Project:

ETAP Page: 1
12.6.0H
Location: Date: 17-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LF-Example1 Config.: Normal

SHORT- CIRCUIT REPORT

Fault at bus: Bus1


Nominal kV = 33.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus1 Total 0.00 42.895 0.00 101.24 101.16 41.885 41.885 3.26E-001 4.47E+000 3.43E-001 4.80E+000

Bus2 Bus1 27.40 1.413 70.76 104.55 69.88 0.920 0.000 1.18E+001 1.36E+002

Bus5 Bus1 28.76 1.483 71.43 104.55 70.23 0.965 0.000 1.28E+001 1.29E+002

U1 Bus1 100.00 40.000 100.00 100.00 100.00 40.000 41.885 3.43E-001 4.80E+000 3.43E-001 4.80E+000

Bus4 Bus3 27.89 0.000 96.55 95.89 55.29 0.000 0.000

Lump1 Bus3 104.55 6.758 104.55 104.55 104.55 3.810 0.000 1.00E+001 1.00E+002

Bus6 Bus7 40.47 0.467 98.53 96.39 63.43 0.263 0.000 1.35E+003 7.54E+002

Lump3 Bus7 104.55 6.641 104.55 104.55 104.55 3.744 0.000 1.00E+001 1.00E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 42.895 41.885 37.148 42.428
Peak Current (kA), Method C : 109.676 107.092 94.982 108.481
Breaking Current (kA, rms, symm) : 41.885 37.148 42.428
Steady State Current (kA, rms) : 40.000 41.885 37.148 42.428

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 2
12.6.0H
Location: Date: 17-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LF-Example1 Config.: Normal

Fault at bus: Bus2


Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus2 Total 0.00 30.578 0.00 173.01 173.36 0.105 0.105 1.90E+000 2.87E+001 2.51E+004 3.57E+001

Bus1 Bus2 84.65 21.828 95.66 95.64 95.65 0.085 0.105 * 2.12E+000 4.03E+001 2.51E+004 3.57E+001

Bus4 Bus3 0.00 0.000 101.68 101.79 101.88 0.000 0.000

Lump1 Bus3 100.00 8.756 100.00 100.00 100.00 0.020 0.000 1.00E+001 1.00E+002

Bus5 Bus1 91.66 0.163 100.00 99.99 100.01 0.000 0.000 5.62E+002 2.28E+001

U1 Bus1 95.65 4.401 95.65 95.65 95.65 0.009 0.000 3.43E-001 4.80E+000 3.43E-001 4.80E+000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 30.578 0.105 26.481 26.507
Peak Current (kA), Method C : 78.900 0.271 68.329 68.397
Breaking Current (kA, rms, symm) : 0.105 26.481 26.507
Steady State Current (kA, rms) : 21.735 0.105 26.481 26.507

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 3
12.6.0H
Location: Date: 17-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LF-Example1 Config.: Normal

Fault at bus: Bus3


Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus3 Total 0.00 30.578 0.00 173.01 173.36 0.105 0.105 1.90E+000 2.87E+001 2.51E+004 3.57E+001

Bus4 Bus3 0.00 0.000 101.68 101.79 101.88 0.000 0.000

Lump1 Bus3 100.00 8.756 100.00 100.00 100.00 0.020 0.000 1.00E+001 1.00E+002

Bus1 Bus2 84.65 21.828 95.66 95.64 95.65 0.085 0.105 * 2.12E+000 4.03E+001 2.51E+004 3.57E+001

Bus5 Bus1 91.66 0.163 100.00 99.99 100.01 0.000 0.000 5.62E+002 2.28E+001

U1 Bus1 95.65 4.401 95.65 95.65 95.65 0.009 0.000 3.43E-001 4.80E+000 3.43E-001 4.80E+000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 30.578 0.105 26.481 26.507
Peak Current (kA), Method C : 78.900 0.271 68.329 68.397
Breaking Current (kA, rms, symm) : 0.105 26.481 26.507
Steady State Current (kA, rms) : 21.735 0.105 26.481 26.507

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 4
12.6.0H
Location: Date: 17-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LF-Example1 Config.: Normal

Fault at bus: Bus4


Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus4 Total 0.00 54.319 0.00 97.63 98.31 56.597 56.597 3.62E+001 2.35E+002 3.43E+001 2.06E+002

Bus3 Bus4 86.38 54.319 92.48 91.78 98.24 56.597 56.597 * 3.62E+001 2.35E+002 3.43E+001 2.06E+002

Lump1 Bus3 98.24 0.996 98.24 98.24 98.24 0.599 0.000 1.00E+001 1.00E+002

Bus1 Bus2 92.66 2.482 93.77 93.06 93.71 1.493 0.000 * 1.69E+002 1.93E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 54.319 56.597 47.042 55.737
Peak Current (kA), Method C : 125.744 131.018 108.897 129.026
Breaking Current (kA, rms, symm) : 56.597 47.042 55.737
Steady State Current (kA, rms) : 51.784 56.597 47.042 55.737

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 5
12.6.0H
Location: Date: 17-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LF-Example1 Config.: Normal

Fault at bus: Bus5


Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus5 Total 0.00 31.162 0.00 173.02 173.35 0.105 0.105 2.03E+000 2.82E+001 2.51E+004 3.57E+001

Bus1 Bus5 84.64 21.824 95.66 95.64 95.65 0.084 0.105 * 2.12E+000 4.03E+001 2.51E+004 3.57E+001

Bus6 Bus7 14.86 0.616 101.69 101.79 101.86 0.001 0.000 5.09E+002 1.34E+003

Lump3 Bus7 100.00 8.756 100.00 100.00 100.00 0.020 0.000 1.00E+001 1.00E+002

Bus2 Bus1 91.50 0.156 100.00 99.99 100.01 0.000 0.000 5.89E+002 1.74E+001

U1 Bus1 95.65 4.407 95.65 95.65 95.65 0.009 0.000 3.43E-001 4.80E+000 3.43E-001 4.80E+000

Lump4 Bus6 101.79 9.616 101.79 101.79 101.79 0.019 0.000 4.75E+002 1.13E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 31.162 0.105 26.987 27.014
Peak Current (kA), Method C : 80.028 0.270 69.306 69.373
Breaking Current (kA, rms, symm) : 0.105 26.987 27.014
Steady State Current (kA, rms) : 21.735 0.105 26.987 27.014

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 6
12.6.0H
Location: Date: 17-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LF-Example1 Config.: Normal

Fault at bus: Bus6


Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus6 Total 0.00 64.573 0.00 101.55 99.95 63.619 63.619 3.82E+001 1.96E+002 3.43E+001 2.06E+002

Bus7 Bus6 86.38 54.318 92.73 92.17 98.24 56.873 63.619 * 3.62E+001 2.35E+002 3.43E+001 2.06E+002

Lump4 Bus6 100.00 10.518 100.00 100.00 100.00 6.908 0.000 4.75E+002 1.13E+003

Lump3 Bus7 98.24 0.996 98.24 98.24 98.24 0.566 0.000 1.00E+001 1.00E+002

Bus1 Bus5 92.66 2.482 93.78 93.11 93.73 1.412 0.000 * 1.69E+002 1.93E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 64.573 63.619 55.922 64.612
Peak Current (kA), Method C : 145.085 142.941 125.647 145.174
Breaking Current (kA, rms, symm) : 63.619 55.922 64.612
Steady State Current (kA, rms) : 51.784 63.619 55.922 64.612

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 7
12.6.0H
Location: Date: 17-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LF-Example1 Config.: Normal

Fault at bus: Bus7


Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus7 Total 0.00 31.162 0.00 173.02 173.35 0.105 0.105 2.03E+000 2.82E+001 2.51E+004 3.57E+001

Bus6 Bus7 14.86 0.616 101.69 101.79 101.86 0.001 0.000 5.09E+002 1.34E+003

Lump3 Bus7 100.00 8.756 100.00 100.00 100.00 0.020 0.000 1.00E+001 1.00E+002

Bus1 Bus5 84.64 21.824 95.66 95.64 95.65 0.084 0.105 * 2.12E+000 4.03E+001 2.51E+004 3.57E+001

Lump4 Bus6 101.79 9.616 101.79 101.79 101.79 0.019 0.000 4.75E+002 1.13E+003

Bus2 Bus1 91.50 0.156 100.00 99.99 100.01 0.000 0.000 5.89E+002 1.74E+001

U1 Bus1 95.65 4.407 95.65 95.65 95.65 0.009 0.000 3.43E-001 4.80E+000 3.43E-001 4.80E+000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 31.162 0.105 26.987 27.014
Peak Current (kA), Method C : 80.028 0.270 69.306 69.373
Breaking Current (kA, rms, symm) : 0.105 26.987 27.014
Steady State Current (kA, rms) : 21.735 0.105 26.987 27.014

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer