Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL

OSLA HOMES HOTEL


LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-1

PAD/PILE FOOTING RESULTS

F1
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C1 1 -111.7 -0.2 3.6 G+Q *F
2 -97.6 -0.2 3.1 (G+Q)P11 *F
3 -106.8 -0.1 3.8 (G+Q)P12 *F
4 -88.3 -0.1 2.5 (G+Q)P21 *F
5 -94.0 -0.2 2.5 (G+Q)P22 *F
6 -96.7 -0.1 3.1 (G+Q)P31 *F
7 -113.2 -0.1 3.6 (G+Q)P32 *F
8 -88.5 -0.1 2.6 (G+Q)P41 *F
9 -93.4 -0.2 2.5 (G+Q)P42 *F
10 -97.2 -0.2 3.2 (G+Q)P51 *F
11 -106.7 -0.1 3.8 (G+Q)P52 *F
12 -91.0 4.3 2.8 G+Q+Nx
13 -100.6 -4.6 3.3 G+Q-Nx
14 -75.5 0.1 14.5 G+Q+Ny
15 -116.1 -0.3 -8.3 G+Q-Ny
Column: 1C1
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 15 (G+Q-Ny)
N = -116.1 kN Mx = 0.3 kN.m
My = 8.3 kN.m
Footing Dimensions:
Lx = 1000.0 mm Ly = 1000.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 190.185 kN/m2 S-min = 86.504 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 15.2 kN.m/m
K/K' = 0.03 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.22 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.03 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 130.0 kN V-eff = 142.5 kN
v = 0.41 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 10.9 kN.m/m
K/K' = 0.02 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.20 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.01 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 130.0 kN V-eff = 142.5 kN
v = 0.41 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.41 N/mm2

F2
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C2 1 -414.8 -1.4 -7.6 G+Q *F
2 -373.6 -0.7 -7.9 (G+Q)P11 *F
3 -375.3 -0.5 -7.6 (G+Q)P12 *F
4 -395.8 -1.8 -6.0 (G+Q)P21 *F
5 -305.9 -1.1 -5.6 (G+Q)P22 *F
6 -414.5 -1.4 -7.6 (G+Q)P31 *F
7 -375.0 -0.6 -7.7 (G+Q)P32 *F
8 -397.5 -1.8 -6.5 (G+Q)P41 *F
9 -305.6 -1.1 -5.6 (G+Q)P42 *F
10 -373.6 -0.8 -7.9 (G+Q)P51 *F
11 -375.3 -0.5 -7.6 (G+Q)P52 *F
12 -343.9 14.1 -6.6 G+Q+Nx
13 -367.1 -16.4 -6.5 G+Q-Nx
14 -346.8 -1.4 -0.6 G+Q+Ny
15 -364.2 -0.9 -12.5 G+Q-Ny
Column: 1C2
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 13 (G+Q-Nx)

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-2

N = -367.1 kN Mx = 16.4 kN.m


My = 6.5 kN.m
Footing Dimensions:
Lx = 1400.0 mm Ly = 1400.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 259.839 kN/m2 S-min = 159.633 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 37.9 kN.m/m
K/K' = 0.08 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.41 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.15 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 398.5 kN V-eff = 418.5 kN
v = 1.22 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 66.9 kN V-eff = 86.9 kN
v = 0.05 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 46.0 kN.m/m
K/K' = 0.10 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.46 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.20 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 398.5 kN V-eff = 418.5 kN
v = 1.22 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 66.9 kN V-eff = 74.2 kN
v = 0.04 N/mm2 < vc = 0.41 N/mm2

F3
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C3 1 -686.8 -0.3 -17.6 G+Q *F
2 -637.8 -1.2 -15.7 (G+Q)P11 *F
3 -606.0 -0.2 -17.7 (G+Q)P12 *F
4 -636.7 0.5 -15.6 (G+Q)P21 *F
5 -499.5 -0.4 -12.7 (G+Q)P22 *F
6 -644.8 0.5 -17.7 (G+Q)P31 *F
7 -604.7 -0.3 -17.7 (G+Q)P32 *F
8 -681.9 -0.3 -16.0 (G+Q)P41 *F
9 -499.2 -0.4 -12.6 (G+Q)P42 *F
10 -637.2 -1.2 -15.7 (G+Q)P51 *F
11 -606.0 -0.2 -17.7 (G+Q)P52 *F
12 -589.4 15.9 -15.1 G+Q+Nx
13 -588.0 -16.5 -15.1 G+Q-Nx
14 -581.7 -0.3 -9.3 G+Q+Ny
15 -595.7 -0.3 -20.9 G+Q-Ny
Column: 1C3
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 1 (G+Q *F)
N = -686.8 kN Mx = 0.3 kN.m
My = 17.6 kN.m
Footing Dimensions:
Lx = 1800.0 mm Ly = 1800.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 252.957 kN/m2 S-min = 215.998 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 71.1 kN.m/m
K/K' = 0.15 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.54 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.29 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 745.6 kN V-eff = 765.5 kN
v = 2.23 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 374.9 kN V-eff = 375.3 kN
v = 0.21 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 79.2 kN.m/m
K/K' = 0.18 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-3

v = 0.60 N/mm2 < v-max = 4.00 N/mm2


Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.35 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 745.6 kN V-eff = 765.5 kN
v = 2.23 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 374.9 kN V-eff = 394.8 kN
v = 0.22 N/mm2 < vc = 0.41 N/mm2

F4
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C4 1 -685.7 -0.2 -16.7 G+Q *F
2 -637.0 0.5 -14.9 (G+Q)P11 *F
3 -605.8 -0.1 -16.7 (G+Q)P12 *F
4 -637.3 -0.9 -15.0 (G+Q)P21 *F
5 -499.2 -0.3 -12.0 (G+Q)P22 *F
6 -635.9 -0.9 -14.7 (G+Q)P31 *F
7 -604.7 -0.2 -16.7 (G+Q)P32 *F
8 -644.2 0.6 -17.0 (G+Q)P41 *F
9 -499.0 -0.3 -12.0 (G+Q)P42 *F
10 -679.5 -0.4 -14.7 (G+Q)P51 *F
11 -605.8 -0.1 -16.7 (G+Q)P52 *F
12 -587.6 15.9 -14.3 G+Q+Nx
13 -587.9 -16.3 -14.3 G+Q-Nx
14 -580.4 -0.2 -8.5 G+Q+Ny
15 -595.1 -0.2 -20.0 G+Q-Ny
Column: 1C4
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 1 (G+Q *F)
N = -685.7 kN Mx = 0.2 kN.m
My = 16.7 kN.m
Footing Dimensions:
Lx = 1800.0 mm Ly = 1800.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 251.528 kN/m2 S-min = 216.759 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 70.7 kN.m/m
K/K' = 0.15 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.54 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.28 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 744.6 kN V-eff = 763.3 kN
v = 2.22 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 374.4 kN V-eff = 374.7 kN
v = 0.21 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 78.9 kN.m/m
K/K' = 0.18 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.60 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.35 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 744.6 kN V-eff = 763.3 kN
v = 2.22 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 374.4 kN V-eff = 393.2 kN
v = 0.22 N/mm2 < vc = 0.41 N/mm2

F5
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C5 1 -680.0 -0.2 -15.9 G+Q *F
2 -632.2 -1.1 -14.2 (G+Q)P11 *F
3 -601.1 -0.1 -15.9 (G+Q)P12 *F
4 -632.5 0.6 -14.4 (G+Q)P21 *F
5 -495.2 -0.3 -11.5 (G+Q)P22 *F
6 -674.8 -0.2 -13.9 (G+Q)P31 *F
7 -600.0 -0.2 -15.9 (G+Q)P32 *F
8 -630.2 -0.9 -14.0 (G+Q)P41 *F
9 -495.2 -0.3 -11.5 (G+Q)P42 *F
10 -639.8 0.4 -16.6 (G+Q)P51 *F
11 -601.1 -0.1 -15.9 (G+Q)P52 *F
12 -582.6 16.0 -13.6 G+Q+Nx
13 -583.1 -16.3 -13.7 G+Q-Nx

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-4

14 -575.4 -0.2 -7.9 G+Q+Ny


15 -590.4 -0.2 -19.4 G+Q-Ny
Column: 1C5
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 1 (G+Q *F)
N = -680.0 kN Mx = 0.2 kN.m
My = 15.9 kN.m
Footing Dimensions:
Lx = 1700.0 mm Ly = 1700.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 277.502 kN/m2 S-min = 238.095 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 68.0 kN.m/m
K/K' = 0.14 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.55 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.27 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 729.6 kN V-eff = 747.5 kN
v = 2.17 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 322.0 kN V-eff = 322.3 kN
v = 0.18 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 76.4 kN.m/m
K/K' = 0.17 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.62 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.34 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 729.6 kN V-eff = 747.5 kN
v = 2.17 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 322.0 kN V-eff = 339.9 kN
v = 0.19 N/mm2 < vc = 0.41 N/mm2

F6
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C6 1 -760.9 -1.3 -20.1 G+Q *F
2 -696.4 -0.3 -18.2 (G+Q)P11 *F
3 -664.6 -0.8 -20.1 (G+Q)P12 *F
4 -707.4 -1.9 -17.5 (G+Q)P21 *F
5 -553.2 -1.1 -14.4 (G+Q)P22 *F
6 -703.8 -0.2 -20.3 (G+Q)P31 *F
7 -663.6 -0.9 -20.1 (G+Q)P32 *F
8 -753.7 -1.2 -18.2 (G+Q)P41 *F
9 -553.2 -1.0 -14.4 (G+Q)P42 *F
10 -707.3 -2.1 -17.3 (G+Q)P51 *F
11 -664.6 -0.8 -20.1 (G+Q)P52 *F
12 -654.2 15.0 -17.1 G+Q+Nx
13 -650.2 -17.2 -17.3 G+Q-Nx
14 -644.5 -1.1 -11.5 G+Q+Ny
15 -659.9 -1.1 -22.9 G+Q-Ny
Column: 1C6
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 1 (G+Q *F)
N = -760.9 kN Mx = 1.3 kN.m
My = 20.1 kN.m
Footing Dimensions:
Lx = 1800.0 mm Ly = 1800.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 279.310 kN/m2 S-min = 235.397 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 78.5 kN.m/m
K/K' = 0.16 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.60 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.32 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 818.4 kN V-eff = 841.0 kN
v = 2.44 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 411.5 kN V-eff = 413.0 kN

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-5

v = 0.23 N/mm2 < vc = 0.40 N/mm2


Y Dir: Footing Design: M = 87.4 kN.m/m
K/K' = 0.20 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.67 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.39 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 818.4 kN V-eff = 841.0 kN
v = 2.44 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 411.5 kN V-eff = 434.1 kN
v = 0.25 N/mm2 < vc = 0.41 N/mm2

F7
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C7 1 -428.6 3.9 -8.7 G+Q *F
2 -374.8 2.7 -9.0 (G+Q)P11 *F
3 -375.8 2.9 -8.7 (G+Q)P12 *F
4 -421.7 4.0 -7.0 (G+Q)P21 *F
5 -315.4 2.7 -6.3 (G+Q)P22 *F
6 -374.7 2.8 -8.8 (G+Q)P31 *F
7 -375.5 2.8 -8.7 (G+Q)P32 *F
8 -429.3 4.0 -9.0 (G+Q)P41 *F
9 -315.4 2.7 -6.3 (G+Q)P42 *F
10 -421.2 3.8 -6.9 (G+Q)P51 *F
11 -375.8 2.9 -8.7 (G+Q)P52 *F
12 -378.7 17.5 -7.3 G+Q+Nx
13 -356.1 -10.7 -7.6 G+Q-Nx
14 -358.7 3.3 -1.7 G+Q+Ny
15 -376.1 3.4 -13.3 G+Q-Ny
Column: 1C7
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 12 (G+Q+Nx)
N = -378.7 kN Mx = 17.5 kN.m
My = 7.3 kN.m
Footing Dimensions:
Lx = 1400.0 mm Ly = 1400.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 269.863 kN/m2 S-min = 161.439 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 39.3 kN.m/m
K/K' = 0.08 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.42 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.15 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 409.7 kN V-eff = 431.0 kN
v = 1.25 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 68.8 kN V-eff = 90.1 kN
v = 0.05 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 47.8 kN.m/m
K/K' = 0.11 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.48 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.21 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 409.7 kN V-eff = 431.0 kN
v = 1.25 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 68.8 kN V-eff = 77.0 kN
v = 0.04 N/mm2 < vc = 0.41 N/mm2

F8
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C8 1 -74.6 -0.7 -0.3 G+Q *F
2 -70.0 -0.6 -0.3 (G+Q)P11 *F
3 -69.4 -0.6 -0.3 (G+Q)P12 *F
4 -68.3 -0.5 -0.2 (G+Q)P21 *F
5 -71.2 -0.6 -0.1 (G+Q)P22 *F
6 -70.8 -0.6 -0.2 (G+Q)P31 *F
7 -73.7 -0.7 -0.3 (G+Q)P32 *F
8 -69.4 -0.6 -0.2 (G+Q)P41 *F

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-6

9 -71.6 -0.6 -0.1 (G+Q)P42 *F


10 -69.8 -0.6 -0.2 (G+Q)P51 *F
11 -69.4 -0.6 -0.3 (G+Q)P52 *F
12 -1.7 7.8 -0.1 G+Q+Nx
13 -126.2 -8.9 -0.4 G+Q-Nx
14 -77.1 -0.4 11.1 G+Q+Ny
15 -50.8 -0.7 -11.6 G+Q-Ny
Column: 1C8
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 13 (G+Q-Nx)
N = -126.2 kN Mx = 8.9 kN.m
My = 0.4 kN.m
Footing Dimensions:
Lx = 1300.0 mm Ly = 1300.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 122.356 kN/m2 S-min = 71.853 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 17.5 kN.m/m
K/K' = 0.04 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.19 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.07 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 158.3 kN V-eff = 168.5 kN
v = 0.49 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 8.6 kN V-eff = 18.8 kN
v = 0.01 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 15.3 kN.m/m
K/K' = 0.03 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.18 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.06 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 158.3 kN V-eff = 168.5 kN
v = 0.49 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 8.6 kN V-eff = 9.0 kN
v = 0.01 N/mm2 < vc = 0.41 N/mm2

F9
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C9 1 -233.4 -3.6 -1.8 G+Q *F
2 -197.4 -3.1 -1.9 (G+Q)P11 *F
3 -232.9 -3.6 -1.8 (G+Q)P12 *F
4 -233.9 -3.5 -1.5 (G+Q)P21 *F
5 -209.1 -3.1 -1.3 (G+Q)P22 *F
6 -236.3 -3.6 -1.8 (G+Q)P31 *F
7 -233.8 -3.6 -1.9 (G+Q)P32 *F
8 -228.5 -3.3 -1.5 (G+Q)P41 *F
9 -208.9 -3.1 -1.3 (G+Q)P42 *F
10 -198.0 -3.2 -1.8 (G+Q)P51 *F
11 -232.9 -3.6 -1.8 (G+Q)P52 *F
12 -250.8 14.1 -1.6 G+Q+Nx
13 -149.2 -20.3 -1.6 G+Q-Nx
14 -193.2 -2.9 4.7 G+Q+Ny
15 -206.8 -3.3 -7.9 G+Q-Ny
Column: 1C9
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 12 (G+Q+Nx)
N = -250.8 kN Mx = 14.1 kN.m
My = 1.6 kN.m
Footing Dimensions:
Lx = 1200.0 mm Ly = 1200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 251.167 kN/m2 S-min = 142.002 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 24.2 kN.m/m
K/K' = 0.05 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.32 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.07 N/mm2 < vc = 0.40 N/mm2

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-7

Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)


Vt = 271.3 kN V-eff = 288.9 kN
v = 0.84 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 17.6 kN
v = 0.01 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 31.2 kN.m/m
K/K' = 0.07 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.37 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.12 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 271.3 kN V-eff = 288.9 kN
v = 0.84 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 2.0 kN
v = 0.00 N/mm2 < vc = 0.41 N/mm2

F10
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C10 1 -472.9 -0.6 -1.0 G+Q *F
2 -426.7 0.9 -1.0 (G+Q)P11 *F
3 -473.7 -0.5 -1.0 (G+Q)P12 *F
4 -431.4 -1.7 -1.0 (G+Q)P21 *F
5 -431.2 0.3 -0.7 (G+Q)P22 *F
6 -475.1 -0.5 -1.0 (G+Q)P31 *F
7 -430.4 0.2 -0.7 (G+Q)P32 *F
8 -429.1 -1.6 -1.0 (G+Q)P41 *F
9 -473.7 -0.4 -1.0 (G+Q)P42 *F
10 -426.8 0.9 -1.0 (G+Q)P51 *F
11 -473.7 -0.5 -1.0 (G+Q)P52 *F
12 -405.9 15.5 -0.9 G+Q+Nx
13 -404.8 -16.4 -0.8 G+Q-Nx
14 -414.7 -0.3 3.1 G+Q+Ny
15 -396.0 -0.6 -4.8 G+Q-Ny
Column: 1C10
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 6 ((G+Q)P31 *F)
N = -475.1 kN Mx = 0.5 kN.m
My = 1.0 kN.m
Footing Dimensions:
Lx = 1400.0 mm Ly = 1400.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 268.149 kN/m2 S-min = 261.515 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 40.5 kN.m/m
K/K' = 0.08 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.42 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.15 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 503.2 kN V-eff = 504.3 kN
v = 1.47 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 84.5 kN V-eff = 85.1 kN
v = 0.05 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 48.2 kN.m/m
K/K' = 0.11 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.48 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.21 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 503.2 kN V-eff = 504.3 kN
v = 1.47 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 84.5 kN V-eff = 85.6 kN
v = 0.05 N/mm2 < vc = 0.41 N/mm2

F11
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C11 1 -485.5 -1.0 2.5 G+Q *F
2 -443.2 -2.4 2.4 (G+Q)P11 *F
3 -487.5 -0.8 2.5 (G+Q)P12 *F

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-8

4 -443.1 0.7 2.4 (G+Q)P21 *F


5 -437.1 -1.7 1.8 (G+Q)P22 *F
6 -441.0 0.4 2.5 (G+Q)P31 *F
7 -436.3 -1.8 1.8 (G+Q)P32 *F
8 -488.1 -0.7 2.5 (G+Q)P41 *F
9 -486.3 -0.9 2.5 (G+Q)P42 *F
10 -442.8 -2.3 2.4 (G+Q)P51 *F
11 -487.7 -0.8 2.5 (G+Q)P52 *F
12 -416.7 15.0 2.1 G+Q+Nx
13 -415.6 -16.8 2.1 G+Q-Nx
14 -431.9 -0.8 8.4 G+Q+Ny
15 -400.4 -1.0 -4.1 G+Q-Ny
Column: 1C11
bx = 300.0 mm by = 200.0 mm
Effects: Critical Combination = 11 ((G+Q)P52 *F)
N = -487.7 kN Mx = 0.8 kN.m
My = 2.5 kN.m
Footing Dimensions:
Lx = 1400.0 mm Ly = 1400.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 278.524 kN/m2 S-min = 264.010 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 42.1 kN.m/m
K/K' = 0.09 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.44 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.16 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 515.4 kN V-eff = 518.2 kN
v = 1.51 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 86.5 kN V-eff = 87.6 kN
v = 0.05 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 49.9 kN.m/m
K/K' = 0.11 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.50 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.22 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 515.4 kN V-eff = 518.2 kN
v = 1.51 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 86.5 kN V-eff = 89.3 kN
v = 0.05 N/mm2 < vc = 0.41 N/mm2

F12
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C12 1 -249.2 -3.6 1.3 G+Q *F
2 -251.1 -3.7 1.3 (G+Q)P11 *F
3 -221.9 -3.6 0.8 (G+Q)P12 *F
4 -212.8 -2.4 1.5 (G+Q)P21 *F
5 -249.2 -3.6 1.4 (G+Q)P22 *F
6 -249.1 -3.5 1.4 (G+Q)P31 *F
7 -248.2 -3.7 1.3 (G+Q)P32 *F
8 -213.2 -2.5 1.5 (G+Q)P41 *F
9 -250.2 -3.6 1.4 (G+Q)P42 *F
10 -251.1 -3.7 1.4 (G+Q)P51 *F
11 -221.9 -3.6 0.8 (G+Q)P52 *F
12 -199.5 4.3 1.0 G+Q+Nx
13 -227.7 -10.5 1.3 G+Q-Nx
14 -231.0 -3.0 13.3 G+Q+Ny
15 -196.2 -3.2 -11.1 G+Q-Ny
Column: 1C12
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 14 (G+Q+Ny)
N = -231.0 kN Mx = 3.0 kN.m
My = 13.3 kN.m
Footing Dimensions:
Lx = 1200.0 mm Ly = 1200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 239.523 kN/m2 S-min = 126.063 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 29.6 kN.m/m
K/K' = 0.06 < 1.0

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-9

As = 800.00 mm2/m H16-250


Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.34 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.10 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 252.3 kN V-eff = 268.9 kN
v = 0.78 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 3.8 kN
v = 0.00 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 23.1 kN.m/m
K/K' = 0.05 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.32 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.08 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 252.3 kN V-eff = 268.9 kN
v = 0.78 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 16.6 kN
v = 0.01 N/mm2 < vc = 0.41 N/mm2

F13
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C13 1 -397.5 -7.6 -0.3 G+Q *F
2 -397.3 -7.9 -0.3 (G+Q)P11 *F
3 -353.5 -7.6 0.3 (G+Q)P12 *F
4 -383.5 -5.5 -0.4 (G+Q)P21 *F
5 -348.4 -6.9 -0.7 (G+Q)P22 *F
6 -397.5 -7.5 -0.2 (G+Q)P31 *F
7 -398.0 -7.7 -0.3 (G+Q)P32 *F
8 -383.4 -5.6 -0.4 (G+Q)P41 *F
9 -348.0 -6.8 -0.7 (G+Q)P42 *F
10 -397.3 -7.9 -0.2 (G+Q)P51 *F
11 -353.5 -7.6 0.3 (G+Q)P52 *F
12 -338.5 0.9 -0.3 G+Q+Nx
13 -342.9 -13.9 -0.1 G+Q-Nx
14 -338.1 -6.5 13.6 G+Q+Ny
15 -343.4 -6.5 -14.1 G+Q-Ny
Column: 1C13
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 2 ((G+Q)P11 *F)
N = -397.3 kN Mx = 7.9 kN.m
My = 0.3 kN.m
Footing Dimensions:
Lx = 1400.0 mm Ly = 1400.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 243.082 kN/m2 S-min = 207.199 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 42.9 kN.m/m
K/K' = 0.09 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.41 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.17 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 427.8 kN V-eff = 436.7 kN
v = 1.27 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 71.8 kN V-eff = 80.7 kN
v = 0.05 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 36.7 kN.m/m
K/K' = 0.08 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.40 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.15 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 427.8 kN V-eff = 436.7 kN
v = 1.27 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 71.8 kN V-eff = 72.2 kN
v = 0.04 N/mm2 < vc = 0.41 N/mm2

F14
--------------------------------------------------------------------------------

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-10

Columns/Loadings:
Column Cmb N Mx My
1C14 1 -711.1 -0.3 -0.2 G+Q *F
2 -693.5 1.4 -0.2 (G+Q)P11 *F
3 -634.6 0.5 0.3 (G+Q)P12 *F
4 -672.9 -2.0 0.0 (G+Q)P21 *F
5 -628.0 -0.4 -0.6 (G+Q)P22 *F
6 -708.6 -0.4 -0.1 (G+Q)P31 *F
7 -629.4 0.4 -0.5 (G+Q)P32 *F
8 -675.4 -1.9 0.1 (G+Q)P41 *F
9 -709.8 -1.2 -0.2 (G+Q)P42 *F
10 -693.2 1.4 -0.2 (G+Q)P51 *F
11 -634.6 0.5 0.3 (G+Q)P52 *F
12 -610.7 8.2 -0.2 G+Q+Nx
13 -608.3 -8.7 -0.1 G+Q-Nx
14 -610.4 -0.2 8.7 G+Q+Ny
15 -608.6 -0.3 -9.0 G+Q-Ny
Column: 1C14
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 9 ((G+Q)P42 *F)
N = -709.8 kN Mx = 1.2 kN.m
My = 0.2 kN.m
Footing Dimensions:
Lx = 1700.0 mm Ly = 1700.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 269.740 kN/m2 S-min = 266.452 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 75.7 kN.m/m
K/K' = 0.16 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.57 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.30 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 758.7 kN V-eff = 760.0 kN
v = 2.21 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 334.8 kN V-eff = 336.2 kN
v = 0.19 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 66.1 kN.m/m
K/K' = 0.15 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.56 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.29 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 758.7 kN V-eff = 760.0 kN
v = 2.21 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 334.8 kN V-eff = 335.1 kN
v = 0.19 N/mm2 < vc = 0.41 N/mm2

F15
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C15 1 -806.8 -4.6 8.5 G+Q *F
2 -775.5 -5.1 8.7 (G+Q)P11 *F
3 -750.4 -3.8 8.3 (G+Q)P12 *F
4 -714.0 -3.1 7.0 (G+Q)P21 *F
5 -732.6 -4.2 6.2 (G+Q)P22 *F
6 -748.9 -3.9 8.5 (G+Q)P31 *F
7 -806.8 -4.6 8.5 (G+Q)P32 *F
8 -782.5 -4.7 7.5 (G+Q)P41 *F
9 -732.1 -4.2 6.2 (G+Q)P42 *F
10 -771.3 -5.0 8.7 (G+Q)P51 *F
11 -750.3 -3.8 8.3 (G+Q)P52 *F
12 -695.0 4.3 7.2 G+Q+Nx
13 -688.0 -12.2 7.4 G+Q-Nx
14 -688.4 -3.9 18.4 G+Q+Ny
15 -694.6 -4.0 -3.9 G+Q-Ny
Column: 1C15
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 7 ((G+Q)P32 *F)
N = -806.8 kN Mx = 4.6 kN.m
My = 8.5 kN.m
Footing Dimensions:
Lx = 1900.0 mm Ly = 1900.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 257.462 kN/m2 S-min = 234.526 kN/m2

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-11

Allowable Soil Stress will be amplified by the factor (x1.4) =


280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 92.6 kN.m/m
K/K' = 0.19 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.62 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.36 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 873.3 kN V-eff = 883.6 kN
v = 2.57 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 484.4 kN V-eff = 489.6 kN
v = 0.28 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 81.7 kN.m/m
K/K' = 0.19 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.61 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.36 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 873.3 kN V-eff = 883.6 kN
v = 2.57 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 484.4 kN V-eff = 494.7 kN
v = 0.28 N/mm2 < vc = 0.41 N/mm2

F16
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C16 1 -762.7 -0.3 -1.6 G+Q *F
2 -722.8 -1.8 -1.4 (G+Q)P11 *F
3 -665.1 -0.9 -2.2 (G+Q)P12 *F
4 -721.5 1.9 -1.4 (G+Q)P21 *F
5 -682.3 -0.7 -0.5 (G+Q)P22 *F
6 -746.3 1.5 -1.6 (G+Q)P31 *F
7 -673.7 -1.0 -0.8 (G+Q)P32 *F
8 -734.2 0.1 -1.4 (G+Q)P41 *F
9 -771.5 0.0 -1.3 (G+Q)P42 *F
10 -725.9 -1.9 -1.4 (G+Q)P51 *F
11 -665.1 -0.9 -2.2 (G+Q)P52 *F
12 -652.9 8.2 -1.4 G+Q+Nx
13 -654.5 -8.7 -1.4 G+Q-Nx
14 -654.8 -0.2 12.2 G+Q+Ny
15 -652.6 -0.3 -15.0 G+Q-Ny
Column: 1C16
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 9 ((G+Q)P42 *F)
N = -771.5 kN Mx = 0.0 kN.m
My = 1.3 kN.m
Footing Dimensions:
Lx = 1800.0 mm Ly = 1800.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 261.973 kN/m2 S-min = 259.271 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 83.8 kN.m/m
K/K' = 0.17 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.60 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.33 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 828.8 kN V-eff = 830.4 kN
v = 2.41 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 416.7 kN V-eff = 416.7 kN
v = 0.24 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 73.6 kN.m/m
K/K' = 0.17 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.58 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.32 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 828.8 kN V-eff = 830.4 kN
v = 2.41 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-12

Vt = 416.7 kN V-eff = 418.3 kN


v = 0.24 N/mm2 < vc = 0.41 N/mm2

F17
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C17 1 -1191.8 2.0 12.8 G+Q *F
2 -1092.8 3.6 11.3 (G+Q)P11 *F
3 -1095.8 1.5 13.5 (G+Q)P12 *F
4 -1097.9 0.5 11.2 (G+Q)P21 *F
5 -1068.0 1.2 8.5 (G+Q)P22 *F
6 -1140.0 1.5 12.9 (G+Q)P31 *F
7 -1191.0 2.0 12.9 (G+Q)P32 *F
8 -1088.0 3.5 11.6 (G+Q)P41 *F
9 -1067.6 1.2 8.5 (G+Q)P42 *F
10 -1160.7 1.8 11.3 (G+Q)P51 *F
11 -1095.8 1.5 13.5 (G+Q)P52 *F
12 -1021.1 9.8 11.0 G+Q+Nx
13 -1022.0 -6.4 11.0 G+Q-Nx
14 -1012.2 1.8 24.2 G+Q+Ny
15 -1030.9 1.7 -2.2 G+Q-Ny
Column: 1C17
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 1 (G+Q *F)
N = -1191.8 kN Mx = 2.0 kN.m
My = 12.8 kN.m
Footing Dimensions:
Lx = 2200.0 mm Ly = 2200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 277.149 kN/m2 S-min = 260.412 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 138.4 kN.m/m
K/K' = 0.29 < 1.0
As = 954.33 mm2/m H16-200
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.79 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.51 N/mm2 > vc = 0.43 N/mm2 Fail !!!
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 1284.8 kN V-eff = 1300.4 kN
v = 3.78 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 859.8 kN V-eff = 862.1 kN
v = 0.49 N/mm2 > vc = 0.43 N/mm2 Fail !!!
Y Dir: Footing Design: M = 124.1 kN.m/m
K/K' = 0.28 < 1.0
As = 895.81 mm2/m H16-200
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.78 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.51 N/mm2 > vc = 0.44 N/mm2 Fail !!!
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 1284.8 kN V-eff = 1300.4 kN
v = 3.78 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 859.8 kN V-eff = 875.5 kN
v = 0.50 N/mm2 > vc = 0.44 N/mm2 Fail !!!

F18
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C18 1 -200.4 3.2 0.7 G+Q *F
2 -203.0 3.3 0.6 (G+Q)P11 *F
3 -192.7 3.3 0.6 (G+Q)P12 *F
4 -161.2 2.3 0.5 (G+Q)P21 *F
5 -199.1 3.3 0.5 (G+Q)P22 *F
6 -167.0 2.2 0.7 (G+Q)P31 *F
7 -197.0 3.3 0.6 (G+Q)P32 *F
8 -195.6 3.3 0.5 (G+Q)P41 *F
9 -192.9 3.3 0.4 (G+Q)P42 *F
10 -202.4 3.3 0.5 (G+Q)P51 *F
11 -203.0 3.3 0.7 (G+Q)P52 *F
12 -182.3 10.1 0.6 G+Q+Nx
13 -161.3 -4.5 0.6 G+Q-Nx
14 -215.1 2.8 13.5 G+Q+Ny
15 -128.4 2.7 -12.3 G+Q-Ny
Column: 1C18
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 14 (G+Q+Ny)
N = -215.1 kN Mx = 2.8 kN.m
My = 13.5 kN.m

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-13

Footing Dimensions:
Lx = 1100.0 mm Ly = 1100.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 273.523 kN/m2 S-min = 126.735 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 27.3 kN.m/m
K/K' = 0.06 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.35 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.08 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 230.1 kN V-eff = 248.5 kN
v = 0.72 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 20.7 kN.m/m
K/K' = 0.05 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.33 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.05 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 230.1 kN V-eff = 248.5 kN
v = 0.72 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.41 N/mm2

F19
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C19 1 -508.2 7.2 2.4 G+Q *F
2 -485.9 7.5 2.4 (G+Q)P11 *F
3 -422.1 7.4 1.5 (G+Q)P12 *F
4 -468.6 4.8 2.4 (G+Q)P21 *F
5 -482.7 7.3 2.7 (G+Q)P22 *F
6 -475.5 4.8 2.5 (G+Q)P31 *F
7 -477.5 7.3 2.5 (G+Q)P32 *F
8 -503.1 7.2 2.4 (G+Q)P41 *F
9 -510.6 7.2 2.6 (G+Q)P42 *F
10 -483.9 7.5 2.3 (G+Q)P51 *F
11 -424.5 7.4 1.4 (G+Q)P52 *F
12 -435.7 13.5 2.2 G+Q+Nx
13 -435.5 -1.2 1.9 G+Q-Nx
14 -407.4 6.2 16.3 G+Q+Ny
15 -463.8 6.1 -12.2 G+Q-Ny
Column: 1C19
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 9 ((G+Q)P42 *F)
N = -510.6 kN Mx = 7.2 kN.m
My = 2.6 kN.m
Footing Dimensions:
Lx = 1500.0 mm Ly = 1500.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 266.720 kN/m2 S-min = 232.037 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 55.6 kN.m/m
K/K' = 0.11 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.49 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.23 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 546.1 kN V-eff = 554.2 kN
v = 1.61 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 151.9 kN V-eff = 159.9 kN
v = 0.09 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 47.8 kN.m/m
K/K' = 0.11 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.48 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-14

v = 0.21 N/mm2 < vc = 0.41 N/mm2


Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 546.1 kN V-eff = 554.2 kN
v = 1.61 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 151.9 kN V-eff = 155.0 kN
v = 0.09 N/mm2 < vc = 0.41 N/mm2

F20
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C20 1 -452.7 -4.6 3.0 G+Q *F
2 -435.6 -4.6 2.9 (G+Q)P11 *F
3 -378.4 -4.6 2.0 (G+Q)P12 *F
4 -395.8 -3.2 2.8 (G+Q)P21 *F
5 -445.6 -4.6 3.1 (G+Q)P22 *F
6 -428.5 -4.6 3.0 (G+Q)P31 *F
7 -440.2 -4.6 3.1 (G+Q)P32 *F
8 -401.8 -3.3 3.1 (G+Q)P41 *F
9 -457.6 -4.6 3.0 (G+Q)P42 *F
10 -453.7 -4.6 2.6 (G+Q)P51 *F
11 -378.3 -4.6 2.0 (G+Q)P52 *F
12 -379.4 3.3 2.6 G+Q+Nx
13 -396.6 -11.3 2.4 G+Q-Nx
14 -358.3 -3.9 16.8 G+Q+Ny
15 -417.7 -4.0 -11.8 G+Q-Ny
Column: 1C20
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 9 ((G+Q)P42 *F)
N = -457.6 kN Mx = 4.6 kN.m
My = 3.0 kN.m
Footing Dimensions:
Lx = 1400.0 mm Ly = 1400.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 272.616 kN/m2 S-min = 239.248 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 48.6 kN.m/m
K/K' = 0.10 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.46 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.19 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 486.3 kN V-eff = 491.5 kN
v = 1.43 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 81.6 kN V-eff = 86.8 kN
v = 0.05 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 41.0 kN.m/m
K/K' = 0.09 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.45 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.17 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 486.3 kN V-eff = 491.5 kN
v = 1.43 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 81.6 kN V-eff = 85.3 kN
v = 0.05 N/mm2 < vc = 0.41 N/mm2

F21
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C21 1 -344.7 4.1 2.1 G+Q *F
2 -324.4 4.1 2.2 (G+Q)P11 *F
3 -281.3 4.2 1.3 (G+Q)P12 *F
4 -290.0 3.0 1.9 (G+Q)P21 *F
5 -353.7 4.2 2.4 (G+Q)P22 *F
6 -345.6 4.2 1.9 (G+Q)P31 *F
7 -345.3 4.1 2.2 (G+Q)P32 *F
8 -280.0 3.0 2.1 (G+Q)P41 *F
9 -353.8 4.2 2.4 (G+Q)P42 *F
10 -333.5 4.1 2.2 (G+Q)P51 *F
11 -281.4 4.2 1.3 (G+Q)P52 *F
12 -303.2 10.9 1.9 G+Q+Nx
13 -287.8 -3.8 1.7 G+Q-Nx
14 -316.1 3.6 13.8 G+Q+Ny
15 -274.9 3.5 -10.1 G+Q-Ny

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-15

Column: 1C21
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 14 (G+Q+Ny)
N = -316.1 kN Mx = 3.6 kN.m
My = 13.8 kN.m
Footing Dimensions:
Lx = 1300.0 mm Ly = 1300.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 256.791 kN/m2 S-min = 162.151 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 38.4 kN.m/m
K/K' = 0.08 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.40 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.14 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 341.4 kN V-eff = 358.2 kN
v = 1.04 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 18.5 kN V-eff = 22.6 kN
v = 0.01 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 30.9 kN.m/m
K/K' = 0.07 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.38 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.13 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 341.4 kN V-eff = 358.2 kN
v = 1.04 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 18.5 kN V-eff = 35.3 kN
v = 0.02 N/mm2 < vc = 0.41 N/mm2

F22
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C22 1 -214.0 -0.3 10.6 G+Q *F
2 -206.6 -0.4 10.5 (G+Q)P11 *F
3 -214.4 -0.2 10.6 (G+Q)P12 *F
4 -216.9 -0.2 8.5 (G+Q)P21 *F
5 -162.8 -0.2 7.5 (G+Q)P22 *F
6 -213.0 -0.3 10.5 (G+Q)P31 *F
7 -213.9 -0.3 10.7 (G+Q)P32 *F
8 -221.8 -0.2 10.5 (G+Q)P41 *F
9 -162.7 -0.2 7.5 (G+Q)P42 *F
10 -202.8 -0.4 8.6 (G+Q)P51 *F
11 -214.4 -0.2 10.6 (G+Q)P52 *F
12 -229.5 7.9 9.3 G+Q+Nx
13 -137.4 -8.4 8.9 G+Q-Nx
14 -183.8 -0.4 20.2 G+Q+Ny
15 -183.2 -0.1 -2.0 G+Q-Ny
Column: 1C22
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 12 (G+Q+Nx)
N = -229.5 kN Mx = 7.9 kN.m
My = 9.3 kN.m
Footing Dimensions:
Lx = 1200.0 mm Ly = 1200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 241.574 kN/m2 S-min = 121.976 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 29.2 kN.m/m
K/K' = 0.06 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.34 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.10 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 250.8 kN V-eff = 262.5 kN
v = 0.76 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 9.8 kN
v = 0.01 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 23.6 kN.m/m

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-16

K/K' = 0.05 < 1.0


As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.32 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.08 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 250.8 kN V-eff = 262.5 kN
v = 0.76 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 11.7 kN
v = 0.01 N/mm2 < vc = 0.41 N/mm2

F23
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C23 1 -1075.6 1.3 15.3 G+Q *F
2 -979.0 -0.3 13.7 (G+Q)P11 *F
3 -1012.1 1.3 16.1 (G+Q)P12 *F
4 -1004.6 2.6 13.2 (G+Q)P21 *F
5 -955.3 1.2 10.2 (G+Q)P22 *F
6 -1015.3 -0.2 15.4 (G+Q)P31 *F
7 -1074.0 1.3 15.4 (G+Q)P32 *F
8 -986.9 2.4 13.8 (G+Q)P41 *F
9 -955.3 1.2 10.2 (G+Q)P42 *F
10 -1057.0 1.5 13.0 (G+Q)P51 *F
11 -1012.0 1.3 16.1 (G+Q)P52 *F
12 -917.2 9.2 13.4 G+Q+Nx
13 -926.7 -7.0 12.9 G+Q-Nx
14 -908.5 1.2 26.3 G+Q+Ny
15 -935.4 1.0 0.0 G+Q-Ny
Column: 1C23
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 1 (G+Q *F)
N = -1075.6 kN Mx = 1.3 kN.m
My = 15.3 kN.m
Footing Dimensions:
Lx = 2100.0 mm Ly = 2100.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 277.220 kN/m2 S-min = 255.648 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 125.0 kN.m/m
K/K' = 0.26 < 1.0
As = 859.61 mm2/m H16-225
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.75 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.47 N/mm2 > vc = 0.41 N/mm2 Fail !!!
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 1159.0 kN V-eff = 1177.7 kN
v = 3.42 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 737.7 kN V-eff = 739.2 kN
v = 0.42 N/mm2 > vc = 0.41 N/mm2 Fail !!!
Y Dir: Footing Design: M = 111.1 kN.m/m
K/K' = 0.25 < 1.0
As = 800.70 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.74 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.47 N/mm2 > vc = 0.41 N/mm2 Fail !!!
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 1159.0 kN V-eff = 1177.7 kN
v = 3.42 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 737.7 kN V-eff = 756.4 kN
v = 0.43 N/mm2 > vc = 0.41 N/mm2 Fail !!!

F24
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C24 1 -1151.8 -0.1 11.7 G+Q *F
2 -1066.6 1.7 10.2 (G+Q)P11 *F
3 -1071.7 -0.1 12.5 (G+Q)P12 *F
4 -1054.6 -1.8 10.2 (G+Q)P21 *F
5 -1032.0 -0.1 7.4 (G+Q)P22 *F
6 -1052.8 1.5 10.1 (G+Q)P31 *F
7 -1150.3 -0.1 11.7 (G+Q)P32 *F
8 -1126.0 0.1 10.2 (G+Q)P41 *F
9 -1032.3 -0.1 7.4 (G+Q)P42 *F
10 -1094.1 -1.8 11.8 (G+Q)P51 *F

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-17

11 -1071.7 -0.1 12.5 (G+Q)P52 *F


12 -987.1 8.0 10.2 G+Q+Nx
13 -987.5 -8.2 9.8 G+Q-Nx
14 -977.0 -0.1 23.0 G+Q+Ny
15 -997.5 -0.1 -3.0 G+Q-Ny
Column: 1C24
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 1 (G+Q *F)
N = -1151.8 kN Mx = 0.1 kN.m
My = 11.7 kN.m
Footing Dimensions:
Lx = 2200.0 mm Ly = 2200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 267.150 kN/m2 S-min = 253.880 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 133.6 kN.m/m
K/K' = 0.28 < 1.0
As = 919.11 mm2/m H16-200
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.76 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.49 N/mm2 > vc = 0.43 N/mm2 Fail !!!
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 1245.3 kN V-eff = 1259.5 kN
v = 3.66 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 833.4 kN V-eff = 833.5 kN
v = 0.47 N/mm2 > vc = 0.43 N/mm2 Fail !!!
Y Dir: Footing Design: M = 119.7 kN.m/m
K/K' = 0.27 < 1.0
As = 862.48 mm2/m H16-225
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.76 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.49 N/mm2 > vc = 0.42 N/mm2 Fail !!!
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 1245.3 kN V-eff = 1259.5 kN
v = 3.66 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 833.4 kN V-eff = 847.6 kN
v = 0.48 N/mm2 > vc = 0.42 N/mm2 Fail !!!

F25
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C25 1 -1160.7 -0.8 12.0 G+Q *F
2 -1066.9 -2.6 10.5 (G+Q)P11 *F
3 -1076.4 -0.7 12.8 (G+Q)P12 *F
4 -1069.4 1.2 10.5 (G+Q)P21 *F
5 -1041.0 -0.7 7.7 (G+Q)P22 *F
6 -1131.2 -0.9 10.5 (G+Q)P31 *F
7 -1158.7 -0.8 12.0 (G+Q)P32 *F
8 -1105.3 -2.3 12.2 (G+Q)P41 *F
9 -1041.9 -0.7 7.7 (G+Q)P42 *F
10 -1059.8 0.8 10.3 (G+Q)P51 *F
11 -1076.3 -0.7 12.8 (G+Q)P52 *F
12 -994.7 7.4 10.3 G+Q+Nx
13 -995.0 -8.8 10.2 G+Q-Nx
14 -985.1 -0.7 23.3 G+Q+Ny
15 -1004.6 -0.7 -2.8 G+Q-Ny
Column: 1C25
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 1 (G+Q *F)
N = -1160.7 kN Mx = 0.8 kN.m
My = 12.0 kN.m
Footing Dimensions:
Lx = 2200.0 mm Ly = 2200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 269.538 kN/m2 S-min = 255.147 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 134.7 kN.m/m
K/K' = 0.28 < 1.0
As = 927.35 mm2/m H16-200
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.77 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.50 N/mm2 > vc = 0.43 N/mm2 Fail !!!
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 1254.0 kN V-eff = 1268.6 kN

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-18

v = 3.69 N/mm2 < v-max = 4.00 N/mm2


Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 839.2 kN V-eff = 840.1 kN
v = 0.48 N/mm2 > vc = 0.43 N/mm2 Fail !!!
Y Dir: Footing Design: M = 120.8 kN.m/m
K/K' = 0.27 < 1.0
As = 870.13 mm2/m H16-225
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.76 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.49 N/mm2 > vc = 0.42 N/mm2 Fail !!!
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 1254.0 kN V-eff = 1268.6 kN
v = 3.69 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 839.2 kN V-eff = 853.8 kN
v = 0.48 N/mm2 > vc = 0.42 N/mm2 Fail !!!

F26
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C26 1 -314.6 -4.8 0.6 G+Q *F
2 -313.6 -4.8 0.4 (G+Q)P11 *F
3 -293.3 -4.7 0.6 (G+Q)P12 *F
4 -278.0 -3.4 0.4 (G+Q)P21 *F
5 -289.4 -4.8 0.3 (G+Q)P22 *F
6 -305.8 -4.7 0.5 (G+Q)P31 *F
7 -288.8 -4.8 0.4 (G+Q)P32 *F
8 -287.0 -3.4 0.6 (G+Q)P41 *F
9 -301.4 -4.8 0.6 (G+Q)P42 *F
10 -313.3 -4.8 0.3 (G+Q)P51 *F
11 -307.1 -4.7 0.5 (G+Q)P52 *F
12 -262.4 3.2 0.5 G+Q+Nx
13 -276.9 -11.4 0.4 G+Q-Nx
14 -271.7 -4.1 15.3 G+Q+Ny
15 -267.6 -4.1 -14.4 G+Q-Ny
Column: 1C26
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 14 (G+Q+Ny)
N = -271.7 kN Mx = 4.1 kN.m
My = 15.3 kN.m
Footing Dimensions:
Lx = 1200.0 mm Ly = 1200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 278.504 kN/m2 S-min = 143.694 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 34.3 kN.m/m
K/K' = 0.07 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.40 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.12 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 291.3 kN V-eff = 310.5 kN
v = 0.90 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 26.9 kN.m/m
K/K' = 0.06 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.37 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.09 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 291.3 kN V-eff = 310.5 kN
v = 0.90 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.41 N/mm2

F27
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C27 1 -197.0 4.3 1.1 G+Q *F
2 -197.6 4.3 0.9 (G+Q)P11 *F
3 -193.8 4.4 1.1 (G+Q)P12 *F
4 -157.2 3.2 0.8 (G+Q)P21 *F
5 -191.3 4.3 0.8 (G+Q)P22 *F

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-19

6 -196.9 4.4 0.9 (G+Q)P31 *F


7 -188.8 4.3 1.1 (G+Q)P32 *F
8 -157.6 3.1 0.9 (G+Q)P41 *F
9 -200.3 4.4 0.9 (G+Q)P42 *F
10 -197.4 4.3 0.9 (G+Q)P51 *F
11 -194.0 4.4 1.1 (G+Q)P52 *F
12 -178.9 11.0 1.0 G+Q+Nx
13 -158.8 -3.6 0.9 G+Q-Nx
14 -216.3 3.7 13.9 G+Q+Ny
15 -121.4 3.7 -12.0 G+Q-Ny
Column: 1C27
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 14 (G+Q+Ny)
N = -216.3 kN Mx = 3.7 kN.m
My = 13.9 kN.m
Footing Dimensions:
Lx = 1200.0 mm Ly = 1200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 234.000 kN/m2 S-min = 111.252 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 28.8 kN.m/m
K/K' = 0.06 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.33 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.10 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 238.2 kN V-eff = 255.6 kN
v = 0.74 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 22.5 kN.m/m
K/K' = 0.05 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.31 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.08 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 238.2 kN V-eff = 255.6 kN
v = 0.74 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.41 N/mm2

F28
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C28 1 -211.1 3.5 0.6 G+Q *F
2 -215.9 3.5 0.3 (G+Q)P11 *F
3 -179.4 2.5 1.0 (G+Q)P12 *F
4 -158.7 2.6 0.3 (G+Q)P21 *F
5 -206.4 3.5 0.1 (G+Q)P22 *F
6 -211.6 3.6 0.5 (G+Q)P31 *F
7 -212.9 3.5 0.6 (G+Q)P32 *F
8 -183.3 2.4 0.4 (G+Q)P41 *F
9 -206.2 3.5 0.1 (G+Q)P42 *F
10 -190.5 3.6 0.3 (G+Q)P51 *F
11 -179.5 2.5 1.0 (G+Q)P52 *F
12 -185.5 9.4 0.3 G+Q+Nx
13 -176.4 -3.4 0.7 G+Q-Nx
14 -237.5 2.8 13.6 G+Q+Ny
15 -124.4 3.3 -12.6 G+Q-Ny
Column: 1C28
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 14 (G+Q+Ny)
N = -237.5 kN Mx = 2.8 kN.m
My = 13.6 kN.m
Footing Dimensions:
Lx = 1200.0 mm Ly = 1200.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 244.110 kN/m2 S-min = 130.485 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 30.2 kN.m/m
K/K' = 0.06 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)

Project: CASINO01
Project: CASINO01 - PROPOSED ADDITIONS AND ALTERATIONS TO EXISTING RESIDENTIAL
OSLA HOMES HOTEL
LIMITED (*1E9-AC56-URWJ-HHB8)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-20

v = 0.35 N/mm2 < v-max = 4.00 N/mm2


Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.10 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 258.5 kN V-eff = 275.4 kN
v = 0.80 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 23.5 kN.m/m
K/K' = 0.05 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.33 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.08 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 258.5 kN V-eff = 275.4 kN
v = 0.80 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 0.0 kN V-eff = 0.0 kN
v = 0.00 N/mm2 < vc = 0.41 N/mm2

F29
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C29 1 -381.9 2.4 1.3 G+Q *F
2 -377.5 2.6 1.1 (G+Q)P11 *F
3 -373.5 2.5 1.4 (G+Q)P12 *F
4 -307.7 1.6 0.7 (G+Q)P21 *F
5 -361.6 2.5 1.0 (G+Q)P22 *F
6 -385.6 2.6 1.2 (G+Q)P31 *F
7 -380.3 2.4 1.4 (G+Q)P32 *F
8 -313.1 1.6 0.9 (G+Q)P41 *F
9 -361.8 2.5 1.0 (G+Q)P42 *F
10 -368.7 2.4 1.0 (G+Q)P51 *F
11 -373.4 2.5 1.4 (G+Q)P52 *F
12 -295.3 10.8 1.3 G+Q+Nx
13 -359.4 -6.7 0.9 G+Q-Nx
14 -279.9 2.0 14.1 G+Q+Ny
15 -374.9 2.1 -11.9 G+Q-Ny
Column: 1C29
bx = 200.0 mm by = 300.0 mm
Effects: Critical Combination = 15 (G+Q-Ny)
N = -374.9 kN Mx = 2.1 kN.m
My = 11.9 kN.m
Footing Dimensions:
Lx = 1400.0 mm Ly = 1400.0 mm
h = 400.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 244.439 kN/m2 S-min = 182.994 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
280.000 kN/m2
As-min (Both Dir's) = 800.00 mm2/m
X Dir: Footing Design: M = 43.8 kN.m/m
K/K' = 0.09 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.42 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.17 N/mm2 < vc = 0.40 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 406.1 kN V-eff = 420.6 kN
v = 1.22 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 68.2 kN V-eff = 70.6 kN
v = 0.04 N/mm2 < vc = 0.40 N/mm2
Y Dir: Footing Design: M = 35.9 kN.m/m
K/K' = 0.08 < 1.0
As = 800.00 mm2/m H16-250
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.40 N/mm2 < v-max = 4.00 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.16 N/mm2 < vc = 0.41 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 406.1 kN V-eff = 420.6 kN
v = 1.22 N/mm2 < v-max = 4.00 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 68.2 kN V-eff = 82.7 kN
v = 0.05 N/mm2 < vc = 0.41 N/mm2