0% found this document useful (0 votes)
53 views50 pages

CT00-000 811 02 05 02

Uploaded by

melquicedec
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views50 pages

CT00-000 811 02 05 02

Uploaded by

melquicedec
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 50

Common CT

Pre-Installation
System
Installation of the external air split cooling system
2 Document Version / Disclaimer / Copyright

Document Version
Siemens reserves the right to change its products and services at any time.
In addition, manuals are subject to change without notice. The hardcopy documents cor‐
respond to the version at the time of system delivery and/or printout. Versions to hard‐
copy documentation are not automatically distributed.
Please contact your local Siemens office to order a current version or refer to our website
http://www.siemens-healthineers.com.

Disclaimer
Siemens provides this documentation “as is” without the assumption of any liability under
any theory of law.
The content described herein requires superior understanding of our equipment and may
only be performed by qualified personnel who are specially trained for such installation
and/or service.

Copyright
“© Siemens, 2005” refers to the copyright of a Siemens entity such as:
Siemens Healthcare GmbH - Germany
Siemens Aktiengesellschaft - Germany
Siemens Shenzhen Magnetic Resonance Ltd. - China
Siemens Shanghai Medical Equipment Ltd. - China
Siemens Healthcare Private Ltd. - India
Siemens Medical Solutions USA Inc. - USA
Siemens Healthcare Diagnostics Inc. - USA and/or
Siemens Healthcare Diagnostics Products GmbH - Germany

Common CT CT00-000.811.02.05.02 Page 2 of 50 © Siemens, 2005


01.09 CTL EN
Table of Contents 3

1 General Information 5

1.1 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.1 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.2 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Abbreviations, Acronyms and Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Overview of system components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.1 Standard components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.2 Optional components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.4 Required tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

2 Unpacking and Setting up 11

2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 WCS (Indoor unit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.3 Outside ventilator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4 Flow heater (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.4.1 Instructions for flow heater installation . . . . . . . . . . . . . . . . . . . . 14
2.4.2 Special component mounting for the flow heater cabinet . . . . . . 15
2.5 Repair Switch (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

3 Installation 17

3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2 WCS (Indoor unit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2.1 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2.2 Cooling hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.3 Flow Heater (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.3.1 Type A - connecting the cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.3.2 Type B - connecting the cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.3.3 Connecting the cooling hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4 Repair Switch (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.5 Pipe kit (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.6 Outside ventilator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.6.1 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.6.2 Cooling hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.7 Additional installation hints for outdoor unit . . . . . . . . . . . . . . . . . . . . . . . . 34
3.8 Installation of a hose connection piece. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.9 Capillary tube device (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.9.1 Upgrade of capillary tube device. . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.9.2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.9.3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

© Siemens, 2005 CT00-000.811.02.05.02 Page 3 of 50 Common CT


01.09 CTL EN
4 Table of Contents

4 Filling the cooling system 41

4.1 Primary circuit (WCS/outside ventilator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41


4.1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.1.2 Filling without flow heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.1.3 Filling with flow heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

5 Changes to previous version 48

6 List of Hazard IDs 49

Common CT CT00-000.811.02.05.02 Page 4 of 50 © Siemens, 2005


01.09 CTL EN
General Information 1 5

1.1 Notes
This document describes all steps necessary for pre-installing the water/air-split cooling
system.
This optional cooling system can be used with:
SOMATOM SENSATION 10, SENSATION 16, SOMATOM SENSATION CARDIAC, SOMA‐
TOM SENSATION 40, SOMATOM SENSATION 64, SOMATOM SENSATION CARDIAC 64,
SOMATOM SENSATION OPEN


The cooling system can be put into operation only after installing the entire CT system.
C
Otherwise, the pump of the split cooling system will be irreversibly damaged.

1.1.1 Safety information


Additionally, supplemental safety-relevant aspects are included in the following docu‐
ments:
n General Safety Notes - print number TD00-000.860.01
n Product-specific Safety Notes (Sensation) - print number CT02-023.860.01
and in this chapter. Please adhere to the safety information.

1.1.1.1 Work with heavy loads


For your own safety, we recommend that you wear safety clothing (safety shoes, ...)

 Put on safety clothes before you start working on the system.

1.1.1.2 Protection against electrical accidents

 Prior to connecting the components to the external voltage supply, ensure that there is
no voltage present at the cable and safeguard it against switch-on.

1.1.2 General Information


To ensure correct installation, the requirements from the the following document Plan‐
ning Guide (PG) CT02-023.891.xx.xx have to be met.
The newest version of the document is available only via the Siemens Intranet. This docu‐
ment is not part of the system documentation.
It can be viewed on the CS home page:

© Siemens, 2005 CT00-000.811.02.05.02 Page 5 of 50 Common CT


01.09 CTL EN
6 1 General Information

http://cs.med.siemens.de

Common CT CT00-000.811.02.05.02 Page 6 of 50 © Siemens, 2005


01.09 CTL EN
General Information 1 7

1.2 Abbreviations, Acronyms and Definitions


Designation Description
PE Protective Earth (Protective Ground)
PM Project Manager
Primary cooling circuit Cooling circuit between the outdoor unit and indoor unit.
Secondary cooling circuit Cooling circuit between the gantry and the indoor unit.
W/A Water/Air
WCS Water Cooling System (Indoor unit)

© Siemens, 2005 CT00-000.811.02.05.02 Page 7 of 50 Common CT


01.09 CTL EN
8 1 General Information

1.3 Overview of system components

1.3.1 Standard components


The water/air-split cooling system contains:
n WCS (Indoor unit)
n Outside ventilator (with installation accessories for the feet)
n 3 containers of cooling agent (mixture of glycol and water (40:60))
n 2 x 40 m cooling hoses (with installation accessories - connection pieces for the ends
of the hoses)
n W98 power and signal cable
n Protective conductor PE (green, yellow)
n Capillary tube device (included in standard delivery volume and can be installed op‐
tionally)
Fig. 1: W/A split cooling system - component overview

1.3.2 Optional components


The optional flow heater contains:
n 1 container of pure glycol (labeled as “GLYKOSOL N”) and 1 glycol tester
n 2 x 3 m connection hoses
n Installation material (screws and anchors for wall mounting; two connection adapters
for the cooling hoses, M45x2 / M36x2)
n Thermal sensor with cable (provided in the flow heater)

Common CT CT00-000.811.02.05.02 Page 8 of 50 © Siemens, 2005


01.09 CTL EN
General Information 1 9

Fig. 2: W/A split cooling system - component overview with optional flow heater

Additional options:
n Repair switch contains:
- Electronics box with power switch
- Wire end ferrules
- Anchor, washer, and screws
n Pipe kit contains:
- 4x hose connection pieces (DN25 M36x2 inside)
- 4x hose to pipe adapter (M36x2 R1” outside, G1” inside)
- The kit contains no pipes.
Fig. 3: Split cooling system with all available options

© Siemens, 2005 CT00-000.811.02.05.02 Page 9 of 50 Common CT


01.09 CTL EN
10 1 General Information

1.4 Required tools


Included in the
Name scope of delivery: Use
1/2" garden hose No Connect filling system to the WCS
Crimping tool No Needed for repair switch installation
to crimp the 1.5 mm² wire end fer‐
rules.
Crowbar No Wooden crate (outside ventilator, op‐
tional flow heater)
Drilling machine and drill No Drilling the anchor holes for the WCS
(drill M10 is needed for the (and optional flow heater) in earth‐
preferred wall mounting quake-prone areas.
solution of the optional
flow heater)
Filling system (a pressure of No Filling
up to 6 bar is needed)
Forklift, adjustable in No Lift WCS of the pallet, install the feet
height, min. 1.5 m of the outside ventilator.
And lift the optional flow heater from
the pallet.
Hammer, vacuum cleaner, No Anchor installation for the WCS (and
torque wrench (up to 25 optional flow heater) in earthquake-
Nm) prone areas.
Hexagonal wrench, size 36 No Connecting the cooling hoses
Hexagonal wrench, size 40 No Connecting the cooling hoses
Hexagonal wrench, size 41 No Connecting the cooling hoses
(only for the optional flow
heater, two of them are
needed - contra hold)

Common CT CT00-000.811.02.05.02 Page 10 of 50 © Siemens, 2005


01.09 CTL EN
Unpacking and Setting up 2 11

2.1 General

 After the components are unpacked, inspect them for transport damage.

After the components are unpacked, check the shipment for missing parts. For the mate‐
 rial included in the delivery volume, refer to ( Overview of system compo‐
nents / Page 8).

© Siemens, 2005 CT00-000.811.02.05.02 Page 11 of 50 Common CT


01.09 CTL EN
12 2 Unpacking and Setting up

2.2 WCS (Indoor unit)


n Position the pallet with the WCS at the final location.
n Remove the foil and packaging material in the carton.

Fig. 4: WCS cabinet with pallet Fig. 5: WCS attachment points at pallet

Take WCS off the pallet:


n For this purpose, remove the two screws ( 1/Fig. 5 Page 12) from the wooden block
( 2/Fig. 5 Page 12) in back and in front of it.
n Remove the wooden board ( 4/Fig. 5 Page 12) attached to the wooden block.
n Remove the wooden block and board.
n Remove the two grey metal covers (bottom) ( 3/Fig. 5 Page 12) in back and in front
(4 plastic covers and 4 screws each per metal cover).
n Remove the four screw connections in the floor of the cabinet that connects the WCS
with the pallet.
n Lift the cabinet with a forklift and remove the pallet.
n Lower the WCS to the floor and remove the forklift.

Common CT CT00-000.811.02.05.02 Page 12 of 50 © Siemens, 2005


01.09 CTL EN
Unpacking and Setting up 2 13

2.3 Outside ventilator


Fig. 6: Water/Air-split outside ventilator Fig. 7: Outside ventilator - foot

(1) Transport bracket

When lifting the outside ventilator, please note the following:


n The outside ventilator is taken up by the forklift from the side and the center.
n To avoid damaging the cooling fins, the prongs of the forklift must protrude on the
opposite side.

n Remove the upper and side parts of the wooden packaging.


n Remove the four metal brackets ( 1/Fig. 6 Page 13) at the corners that connect the
outside ventilator with the pallet.
n Removing the foil packaging
n Lift the outside ventilator with the forklift so that the feet can be mounted.
n The feet are attached via screws to the pallet. Remove the screws at the feet
n Connect all four feet ( 1/Fig. 7 Page 13) to the outside ventilator. Use the delivered
installation material for this purpose.
n Position the outside ventilator at its final destination.

© Siemens, 2005 CT00-000.811.02.05.02 Page 13 of 50 Common CT


01.09 CTL EN
14 2 Unpacking and Setting up

2.4 Flow heater (optional)


Some countries (earthquake-prone areas) require special floor mounting for the flow
heater cabinet. In this case, adhere to ( Special component mounting for the flow heat‐
er cabinet / Page 15) as well.
The flow heater has to be positioned next to the indoor unit of the W/A split cooling sys‐
tem inside the building.

2.4.1 Instructions for flow heater installation


n Transport the packaging of the flow heater cabinet to the final position.
n Open the wooden packaging.
n Unpack the hoses and the container of glycol.
n Lift the flow heater cabinet (use a forklift to move the foot of the cabinet) Take the
cabinet out of the packaging and position it.
n Remove the foil completely from the flow heater cabinet.
n Position the flow heater at its final location (ask the local PM or refer to the project
plan).

2.4.1.1 Wall mounting


You can use the provided material to mount the flow heater cabinet to the wall. This
mounting is optional. The preferred solution for mounting is a standing cabinet with wall
mounting.
Fig. 8: Flow heater - wall mounting

n Drill the holes with a M10 drill.


n Use the provided material (anchors, screws,...) to mount the cabinet to the wall
( 1/Fig. 8 Page 14).

Common CT CT00-000.811.02.05.02 Page 14 of 50 © Siemens, 2005


01.09 CTL EN
Unpacking and Setting up 2 15

2.4.2 Special component mounting for the flow heater cabinet


T The flow heater can be mounted to the wall (preferred) or to the ground.
The local PM has to provide a specific solution when the flow heater has to be bolted to
the floor. The local PM has to provide the required special mounting equipment (anchors,
screws, and so on).

© Siemens, 2005 CT00-000.811.02.05.02 Page 15 of 50 Common CT


01.09 CTL EN
16 2 Unpacking and Setting up

2.5 Repair Switch (optional)


The repair switch cannot be attached to the outdoor unit. For this reason, the switch
must mounted to a wall. The switch should mounted near the outdoor unit.
T The enclosed anchors are only suitable for the concrete and brick walls. The PM must pro‐
vide proper anchors for other types of construction.
Fig. 9: Mounting of service switch

Common CT CT00-000.811.02.05.02 Page 16 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 17

3.1 General
A schematic display of the cable and hose routings is located under ( Overview of sys‐
tem components / Page 8).

 The water hoses have imprinted directional arrows. While routing the hoses, ensure that
the arrows on the water hoses show the water flow.

 To ensure that they are watertight, wait two hours after the filling procedure to insulate
the connections.

All cooling water connections, hoses, and pipes have to be insulated (e.g. , material from
Armacell, 13 mm thick). Otherwise, excessive condensation will form.

 The insulation material has to be air-tight around parts that transport cooling liquid. In‐
sulation material cut in two has to be glued together again.
The insulation material for the primary cooling circuit is not included in the delivery vol‐
ume.

 The cables routed in the indoor unit, flow heater cabinet (optional) and at the outdoor
unit have to be secured with cable ties.

Excessive cable lengths must not be rolled up and tied together.


The excess cable lengths should meander in the cable ducts. If there are no cable ducts,
roll up the excess length using the largest possible loops.
Refer to ( Fig. 10 Page 18).

© Siemens, 2005 CT00-000.811.02.05.02 Page 17 of 50 Common CT


01.09 CTL EN
18 3 Installation

Fig. 10: Cable routing

Common CT CT00-000.811.02.05.02 Page 18 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 19

3.2 WCS (Indoor unit)

3.2.1 Wiring
Fig. 11: W/A-Split WCS - Electronic Box

Fig. 12: W/A split WCS - cable connection Fig. 13: W/A-Split WCS - Cable Connection

(1) Supply voltage - terminal clamp

(1) W98
(2) PE - protective earthing

n Remove the cover of of the WCS connection board/electronic box ( Fig. 11 Page 19).
n Connect the power cable W98 to ( 1/Fig. 12 Page 19).
n Connect the protective conductor cable to ( 2/Fig. 12 Page 19)
n Connect the cable of the external voltage supply to terminal (L1, L2, L3, N, PE)
( 1/Fig. 13 Page 19).
n Mount the cover of of the WCS connection board/electronic box.
n Route W98 to the outdoor unit or to the optional repair switch.

© Siemens, 2005 CT00-000.811.02.05.02 Page 19 of 50 Common CT


01.09 CTL EN
20 3 Installation

3.2.2 Cooling hoses

 The water hoses have imprinted directional arrows. While you route the hoses, ensure
that the arrows at the water hoses show the water flow.

Fig. 14: W/A-Split WCS - Water connection

(1) Leading to the outside ventilator of the outdoor unit


(2) Coming from the outside ventilator of the outdoor unit

Connecting the cooling hoses (without optional flow heater):


n Connect the two cooling hoses to the WCS as shown in picture ( Fig. 14 Page 20).
n Tighten the hose connection pieces. For this purpose use a hexagonal wrench, size 36
and 40.
n Routing of cooling hoses:
- Route the two cooling hoses to the outside ventilator.
- If using the pipe kit, route the two cooling hoses to the on-site pipes. For pipe kit
installation refer to ( Pipe kit (optional) / Page 30).

Connecting the cooling hoses (with optional flow heater):


n Connect the two provided adapters (provided in the delivery volume of the flow heat‐
er) to the cooling hose connections as shown in the picture
( Pos. 1 and 2/Fig. 14 Page 20).
n Tighten the adapters with two hexagonal wrenches (size 36 and 41).
n Connect the two 3m cooling hoses to the adapters just attached to the WCS
( Pos. 1 and 2/Fig. 14 Page 20).

Common CT CT00-000.811.02.05.02 Page 20 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 21

n Tighten the connection pieces. For this purpose use a hexagonal wrench, size 40 and
41.
n Route the two cooling hoses to the flow heater.

The cooling hoses and the connection pieces must be insulated against condensation
 water. To ensure that they are watertight, wait two hours after the filling procedure to
insulate the connections.

© Siemens, 2005 CT00-000.811.02.05.02 Page 21 of 50 Common CT


01.09 CTL EN
22 3 Installation

3.3 Flow Heater (optional)

3.3.1 Type A - connecting the cables


Fig. 15: Flow heater - Mains supply / thermal sensor connection

(1) X2 terminal clamp of the thermal sensor (pre-connected at X2)


(2) Terminal clamp X1 (L1, L2, L3, PE)
(3) Cable with thermal sensor (pre-connected, has to be routed to the outdoor unit)

n Open the front cover of the flow heater cabinet.


n Open the door of the switching cabinet.
n Route the main power cable through the socket and through the feedthrough of the
switching cabinet (bottom side).
n Connect the main power cable to the terminal clamp X1 of the switching cabinet
( Pos. 2/Fig. 15 Page 22).
n Tighten the feedthrough of the switching cabinet.

Common CT CT00-000.811.02.05.02 Page 22 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 23

n Route the cable with thermal sensor ( Pos. 3/Fig. 15 Page 22) to the outdoor unit.
This cable is preconnected at X2 in the switching cabinet ( Pos. 1/Fig. 15 Page 22).
 The thermal sensor must be secured with cable ties or a pipe clip at the outlet
pipe (bottom pipe) of the outdoor unit ( Pos. 2/Fig. 26 Page 33) /
( Pos. 1/Fig. 23 Page 31). Its very important to insulate the sensor and the
outlet pipe.
n Switch all fuses (F1, F2, Q1 and Q2) on.

3.3.1.1 Type A - voltage adaptation of mains supply

Fig. 16: Flow heater - Voltage adaption

(1) Terminal clamp of T1 (port 1 to 7)


(2) Label of voltage adaption

The flow heater must be adapted to the local mains supply.


n Switch and connect the two black wires at the terminal clamp of T1 to the correct port
of your local mains supply voltage ( Pos. 1/Fig. 16 Page 23).
n For the correct ports, refer to the label at T1 ( Pos. 2/Fig. 16 Page 23).
n Close the door of the switching board.
n Turn the red main switch off.

© Siemens, 2005 CT00-000.811.02.05.02 Page 23 of 50 Common CT


01.09 CTL EN
24 3 Installation

3.3.2 Type B - connecting the cables


Fig. 17: Flow heater - Mains power supply, thermal sensor connection

(1) Terminal clamp X1 (mains power supply)


(2) Cable with thermal sensor (pre-connected at X2, has to be routed to the outdoor unit)

n Open the front cover of the flow heater cabinet.


n Open the door of the switching cabinet.
n Route the mains power cable through the socket and through the cable feed-through
( Pos. 3/Fig. 17 Page 24) of the switching cabinet.
n Connect the mains power cable to the terminal clamp X1 ( Pos. 1/Fig. 17 Page 24).
n Tighten the cable feed-through of the switching cabinet.
n Route the cable with thermal sensor ( Pos. 2/Fig. 17 Page 24) to the outdoor unit.
This cable is preconnected at X2 ( Pos. 2/Fig. 17 Page 24).
 The thermal sensor must be secured with cable ties or a pipe clip at the outlet
pipe (bottom pipe) of the outdoor unit ( Pos. 2/Fig. 26 Page 33) /
( Pos. 1/Fig. 23 Page 31). Its very important to insulate the sensor and the
outlet pipe.
n Switch all fuses (F1, F2, Q1, and Q2) on.

Common CT CT00-000.811.02.05.02 Page 24 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 25

3.3.2.1 Type B - Voltage adaptation of mains supply

Fig. 18: Flow heater - Voltage adaption

(1) Terminal clamp of T1 (port 1 to 7)


(2) Description of voltage adaption

The flow heater must be adapted to the local mains supply.


n Switch and connect the two black wires at the terminal clamp of T1 to the correct port
of your local mains supply voltage ( Pos. 1/Fig. 18 Page 25).
n For the correct ports, refer to the label at T1 ( Pos. 2/Fig. 18 Page 25).
n Close the door of the switching board.
n Turn the red main switch off.

© Siemens, 2005 CT00-000.811.02.05.02 Page 25 of 50 Common CT


01.09 CTL EN
26 3 Installation

3.3.3 Connecting the cooling hoses

The cooling hoses and the connection pieces must be insulated against condensation
water. The insulation material for the primary circuit is not included in the delivery vol‐

 ume.
To ensure that they are watertight, wait two hours after the filling procedure to insulate
the connections.

Fig. 19: Flow heater - cooling hose connections

(1) Inlet (from outdoor unit)


(2) Outlet (to indoor unit)
(3) Inlet (from indoor unit)
(4) Outlet (to outdoor unit)

Common CT CT00-000.811.02.05.02 Page 26 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 27

Connecting the cooling hoses from the indoor unit:


n Connect the 3m hoses from the indoor unit to the flow heater. Refer to
( Pos. 2 and 3/Fig. 19 Page 26) / ( Pos. 1 and 2/Fig. 14 Page 20). Ensure that the
flow direction is not reversed (observe the imprinted directional arrows).
Arrows are printed on the hose, follow the conditions stated below:
 At the inlet connection of the flow heater ( 3/Fig. 19 Page 26), the arrows
have to point to the flow heater cabinet.
 At the outlet connection of the flow heater ( 2/Fig. 19 Page 26), the arrows
have to point away from the flow heater cabinet.
n Tighten the connection pieces. For this purpose, use two hexagonal wrench, size 41.
Connecting the cooling hoses for the outdoor unit:
n Connect the two 40m cooling hoses to the flow heater ( 1 and 4/Fig. 19 Page 26).
Refer to ( Pos. 1 and 4/Fig. 19 Page 26) / ( Pos. 1 and 2/Fig. 14 Page 20).
Ensure that the flow direction is not reversed (observe the imprinted directional ar‐
rows).
Arrows are printed on the hose, follow the conditions stated below:
 At the inlet connection of the flow heater ( 1/Fig. 19 Page 26), the arrows
have to point to the flow heater cabinet.
 At the outlet connection of the flow heater ( 4/Fig. 19 Page 26), the arrows
have to point away from the flow heater cabinet.
n Tighten the connection pieces and the connection adapters. For this purpose, use a
hexagonal wrench, size 36 and size 41.
n Routing of cooling hoses:
- Route the two cooling hoses to the outside ventilator.
- If using the pipe kit, route the two cooling hoses to the on-site pipes. For pipe kit
installation refer to ( Pipe kit (optional) / Page 30).

© Siemens, 2005 CT00-000.811.02.05.02 Page 27 of 50 Common CT


01.09 CTL EN
28 3 Installation

3.4 Repair Switch (optional)


When using the repair switch, W98 is used as the power cable from the indoor unit to the
repair switch and to the outdoor unit. For this reason W98 must be cut to connect the
repair switch.
n Route W98 to the repair switch and cut the excess length. For the cable length needed
inside the repair switch box refer to ( Fig. 20 Page 28).
 Do not cut the separate PE cable attached to W98. Route the PE cable directly
to the outdoor unit.
 Please note that the excess length must be long enough to connect the repair
switch with the outdoor unit.
n Dismantle both ends of W98 as shown in ( Fig. 20 Page 28). 350 mm for the cable
end “from indoor unit” and 250 mm for the cable end “to outdoor unit”.
n At both cable-ends, dismantle 10 mm of the wires 1, 2, 3, 4, 5 and green/yellow as
shown in ( Fig. 20 Page 28).
n Crimp the provided wire end ferrules to the wire 1, 2, 3, 4, 5 and green/yellow.
Fig. 20: Service switch - dismantling the cable

n Open the repair switch box.


n Route the cable inside the repair switch box by using the feedthrough.
n Connect the cable as shown in ( Fig. 21 Page 29).

Common CT CT00-000.811.02.05.02 Page 28 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 29

n Tighten the feedthrough of the box.


n Close the repair switch box.
n Route the excess length of W98 to the outdoor unit.
Fig. 21: Service switch - cabling

© Siemens, 2005 CT00-000.811.02.05.02 Page 29 of 50 Common CT


01.09 CTL EN
30 3 Installation

3.5 Pipe kit (optional)


The pipe kit adapters can used at the connection between the hoses and the on-site
pipes.
n Route the hoses to the on-site pipes.
n Cut off the hoses at the connection of the on-site pipes.
 Please note that the excess length must be long enough to connect to the on-
site pipes.
n Attach the hose connection pieces to the hoses. Refer to ( Installation of a hose con‐
nection piece / Page 35).
n Attach and tighten the pipe kit adapter ( Fig. 22 Page 30) to the on-site pipes.
 You cannot connect the adapter directly to the on-site pipes. The on-site part
of the adapter must be sealed!
n Attach and tighten the hose to the on-site pipes.
Fig. 22: Adapter - hose to pipe

n Route the hoses between on-site pipes and the outside ventilator.
The free ends may be cut to the length required.
n To connect the hoses to the on-site pipes attach the hose connection pieces. Refer to
( Installation of a hose connection piece / Page 35).
n Attach and tighten the adapter ( Fig. 22 Page 30) of the pipe kit to the on-site pipes.
 You cannot connect the adapter directly to the on-site pipes. The on-site part
of the adapter must be sealed!
n Attach and tighten the hoses to the on-site pipes.

Common CT CT00-000.811.02.05.02 Page 30 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 31

3.6 Outside ventilator

3.6.1 Wiring

3.6.1.1 Installing the cable with thermal sensor for the optional flow heater

Fig. 23: Cable with thermal sensor mounted to the outlet pipe of the outdoor unit

(1) Outlet pipe (bottom pipe)


(2) Cable with thermal sensor secured with cable ties to the outlet pipe
(3) Inlet pipe (upper pipe)

n The cable with thermal sensor is part of the optional flow heater.
 The thermal sensor must be secured with cable ties ( Pos. 2/Fig. 23 Page 31)
or a pipe clip at the outlet pipe of the outdoor unit ( Pos. 1/Fig. 23 Page 31).
 Secure the cable with cable ties to the outlet pipe of the outdoor unit.
 Its very important to insulate the sensor and the outlet pipe.

© Siemens, 2005 CT00-000.811.02.05.02 Page 31 of 50 Common CT


01.09 CTL EN
32 3 Installation

3.6.1.2 Installing the cables to the outside ventilator’s electronics

Fig. 24: Outside ventilator - cable connection Fig. 25: Outside ventilator - PE connection

(1) W98 and terminal clamp


(2) PE - protective earthing
(3) Secure part

n Connect the protective conductor to ( 2/Fig. 24 Page 32). Use the material supplied.
Connect screw, washer, cable and serrated lock washer as shown ( Fig. 25 Page 32).
n Remove the two screws from the cover to the connection box.
n Open the cover.
n Unscrew the plastic of the cable feedthrough and push it correctly on cable W98.
n Route cable W98 ( 1/Fig. 24 Page 32) through the feedthrough and tighten it by con‐
necting the secure part ( 3/Fig. 24 Page 32)
n Connect the conductors of cable W98 as follows:

Tab. 1 Outside ventilator - terminal clamp for W98

Outside ventilator W98 W98


Terminal clamp Designation for conductor Color of conductor
Green green-yellow
TK 5 Black
TK 4 Black
U1 1 Black
V1 2 Black
W1 3 Black

Common CT CT00-000.811.02.05.02 Page 32 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 33

n Close the cover and tighten it with the material delivered.

3.6.2 Cooling hoses

 The water hoses have imprinted directional arrows. While routing the hoses, ensure that
the arrows at the water hoses show the water flow.

Fig. 26: Outside ventilator - water connection

(1) Coming from the WCS (from the indoor unit)


(2) Leading to WCS (to the indoor unit)

Connecting the cooling hoses:


n The cooling hoses can be cut to size (recommended).
n To install the adapters, refer to ( Installation of a hose connection piece / Page 35).
n Connect the hoses from the WCS (or from the flow heater) to the outside ventilator,
refer to ( Fig. 26 Page 33). Ensure that the flow direction is not reversed (observe
the imprinted directional arrows). Refer to ( Fig. 26 Page 33).
n Tighten the connection pieces. For this purpose use a hexagonal wrench, size 36 and
40.

The cooling hoses and the connection pieces must be insulated against condensation
 water. To ensure that they are watertight, wait two hours after the filling procedure to
insulate the connections.

© Siemens, 2005 CT00-000.811.02.05.02 Page 33 of 50 Common CT


01.09 CTL EN
34 3 Installation

3.7 Additional installation hints for outdoor unit


Fig. 27: Canopy for the outdoor unit

(1) Distance between canopy and outdoor unit

By installation of the outdoor unit you can use a canopy (not needed at all). A canopy is a
recommended protection against environmental effects, e.g. rain, snow, hail. The dis‐
tance between the outdoor unit and canopy should be not less than 1000m.The material
for a canopy must be provided by the local PM.

Common CT CT00-000.811.02.05.02 Page 34 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 35

3.8 Installation of a hose connection piece


Fig. 28: Overview of the required parts Fig. 29: Metal hose adapter and half shell

Fig. 30: Installed connecting piece Fig. 31: Completed connecting piece

(1) Spacer disks (1) Spacer disk


(2) Half-shells

n Insert the adapter as shown ( Fig. 29 Page 35) into the hose.
n Position the hose with adapter as shown ( Fig. 29 Page 35) into a metal half-shell
n Slide 4 Allen screws (size 5 mm) from the bottom into the half-shell and place a
spacer on each screw. Refer to ( 1/Fig. 30 Page 35).
n Position the second half-shell on the ( 2/Fig. 31 Page 35).
n Tighten the scews with nuts on the opposite side, until the spacers abut between the
half shells ( 1/Fig. 31 Page 35).

© Siemens, 2005 CT00-000.811.02.05.02 Page 35 of 50 Common CT


01.09 CTL EN
36 3 Installation

3.9 Capillary tube device (optional)


The capillary tube device is included in standard delivery volume and can be installed op‐
tionally.
With an installed capillary tube device, the split cooling system will switch off the outdoor
unit when the outdoor temperature is low. As a result, the split cooling system will have a
power saving feature.
In countries without UL requirements, you can install the optional capillary tube device.
In countries with UL requirements, make note of the following:
n All parts of the capillary tube device have a UL approval and UL label.
n The split cooling system as stand-alone device has a UL approval and UL label.
n The capillary tube device in combination with the indoor unit does not have UL ap‐
proval!
n In countries with UL requirements, you must perform a UL approval of the split cool‐
ing system in combination with the capillary tube device yourself!

3.9.1 Upgrade of capillary tube device


All split cooling systems can be upgraded with the capillary tube device.
n Shut down the system
n Switch off the mains power supply
n Refer to the installation instruction in chapter ( Installation / Page 38) and ( Wir‐
ing / Page 39).

In older indoor units, where no capillary tube controller was installed before, the attach‐
 ment holes/holes for the sensor have to be drilled into the ground plate of the control
box.

Common CT CT00-000.811.02.05.02 Page 36 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 37

Fig. 32: Sketch for drilling holes

© Siemens, 2005 CT00-000.811.02.05.02 Page 37 of 50 Common CT


01.09 CTL EN
38 3 Installation

3.9.2 Installation

Fig. 33: Capillary tube device Fig. 34: Sensor

2
3

(1) Controller with sensor


(2) Immersion sleeve
(3) Tube of primary cooling circuit

n Install the new capillary tube controller and attach it at the ground plate of the control
box with the M4x8 screws provided (included in delivery volume); also refer to
( Pos. 1/Fig. 33 Page 38).
n Put the controller sensor down through the existing grommet out of the electronic
box.
n With newer systems:
- There is an immersion sleeve (small pipe) ( Pos. 2/Fig. 33 Page 38) for the sensor,
in addition to the pipe of the primary cooling circuit ( Pos. 3/Fig. 33 Page 38).
 This immersion sleeve is behind the insulation material, and is soldered to the
primary supply outlet.

Common CT CT00-000.811.02.05.02 Page 38 of 50 © Siemens, 2005


01.09 CTL EN
Installation 3 39

- Apply the heat-conductive paste provided to the sensor and put the sensor into the
immersion sleeve ( Pos. A/Fig. 33 Page 38).
n With older systems:
- Apply the heat-conductive paste provided to the sensor and put the sensor directly
on the pipe of primary cooling circuit.
- Secure the sensor with two cable ties ( Fig. 34 Page 38).
n Insulate the immersion sleeve and the pipe of the primary cooling circuit.

3.9.3 Wiring
Fig. 35: Capillary tube device

1 3
P1 P4

(1) Controller
(2) X4
(3) K20

© Siemens, 2005 CT00-000.811.02.05.02 Page 39 of 50 Common CT


01.09 CTL EN
40 3 Installation

Fig. 36: Wiring of capillary tube device

Rewire the capillary tube device (new cables included in delivery volume):
n Remove the wire between X4/2 and K20/A1
n Route a cable from capillary tube device P1 to X4 Port 2
n Route a cable from the capillary tube device P4 to the K20 Port A1

Common CT CT00-000.811.02.05.02 Page 40 of 50 © Siemens, 2005


01.09 CTL EN
Filling the cooling system 4 41

4.1 Primary circuit (WCS/outside ventilator)

4.1.1 General

The cooling liquid provided and used for the W/A split cooling system is Glykosol N.
In no case should Glykosol N be mixed with another cooling liquid products! This will de‐
C  crease the anti-freeze protection of Glykosol N.
If the provided Glykosol N is not sufficient, order an additional container via Internet or
your local supplier.

The W/A split cooling system without an optional flow heater may be filled with a glycol/
 water mixture of 40:60 only. For this purpose, use the 3 provided containers of cooling
liquid.

With an optional flow heater, the mixture of glycol/water has to be 50:50. The delivery
volume of the flow heater provides a container of pure glycol.

 A total of 4 containers are provided (3 containers of a cooling liquid with a mixture of


glycol/water (40:60) and 1 container of pure glycol). These containers have to be used to
obtain a mixture with an antifreeze agent applicable to -40 Celsius.


The cooling system can be put into operation only after installing the entire CT system.
C
Otherwise, the pump of the split cooling system will be irreversibly damaged.

© Siemens, 2005 CT00-000.811.02.05.02 Page 41 of 50 Common CT


01.09 CTL EN
42 4 Filling the cooling system

4.1.2 Filling without flow heater


Fig. 37: W/A split WCS - filling

(1) Filling and draining valve


(2) Filling and draining valve
(3) Shut-off valve (red lever)
(4) Pressure gage

After connecting the inside unit and the outside ventilator, the system can be filled at the
WCS cabinet as follows:
n Fill the contents (glycol/water mixture) of the delivered canisters into the filling sys‐
tem (not included in the delivery volume).
n Check to ensure that the two valves at the outside ventilator are closed. The valves are
located close to the hose connection. Refer to ( Fig. 26 Page 33).
n Connect the filling system to the filling valve of the WCS ( Pos. 1/Fig. 37 Page 42).
For this purpose, use a 1/2" garden hose (not included in the delivery volume)
n Close the shut-off valve ( Pos. 3/Fig. 37 Page 42) (horizontal/lower position)
n Open the valve ( Pos. 1/Fig. 37 Page 42) (horizontal position).

Common CT CT00-000.811.02.05.02 Page 42 of 50 © Siemens, 2005


01.09 CTL EN
Filling the cooling system 4 43

n Close the valve ( Pos. 2/Fig. 37 Page 42) (vertical position).


n Switch on the filling system. Fill the circuit up to a pressure of 6 bar (read at
( Pos. 4/Fig. 37 Page 42) pressure gage).
n Open the valve ( Pos. 3/Fig. 37 Page 42) (vertical/upper position).
n Close the valve ( Pos. 1/Fig. 37 Page 42) (vertical position) and switch off the filling
system.
n Monitor the filling pressure for 20 min. and check for leaks.
 The primary circuit will be vented automatically by the permanent bleeding de‐
vice.
n Connect a garden hose to the valve ( Pos. 2/Fig. 37 Page 42) and put the other end
of the garden hose into the container of the filling system.
n Set a filling pressure of 2 bar by opening the valve ( Pos. 2/Fig. 37 Page 42) (horizon‐
tal position). Check the filling pressure at the pressure gages
( Pos. 4/Fig. 37 Page 42).
n Close the valve ( Pos. 2/Fig. 37 Page 42) (vertical position).
n Remove the filling hose and check the cooling system for leaks.

After the primary cooling circuit is completely filled, all cooling hose connections have to


be checked at regular 20 min. intervals for possible leaks.
If the connections are free of leaks, the connections have to be insulated as well with
insulation material.

Use insulation material (not in the delivery volume) and insulate blank metal parts at the

 hose connection parts of the indoor unit, outdoor unit, and the optional flow heater.
The cooling hoses and the on-site pipes must be insulated as well.

© Siemens, 2005 CT00-000.811.02.05.02 Page 43 of 50 Common CT


01.09 CTL EN
44 4 Filling the cooling system

4.1.3 Filling with flow heater

The antifreeze protection of the cooling liquid mixture has to be effective down to -40˚
Celsius.
With an optional flow heater, the mixture of glycol/water has to be 50:50.
The provided containers of cooling liquid have to be used to reach this mixing ratio:

 -there are 3 containers with a mixing ratio of 40:60 (glycol/water), provided with the de‐
livery volume of the W/A split cooling system
-there is 1 container of pure glycol (labeled as “GLYKOSOL N”) included in the flow heat‐
er’s delivery volume
With the optional flow heater, a new mixture of cooling liquid is provided in 4 contain‐
ers.

Fig. 38: WCS (indoor unit)

(1) Bleeding device

Common CT CT00-000.811.02.05.02 Page 44 of 50 © Siemens, 2005


01.09 CTL EN
Filling the cooling system 4 45

Fig. 39: Flow heater - connections for filling

(1) Bleeding device


(2) Valve of return route (outdoor to indoor)
(3) Valve of inflow route (indoor to outdoor)
(4) Filling and draining valve for return route
(5) Filling and draining valve for inflow route

After connecting the inside unit, the flow heater and the outside ventilator, the system
can be filled at the WCS cabinet as follows:
Preparatory steps:
n Check to ensure that the two valves at the outside ventilator are closed. The valves are
located close to the hose connection. Refer to ( Fig. 26 Page 33).
n Close the shut-off valve ( Pos. 3/Fig. 37 Page 42) (horizontal/lower position)
n Open the valve ( Pos. 1/Fig. 37 Page 42) (horizontal position).
n Close the valve ( Pos. 2/Fig. 37 Page 42) (vertical position).
n Open the colored cap of the permanent bleeding device ( Pos. 1/Fig. 38 Page 44) at
the WCS cabinet.
n Open the colored cap of the permanent bleeding device ( Pos. 1/Fig. 39 Page 45) at
the flow heater.

© Siemens, 2005 CT00-000.811.02.05.02 Page 45 of 50 Common CT


01.09 CTL EN
46 4 Filling the cooling system

n Open the red valves ( Pos. 2 and 3/Fig. 39 Page 45) at the flow heater.
n Connect the filling system to the filling valve of the WCS ( Pos. 1/Fig. 37 Page 42).
For this purpose, use a 1/2" garden hose (not included in the delivery volume)
Cooling liquid mixture steps:
n Pour the contents of the containers (3 containers are provided with the W/A split cool‐
ing system) into the filler device (filler device is not part of the delivery volume).
 Do not fill the filler device to the limit.
n Use the container of pure glycol (Glykosol N) and the antifreeze check tool to obtain
antifreeze protection effective down to -40˚ Celsius (new mixture of glycol/water is
50:50) in the filler device.
 Before using the antifreeze check tool, read the operator manual!
Filling steps:
n Switch on the filling system. Fill the circuit up to a pressure of 6 bar (read at
( Pos. 4/Fig. 37 Page 42) pressure gage).
 When the filler device no longer contains mixed cooling liquid, close the fill
valve ( Pos. 1/Fig. 37 Page 42) and turn off the filler device.
Prepare a new cooling liquid mixture in the container of the filler device, refer
to “Cooling liquid mixture steps." Subsequently, turn on the filler device and
open the filling valve ( Pos. 1/Fig. 37 Page 42).
Repeat these steps until the cooling circuit is filled up completely.
After the primary cooling circuit is filled up to 6 bar:
n Open the valve ( Pos. 3/Fig. 37 Page 42) (vertical/upper position).
n Close the valve ( Pos. 1/Fig. 37 Page 42) (vertical position) and switch off the filling
system.
n Monitor the filling pressure for 20 min. and check for leaks.
 The primary circuit will be vented automatically by the permanent bleeding de‐
vice.
n Connect a garden hose to the valve ( Pos. 2/Fig. 37 Page 42) and put the other end
of the garden hose into the container of the filling system.
n Set a filling pressure of 2 bar by opening the valve ( Pos. 2/Fig. 37 Page 42) (horizon‐
tal position). Check the filling pressure at the pressure gages
( Pos. 4/Fig. 37 Page 42).
n Close the valve ( Pos. 2/Fig. 37 Page 42) (vertical position).
Final steps:
n Remove the filling hose and check the cooling system for leaks.
n Close the colored cap of the permanent bleeding device ( Pos. 1/Fig. 38 Page 44) at
the WCS cabinet.

Common CT CT00-000.811.02.05.02 Page 46 of 50 © Siemens, 2005


01.09 CTL EN
Filling the cooling system 4 47

n Close the colored cap of the permament bleeding device( Pos. 1/Fig. 39 Page 45) at
the flow heater.

After the primary cooling circuit is completely filled, all cooling hose connections have to


be checked at regular 20 min. intervals for possible leaks.
If the connections are free of leaks, the connections have to be insulated as well with
insulation material.

Use insulation material (not in the delivery volume) and insulate blank metal parts at the
hose connection parts of the indoor unit, outdoor unit, and the optional flow heater.
 For the function of the regulator, the sensor and the outlet pipe have to be insulated!
The cooling hoses and the on-site pipes must be insulated as well.

© Siemens, 2005 CT00-000.811.02.05.02 Page 47 of 50 Common CT


01.09 CTL EN
48 5 Changes to previous version

Page Changes Reason


( Type B - con‐ Switching cabinet of flow heater. Change no.: 522903
necting the ca‐ Thermal sensor cable with immersion sleeve.
bles / Page 24)
( Capillary tube Installation of optional capillary tube device. Change no.: 522904
device (option‐
al) / Page 36)

Common CT CT00-000.811.02.05.02 Page 48 of 50 © Siemens, 2005


01.09 CTL EN
List of Hazard IDs 6 49

There are no Hazard IDs in this document.

© Siemens, 2005 CT00-000.811.02.05.02 Page 49 of 50 Common CT


01.09 CTL EN
All documents may only be used for
rendering services on Siemens
Healthcare Products. Any document
in electronic form may be printed
once. Copy and distribution of elec‐
tronic documents and hardcopies is
prohibited. Offenders will be liable
for damages. All other rights are re‐
served.

siemens-healthineers.com

Siemens Healthineers Headquarters


Siemens Healthcare GmbH
Henkestr. 127
91052 Erlangen
Germany
Telephone: +49 9131 84-0
siemens-healthineers.com

Print No.: CT00-000.811.02.05.02 | Replaces: CT00-000.811.02.04.02


Doc. Gen. Date: 01.09 | Language: English
© Siemens Healthcare GmbH, 2005

siemens-healthineers.com

You might also like