BU615 Critical Connections
BU615 Critical Connections
CRITICAL CONNECTIONS
Critical connections in a building Failure of a connection is likely to This bulletin describes critical
October 2017
occur where loads are transferred result in loss of structural integrity. connections of timber-framed
from one structural element to buildings and the fixings required to
another. meet design loads.
1 INTRODUCTION Table 1. Fixing type and capacity reference guide
(from NZS 3604:2011 Table 2.2 1).
1.0.1 Loads imposed on buildings are transferred through
framing via load paths. The connections between elements Fixing Description (and Alternative See NZS
within a load path are critical to a building’s structural type NZS 3604:2011 fixing 3604:2011
integrity. If connections fail, load transference will not figure reference) capacity (kN) table
occur, and the building (or part of it) may fail. A 2/90 x 3.15 end nails 0.7 8.18
B 2/90 x 3.15 end nails 4.7
1.0.2 Critical connection locations are: + 2 wire dogs
∫∫ roof framing
∫∫ roof to wall C 2/90 x 3.15 end nails 8.5
+ strap fixing (see
∫∫ wall and wall to floor/subfloor
Figure 8.12)
∫∫ subfloor to foundation (suspended timber floor).
D 4/90 x 3.15 end 16.0
1.0.3 NZS 3604:2011 Timber-framed buildings specifies nails + 2 strap fixing
connections at the critical areas of timber-framed (double stud)
buildings. It gives fixing capacities in kilonewtons (kN) to E 2/90 x 3.15 skew 4.7 10.1, A10.1,
allow manufacturers to develop proprietary fixings that nails + 2 wire dogs 10.7, A10.7,
meet or exceed NZS 3604:2011 requirements. 10.11, A10.11,
F 2/90 x 3.15 skew 7.0 10.14, 10.15,
nails + strap fixing 15.6, A15.6,
1.0.4 This bulletin outlines the critical connections for (see Figure 10.6)
light timber-framed buildings and explains where the 15.10, A15.10
required fixing type and capacity can be found in G 10/90 x 3.15 nails (5 4.7 10.2, A10.2,
NZS 3604:2011. each side) 15.7, A15.7
H 1/M12 bolt 8.5
2 TYPES OF CONNECTIONS I 2/M12 bolts 16.0
2.0.1 Connections consist of: J 2/M16 bolts 24.0
∫∫ connectors such as straps, hangers, angles, plates
K 6/90 x 3.15 nails 3.0 10.5, A10.5
and cleats
∫∫ fasteners such as nails, screws and bolts. L 2/M12 bolts 9.8
M 2/M16 bolts 13.0
2.0.2 Tables in NZS 3604:2011 specify connections
based on timber size, span, moisture and exposure N 6/100 x 4.0 HDG 4.7 10.8, A10.8,
nails (hand-driven) 15.8, A15.8
levels, wind zone and light or heavy claddings.
O 2/M12 bolts (see 6.8
2.0.3 Conditions outside the scope of NZS 3604:2011 Figure 9.3(C))
require specific engineering design. P 2 HDG 'flat' straps 13.7
(see Figure 9.3(B))
2.0.4 NZS 3604:2011 uses letters to identify each type of
fixing (Figure 1). Q 2 HDG 'tee' straps 25.5
(see Figure 9.3(A))
2.0.5 Table 1 describes fixing types, alternative fixing R 1/90 x 3.15 nail 0.55 10.10, A10.10,
capacities and the tables in the standard where they can be 10.12,
S 2/90 x 3.15 nails 0.8
found. Fixings in each colour-shaded group can be used in 15.9, A15.9
the same location but may have different fixing capacities. T 1/10 g self-drilling 2.4
screw, 80 mm long
2.0.6 Each fixing type has a capacity based on the U 1/14 g self-drilling 5.5
configuration of the connection, load direction (e.g. type 17 screw,
gravity or uplift) and the in-service environment (wet or 100 mm long
dry). There may be situations where the fasteners are
Note: Capacities are associated with fixing type, not fasteners. See
the same but have different capacities. For example, individual selection tables for the appropriate fixing type for the
fixing types I and O both use 2/M12 bolts but the fixing application.
capacities are rated differently. Fixing type I connects
a ridge beam to its supporting studs for use in dry 3.1.2 NZS 3604:2011 Table 10.1(a) specifies fixing
internal environments, while fixing type O is for exposed types for ordinary and hip rafter connections and types,
situations (wet) to connect a veranda beam to post based on rafter size, spacing and span, as follows:
connections. ∫∫ Type E = 2/90 x 3.15 mm skew nails plus two wire dogs
(4.7 kN capacity).
3 ROOF FRAMING AND ROOF-TO-WALL ∫∫ Type F = 2/90 x 3.15 mm skew nails plus strap fixing
as shown in NZS 3604:2011 Figure 10.6 (7.0 kN
CONNECTIONS capacity).
3.1 RAFTER CONNECTIONS 3.1.3 NZS 3604:2011 Table 10.1(b) specifies 4.7 kN
fixings (type E) for valley rafter connections based on
3.1.1 Figures 2–5 describe rafter connections. rafter size, spacing and span.
1
Copyright in NZS 3604:2011 is owned by the Crown in right of New Zealand and administered by the New Zealand. Standards Executive.
Reproduced with permission from Standards New Zealand, on behalf of the New Zealand. Standards Executive, under copyright licence LN001236.
blocking
for ceiling
rafter
single top
plate
blocking
for ceiling
top plate
ceiling
joist
rafter
rafter
stud
stud
double top
plate
type E: type F:
-- 2/90 x 3.15 mm skew nails -- 2/90 x 3.15 mm skew nails
and two wire dogs or plus strap fixings as per fix strap to each side of rafter with:
NZS 3604:2011 Figure 10.6 or
-- 4.7 kN connectors -- 4/30 x 3.15 mm nails to side of both top plates
-- 7.0 kN connectors
-- 4/30 x 3.15 mm nails to side of rafter
(NZS 3604:2011 Table 10.1)
Figure 2. Rafter to ridge board and top plate connections. Figure 3. Fixing straps to rafters.
fix each rafter to beam with 4/75 x 3.15 mm skew nails plus fix each rafter to ridge beam with:
fixings from NZS 3604:2011 Table 10.1 or 10.15
-- 4/75 x 3.15 mm skew nails plus fixings
(type E or type F fixings)
from NZS 3604:2011 Table 10.1 or 10.15
(type E or type F fixings)
rafter
rafter
rafter ridge beam
ridge beam
rafter
Figure 4. Rafter to ridge beam connections from NZS 3604:2011 Figure 10.5.
(a) Hip and common rafter connection (b) Jack rafter to hip rafter connection
common rafter
hip rafter
ridge
board
3.3.1 End support and resistance to uplift for ridge top plate
beams must be provided by gable end wall framing or
internal posts (Figure 7).
90 x 3.15 mm skew nail
3.4 UNDERPURLINS, STRUTS AND STRUTTING BEAMS stud
each side plus strap fixing
as per NZS 3604:2011
3.4.1 Underpurlins support rafters at an intermediate Figure 10.6 for 7.0 kN capacity
point along their length. They are supported by
underpurlin struts or strutting beams, which are Figure 6. Truss to single top plate showing type F connection
supported off internal loadbearing walls. (NZS 3604:2011 Table 10.14, 10.15 and Figure 10.6).
fix strap with 3.7.1 NZS 3604:2011 fixing requirements for roof
30 x 2.5 mm bracing are given in Figures 8–13.
80 mm nails
3.8 VERANDA POSTS AND BEAMS
built-up raking
studs plate 3.8.1 Wind uplift forces can be greater on veranda roofs
bolt that are open to wind exposure.
fixing
bolt fixing: 3.8.2 NZS 3604:2011 section 9 deals with posts
-- type H: 1/M12 bolt (8.5 kN) supporting roofs. Table 9.2 gives connection capacities
-- type I: 2/M12 bolts (16.0 kN) based on the area of roof supported, wind zone and
-- type J: 2/M16 bolts (24.0 kN) roof cladding weight. Post/beam connection details are
(Note: bolt fixings include 50 x 50 x 3 mm washers) shown in Figure 14.
Figure 7. Ridge beam to wall connection (NZS 3604:2011 Table 10.2). 3.8.3 NZS 3604:2011 Table 10.8 sets out veranda beam
sizes and fixings for all wind zones based on beam span
3.4.2 NZS 3604:2011 Table 10.5 provides details for and loaded dimension.
underpurlin sizes, spans, loaded dimensions and fixings.
Table 10.5 describes fixing types L and M. These use M12 3.8.4 The post connections in NZS 3604:2011 Tables 9.1
and M16 bolts, which are not shown in Figures 10.11 and and 9.2 may be applied to carports. The veranda beam
10.12. table only applies to verandas.
3.4.3 NZS 3604:2011 Table 10.7 and Figure 10.13 4 WALL AND WALL-TO-FLOOR
describe the fixings for strutting beams.
CONNECTIONS
3.5 OUTRIGGERS AND FLYING RAFTERS
4.0.1 Wall and wall-to-floor connections resist vertical
3.5.1 Overhanging gables are vulnerable to wind uplift downwards and upwards and in-plane and out-of-plane
forces. NZS 3604:2011 clause 10.2.1.15 describes loads that occur at studs, lintels and top and bottom
the requirements for cantilevered purlins or outrigger plates.
framing but it contains some errors.
4.1 LINTEL SUPPORT
3.5.2 BRANZ Build 142 ‘Constructing timber outriggers’
provides alternative tables adapted from Table 10.9 in 4.1.1 NZS 3604:2011 Table 8.19 gives lintel to trimmer
NZS 3604:2011 and clarifies the following: stud fixing.
∫∫ Table 10.10 fixings for purlins on the flat are suitable
for the cantilever distances given in 10.2.1.15.2(a). 4.2 SECURING LINTELS AGAINST UPLIFT
∫∫ For 10.2.1.15.2(b), use Table 10.9 for purlins on edge
when cantilevered, not Table 10.8(a). 4.2.1 Lintels supporting rafters or trusses may be
∫∫ For 10.2.1.15.3, use Figure 10.16(B), not Figure required to be secured against uplift based on wind zone,
10.16(A). loaded dimension and maximum span (NZS 3604:2011
∫∫ For 10.2.1.15.3(a), use Figure 10.16(B), not Figure Table 8.14). Fixings to resist uplift are given in Figure 15.
10.17. The bottom of both trimming studs must be fixed to a
concrete floor slab as shown in NZS 3604:2011 Figure
3.6 PURLINS AND TILE BATTENS 8.12 or with an alternative fixing capacity of 7.5 kN in
tension along the line of the trimming stud.
3.6.1 Purlins or tile battens span across and are fixed to
rafters or trusses. 4.3 TOP PLATES
3.6.2 Tile batten spacing is determined by tile size (400 4.3.1 Top plates transfer and distribute loads from
mm maximum spacing) while purlin spacings are based rafters and ceiling joists to wall studs.
on roof cladding span and rafter spacing. Graded timber
must be used for purlins, while battens can be ungraded. 4.3.2 Top plate fixings (NZS 3604:2011 Table 8.18) are
based on roof member spacing, wind zone, roof type and
3.6.3 NZS 3604:2011 Tables 10.10 and 10.11 give purlin loaded dimension of the wall. In addition, when a truss
sizes and fixings to rafters and trusses. Figure 10.20(B) lands on a top plate more than 150 mm from the face
gives fixings for purlins laid over sheet sarking or ceiling of a stud, fix the strengthener under the top plate as in
sheet lining material that is 20 mm maximum thick. Figure 16.
fold down
strap
strap
tensioners 45°
max.
brace rafters
wall framing
see Figure 9
blocking
rafters
45°
maximum
fix with 3/90 x 3.15 mm 4.5.2 Fix blocking to the top plate or spanning between
nails both sides joist, truss or rafter with 4/100 x 3.75 mm hand-driven
rafter nails, or 6/90 x 3.15 mm power-driven nails.
ridge board
4.6 CEILING DIAPHRAGM CONNECTIONS
rafter
Figure 11. Fixing detail of roof space bracing longer than 2 metres.
Figure 12. Fixing detail of roof space bracing less than 2 metres.
purlins
rafter
fixings must be a
minimum of 10 mm
from sheet edges
ceiling joist or
truss cord
50 mm
2/M12 bolts and minimum
100 mm minimum
50 x 50 x 3 mm 100 mm
washers, bolts 60 60 mm minimum minimum
mm minimum apart
rebate cut 60 mm
M12 bolts with 50 x 6 mm minimum
in post post 6 mm
50 x 50 x 3 mm strap
welded
washers where
75 mm bracket
bolts bear on
minimum timber
fixing capacity = 6.8 kN fixing capacities: capacity of 1 strap = 6.8 kN
-- 1 bracket = 12.2 kN capacity of 2 straps = 13.7 kN
-- 2 brackets = 25.5 kN
bottom plate floor joist or blocking Figure 16. Fixings for top plate strengthened with
a dwang (as required by NZS 3604:2011 clause
Figure 15. Lintel and trimming stud fixings to resist uplift. 8.7.1.1(c) and Figure 8.13).
stud
blocking
top plate
-- less than 100 bracing units (BUs) – 3.0 kN capacity connection in tension and compression along the plate
-- more than 100 BUs and walls to which ceiling diaphragms are attached – 6.0 kN capacity connection in
tension and compression along the plate
-- total bracing capacity of each wall less than 125 BUs and at least one external wall – 6.0 kN capacity connection
-- total bracing capacity of each wall less than 250 BUs and at least two external walls – 6.0 kN capacity connection
-- total bracing capacity of each wall more than 250 BUs and at least two external walls – 2.4 kN per 100 BUs
(a) In situ concrete slab edge (b) Concrete masonry header blocks at slab edge
90 x 45 mm
90 x 45 mm
cast-in M12 cranked anchor bottom plate cast-in M12 cranked anchor bolt bottom plate
bolt with 50 x 50 x 3 mm washer with 50 x 50 x 3 mm washer
DPC DPC
120 mm minimum
90 mm minimum bolt 50 mm minimum bolt embedment
50 mm minimum centre embedment in slab centre of bolt to in slab
line of bolts to outside outside face of header block
face of concrete header block
CONNECTIONS
(a) Bearer connection to ordinary concrete pile
5.0.1 Suspended timber floor structures must resist
downwards and uplift vertical loads and horizontal or 4 mm wire fixed with 2/3.5 mm
lateral loads. staples at both ends
5.3 WALL PLATES TO FOUNDATION WALLS Figure 20. Ordinary pile-to-bearer connections.
bearer
bearer
12.0 kN pile to
maximum height: bearer connections
-- timber pile 3.0 m 6.0 kN connections braced pile 125 mm
-- concrete pile 1.5 m square or 140 mm round
and minimum of 3 x 100 mm
minimum brace
H where H = brace
connection to
cleared ground braced pile
maximum 45°
200 mm minimum
300 mm maximum
90 mm minimum
both ends
bearer
brace
M12 bolt and
50 x 50 x 3 mm
washers
pile
Calls cost $1.99 per minute plus GST. Children please ask your parents first.