MNET HART Analog Datasheet
MNET HART Analog Datasheet
Modbus TCP/IP
The Modbus TCP/IP driver interfaces with a common
internal database in the module. This permits the sharing
of data between the Modbus TCP/IP and other networks
and devices.
Modbus TCP/IP Server
General Server supports up to 5 independent
connections each to Modbus TCP/IP
clients on Service Port 502 using the
standard MBAP protocol, and
Service Port 2000.
Configurable Module IP Address
Parameters Modbus address offsetting
Modbus TCP/IP Client
General Actively reads and writes data with
Modbus TCP/IP compatible devices.
Modbus TCP/IP to HART One client connection (up to 100
Analog Gateway servers/devices with 100
commands)
5208-MNET-HART / 5228-MNET-HART
Configurable Number of active commands, Min
The HART Analog Input Gateway provides a clean way parameters Command Delay, Response
to integrate HART Analog instruments with existing Timeout, Retry Count, Command
controller platforms on a Modbus TCP/IP network. The Error Pointer
gateway works well for field applications where it can be Command List Up to 100 fully configurable
installed closer to HART instrument, saving on copper commands on the Client port
cable and installation costs. The gateway also saves
valuable rack space for other in-chassis options. The
gateways provide extremely fast channel update times HART Analog
(all channels updating simultaneously in 67 ms) making The HART Analog Protocol exists in 4 and 8 channel
the HART Analog Input Gateway ideal for applications implementations. This driver can be configured on an
where high speeds and point-to-point connectivity are individual channel basis to operate as a HART Master
required. These gateways are available in 4 and 8 Station and supports all the available HART commands
Analog input channel options. including Universal, Common Practice and Device
Specific Commands. Each HART channel is
independently configured to interface with the internal
database in the module.
The auto-poll mode allows the module to automatically
collect data from each HART instrument on the channel
and store the data in the module's database without the
use of user commands. The module automatically Hardware Specifications
generates HART commands 0, 3, 13, 14 and 15. Specification Description
General Parameters Power Supply Input 24 VDC nominal
Communication Number of HART Preambles: 2 to 50 18 to 32 VDC allowed
parameters Enable Handheld: Y or N Positive, Negative, GND Terminals
Primary Master: Y or N 2.5 mm screwdriver blade
Configurable Auto-Poll Enable, Short / Long Current Load 1-4 ch: 190 mA max@ 32 VDC max
Parameters per Address Retries, Retries After Error 5-8 ch: 250 mA max@ 32 VDC max
Channel Poll Time After Error, Number of Operating -20 to 50°C (-4 to 122°F)
Commands, Slave List Error Pointer Temperature
HART Driver Storage -40 to 85°C (-40 to 185°F)
Command List Up to 100 fully configurable Temperature
commands per channel Relative Humidity 5% to 95% (non-condensing)
Polling of command list User configurable polling of Dimensions Standard: 5.20H x 2.07W x 4.52D in.
commands, including disabled, (13.2cmH x 5.25cmW x 11.48cmD)
continuous, on change of data (write Extended: 5.20H x 2.73W x 4.52D in.
only) and dynamically user or (13.2cmH x 6.934cmW x 11.48cmD)
automatic enabled.
LED Indicators Power and Module Status
Isolated HART Analog Input Specifications Application Status
Input Range Current: 4 to 20mA with HART HART Channel Activity (Green)
Ordering Information
To order this product, please use the following:
5208-MNET-HART / Modbus TCP/IP to HART Analog
5228-MNET-HART Gateway
To place an order, please contact your local ProSoft
Technology distributor. For a list of ProSoft Technology
distributors near you, go to http://www.prosoft-
technology.com
Distributors:
Place your order by email or fax to:
Europe
[email protected],
fax to +33 (0) 5.61.78.40.52
Specifications are subject to change without notice.