION AT EAST INSET WALL SECTION AT EAST WEST & SOUTH PARAPET SECTION AT NORTH PARAPET
5 3/4" = 1'-0" 6 1" = 1'-0" 7 1" = 1'-0"
C E
2' - 0" 4' - 10 3/4"
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
5"
Revision
1' - 9"
1' - 9"
2' - 11 1/4"
SECTION AT WEST RETAIL ENTRY SECTION AT EAST MAIN ENTRY AT PORTE COCHERE
9 3/4" = 1'-0"
FRAMING SECTIONS
AND DETAILS
5/25/2023 4:01:57 PM
S431
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
OF WIDE FLANGE COLUMN
Approved By: Approver
Checker
OF GIRDER
MVW
3/4" MIN.
O TER
COVER
COPE BEAM FLANGE AND COLUMN
STUDS IN EACH FLUTE ON SIDE OF
Checked By:
0' - 0 1/2" "Leh" 0' - 0 1/2" "Leh" 0' - 0 1/2" "Leh" COMPOSITE DETAIL
PP E
WEB AS REQUIRED
RT
SU RIM
Drawn By:
PE
BEAM BEAM BEAM 3/4"ø PUDDLE WELD
STUD
0' - 2 1/4"
GreshamSmith.com
INTERMEDIATE
"Lev"
"Lev"
"Lev"
CL
SUPPORT
"N"-1@3"
"N"-1@3"
"N"-1@3"
"L"
"L"
"L"
COMPOSITE BEAM (6) #10 SELF-DRILLING SIDELAP
FASTENERS AT EA. JOIST
AN
SPACE (TYP.)
SP
"Z" "Z" "Z" 222 Second Avenue South
K
C
Suite 1400
DE
NOTES:
"Z" "Z" "Z" 1. ALL BEAMS SHALL HAVE STUDS SPACED UNIFORMLY ALONG LENGTH OF BEAM UNLESS OTHERWISE NOTED ON THE PLANS. WHERE A NON- Nashville, TN 37201
UNIFORM SPACING IS INDICATED ON THE FRAMING PLANS, SEE NOTES FOR TYPICAL COMPOSITE GIRDER.
"W" "W" "W"
2. STUD SPACING PROCEDURES:
615.770.8100
SHEAR TAB SHEAR TAB SHEAR TAB CASE 1 - TOTAL NUMBER OF STUDS IS LESS THAN THE NUMBER OF DECK RIBS. START AT BEAM ENDS AND PLACE STUDS AT UNIFORM END
SPACING ALONG THE BEAM LENGTH WHICH CORRESPONDS TO A DECK RIB MULTIPLE. WORK TOWARD CENTER OF THE BEAM. CL
SUPPORT 3/4" PUDDLE WELDS @ 6" O.C.
MAXIMUM SPACING BETWEEN ADJACENT STUDS SHALL NOT EXCEED 36". PROVIDE ADDITIONAL STUDS AS REQ'D. IF NUMBER OF STUDS
NOTED ON PLAN ARE INSUFFICIENT TO MEET MAX. SPACING LIMITS. AT PERIMETER SUPPORTS
CASE 2 - TOTAL NUMBER OF STUDS IS MORE THAN THE NUMBER OF DECK RIBS. IF MORE THAN ONE STUD PER RIB IS REQUIRED. PLACE
A DOUBLE ROW AS NEEDED, STARTING FROM BEAM ENDS AND WORKING TOWARD THE CENTER OF THE BEAM. 3/4" PUDDLE WELDS @ 6" O.C.
2" VLI 18 GA.
BEAM TO COLUMN FLANGE BEAM TO COLUMN WEB BEAM TO GIRDER 3. IF STUDS CANNOT BE PLACED WITH A UNIFORM SPACING ALONG THE FULL LENGTH OF THE BEAM, PROVIDE THE MORE CLOSELY SPACED (36/4 PATTERN) TYP. U.N.O.
STUDS NEAR THE ENDS OF THE BEAM.
OF HSS COLUMN 0' - 3" MIN. (SEE GIRDER
DIAMETER SHEAR TAB LRFD
NOTES THIS SHEET Smith
Seckman
MIN. CVR.
MIN. CVR.
BEAM "N" ROWS ("D") OF CONN.
0' - 0 3/4"
0' - 0 3/4"
0' - 1 1/2"
1' - 0" 1' - 0" 1' - 0"
0' - 1 1/2"
DESIGNATION OF BOLTS A325N LENGTH WIDTH THICKNESS WELD SIZE CAPACITY
Reid, Inc.
MIN.
MIN.
0' - 0 1/2"
BOLTS ("L") ("W") ("T") ("Z") (KIPS) 3' - 0"
W36 N=10 1" 30 1/2" 4 1/2" 1/2" 3/8" 251.0 2995 Sidco Drive
Nashville, TN 37204
W33 N=9 1" 27 1/2" 4 1/2" 1/2" 3/8" 226.0 36/4 PATTERN (615) 383-1113
W30 N=8 1" 24 1/2" 4 1/2" 1/2" 3/8" 202.0 FAX: (615) 386-8469
0' - 0 1/2" "Leh"
W27 N=7 1" 21 1/2" 4 1/2" 1/2" 3/8" 177.0 www.ssr-inc.com
NOTES:
BEAM W24 N=7 1" 21 1/2" 4 1/2" 7/16" 5/16" 155.0
COMPOSITE 1. SEE GENERAL NOTES AND FRAMING PLANS FOR DECK
W21 N=6 1" 18 1/2" 4 1/2" 7/16" 5/16" 132.0 DECK 1 1/2" MIN. REQUIREMENTS. SSR Project #: 21640780
W18 N=5 1" 15 1/2" 4 1/2" 7/16" 5/16" 88.0 (TYP.) SEE PLAN 2. DECK SHALL COVER A MINIMUM OF 3 SPANS.
W16 N=4 1" 12 1/2" 4 1/2" 5/16" 1/4" 65.0 3. SHEAR STUDS WELDED THRU THE DECK TO COMPOSITE
W14 N=3 1" 9 1/2" 4 1/2" 1/4" 3/16" 39.0 BEAMS. REPLACE THE PUDDLE WELDS ON A 1 FOR 1 BASIS.
"Lev"
W12 N=3 1" 9 1/2" 4 1/2" 1/4" 3/16" 37.0 DECK BUTTED NOT LOCATE STUDS ON OF WHERE TWO ROWS OF
"N"-1@3"
W10 N=2 1" 6 1/2" 4 1/2" 1/4" 3/16" 25.0 LAPPED AT JOINTS BEAM WHEN POSSIBLE STUDS PER RIB ARE REQ'D.
"L"
NOTES:
"Z" 1. ALL SHEAR TABS SHALL BE ASTM A36. COMPOSITE DECK CONNECTION
2. VERTICAL EDGE DISTANCE (Lev), SHALL BE 1 3/4" FOR ALL SINGLE SHEAR TAB SIMPLE BEAM 3 1" = 1'-0"
"Z" CONNECTIONS, UNLESS NOTED OTHERWISE.
3. HORIZONTAL EDGE DISTANCE (Leh), SHALL BE 2" FOR ALL SINGLE SHEAR TAB SIMPLE BEAM TYPICAL COMPOSITE BEAM TENNESSEE
"W"
SHEAR TAB
CONNECTIONS, UNLESS NOTED OTHERWISE.
4. ALL HOLES IN SHEAR TABS SHALL BE SHORT SLOTTED HORIZONTAL HOLES.
2 3/4" = 1'-0"
ONCOLOGY
5. ALL HOLES IN BEAM SHALL BE STANDARD DIAMETER HOLES PER AISC 360, TABLE J3.3.
6. ALL BOLTS SHALL BE HIGH STRENGTH OR TENSION CONTROL BOLTS PER ASTM F3125 GROUP A, (A325)
AND GROUP B, (A490).
7. ALL BOLTS INDICATED ABOVE SHALL BE INSTALLED AS "PRE-TENSIONED" IN ACCORDANCE WITH ONE OF
THE FOLLOWING INSTALLATION METHODS:
A. TURN OF THE NUT METHOD WITH MATCH MARKING.
MIN. CVR.
1st STUD
0' - 0 3/4"
0' - 1 1/2"
TYPICAL STEEL BEAM FRAMING CONNECTIONS (SINGLE PLATE SHEAR TAB) S1 S1 S2 S2
MIN.
1 1 1/2" = 1'-0"
TYP. 36" MAX.
HEADED STUD
SEE - PLAN
MINIMUM
S1 AND S2 = 4 1/2"
MAXIMUM
S1 AND S2 = 36"
1 1/2"
NOTES:
1. N1, N2, ETC. DENOTES THE NUMBER OF STUDS REQUIRED PER SEGMENT OF GIRDER. A SEGMENT IS THE SECTION OF GIRDER
BETWEEN THE END OF THE GIRDER AND THE NEAREST INTERIOR BEAM SUPPORTED BY THE GIRDER OR BETWEEN TWO
ADJACENT SUPPORTED BEAMS. THE NUMBER OF STUDS PER SEGMENT IS SHOWN ON THE FRAMING PLANS FOR EACH
FLOOR THICKNESS
EDGE ANGLE GIRDER. THE SPACING OF STUDS IN EACH SEGMENT (N1, N2 ETC.)SHALL BE DETERMINED BY THE LENGTH OF THE
SEGMENT AND THE NUMBER OF STUDS REQUIRED FOR THE SEGMENT AS SHOWN ABOVE.
PLAN PLAN
SEE PLAN
2. WHEN DOUBLE ROW OF STUDS IS REQUIRED, USE A STAGGERED PATTERN IF SPACING PERMITS. SEE MAXIMUM SPACING
DETAILS BELOW.
3. PROVIDE ADDITIONAL LAYER OF W.W.F. (MATCH REINFORCING) OVER GIRDERS.
4. WHERE STUDS ARE INDICATED TO BE UNIFORM SPACING, REFER TO COMPOSITE BEAM NOTES THIS SHEET.
CJP CJP D.E. (DECK EDGE) EDGE ANGLE
MIN. CVR.
0' - 0 3/4"
LOCATE STUDS ON
0' - 1 1/2"
0' - 1 1/2"
< 4" L6"x3 1/2"x5/16" L.L.V. CENTERLINE OF GIRDER
MIN.
MIN.
WHEN POSSIBLE GIRDER TOP
>4"<6" L6"x4"x5/16" L.L.V.
0' - 4 1/2"
FLANGE
MIN.
3"
0' - 4 1/2"
>6" L6"x6"x3/8" L.L.V. MIN
MIN.
.
MATCH tf, BEAM MATCH tf, BEAM
MIN. CVR.
0' - 0 3/4"
A572 GRADE 50 A572 GRADE 50 NOTE: ALL EDGE ANGLE SHALL HAVE 3/4"øx5" HEADED STUDS @ 16" O.C.
PLATE PLATE
COMPOSITE
DECK EDGE DETAIL GIRDER 0' - 3" 0' - 3" COMPOSITE
SIMPLE TYPE CONNECTION EXTENDED SHEAR TAB TYPE BEAM UNIFORM SPACING STAGGERED SPACING
SCHEDULE CONNECTION SCHEDULE
MATCH tf, BEAM, A572,
GRADE 50 PLATE
ELEVATION ELEVATION TYPICAL COMPOSITE GIRDER
6
Autodesk Docs://44791.00 MP TN Oncology Midtown R22/SSR_STRUCT_TN ONCOLOGY_21640780_R22.rvt
3/4" = 1'-0"
FULLY RESTRAINED - WELDED
MOMENT CONNECTION
4 3/4" = 1'-0"
Revision
No. Date Description
7
BEAM TO BEAM MOMENT CONNECTION OF SAME BEAM DEPTHS
3/4" = 1'-0"
S440
44791.01
04/27/2023
This Line is 3 Inches When Printed Full Size
CL OF COLUMN
"L" X "L" X 3/8" THICK
AND BASE PLATE #
PLATE WASHERS
"A" "A" "A" WF COLUMN
Approved By: Approver
Checker
FUTURE COL.
"C" THICK BASE PLATE
1 1/2"
1 1/2"
TYP.
TYP.
TYP.
MOMENT FRAME
CAP PLT. TO
2"
DIRECTION OF
"D" "D" "D" "H" THICK NON-SHRINK, BEAM
F
NON-METALLIC GROUT BASE 3/4" THK. A572 GR.
"B"
"B"
"B"
CL OF COLUMN CL OF BASE PLATE CL OF BASE PLATE 50 CAP PLT. GreshamSmith.com
"B1"
"B1"
AND BASE PLATE
CL OF COLUMN CL OF COLUMN T/STL. = 24'-0" A.F.F.
COLUMN
"J"x"J"x"K" EMBED PLATE
G
(REFER TO PLANS FOR SIZE) COLUMN COLUMN 1/4
1' - 0"
(REFER TO PLANS FOR SIZE) (REFER TO PLANS FOR SIZE)
CONNECTOR BY
23'-0" SCREENWALL MANUF.
CL OF COLUMN CL OF COLUMN CL OF COLUMN
AND BASE PLATE AND BASE PLATE CL OF BASE PLATE HSS8x8x3/8" x CONT. @ 5'-0"O.C.
222 Second Avenue South
T/STL. EL. = SEE BELOW Suite 1400
PLAN VIEW - TYPE 1 PLAN VIEW - TYPE 2 PLAN VIEW - TYPE 3 WF SECTION VIEW +3'-2" OVER 6TH FLOOR FFE
+8'-2" OVER 6TH FLOOR FFE
Nashville, TN 37201
615.770.8100
W24 - SEE +13'-2" OVER 6TH FLOOR FFE
CL OF COLUMN +18'-2"OVER 6TH FLOOR FFE
PLAN 1/4
"L" X "L" X 3/8" THICK AND BASE PLATE +23'-0"OVER 6TH FLOOR FFE
PLATE WASHERS
"A" "A" "A"
HSS COLUMN 1' - 4" +/- L6x6x3/8 x 0'-6"
1/4 2" (4) "E"ø HEADED ANCHOR 1 1/2" (4) "E"ø HEADED ANCHOR 1 1/2" (4) "E"ø HEADED ANCHOR (REFER TO PLANS FOR SIZE)
"A1" 3/4" A572 GR. 50
TYP. RODS W/"F" PROJECTION TYP. RODS W/"F" PROJECTION TYP. RODS W/"F" PROJECTION
REFER TO PLAN STIFF. PLT. EA. SIDE
AND "G" EMBEDMENT AND "G" EMBEDMENT AND "G" EMBEDMENT "E"ø HEADED ANCHOR RODS SCREENWALL SYSTEM
W/"F" PROJECTION AND "G" W24 7 3/8" SEE ARCH.
"C" THICK BASE PLATE "C" THICK BASE PLATE "C" THICK BASE PLATE EMBEDMENT SEE PLAN Smith
Seckman
1 1/2"
1 1/2"
TYP.
TYP.
"C" THICK BASE PLATE
TYP.
Reid, Inc.
2"
F
DIRECTION OF NON-METALLIC GROUT BASE
"B"
"B"
"B"
CL OF COLUMN CL OF BASE PLATE CL OF BASE PLATE
"B1"
"B1"
MOMENT FRAME Nashville, TN 37204
AND BASE PLATE
CL OF COLUMN CL OF COLUMN (615) 383-1113
FAX: (615) 386-8469
COLUMN www.ssr-inc.com
(REFER TO PLANS FOR SIZE) COLUMN COLUMN "J"x"J"x"K" EMBED PLATE
G
(REFER TO PLANS FOR SIZE) (REFER TO PLANS FOR SIZE) W14
SEE PLAN SSR Project #: 21640780
BASE PLATE DIMENSIONS WELD ANCHOR BOLT GROUT EMBED PLATE PL WASHER
COLUMN SIZE TYPE "A" "A1" "B" "B1" "C" "D" "E" "F" "G" "H" "J" "K" "L" 1
W14x123
W14X145
1
1
18"
20"
-
-
24"
24"
-
-
1.75"
1.5"
7/16"
7/16"
1"
1-1/4"
7"
7"
28"
28"
1.75"
1.5"
-
3"
-
1/2"
-
3"
BASE PLATE
(SEE SCHEDULE)
1/4 TENNESSEE
W14x211 1 20" - 26" - 2" 7/16" 1-3/4" 9" 28" 2" 4 1/2" 3.5" 2' - 6"
L6x6x3/8 x 0'-6"
ONCOLOGY
2' - 0"
BEAM - SEE
PLAN
5"
1' - 0"