Zucchini Busbar: For Power Applications
Zucchini Busbar: For Power Applications
ZUCCHINI
BUSBAR
FOR POWER
APPLICATIONS
23-96 XCP-S. . . . . . . . . . . . . . . . . . . . . . . . 23
Catalogue XCP-HP . . . . . . . . . . . . . . . . . . . . . . . 51
Accessories . . . . . . . . . . . . . . . . . . . . 79
Tap-off boxes . . . . . . . . . . . . . . . . . . . 90
CATALOGUE XCP 3
XCP IP55
busbar trunking
Typical applications
■ Industry.
■ Riser end feed units.
■ Commercial and service sector buildings
(banks, hospital, data center, business
centres).
2
*The standard degree of protection is IP55. IP65 is available by request for transport of energy.
Safety
Fire resistance Maximum strength
In installations where there is a high risk of fire, the XCP The XCP range has been designed and manufactured for
busbar trunking system solution can provide technical heavy industrial environments.
advantages. Thanks to the low fire load of the busbar, the The busbar is self-supporting and the
safety of the building is much improved. degree of impact resistance of the casing
XCP has been fire resistance tested in accordance with which houses this line, is the maximum
IEC 60331-1. stated in IEC EN 60068-2-62: IK10.
Electromagnetic emission
The ferromagnetic structure of the casing and the
compactness of the bars significantly reduce the
electromagnetic field emitted. The magnetic induction
measured at 1 metre from the XCP busbar is much lower
than 3µT which represents the quality objective of several
countries.
Sprinkler proof
Upon request it is possible to accessorise XCP with a
sprinkler kit that makes the busbar system resistant to the
sprinkler test.
Flexibility
By using the outlet windows located on the straight elements, XCP provides high
flexibility, both when planning (electrical engineer) and when installing the system
(installer); they are also used for the unavoidable changes required by the electric
system to adapt to the various needs of the end user during the life of the plant.
The XCP range provides all the necessary components needed for the installation of
rising mains.
This is an excellent solution for all high-rise buildings; residential or commercial
blocks, hospitals and office blocks which have power distribution on every floor.
CATALOGUE XCP 5
*g=9,81m/s2 (gravitational acceleration)
Simplicity PRE-INSTALLED
MONOBLOC
PSZ software
To guarantee a fast and accurate service to its customers, Legrand has developed PSZ, a proprietary software for the
processing and realization of projects with busbar trunking.
This service supports the customer in detailed and complex projects.
PSZ transforms a graphic project into a list of materials, including mandatory accessories, to get an offer identical to the
final design and it is fully compatible with Autocad 2021 and Revit 2021 (and previous versions of both programs).
6
With PSZ* you can have a detailed list of the item codes that
you find in this catalogue.
Furthermore, the possibility to export the drawing to Autocad
or Revit**, allows you to enter the paths of the busbar directly
into the design of the building and to follow any design changes
quickly and professionally.
** Autodesk Revit is a building information modeling software for architects, landscape architects,
structural engineers, MEP engineers, designers and contractors. The software allows users to
design a building structure and its components in 3D, annotate the model with 2D drafting elements,
and access building information from the building model's database.
* For more information about the request and use of the Legrand PSZ software, please contact Legrand
CATALOGUE XCP 7
RANGE
features
Xtra-compact design
XCP is available with aluminium or copper conductors and is characterised
by a smart and extra-compact design.
The external dimensions do not change based on the number of conductors.
The length and height change with the rating, but are the same for all three
combinations of conductors (3 - 4 - 5 conductors) available.
Aluminium conductors
8
XCP-S and XCP-HP
2 product lines
The range of XCP busbars consists of two different product lines:
• XCP-S
• XCP-HP
While maintaining the same basic characteristics, such as the range of rated current, the
construction materials and the same amount of accessories available, XCP-S and XCP-HP have
different properties that make them able to satisfy all the demands of the world market.
RATED CURRENT 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A
RATED CURRENT 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A
* Triple bar
CATALOGUE XCP 9
XCP-S and XCP-HP
2 product lines
Energy Saving
The two busbar ranges, XCP-S and XCP-HP, also differ in the loss values due to the Joule effect.
XCP-HP has lower Joule losses compared to XCP-S and this feature means that in a relatively
short time it will be possible to recover the additional cost invested in the purchase of a low loss
busbar duct, compared to the cost of a standard loss busbar duct.
In the graph below you can see an indicative example of the possible economic savings in relation
to the loss values of the busbar duct.
Price (€)
XCP-HP (Cu)
Difference
Tot.cost (€)
XCP-S (Cu)
in initial
investment
Saving (€)
XCP-S XCP-HP
BEP (break
even point)
Pj losses
Difference
in losses
0 5 10 15 20 25 30 35 40 45
years
2 years
XCP-S XCP-HP 6 months
Note: The time required to reach the break even point changes depending on energy costs in the country in which the analysis is
carried out.
Total Ownership Costs = PURCHASE COST + OPERATING COST of the busbar
XCP can be connected to the resin busbar RCP ADAPTER ELEMENT (IP55/65 TO IP68)
thanks to an adapter element.
This solution allows XCP to be used in hybrid systems where
P
different degrees of protection are required.
RC
It is possible to transition from the inside to the outside of a
building by connecting the IP55 XCP busbar trunking with IP68
RCP resin busbar trunking using the adaptor element.
P
XC
10
RANGE
composition
XCP includes all the necessary components
to enable any path for the busbar run that
the project requires.
STRAIGHT ELEMENTS:
for transport and distribution (with tap-off
outlets) of high-power energy.
ADDITIONAL ELEMENTS:
able to meet any installation requirement (fire HORIZONTAL ELBOW WITH DOUBLE BAR VERTICAL ELBOW WITH DOUBLE BAR
barrier, phase inversion...)
ELBOWS:
able to meet any change of direction and plan
with standard or special solutions.
TAP-OFF BOXES:
for connecting and energising electric loads.
Available in plug-in and bolt-on versions.
CONNECTION INTERFACES PLASTIC TAP-OFF BOXES PLUG-IN TYPE
CONNECTION INTERFACES:
for connecting the busbar to the electric board or
transformer.
FIXING SUPPORTS:
for fixing the busbar to the structure of the
building, for horizontal and vertical installations
and special applications (seismic areas). STRAIGHT ELEMENTS WITH TAP OFF OUTLETS FOR DISTRIBUTION
IT IS POSSIBLE (ON REQUEST) TO HAVE XCP IN SPECIAL VERSIONS. BELOW YOU CAN SEE SOME EXAMPLES OF SPECIAL
VERSION CODES AVAILABLE.
Reference Version description Conductor versions
64280102P standard 4 conductors (3Ph + N + PE casing) 3 conductors + PE: for applications where neutral distribution is not required
64280102P-R5 4 conductors RAL painted on request 4 conductors + PE: with pariphase neutral
64240102P 5 conductors (3Ph + N + FE + PE casing) 4 conductors + PE: with double neutral with respect to the phase section for applications with
high values of third order harmonics (THD%)
64250102P double neutral 5 conductors + PE: 3 phases + Neutral pariphase + FE functional earth + PE
64280102P-3W 3 conductors (3Ph + PE casing)
64280102PF Class F insulation (155 °C) Versions of PE:
64280102P-RL PEN conductor PE1 with casing used as earth conductor
64280102P-R3 with aluminum extra-ground (reinforced PE) PE2: with additional earth in copper plate
64280102P-R4 with copper extra-ground (reinforced PE) PE3: with additional earth in aluminium plate
CATALOGUE XCP 11
PRODUCT
news
End feed unit for rising mains
New feed units are used at the start of the riser mains lines,
when the busbar must be placed against the wall and powered
using cables.
These new feed units allow you to install the product at a
minimum distance of 40 mm from the wall.
New monobloc
XCP is equipped with a new monobloc covered by a Legrand
patent. This new monobloc ensures a better connection of
the junction with less contact resistance.
The insulation part of the monobloc is made by termo-
set insulation material Class F (155°C) and for each
conductor there are two plates that assure the continuity
between each conductor. A system of Belleville washers
ensure the correct pressure during thermal expansion
of the conductors. A double head nut breaks when it
reaches the nominal torque (85 N•m). In the double/triple
configurations, the monobloc ensures the current balancing
on the same conductors.
DOUBLE HEAD NUT THAT BREAKS
AT NOMINAL TORQUE (85 N•m)
DURING 1st INSTALLATION
SmartBolts®
SmartBolts are available on request. These bolts are
equipped with a visual indication system that turns from
red to black when you reach the right tightening torque
(85 N•m). They are also useful after installation and during
checks and maintenance operations because they allow you
to see at a glance if a bolt has come loose or if it has lost
the right torque by turning back to red. SmartBolt
12
NEW FIBERGLASS
AND METAL
tap-off boxes
XCP distribution elements are equipped with new outlets suitable for the new range of dedicated
tap-off boxes.
The new tap-off boxes are available in two different construction materials:
• 25% fiberglass with rating up to 250 A, plug-in type (to be installed on outlets)
• with metal sheet case, with rating up to 630 A for plug-in type (to be installed on outlets)
and up to 1250 A for bolt-on type (to be installed on the junction)
They are universal and therefore can be used on both (XCP-S and XCP-HP) product lines.
Safety
Optimised dimensions
Reduced maintenance costs
Ready for MCB/MCCB circuit breakers
SAFETY SYSTEM
FOR HANDS
CATALOGUE XCP 13
Tap-off boxes for XCP are available in two different Tap-off boxes can be installed and removed when the
materials: fiberglass and metal sheet, both characterised busbar is energised and it can be used for DPX3 moulded
by a simple installation and fast connection thanks to the case circuit breakers.
new layout of hooks that offer safety and speed of assembly.
Fiberglass version:
Range from 32 A to 250 A
Optimised installation of Legrand circuit breakers (MCCB)
Optimised for P17 Tempra Pro CEE sockets
Ready for data center applications
Empty or with fuse carrier version available
Total insulation (no metallic parts from inside to outside)
Plug-in / Plug-out under live voltage
CONTENTS
CATALOGUE XCP 15
Selection of the busbar based on Temperature impact on the rating
the rated transformer data of the busbar trunking system
P In -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
In = P = In • 3 • Un Ik = In • Ik = Ik • Un
3 • Un Uk 1.38 1.34 1.31 1.28 1.25 1.21 1.18 1.15 1.11 1.07 1.04 1 0.96 0.92 0.88 0.84
kt thermal correction factor
Crossing busbars datasheet with previous chart, the proper busbar
trunking systems can be selected. First selection parameter for XCP-HP (Cu)
appropriate busbar is linked to transformer’s rated current In (lower Ambient temperature [°C]
than rated current of selected busbar). Second parameter to be
evaluated is short-circuit rating of busbar trunking system, which -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
usually must be higher than transformer’s peak short-circuit current Ik. 1.43 1.40 1.37 1.33 1.30 1.26 1.23 1.19 1.16 1.12 1.08 1.04 1 0.96 0.92 0.87
NOTE: previous consideration applies if just a single transformer kt thermal correction factor
is used for LV supply. For system with ring, meshed network or
with transformers connected in parallel, the short-circuit current
Ik increases (i.e. Ik double if two transformers in parallel).
Selection example:
As practical example, given a transformer
P = 1000 kVA
Uk = 6%
Un = 400 V
from previous calculation and table,
P 1000000
In = In = = 1443 A ;
3 • Un 3 • 400
In 1443
Ik = Ik = = 24,05 kA
Uk 6% • 1000
from here:
possible choice of XCP-S (50 Hz, Al, 4C) having In=1600A
and short-circuit rating Icw = 42 kA or XCP-HP (50 Hz, Al,
4C) having In=1600A and short-circuit rating Icw = 70 kA
To select other system trunking paths (not just the main units at the transformer output),
16 you need to consider and calculate the parameters on the following pages.
Joule effect losses in busbar
n Technical information
Losses due to the Joule effect are essentially caused Three-phase regime losses are:
by the electrical resistance of the busbar.
Lost energy is transformed into heat and contributes Pj = 3•Rt•Ib2•L
to the heating of the conduit of the environment. 1000
The calculation of power loss is a useful data for correct
sizing of the building air conditioning system. In one-phase regime:
Pj = 2•Rt•Ib2•L
1000
Where:
Ib = Utilisation current (A)
Rt = Phase resistance for unit of length of the busbar
trunking system, measured at thermal regime (mΩ/m)
L = Busbar length (m)
For accurate calculation, losses must be assessed trunk by trunk taking into account the transiting currents;
for example, in the case of the distribution of the loads represented in the figure one has:
L3
L2
L1
I1+I2+I3 I2+I3 I3
l1 l2 l3
L L L
17
Selection of the busbar trunking system based on voltage drop
n Technical information
If the line is particularly long (> 100 m), it will be necessary If the three-phase system and the power factor are not lower than
to check the value of the voltage drop. For systems with cosϕ = 0.7, the voltage loss may be calculated using the voltage drop
power factor (cosϕm) not lower than 0.8 the voltage coefficient shown in table 1
loss can be calculated using the following formulas:
k • Ib • L
∆v% = 2b • Vn • 100
The percentage voltage drop can be obtained from: The current distribution factor “b” depends on how the circuit is
fed and on the distribution of the electric loads along the busbar:
∆v% = ∆v • 100
Vr Table 1 - The distribution factor of the current “b”
Where Vr is the system rated voltage
Ib
In order to limit the voltage drop in case of very long busbar b=1 Supplies at one end and load Ib
trunking systems, it is possible to allow for a power supply at at the end of the line L
an intermediate position, rather than at the terminal point
Ib
b = 1/2 Supplies at one end and with
load evenly distributed L
Ib Ib
b = 1/4 Supplies at both ends and
with load evenly distributed L
LOADS LOADS
Ib
b = 1/4 Central supply with loads Ib Ib
Busbar trunking at both ends 2 L 2
system intermediate
power supply point Ib
b = 1/8 Central supply with load
distributed evenly
In case the load cannot be considered evenly distributed, the Ib = 1600A operating current
voltage drop may be determined more accurately using the b = 1/2 load evenly distributed 27.3 • 10-6 • 1600 • 100
relationships shown below k = 27.3 see technical data table
Dv% =
400
• 100 = 1.09%
For the distribution of three-phase loads, the voltage drop can (XCP 2000 A Al cosϕ = 0.85)
be calculated using the following formula, on the assumption cosϕ = 0.85
(generally verified) that the section of the busbar trunking system
L = 100 m line length
is consistent:
Vn = 400 V operating voltage
∆v = √3 [Rt (I1L1cosϕ1 + I2L2 cosϕ2 + I3L3 cosϕ3)
+ x (I1L1sinϕ1 + I2L2 sinϕ2 + I3L3 sinϕ3)] Legend:
Ib = the current that supplies the busbar [A]
In general terms this becomes: Vn = the voltage power supply of the busbar [V]
L = the length of the busbar [m]
∆v = √3(Rt•∑Ii•Li• cosϕmi + x•∑Ii•Li• sinϕmi) Dv% = the voltage drop percentage
1.000 b = the distribution factor of the current
k = corresponding voltage drop factor
a cosϕ [V/m/A] (see technical data table)
cosϕ m = Average power factor of the loads
x = phase reactance by unit of length of the busbar (mΩ/m)
Rt = phase resistance by unit of length of the busbar (mΩ/m)
cosϕ mi = i-th load average power factor
li = i-th load current (A)
Li = distance of the i-th load from the origin of the busbar trunking system
18
Short circuit withstand
n Technical information
The IEC 64-8 standard indicates that, for the protection of
the circuits of the system, it is necessary to allow for devices
aimed at interrupting short circuit currents before these
become dangerous due to the thermal and mechanical
effects generated in the conductors and the connections.
In order to size the electric system and the protection devices
correctly, it is necessary to know the value of the estimated short
circuit current at the point where this is to be created.
This value enables in fact to correctly select protection devices
based on their own tripping and closing powers, and to check
the resistance to electro-dynamic stress of the busbar supports
installed in control panels, and/or of the busbar trunking systems.
The intensity of the estimated short circuit current essentially Symmetric component
depends on the following factors:
• Power of the cabin transformer, meaning that the higher is the
power, the higher is the current;
• length of the line upstream
The formula for the calculation of the symmetric component is: 2 Icc
Icc = E
In
ZE+ZL Time (t)
Where:
• E is the phase voltage;
• ZE is the secondary equivalent impedance
of the TRANSFORMER measured between
the phase and the neutral;
• ZL is the impedance of the phase conductor only
3 E
ZE IccFF =
2ZE + 2ZL
Icc3~ IccFN
ZE
ZE E
IccFN =
ZE + 2ZL
E
Icc3~ =
ZE + ZL
IccFF
E = phase voltage
19
Short circuit withstand (continued)
TRANSFORMER reactance
XE = transformer secondary equivalent reactance (m)
XE = ZE2 – RE2
Estimated short circuit current lcc = symmetric component of the short circuit current (kA)
Icc = Vcc
3 • Zcc
XCP-S 4C (AL)
Rated current In [A] 630 800 1000 1250 1600 2000 2500 3200 4000 5000
XCP-S 4C (CU)
Rated current In [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Rated short-time current (1 s) Icw [kA]rms 25 36 42 42 50 65 80 100 120 150
Peak current Ipk [kA] 53 78 88 88 105 143 176 220 264 330
Rated short-time current of the Icw [kA]rms 15 22 25 25 30 39 48 60 72 90
neutral bar (1 s)
Peak current of the neutral bar Ipk [kA] 30 46 53 53 63 82 101 132 158 198
* Icw value at 0,5 s.
XCP-HP 4C (AL)
Rated current In [A] 630 800 1000 1250 1600 2000 2500 3200 4000 5000
Rated short-time current (1 s) Icw [kA]rms 36 36 50 70 70 85 120 120 150 150
Peak current Ipk [kA] 76 76 105 154 154 187 264 264 330 330
Rated short-time current of the Icw [kA]rms 22 22 30 42 42 51 72 72 90 90
neutral bar (1 s)
Peak current of the neutral bar Ipk [kA] 45 45 63 88 88 112 158 158 198 198
XCP-HP 4C (CU)
Rated current In [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Rated short-time current (1 s) Icw [kA]rms 36 50 70 70 85 120 120 150 150 150
Peak current Ipk [kA] 76 105 154 154 187 264 264 330 330 330
Rated short-time current of the Icw [kA]rms 22 30 42 42 51 72 72 90 90 90
neutral bar (1 s)
Peak current of the neutral bar Ipk [kA] 45 63 88 88 112 158 158 198 198 198
20
Harmonics
The currents absorbed, although at regular intervals Rated 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
and with frequencies equal to that of the rated current [A]
voltage, sometime have a non-sinusoidal wave form, XCP busbar to be used:
which has the following negative effects:
THD ≤ 15% 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
• worsening of the power factor;
• heating of the neutral; 15% < THD ≤ 33% 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 -
• additional losses in electric machinery
(transformers and motors); 6300
THD > 33% 1000 1250 1600 2000 2500 3200 4000 5000 - -
• instable operation of the protection elements (thermal
magnetic and earth leakage circuit breakers)
Measurement
of harmonic
distortion carried
out with a network
analyser Fundamental (50 Hz) Fifth harmonic (250 Hz) A solution to guarantee
Third harmonic (150 Hz) Resulting wave shape
protection against overloads
due to the presence of
harmonics, is the choice
100%
Distortion of the individual harmonics of XCP busbars equipped
with double neutral
( )Uh
( )( )23 11
H 2 2 2
THD% = 100 = 100 + = 25.5 %
h=2 U1 100 100
23%
11%
50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 Hz
21
Degrees of protection Degrees of protection
IP: degree of protection provided against intrusion IK: degree of protection of equipment against mechanical impact
n IP n IK
The protection enclosures are classified (IEC 60529) Standard IEC 62262 defines an IK code that characterises the
according to their degree of protection against aptitude of equipment to resist mechanical impacts on all sides
weather conditions and external agents. The degree of
protection is indicated by two digits (protection against
solid bodies and liquids) following the symbol IP
To increase the ease of choice of the most suitable busbar,
in according to installation requirements, below there is a
summary of their performance, based on the IP degree
of protection according to the IEC 60529 standard
1st digit IP
Impact
Protection against penetration of solid bodies energy
IK Test
0
(In Joules)
s52/01/95F
No protection
IK 00 0
1
Ø 50 mm
Protection against solid bodies larger
s52/02/95F
than 50 mm (e.g.: accidental contact)
0.2 kg
Ø 12,5 mm 0.15
2
IK 01 75 mm
Protection against solid bodies larger
s52/03/95F
than 12 mm (e.g.: finger)
0.2 kg
s52/04/95F
Ø 2,5 mm
0.2 kg
100 mm 0.2
4
s52/05/95F
Ø 1 mm Protection against solid bodies 0.35
IK 03 175 mm
larger than 1 mm
5
s52/06/95F
0.2 kg
Protection against dust 0.5
IK 04 250 mm
2nd digit IP
0.5 kg
Protection against penetration of liquids 1
IK 06 200 mm
0 No protection
0.5 kg
1
IK 07 400 mm
2
Protection against vertically-falling
s52/08/95F drops of water (condensation)
2
15°
1.7 kg
s52/09/95F
Protection against drops of water IK 08 295 mm 5
falling up to 15° from the vertical
3
°
60 Protection against drops of water 5 kg
s52/10/95F up to 60° from the vertical IK 09 200 mm
10
s52/11/95F
4 Protection against sprays of water
from all directions
IK 10
5 kg
20
5
400 mm
Protection against jets of water
s52/12/95F
from all directions
s52/13/95F
6 Protection against jets of water
(similar force to heavy seas)
s52/14/95F
mini
under pressure
22
XCP-S
BUSBAR FROM
630 TO 6300 A
The light and compact XCP-S is an extra compact and light busbar
trunking system. It is the range used for
power solutions, transport and distribution of high power,
and is also highly valued in rising mains.
optimised for standard The applications include all industrial,
commercial and service sector buildings
applications (factories, banks, trade and business centres,
hospitals, data centres, etc.)
23
Xtra Compact (XCP-S)
straight elements
n Dimensions
Straight elements
Standard 3000 mm
H
64280100P
XCP-S Line: A
Reference standard: IEC 61439-6. Reference temperature: 35 °C.
Protection degree: IP55. Thickness of metal sheet: 1.5 mm.
N° of conductors: 3, 4 or 5. Painted: RAL 7035. Halogen Free.
The insulation between bars is ensured by a double sheet made
with polyester film class B(130°C), class F (155°C) thermal
resistance available on request. All plastic components have a V1 Dimension H changes with the ratings and
self-extinguishing degree (as per UL94); they are fire retardant is specified in the technical information
and comply with the glow-wire test according to standards.
Item Straight elements for transport
Al Cu In (A) A (mm)
64280100P - 630 MIN AND MAX DIMENSIONS OF SINGLE AND DOUBLE BAR
64280101P 67280100P 800 Aluminium (AI) 630A – 5000A
64280102P 67280101P 1000 Copper (Cu) 800A – 6300A
64280104P 67280103P 1250 3000 (L) min/MAX [mm] 500/3000
64280106P 67280105P 1600
64280107P 67280106P 2000 Straight elements are available on reques only for transport of energy:
64390104P 67390104P 2500 Al: 5000A
64390106P 67390105P 3200 Cu: 6300A
64390107P 67390106P 4000
64390108P 67390108P 5000
- 67390109P 6300
64280110P - 630 Notes
64280111P 67280110P 800 The product versions in this
64280112P 67280111P 1000 catalogue will be simplified as
64280114P 67280113P 1250 shown opposite, highlighting Neutral
64280116P 67280115P 1600 the part with the monobloc
64280117P 67280116P 2000 500-1000 installed in red and the
neutral side in blue.
64390114P 67390114P 2500 In this catalogue, the
64390116P 67390115P 3200 measurements shown refer to Monobloc
64390117P 67390116P 4000 the element centre distance
64390118P 67390118P 5000
- 67390119P 6300
64280170P - 630
64280171P 67280170P 800 The range is also available in different versions on request:
64280172P 67280171P 1000
(5 conductors with dedicated PE conductor, double neutral
and more others...)
64280174P 67280173P 1250
64280176P 67280175P 1600
64280177P 67280176P 2000 1001-1500
64390174P 67390174P 2500
64390176P 67390175P 3200
64390177P 67390176P 4000
64390178P 67390178P 5000
- 67390179P 6300
64280120P - 630 Item Straight elements for transport
64280121P 67280120P 800 Al Cu In (A) A (mm)
64280122P 67280121P 1000 64280150P - 630
64280124P 67280123P 1250 64280151P 67280150P 800
64280126P 67280125P 1600 64280152P 67280151P 1000
64280127P 67280126P 2000 1501-2000 64280154P 67280153P 1250
64390124P 67390124P 2500 64280156P 67280155P 1600
64390126P 67390125P 3200 64280157P 67280156P 2000 2501-2999
64390127P 67390126P 4000 64390154P 67390154P 2500
64390128P 67390128P 5000 64390156P 67390155P 3200
- 67390129P 6300 64390157P 67390156P 4000
64280180P - 630 64390158P 67390158P 5000
64280181P 67280180P 800 - 67390159P 6300
64280182P 67280181P 1000
64280184P 67280183P 1250
64280186P 67280185P 1600
64280187P 67280186P 2000 2001-2500
64390184P 67390184P 2500
64390186P 67390185P 3200
64390187P 67390186P 4000
64390188P 67390188P 5000
- 67390189P 6300
24
Xtra Compact (XCP-S)
straight elements
n Dimensions
Straight elements for distribution
- Straight elements for plug-in type tap-off boxes
- Standard 3000 mm
- Tap-off outlets on both sides
64280130P These straight elements enable the application of plug-in boxes on
dedicated outlets
Available in lengths from 1 to 3 meters, these elements have
Item Straight elements for distribution respectively 1, 2 and 3 outlets at preset distances with centre
distances of 850 mm on both sides.
Al Cu In (A) N° outlets A (mm) (*) The exception to these are 630-800 A elements with aluminium
*64280130P - 630 conductors (Al) and 800-1000 A elements with copper conductors
(Cu), where distributions are only available on the top side (in standard
*64280131P *67280130P 800 3+3 ** 3000 execution) for example “3+0”
64280132P *67280131P 1000 On request, the length of the elements and the number and position
64280134P 67280133P 1250 of distribution outlets may be different from the standards measures.
64280136P 67280135P 1600
64280137P 67280136P 2000
64390134P 67390134P 2500
64390136P 67390135P 3200 d
64390137P 67390136P 4000
H
64390138P 67390138P 5000
- 67390139P 6300 c
*64280970P - 630 A
*64280971P *67280970P 800
64280972P *67280971P 1000
64280974P 67280973P 1250 b
64280976P 67280975P 1600
64280977P 67280976P 2000 1+1 1001-1500
64390974P 67390974P 2500 a Dimension H changes with the ratings and
64390976P 67390975P 3200 it is specified in the technical information
64390977P 67390976P 4000
64390978P 67390978P 5000 at request: outlets in special
position 1+1 only combination
- 67390979P 6300
*64280920P - 630
*64280921P *67280920P 800
64280922P *67280921P 1000
64280924P 67280923P 1250
64280926P 67280925P 1600 MIN AND MAX DIMENSIONS OF SINGLE AND DOUBLE BAR
64280927P 67280926P 2000 2+2 ** 1501-2000
Aluminium (Al) 630A – 5000A
64390924P 67390924P 2500
64390926P 67390925P 3200 Copper (Cu) 800A – 6300A
64390927P 67390926P 4000 (L) min/MAX [mm] 1001 ***/3000
64390928P 67390928P 5000
- 67390929P 6300 (***) Lengths from 1001 mm to 1250 mm can only be installed with
type 1 and 3 plug-in boxes.
*64280980P - 630 From 1250 mm to 3000 mm it is possible to install all types of plug-in boxes.
*64280981P *67280980P 800 Compatible boxes are listed in dedicated chapter. See page 96.
64280982P *67280981P 1000
64280984P 67280983P 1250 (**) on request it is possible to have other combinations of outlets:
64280986P 67280985P 1600 length: 1501÷2000 - outlets: (1+1)
64280987P 67280986P 2000 2+2 ** 2001-2500 length: 2001÷2500 - outlets: (1+1)
64390984P 67390984P 2500 length: 2501÷2999 - outlets: (1+1) and (2+2)
64390986P 67390985P 3200 length: 3000 - outlets: (1+1) and (2+2)
64390987P Possibility to have outlets in special position
67390986P 4000
64390988P 67390988P 5000
For a correct evaluation of the number of outlets, take into account
- 67390989P 6300 the length of the element and the size of the boxes to be installed.
*64280950P - 630
*64280951P *67280950P 800
64280952P *67280951P 1000
64280954P 67280953P 1250
64280956P 67280955P 1600
64280957P 67280956P 2000 3+3 ** 2501-2999
64390954P 67390954P 2500
64390956P 67390955P 3200
64390957P 67390956P 4000
64390958P 67390958P 5000
- 67390959P 6300
25
Xtra Compact (XCP-S)
straight elements
n Dimensions
Fire barrier elements EI120 (EN 1366-3)
200
673IFB01
Fire barrier
H + 82
H
Item Fire barrier elements S120 EI120 EI120
(EN 1366-3)
When the busbar trunking system crosses Fire barrier sizes
fire resistant walls or ceilings, it must be Dimension H changes
fitted with appropriate fire barriers. with the rating; it
The fire barrier is 630 mm (Al) and is specified in the
technical information
1000 mm (Cu) long and must always be
positioned in the middle of the fire resistant
wall or ceiling crossed by the busbar.
After crossing fire resistant walls or
ceilings, any cavity must be sealed with
material meeting current regulations for the
required building fire resistance class.
Al Cu In (A) Type For some ratings it is necessary to have an internal fire barrier
673IFB01 - 630 fitted at the factory following the guidelines on the table.
It is therefore necessary to indicate at the order stage
673IFB01 673IFB01 800 which elements will cross fire resistant walls or ceilings
* 673IFB01 1000
1250 – 2000 internal
* * fire barrier
673IFB01 673IFB01 2500 – 4000 Figure 1 minimum straight dimensions
* 673IFB01 5000
No fire barrier No fire barrier
- * 6300
672EFB01 - 630 Al: 630 mm
≥ 200 Cu:1000 mm ≥ 200
672EFB01 672EFB51 800 – 1000
672EFB02 672EFB51 1250 ✕ ✕
672EFB03 672EFB52 1600
672EFB04 672EFB53 2000 external
673EFB02 673EFB51 2500 fire barrier
673EFB03 673EFB52 3200
673EFB04 673EFB53 4000 Figure 2 minimum dimensions in an elbow
673EFB05 673EFB54 5000 No fire barrier
- 673EFB55 6300 Al: 630 mm
≥ 200 Cu:1000 mm
*There are no air gaps inside these busbar therefore there is no need to * INTERNAL BARRIER IN FEW RATINGS IS NOT
add internal fire barriers. ✕ REQUIRED
26
Xtra Compact (XCP-S)
straight elements
n Dimensions
Expansion element
H
1.5
64280200P
170
170 m
m
Example:
Straight section length 170 m = no. 4 expansion elements,
one every 34 m
35 m 35 m
70 m
Example:
Section length 70 m. When the section is not straight,
no expansion element is necessary
27
Xtra Compact (XCP-S)
straight elements
n Dimensions
Phase balancing 1200 mm
0
120
64287100P
H
64287120P
Dimension H changes
with the rating; it
is specified in the
technical information.
64287140P
1/3L 2/3L
Item Phase balancing
N N N N
Al Cu In (A) 1 3 2 1
2 1 3 2
(fig. 1) 3 2 1 3
64287100P - 630 Straight elements with phase
64287101P 67287100P 800 balancing are used to reduce and Electric
N
diagram: 2 elements
1
offer all the possible
reciprocal positions among2the phases along the line.
balance mutual phase reactance and 1
2 3
64287102P 67287101P 1000 impedance in case of long lines. 3 N
1/6L 1/2L 5/6L
64287104P 67287103P 1250 In particular long sections N 3
H
64287121P 67287120P 800 completely reverse the positions of the
phases and the neutral. It is normally
64287122P 67287121P 1000 used in the connection between the
N 1
1 2
64287124P 67287123P 1250 transformer and the electric board, 2 3
or in the connection between electric 3 N
64287126P 67287125P 1600
boards, when the starting sequence
64287127P 67287126P 2000 is different to the arrival sequence N 3
64397124P 67397124P 2500 1 2
2 1
64397126P 67397125P 3200 3 N
64397127P 67397126P 4000 Electrical diagram
28
Xtra Compact (XCP-S)
feed unit
n Dimensions
Feed unit
B
C
10
0*
10
0*
10
0*
200
300
A
64281106P
The feed units are used at the end of the lines, when the busbar must be
powered using cables.
Right-hand feed units do not come with a Monobloc but left-hand feed
units come with a pre-fitted Monobloc.
H
Dimension H changes For dimensions of holes for
They are available with non-standard execution, on request. with the rating; it connections, see the specific
End feed units for single bar busbars are supplied with an aluminium blind is specified in the pages with coverplate drilling
technical information details (page 40-41).
back closing plate. For double bar busbar trunking systems the plates are 2.
Both versions are fitted with 2 extra side steel flanges and 2 inspection steel
flanges (dark grey colour). * 120 mm for 6300 A (Cu) and 5000 A (Al)
The cable is connected directly to the busbars using bolts.
For more information on board/busbar connection see the tables
(Dimensions For The Box). Rear cable input
To feed the power supply cable through the back power supply flanges it Aluminium gland plate(s) for cable entry 170 x 410 mm
will be necessary to drill a hole in case of single bar and two holes in case
of double bar. The size of the holes is 170 x 410 mm. Single bar: 1 plate
Double bar: 2 plates
29
Xtra Compact (XCP-S)
rising mains feed unit
B
C
10
0*
10
0*
10
200
0*
300
A
67281133P
The rising mains feed units are used at the departure of the riser mains lines,
when the busbar must be placed close to the wall and powered using cables.
They allow the busbar to be installed 40 mm away from the wall.
H
Right-hand feed units do not come with a Monobloc but left-hand feed units Dimension H changes For dimensions of holes
with the rating; it for connections, see
come with a pre-fitted Monobloc. is specified in the the specific pages with
They are available with non-standard execution, on request. technical information coverplate drilling details
End feed units for single bar busbars are supplied with an aluminium blind (40-41).
back closing plate. For double bar busbar trunking systems the plates are 2.
Both versions are fitted with 2 extra side steel flanges and 2 inspection steel * 120 mm for 6300 A (Cu) and 5000 A (Al)
flanges (dark grey colour). The cable is connected directly to the busbars
using bolts.
For more information on board/busbar connection see the tables below Rear cable input
(Dimensions For The Box).
To feed the power supply cable through the back power supply flanges Aluminium gland plate(s) for cable entry 170 x 410 mm
it will be necessary to drill a hole in case of single bar and two holes Single bar: 1 plate
in case of double bar. The size of the holes is 170 x 410 mm. Double bar: 2 plates
30
Xtra Compact (XCP-S)
elbows
n Dimensions
Horizontal elbow
In order to define the type of horizontal elbow required, consider
to place the element “edgewise” (conductors perpendicular
to the ground). In this configuration “horizontal” elbows
enable a path variation which is parallel to the ground.
64280306P When the neutral busbar conductor faces the outside of the
elbow, there will be a Right horizontal elbow (type 1)
Contrariwise, with the neutral busbar conductor facing the inside
Item Horizontal elbow of the elbow there will be a Left horizontal elbow (type 2)
Al Cu In (A) Type Type
Type 1 Type 2
64280300P - 630
64280301P 67280300P 800 B
A B
64280302P 67280301P 1000 A
31
Xtra Compact (XCP-S)
elbows
n Dimensions
Vertical elbow
In order to define the type of vertical elbow, it is necessary to
still place the element "edgewise" (conductors perpendicular
to the ground), with the section with Monobloc facing
the observer and the section without facing up.
In this configuration, vertical “elbows” enable an up or down facing
variation. If the neutral is on the left side, there will be a left vertical
elbow (Type 1).
If, on the other side, it is on the right side, there will be a right
vertical elbow (Type 2)
A B
A
Item Vertical elbow
Al Cu In (A) Type Type
B
64280400P - 630
64280401P 67280400P 800 MIN AND MAX DIMENSIONS
64280402P 67280401P 1000
Single bar min/MAX
64280404P 67280403P 1250
B
A 250/1299*
64280406P 67280405P 1600
64280407P 67280406P 2000 B 250/1299*
Standard
64390404P 67390404P 2500 Double bar min/MAX
B 485/1199*
64280421P 67280420P 800
Dimension H changes with the rating;
64280422P 67280421P 1000 it is specified in the technical information
64280424P 67280423P 1250 The dimensions are referred to the standard elements.
Single bar (A+B) : 300+300 mm
64280426P 67280425P 1600 Double bar (A+B) : 450+450 mm
64280427P 67280426P 2000 Special Triple bar (A+B) : 500+500 mm
length
64390424P 67390424P 2500 Non-standard elements “Special” (with measurements that are
64390426P 67390425P 3200 different from those show in the figure) are referred to the
Min and Max dimensions specified in the table
64390427P 67390426P 4000
* For all the non standard vertical elbows (special), it is possible
64390428P 67390428P 5000 to have only one of the two sides in size exceeding 600 mm
- 67390429P 6300 For example, when ordering a vertical elbow with size
A=1000 mm, the B size will have to be ≤ 600 mm
64280410P - 630
64280411P 67280410P 800 How to measure vertical angles
64280412P 67280411P 1000
B
1600
64280417P 67280416P 2000 Standard
64390414P 67390414P 2500
64390416P 67390415P 3200
64390417P 67390416P 4000
A
64390418P 67390418P 5000 A
H
- 67390419P 6300
H
64280430P - 630
64280431P 67280430P
B
800
Triple bar
64280432P 67280431P 1000
Left Type 1
64280434P 67280433P 1250
64280436P 67280435P 1600
64280437P 67280436P 2000 Special
length To calculate the measurements
64390434P 67390434P 2500 of vertical elbows, consider
the center-to-center distance
64390436P 67390435P 3200 A as shown in the drawings.
H
32
Xtra Compact (XCP-S)
elbows
n Dimensions
Double horizontal elbow
Double horizontal elbows are the union of two horizontal elbows; in
order to define the type, it is enough to observe them starting from
64280346P
the Monobloc; if the first elbow met is left, we will have a double
horizontal elbow left + right (Type 2). Contrariwise, if the first elbow met
is right, we will have a double horizontal elbow right + left (Type 1)
B
H
A 250/1299*
64280340P - 630 B 50/599*
64280341P 67280340P 800 C 250/1299*
64280342P 67280341P 1000 The dimensions are referred to the Triple bar min/MAX
standard elements. A 250/999*
64280344P 67280343P 1250 B 50/599*
Single/double/triple bar (A+B+C):
64280346P 67280345P 1600 300+300+300 mm C 250/999*
64280347P 67280346P 2000 Dimension H changes with
the rating; it is specified in
64390344P 67390344P 2500 the technical information
Right Type 1
64390346P 67390345P 3200
Type 1 Type 2
64390347P 67390346P 4000
C
64390348P 67390348P 5000
A B C
- 67390349P 6300
B
64280350P - 630 A
64280351P 67280350P 800
64280352P 67280351P 1000
64280354P 67280353P 1250
Double vertical elbow
64280356P 67280355P 1600 Double vertical elbows are the union of two vertical elbows; in order
64280357P 67280356P 2000 to define the type, it is enough to observe them starting from the
64390354P 67390354P 2500 Monobloc; if the first elbow met is left, we will have a double vertical
Left Type 2 elbow left + right (Type 1). Contrariwise, if the first elbow met is
64390356P 67390355P 3200 right, we will have a double vertical elbow right + left (Type 2)
64390357P 67390356P 4000
64390358P 67390358P 5000 MIN AND MAX DIMENSIONS
Single bar min/MAX
- 67390359P 6300 A 250/1299*
B 50/599*
Double vertical elbow
C 250/1299*
Al Cu In (A) Type C
Double bar min/MAX
64280440P - 630 A 340/1449*
B 50/899*
64280441P 67280440P 800
C 340/1449*
64280442P 67280441P 1000 Triple bar min/MAX
64280444P 67280443P 1250 A 485/1199*
B 50/999*
B
33
Xtra Compact (XCP-S)
elbows
n Dimensions
Double elbow horizontal + vertical
Double elbows horizontal + vertical are the union of a horizontal
and a vertical elbow, placed in succession starting from the side
with Monobloc.
Depending on the type of elbows, the double horizontal
+ vertical elbow may be of four different types:
• Double elbow Horizontal RH + Vertical RH (Type 1)
• Double elbow Horizontal RH + Vertical LH (Type 2)
• Double elbow Horizontal LH + Vertical RH (Type 3)
• Double elbow Horizontal LH + Vertical LH (Type 4)
64280606P
B
DIMENSIONS OF SINGLE
64390606P 67390605P 3200
Type 1 Single bar min/MAX
64390607P 67390606P 4000
A 250/1299*
64390608P 67390608P 5000
B 150/599*
- 67390609P 6300
C 250/1299*
64280610P - 630
Double bar min/MAX
64280611P 67280610P 800
H
A 250/1299*
64280612P 67280611P 1000
C
B 235/899*
64280614P 67280613P 1250
C 340/1449*
64280616P 67280615P 1600 Triple bar min/MAX
64280617P 67280616P 2000 A 250/999*
The dimensions are referred to the
64390614P 67390614P 2500 standard elements B 380/799*
64390616P 67390615P 3200 Single bar (A+B+C): 300+300+300 mm
Type 2 Double bar (A+B+C): 300+450+450 mm C 485/999*
64390617P 67390616P 4000 Triple bar (A+B+C): 300+500+500 mm Dimension H changes with
64390618P 67390618P 5000 the rating; it is specified in
the technical information
- 67390619P 6300
64280620P - 630
64280621P 67280620P 800
64280622P 67280621P 1000
64280624P 67280623P 1250 Non-standard elements “Special” (with measurements that are different
from those show in the figure) are referred to the Min and Max
64280626P 67280625P 1600 dimensions specified in the table.
64280627P 67280626P 2000
64390624P 67390624P 2500 * Warning: for safety reasons in production and also to help in
64390626P 67390625P 3200 the installation, if one dimension is pulled close to the maximum
length (i.e. A=1100 mm) then the other two dimensions should be
64390627P 67390626P 4000 Type 3 kept as close as possible to their standard lengths (i.e. B=300 mm,
64390628P 67390628P 5000 C=310 mm).
- 67390629P 6300
64280630P - 630 Note:
RH - Right
64280631P 67280630P 800 LH - Left
64280632P 67280631P 1000
64280634P 67280633P 1250
64280636P 67280635P 1600
64280637P 67280636P 2000
64390634P 67390634P 2500
64390636P 67390635P 3200
64390637P 67390636P 4000 Type 4
64390638P 67390638P 5000
- 67390639P 6300
34
Xtra Compact (XCP-S)
elbows
n Dimensions
Double elbow vertical + horizontal
Double elbows vertical + horizontal are the union of a vertical
and a horizontal elbow, placed in succession starting from the
side with Monobloc
Depending on the type of elbows, the double vertical + horizontal
elbow may be of four different types:
• Double elbow vertical RH + horizontal RH (Type 1)
• Double elbow vertical RH + horizontal LH (Type 2)
• Double elbow vertical LH + horizontal RH (Type 3)
• Double elbow vertical LH + horizontal LH (Type 4)
64280506P
Type 1 Type 2 Type 3 Type 4
A A
Item Double elbow vertical + horizontal B B C
C
B
Al Cu In (A) Type A B
A
64280500P - 630
C
64280501P 67280500P 800 C
64280502P 67280501P 1000
64280504P 67280503P 1250
64280506P 67280505P 1600 A MIN AND MAX DIMENSIONS
64280507P 67280506P 2000 Single bar min/MAX
64390504P 67390504P 2500 A 250/1299*
Type 1
H
35
Xtra Compact (XCP-S)
T elements
n Dimensions
Horizontal T element
T-elements can be used to split the line in two branches,
adding together the effect of two diverging elbows
There are four types of horizontal “T” elements, as shown below
64280706P B B C C
A C A
C B
Item Horizontal T element B
A A
Al Cu In (A) Type
64280700P - 630
64280701P 67280700P 800
B MIN AND MAX DIMENSIONS
64280702P 67280701P 1000
Single bar min/MAX
64280704P 67280703P 1250
A 600/1449*
64280706P 67280705P 1600 A
B 600/1449*
64280707P 67280706P 2000
C 600/1449*
64390704P 67390704P 2500 H
Double bar min/MAX
64390706P 67390705P 3200
Type 1 A 600/1449*
64390707P 67390706P 4000
C
B 600/1449*
64390708P 67390708P 5000
C 600/1449*
- 67390709P 6300
Triple bar min/MAX
64280710P - 630
The dimensions are referred A 600/1449*
64280711P 67280710P 800 to the standard elements. B 600/1449*
64280712P 67280711P 1000 Single/double/triple bar (A+B+C): C 600/1449*
600+600+600 mm
64280714P 67280713P 1250
Dimension H changes with the rating; it
64280716P 67280715P 1600 is specified in the technical information
64280717P 67280716P 2000
64390714P 67390714P 2500 Non-standard elements “Special” (with measurements that are different
64390716P 67390715P 3200 from those show in the figure ) are referred to the Min and Max
Type 2 dimensions specified in the table
64390717P 67390716P 4000
64390718P 67390718P 5000 * For all the non standard Horizontal T elements (special), it is possible
to have only one of the three sides in size exceeding 600 mm.
- 67390719P 6300 For example, when ordering a T horizontal element with size
64280720P - 630 A=650 mm, the B and C size will have to be ≤ 600 mm
64280721P 67280720P 800
64280722P 67280721P 1000
Note:
64280724P 67280723P 1250 Only in special cases, where is not possible to use the standard
64280726P 67280725P 1600 element, is possible to have only one of three arms with minimum
dimension of 300mm.
64280727P 67280726P 2000 For more informations please contact Legrand
64390724P 67390724P 2500
64390726P 67390725P 3200 Type 3
64390727P 67390726P 4000
64390728P 67390728P 5000
- 67390729P 6300
64280730P - 630
64280731P 67280730P 800
64280732P 67280731P 1000
64280734P 67280733P 1250
64280736P 67280735P 1600
64280737P 67280736P 2000
64390734P 67390734P 2500
64390736P 67390735P 3200 Type 4
64390737P 67390736P 4000
64390738P 67390738P 5000
- 67390739P 6300
36
Xtra Compact (XCP-S)
T elements
n Dimensions
Vertical T element
T-elements can be used to split the line in two branches,
adding together the effect of two diverging elbows
There are four types of verticals “T” elements, as shown below
B
B C
64280806P A C
A
C C B
B
A
A
Item Vertical t element
Al Cu In (A) Type
C 450/1449*
64390807P 67390806P 4000
Triple bar min/MAX
64390808P 67390808P 5000
A 485/1449*
- 67390809P 6300
B 485/1449*
64280810P - 630
C 485/1449*
64280811P 67280810P 800
Dimension H changes with the rating; it
64280812P 67280811P 1000 is specified in the technical information
64280814P 67280813P 1250
64280816P 67280815P 1600
64280817P 67280816P 2000 The dimensions are referred to the standard elements
Single bar (A+B+C): 300+300+300 mm
64390814P 67390814P 2500 Double bar (A+B+C): 600+600+600 mm
64390816P 67390815P 3200 Triple bar (A+B+C): 600+600+600 mm
Type 2
64390817P 67390816P 4000
64390818P 67390818P 5000 Non-standard elements “Special” (with measurements that are different
from those show in the figure) are referred to the Min and Max
- 67390819P 6300 dimensions specified in the table
64280820P - 630
64280821P 67280820P 800 * For all the non standard Vertical T elements (special), it is possible
64280822P 67280821P 1000 to have only one of the three sides in size exceeding 600 mm.
64280824P 67280823P 1250 For example, when ordering a T vertical element with size
A=650 mm, the B and C size will have to be ≤600 mm
64280826P 67280825P 1600
64280827P 67280826P 2000
64390824P 67390824P 2500
64390826P 67390825P 3200
64390827P 67390826P 4000 Type 3
64390828P 67390828P 5000
- 67390829P 6300
64280830P - 630
64280831P 67280830P 800
64280832P 67280831P 1000
64280834P 67280833P 1250
64280836P 67280835P 1600
64280837P 67280836P 2000
64390834P 67390834P 2500
64390836P 67390835P 3200
64390837P 67390836P 4000 Type 4
64390838P 67390838P 5000
- 67390839P 6300
37
Xtra Compact (XCP-S)
connection interfaces with exit bars
n Dimensions
Connection interfaces with exit bars
Standard connection interfaces are used at the end of the
lines to connect the busbar to boards or transformers. They are
available in right (without Monobloc) and left (with Monobloc fitted)
versions. The drawings below refer to the standard versions.
Different combinations are available on request (e.g.: length,
centre distance between bar conductors, drilling, etc.)
U
64281016P A
U A
Item Connection interfaces with exit bars
for panel boards
Al Cu In (A) Type Type
64281000P - 630
Note:
64281001P 67281000P 800 RH - Right
64281002P 67281001P 1000 LH - Left
64281004P 67281003P 1250
64281006P 67281005P 1600 Standard connection interface See on page 40-41 the drawings
with all drilling details for dimensions
64281007P 67281006P 2000 Standard of coverplate (1) and bars (2)
64391004P 67391004P 2500 U
MIN AND MAX DIMENSIONS
64391006P 67391005P 3200
A Single bar min/MAX
64391007P 67391006P 4000
10
U 150/400
0*
64391008P 67391008P 5000
10
0*
A 200/1299
10
0*
- 67391009P 6300
Double bar min/MAX
64281020P - 630
U 150/400
64281021P 67281020P 800
A 200/1299
64281022P 67281021P 1000 Right Type 2
Triple bar min/MAX
64281024P 67281023P 1250
U 150/400
64281026P 67281025P 1600
H
A 200/1299
64281027P 67281026P 2000 Special
Dimension H changes with the rating; it
64391024P 67391024P 2500 is specified in the technical information
64391026P 67391025P 3200 The dimensions are referred to
the standard elements.
64391027P 67391026P 4000 Single/double/triple bar (U+A): 200+300 mm
64391028P 67391028P 5000
* 120 mm for 6300 A (Cu) and 5000 A (Al)
- 67391029P 6300
64281010P - 630 Non-standard elements “Special” (with measurements that are different
64281011P 67281010P 800 from those show in the figure) are referred to the Min and Max
dimensions specified in the table.
64281012P 67281011P 1000
64281014P 67281013P 1250
64281016P 67281015P 1600
64281017P 67281016P 2000 Standard
64391014P 67391014P 2500
64391016P 67391015P 3200
64391017P 67391016P 4000
64391018P 67391018P 5000
- 67391019P 6300
64281030P - 630
64281031P 67281030P 800
64281032P 67281031P 1000 Left Special connection interface with not standard interaxes
64281034P 67281033P 1250 Type 1
64281036P 67281035P 1600
D
E
38
Xtra Compact (XCP-S)
connection interfaces with exit bars
300
n Dimensions
Connection interfaces with exit bars
Special connection interfaces are used at the end of the lines to
300
connect the busbar to dry transformers. They are available
in right (without Monobloc) and left (with Monobloc fitted)
N L1 L2 L3 versions. The drawings below refer to the standard versions.
80 80 Different combinations are available on request (e.g.: length,
centre distance between bar conductors, drilling, etc.)
135 160 135
13
5
U 300/400
16
0
A 200/1299
13
5
Double bar min/MAX
U 300/400
6428T016P A 200/1299
Triple bar min/MAX
H
U 300/400
Item Connection interfaces with exit bars A 200/1299
for transformers*
Dimension H changes with the rating; it
Al Cu In (A) Type Type is specified in the technical information
6428T000P - 630
6428T001P 6728T000P 800
6428T002P 6728T001P 1000
6428T004P 6728T003P 1250
6428T006P 6728T005P 1600
6428T007P 6728T006P 2000 CRT
6439T004P 6739T004P 2500
300
6428T010P - 630
6428T011P 6728T010P 800 N L1 L2 L3
6428T012P 6728T011P 1000 80 80
6428T014P 6728T013P 1250 135 160 135
6428T016P 6728T015P 1600
6428T017P 6728T016P 2000 CRT
6439T014P 6739T014P 2500
6439T016P 6739T015P 3200 Left Flange size details
6439T017P 6739T016P 4000 Type 1
6439T018P 6739T018P 5000 15 165 170 170 165 15
15
- 6739T019P 6300
165
170
700
170
165
39
167 Holes 9x30 170 167 167
167 167 Holes 9x30
40
Holes 9x30 Holes 15x20 167 100 Holes 9x30
40
40
Holes 15x20
40
100 Holes 9x30
15
Holes 15x30 100 100 100 100 Holes 15x20
60
15
40
15
Xtra Compact (XCP-S)
15
Holes 15x20
60
60
60
10020 30 20
30
5 70 20 50 50 50 20
15
35 90 35 30
60
120 dimensions 190 50 190
30
160 50 160
30
30
370 430
35 90 35
160
30
n Coverplate drilling details (1)
Al 630A–2000A Al 2500A–3200A Al 4000A Al 5000A
Cu 800A–2000A Cu 2500A–4000A Cu 5000A Cu 6300A
430 430 130 500
100 100 100 100
15
100 100 100 100
15
15 15 15 15 15 115 120 120 115 15
15
430
100 100 100 100 167
15
15 15
100 75 75 75 75 75 100
100 100 125 100 100
Holes 9x30
40
0 Holes 15x20 100
330
15
15
60
555
605
700
20 35 50 35
120
30
Holes ø 9
15
Holes ø 9 Holes ø 9
15
15
Holes ø 9
15
n Bar drilling details (2) Side and front view
220
Al 630A Al 800A
Cu 167
800A Cu 1000A
120 120 120 120 120
Holes 9x30 130 130 130
40
40
40
Holes 15x20 10050 50 Holes 15x20 100 Holes 15x20 100
30 50 30
200
200
210
15
200
200
15
30
60
60
15
60
N L1
30
70 50 50 50 50 120 480
30
80 50 50 50 50 50 50
100 100 100 100 100 100 100 100 100 100 167
100 100 167 100 100
167
Holes 9x30
40
40
100 Holes 15x20 100 100
15
15
120 120
60
130 40 40
40 170 120 40 220 120
100 100 100
200
40 40
40
40
40
40
40 40 Holes 15x2040 40
200
0 Holes 15x20 100 Holes 15x20 100 100 Holes ø 9
15
N L1 L2 L3 N L1 L2 L3
200
200
200
200
200
200
15
15
15
15
60
60
60
200
N L1 L2 L3 N L1
200
430 50 50 50 50
200
50 50 50 50
200
200
20 L1 L3 35 N L1 100L2100 100 30N
15
N L2 50 L1 35L2 L3 N15 100 L3 N15 100L1 100L2 100L3 35 100N90 100 L135 100L2 L3 50L1
50 50 L2 30 L3
N L1 L2 L3 N L1 100 100 100 N 100 L2100
120 50 50 160 50L250 L3 210 L1
30
30
50 50 50 50
30
50 50 50 50
N L1 L2 L3 50 50 N L1 L2 L3 50 50 N L1 L2 L3 50 50
100 75 75 75 75 75 100
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
50 50 100 100 100 50 50 50 50
100 100 100 100 100 100
100 100 100 100 100 100 100 100 120100
120 120 120
605
15 120
220 120
200
40
100 100 100
40 40
40 40 40
40 40
Holes ø 9 40 40 40 167
167 40 40
200
200 330
200
200
15
40 40 Holes 9x30 40
Holes 9x30 130 40 40 170
40
40
NHoles 15x20
200
40
N L1 L2 L3 L1 L2 L3
100 N L1 L2 L3 N L1
200
200
Holes 15x20
200
200 200
167
100 167
200
Holes ø 9 50 50 50 50 50 50 50 5
200
15
15
Holes 9x30
15
60
Holes 9x30
15
L1 L2 L3
60
N L1 L2 L3 N L2 L3
40
40
50
35 50 Holes 15x20 50 5030 50 50 50 30 50 50
Holes 15x20 N L1 L2 L3
20 10050 50 50 20
50 50 N 50 50 L2
L1 L3 50 50 100
00 100 100 210 N 100L1 100L2 100L3 N
100 120 120
30
50
60
15
35 90 35
80 40 40 40 160 40
30
200
40 40 40
40 40 40 40
40 40
40 40 40 40
N L1 L2 L3
N L1 L2 L3
40 40 40 40
40 430 60 60 60 60
100 100 100 100
20015
15 15
200
200
200
200
15
200
200
100 100 125 100 100
Xtra Compact (XCP-S)
200
200
200
N L1 L2 L3 N L1 L2 L3
dimensions 50 50 50 50
555
L1 L2 L3 N L1 L2 L3 N L1 L2 L3
100 100 100 100 100 100
50 50 50 50 50 50
100 100 100 100 100 100 100 100
15
Cu 2500A440
40 120 120
40 40 40 40 40
300 40 40
167 167 40
Holes 9x30
167 167
Holes 9x30 40 40 40 40 Holes 9x30
200
40
Holes 15x20
200
200
100 100
200
40 Holes 15x20
Holes 15x20 100 100
15
N L1 L2 L3
60
N L1 L2 L3 N L1 L2 L3 N L1
20015
200
50 50 N L1 L250 50L3
60
50 50 50 5
60
20
50 50 50 20 N L1 L2
100 100 100 50 100
50 100 50 1002
50190 3550 190 100 100 100 100 100
30
35 N L1 L2 L3 50
N L1
120 50 L2 430
120 L3 100 100 100
30
30
50 50 100 100 10
50 50290
100 100 100 100 100 100
200
200
200
200
200
40
200
100 100 125 100 100
Holes 15x30 100 100 Holes 15x20
200
200
200
L3 N L1 L2 L3 L1 N L2 L3
15
N L1 L2 L3
60
60
N L1 L2 L3
200
200
50 50 N L1 50L250 L3
50 50 N L1 L2 L3 N L1 L2 L3 N L1 L2
35 90 100 35 50 50N 100 L1100 L2 L3 N 50 50L1 L2 L3 3
555
30
100 100 100
30
120
440 40 120 40
40
40 40
40167 40 40 40 40430 40
40 167
Holes 9x30 100 100 100 100
15
40 40 15 15
40 40
200
40
Holes 15x20
100 75 75 75 75 75 100
100 100
200
200
200
200
200
N L1 L2 L3
15
60
200
N L1 L2 N L3 L1
200
N L1 L2 L3 L2 L3 60 60 N L1 L2
2 L3 20 50 50 50 20
605
50
50 50
50 50 50 50 50 120 120 120 50 50
190 50 190 N L1 L2 L3
30
100 100 100 100 100 100100 100 100 N L1 L2 L3 100 100 1
120 100 100 100 430 50 50
50 50
100 100 100
120 100 100 100
40
480 40
120 120
380
40 40167 167 40 40
Holes 9x30 167 167
200
40 40 40 40
Holes 9x30
40
Holes 15x20
Holes 9x30
100 100
200
200
40
100 100
60
60 60
15
200
200
60
60
N L1 L2 L3 N L1 L2 L3
30 50 50 50 30 120 120 120
50 50 50 210 50 50
90 210
30
35 35 N L1 L2 L3 N L1 L2 L3 30
100 100 100 160 50 470 160 100 100 100
30
30
50 50 50 50
370
100 100 100 100 100 100
Al 5000A
Cu 6300A 120
590
170 40 170 40 170
40 40
Holes 9x30 430
167 167 167
100 100 100 100
15
15 15
200
Holes 15x20
40
100 75 75 75 75 75 100
200
N L1 L2 L3
35 90 35
605
60 60
160 50 160 50 160
30
Holes ø 9 41
15
480
Xtra Compact (XCP-S)
technical information
n Structural features
The outer casing of the XCP-S line consists of four C-ribbed
section bars, bordered and riveted (thickness 1.5mm), with
excellent mechanical, electric and heat loss efficiency.
The sheet metal is made of galvanized steel, treated N L1 L2 L3 PE
according to UNI EN10327 and painted with RAL7035
resins with a high resistance to chemical agents
The standard degree of protection is IP55, on request IP65 (only
for transport of energy); with certain accessories, it can also XCP-S 5 line with 5 conductors
be installed outdoors. 3P+N+FE+PE
The busbar conductors have a rectangular cross section Note: For dimension H, see technical data section
with rounded corners; there are two versions: PE: Protection Earth
FE: Functional Earth (Clean Earth)
42
Xtra Compact (XCP-S)
technical data
n XCP-S Al (4 Conductors)
TRIPLE
3P+N+PE SINGLE BAR DOUBLE BAR BAR
Rated current In [A] 630 800 1000 1250 1600 2000 2500 3200 4000 5000
Overall dimension of the busbars L x H [mm] 120 x 130 120 x 130 120 x 130 120 x 170 120 x 200 120 x 220 120 x 380 120 x 440 120 x 480 120 x 590
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 25*** 25*** 36 42 42 50 65 80 100 120
Peak current Ipk [kA] 53 53 76 88 88 105 143 176 220 264
Allowable specific energy for three-phase I²t [MA²s] 312 312 1296 1764 1764 2500 4225 6400 10000 14400
fault
Rated short-time current of the neutral ICW [kA]rms 15*** 15*** 22 25 25 30 39 48 60 72
bar (1 s)
Peak current of the neutral bar Ipk [kA] 30 30 46 53 53 63 82 101 132 158
Rated short-time current of the protective ICW [kA]rms 15*** 15*** 22 25 25 30 39 48 60 72
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 30 30 46 53 53 63 82 101 132 158
Phase resistance at 20°C R20 [mΩ/m] 0,140 0,092 0,077 0,057 0,041 0,029 0,029 0,021 0,014 0,011
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,016 0,015 0,014 0,011 0,007 0,006 0,005
Phase impedance Z [mΩ/m] 0,142 0,094 0,079 0,060 0,044 0,032 0,031 0,022 0,016 0,012
Phase resistance at thermal conditions R [mΩ/m] 0,185 0,122 0,104 0,080 0,058 0,040 0,041 0,030 0,021 0,015
Phase impedance at thermal conditions Z [mΩ/m] 0,186 0,123 0,105 0,081 0,059 0,043 0,042 0,031 0,022 0,016
Neutral resistance R20 [mΩ/m] 0,140 0,092 0,077 0,057 0,041 0,029 0,029 0,021 0,014 0,011
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,132 0,132 0,132 0,119 0,110 0,106 0,078 0,071 0,067 0,040
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,038 0,032 0,025 0,021 0,017 0,016 0,013
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,064 0,054 0,049 0,035 0,029 0,026 0,021
Reactance of the protective bar XPE [mΩ/m] 0,080 0,078 0,078 0,048 0,039 0,028 0,020 0,015 0,016 0,014
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,272 0,224 0,208 0,176 0,152 0,135 0,107 0,092 0,082 0,051
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,190 0,142 0,126 0,095 0,073 0,054 0,049 0,038 0,030 0,023
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,224 0,176 0,161 0,121 0,096 0,078 0,064 0,050 0,040 0,032
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,10 0,10 0,10 0,06 0,05 0,04 0,03 0,02 0,02 0,02
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,291 0,243 0,229 0,188 0,161 0,142 0,111 0,094 0,085 0,054
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,216 0,171 0,158 0,115 0,091 0,069 0,058 0,044 0,037 0,030
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,247 0,200 0,187 0,137 0,110 0,089 0,071 0,054 0,046 0,037
Zero-sequence short-circuit average Ro [mΩ/m] 0,187 0,123 0,102 0,077 0,055 0,039 0,038 0,028 0,019 0,014
resistance phase - N
Zero-sequence short-circuit average Xo [mΩ/m] 0,031 0,023 0,023 0,021 0,020 0,019 0,015 0,009 0,008 0,007
reactance phase - N
Zero-sequence short-circuit average Zo [mΩ/m] 0,189 0,125 0,105 0,080 0,059 0,043 0,041 0,029 0,021 0,016
impedance phase - N
Zero-sequence short-circuit average Ro [mΩ/m] 0,178 0,162 0,157 0,138 0,124 0,116 0,088 0,078 0,072 0,044
resistance phase - PE
Zero-sequence short-circuit average
reactance phase - PE Xo [mΩ/m] 0,031 0,023 0,023 0,021 0,020 0,019 0,015 0,009 0,008 0,007
Zero-sequence short-circuit average Zo [mΩ/m] 0,181 0,164 0,159 0,140 0,126 0,117 0,089 0,079 0,073 0,044
impedance phase - PE
cosϕ = 0,70 126,3 84,4 73,4 58,1 44,1 33,2 31,5 22,4 16,3 12,4
cosϕ = 0,75 133,3 88,9 77,1 60,8 45,9 34,3 32,8 23,3 17,0 12,9
cosϕ = 0,80 140,1 93,3 80,7 63,4 47,6 35,3 34,0 24,2 17,6 13,3
Voltage drop with distribuited load cosϕ = 0,85 146,6 97,5 84,1 65,9 49,2 36,1 35,1 25,1 18,1 13,6
ΔV [V/(m*A)]10-6
cosϕ = 0,90 152,8 101,5 87,3 68,0 50,5 36,8 36,0 25,8 18,5 13,9
cosϕ = 0,95 158,4 104,9 90,0 69,8 51,4 37,0 36,5 26,4 18,8 14,0
cosϕ = 1,00 160,2 105,6 89,9 68,9 49,8 35,0 35,3 25,8 18,0 13,3
Weight (PE 1) p [kg/m] 14,3 15,6 16,0 18,9 22,5 27,4 34,1 41,5 50,4 88,3
Weight (PE 2) p [kg/m] 17,6 18,9 19,3 23,3 27,7 33,9 42,1 51,0 61,0 101,4
Weight (PE 3) p [kg/m] 15,4 16,7 17,1 20,3 24,2 29,2 36,7 44,6 54,0 92,6
Fire load [kWh/m] 4,5 5,5 5,5 6,0 8,5 10,5 16,0 19,0 21,0 21,0
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect P [W/m] 220 234 311 373 442 485 765 914 1000 1154
at nominal current
Ambient temperature min/ [°C] -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50
MAX (daily average)
For temperatures over 35°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. Standard version Extra earth - COPPER Extra earth - ALUMINUM
XCP Al 3L+N+50%PE
(available on request)
43
Xtra Compact (XCP-S)
technical data
For temperatures over 35°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. PE 1 PE 2 PE 3
Standard version Extra earth - COPPER Extra earth - ALUMINUM
XCP Al 3L+N+50%PE
(available on request)
44
Xtra Compact (XCP-S)
technical data
For temperatures over 35°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. PE 1 PE 2 PE 3
Standard version Extra earth - COPPER Extra earth - ALUMINUM
XCP Al 3L+N+50%PE
(available on request)
45
Xtra Compact (XCP-S)
technical data
n XCP-S AI (3 Conductors)
TRIPLE
3P+PE SINGLE BAR DOUBLE BAR
BAR
Rated current In [A] 630 800 1000 1250 1600 2000 2500 3200 4000 5000
Overall dimension of the busbars L x H [mm] 120 x 130 120 x 130 120 x 130 120 x 170 120 x 200 120 x 220 120 x 380 120 x 440 120 x 480 120 x 590
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 25*** 25*** 36 42 42 50 65 80 100 120
Peak current Ipk [kA] 53 53 76 88 88 105 143 176 220 264
Allowable specific energy for three-phase I²t [MA²s] 312 312 1296 1764 1764 2500 4225 6400 10000 14400
fault
Rated short-time current of the protective ICW [kA]rms 15*** 15*** 22 25 25 30 39 48 60 72
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 30 30 46 53 53 63 82 101 132 158
Phase resistance at 20°C R20 [mΩ/m] 0,140 0,092 0,077 0,057 0,041 0,029 0,029 0,021 0,014 0,011
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,016 0,015 0,014 0,011 0,007 0,006 0,005
Phase impedance Z [mΩ/m] 0,142 0,094 0,079 0,060 0,044 0,032 0,031 0,022 0,016 0,012
Phase resistance at thermal conditions R [mΩ/m] 0,185 0,122 0,104 0,080 0,058 0,040 0,041 0,030 0,021 0,015
Phase impedance at thermal conditions Z [mΩ/m] 0,186 0,123 0,105 0,081 0,059 0,043 0,042 0,031 0,022 0,016
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,132 0,132 0,132 0,119 0,110 0,106 0,078 0,071 0,067 0,040
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,038 0,032 0,025 0,021 0,017 0,016 0,013
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,064 0,054 0,049 0,035 0,029 0,026 0,021
Reactance of the protective bar XPE [mΩ/m] 0,080 0,078 0,078 0,048 0,039 0,028 0,020 0,015 0,016 0,014
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,272 0,224 0,208 0,176 0,152 0,135 0,107 0,092 0,082 0,051
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,190 0,142 0,126 0,095 0,073 0,054 0,049 0,038 0,030 0,023
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,224 0,176 0,161 0,121 0,096 0,078 0,064 0,050 0,040 0,032
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,10 0,10 0,10 0,06 0,05 0,04 0,03 0,02 0,02 0,02
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,291 0,243 0,229 0,188 0,161 0,142 0,111 0,094 0,085 0,054
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,216 0,171 0,158 0,115 0,091 0,069 0,058 0,044 0,037 0,030
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,247 0,200 0,187 0,137 0,110 0,089 0,071 0,054 0,046 0,037
Zero-sequence short-circuit average Ro [mΩ/m] 0,178 0,162 0,157 0,138 0,124 0,116 0,088 0,078 0,072 0,044
resistance phase - PE
Zero-sequence short-circuit average Xo [mΩ/m] 0,031 0,023 0,023 0,021 0,020 0,019 0,015 0,009 0,008 0,007
reactance phase - PE
Zero-sequence short-circuit average Zo [mΩ/m] 0,181 0,164 0,159 0,140 0,126 0,117 0,089 0,079 0,073 0,044
impedance phase - PE
cosϕ = 0,70 126,3 84,4 73,4 58,1 44,1 33,2 31,5 22,4 16,3 12,4
cosϕ = 0,75 133,3 88,9 77,1 60,8 45,9 34,3 32,8 23,3 17,0 12,9
cosϕ = 0,80 140,1 93,3 80,7 63,4 47,6 35,3 34,0 24,2 17,6 13,3
Voltage drop with distribuited load cosϕ = 0,85 146,6 97,5 84,1 65,9 49,2 36,1 35,1 25,1 18,1 13,6
ΔV [V/(m*A)]10-6
cosϕ = 0,90 152,8 101,5 87,3 68,0 50,5 36,8 36,0 25,8 18,5 13,9
cosϕ = 0,95 158,4 104,9 90,0 69,8 51,4 37,0 36,5 26,4 18,8 14,0
cosϕ = 1,00 160,2 105,6 89,9 68,9 49,8 35,0 35,3 25,8 18,0 13,3
Weight (PE 1) p [kg/m] 13,3 14,2 14,5 16,9 19,8 23,6 29,9 35,9 42,9 78,4
Weight (PE 2) p [kg/m] 16,6 17,5 17,8 21,3 25,0 30,1 37,9 45,4 53,4 91,5
Weight (PE 3) p [kg/m] 14,3 15,3 15,5 18,3 21,5 25,5 32,5 39,0 46,4 82,7
Fire load [kWh/m] 3,4 4,1 4,1 4,5 6,4 7,9 12,0 14,3 15,8 14,8
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect P [W/m] 220 234 311 373 442 485 765 914 1000 1154
at nominal current
Ambient temperature min/ [°C] -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50
MAX (daily average)**
For temperatures over 35°C it will be necessary to derate the busbar and
PE 1 PE 2 PE 3
for ambient temperatures under -5°C contact the technical support. Standard version Extra earth - COPPER Extra earth - ALUMINUM
XCP Al 3L+N+50%PE
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. (available on request)
46
Xtra Compact (XCP-S)
technical data
n XCP-S CU (4 Conductors)
TRIPLE
3P+N+PE SINGLE BAR DOUBLE BAR BAR
Rated current In [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Overall dimension of the busbars L x H [mm] 120 x 130 120 x 130 120 x 130 120 x 170 120 x 200 120 x 300 120 x 380 120 x 440 120 x 480 120 x 590
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 25 36 42 42 50 65 80 100 120 150
Peak current Ipk [kA] 53 76 88 88 105 143 176 220 264 330
Allowable specific energy for three-phase I²t [MA²s] 625 1296 1764 1764 2500 4225 6400 10000 14400 22500
fault
Rated short-time current of the neutral ICW [kA]rms 15 22 25 25 30 39 48 60 72 90
bar (1 s)
Peak current of the neutral bar Ipk [kA] 30 46 53 53 63 82 101 132 158 198
Rated short-time current of the protective ICW [kA]rms 15 22 25 25 30 39 48 60 72 90
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 30 46 53 53 63 82 101 132 158 198
Phase resistance at 20°C R20 [mΩ/m] 0,077 0,058 0,045 0,034 0,024 0,021 0,017 0,012 0,008 0,0062
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,007 0,006 0,006 0,0050
Phase impedance Z [mΩ/m] 0,080 0,061 0,048 0,037 0,028 0,024 0,018 0,014 0,010 0,0079
Phase resistance at thermal conditions R [mΩ/m] 0,100 0,081 0,061 0,045 0,034 0,029 0,024 0,017 0,011 0,0085
Phase impedance at thermal conditions Z [mΩ/m] 0,103 0,082 0,063 0,048 0,036 0,031 0,025 0,018 0,012 0,0099
Neutral resistance R20 [mΩ/m] 0,077 0,058 0,045 0,034 0,024 0,021 0,017 0,012 0,008 0,0062
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,132 0,132 0,132 0,119 0,110 0,090 0,078 0,071 0,067 0,0402
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,038 0,032 0,025 0,021 0,017 0,016 0,0125
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,064 0,054 0,042 0,035 0,029 0,026 0,0213
Reactance of the protective bar XPE [mΩ/m] 0,054 0,054 0,054 0,044 0,044 0,032 0,022 0,017 0,016 0,0140
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,209 0,190 0,176 0,153 0,135 0,111 0,095 0,083 0,075 0,0464
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,126 0,108 0,094 0,072 0,056 0,046 0,038 0,029 0,023 0,0187
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,161 0,143 0,129 0,098 0,079 0,063 0,052 0,041 0,033 0,0275
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,08 0,07 0,07 0,06 0,06 0,04 0,03 0,02 0,02 0,02
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,222 0,203 0,190 0,164 0,147 0,119 0,099 0,087 0,078 0,0501
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,148 0,129 0,118 0,093 0,081 0,063 0,047 0,037 0,032 0,0267
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,179 0,159 0,147 0,114 0,098 0,076 0,059 0,047 0,040 0,0334
Zero-sequence short-circuit average Ro [mΩ/m] 0,103 0,078 0,060 0,045 0,033 0,028 0,023 0,016 0,010 0,0082
resistance phase - N
Zero-sequence short-circuit average Xo [mΩ/m] 0,031 0,023 0,023 0,020 0,019 0,015 0,009 0,008 0,008 0,0067
reactance phase - N
Zero-sequence short-circuit average Zo [mΩ/m] 0,107 0,081 0,064 0,050 0,038 0,032 0,025 0,018 0,013 0,0106
impedance phase - N
Zero-sequence short-circuit average Ro [mΩ/m] 0,157 0,151 0,147 0,130 0,118 0,097 0,084 0,075 0,070 0,0423
resistance phase - PE
Zero-sequence short-circuit average Xo [mΩ/m] 0,062 0,060 0,060 0,049 0,049 0,036 0,024 0,019 0,018 0,0157
reactance phase - PE
Zero-sequence short-circuit average Zo [mΩ/m] 0,169 0,163 0,158 0,139 0,128 0,103 0,087 0,078 0,072 0,0451
impedance phase - PE
cosϕ = 0,70 75,1 59,5 47,2 36,7 29,0 24,5 19,2 14,1 10,3 8,3
cosϕ = 0,75 78,4 62,2 49,1 37,9 29,9 25,3 19,9 14,6 10,5 8,4
cosϕ = 0,80 81,5 64,8 50,8 39,1 30,6 25,9 20,6 15,0 10,7 8,5
Voltage drop with distribuited load cosϕ = 0,85 84,4 67,2 52,3 40,1 31,1 26,5 21,2 15,4 10,7 8,6
ΔV [V/(m*A)]10-6
cosϕ = 0,90 86,9 69,3 53,6 40,9 31,5 26,9 21,7 15,6 10,7 8,5
cosϕ = 0,95 88,8 71,0 54,4 41,2 31,4 27,0 22,0 15,7 10,6 8,4
cosϕ = 1,00 86,9 69,9 52,4 39,1 29,1 25,3 21,2 14,8 9,4 7,4
Weight (PE 1) p [kg/m] 21,2 23,8 26,9 33,5 42,5 51,0 63,0 80,9 114,9 165,1
Weight (PE 2) p [kg/m] 24,5 27,1 30,2 37,8 47,6 57,7 71,0 90,4 125,4 178,2
Weight (PE 3) p [kg/m] 22,3 24,9 28,0 34,9 44,2 53,2 65,6 84,0 118,4 169,3
Fire load [kWh/m] 4,5 5,5 5,5 8,0 8,2 10,5 16,0 19,0 21,0 22,0
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect P [W/m] 193 242 284 347 403 547 752 823 816 1015
at nominal current
Ambient temperature min/ [°C] -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50
MAX (daily average)
For temperatures over 35°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
Standard version Extra earth - COPPER XCP Cu 3L+N+50%PE Extra earth - ALUMINUM
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. (tinned copper conductors
available on request)
47
Xtra Compact (XCP-S)
technical data (continued)
TRIPLE
3P+N+PE+FE SINGLE BAR DOUBLE BAR BAR
Rated current In [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Overall dimension of the busbars L x H [mm] 120 x 130 120 x 130 120 x 130 120 x 170 120 x 200 120 x 300 120 x 380 120 x 440 120 x 480 120 x 590
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 25 36 42 42 50 65 80 100 120 150
Peak current Ipk [kA] 53 76 88 88 105 143 176 220 264 330
Allowable specific energy for three-phase
I²t [MA²s] 625 1296 1764 1764 2500 4225 6400 10000 14400 22500
fault
Rated short-time current of the neutral
ICW [kA]rms 15 22 25 25 30 39 48 60 72 90
bar (1 s)
Peak current of the neutral bar Ipk [kA] 30 46 53 53 63 82 101 132 158 198
Rated short-time current of the protective
ICW [kA]rms 15 22 25 25 30 39 48 60 72 90
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 30 46 53 53 63 82 101 132 158 198
Phase resistance at 20°C R20 [mΩ/m] 0,077 0,058 0,045 0,034 0,024 0,021 0,017 0,012 0,008 0,0062
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,007 0,006 0,006 0,0050
Phase impedance Z [mΩ/m] 0,080 0,061 0,048 0,037 0,028 0,024 0,018 0,014 0,010 0,0079
Phase resistance at thermal conditions R [mΩ/m] 0,100 0,081 0,061 0,045 0,034 0,029 0,024 0,017 0,011 0,0085
Phase impedance at thermal conditions Z [mΩ/m] 0,103 0,082 0,063 0,048 0,036 0,031 0,025 0,018 0,012 0,0099
Neutral resistance R20 [mΩ/m] 0,077 0,058 0,045 0,034 0,024 0,021 0,017 0,012 0,008 0,0062
Functional Earth resistance (FE) R20 [mΩ/m] 0,077 0,058 0,045 0,034 0,024 0,021 0,017 0,012 0,008 0,0062
Functional Earth reactance (FE) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,007 0,006 0,006 0,0050
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,133 0,133 0,133 0,120 0,111 0,090 0,079 0,072 0,068 0,0412
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,038 0,032 0,025 0,021 0,017 0,016 0,0125
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,064 0,054 0,042 0,035 0,029 0,026 0,0213
Reactance of the protective bar XPE [mΩ/m] 0,054 0,054 0,054 0,044 0,044 0,032 0,022 0,017 0,016 0,0140
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,126 0,099 0,078 0,060 0,045 0,038 0,031 0,023 0,015 0,0115
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,107 0,085 0,068 0,052 0,038 0,032 0,026 0,019 0,013 0,0103
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,117 0,093 0,074 0,056 0,041 0,035 0,028 0,021 0,014 0,0109
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,077 0,071 0,071 0,059 0,058 0,043 0,029 0,023 0,022 0,0190
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,147 0,122 0,106 0,084 0,073 0,058 0,042 0,032 0,026 0,0222
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,132 0,111 0,098 0,079 0,070 0,054 0,039 0,030 0,025 0,0216
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,140 0,117 0,102 0,081 0,071 0,056 0,041 0,031 0,026 0,0219
Zero-sequence short-circuit average
Ro [mΩ/m] 0,103 0,078 0,060 0,045 0,033 0,028 0,023 0,016 0,010 0,0082
resistance phase - N
Zero-sequence short-circuit average
Xo [mΩ/m] 0,031 0,023 0,023 0,020 0,019 0,015 0,009 0,008 0,008 0,0067
reactance phase - N
Zero-sequence short-circuit average
Zo [mΩ/m] 0,107 0,081 0,064 0,050 0,038 0,032 0,025 0,018 0,013 0,0106
impedance phase - N
Zero-sequence short-circuit average
Ro [mΩ/m] 0,103 0,078 0,060 0,045 0,033 0,028 0,023 0,016 0,010 0,0082
resistance phase - PE
Zero-sequence short-circuit
Xo [mΩ/m] 0,031 0,023 0,023 0,020 0,019 0,015 0,009 0,008 0,008 0,0067
average reactance phase - PE
Zero-sequence short-circuit
Zo [mΩ/m] 0,107 0,081 0,064 0,050 0,038 0,032 0,025 0,018 0,013 0,0106
average impedance phase - PE
cosϕ = 0,70 75,1 59,5 47,2 36,7 29,0 24,5 19,2 14,1 10,3 8,3
cosϕ = 0,75 78,4 62,2 49,1 37,9 29,9 25,3 19,9 14,6 10,5 8,4
cosϕ = 0,80 81,5 64,8 50,8 39,1 30,6 25,9 20,6 15,0 10,7 8,5
Voltage drop with distribuited load cosϕ = 0,85 84,4 67,2 52,3 40,1 31,1 26,5 21,2 15,4 10,7 8,6
ΔV [V/(m*A)]10-6
cosϕ = 0,90 86,9 69,3 53,6 40,9 31,5 26,9 21,7 15,6 10,7 8,5
cosϕ = 0,95 88,8 71,0 54,4 41,2 31,4 27,0 22,0 15,7 10,6 8,4
cosϕ = 1,00 86,9 69,9 52,4 39,1 29,1 25,3 21,2 14,8 9,4 7,4
Weight (PE 1) p [kg/m] 23,7 27,1 31,0 38,9 49,9 59,9 74,1 96,0 138,1 193,1
Weight (PE 2) p [kg/m] 27,1 30,4 34,4 43,3 55,1 66,5 82,1 105,5 148,6 206,2
Weight (PE 3) p [kg/m] 24,8 28,1 32,1 40,3 51,6 62,0 76,7 99,1 141,6 197,4
Fire load [kWh/m] 5,6 6,9 6,9 10,0 10,3 13,1 20,0 23,8 26,3 27,3
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal
B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect
P [W/m] 193 242 284 347 403 547 752 823 816 1015
at nominal current
Ambient temperature min/
[°C] -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50
MAX (daily average)
For temperatures over 35°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support. PE 2 PE 3
PE 1
Standard version Extra earth - COPPER XCP Cu 3L+N+50%PE Extra earth - ALUMINUM
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. (tinned copper conductors
available on request)
48
Xtra Compact (XCP-S)
technical data
For temperatures over 35°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. Standard version Extra earth - COPPER XCP Cu 3L+N+50%PE Extra earth - ALUMINUM
(tinned copper conductors
available on request)
49
Xtra Compact (XCP-S)
technical data
n XCP-S CU (3 Conductors)
TRIPLE
3P+PE SINGLE BAR DOUBLE BAR BAR
Rated current In [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Overall dimension of the busbars L x H [mm] 120 x 130 120 x 130 120 x 130 120 x 170 120 x 200 120 x 300 120 x 380 120 x 440 120 x 480 120 x 590
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 25 36 42 42 50 65 80 100 120 150
Peak current Ipk [kA] 53 76 88 88 105 143 176 220 264 330
Allowable specific energy for three-phase
I²t [MA²s] 625 1296 1764 1764 2500 4225 6400 10000 14400 22500
fault
Rated short-time current of the protective
ICW [kA]rms 15 22 25 25 30 39 48 60 72 90
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 30 46 53 53 63 82 101 132 158 198
Phase resistance at 20°C R20 [mΩ/m] 0,077 0,058 0,045 0,034 0,024 0,021 0,017 0,012 0,008 0,0062
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,007 0,006 0,006 0,0050
Phase impedance Z [mΩ/m] 0,080 0,061 0,048 0,037 0,028 0,024 0,018 0,014 0,010 0,0079
Phase resistance at thermal conditions R [mΩ/m] 0,100 0,081 0,061 0,045 0,034 0,029 0,024 0,017 0,011 0,0085
Phase impedance at thermal conditions Z [mΩ/m] 0,103 0,082 0,063 0,048 0,036 0,031 0,025 0,018 0,012 0,0099
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,130 0,130 0,130 0,118 0,110 0,089 0,078 0,071 0,067 0,0396
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,038 0,032 0,025 0,021 0,017 0,016 0,0125
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,064 0,054 0,042 0,035 0,029 0,026 0,0213
Reactance of the protective bar XPE [mΩ/m] 0,054 0,054 0,054 0,044 0,044 0,032 0,022 0,017 0,016 0,0140
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,206 0,188 0,174 0,152 0,134 0,110 0,095 0,083 0,075 0,0458
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,126 0,108 0,094 0,072 0,056 0,046 0,038 0,029 0,023 0,0187
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,161 0,143 0,129 0,098 0,079 0,063 0,052 0,041 0,033 0,0275
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,077 0,071 0,071 0,059 0,058 0,043 0,029 0,023 0,022 0,0190
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,220 0,201 0,188 0,163 0,146 0,118 0,099 0,086 0,078 0,0496
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,148 0,129 0,118 0,093 0,081 0,063 0,047 0,037 0,032 0,0267
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,179 0,159 0,147 0,114 0,098 0,076 0,059 0,047 0,040 0,0334
Zero-sequence short-circuit average
Ro [mΩ/m] 0,157 0,151 0,147 0,130 0,118 0,097 0,084 0,075 0,070 0,0423
resistance phase - PE
Zero-sequence short-circuit average
Xo [mΩ/m] 0,062 0,060 0,060 0,049 0,049 0,036 0,024 0,019 0,018 0,0157
reactance phase - PE
Zero-sequence short-circuit average
Zo [mΩ/m] 0,169 0,163 0,158 0,139 0,128 0,103 0,087 0,078 0,072 0,0451
impedance phase - PE
cosϕ = 0,70 75,1 59,5 47,2 36,7 29,0 24,5 19,2 14,1 10,3 8,3
cosϕ = 0,75 78,4 62,2 49,1 37,9 29,9 25,3 19,9 14,6 10,5 8,4
cosϕ = 0,80 81,5 64,8 50,8 39,1 30,6 25,9 20,6 15,0 10,7 8,5
Voltage drop with distribuited load cosϕ = 0,85 84,4 67,2 52,3 40,1 31,1 26,5 21,2 15,4 10,7 8,6
ΔV [V/(m*A)]10-6
cosϕ= 0,90 86,9 69,3 53,6 40,9 31,5 26,9 21,7 15,6 10,7 8,5
cosϕ = 0,95 88,8 71,0 54,4 41,2 31,4 27,0 22,0 15,7 10,6 8,4
cosϕ = 1,00 86,9 69,9 52,4 39,1 29,1 25,3 21,2 14,8 9,4 7,4
Weight (PE 1) p [kg/m] 18,7 20,6 22,9 28,0 35,0 42,2 51,9 65,8 91,6 136,8
Weight (PE 2) p [kg/m] 22,0 23,9 26,2 32,4 40,2 48,8 59,9 75,3 102,1 149,9
Weight (PE 3) p [kg/m] 19,7 21,7 23,9 29,5 36,7 44,4 54,5 68,9 95,1 141,0
Fire load [kWh/m] 3,4 4,1 4,1 6,0 6,2 7,9 12,0 14,3 15,8 16,8
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect P [W/m] 193 242 284 347 403 547 752 823 816 1015
at nominal current
Ambient temperature min/
[°C] -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50
MAX (daily average)
For temperatures over 35°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. PE 1 PE 2 PE 3
Standard version Extra earth - COPPER XCP Cu 3L+N+50%PE Extra earth - ALUMINUM
(tinned copper conductors
available on request)
50
XCP-HP
BUSBAR FROM
630 TO 6300 A
The High Performance XCP-HP is a busbar trunking system
characterised by high performance and low
power solutions for losses due to the joule effect.
Used for transport and distribution of High
industrial and service Power, and is also highly valued in rising
mains. The applications include all industrial,
sector applications commercial and service sector buildings
(factories, banks, trade and business centres,
hospitals, data center, etc.)
51
Xtra Compact (XCP-HP)
straight elements
n Dimensions
Straight elements
Standard 3000 mm
H
63280100P
A
XCP-HP Line:
Reference standard: IEC 61439-6. Reference temperature: up to 55 °C.
Protection degree: IP55. Thickness of metal sheet: 1.5 mm.
N° of conductors: 3, 4 or 5. Painted: RAL 7035. Halogen Free. Dimension H changes with the ratings and
The insulation between bars is ensured by a double sheet made it is specified in the technical information
with polyester film class B(130°C), class F (155°C) thermal
resistance available on request. All plastic components have a V1
self-extinguishing degree (as per UL94); they are fire retardant
and comply with the glow-wire test according to standards.
52
Xtra Compact (XCP-HP)
straight elements
n Dimensions
Straight elements for distribution
- Straight elements for plug-in type tap-off boxes
- Standard 3000 mm
- Tap-off outlets on both sides
63280130P These straight elements enable the application of plug-in boxes on
dedicated outlets
Available in lengths from 1 to 3 meters, these elements have
Item Straight elements for distribution respectively 1, 2 and 3 outlets at preset distances with centre
distances of 850 mm on both sides.
Al Cu In (A) N° outlets A (mm) (*) The exception to these are 630-800 A elements with aluminium
63280130P - 630 conductors (Al) and 800-1000 A elements with copper conductors
(Cu), where distribution is only available on the top side (in standard
63280131P *66280130P 800 3+3 ** 3000 execution) for example “3+0”
63280132P 66280131P 1000 On request, the length of the elements and the number and position
63280134P 66280133P 1250 of distribution outlets may be different from the standards measures.
63280136P 66280135P 1600
63280137P 66280136P 2000
63390134P 66280138P 2500
63390136P 66390135P 3200 d
63390137P 66390136P 4000
H
63390138P 66390138P 5000
- 66390139P 6300 c
63280970P - 630 A
63280971P *66280970P 800
63280972P 66280971P 1000
63280974P 66280973P 1250 b
63280976P 66280975P 1600
63280977P 66280976P 2000 1+1 1001-1500
63390974P 66280978P 2500 a Dimension H changes with the ratings and
63390976P 66390975P 3200 it is specified in the technical information
63390977P 66390976P 4000
63390978P 66390978P 5000 at request: outlets in special
- 66390979P 6300 position 1+1 only combination
63280920P - 630
63280921P *66280920P 800
63280922P 66280921P 1000
63280924P 66280923P 1250
63280926P 66280925P 1600 MIN AND MAX DIMENSIONS OF SINGLE AND DOUBLE BAR
63280927P 66280926P 2000 2+2 ** 1501-2000
Aluminium (Al) 630A – 5000A
63390924P 66280928P 2500
63390926P 3200 Copper (Cu) 800A – 6300A
66390925P
63390927P 66390926P 4000 (L) min/MAX [mm] 1001 ***/3000
63390928P 66390928P 5000
- 66390929P 6300 (***) Lengths from 1001 mm to 1250 mm can only be installed with
63280980P - 630 type 1 and 3 plug-in boxes
63280981P *66280980P 800 From 1250 mm to 3000 mm it is possible to install all types of plug-in boxes.
63280982P 66280981P 1000 Compatible boxes are listed in dedicated chapter. See page 96.
63280984P 66280983P 1250
63280986P 66280985P 1600 (**) on request it is possible to have other combinations of outlets:
63280987P 66280986P 2000 2+2 ** 2001-2500 length: 1501÷2000 - outlets: (1+1)
66280988P 2500 length: 2001÷2500 - outlets: (1+1)
63390984P length: 2501÷2999 - outlets: (1+1) and (2+2)
63390986P 66390985P 3200 length: 3000 - outlets: (1+1) and (2+2)
63390987P 66390986P 4000 Possibility to have outlets in special position
63390988P 66390988P 5000
- 66390989P 6300
63280950P - 630
63280951P *66280950P 800
63280952P 66280951P 1000
63280954P 66280953P 1250
63280956P 66280955P 1600
63280957P 66280956P 2000 3+3 ** 2501-2999
63390954P 66280958P 2500
63390956P 66390955P 3200
63390957P 66390956P 4000
63390958P 66390958P 5000
- 66390959P 6300
53
Xtra Compact (XCP-HP)
straight elements
n Dimensions
Fire barrier elements EI120 (EN 1366-3)
205
673IFB01
Fire barrier
H + 82
H
Item Fire barrier elements S120 EI120 EI120
(EN 1366-3)
When the busbar trunking system crosses Fire barrier sizes
fire resistant walls or ceilings, it must be Dimension H changes
fitted with appropriate fire barriers. with the rating; it
The fire barrier is 630 mm (Al) and is specified in the
technical information
1000 mm (Cu) long and must always be
positioned in the middle of the fire resistant
wall or ceiling crossed by the busbar.
After crossing fire resistant walls or
ceilings, any cavity must be sealed with
material meeting current regulations for the
required building fire resistance class.
Al Cu In (A) Type For some ratings it is necessary to have an internal fire barrier
* - 630 fitted at the factory following the guidelines on the table.
It is therefore necessary to indicate at the order stage
* 673IFB01 800 which elements will cross fire resistant walls or ceilings
673IFB01 * 1000
* * 1250 internal
673IFB01 * 1600 – 2500 fire barrier Figure 1 minimum straight dimensions
673IFB01 673IFB01 3200 – 4000
No fire barrier
* 673IFB01 5000 No fire barrier
The external fire barrier can be used on any trunking component in compliance with the
operating instructions specified in figures 1 and 2
54
Xtra Compact (XCP-HP)
straight elements
n Dimensions
Expansion element
H
A
63280200P
170
170 m
m
Example:
Straight section length 170 m = no. 4 expansion elements,
one every 34 m
35 m 35 m
70 m
Example:
Section length 70 m. When the section is not straight,
no expansion element is necessary
55
Xtra Compact (XCP-HP)
straight elements
n Dimensions
Phase balancing 1200 mm
0
120
63287100P
H
63287120P
Dimension H changes
with the rating; it
is specified in the
technical information.
63287140P
1/3L 2/3L
Item Phase balancing
N N N N
Al Cu In (A) 1 3 2 1
2 1 3 2
(fig. 1) 3 2 1 3
63287100P - 630 Straight elements with phase
63287101P 66287100P 800 balancing are used to reduce and Electric
N
diagram: 2 elements
1
offer all the possible
balance mutual phase reactance and reciprocal
1 positions among2the phases along the line.
2 3
63287102P 66287101P 1000 impedance in case of long lines. 3 N
two thirds of the path), to balance IfNit's necessary to have the1 same phase sequence at the
63397104P 66287108P 2500 the system electric impedance: start
1 and the end, use 3 phase
2 balancing elements.
2 3
63397106P 66397105P 3200 In this way, it will be possible to 3 N
have along the installation path In particularly long carrying sections (L> 100 meters) it is recom-
63397107P 66397106P 4000 mended to insert 2 elements:
N (one placed3 at 1/3 and one placed at
all the possible combinations, of 1 2
63397108P 66397108P 5000 reciprocal positions among phases, 2/3 of the trunking path)
2
3
to balance the 1Nelectric impedance of the
- 66397109P 6300 minimising load losses (Fig.1). system.
If it's necessary to have the "L" is the total length of the path.
same phase sequence at the For example, in a line exceeding 300 m it is recommended that one
start and the end, use 3 phase phase transposition is fitted at 100 m, and another one at 200 m.
balancing elements (fig.2).
H
phases and the neutral. It is normally
63287122P 66287121P 1000 used in connections between the
N 1
63287124P 66287123P 1250 transformer and electric board, or 1 2
in the connections between electric 2 3
63287126P 66287125P 1600 boards, when the starting sequence 3 N
63287127P 66287126P 2000 is different from the arrival sequence
63397124P 66287128P 2500 N 3
1 2
63397126P 66397125P 3200 2 1
3 N
63397127P 66397126P 4000
Electrical diagram
63397128P 66397128P 5000
- 66397129P 6300
Element with neutral rotation 1000 mm
Element with neutral rotation
Al Cu In (A)
N N N
63287144P 66287143P 1250 at the ends of the connections, 1 3 2
should these be different. 2 1 3
63287146P 66287145P 1600 In the connection between electric 3 2 1
63287147P 66287146P 2000 boards, the neutral jump is
normally used, as only the neutral
63397144P 66287148P 2500 position is normally identified
N 1
1 2
63397146P 66397145P 3200 2 3
3 N
63397147P 66397146P 4000
63397148P 66397148P 5000 Electrical diagram
N 3
- 66397149P 6300 When the position of neutral of
1 the distribution board 2
phases is different from that of
2 the transformer, it is possible
1
to use an element that allows3a neutral rotation only. N
56
Xtra Compact (XCP-HP)
feed unit
n Dimensions
Feed unit
B
C
10
0*
10
0*
10
0*
200
300
A
63281106P
The feed units are used at the end of the lines, when the busbar must
be powered using cables.
Right-hand feed units do not come with a Monobloc but left-hand feed
H
units come with a pre-fitted Monobloc. Dimension H changes For dimensions of holes for
with the rating; it connections, see the specific
They are available with non-standard execution, on request. is specified in the pages of coverplate drilling
End feed units for single bar busbars are supplied with an aluminium technical information details (page 68-69).
blind back closing plate. For double bar busbar trunking systems the
plates are 2. Both versions are fitted with 2 extra side steel flanges * 120 mm for 6300 A (Cu) and 5000 A (Al)
and 2 inspection steel flanges (dark grey colour). The cable is con-
nected directly to the busbars using bolts.
For more information on board/busbar connection see the tables Rear cable input
(Dimensions For The Box).
To feed the power supply cable through the back power supply Aluminium gland plate(s) for cable entry 170 x 410 mm
flanges it will be necessary to drill a hole in case of single bar and two Single bar: 1 plate
holes in case of double bar. The size of the holes is 170 x 410 mm. Double bar: 2 plates
57
Xtra Compact (XCP-HP)
rising mains feed unit
B
C
10
0*
10
0*
10
200
0*
300
A
66281133P
The rising mains feed units are used at the departure of the riser mains lines,
when the busbar must be placed close to the wall and powered using cables.
H
They allow the busbar to be installed 40 mm away from the wall. Dimension H changes For dimensions of holes
with the rating; it for connections, see
Right-hand feed units do not come with a Monobloc but left-hand feed units is specified in the the specific pages of
come with a pre-fitted Monobloc. technical information coverplate drilling details
They are available with non-standard execution, on request. End feed units (68-69).
for single bar busbars are supplied with an aluminium blind back closing
plate. For double bar busbar trunking systems the plates are 2. Both versions * 120 mm for 6300 A (Cu) and 5000 A (Al)
are fitted with 2 extra side steel flanges and 2 inspection steel flanges (dark
grey colour). The cable is connected directly to the busbars using bolts.
For more information on board/busbar connection see the tables below Rear cable input
(Dimensions For The Box).
To feed the power supply cable through the back power supply flanges Aluminium gland plate(s) for cable entry 170 x 410 mm
it will be necessary to drill a hole in case of single bar and two holes Single bar: 1 plate
in case of double bar. The size of the holes is 170 x 410 mm. Double bar: 2 plates
58
Xtra Compact (XCP-HP)
elbows
n Dimensions
Horizontal elbow
In order to define the type of horizontal elbow required, consider
to place the element “edgewise” (conductors perpendicular
to the ground). In this configuration “horizontal” elbows
enable a path variation which is parallel to the ground.
63280306P When the neutral busbar conductor faces the outside of the
elbow, there will be a Right horizontal elbow (type 1)
Contrariwise, with the neutral busbar conductor facing the inside
Item Horizontal elbow of the elbow there will be a Left horizontal elbow (type 2)
Al Cu In (A) Type Type
59
Xtra Compact (XCP-HP)
elbows
n Dimensions
Vertical elbow
In order to define the type of vertical elbow, it is necessary to
still place the element "edgewise" (conductors perpendicular
to the ground), with the section with Monobloc facing
the observer and the section without facing up.
In this configuration, vertical “elbows” enable an up or down facing
variation If the neutral is on the left side, there will be a left vertical
elbow (Type 1).
If, on the other side, it is on the right side, there will be a right
vertical elbow (Type 2)
A B
A
Item Vertical elbow
Al Cu In (A) Type Type
B
63280400P - 630
63280401P 66280400P 800
MIN AND MAX DIMENSIONS
63280402P 66280401P 1000
Single bar min/MAX
63280404P 66280403P 1250 A 250/1299*
B
63280406P 66280405P 1600 B 250/1299*
63280407P 66280406P 2000 Standard Double bar min/MAX
63390404P 66280408P 2500 A 340/1449*
63390406P 66390405P 3200 B 340/1449*
63390407P 66390406P 4000 Triple bar min/MAX
63390408P 66390408P 5000 A 560/1199* (AL)
A 530/1199* (CU)
- 66390409P 6300 B 560/1199* (AL)
Right Type 2
63280420P - 630 530/1199* (CU)
H
1600
63280417P 66280416P 2000 Standard
63390414P 66280418P 2500
63390416P 66390415P 3200
63390417P 66390416P 4000
A
63390418P 66390418P 5000 A
H
- 66390419P 6300
H
63280430P - 630
63280431P 66280430P
B
800
Triple bar
63280432P 66280431P 1000
Left Type 1
63280434P 66280433P 1250
63280436P 66280435P 1600
63280437P 66280436P 2000 Special
length To calculate the measurements
63390434P 66280438P 2500 of vertical elbows, consider
the center-to-center distance
63390436P 66390435P 3200 A as shown in the drawings.
H
60
Xtra Compact (XCP-HP)
elbows
n Dimensions
Double horizontal elbow
Double horizontal elbows are the union of two horizontal elbows; in
order to define the type, it is enough to observe them starting from
63280346P
the Monobloc; if the first elbow met is left, we will have a double
horizontal elbow left + right (Type 2). Contrariwise, if the first elbow met
is right, we will have a double horizontal elbow right + left (Type 1)
63280456P
MIN AND MAX DIMENSIONS
Single bar min/MAX
A 250/1299*
Item Double horizontal elbow C B 50/599*
C 250/1299*
Al Cu In (A) Type Double bar min/MAX
A
B
63280340P - 630 A 250/1299*
H
B 50/599*
63280341P 66280340P 800
C 250/1299*
63280342P 66280341P 1000 Triple bar min/MAX
The dimensions are referred to the
63280344P 66280343P 1250 standard elements.
A 250/999*
B 50/599*
63280346P 66280345P 1600 Single/double/triple bar (A+B+C):
C 250/999*
63280347P 66280346P 2000 300+300+300 mm
Dimension H changes with the rating; it
63390344P 66280348P 2500 is specified in the technical information
Right Type 1
63390346P 66390345P 3200 Type 1 Type 2
63390347P 66390346P 4000
C
63390348P 66390348P 5000 A B C
- 66390349P 6300
B
63280350P - 630 A
63280351P 66280350P 800
63280352P 66280351P 1000
63280354P 66280353P 1250 Double vertical elbow
63280356P 66280355P 1600 Double vertical elbows are the union of two vertical elbows; in order
63280357P 66280356P 2000 to define the type, it is enough to observe them starting from the
Monobloc; if the first elbow met is left, we will have a double vertical
63390354P 66280358P 2500 Left Type 2 elbow left + right (Type 1). Contrariwise, if the first elbow met is
63390356P 66390355P 3200 right, we will have a double vertical elbow right + left (Type 2)
63390357P 66390356P 4000 MIN AND MAX DIMENSIONS
63390358P 66390358P 5000 Single bar min/MAX
A 250/1299*
- 66390359P 6300
B 50/599*
Double vertical elbow C C 250/1299*
Double bar min/MAX
Al Cu In (A) Type
A 340/1449*
63280440P - 630 B 50/899*
63280441P 66280440P 800 C 340/1449*
Triple bar min/MAX
63280442P 66280441P 1000 A 560/1199* (AL)
63280444P 66280443P 1250 530/1199* (CU)
B
A B 50/999*
63280446P 66280445P 1600 C 560/1199* (AL)
63280447P 66280446P 2000 530/1199* (CU)
H
61
Xtra Compact (XCP-HP)
elbows
n Dimensions
Double elbow horizontal + vertical
Double elbows horizontal + vertical are the union of a horizontal
and a vertical elbow, placed in succession starting from the side
with Monobloc
Depending on the type of elbows, the double horizontal
+ vertical elbow may be of four different types:
• Double elbow Horizontal RH + Vertical RH (Type 1)
• Double elbow Horizontal RH + Vertical LH (Type 2)
• Double elbow Horizontal LH + Vertical RH (Type 3)
• Double elbow Horizontal LH + Vertical LH (Type 4)
63280606P
Type 1 Type 2 Type 3 Type 4
Item Double elbow horizontal + vertical B
A B B
Al Cu In (A) Type C C
A B
63280600P - 630 C
C
63280601P 66280600P 800
63280602P 66280601P 1000 A A
B
DIMENSIONS OF SINGLE
63390606P 66390605P 3200
Type 1 Single bar min/MAX
63390607P 66390606P 4000
A 250/1299*
63390608P 66390608P 5000
B 150/599*
- 66390609P 6300
C 250/1299*
63280610P - 630
Double bar min/MAX
63280611P 66280610P 800
H
A 250/1299*
63280612P 66280611P 1000
C
B 235/899*
63280614P 66280613P 1250
C 340/1449*
63280616P 66280615P 1600
Triple bar min/MAX
63280617P 66280616P 2000
The dimensions refer to the standard A 250/999*
63390614P 66280618P 2500 elements B 458/799* (AL)
63390616P 66390615P 3200 Single bar (A+B+C): 300+300+300 mm 428/799* (CU)
Type 2 Double bar (A+B+C): 300+450+450 mm
63390617P 66390616P 4000 C 560/999* (AL)
Triple bar (A+B+C): 300+600+600 mm 530/999* (CU)
63390618P 66390618P 5000
- 66390619P 6300 Dimension H changes with
the rating; it is specified in
63280620P - 630 the technical information
63280621P 66280620P 800
63280622P 66280621P 1000
63280624P 66280623P 1250 Non-standard elements “Special” (with measurements that are different
from those show in the figure) are referred to the Min and Max
63280626P 66280625P 1600 dimensions specified in the table.
63280627P 66280626P 2000
63390624P 66280628P 2500 * Warning: for safety reasons in production and also to help in
63390626P 66390625P 3200 the installation, if one dimension is pulled close to the maximum
length (i.e. A=1100 mm) then the other two dimensions
63390627P 66390626P 4000 Type 3 should be kept as close as possible to their standard lengths
63390628P 66390628P 5000 (i.e. B=300 mm, C=310 mm).
- 66390629P 6300
63280630P - 630 Note:
RH - Right
63280631P 66280630P 800 LH - Left
63280632P 66280631P 1000
63280634P 66280633P 1250
63280636P 66280635P 1600
63280637P 66280636P 2000
63390634P 66280638P 2500
63390636P 66390635P 3200
63390637P 66390636P 4000 Type 4
63390638P 66390638P 5000
- 66390639P 6300
62
Xtra Compact (XCP-HP)
elbows
n Dimensions
Double elbow vertical + horizontal
Double elbows vertical + horizontal are the union of a vertical
and a horizontal elbow, placed in succession starting from the
side with Monobloc
Depending on the type of elbows, the double vertical + horizontal
elbow may be of four different types:
• Double elbow vertical RH + horizontal RH (Type 1)
• Double elbow vertical RH + horizontal LH (Type 2)
• Double elbow vertical LH + horizontal RH (Type 3)
• Double elbow vertical LH + horizontal LH (Type 4)
63280506P
B 150/599*
63390507P 66390506P 4000 C 250/1299*
63390508P 66390508P 5000 Double bar min/MAX
- 66390509P 6300 A 340/1449*
63280510P - 630
B
B 325/899*
63280511P 66280510P 800 C 250/1299*
63280512P 66280511P 1000 Triple bar min/MAX
C
63
Xtra Compact (XCP-HP)
T elements
n Dimensions
Horizontal T element
T-elements can be used to split the line in two branches,
adding together the effect of two diverging elbows
There are four types of horizontal “T” elements, as shown below
63280706P B B C C
A C A
C B
B
A A
Item Horizontal T element
Al Cu In (A) Type
63280700P - 630
B MIN AND MAX DIMENSIONS
63280701P 66280700P 800
Single bar min/MAX
63280702P 66280701P 1000
A 600/1449*
63280704P 66280703P 1250 A
B 600/1449*
63280706P 66280705P 1600
C 600/1449*
63280707P 66280706P 2000 H
Double bar min/MAX
63390704P 66280708P 2500
A 600/1449*
63390706P 66390705P 3200
Type 1
C
B 600/1449*
63390707P 66390706P 4000
C 600/1449*
63390708P 66390708P 5000
Triple bar min/MAX
- 66390709P 6300
The dimensions refer to the standard A 600/1449*
63280710P - 630 elements. B 600/1449*
63280711P 66280710P 800 Single/double/triple bar (A+B+C): C 600/1449*
600+600+600 mm
63280712P 66280711P 1000
Dimension H changes with the rating; it
63280714P 66280713P 1250 is specified in the technical information
64
Xtra Compact (XCP-HP)
T elements
n Dimensions
Vertical T element
T-elements can be used to split the line in two branches,
adding together the effect of two diverging elbows
There are four types of verticals “T” elements, as shown below
B
B C
A C
A
63280806P
C C B
B
A
A
Item Vertical t element
Al Cu In (A) Type
MIN AND MAX DIMENSIONS
63280800P - 630
Single bar min/MAX
63280801P 66280800P 800
A 300/1299*
63280802P 66280801P 1000
B 300/1299*
63280804P 66280803P 1250 B C 300/1299*
63280806P 66280805P 1600 H Double bar min/MAX
63280807P 66280806P 2000 A A 450/1449*
63390804P 66280808P 2500 B 450/1449*
C
65
Xtra Compact (XCP-HP)
connection interfaces with exit bars
n Dimensions
Connection interfaces with exit bars
Standard connection interfaces are used at the end of the
lines to connect the busbar to boards or transformers. They are
available in right (without Monobloc) and left (with Monobloc fitted)
versions. The drawings below refer to the standard versions.
Different combinations are available on request (e.g.: length,
centre distance between bar conductors, drilling, etc.)
63281000P - 630
63281001P 66281000P 800
63281002P 66281001P 1000 Note:
RH - Right
63281004P 66281003P 1250 LH - Left
63281006P 66281005P 1600
63281007P 66281006P 2000 Standard Standard connection interface See on page 68-69 the drawings
63391004P 66281008P 2500 with all drilling details for dimensions
of coverplate (1) and bars (2)
63391006P 66391005P 3200 U
63391007P 66391006P 4000 MIN AND MAX DIMENSIONS
10
U 150/400
0*
- 66391009P 6300
10
0*
A 200/1299
10
63281020P - 630
0*
63281021P 66281020P 800 Double bar min/MAX
A 200/1299
63391024P 66281028P 2500
63391026P 66391025P 3200 Dimension H changes with the rating; it
is specified in the technical information
63391027P 66391026P 4000
63391028P 66391028P 5000
The dimensions refer to the standard elements.
- 66391029P 6300 Single/double/triple bar (U+A): 200+300 mm
63281010P - 630
63281011P 66281010P 800 * 120 mm for 6300 A (Cu) and 5000 A (Al)
63281012P 66281011P 1000 Non-standard elements “Special” (with measurements that are different
63281014P 66281013P 1250 from those show in the figure) are referred to the Min and Max
dimensions specified in the table.
63281016P 66281015P 1600
63281017P 66281016P 2000 Standard
63391014P 66281018P 2500
63391016P 66391015P 3200
63391017P 66391016P 4000
63391018P 66391018P 5000
- 66391019P 6300
63281030P - 630
63281031P 66281030P 800
63281032P 66281031P 1000 Left
63281034P 66281033P 1250 Type 1
Special connection interface with interaxes not standard
63281036P 66281035P 1600
63281037P 66281036P 2000 Special
D
E
66
Xtra Compact (XCP-HP)
connection interfaces with exit bars
300
n Dimensions
Connection interfaces with exit bars
Special connection interfaces are used at the end of the lines to
300
connect the busbar to dry transformers. They are available
in right (without Monobloc) and left (with Monobloc fitted)
N L1 L2 L3 versions. The drawings below refer to the standard versions.
80 80 Different combinations are available on request (e.g.: length,
centre distance between bar conductors, drilling, etc.)
135 160 135
13
5
U 300/400
16
0
A 200/1299
13
5
Double bar min/MAX
U 300/400
6328T016P A 200/1299
Triple bar min/MAX
H
U 300/400
Item Connection interfaces with exit bars A 200/1299
for transformers*
Al Cu In (A) Type Type Dimension H changes with the rating; it
is specified in the technical information
6328T000P - 630
6328T001P 6628T000P 800
6328T002P 6628T001P 1000
6328T004P 6628T003P 1250
6328T006P 6628T005P 1600
6328T007P 6628T006P 2000 CRT
6339T004P 6628T008P 2500
300
6328T010P - 630
6328T011P 6628T010P 800 N L1 L2 L3
6328T012P 6628T011P 1000 80 80
6328T014P 6628T013P 1250 135 160 135
6328T016P 6628T015P 1600
6328T017P 6628T016P 2000 CRT
6339T014P 6628T018P 2500
6339T016P 6639T015P 3200 Left
6339T017P 6639T016P 4000 Type 1 Flange size details
6339T018P 6639T018P 5000
- 6639T019P 6300 15 165 170 170 165 15
15
165
170
700
170
165
For the versions of XCP-HP 5000A Al and 6300A Cu, the dimensions
are different. For more details please contact Legrand.
67
DETTAGLIO ELEMENTO DI CONESSIONE CON
USCITA BARRE XCP-HP 4000A Al
AGLIO ELEMENTO DI CONESSIONE CON
480 125
Xtra Compact (XCP-HP)
USCITA BARRE XCP-HP 1000A Al DETTAGLIO ELEMENTO DI CONESSIONE CON
USCITA BARRE XCP-HP 2500A Al
167 167
130 125 45 45
dimensions 380 125
167 167 167 ASOLE 9x30 2
42
40 40 ASOLE 15x20 40 100 100
40
200
HOLES 9x30
15
40
HOLES 15x20 60
40
00 n Coverplate 100
drilling details (1) 100 N L1 L2 L3
6.3
200
27.5 50 50 50 27.5 50 50
15
200
60
15
50 30 50 50
110 100 100 100 370
430 430
15 100 100 100 100 15 15 100 100 100 100 15
15
15
430
15 100 100 100 100 15
15
100 100
100
MENTO DI CONESSIONE CON
BARRE XCP-HP 5000A Al
DETTAGLIO ELEMENTO DI CONESSIONE CON
75
100
75 75
555
125
330
100
605
40 40
100
167 167 167
100
75
40 40
40
40 100
100
75
HOLES 9x30 HOLES Ø9
HOLES 15x20 N
200
100
200
L1 4.5 L2 L36
15
N
15
60
60 60 100 N L1 L2 L3
210 120 20 120 50 50
12050 20 60 60 FORI Ø9
15
Al 5000A190 50 190 50 190 Cu 120 6300A
120 120
30
670
500 500
15
100
100
100
100
80 80 100
110
850
790
110
100
100
100
N
100
100
6 6 6
5.5
100
120 HOLES Ø9
15
HOLES Ø9
15
40
HOLES
HOLES 15x20
15x20 100100 HOLES 15x20 100
200
200
200
15
15
15
60
60
60
N N L1 L1 L2 L2 L3 L3 N L1 L2 L3
35 35 50 50 35 35 50 50
50 50 20 30 20 50 50
30
30
USCITA
USCITA
BARRE
BARRE 15 151000A
XCP-HP
XCP-HP 100100Al100Al
1000A 100 100100 100100 15 15 DETTAGLIO
DETTAGLIOELEMENTO
ELEMENTODIDI
CONESSIONE
CONESSIONECON
CON
15
15
Al 1000A Al BARRE
USCITA
USCITA 1250A
BARREXCP-HP
XCP-HP1000A
1000A
CuCu
Cu 1000A–1250A
130 130 125 125
100
130130 125125
100
100
330
100
167 167
167167
330
330
100
100
40 40 40 40 40 40 40 40
15 40 100
HOLESHOLES
9x30 9x30 HOLES
HOLES9x30
9x30
100
100
40
40
HOLESHOLES
15x2015x20
40
200
200
15
15
FORIFORI
Ø9 Ø9
15
15
60
60
60
60
15
15
N N L1 L1 L2 L2 L3 L3 N N L1 L1 L2 L2 L3 L3
30 30 50 50 30 30 50 5050 50 3535 5050 3535 50505050
100100 100100 100100
30
30
30
30
68
100
100
100
100
30
300
0
Xtra Compact (XCP-HP)
dimensions
167 167
40 40 40 40
HOLES 9x30 HOLES 9x30
40
40
HOLES 15x20 100 HOLES 15x20 100
200
200
15
15
60
60
N L1 L2 L3 N L1 L2 L3
15 50 50 50 15 50 50 35 90 35 50 50
180 100 100 100 160 100 100 100
30
30
430 430
15 100 100 100 100 15 15 100 100 100 100 15
15
15
100
100
330
100
330
100
100
100
40
40
HOLES HOLES
15x20 15x20
40
200
200
200
15
15
15
60
60
15
15
60
N L1 L2 L3 N NL1 L1 L2 L2L3 L3
50 50 35 35 90 90 35 35 50 50 50 50
27.5 50 50 50 27.5 160 160
50 50
160 160 100 100
100 100
100 100
30
30
15
15
15 100 100 100 100 15
15
100 100
100 100
USCITA
CuUSCITA
BARRE
BARRE
4000A XCP-HP
XCP-HP3200A
3200A
Al Al
100
220 125
440 440 125 125
100
330
167
555
555
125
125
167 167 167 167
40 40
15 40 100
40 40 40 40
HOLES 9x30 100 40100
100 100
HOLES 9x309x30
HOLES
15 40
HOLES 15x20 100 FORI Ø9 HOLES 15x2015x20
HOLES 100 100 100 100
200
200
200
15
15
60
60
N N
60
N L1 L2 L3 N L1HOLES
N HOLES Ø9L1 L2Ø9 L2 L3 L3
4.515 4.5
15 50 650
50 50
506 5015 15 50 5050 50
15
15
30 50 50 50 30 50 50
180100180 100
70 70 180 180 100 100100 100100 100
30
30
30
Al ELEMENTO
DETTAGLIO 4000A
DETTAGLIO ELEMENTO
DI CONESSIONE
DI CONESSIONE
CON CON Al 5000A
100
100
USCITA
USCITA
BARRE
BARRE
XCP-HP
XCP-HP
4000A
4000A
Al Al DETTAGLIO
DETTAGLIO ELEMENTO
ELEMENTO DI CONESSIONE
DI CONESSIONE
CON CON
100
USCITA
USCITA
BARRE
BARRE
XCP-HP
XCP-HP
5000A
5000A
Al Al
100
100
555
555
125
125
167 167 167 167 167 167 167 167 167 167
40 40 40 40 40 40 40 40
100
100 40100
100 40100
HOLESHOLES
9x30 9x30 HOLESHOLES
9x309x30
40
40
HOLESHOLES
15x20 15x20 100 100 100 100 HOLESHOLES
15x2015x20 100 100 100 100 100 100
FORI Ø9
200
200
200
200
1515
15
15
15
60
60
60
60
100
100
DETTAGLIO
DETTAGLIO
Cu ELEMENTO
ELEMENTO
5000A DI CONESSIONE
DI CONESSIONE
CONCON Cu 6300A
USCITA
USCITA
BARRE
BARRE
XCP-HP
XCP-HP
5000A
5000A
Cu Cu DETTAGLIO ELEMENTO DI CONESSIONE CON
100
100
40 40 40 40 40 40
850
HOLESHOLES
9x30 9x30 HOLES 9x30
605
605
125
125
110
40
40
HOLESHOLES
15x2015x20 100 100 100 100 HOLES 15x20 100 100 100
200
200
200
100
100
15
75 75 75
75 75 75
60
15
15
60
60
N L1 L2 L3
N NL1 L1L2 L2L3 L3 50 50 50 N 20N
100
100
20 60 60
30 30 50N 505050
N50 50 30 30 50 5050 50
6 6 190 50 190 50 190 120 120 120
30
30
30
15
15 15 100 100
100 100
100 100
100 100 15 15
100
100
75 75 75
75 75 75
69
80 100
Xtra Compact (XCP-HP)
technical information
n Structural features
The outer casing of the XCP-HP line consists of four C-ribbed section
bars, bordered and riveted (thickness 1.5mm), with excellent
mechanical, electric and heat loss efficiency. The sheet metal is made
of galvanized steel, treated according to UNI EN10327 and painted
with RAL7035 resins with a high resistance to chemical agents N L1 L2 L3 PE
The standard degree of protection is IP55, on request IP65
(only for transport of energy); with certain accessories, it can also
be installed outdoors.
The busbar conductors have a rectangular cross section with rounded XCP-HP 5 line with 5 conductors
corners; there are two versions: 3P+N+FE+PE
Note: For dimension H, see technical data section
- Electrolytic copper ETP 99.9 UNI EN 13601 PE: Protection Earth
FE: Functional Earth (Clean Earth)
- Aluminum alloy treated over the entire surface with 5 galvanic
processes (copper plating + tin plating) Phase sequence
XCP-HP (CU)
Daily avg Ambient temperature -5°C 0°C 5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C 65°C 70°C
Kt factor 1,43 1,40 1,37 1,33 1,30 1,26 1,23 1,19 1,16 1,12 1,08 1,04 1 0,96 0,92 0,87
70
Xtra Compact (XCP-HP)
technical data
n XCP-HP Al (4 Conductors)
TRIPLE
3P+N+PE SINGLE BAR DOUBLE BAR BAR
Rated current In [A] 630 800 1000 1250 1600 2000 2500 3200 4000 5000
Overall dimension of the busbars L x H [mm] 125 x 130 125 x 130 125 x 130 125 x 130 125 x 200 125 x 220 125 x 380 125 x 440 125 x 480 125 x 740
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 36 36 50 70 70 85 120 120 150 150
Peak current Ipk [kA] 76 76 105 154 154 187 264 264 330 330
Allowable specific energy for three-phase I²t [MA²s] 1296 1296 2500 4900 4900 7225 14400 14400 22500 22500
fault
Rated short-time current of the neutral ICW [kA]rms 22 22 30 42 42 51 72 72 90 90
bar (1 s)
Peak current of the neutral bar Ipk [kA] 45 45 63 88 88 112 158 158 198 198
Rated short-time current of the protective ICW [kA]rms 22 22 30 42 42 51 72 72 90 90
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 45 45 63 88 88 112 158 158 198 198
Phase resistance at 20°C R20 [mΩ/m] 0,077 0,077 0,056 0,045 0,031 0,025 0,022 0,015 0,012 0,010
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,006 0,006 0,006 0,005
Phase impedance Z [mΩ/m] 0,080 0,079 0,059 0,047 0,034 0,027 0,023 0,017 0,014 0,011
Phase resistance at thermal conditions R [mΩ/m] 0,101 0,102 0,076 0,062 0,043 0,035 0,032 0,022 0,018 0,014
Phase impedance at thermal conditions Z [mΩ/m] 0,104 0,103 0,078 0,064 0,045 0,037 0,032 0,023 0,019 0,015
Neutral resistance R20 [mΩ/m] 0,077 0,077 0,056 0,045 0,031 0,025 0,022 0,015 0,012 0,010
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,132 0,132 0,132 0,133 0,111 0,106 0,078 0,072 0,068 0,035
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,049 0,032 0,029 0,019 0,016 0,014 0,010
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,084 0,054 0,049 0,032 0,027 0,025 0,016
Reactance of the protective bar XPE [mΩ/m] 0,080 0,078 0,078 0,048 0,039 0,028 0,020 0,015 0,016 0,014
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,208 0,208 0,188 0,178 0,142 0,131 0,101 0,087 0,080 0,045
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,126 0,126 0,106 0,094 0,063 0,054 0,041 0,031 0,027 0,019
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,161 0,161 0,140 0,129 0,085 0,074 0,054 0,043 0,037 0,026
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,10 0,10 0,10 0,06 0,05 0,04 0,03 0,02 0,02 0,02
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,232 0,229 0,210 0,189 0,151 0,137 0,104 0,089 0,083 0,049
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,163 0,158 0,142 0,114 0,082 0,067 0,049 0,038 0,035 0,027
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,191 0,187 0,169 0,144 0,100 0,084 0,060 0,047 0,043 0,032
Zero-sequence short-circuit average Ro [mΩ/m] 0,102 0,102 0,075 0,060 0,041 0,033 0,030 0,021 0,017 0,013
resistance phase - N
Zero-sequence short-circuit average Xo [mΩ/m] 0,031 0,023 0,023 0,020 0,019 0,015 0,008 0,008 0,008 0,007
reactance phase - N
Zero-sequence short-circuit average Zo [mΩ/m] 0,107 0,105 0,078 0,063 0,045 0,036 0,031 0,022 0,018 0,014
impedance phase - N
Zero-sequence short-circuit average Ro [mΩ/m] 0,157 0,157 0,150 0,148 0,121 0,115 0,086 0,077 0,072 0,039
resistance phase - PE
Zero-sequence short-circuit average
reactance phase - PE Xo [mΩ/m] 0,088 0,084 0,084 0,053 0,044 0,032 0,022 0,017 0,018 0,016
Zero-sequence short-circuit average Zo [mΩ/m] 0,180 0,178 0,172 0,157 0,129 0,119 0,088 0,079 0,074 0,042
impedance phase - PE
cosϕ = 0,70 75,6 72,1 56,5 47,0 34,7 27,9 23,0 17,2 14,6 11,5
cosϕ = 0,75 79,0 75,7 59,0 49,0 36,0 28,9 24,1 17,9 15,1 11,9
cosϕ = 0,80 82,1 79,2 61,3 50,9 37,1 29,9 25,1 18,5 15,6 12,2
Voltage drop with distribuited load cosϕ = 0,85 85,1 82,6 63,5 52,7 38,1 30,7 26,1 19,1 16,0 12,5
ΔV [V/(m*A)]10-6
cosϕ = 0,90 87,7 85,6 65,5 54,2 38,8 31,3 27,0 19,6 16,3 12,7
cosϕ = 0,95 89,6 88,2 66,9 55,3 39,2 31,7 27,8 19,9 16,4 12,8
cosϕ = 1,00 87,7 88,0 65,6 53,9 37,3 30,2 27,5 19,3 15,6 12,0
Weight (PE 1) p [kg/m] 16,0 16,0 17,8 19,3 25,4 29,4 37,7 47,3 54,3 91,0
Weight (PE 2) p [kg/m] 19,3 19,3 21,1 22,6 30,5 35,0 46,4 57,6 65,7 108,0
Weight (PE 3) p [kg/m] 17,1 17,1 18,9 20,3 27,1 31,2 40,5 50,7 58,0 96,5
Fire load [kWh/m] 4,5 5,5 5,5 6,0 8,5 10,5 16,0 19,0 21,0 21,0
Degree of protection IP 24,9 32,2 35,5 40,4 61,3 78,0 91,1 120,8 161,4 204,5
Insulation material thermal 5,625 6,875 6,875 10 10,25 13,125 20 23,75 26,25 27,25
resistance class
Losses for the Joule effect P [W/m] 121 195 227 292 330 418 596 683 863 1042
at nominal current
Ambient temperature min/ [°C] -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70
MAX (daily average)
For temperatures over 50°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
Standard version Extra earth - COPPER Extra earth - ALUMINUM
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. XCP Al 3L+N+50%PE
(available on request)
71
Xtra Compact (XCP-HP)
technical data
For temperatures over 50°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support. PE 1 PE 2 PE 3
Standard version Extra earth - COPPER Extra earth - ALUMINUM
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. XCP Al 3L+N+50%PE
(available on request)
72
Xtra Compact (XCP-HP)
technical data
For temperatures over 50°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. Standard version Extra earth - COPPER Extra earth - ALUMINUM
XCP Al 3L+N+50%PE
(available on request)
73
Xtra Compact (XCP-HP)
technical data
n XCP-HP AI (3 Conductors)
TRIPLE
3P+PE SINGLE BAR DOUBLE BAR BAR
Rated current In [A] 630 800 1000 1250 1600 2000 2500 3200 4000 5000
Overall dimension of the busbars L x H [mm] 125 x 130 125 x 130 125 x 130 125 x 130 125 x 200 125 x 220 125 x 380 125 x 440 125 x 480 125 x 740
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 36 36 50 70 70 85 120 120 150 150
Peak current Ipk [kA] 76 76 105 154 154 187 264 264 330 330
Allowable specific energy for three-phase I²t [MA²s] 1296 1296 2500 4900 4900 7225 14400 14400 22500 22500
fault
Rated short-time current of the protective ICW [kA]rms 22 22 30 42 42 51 72 72 90 90
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 45 45 63 88 88 112 158 158 198 198
Phase resistance at 20°C R20 [mΩ/m] 0,077 0,077 0,056 0,045 0,031 0,025 0,022 0,015 0,012 0,010
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,006 0,006 0,006 0,005
Phase impedance Z [mΩ/m] 0,080 0,079 0,059 0,047 0,034 0,027 0,023 0,017 0,014 0,011
Phase resistance at thermal conditions R [mΩ/m] 0,101 0,102 0,076 0,062 0,043 0,035 0,032 0,022 0,018 0,014
Phase impedance at thermal conditions Z [mΩ/m] 0,104 0,103 0,078 0,064 0,045 0,037 0,032 0,023 0,019 0,015
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,132 0,132 0,132 0,133 0,111 0,106 0,078 0,072 0,068 0,035
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,049 0,032 0,029 0,019 0,016 0,014 0,010
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,084 0,054 0,049 0,032 0,027 0,025 0,016
Reactance of the protective bar XPE [mΩ/m] 0,080 0,078 0,078 0,048 0,039 0,028 0,020 0,015 0,016 0,014
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,208 0,208 0,188 0,178 0,142 0,131 0,101 0,087 0,080 0,045
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,126 0,126 0,106 0,094 0,063 0,054 0,041 0,031 0,027 0,019
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,161 0,161 0,140 0,129 0,085 0,074 0,054 0,043 0,037 0,026
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,10 0,10 0,10 0,06 0,05 0,04 0,03 0,02 0,02 0,02
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,232 0,229 0,210 0,189 0,151 0,137 0,104 0,089 0,083 0,049
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,163 0,158 0,142 0,114 0,082 0,067 0,049 0,038 0,035 0,027
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,191 0,187 0,169 0,144 0,100 0,084 0,060 0,047 0,043 0,032
Zero-sequence short-circuit average Ro [mΩ/m] 0,157 0,157 0,150 0,148 0,121 0,115 0,086 0,077 0,072 0,039
resistance phase - PE
Zero-sequence short-circuit average Xo [mΩ/m] 0,088 0,084 0,084 0,053 0,044 0,032 0,022 0,017 0,018 0,016
reactance phase - PE
Zero-sequence short-circuit average Zo [mΩ/m] 0,180 0,178 0,172 0,157 0,129 0,119 0,088 0,079 0,074 0,042
impedance phase - PE
cosϕ = 0,70 75,6 72,1 56,5 47,0 34,7 27,9 23,0 17,2 14,6 11,5
cosϕ = 0,75 79,0 75,7 59,0 49,0 36,0 28,9 24,1 17,9 15,1 11,9
cosϕ = 0,80 82,1 79,2 61,3 50,9 37,1 29,9 25,1 18,5 15,6 12,2
Voltage drop with distribuited load cosϕ = 0,85 85,1 82,6 63,5 52,7 38,1 30,7 26,1 19,1 16,0 12,5
ΔV [V/(m*A)]10-6
cosϕ = 0,90 87,7 85,6 65,5 54,2 38,8 31,3 27,0 19,6 16,3 12,7
cosϕ = 0,95 89,6 88,2 66,9 55,3 39,2 31,7 27,8 19,9 16,4 12,8
cosϕ = 1,00 87,7 88,0 65,6 53,9 37,3 30,2 27,5 19,3 15,6 12,0
Weight (PE 1) p [kg/m] 14,5 14,5 15,8 16,9 22,0 25,1 32,6 40,2 45,8 79,7
Weight (PE 2) p [kg/m] 17,8 17,8 19,1 20,2 27,1 30,8 41,3 50,5 57,1 96,7
Weight (PE 3) p [kg/m] 15,5 15,5 16,9 18,0 23,6 27,0 35,4 43,6 49,5 85,2
Fire load [kWh/m] 3,4 4,1 4,1 4,5 6,4 7,9 12,0 14,3 15,8 14,8
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect P [W/m] 121 195 227 292 330 418 596 683 863 1042
at nominal current
Ambient temperature min/ [°C] -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70
MAX (daily average)
For temperatures over 50°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
Standard version Extra earth - COPPER Extra earth - ALUMINUM
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. XCP Al 3L+N+50%PE
(available on request)
74
Xtra Compact (XCP-HP)
technical data
n XCP-HP CU (4 Conductors)
TRIPLE
3P+N+PE SINGLE BAR DOUBLE BAR
BAR
Rated current In [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Overall dimension of the busbars L x H [mm] 125 x 130 125 x 130 125 x 130 125 x 170 125 x 170 125 x 220 125 x 380 125 x 440 125 x 480 125 x 680
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 36 50 70 70 85 120 120 150 150 150
Peak current Ipk [kA] 76 105 154 154 187 264 264 330 330 330
Allowable specific energy for three-phase I²t [MA²s] 1296 2500 4900 4900 7225 14400 14400 22500 22500 22500
fault
Rated short-time current of the neutral ICW [kA]rms 22 30,0 42 42 51 72 72 90 90 90
bar (1 s)
Peak current of the neutral bar Ipk [kA] 45 63 88 88 112 158 158 198 198 198
Rated short-time current of the protective ICW [kA]rms 22 30,0 42 42 51 72 72 90 90 90
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 45 63 88 88 112 158 158 198 198 198
Phase resistance at 20°C R20 [mΩ/m] 0,077 0,045 0,038 0,034 0,018 0,015 0,013 0,009 0,006 0,006
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,007 0,006 0,006 0,004
Phase impedance Z [mΩ/m] 0,080 0,048 0,042 0,037 0,023 0,018 0,015 0,011 0,009 0,007
Phase resistance at thermal conditions R [mΩ/m] 0,100 0,055 0,048 0,044 0,024 0,019 0,017 0,012 0,009 0,008
Phase impedance at thermal conditions Z [mΩ/m] 0,103 0,058 0,051 0,047 0,028 0,022 0,019 0,014 0,011 0,009
Neutral resistance R20 [mΩ/m] 0,077 0,045 0,038 0,034 0,018 0,015 0,013 0,009 0,006 0,006
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,132 0,132 0,132 0,119 0,119 0,106 0,078 0,072 0,068 0,037
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,038 0,038 0,014 0,019 0,016 0,014 0,011
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,064 0,064 0,025 0,032 0,025 0,023 0,018
Reactance of the protective bar XPE [mΩ/m] 0,054 0,054 0,054 0,044 0,044 0,032 0,022 0,017 0,016 0,014
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,209 0,176 0,170 0,153 0,137 0,121 0,091 0,081 0,074 0,043
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,126 0,094 0,087 0,072 0,056 0,029 0,032 0,025 0,021 0,016
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,16 0,13 0,12 0,10 0,08 0,04 0,05 0,03 0,03 0,02
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,077 0,071 0,071 0,059 0,058 0,043 0,029 0,023 0,022 0,018
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,222 0,190 0,184 0,164 0,149 0,129 0,096 0,084 0,078 0,046
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,148 0,118 0,113 0,093 0,081 0,052 0,043 0,034 0,030 0,024
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,179 0,147 0,141 0,114 0,101 0,058 0,054 0,042 0,037 0,030
Zero-sequence short-circuit average Ro [mΩ/m] 0,103 0,060 0,050 0,045 0,025 0,020 0,018 0,012 0,009 0,008
resistance phase - N
Zero-sequence short-circuit average Xo [mΩ/m] 0,031 0,023 0,023 0,020 0,019 0,015 0,009 0,008 0,008 0,005
reactance phase - N
Zero-sequence short-circuit average Zo [mΩ/m] 0,107 0,064 0,055 0,050 0,031 0,025 0,020 0,015 0,012 0,009
impedance phase - N
Zero-sequence short-circuit average Ro [mΩ/m] 0,157 0,147 0,144 0,130 0,125 0,111 0,083 0,075 0,070 0,039
resistance phase - PE
Zero-sequence short-circuit average Xo [mΩ/m] 0,062 0,060 0,060 0,049 0,049 0,036 0,024 0,019 0,018 0,015
reactance phase - PE
Zero-sequence short-circuit average Zo [mΩ/m] 0,2 0,2 0,2 0,1 0,1 0,1 0,1 0,1 0,1 0,0
impedance phase - PE
cosϕ = 0,70 74,9 43,9 39,4 36,1 23,3 18,5 14,8 11,1 9,0 7,1
cosϕ = 0,75 78,2 45,5 40,7 37,3 23,7 18,8 15,2 11,4 9,1 7,2
cosϕ = 0,80 81,3 47,0 41,9 38,4 24,0 19,0 15,6 11,6 9,1 7,3
Voltage drop with distribuited load cosϕ = 0,85 84,1 48,3 42,9 39,4 24,1 19,2 15,9 11,8 9,1 7,4
ΔV [V/(m*A)]10-6
cosϕ = 0,90 86,7 49,3 43,6 40,1 24,1 19,1 16,1 11,8 9,0 7,4
cosϕ = 0,95 88,5 49,9 43,9 40,4 23,6 18,8 16,1 11,7 8,7 7,3
cosϕ = 1,00 86,7 47,7 41,3 38,3 20,9 16,6 14,9 10,6 7,5 6,6
Weight (PE 1) p [kg/m] 21,2 26,9 29,6 33,5 50,4 62,2 74,2 97,9 130,3 173,6
Weight (PE 2) p [kg/m] 24,5 30,2 32,9 37,8 54,8 73,6 83,0 108,2 141,6 189,1
Weight (PE 3) p [kg/m] 22,3 28,0 30,7 34,9 51,8 65,9 77,1 101,5 134,2 178,7
Fire load [kWh/m] 4,5 5,5 5,5 8 8,2 10,5 16 19 21 22
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect P [W/m] 192 165 224 339 289 360 529 588 648 901
at nominal current
Ambient temperature min/ [°C] -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70
MAX (daily average)
For temperatures over 55°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
Standard version Extra earth - COPPER XCP Cu 3L+N+50%PE Extra earth - ALUMINUM
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. (tinned copper conductors
available on request)
75
Xtra Compact (XCP-HP)
technical data (continued)
TRIPLE
3P+N+PE+FE SINGLE BAR DOUBLE BAR
BAR
Rated current In [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Overall dimension of the busbars L x H [mm] 125 x 130 125 x 130 125 x 130 125 x 170 125 x 170 125 x 220 125 x 380 125 x 440 125 x 480 125 x 680
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 36 50 70 70 85 120 120 150 150 150
Peak current Ipk [kA] 76 105 154 154 187 264 264 330 330 330
Allowable specific energy for three-phase
I²t [MA²s] 1296 2500 4900 4900 7225 14400 14400 22500 22500 22500
fault
Rated short-time current of the neutral
ICW [kA]rms 22 30 42 42 51 72 72 90 90 90
bar (1 s)
Peak current of the neutral bar Ipk [kA] 45 63 88 88 112 158 158 198 198 198
Rated short-time current of the protective
ICW [kA]rms 22 30 42 42 51 72 72 90 90 90
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 45 63 88 88 112 158 158 198 198 198
Phase resistance at 20°C R20 [mΩ/m] 0,077 0,045 0,038 0,034 0,018 0,015 0,013 0,009 0,006 0,006
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,007 0,006 0,006 0,004
Phase impedance Z [mΩ/m] 0,080 0,048 0,042 0,037 0,023 0,018 0,015 0,011 0,009 0,007
Phase resistance at thermal conditions R [mΩ/m] 0,100 0,055 0,048 0,044 0,024 0,019 0,017 0,012 0,009 0,008
Phase impedance at thermal conditions Z [mΩ/m] 0,103 0,058 0,051 0,047 0,028 0,022 0,019 0,014 0,011 0,009
Neutral resistance R20 [mΩ/m] 0,077 0,045 0,038 0,034 0,018 0,015 0,013 0,009 0,006 0,006
Functional Earth resistance (FE) R20 [mΩ/m] 0,077 0,045 0,038 0,034 0,018 0,015 0,013 0,009 0,006 0,006
Functional Earth reactance (FE) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,007 0,006 0,006 0,004
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,132 0,132 0,132 0,119 0,122 0,108 0,078 0,072 0,068 0,037
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,038 0,038 0,014 0,019 0,016 0,014 0,011
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,064 0,064 0,025 0,032 0,025 0,023 0,021
Reactance of the protective bar XPE [mΩ/m] 0,054 0,054 0,054 0,044 0,044 0,032 0,022 0,017 0,016 0,014
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,126 0,078 0,067 0,060 0,035 0,028 0,024 0,018 0,012 0,011
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,107 0,068 0,059 0,052 0,031 0,022 0,021 0,015 0,011 0,009
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,12 0,07 0,06 0,06 0,03 0,02 0,02 0,02 0,01 0,01
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,077 0,071 0,071 0,059 0,058 0,043 0,029 0,023 0,022 0,018
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,147 0,106 0,098 0,084 0,067 0,051 0,038 0,029 0,025 0,021
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,132 0,098 0,093 0,079 0,066 0,048 0,036 0,028 0,025 0,020
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,140 0,102 0,096 0,081 0,067 0,049 0,037 0,028 0,025 0,021
Zero-sequence short-circuit average
Ro [mΩ/m] 0,103 0,060 0,050 0,045 0,025 0,020 0,018 0,012 0,009 0,008
resistance phase - N
Zero-sequence short-circuit average
Xo [mΩ/m] 0,031 0,023 0,023 0,020 0,019 0,015 0,009 0,008 0,008 0,005
reactance phase - N
Zero-sequence short-circuit average
Zo [mΩ/m] 0,107 0,064 0,055 0,050 0,031 0,025 0,020 0,015 0,012 0,009
impedance phase - N
Zero-sequence short-circuit average
Ro [mΩ/m] 0,103 0,060 0,050 0,045 0,025 0,020 0,018 0,012 0,009 0,008
resistance phase - PE
Zero-sequence short-circuit
Xo [mΩ/m] 0,031 0,023 0,023 0,020 0,019 0,015 0,009 0,008 0,008 0,005
average reactance phase - PE
Zero-sequence short-circuit
Zo [mΩ/m] 0,107 0,064 0,055 0,050 0,031 0,025 0,020 0,015 0,012 0,009
average impedance phase - PE
cosϕ = 0,70 74,9 43,9 39,4 36,1 23,3 18,5 14,8 11,1 9,0 7,1
cosϕ = 0,75 78,2 45,5 40,7 37,3 23,7 18,8 15,2 11,4 9,1 7,2
cosϕ = 0,80 81,3 47,0 41,9 38,4 24,0 19,0 15,6 11,6 9,1 7,3
Voltage drop with distribuited load cosϕ = 0,85 84,1 48,3 42,9 39,4 24,1 19,2 15,9 11,8 9,1 7,4
ΔV [V/(m*A)]10-6
cosϕ = 0,90 86,7 49,3 43,6 40,1 24,1 19,1 16,1 11,8 9,0 7,4
cosϕ = 0,95 88,5 49,9 43,9 40,4 23,6 18,8 16,1 11,7 8,7 7,3
cosϕ = 1,00 86,7 47,7 41,3 38,3 20,9 16,6 14,9 10,6 7,5 6,6
Weight (PE 1) p [kg/m] 23,8 31,1 34,5 39,0 59,9 74,3 88,2 117,3 157,4 200,3
Weight (PE 2) p [kg/m] 27,2 34,5 37,8 43,4 64,3 85,6 96,9 127,6 168,8 215,7
Weight (PE 3) p [kg/m] 24,9 32,2 35,5 40,4 61,3 78,0 91,1 120,8 161,4 204,5
Fire load [kWh/m] 5,625 6,875 6,875 10 10,25 13,125 20 23,75 26,25 27,25
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal
B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect
P [W/m] 192 165 224 339 289 360 529 588 648 901
at nominal current
Ambient temperature min/
[°C] -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70
MAX (daily average)
For temperatures over 55°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support. PE 1 PE 2 PE 3
Standard version Extra earth - COPPER XCP Cu 3L+N+50%PE Extra earth - ALUMINUM
(tinned copper conductors
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. available on request)
76
Xtra Compact (XCP-HP)
technical data
For temperatures over 55°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
Standard version Extra earth - COPPER XCP Cu 3L+N+50%PE Extra earth - ALUMINUM
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. (tinned copper conductors
available on request)
77
Xtra Compact (XCP-HP)
technical data
n XCP-HP CU (3 Conductors)
TRIPLE
3P+PE SINGLE BAR DOUBLE BAR
BAR
Rated current In [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Overall dimension of the busbars L x H [mm] 125 x 130 125 x 130 125 x 130 125 x 170 125 x 170 125 x 220 125 x 380 125 x 440 125 x 480 125 x 680
Rated operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50 50 50 50 50 50 50 50 50 50
Rated short-time current (1 s) ICW [kA]rms 36 50 70 70 85 120 120 150 150 150
Peak current Ipk [kA] 76 105 154 154 187 264 264 330 330 330
Allowable specific energy for three-phase
I²t [MA²s] 1296 2500 4900 4900 7225 14400 14400 22500 22500 22500
fault
Rated short-time current of the protective
ICW [kA]rms 22 30 42 42 51 72 72 90 90 90
circuit (1 s)
Peak current of the protective circuit Ipk [kA] 45 63 88 88 112 158 158 198 198 198
Phase resistance at 20°C R20 [mΩ/m] 0,077 0,045 0,038 0,034 0,018 0,015 0,013 0,009 0,006 0,006
Phase reactance (50hz) X [mΩ/m] 0,023 0,017 0,017 0,015 0,014 0,011 0,007 0,006 0,006 0,004
Phase impedance Z [mΩ/m] 0,080 0,048 0,042 0,037 0,023 0,018 0,015 0,011 0,009 0,007
Phase resistance at thermal conditions R [mΩ/m] 0,100 0,055 0,048 0,044 0,024 0,019 0,017 0,012 0,009 0,008
Phase impedance at thermal conditions Z [mΩ/m] 0,103 0,058 0,051 0,047 0,028 0,022 0,019 0,014 0,011 0,009
Resistance of the protective bar (PE 1) RPE [mΩ/m] 0,130 0,130 0,130 0,118 0,110 0,089 0,078 0,071 0,067 0,040
Resistance of the protective bar (PE 2) RPE [mΩ/m] 0,049 0,049 0,049 0,038 0,038 0,014 0,019 0,016 0,014 0,011
Resistance of the protective bar (PE 3) RPE [mΩ/m] 0,084 0,084 0,084 0,064 0,064 0,025 0,032 0,025 0,023 0,021
Reactance of the protective bar XPE [mΩ/m] 0,054 0,054 0,054 0,044 0,044 0,032 0,022 0,017 0,016 0,014
Resistance of the fault loop (PE 1) Ro [mΩ/m] 0,206 0,174 0,167 0,152 0,128 0,104 0,091 0,080 0,074 0,045
Resistance of the fault loop (PE 2) Ro [mΩ/m] 0,126 0,094 0,087 0,072 0,056 0,029 0,032 0,025 0,021 0,016
Resistance of the fault loop (PE 3) Ro [mΩ/m] 0,16 0,13 0,12 0,10 0,08 0,04 0,05 0,03 0,03 0,03
Reactance of the fault loop (50hz) Xo [mΩ/m] 0,077 0,071 0,071 0,059 0,058 0,043 0,029 0,023 0,022 0,018
Impedance of the fault loop (PE 1) Zo [mΩ/m] 0,220 0,188 0,182 0,163 0,141 0,113 0,095 0,083 0,077 0,049
Impedance of the fault loop (PE 2) Zo [mΩ/m] 0,148 0,118 0,113 0,093 0,081 0,052 0,043 0,034 0,030 0,024
Impedance of the fault loop (PE 3) Zo [mΩ/m] 0,179 0,147 0,141 0,114 0,101 0,058 0,054 0,042 0,037 0,032
Zero-sequence short-circuit average
Ro [mΩ/m] 0,157 0,147 0,144 0,130 0,125 0,111 0,083 0,075 0,070 0,039
resistance phase - PE
Zero-sequence short-circuit average
Xo [mΩ/m] 0,062 0,060 0,060 0,049 0,049 0,036 0,024 0,019 0,018 0,015
reactance phase - PE
Zero-sequence short-circuit average
Zo [mΩ/m] 0,2 0,2 0,2 0,1 0,1 0,1 0,1 0,1 0,1 0,0
impedance phase - PE
cosϕ = 0,70 74,9 43,9 39,4 36,1 23,3 18,5 14,8 11,1 9,0 7,1
cosϕ = 0,75 78,2 45,5 40,7 37,3 23,7 18,8 15,2 11,4 9,1 7,2
cosϕ = 0,80 81,3 47,0 41,9 38,4 24,0 19,0 15,6 11,6 9,1 7,3
Voltage drop with distribuited load cosϕ = 0,85 84,1 48,3 42,9 39,4 24,1 19,2 15,9 11,8 9,1 7,4
ΔV [V/(m*A)]10-6
cosϕ= 0,90 86,7 49,3 43,6 40,1 24,1 19,1 16,1 11,8 9,0 7,4
cosϕ = 0,95 88,5 49,9 43,9 40,4 23,6 18,8 16,1 11,7 8,7 7,3
cosϕ = 1,00 86,7 47,7 41,3 38,3 20,9 16,6 14,9 10,6 7,5 6,6
Weight (PE 1) p [kg/m] 18,7 22,9 24,9 28,0 41,6 52,2 60,3 78,6 103,2 136,2
Weight (PE 2) p [kg/m] 22,0 26,2 28,2 32,4 45,9 63,5 69,0 88,9 114,5 151,6
Weight (PE 3) p [kg/m] 19,7 23,9 25,9 29,5 43,0 55,8 63,1 82,2 107,1 140,4
Fire load [kWh/m] 3,375 4,125 4,125 6 6,15 7,875 12 14,25 15,75 16,75
Degree of protection IP 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65* 55/65*
Insulation material thermal B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F** B/F**
resistance class
Losses for the Joule effect P [W/m] 192 165 224 339 289 360 529 588 648 901
at nominal current
Ambient temperature min/
[°C] -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70 -5/+70
MAX (daily average)
For temperatures over 55°C it will be necessary to derate the busbar and
for ambient temperatures under -5°C contact the technical support.
PE 1 PE 2 PE 3
The data on this page refer to the 50 Hz frequency. For 60 Hz, please contact Legrand. Standard version Extra earth - COPPER XCP Cu 3L+N+50%PE Extra earth - ALUMINUM
(tinned copper conductors
available on request)
78
ACCESSORIES
UNIVERSAL
ACCESSORIES
A range of accessories common to both
product lines, allows you to complete and
Suitable for both customise the path of busbar, according to
the design requirements.
XCP-S and XCP-HP
79
Xtra Compact (XCP)
adapter element (IP68-IP65) and other elements of the range
L(nominal)
300 E A
D=
B
D=
XCP-S
XCP-HP RCP
C
XCP-S 3C - 4C - 5C XCP-HP 3C - 4C - 5C
AL CU L A B C D E AL CU L A B C D E
630–1000 800–1250 1000 400 210 310 105 400 630–1000 800–1250 1000 400 210 310 105 400
1250 1000 400 210 310 125 400
1250 1000 400 250 310 125 400
1600 1000 400 280 310 140 400
1600 1600–2000 1000 400 280 310 140 400
1600–2000 1000 400 250 310 125 400
2000 1000 400 325 310 162.5 400
2000 1000 400 325 310 162.5 400
2500 1000 400 380 310 190 400
2500 1000 400 280 310 140 400
2500 3200 1000 400 460 310 230 400
2500 3200 1000 400 460 310 230 400
3200 4000 1000 400 520 310 260 400 3200 4000 1000 400 520 310 260 400
4000 5000 1000 400 560 310 280 400 4000 5000 1000 400 560 310 280 400
5000 6300 1250 820 670 460 335 500 5000 6300 1250 820 820 460 410 500
XCP includes other elements that allow you to modify the path
of the busbar according to the design requirements.
Note: for more information about the accessories on this page, please contact Legrand
80
Xtra Compact (XCP)
brackets
n Dimensions
Suspension bracket
Edgewise installation
65202001 A (mm)
0
150 Range XCP-S XCP-HP
The brackets enable sturdy installation of the busbar to the system
support structures. Al Cu Al Cu
The recommended installation distance between brackets is 1.5 metres 630 210 – 210 –
Legrand offers suitable bracket solutions certified for any type
of installation, even in the most difficult environments: 800 210 210 210 210
• installations subjected to strong vibrations; 1000 210 210 210 210
• installation in seismic environments
110 1250 250 210 210 210
15
1600 280 250 280 250
Item Suspension Brackets
2000 300 280 300 250
XCP-S XCP-HP M10
Al Cu Al Cu In (A) Type
2500 460 380 460 300
A
65202001 65202001 630 3200 520 460 520 460
60202001 65202001 60202001 65202001 800 4000 560 520 560 520
65202001 65202001 65202001 65202001 1000 hole 9x20 5000 670 560 820 560
65202002 65202001 65202001 65202001 1250
40
190 6300 – 670 – 760
65202003 65202001 65202003 65202002 1600
65222004 65202003 65222004 65202002 2000 edgewise
65222002 65222001 65222002 65202004 2500
65222003 65222002 65222003 65222002 3200
65222004 65222003 65222004 65222003 4000
65222005 65222004 65222007 65222004 5000
65222005 65222006 6300 Flat installation
65202001 65202001 630
65202001 65202001 65202001 65202001 800
0
65202001 65202001 65202001 65202001 1000 150 A (mm)
65202013 65202001 65202001 65202001 1250 Range XCP-S XCP-HP
65202013 65202001 65202013 65202013 1600
Al Cu Al Cu
65202013 60252013 65202013 60252013 2000 flat wise
65202112 65202112 65202112 60252013 2500 630 190 190
65202113 65202112 65202113 65202112 3200 800 190 190 190 190
65202114 65202113 65202114 65202113 4000 1000 190 190 190 190
65202115 65202114 65202116 65202114 5000 1250 315 190 190 190
65202115 65202116 6300 40 40 1600 315 315 315 315
15
81
Xtra Compact (XCP)
brackets
65213711
82
Xtra Compact (XCP)
brackets
n Dimensions
W W
30
30
50
Ø9 x
170
50
84
Ø9
170
84
x
x x
130
170 170
130
210 210
140
240
140
240
30
26
7
5
hole 9x30
hole 9x30
W
Ø9 W
Ø9
174 30 174
Y
Y
50
Z
x
30
84
X
Y
50
84
130
Z
130
Y
160
174
160
375
174
46
160
56
0
375
214
160
214
hole 9x30
hole 9x30
83
Fixing indication
brackets
1.5 m
every
direct any expansion in a precise direction
They therefore operate as a limitation, and
support the traction and compression Standard bracket Standard bracket
forces of the busbar trunking system
EDGEWISE ELEMENT 4
A
EDGEWISE ELEMENT 5
E
5- Fixing for naval installation E
For naval installations always use
a type E bracket every metre E
and a half of the busbar
1.5
m
84
Xtra Compact (XCP)
operating instructions on how to design riser mains
5) Position the IP55 end cover at the end of the riser mains.
In (A) D n° of D n° of D n° of D n° of
max springs max springs max springs max springs
630 11 4 - - 10 4 - -
800 10 4 9 4 10 4 9 4 3
1000 10 4 8 4 9 4 7 4
1250 9 4 7 4 9 4 7 4
1600 10 6 6 4 10 6 6 4
2000 9 6 6 6 9 6 4 4
2500 12 8 9 8 11 8 5 6 2
3200 11 12 7 8 11 12 6 8
4000 10 12 7 12 10 12 6 12
A
5000 7 12 5 12 6 12 5 12
6300 - - 4 12 - - 4 12
C brackets supplied
n Spring preload calculation (H): on request
1
H
*D ≤ Dmax
H
L3
L2
L1
(Kg)
N
Busway x D (m) + total weight of devices (kg)
m
W=
Number of springs A) Floor hanger: use one or more of these suspension brackets,
H = 130 - W depending on the weight of the whole riser mains (including the
3
boxes).
For risers that are shorter than 4 meters, fix to the base with type D
brackets (see page 82), when longer, use type C suspension brackets
n Preload calculation example H (see page 82) respecting the maximum distances (Dmax) indicated in
the tables.
Busway type: 5C - Al (Pe1) B) Standard hanger: use this type of suspension bracket to hang the
In (A): 2000 busbar every 1,5 metres of riser mains.
Dmax (m): 7x0.9 = 6.3 C) Wall hanger: use one or more of these suspension brackets,
D (m): 6 depending on the weight of the whole riser mains (including the
Busway (Kg/m): 29.6 boxes).
Weight box 1 (Kg): 18 For risers that are shorter than 4 meters, fix to the base with type B
Weight box 2 (Kg): 12 brackets (see page 82), when longer, use a type A suspension bracket
(see page 82) respecting the maximum distances (Dmax) indicated in
29.6 x 6 + (18 + 12) 34.6 the tables.
W= = 34.6 kg H = 130 = 118.5 mm
6 3
85
Xtra Compact (XCP)
accessories
n Dimensions 211
B
211
160
H
B
65283101P SF707040 50
165
160
Item End cover IP55
The end cover is XCP-S XCP-HP
50
the component that Al Cu Al Cu
ensures an IP55 165
XCP-S XCP-HP protection degree In (A) H B H B In (A) H B H B
at the end of the 630 130 170 - - 630 130 170 - -
line 800 130 170 130 170 800 130 170 130 170
Al Cu Al Cu In (A)
1000 130 170 130 170 1000 130 170 130 170
67283101P - 67283101P - 630 1250 170 210 130 170 1250 130 170 130 170
67283101P 67283101P 67283101P 67283101P 800 1600 200 240 170 210 1600 200 240 170 210
67283101P 67283101P 67283101P 67283101P 1000 2000 220 260 200 240 2000 220 260 170 210
67283102P 67283101P 67283101P 67283101P 1250 2500 380 420 300 340 2500 380 420 220 260
67283103P 67283102P 67283103P 67283102P 1600 3200 440 480 380 420 3200 440 480 380 420
67283104P 67283103P 67283104P 67283102P 2000 4000 480 520 440 480 4000 480 520 440 480
67393102P 67393101P 67393102P 67283104P 2500 5000 590 630 480 520 5000 740 780 480 520
67393103P 67393102P 67393103P 67393102P 3200 6300 - - 590 630 6300 - - 680 720
67393104P 67393103P 67393104P 67393103P 4000
67393105P 67393104P 67393107P 67393104P 5000 Protective bellow
67393105P - 67393106P 6300 700
15 165 170 170 165 SF707040
Protective bellow
15
400
700
of busbars.
SF707040 Bellow 700X700 mm. H 400 mm
165
SF766040
for outdoor applications, please contact Legrand
600 (A)
540
135 150
700
760 (B)
SF927140
190
150 150
710 (A)
650
190
860
920 (B)
86
Xtra Compact (XCP)
flexible braid connections
n Dimensions
Flexible
holes on busbar
L
side to be specified
Flexible
holes on transformer
B
Flexible braid connections are used to connect the transformer to the side to be specified
connection interface of the busbar when mechanically uncoupling the
two elements is required, to prevent the transmission of vibrations ØD
Item Flexible braid connections A
FC100099 - 630
FC100099 FC100099 800
1
FC200099 FC200099 1000
FC300099 FC300099 1250
FC500099 FC500099 1600
> 750
FC600099 FC600099 2000
FC400099 FC400099 2500
FC500099 FC500099 3200 2
FC600099 FC600099 4000
FC700099 FC700099 5000
- FC600099 6300 3
SIMPLE ATR PE L1
N
Flexible
L2
L3 ≥ 200
200-300
Type 1 Type 2
Cast resin
transformer
Note: for special dimensions, please contact Legrand.
U
PE
L
H A ≤ 3000
B C D E F
A
L3 L2 Pen (N) L1
L3 Pen (N) L2 L1
Possible configurations for
L1 L2 Pen (N) L3
L1 Pen (N) L2 L3
connections to transformers
ATR dimensions
Although designed ad-hoc, ATR elements are still subjected to
construction limits. Below are the summarizing tables indicating
these values
88
Xtra Compact (XCP)
technical information
n The system: the Legrand transformer advantage n The system:the Legrand XL³ advantage
PRO N ° 070B
Signatory of EA, IAF and ILAC
Mutuai Recognltion Agreements
Authorized Signature: Virginio Scarioni
Certificate of conformity
MOD 007 pag 1 Revisione 07 for the connection between
transformer and busbar
mounted on CRT box
89
TAP - OFF BOXES
TAP-OFF BOXES
FROM 32 TO 630 A
The new range Available in 2 different materials: fiberglass
or metal sheet, both characterised by a
of universal tap-off simple installation and fast connection
thanks to the new layout of the hooks that
boxes suitable for both offer safety and speed of assembly
90
Xtra Compact (XCP)
FIBERGLASS tap-off boxes - 32 A to 250 A : plug-in type
191 68
132
159
258
191
159
159
191
84
50485101 50485231 50485343
239
75
239 470 23 302 470
IP55. 470
158 23 302 470 23
Equipped with a sectioning cover. Can be installed and removed when
93
the busbar is energized.
93
251
273
251
273
To be applied on elements with any rating, with tap-off outlets.
273
251
237
181
Its rating is from 32 A to 250 A.
181
Type 2 empty / with fuse carriers Type 2 DPX³ ready
Item Tap-off boxes DPX3 ready*
238 22
Prepared for Legrand MCCB (not provided) and Type 2 empty /with fuse carriers
available in 2 versions, one with hinged cover
and one with completely removable cover.
159
191
Supplied "ready for" DPX3, with rotary handle already
installed on the cover and rotary mechanism inside the box. With fuse carriers terminal
With terminal
Empty fuse carriers
dim. terminaldim. Terminal dim.
In (A) Type Empty terminal dim. 239 Terminal dim.
dim. 470 23 302 470
L1NL2 L3 L1Pe
L2 L3 N FE
50485231 63 2 L1 L2 L3 N FE PeL1 L2 L3 N FE PeL1 L2 L3 FE
L1 L2 L3 N FE Pe N FE Pe
93
50485232 160 2
251
273
50485333 250 3
181
Tap-off boxes with fuse carriers Type 1
Type 1
Type 3 DPX³3 ready
Type 3 DPX³ ready
Equipped with fuse carriers. Fuses not included. Type 3 DPX ready
For the selection of fuses, see Legrand catalogue 251 410
251 410 1
193.62
201 68
201 68
In (A) Type Fuse carrier
60
73
268
169
268
50485101 32 1 3xCH10 With fuse carriers terminal
169
Empty terminal dim. Terminal dim.
dim.
50485202 63 2 3xCH22 135
L1 L2 L3 N FE Pe N FE Pe L1 135
L2 L3 L1 L2 L3 N FE
50485203 125/160 2 3xNH00 312 665 23
312 665 23
50485305 250 3 3xNH2
216
139
139
351
373
351
373
135
169
201
665 23
191
470 50485314
23 250302
A - 12+12 module 470 3 23
50485324 250 A - blind cover 3
373 351
373
93
Terminal
273
251
351
dim.
L1 L2 L3 N FE Pe
Terminal dim.
Total dimensions with cover open (mm)
Type2
Empty terminal dim. Type3
With fuse carriers terminal
dim.
With fuse carriers terminal
Terminal dim.
dim. L1 L2 L3 N FE Pe L1 L2 L3 N FE Pe
L1 L2 L3 N FE Pe
R48
R6
808
Pe N FE Pe L1 L2 L3
R1
75
603
227
0
86
max 10 mm2
169
91
351
373
L1 L2 L3 N FE Pe
Xtra Compact (XCP)
METAL tap-off box Type 1 - 63 A to 160 A : plug-in type
n Dimensions
Type 1 (63 - 125 - 160 A)
Box dimensions (mm)
DPX3 ready 199 242
68
50484002
163
196
264
IP55.
Equipped with a sectioning cover. Can be installed and removed
when the busbar is energized.
To be applied on elements with any rating, with tap-off outlets.
These are the smallest metal tap-off boxes available and the rating 504
is from 63 A to 160 A. 481 24
324
Item Tap-off boxes DPX3 ready*
3 4
96
Prepared for Legrand MCCB (not provided) and
278
280
available in 2 versions, one with hinged cover and
184
one with completely removable cover. Supplied "ready
for" DPX3, with rotary handle already installed on
the cover and rotary mechanism inside the box.
40
In (A)
With fuse carriers 125/160 A
50481721 63/125/160 A
196 196 40
50481731 63/125/160 A - removable cover
163 163
236 236
Tap-off boxes with fuse carriers
Equipped with fuse carriers. Fuses not included.
For the selection of fuses, see Legrand catalogue
In (A) Fuse carrier
280 280
Tap-off boxes with switch fuse
Equipped with a switch disconnector (AC23) and a
fuse carrier. The disconnector switch is operated through
a rotary handle on the cover (not shown in the picture).
N.B. Cover with AC21A disconnection: it is not
possible to open, close, install or pull out the tap- Empty
off box if the switch is in “ON” position. 40
Fuses not included. For the selection of
163
196
236
fuses, see Legrand catalogue
In (A)
50481621 63 A
50481622 125 A 504
50481623 160 A 297 481 24
50481631 63 A - removable cover
50481632 125 A - removable cover
50481633 160 A - removable cover
280
278
1,5 or 70 mm2
or
#16 #2/0 AWG 12 12
36
SolidSolid M6 M8
or (0,472’’)
(0,472’’)
588
Terminal dimensions type 1 - empty (mm) Terminal dimensions type 1 - fuse carriers (mm)
L1 L2 L3
L1 L2 L3 N FE Pe N FE Pe M8 M8
max
max ø 14 ø 14 Flexibile
Flexibile max
max ø 14 ø 14 Flexibile
Flexibile M8
1,5 1,570 mm 702 mm2 1,5 1,570 mm 702 mm2
max ø 14 Flexibile
#16 #16 #2/0 #2/0
AWGAWG max ø 14 Flexibile
#16 #16 #2/0 #2/0
AWGAWG
1,5 or 70 mm2
or 1,5 or 70 mm2
or
SolidSolid AWG
#16 #2/0 12 12 #16 Solid
Solid #2/0 AWG 12 12
or (0,472’’)
(0,472’’) or (0,472’’)
(0,472’’)
1,5 1,595 mm 952 mm2 12 1,5 1,595 mm 952 mm2
Solid
#16 #16 #4/0 #4/0
AWGAWG(0,472’’) Solid 12
#16 #16 #4/0 #4/0
AWGAWG (0,472’’)
1,5 95 mm2 1,5 95 mm2 22 mm
22 mm
#16 #4/0 AWG #16 #4/0 AWG
* DPX3: MCCB (Moulded Case Circuit Breaker) not mounted and not supplied 22 mm
92
Xtra Compact (XCP)
METAL tap-off box Type 2 - 250 A: plug-in type
n Dimensions
Type 2 (250A) 210
210 351
351
23668 68
68
DPX ready 3
203203
203
236236
304
304304
624
624
365
365 601
601
624 24
24
50481732
365 601 24
IP55.
241 159159
159
Equipped with a sectioning cover. Can be installed
and removed when the busbar is energized.
397397
397
400
400400
492492
492
To be applied on elements with any rating, with tap-off outlets.
241241
These are the medium size metal tap-off boxes available and the rating
is 250 A.
67
67
and one with completely removable cover.
In (A)
203
236
203
304
236
304
50481722 250 A
50481724 250 A - DRXHP ready
50481732 250 A - removable cover 624 624
50481734 250 A - DRXHP ready 365 365 601 601 23 23
removable cover
Tap-off boxes with fuse carriers
159
159
400
400
the selection of fuses, see Legrand catalogue
241
241
40
236236 40 40
Tap-off boxes with switch fuse
Empty and with
Equipped with a switch disconnector (AC23) and a fuse
203
236
203
203276
276276
fuse carriers
carrier. The disconnector switch is operated through a
rotary handle on the cover (not shown in the picture).
N.B. Cover with AC21A disconnection: it is not
possible to open, close, install or pull out the
tap-off box if the switch is in “ON” position.
Fuses not included. For the selection of 624 624
fuses, see Legrand catalogue 601 601
624 24 24
337 337
In (A) 601 24
337
50481624 250 A - switch fuse
50481634 250 A - switch fuse
400
492
400400
492492
removable cover
Empty Tap-off boxes
In (A)
50484005 250
Terminal dimensions type 2 Terminal dimensions type 2 Total dimensions with cover open (mm)
DPX3 ready and empty (mm) fuse carriers (mm)
L1 L3
L1 L2 L2 N
L3FE
N Pe
FE Pe L1 L3
L1 L2 L2 N
L3FE
N Pe
FE Pe 50 909
L1 L2 L3 N FE Pe L1 L2 L3 N FE Pe 50 712
1:8 M12
1:8 M12
R4
R5
36
60
752
588
max 10
maxø108.5 32 mm
ø 8.528.5 32 mm
max
max 28.5
* DPX3: MCCB (Moulded Case Circuit Breaker) not mounted and not supplied
Rotary handles for DPX3 already mounted
93
Xtra Compact (XCP)
METAL tap-off box Type 3 - 400 A to 630 A : plug-in type
1 2 2 n Dimensions 3 3 4
Type 3 (400 - 630 A)
Box dimensions (mm) 281 281 475 475
281 475
307 67
307307 67 67
DPX ready3
274
374
274274
374374
795 795
433 433 772 795
772 23 23
50481733 433 772 23
197
263263 197197
IP55.
Equipped with a sectioning cover. Can be installed
460
542
460460
542542
and removed when the busbar is energized.
263
To be applied on elements with any rating, with tap-off outlets.
These are the largest size metal tap-off boxes available and the rating
is 400 A or 630 A.
47.5
47.5
Prepared for Legrand MCCB (not provided) and
available in 2 versions, one with hinged cover With fuse carriers
and one with completely removable cover.
274
307
354
274
307
354
In (A)
460
542
460
542
50484026 630 3xNH3
Tap-off boxes with switch fuse
Equipped with a switch disconnector (AC23) and a
fuse carrier. The disconnector switch is operated
47.5
47.5
through a rotary handle on the cover (not shown in
the picture). Empty
N.B. Cover with AC21A disconnection: it is not possible
to open, close, install or pull out the tap-off
box if the switch is in “ON” position. Fuses not included.
274
307
354
274
307
354
For the selection of fuses, see Legrand catalogue
In (A)
460
542
542
50484006 630 A
A A
Terminal dimensions Terminal dimensions Terminal dimensions type 3 Total dimensions with cover open (mm)
L3
L3 N
N FE
FE Pe
PeL1
L1 3L2
type L3
L3 N
L2- fuse FE
FE Pe
Pe L1
Ncarriers
L1 L2
L2 L3
(mm) L3 N FE
NL1 Pe
FEL2 type
PeL3 N 3FE
- empty (mm) L1 -L2
DPX
L3 Nready
3
(mm)
FE Pe
L2 Pe
963
L1 L3 N FE
50 Pe 909 L1 L2L1L3L2
N L3
FE N
PeFE Pe L1 L2 L3 N FE Pe
N FE Pe 50 L1 L2 L3712 L1 L2 L3 N FE Pe N FE Pe L1 L2 L3
M12 M12
M12 M12 1 : 8 M12
M12 M12
R4
R5
R7
36
1036
60
752
74
588
max 16
max 16 max 10
D11 32 mm 38 mm max 16 max 16
D11 32 mm 38 mm ø 8.5 30 mm
max 32 D11 38 mm D11 38 mm
max 32 max 28.5
max 32 max 32
* DPX3: MCCB (Moulded Case Circuit Breaker) not mounted and not supplied
Rotary handles for DPX3 already mounted
94
Xtra Compact (XCP)
tap-off box on the junction - 125 A to 1250 A: bolt-on type
n Dimensions
From 125 A to 1250 A
cable input
(F x G)
C
67281931P
B
IP55
Can be installed on elements of any rating, with or
without tap-off outlets
Description
G
67281933P Empty bolt-on box for 190 mm single bar
67281934P Empty bolt-on box for 210 mm single bar
67391931P Empty bolt-on box for 2 x 120 mm bars H D F
67391932P Empty bolt-on box for 2 x 160 mm bars
67391933P Empty bolt-on box for 2 x 190 mm bars I L
67391934P Empty bolt-on box for 2 x 210 mm bars
H - Usable internal space
L - Metal internal plate
A
In (A) A B C D E F G H I L
125
250 365 630 270 115 630 290 180 465 142 260
400
630 400 750 280 115 675 290 180 585 227 295
800
1000 450 1050 300 115 745 380 210 885 254 545
1250
100
PP
5A 250 3.3 20 30 M8
18
11 400 3.3 20 30 M8
QQ
5B 630 5.3 20 30 M8
R 800 6.2 20 30 M8
R 5C 1000 6.2 20 30 M8
Phase/Neutral terminal Earth Terminal
Thread M8 1250 6.2 20 30 M8
WARNING
The bolt-on boxes are to be installed when the busbar is
disconnected and not energized
95
Tap-off box installation
example diagram
n Technical information
Not all boxes can be installed in any position
The following figures show where the various Plug-in/Bolt-on boxes may be installed on elements with standard setup
T1M T1P T1M T1P T1M T1P T1M T1P T1M T1P T1M T1P
T2M T2P T2M T2P T2M T2P T2M T2P T2M T2P T2M T2P
T3M T3P T3M T3P T3M T3P T3M T3P
T1M T1P T1M T1P T1M T1M T1P T1M T1P T1M T1P
T2M T2P T2M T2P T1P T2M T2P T2M T2P
T3M T3P T3M T3P T2M T2P T3M T3P T3M T3P T2M T2P
T1M T1P T1M T1P T1M T1P T1M T1P T1M T1P
T2M T2P T2M T2P T2M T2P T.O. BOX BOLT ON T2M T2P T2M T2P
T3M T3P T3M T3P T3M T3P
96
OPERATING
INFORMATION
Suggestions for the Operational information and advice for the
correct design and construction of the busbar
design and installation trunking system
of the busbar
97
Xtra Compact (XCP)
suggestions for the project development
5. Degree of protection:
IP55 (standard)
IP65 (only for transport of Energy)
6. Paint:
RAL7035 (standard)
Different RAL
colour on request …………
7. Neutral section:
100% XCP (standard)
200% XCP 2N
8. Nominal ambient
temperature:
35°C (standard)
Other on request…………
98
Xtra Compact (XCP)
installation guidelines
(fig.1)
Make sure that the earth plate of the straight element is inserted
(fig.2) behind the front plate of the junction monobloc (Fig.2)
m
0m
27 The positioning pin on the monobloc should be fitted
into the corresponding slot on the earth plate
The bolt that tightens the monobloc has a second head which is
used when carrying out operations or inspections on the line
In standard execution
the self-shearing bolt is
(fig.4)
85 N•m fitted on the opposite
side of the Neutral.
(fig.5)
IP55
(fig.6)
99
Xtra Compact (XCP)
mechanical design precautions
Below are some precautions that may be useful to avoid problems during the assembly, which we recommend should be taken
into account during the design
100
300
100
Wall Wall
300
When there are tap-off units along the busbars, the minimum distances depend on the dimensions of the tap-offs selected
Wall Ceiling
* When
300
Wall Ceiling
100
100
Minimum installation
300
80
Minimum installation
Wall Ceiling distance when there are
several overlapped lines
100
100
300
Wall
60
100
Xtra Compact (XCP)
mechanical design precautions
The minimum distance from the junction to the point the busbar crosses the wall or other structure must be at least 200 mm, to ensure the junction
of the junctions
In case plug-in boxes and fire barriers are required on the same element, the minimum distance between the box and the partition must be taken
into account, at the same time allowing for the necessary free space in the junction area and the minimum distance between the distribution outlet
and the start of the element
By taking all these variables into account, it is possible to obtain the minimum size of the element in order be able to fit the partition and the
plug-in box. The tables that follow summarise the minimum sizes
200
200
200
Refered to Aluminium
X 630 200
n Connection to the board n Short circuit withstand
As a rule, the manufacturer of the board is responsible for The short circuit withstand of the connection elements depends on
connecting the connection element and the distribution busbars the connection of the busbars inside the distribution board
inside the board The declaration of short circuit withstand for the system busbars
On request Legrand X may develop and supply 630the connections,
200 may only be supplied by the board manufacturer. When using
subject to all necessary details being available Legrand boards and Legrand busbar trunking systems it will be
All types of connections must be agreed and checked with the possible to obtain a short circuit certification
board manufacturer
101
Xtra Compact (XCP)
measurement of special element lengths
te A
quo
B
Q1
A
N1
2 3 Horizontal elbow
Q2 the exact length of the piece to be ordered can be
determined by measuring the dimensions Q1 and
Q2 (as shown in the picture) and then by subtracting
from each dimension the values indicated below.
XCP-S: A = Q1 - 75 mm
B = Q2 - 75 mm
XCP-HP: A = Q1 - 72.5 mm
B = Q2 - 72.5 mm
102
Xtra Compact (XCP)
Insulation technology
%
So, thanks to the double insulating layer technology together with layer
00
the sandwich construction, XCP range is fully protected
>1
from any problem that can be occur from humidity.
XCP desgin
level
(more than
2nd double than
layer required)
Required
Insulation level
level
1st 1st
layer layer
103
for example : xxxxxxx
NOTES TM
for example : xxxxxxx TM
xxxxxxxx xxxxxxxx
104
FOLLOW US
ALSO ON
legrand.com
youtube.com/user/legrand
twitter.com/legrand_news
pinterest.com/legrandgroup
World Headquarters
and International Department
87045 Limoges Cedex - France
% : + 33 (0) 5 55 06 87 87
Fax: + 33 (0) 5 55 06 74 55
AD-EXLGXCP21C/GB - 03/2021