100% found this document useful (1 vote)
198 views138 pages

AB Bulletin 1333 34-20 HP (.55-15 KW) Adjustable Frequency AC Drive (Series D)

The Allen-Bradley Bulletin 1333 Series D Adjustable Frequency AC Drive (34-20 HP, 0.55-15 kW) is engineered for high-performance motor control in demanding applications. It offers a frequency range up to 400 Hz and features V/Hz and Sensorless Vector control modes. Key benefits include programmable acceleration/deceleration, and comprehensive protection against overcurrent, overload, and undervoltage. The drive’s robust design ensures reliability and flexibility in various industrial settings. F
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
100% found this document useful (1 vote)
198 views138 pages

AB Bulletin 1333 34-20 HP (.55-15 KW) Adjustable Frequency AC Drive (Series D)

The Allen-Bradley Bulletin 1333 Series D Adjustable Frequency AC Drive (34-20 HP, 0.55-15 kW) is engineered for high-performance motor control in demanding applications. It offers a frequency range up to 400 Hz and features V/Hz and Sensorless Vector control modes. Key benefits include programmable acceleration/deceleration, and comprehensive protection against overcurrent, overload, and undervoltage. The drive’s robust design ensures reliability and flexibility in various industrial settings. F
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
You are on page 1/ 138

IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Bulletin 1333 3/4-20 HP (.55-15 kW)


Adjustable Frequency AC Drive
(Series D)

User Manual

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Important User Information Because of the variety of uses for this equipment and because of the
differences between this solid-state equipment and electromechanical
equipment, the user of and those responsible for applying this equipment
must satisfy themselves as to the acceptability of each application and use
of the equipment. In no event will Allen-Bradley Company be responsible
or liable for indirect or consequential damages resulting from the use or
application of this equipment.

The illustrations shown in this manual are intended solely to illustrate the
text of this manual. Because of the many variables and requirements
associated with any particular installation, the Allen-Bradley Company
cannot assume responsibility or liability for actual use based upon the
illustrative uses and applications.
No patent liability is assumed by Allen-Bradley Company with respect to
use of information, circuits or equipment described in this text.
Reproduction of the content of this manual, in whole or in part, without
written permission of the Allen-Bradley Company is prohibited.
The information in this manual is organized in numbered chapters. Read
each chapter in sequence and perform procedures when you are instructed
to do so. Do not proceed to the next chapter until you have completed all
procedures.
Throughout this manual we use notes to make you aware of safety
considerations:

ATTENTION: Identifies information about practices or


! circumstances that can lead to personal injury or death, property
damage or economic loss.

Attentions help you:


• Identify a hazard.
• Avoid the hazard.
• Recognize the consequences.

Important: Identifies information that is especially important for


successful application and understanding of the product.

Shock Hazard labels may be located on or inside the drive to alert


people that dangerous voltage may be present.

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Summary of Changes

Summary of Changes
Summary of Manual Changes This release of the 1333-5.2 User Manual contains some new and corrected
information. The new and corrected information is summarized in the table
below. For further information, refer to the page numbers provided.

Description of New or Corrected Information Page Type

Drive Input Terminals 48 Correction

Recommended Wire Size and Torque 415 Correction

SW2 Factory Setting -- Figure 45 420 New

Terms 6 & 3 Analog Meter Output


Meter Load Impedance 422 Correction

Terms 13 & 14 -- S1/4SP


Terms 13 & 14 -- S2/4SP
SW2 Factory Setting 424 New

Parameter 02 -- Deceleration Time 1


From 00.011000 seconds . . . sets the decel time . . . 59 Correction
From 10001600 seconds . . . sets the decel time . . . 59 Correction

Local/Remote Control Enable


If set to 0 . . .
w Local Jog can be selected by . . . the Shift button. 514 Correction
If set to 2. . .
w Local Jog can be selected by . . . the Shift button. 515 Correction

1. SW2 Factory Setting 524 New

As shown in Figure 45 in Chapter 4


If Parameter 19 = 0
When Control Board Switch SW2 is Set to . . . 525 Correction
If Parameter 19 = 1
When Control Board Switch SW2 is Set to . . . 525 Correction
If Parameter 19 = 2
When Control Board Switch SW2 is Set to . . . 525 Correction
As shown in Figure 45 in Chapter 4
If Parameter 19 = 0 and Parameter 20 = 0
When Control Board Switch SW2 is Set to . . . 526 Correction
If Parameter 19 = 1 and Parameter 20 = 0
When Control Board Switch SW2 is Set to . . . 526 Correction
If Parameter 19 = 2 and Parameter 20 = 0
When Control Board Switch SW2 is Set to . . . 526 Correction
As shown in Figure 45 in Chapter 4
If Parameter 19 = 0 and Parameter 20 = 1
When Control Board Switch SW2 is Set to . . . 527 Correction
If Parameter 19 = 1 and Parameter 20 = 1
When Control Board Switch SW2 is Set to . . . 527 Correction
If Parameter 19 = 2 and Parameter 20 = 1
When Control Board Switch SW2 is Set to . . . 527 Correction

Preset Frequency Settings


Auxiliary Accel and Decel Settings 534 Correction

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Table of Contents

PreInstallation Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11


Before installing and operating your 1333 Series D drive,
carefully read this manual and observe all precautions.
The catalog number of your drive as explained in Chapter 2
Drive Identification lists the drive rating, type of enclosure,
nominal line voltage, phase and frequency. Specifications for
all drives including standard controls, adjustment range,
diagnostics and environmental qualifications are listed in
Chapter 3 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Carefully unpack the drive, taking care to save the shipping carton
and any packing material should return be necessary. Verify
that the items on the packing list or bill of lading agree with
your order. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Factory and Field Parameter Settings . . . . . . . . . . . . . . . . C1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Preface

Manual Objective

This manual defines the installation, operation, startup and fault codes for
the Allen-Bradley 1333 Series D Adjustable Frequency AC Drive. It is
intended for use by personnel familiar with the functions of solid-state
drive equipment. Also provided are interconnection drawings for 1333
options in Appendix A, and Bulletin 1333 Series D application data in
Appendix D.

The 1333 Series D User Manual is designed to be read and used like an
ordinary textbook. Read the manual once from the beginning in the order
presented to gain basic knowledge about your drive. Each chapter builds
upon information presented in the previous chapter. The majority of the
information presented is arranged and written by drive function. Individual
parameters in Chapter 5 are grouped under functional sub-headings (such
as Accel and Decel Settings or Volts-per-Hertz Curve Settings), as is the
statup procedure in Chapter 6. Appendix C provides paired parameter
tables which are also grouped by function to graphically show parameter
interaction.

To assure successful installation and operation, the material presented in


each chapter must be thoroughly read and understood before proceeding to
the next chapter. Particular attention should be directed to the Attention and
Important statements contained within. Become familiar with tasks that
must be performed in a sequence for safety and successful completion.

P-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Preface

Important Information about this Manual


This manual has been prepared primarily to support this product in a single
application. It is a standard document that is intended to help the user
understand the individual operating characteristics and limitations of this
equipment including hazards associated with installation and setup
procedures. Note the following points:
• This equipment has been designed to meet the requirements of a
component in an integrated system.
• It must be noted that special considerations are to be given to
characteristics of other peripheral solid-state control equipment and the
cumulative impact on safety.
• Manufacturers and engineering groups responsible for specification or
design of electrical control equipment must refer to applicable industry
standards and codes for specific safety guidelines and interface
requirements.
• In the actual factory environment, the user is responsible to assure
compliance with applicable machine and operator safety codes or
regulations which are beyond the scope and purpose of this document.

General Precautions In addition to the precautions listed throughout this manual, the following
statements which are general to the system must be read and understood.

ATTENTION: Only personnel familiar with the 1333 AC Drive


! and associated machinery should plan or implement the
installation, start-up and subsequent maintenance of the system.
Failure to comply may result in personal injury and/or equipment
damage.
ATTENTION: This assembly may contain parts and
! sub-assemblies that are sensitive to electrostatic discharge. Static
control precautions are required when testing, servicing or
repairing this assembly. Component damage may result if you
ignore electrostatic discharge control procedures. If you are not
familiar with static control procedures, reference Allen-Bradley
Publication 8000-4.5.2, Guarding Against Electrostatic Damage or
any other applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed system can
! result in component damage or reduction in product life. Wiring or
application errors, such as undersizing the motor, incorrect or
inadequate AC supply, or excessive ambient temperatures may
result in malfunction of the system.

P-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Repair/Exchange

Repair or Repair/Exchange Procedure

For your convenience, the Allen-Bradley Standard Drives Division, and the
Allen-Bradley Support Division, provide an efficient and convenient
method of returning equipment eligible for repair or repair/exchange.

A product service report number is required to return any equipment for


repair. This may be obtained from your local Allen-Bradley Distributor or
Area Sales/Support Office.

Return any equipment to be repaired to the Area Sales/Support Center


nearest you. Be sure to reference the product service report number on the
carton and packing slip. Include your company name and address, your
repair purchase order number and a brief description of the problem. This
will facilitate quick return of your equipment.

A complete listing of Area Sales/Support Centers is available from your


local Allen-Bradley Distributor or Sales Office.

R-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

1
Chapter

PreInstallation Care

Before installing and operating your 1333 Series D drive, carefully read
this manual and observe all precautions. The catalog number of your drive
as explained in Chapter 2 — Drive Identification lists the drive rating, type
of enclosure, nominal line voltage, phase and frequency. Specifications for
all drives including standard controls, adjustment range, diagnostics and
environmental qualifications are listed in Chapter 3 — Specifications.

Receiving Once you have received your drive, careful inspection for shipping damage
must be made. Damage to the shipping carton is usually a good indication
that it has received improper handling. Any and all damage should be
immediately reported to the freight carrier and your nearest Allen-Bradley
Area Sales/Support Center.

Carefully unpack the drive, taking care to save the shipping carton and any
packing material should return be necessary. Verify that the items on the
packing list or bill of lading agree with your order.

Storage If the drive will not immediately be installed, it should be stored in a clean,
dry area where the ambient temperature is not less than -25°C nor more
than +65°C. The drive must not be stored in a corrosive environment nor
subject to conditions in excess of the storage environment parameters
stated in Chapter 3 — Specifications.

Shipping The carton and materials that came with your drive have been designed and
tested to provide reasonable protection against damage during transit.
Should the drive be shipped to another location, it is recommended that the
original shipping carton and packing material be used to protect the drive
from damage in transit.

1-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 1
Pre-Installation Care

ATTENTION: This assembly contains parts and sub-assemblies


! that are sensitive to electrostatic discharge. Static control
precautions are required when servicing this assembly. Component
damage may result if you ignore electrostatic discharge control
procedures. If you are not familiar with static control procedures,
reference Allen-Bradley Publication 8000-4.5.2, Guarding Against
Electrostatic Damage, or any other applicable ESD protection
handbook.

Electrostatic Discharge Electrostatic discharge generated by static electricity can damage the
Precautions complimentary metallic oxide semiconductor devices on various drive
boards. It is recommended that you perform these procedures to guard
against this type of damage when circuit boards are removed or installed:
• Wear a wrist type grounding strap that is grounded to the drive chassis.
• Attach the wrist strap before removing the new circuit board from the
conductive packet.
• Remove boards from the drive and immediately insert them into their
conductive packets.

1-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

2
Chapter

Drive Identification

The following is an explanation of the catalog numbering system and


information provided on the Bulletin 1333 Series D shipping carton label
and drive nameplate.

The 1333 Shipping Carton Label PART NO. 151014


SER. NO. A00224 ➑
BULLETIN

1333
ADJUSTABLE INPUT 230/208/200V, 50/60Hz
OUTPUT KVA 2.0
FREQUENCY ENCL. IP 40 ➏
AC DRIVE PHASE 3


MADE IN JAPAN
CAT SER

1333-AAA D
➊ ➋

➊ ➋ ➐
The 1333 Drive Nameplate
BULLETIN 1333 ADJUSTABLE FREQUENCY AC DRIVE
THE STANDARD UNIT DOES NOT PROVIDE MOTOR
OVERLOAD PROTECTION IN ACCORDANCE WITH
THE NEC OR CEC, PART 1. ED 56L
CAT 1333- AAA SER D S/N A00224
IST
3PH AC INPUT
L

MADE IN JAPAN
UL KVA 2.6 VOLTS 230/208/200 HZ 50/60 AMPS 6.5
IN

D
Q

CONT E  3PH AC OUTPUT


KVA 2.0 VOLTS 230/208/200 HZ 60 AMPS 5

➎ ➏ ➏

2-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 2
Drive Identification

❶ Drive Catalog Numbers 1333 Z A A


Bulletin Drive Enclosure Input
Number Rating Type Voltage

The first letter indicates the drive rating.


200/208/230V AC, 3-Phase, 50/60 Hertz Input Voltage
Rating Nominal
Code HP kW
ZAA 3/4 .55
AAA 1 .75
YAA 2 1.5
BAA 3 2.2
CAA 5 4
DAA 7 1/2 5.5
EAA 10 7.5
FAA 15 11
GAA 20 15

380/415/460V AC, 3-Phase, 50/60 Hertz Input Voltage


Rating Nominal
Code HP kW
AAB 1 .75
YAB 2 1.5
BAB 3 2.2
CAB 5 4

The second letter indicates the type of enclosure as initially shipped from
the factory.
A –– NEMA Type 1 (IP20).

The third letter indicates drive input voltage.

Drives with the code ”A” are suitable for operating from any one of the
following voltage inputs:
200/208/230V AC, 50/60 Hz, 3-phase Nominal Voltage.
200/208/230V AC, 50/60 Hz, 1-phase Derated Voltage.

Drives with the code ”B” are suitable for operating from any one of these
voltage inputs: 380/415/460V AC, 50/60 Hz, 3-phase.
❷ Drive Series Number Series D.
❸ Drive Input/Output Power 3-Phase.
❹ Drive Enclosure Rating NEMA Type 1 (IP 20).
❺ Drive Output kVA Listed in Chapter 3, pg. 3-2.
❻ Drive Input Voltage Rating Explained above.
❼ Drive Serial Number Internal factory code.
❽ Drive Part Number Internal factory code.

2-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

3
Chapter

Specifications

Operating Environment Temperature: –10 to + 50°C (+14 to +122°F).

Relative Humidity: 5 to 95% non-condensing.


Altitude: 3,300 feet (1,000 meters) maximum without
derating.
Vibration: Below 0.5G, 0.8 mm peak-to-peak
amplitude, x-y-z direction.
Shock: 16G peak for 11ms duration.

Storage Environment Temperature: –25 to +65°C (–13 to +149°F)

Relative Humidity: 5 to 95% non-condensing.

Enclosure NEMA Type 1 (IP20).


Indicated by catalog number.

Input Power Specifications Drive Rating ZAA-GAA AAB-CAB

Voltage: 200-230V AC, ± 10% 380-460V AC,


± 10%

Frequency: 50/60 Hz, ± 5% 50/60 Hz, ± 5%


Phase: 1 or 3-phase 3-phase
Bus Overvoltage Trip: 430V DC 820V DC
Bus Undervoltage Trip: 160V DC 310V DC
Bus Overcurrent Trip: 200% IET
Power Ride-Thru: 15 ms or longer depending on the load.
Control Ride-Thru: 100 ms or longer depending on the load.
Control Logic Noise Showering arc transients from 350 to 2,000
Immunity: volts.

3-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 3
Specifications

Standard ThreePhase Data 200/208/230V AC, 3Phase, 50/60 Hertz Input Voltage
Input Current, Output Current 200VAC 208VAC 230VAC 200VAC 208VAC 230VAC Total Heat
Rating Nominal Input Input Input Input Output Output Output Output Dissipated
and kVA
Code HP kW Amps kVA kVA kVA Amps kVA kVA kVA Watts (BTU/hr)
ZAA 3/4 .55 4.1 1.4 1.5 1.6 3.2 1.1 1.2 1.3 80 273
AAA 1 .75 6.5 2.3 2.4 2.6 5.0 1.7 1.8 2.0 100 341
YAA 2 1.5 9.0 3.1 3.2 3.6 8.0 2.8 2.9 3.2 170 580
BAA 3 2.2 14.0 4.8 5.0 5.6 11.0 3.8 4.0 4.4 250 853
CAA 5 4 22.0 7.6 7.9 8.8 17.5 6.1 6.3 7.0 360 1228
DAA 71/2 5.5 27.0 9.3 9.7 10.8 24.0 8.3 8.7 9.7 425 1449
EAA 10 7.5 37.0 12.8 13.3 14.7 33.0 11.5 11.9 13.3 480 1637
FAA 15 11 47.0 16.3 16.9 18.8 45.0 15.6 16.2 18.1 565 1927
GAA 20 15 62.0 21.5 22.3 24.7 61.0 21.1 22.0 24.6 610 2080

380/415/460V AC, 3Phase, 50/60 Hertz Input Voltage


380VAC 415VAC 460VAC 380VAC 415VAC 460VAC Total Heat
Rating Nominal Input Input Input Input Output Output Output Output Dissipated
Code HP kW Amps kVA kVA kVA Amps kVA kVA kVA Watts (BTU/hr)
AAB 1 .75 3.3 2.2 2.4 2.6 2.1 1.4 1.5 1.7 100 341
YAB 2 1.5 4.5 3.0 3.2 3.6 4.0 2.6 2.9 3.2 170 580
BAB 3 2.2 8.0 5.3 5.8 6.4 6.0 3.9 4.3 4.8 250 853
CAB 5 4 13.0 8.6 9.3 10.4 9.4 6.2 6.8 7.5 370 1262

Derated SinglePhase Data ❶ 200/208/230V AC, 1Phase, 50 Hertz Input Voltage


Input Current, Output Current 200VAC 208VAC 230VAC 200VAC 208VAC 230VAC Total Heat
and kVA Rating Nominal Input Input Input Input Output Output Output Output Dissipated
Code HP kW Amps kVA kVA kVA Amps kVA kVA kVA Watts (BTU/hr)
ZAA 1/2 .37 5.7 1.1 1.2 1.3 2.4 0.8 0.9 1.0 80 273
AAA 3/4 .55 7.7 1.5 1.6 1.8 3.4 1.2 1.2 1.4 100 341
YAA 1 .75 8.8 1.8 1.8 2.0 4.5 1.6 1.6 1.8 170 580
BAA 11/2 1.1 11.9 2.4 2.5 2.7 5.4 1.9 1.9 2.2 250 853
CAA 2 1.5 17.3 3.5 3.6 4.0 7.7 2.7 2.8 3.1 360 1228
DAA 3 2.2 21.4 4.3 4.5 4.9 11.0 3.8 4.0 4.4 425 1449
EAA 5 4 29.1 5.8 6.1 6.7 15.0 5.2 5.4 6.0 480 1637
FAA 71/2 5.5 38.0 7.6 7.9 8.7 21.0 7.3 7.6 8.4 565 1927
GAA 10 7.5 49.3 9.9 10.3 11.3 28.0 9.7 10.1 11.2 610 2080

200/208/230V AC, 1Phase, 60 Hertz Input Voltage


200VAC 208VAC 230VAC 200VAC 208VAC 230VAC Total Heat
Rating Nominal Input Input Input Input Output Output Output Output Dissipated
Code HP kW Amps kVA kVA kVA Amps kVA kVA kVA Watts (BTU/hr)
ZAA 1/2 .37 6.2 1.2 1.3 1.4 2.6 0.9 0.9 1.0 80 273
AAA 3/4 .55 8.6 1.7 1.8 2.0 3.8 1.3 1.4 1.5 100 341
YAA 1 .75 9.5 1.9 2.0 2.2 4.9 1.7 1.8 2.0 170 580
BAA 11/2 1.1 13.0 2.6 2.7 3.0 5.9 2.0 2.1 2.4 250 853
CAA 2 1.5 18.8 3.8 3.9 4.3 8.4 2.9 3.0 3.3 360 1228
DAA 3 2.2 23.4 4.7 4.9 5.8 12.0 4.2 4.3 4.8 425 1449
EAA 5 4 31.1 6.2 6.5 7.1 16.0 5.5 5.8 6.4 480 1637
FAA 71/2 5.5 41.6 8.3 8.7 9.6 23.0 10.0 8.3 9.2 565 1927
GAA 10 7.5 54.6 10.9 11.4 12.6 31.0 10.7 11.2 12.3 610 2080

❶ .200/208/230VAC units may be derated for single phase input power The single phase will not appear on
the shipping carton label or the drive nameplate.

3-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 3
Specifications

Load Requirements A balanced 3-phase inductive motor load is typical. Other motor loads may
require application assistance.

Output Power Waveform: Sine coded pulse width modulated waveform.


Specifications

Voltage: Drive Rating ZAA-GAA


0 to applied input voltage, 200V AC,
208V AC,
or 230V AC –– maximum output voltage
cannot exceed applied input voltage.
Drive Rating AAB-CAB
0 to applied input voltage, 380V AC, 415V
AC,
or 460V AC –– maximum output voltage
cannot exceed applied input voltage.

Frequency Programmable Min and Max Limits


Range: 0 to 400 Hz remote frequency command.
0.5 to 400 Hz local frequency command.

Frequency ± 0.5% of selected maximum output frequency


Regulation: –10 to +50°C ambient temperature range.

Accel/Decel: Four independently programmable accel times.


Four independently programmable decel times.
Each time may be programmed over a range
from 0.1 to 1600 seconds. If 0 is entered, the
drive will default to 40 ms.

Accel Stall Protection: 140% of rated current.

Decel Stall Protection: 380V DC for 230V AC drive input voltage.


760V DC for 460V AC drive input voltage.

Volts-per-Hertz: Selectable constant or square v/Hz curves.

DC Boost: 0-40% of maximum output voltage


adjustable in 1% increments.

3-3

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 3
Specifications

Starting Torque: 150% nominal at 5 Hz.

Braking Torque: DC Brake: 20% of rated torque (standard)


programmable duration and voltage
Heavy Duty Dynamic Brake: 100% of rated torque.

Stopping Frequency: 0.5-60 Hz

Intermittent Standard: 140% of rated output current for


Overload Capability: 1 minute.
Inverse Trip: 125% of programmable overload trip
level for one minute.

Drive Programmable overload trip function set to motor


Overload Trip: nameplate value.

Ground Fault: Current sensors detect output ground fault at drive


output leads.

Frequency Control Inputs Digital Input Local Speed Control


Frequency 0.01 Hz up to 100 Hz.
Resolution: 0.1 Hz over 100 Hz.
Analog Input Remote Speed Pot
Frequency (Control Terminal Block, Terminals 1, 2 and 3)
Resolution: 0.1 Hz up to 100 Hz.
0.2 Hz up to 200 Hz.
0.5 Hz over 200 Hz.
0-5V DC Input
(Control Terminal Block, Terminals 3 and 4)
0.1 Hz up to 100 Hz.
0.2 Hz up to 200 Hz.
0.5 Hz over 200 Hz.
0-10V DC Input
(Control Terminal Block, Terminals 3 and 4)
0.1 Hz up to 100 Hz.
0.2 Hz up to 200 Hz.
0.5 Hz over 200 Hz.
4-20 mA Input
(Control Terminal Block, Terminals 3 and 5)
0.1 Hz up to 100 Hz.
0.2 Hz up to 200 Hz.
0.5 Hz over 200 Hz.

3-4

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 3
Specifications

Required Control Inputs As a minimum requirement for drive operation, the following four control
inputs must be present to operate the drive:

Start
A momentary contact closure will start the drive. The drive will continue to
run until a stop input is issued or a drive fault occurs. A start input may
come from:
• Either of the Local Control Panel directional start pushbuttons.
• A user supplied N.O. contact or start switch connected to the Control
and Signal Wiring Terminal Block.

Stop
A momentary open contact will stop the drive. A N.C. contact will permit
the drive to run or jog. A stop input may come from:
• The Local Control Panel stop pushbutton.
• A user supplied N.C. contact or stop switch connected to the Control and
Signal Wiring Terminal Block.

Auxiliary Interlock
A maintained closed contact will permit the drive to start, run, or jog. A
momentary open contact will disable drive output. An auxiliary input may
come from:
• The factory installed metal jumper between terminals 16 and 17 of the
Control and Signal Wiring Terminal Block.
• A user supplied N.C. contact or switch wired to terminals 16 and 17
when the factory supplied jumper is removed.

Speed Reference
A speed reference sets the drive operating frequency. A speed reference
input may come from:
• Either of the Local Control Panel directional start pushbuttons.
• A user supplied 10kΩ, 2W remote speed potentiometer connected to the
Control and Signal Wiring Terminal Block.
• A 0-5V DC analog signal connected to the Control and Signal Wiring
Terminal Block.
• A 0-10V DC analog signal connected to the Control and Signal Wiring
Terminal Block.
• A 4-20 mA analog signal connected to the Control and Signal Wiring
Terminal Block.
• 1-3 programmable preset speed switches connected to the Control and
Signal Wiring Terminal Block. Through programming, a total of seven
preset speeds may be selected.

3-5

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 3
Specifications

Optional Remote Control Inputs The following optional inputs may be connected to the Series D Bulletin
1333 drive at the Control and Signal Wiring Terminal Block.
Two or Three-Wire Start/Stop Control
Forward Reverse Control
Jog
Three Programmable Preset Speed Select Switches
Auxiliary Interlock

Contact Outputs The following contact outputs are available as standard. Contacts are
isolated from Logic Common and other drive circuitry and have the
following ratings.
Resistive rating: 120V AC or 30V DC, 1 Amp.
Inductive rating: 120V AC or 30V DC, 0.5 Amps.

At Speed: 1 N.O. contact, closed when the drive is at or above


command speed
Run or 1 N.O. contact closed when the drive is running, at
Overload: programmed speed, at 140% of rated output current, or
over the programmable overload level.
No Fault/Fault: 1 set of Form C contacts that change state to indicate that
the drive has received a fault or that a fault is present when
the drive is powered up.

Analog Outputs 0-10V DC or 0-1 mA output programmable from 75-125% of running


frequency.

Drive Displays Local Displays drive output frequency, equivalent motor


Programming speed, drive output amps and drive control source. May be
and Display toggled to program and display 62 drive parameters.
Panel: Should a fault occur while the drive is running, the panel
will display the fault code.

Bus Charged: Internal neon display to indicate bus voltage is greater than
50V DC.

3-6

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

4
Chapter

Installation and Wiring


General Input Power Conditioning The Series D 1333 is suitable for direct connection to a correct voltage AC
power line. There are however certain power line conditions which may
introduce the possibility of drive input power component malfunction. To
reduce the possibility of these malfunctions, a line reactor or isolation type
transformer may be required. If the use of an input transformer is desired,
only an isolation type transformer should be used.
The basic rules for determining if a line reactor or isolation type
transformer is required are as follows:
1. If the AC line supplying the drive has power factor correction capacitors
connected, an AC line reactor or isolation type transformer must be
connected between the capacitor bank and the input to the drive.
2. If the AC line frequently experiences transient power interruptions or
significant voltage spikes, an AC line reactor or isolation type
transformer should be used.

General Installation ATTENTION: An incorrectly applied or installed system can


Requirements ! result in component damage or reduction in product life. The most
common causes are:
• Wiring the AC line to the drive output or control terminals.
• Improper bypass or output circuits.
• Output circuits which do not connect directly to the motor.
• Incorrect or inadequate AC supply.
• Excessive ambient temperature.
Contact Allen–Bradley for assistance with application or wiring.

Before actual installation, remove all packing material, wedges or braces


from within and around the drive. The 1333 must be installed in an area
where the following installation and environmental guidelines are met.
• Cabinet mounting must be upright, leaving room for a minimum
clearance of 4 inches (102 mm) on the top and bottom and 2 inches (51
mm) on the sides for proper ventilation.
• The drive should be easily accessible for maintenance and
troubleshooting.
• The rated altitude must not exceed 3,300 feet (1,000 meters).
• Vibration must be within the ratings outlined in Chapter 3 –
Specifications.
• The ambient atmosphere must not contain volatile or corrosive gas,
vapors or dust.
• The relative humidity must not exceed 95% for all drive ratings.
• The ambient temperature for the drive must be kept within –10 to +50°C
for all ratings.
4-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

ZAACAA 230V Dimensions, Weights and Conduit Entry Locations


Nominal Dimensions and Weights in Inches (Millimeters) and Pounds (Kilograms)
HP kW Rating Code A B C D E F G H I J K Weight
3/4, 1 .55, .75 ZAA, AAA 8.90 10.04 4.72 8.27 9.45 0.30 0.30 2.48 1.97 2.24 1.26 6.0
(226) (255) (120) (210) (240) (8) (8) (63) (50) (57) (32) (2.7)
2 1.5 YAA 8.90 11.26 5.31 8.27 10.63 0.30 0.30 2.48 1.97 2.83 1.85 8.0
(226) (286) (135) (210) (270) (8) (8) (63) (50) (72) (47) (3.6)
3, 5 2.2, 4 BAA, CAA 10.20 13.54 6.90 9.45 12.80 0.30 0.30 3.13 1.97 4.13 2.80 20.0
(259) (344) (175) (240) (325) (8) (8) (80) (50) (105) (71) (9.1)

G
0.25 IN (6.35 MM) DIA. MOUNTING HOLES

ADJUSTABLE FREQUENCY AC MOTOR DRIVE

F F Hz

LOCK

SELECT ENTER
E
B
STOP
NO.

03 SHIFT

G
F D F C
A

(NEMA Type 1 –– Front) (NEMA Type 1 –– Side)

0.905 IN (23.0 MM) DIA.


CONDUIT ENTRY HOLES

J
K

I I H

(NEMA Type 1 –– Bottom)


4-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

DAAGAA 230V Dimensions, Weights and Conduit Entry Locations


Nominal Dimensions and Weights in Inches (Millimeters) and Pounds (Kilograms)
HP kW Rating Code A B C D E F G H I J K Weight
71/2, 10 5.5, 7.5 DAA, EAA 10.63 17.72 8.27 7.87 17.13 1.38 0.30 2.76 2.56 6.31 1.38 30.0
(270) (450) (210) (200) (435) (35) (8) (70) (65) (160) (35) (13.6)
15, 20 11, 15 FAA, GAA 10.63 21.65 8.27 7.87 21.06 1.38 0.30 2.76 2.56 6.31 1.72 43.0
(270) (550) (210) (200) (535) (35) (8) (70) (65) (160) (43.8) (19.5)

G
0.28 IN (7.0 MM) DIA. MOUNTING HOLES

ADJUSTABLE FREQUENCY AC MOTOR DRIVE

E
B

I 8 0 0 Hz

LOCK

SELECT ENTER

STOP
NO.

AI. SHIFT

F D F G C
A

(NEMA Type 1 –– Front) (NEMA Type 1 –– Side)

K DIA. CONDUIT ENTRY HOLES

I I H
(NEMA Type 1 –– Bottom)
4-3

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

AABCAB 460V Dimensions, Weights and Conduit Entry Locations


Nominal Dimensions and Weights in Inches (Millimeters) and Pounds (Kilograms)
HP kW Rating Code A B C D E F G H I J K Weight
3/4, 1 .55, .75 AAB 8.90 11.26 5.31 8.27 10.63 0.30 0.30 2.48 1.97 2.83 1.85 9.0
(226) (286) (135) (210) (270) (8) (8) (63) (50) (72) (47) (4.1)
2 1.5 YAB 8.90 11.26 5.31 8.27 10.63 0.30 0.30 2.48 1.97 2.24 1.26 9.0
(226) (286) (135) (210) (270) (8) (8) (63) (50) (57) (32) (4.1)
3, 5 2.2, 4 BAB, CAB 10.20 13.54 6.90 9.45 12.80 0.30 0.30 3.13 1.97 4.13 2.80 20.0
(259) (344) (175) (240) (325) (8) (8) (80) (50) (105) (71) (9.1)

G
0.25 IN (6.35 MM) DIA. MOUNTING HOLES

ADJUSTABLE FREQUENCY AC MOTOR DRIVE

E
60.00 Hz

A
B
LOCK

SELECT ENTER

STOP
NO.

LL. SHIFT

G
F D F C
A
(NEMA Type 1 –– Front) (NEMA Type 1 –– Side)

0.905 IN (23.0 MM) DIA.


CONDUIT ENTRY HOLES

J
K

I I H

(NEMA Type 1 –– Bottom)


4-4

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

General Wiring Procedures ATTENTION: Do not proceed without reading the information
! on this page. Failure to understand procedures and hazards may
result in personal injury or equipment damage.

1. The National Electrical Code requires that a circuit breaker or fusible disconnect
switch be provided in the drive branch circuit. Providing drive input fusing
alone is not sufficient to meet NEC guidelines. The 1333 does not provide this
requirement. Selection of a branch circuit breaker or fusible disconnect should
be based on the drive input current rating. Refer to the 3-Phase and 1-Phase
Power Terminal Block Wiring sections in this chapter for mandatory AC input
fusing recommendations for drive short circuit protection.

2. The National Electrical Code requires that motor overload protection be


provided in the motor branch circuit. Parameter 6 when used with Parameter 7
provides motor overload protection. NEC however, recognizes this protection as
being provided by eutectic alloy or bi-metal overload relays. If it necessary to
meet NEC motor branch protection approval, eutectic alloy, bi-metal overload
relays or an equivalent should be installed. Refer to article 430 of the NEC and
any additional codes for specific requirements and additional information.

3. The National Electrical Code and local regulations govern the installation and
wiring of the 1333. All input and output power wiring, control wiring and
conduit must be brought through the drive conduit entry holes provided on the
enclosure. Connections to the drive must be made as shown in the following
sections and in accordance with the drive nameplate, National Electrical Code
requirements and any additional interconnection diagrams packed with the
drive.

4. The voltage on each phase of the incoming line to the drive must match the
drive input rating. Verify the drive rating by referring to the input voltage listed
on the drive nameplate. If the incoming line voltage is out of this tolerance,
equipment may be damaged or fail to operate.

5. If multiple drives are used, do not use common cabling for AC input or output
leads. If multiconductor cable is used, separate 3-conductor input and output
cable for each drive must be used.

6. All signal wiring must be run separate from power or control wiring. Verify that
shielded cable and/or conduit is used if indicated on any interconnection
diagrams or in the following sections. If shielded cable is required, shields must
be grounded at the drive end only at one of the drive ground lugs provided.

7. Nearby relays, solenoids or brake coils can produce electrical noise transients
and cause erratic drive behavior. Transient suppression networks must be added
across the coils of these devices.

8. Since most startup difficulties result from incorrect wiring, every precaution
should be taken to assure that the wiring is as indicated on the diagrams and
information packed with the drive.

4-5

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Wire Group Numbers The following chart identifies general wire categories that will be
encountered when installing the 1333 and other AC drives. Each category
has an associated wire group number that is used in the following sections
to identify the wire to be used. Application and signal examples along with
the recommended type of cable for each group is provided. A matrix
providing the recommended minimum spacing between different wire
groups run in the same tray or separate conduit is also provided.

For Tray:
Recommended minimum spacing between different wire
groups in the same tray

Wire For Conduit:


Wire Application Signal Recommended Cable
Category Group Example Different wire groups must be run in separate conduit
Inches and (Millimeters)

Wire Power Power Control Control Signal Signal


Group 1 2 3 4 5 6

3Conductor Cable In 9.00 9.00 9.00 9.00


2.3 kV, 3j Per NEC Tray (228.6) (228.6) (228.6) (228.6)
AC Power Local Codes
1 (> 600 V AC) AC Lines
and
Between 3.00 (76.2)
Application Requirements
Conduit Between Conduit
Power
Per NEC In 9.00 9.00 6.00 6.00
Local Codes Tray (228.6) (228.6) (152.4) (152.4)
2
AC Power
(to 600 V AC)
480V, 3j ❶ and
Application Between 3.00 (76.2)
Requirements Conduit Between Conduit

115V AC or 115V DC Relay Logic Per NEC In 9.00 6.00 9.00 6.00
Logic PLC I/O Local Codes Tray (228.6) (152.4) (228.6) (152.4)
3 and
115V AC Power Supplies Application Between 3.00 (76.2)
Power Instruments Requirements Conduit Between Conduit
Control
Per NEC In 9.00 6.00 6.00 9.00
Local Codes Tray (228.6) (152.4) (152.4) (228.6)
24V AC or 24V DC and
4 PLC I/O
Logic Application
Between 3.00 (76.2)
Requirements
Conduit Between Conduit

Analog Signals
524V DC Supplies Belden 8760
DC Supplies
5 Belden 8770
Digital Power Supplies Belden 9460 All signal wiring must be run in separate steel conduit.
(Low Speed) TTL Logic Level A wire tray is not suitable.
Signal

The minimum spacing between conduit containing different


Digital Pulse Train Belden 8760
6 wire groups is 3.00 inches (78.2 mm).
(High Speed) Input Belden 9460

❶ Refer to precautions in General Wiring Procedures concerning multiconductor cables.

Belden 8760 18 AWG, twisted pair, shielded.


Belden 8770 18 AWG, 3 conductor, shielded.
Belden 9460 18 AWG, twisted pair, shielded.
Note 1 Steel conduit is recommended for all 1333 power or control wiring and required for all 1333 signal wiring. All input and output power wiring, control wiring or conduit
should be brought through the drive conduit entry holes provided. Use appropriate connectors to maintain the environmental rating of the enclosure.
Note 2 Spacing between wire groups is the recommended minimum for parallel runs of 200 feet or less.
Note 3 All shields for shielded cable must be grounded at the drive end only, at one of the ground terminal lugs provided -- The other end must be insulated and remain
floating. Shields for cables from one enclosure to another must be grounded only at the enclosure nearest the drive. If splicing of shielded cables is required, the
shield must remain continuous and insulated from ground.
Note 4 AC and DC circuits must be run in separate conduit or trays.
Note 5 A voltage drop in motor leads may adversely affect motor starting and running performance. Installation and application requirements may dictate larger wire sizes
than indicated in the NEC guidelines.

4-6

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Terminal Block Power Wiring Important:


1. The 1333 does not provide input power short circuit fusing.
Specifications for the recommended fuse size and type to provide drive
input power protection against short circuits are provided on the
following pages. Branch circuit breakers or disconnect switches cannot
provide this level of protection for drive components.
2. Each Bulletin 1333 must have its own dedicated input and output power
leads. If multiconductor cable is used, separate 3-conductor input and
output cable for each drive must be used.
3. For multimotor operation, the combined total of motor full load current
must not exceed the rated output current of the drive.
4. Verify that the motor windings are properly connected to receive the full
drive output voltage rating.

ATTENTION:
! 1. Any disconnecting means wired to drive output terminals
U/ V W/ must be capable of stopping the drive if
T1, /T2 and T3
opened during drive operation. If opened during drive operation,
the drive will continue to produce output voltage into an open
motor circuit causing a potential shock hazard.
2. The start/stop control circuitry in the 1333 includes solid-state
components. If hazards due to accidental contact with moving
machinery or unintentional flow of liquid, gas or solids exist, an
additional hard wired stop circuit is required to remove AC line
power to the drive. When AC input power is removed, there will
be a loss of inherent regenerative braking effect and the motor
will coast to a stop. An auxiliary braking method may be
required.
The 1333 is intended to be controlled by control input signals
that will start and stop the motor. A device that routinely
disconnects then reapplies line power to the drive for the purpose
of starting and stopping the motor must not be used. After a
hard wired stop has been initiated, allow at least five minutes
before reapplying input power to the drive. The allowable
number of hard wired start/stops are 1 cycle within a 5 minute
period. Wait 5 minutes before attempting the next hard wired
stop cycle to allow the drive precharge resistors to cool.
Refer to codes and standards applicable to your particular system
for specific requirements and additional information.

4-7

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

3/45HP (.554kW) Input and output power connections are marked on the drive Power
Terminal Block Power Wiring Terminal Block. The Power Terminal Block is an eight position terminal
block located at the bottom of the Main Control Board. For maintenance
and setup procedures, the drive may be operated without a motor
connected.

Drive Input Terminals


T/
L3
S/
L2
R/
L1

Drive Power Terminal Block

Drive Ground Terminals

Figure 41 -- 3/45HP (.554kW) Terminal Block Power Wiring

4-8

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

71/220HP (5.515kW) Input and output power connections are marked on the drive Power
Terminal Block Power Wiring Terminal Block. The Power Terminal Block is an eight position terminal
block located at the bottom of the drive. For maintenance and setup
procedures, the drive may be operated without a motor connected.

Drive Output Terminals


W/
T3
V/
T2
U/
T1

Drive Power Terminal Block

Drive Ground Terminals

Figure 42 -- 71/220HP (5.515kW) Terminal Block Power Wiring

4-9

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

ZAAEAA 3Phase R/ S/ T/ U/ V/ W/ +BUS -BUS


L1 L2 L3 T1 T2 T
Power Terminal Block Wiring 3

jA jB jC
❶ ❶ ❶
1333
Motor Dynamic Brake

jA jB jC

AC Incoming Line

Earth Earth
Ground Ground

❶ User supplied drive input fuses.


❷ Motor disconnecting means including branch circuit, short circuit, and ground-fault protection.

R/ S/ T/
L1, L2, L3
Input AC line Terminals are not phase sensitive.
For drives rated ZAA-EAA, nominal 3-phase input voltage is
200/208/230V AC, 50/60 Hz.
For drives rated AAB-CAB, nominal 3-phase input voltage is
380/415/460V AC, 50/60 Hz.
Branch disconnect and short circuit protection is not part of the standard
1333 and must be supplied by the user. Drive input fuses are required to
provide component protection against malfunction of electronic circuits.

U/T1, V/T2, W/T3


Connect the motor leads to these terminals.

+ BUS, - BUS
DC bus terminals are reserved for the 1333 dynamic brake option. Refer to
the 1333 dynamic brake option instructions for installation and connection
details.

GND
Two ground terminals have been provided in the drive. Either one of these
terminals must be connected to earth ground or the ground of the building
electrical system. The motor frame must also be connected to earth ground.
Refer to the motor manufacturer’s installation instructions for specific
details.

4-10

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

If You Use
200/208/230V AC, 3Phase Input Voltage

: 230/208VA.C.
CAUTION Input Voltage Only
Use 75 Degree C ❷ AWG Copper Wire
Torque to ❸ Lb-in
(Power Terminal Block Cover)

Power Recommended
Rating Wire Wire Recommended
Code Group ❶ Size ❷ Torque ❸
ZAA 2 14 AWG (2.5mm2) 9 Inlbs (1.02Nm)
AAA 2 14 AWG (2.5mm2) 9 Inlbs (1.02Nm)
YAA 2 14 AWG (2.5mm2) 9 Inlbs (1.02Nm)
BAA 2 12 AWG (4.0mm2) 9 Inlbs (1.02Nm)
CAA 2 10 AWG (6.0mm2) 9 Inlbs (1.02Nm)
DAA 2 8 AWG (10.0mm2) 10 Inlbs (1.13Nm)
EAA 2 8 AWG (10.0mm2) 10 Inlbs (1.13Nm)
❶ Wire group number chart, page 46.

Select from the following drive input fuses.


Drive Rating ZAA Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating AAA Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating YAA Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating BAA Fuse Size 30AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating CAA Fuse Size 40AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating DAA Fuse Size 70AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating EAA Fuse Size 80AFuse Type 600V Class K5 UL Listed or Equivalent

If You Use
380/415/460V AC, 3Phase Input Voltage

460/415/380VA.C.
CAUTION Input
: Voltage Only
Use 75 Degree C ❷ AWG Copper Wire
Torque to ❸ Lb-in
(Power Terminal Block Cover)

Power Recommended
Rating Wire Wire Recommended
Code Group ❶ Size ❷ Torque ❸
AAB 2 14 AWG (2.5mm2) 9 In-lbs (1.02N-m)
YAB 2 14 AWG (2.5mm2) 9 In-lbs (1.02N-m)
BAB 2 14 AWG (2.5mm2) 9 In-lbs (1.02N-m)
CAB 2 14 AWG (2.5mm2) 9 In-lbs (1.02N-m)
❶ Wire group number chart, page 4-6.

Select from the following drive input fuses.


Drive Rating AABFuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating YABFuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating BABFuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating CABFuse Size 20AFuse Type 600V Class K5 UL Listed or Equivalent
4-11

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

FAA or GAA 3Phase


Power Terminal Block Wiring
GND R/ S/ T/ U/ V/ W/ +BUS -BUS GND
L L L T T T
1 2 3 1 2 3
Earth Earth
Ground Ground
❶ ❶ ❶ jA jB jC

Motor 1333
Dynamic Brake

jA jB jC

AC Incoming Line

❶ User supplied drive input fuses.


❶ Motor disconnecting means including branch circuit, short circuit, and ground-fault protection.

R/ S/ T/
L1, L2, L3
Input AC line Terminals are not phase sensitive.
For drives rated FAA or GAA, nominal 3-phase input voltage is
200/208/230V AC, 50/60 Hz.
Branch disconnect and short circuit protection is not part of the standard
1333 and must be supplied by the user. Drive input fuses are required to
provide component protection against malfunction of electronic circuits.

U/ V/ W/
T1, T2, T3
Connect the motor leads to these terminals.

+ BUS, - BUS
DC bus terminals are reserved for the 1333 dynamic brake option. Refer to
the 1333 dynamic brake option instructions for installation and connection
details.

GND
Two ground terminals have been provided in the drive. Either one of these
terminals must be connected to earth ground or the ground of the building
electrical system. The motor frame must also be connected to earth ground.
Refer to the motor manufacturer’s installation instructions for specific
details.

4-12

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

If You Use
FAA or GAA Units
Lugs are required to terminate wires for FAA or GAA units at the Power Terminal Block.

CAUTION : 230/208VA.C.
Input Voltage Only
Use 75 Degree C ❷ AWG Copper Wire
Use U.L. Listed Crimp Connectors ❸
(Power Terminal Block Cover)
Power Recommended
Rating Wire Wire
Code Group ❶ Size ❷
FAA 2 6 AWG (16.0mm2)
GAA 2 3 AWG (30.0mm2)
❶ Wire group number chart, page 46.
❸ UL Listed crimp connectors are required and must be installed using the proper crimping tool.
Crimp connectors must be sized to the wire size chosed.
When using crimp connectors on terminal studs that are not isolated from each other,
a minimum spacing of 0.4 Inches (10.16mm) is required.

Select from the following drive input fuses.

Drive Rating FAA Fuse Size 100AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating GAA Fuse Size 125AFuse Type 600V Class K5 UL Listed or Equivalent

4-13

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

ZAAEAA 1Phase R/ S/ T/ U/ V/ W/ +BUS -BUS


L1 L2 L3 T1 T2 T
Power Terminal Block Wiring 3

jA jB jC
❶ ❶
1333
Motor Dynamic Brake

AC Incoming Line

Earth Earth
Ground Ground

❶ User supplied drive input fuses.


❷ Motor disconnecting means including branch circuit, short circuit, and ground-fault protection.

S/ and T/
L2 L3
Input AC line Terminals are not phase sensitive.
For drives rated ZAA-EAA, nominal 1-phase input voltage is
200/208/230V AC, 50/60 Hz.
Branch disconnect and short circuit protection is not part of the standard
1333 and must be supplied by the user. Drive input fuses are required to
provide component protection against malfunction of electronic circuits.

U/ V/ W/
T1, T2, T3
Connect the motor leads to these terminals.

+ BUS, - BUS
DC bus terminals are reserved for the 1333 Dynamic Brake Option. Refer
to the 1333 Dynamic Brake Option instructions for installation and
connection details.

GND
Two ground terminals have been provided in the drive. Either one of these
terminals must be connected to earth ground or the ground of the building
electrical system. The motor frame must also be connected to earth ground.
Refer to the motor installation instructions for specific details.

4-14

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

If You Use
200/208/230V AC, 1Phase Input Voltage

CAUTION : 230/208VA.C.
Input Voltage Only
Use 75 Degree C ❷ AWG Copper Wire
Torque to ❸ Lb-in
(Power Terminal Block Cover)

Power Recommended
Rating Wire Wire Recommended
Code Group ❶ Size ❷ Torque ❸
ZAA 2 14 AWG (2.5mm2) 9 In-lbs (1.02N-m)
AAA 2 14 AWG (2.5mm2) 9 In-lbs (1.02N-m)
YAA 2 14 AWG (2.5mm2) 9 In-lbs (1.02N-m)
BAA 2 12 AWG (4.0mm2) 9 In-lbs (1.02N-m)
CAA 2 10 AWG (6.0mm2) 9 In-lbs (1.02N-m)
DAA 2 8 AWG (10.0mm2) 10 In-lbs (1.13N-m)
EAA 2 8 AWG (10.0mm2) 10 In-lbs (1.13N-m)
❷ Wire group number chart, page 4-6.

Select from the following drive input fuses.

Drive Rating ZAA Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating AAA Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating YAA Fuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating BAA Fuse Size 30AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating CAA Fuse Size 40AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating DAA Fuse Size 70AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating EAA Fuse Size 80AFuse Type 600V Class K5 UL Listed or Equivalent

4-15

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

FAA or GAA 1Phase


Power Terminal Block Wiring
GND R/ S/ T/ U/ V/ W/ +BUS -BUS GND
L L L T T T
1 2 3 1 2 3
Earth Earth
Ground Ground
❶ ❶ jA jB jC

Motor 1333
❷ Dynamic Brake

AC Incoming Line

❶ User supplied drive input fuses.


❷ Motor disconnecting means including branch circuit, short circuit, and ground-fault protection.

S/ and T/
L2 L3
Input AC line Terminals are not phase sensitive.
For drives rated FAA or GAA, nominal 1-phase input voltage is
200/208/230V AC, 50/60 Hz.
Branch disconnect and short circuit protection is not part of the standard
1333 and must be supplied by the user. Drive input fuses are required to
provide component protection against malfunction of electronic circuits.

U/ V/ W/
T1, T2, T3
Connect the motor leads to these terminals.

+ BUS, - BUS
DC bus terminals are reserved for the 1333 Dynamic Brake Option. Refer
to the 1333 Dynamic Brake Option instructions for installation and
connection details.

GND
Two ground terminals have been provided in the drive. Either one of these
terminals must be connected to earth ground or the ground of the building
electrical system. The motor frame must also be connected to earth ground.
Refer to the motor installation instructions for specific details.

4-16

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

If You Use
FAA or GAA Units
Lugs are required to terminate wires for FAA or GAA units at the Power Terminal Block.

CAUTION : 230/208VA.C.
Input Voltage Only
Use 75 Degree C ❷ AWG Copper Wire
Use U.L. Listed Crimp Connectors ❸

(Power Terminal Block Cover)


Power Recommended
Rating Wire Wire
Code Group ❶ Size ❷
FAA 2 6 AWG (16.0mm2)
GAA 2 3 AWG (30.0mm2)

❶ Wire group number chart, page 46.


❸ UL Listed crimp connectors are required and must be installed using the proper crimping tool.
Crimp connectors must be sized to the wire size chosed.
When using crimp connectors on terminal studs that are not isolated from each other,
a minimum spacing of 0.4 Inches (10.16mm) is required.

Select from the following drive input fuses.

Drive Rating FAA Fuse Size 100AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating GAA Fuse Size 125AFuse Type 600V Class K5 UL Listed or Equivalent

4-17

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Control and Signal Wiring The Control and Signal Wiring Terminal Block is located at the bottom of
Terminal Block the Control Board. The Control and Signal Wiring Terminal Block is a
twenty-four position terminal block with markings of 1 to 24. The drive is
capable of operating from the Local Control and Programming Panel
without any external control or signal connections provided the factory
installed jumper at terminals 16 and 17 is installed. When required,
external operator elements may be connected to provide remote control of
the drive. Several additional drive control functions and status outputs are
also available for use at this terminal block.

Drive Control Board Switches


SW2
SW1

Drive Control and Signal Wiring Terminal Block

Drive Ground Terminals

Figure 43 -- 3/45HP (.554kW) Control and Signal Wiring Terminal Block

4-18

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Drive Control Board Switches


SW2
SW1

Drive Control and Signal Wiring Terminal Block

Drive Ground Terminals

Figure 44 -- 71/220HP (5.515kW) Control and Signal Wiring Terminal Block

4-19

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Figure 45 -- Control and Signal Wiring Terminal Block Interconnection Diagram

SW1 SW2
1mA 4SP Factory
Logic Set to
Common 4SP

CR1 CR2 CR3 CR3

10V 8SP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Drive Start Stop Rev Jog S1 S2


End Factory
Shield Installed
Jumper
Pot CR1 CR2 CR3 CR3
Pot Wiper Pot Programmable Outputs Fault Contacts
High Low Drive Input Power Applied Drive Input Power Applied
Start/Stop SW2 set to 4SP No Output Signal Present No Fault Present
3Wire Control
Aux Reset
- + Interlock Lockout
05V
External 010V S1
Speed Pot Stop
- +
4-20mA Start
2Wire Control
S2

- +

Earth Analog Meter


Ground S3
1mA Maximum when SW1 set to 1mA
10V Maximum when SW1 set to 10V
SW2 set to 8SP

Input Signal Recommended Recommended


Terminals Input Signal Wire Group ❶ Wire Size Torque
Terminals 1, 2, 3 External Speed Potentiometer 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 3, 8, 11 and 17 Logic Common 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 4 and 3 05 or 010V DC 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 5 and 3 420mA 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 7 and 8 Start 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 9 and 8 Stop 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 10 and 11 Reverse 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 12 and 11 Jog 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 13 and 14 S1/4SP Position 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 14 and 15 S2/4SP Position 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 11 and 13 S1/8SP Position 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 11 and 14 S2/8SP Position 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 11 and 15 S3/8SP Position 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 16 and 17 Auxiliary Interlock 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 17 and 18 Reset Lockout 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)

Output Signal Recommended Recommended


Terminals Output Signal Wire Group ❶ Wire Size Torque
Terminal 6 and Logic Common 01mA or 010V Meter 5 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 19 and I20 CR1 Programmable Contact 3 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 20 and 21 CR2 Programmable Contact 3 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 22 and 23 CR3 Fault Contact 3 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
Terminals 23 and 24 CR3 Fault Contact 3 16 AWG (1.5mm2) 7 InLbs (.791 Nm)
❶ Wire group number chart, page 46.

4-20

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Important: Control and signal functions affected by drive parameter


selection and programming are indicated on the following pages. Refer to
the Programming section in Chapter 5 for detailed parameter operating
descriptions.

Terminals 1, 2 and 3
These terminals are provided for connecting a remote 10kΩ, 2W
potentiometer. To enable a potentiometer to be connected to these
terminals, Parameter 9 must be set to 1, 2 or 3. The potentiometer
frequency control range is the range between minimum and maximum
drive frequency as set by Parameters 15, 16, 50, 51, 53 and/or 54. The
frequency resolution is 0.1 Hz up to 100 Hz, 0.2 Hz up to 200 Hz, and
0.5 Hz if over 200 Hz.

Terminal 1
Potentiometer High
Full CW or high side external potentiometer connection.

Terminal 2
Potentiometer Wiper
Wiper external potentiometer connection.

Terminal 3
Potentiometer Low
Full CCW or low side external potentiometer connection.

Terminals 3, 8, 11, and 17


Logic Common
These terminals are provided to terminate both minus and drive common
signals to the Control and Signal Wiring Terminal Block.

Terminals 4 and 3
05 or 010VDC
This terminal is provided to terminate a 0 to +5 or +10V DC speed
reference signal. The minus signal is terminated at Logic Common.
Parameter 9 enables the speed reference signal and selects either a 0-5V
input signal (when set to 1), or a 0-10V input signal (when set to 2).
Parameters 52, 53 and 54 sets the output signal to be either directly or
inversely proportional. The input impedance from Terminal 4 to logic
common is approximately 40kΩ. The range of frequency control is
between the minimum and maximum drive frequency settings or frequency
clamps as set by Parameters 15, 16, 50, 51, 53 and/or 54. The frequency
resolution is 0.1 Hz up to 100 Hz, 0.2 Hz up to 200 Hz, and 0.5 Hz if over
200 Hz.

4-21

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

ATTENTION: Unexpected machine acceleration can cause injury


! or death.
If Parameter 9 is set to a value other than 0, a loss of the
potentiometer low reference signal at terminal 3 of the drive
terminal block will allow the drive to immediately accelerate to
maximum frequency if the drive is running or a start command has
been received.
Ensure that remote potentiometer connection integrity is
maintained and inspected in accordance with NFPA 70B standards
for maintenance of electrical equipment.

ATTENTION: Terminals 4, 5 and 6 are internally protected from


! reverse polarity signals or input signals rising above 120% of the
maximum input signal. If reverse polarity or levels are maintained
above 120%, signals may be degraded and component damage may
result.

Terminals 5 and 3
420mA Input
This terminal is provided to terminate a +4 to 20 mA DC speed reference
signal. The minus signal is terminated at Logic Common. Parameter 9
enables and selects the 4-20mA input signal. Parameters 52, 53 and 54 sets
the input signal to be either directly or inversely proportional. The input
impedance from Terminal 5 to logic common is approximately 390Ω. The
range of frequency control is between the minimum and maximum drive
frequency settings or frequency clamps. The frequency resolution is 0.1 Hz
up to 100 Hz, 0.2 Hz up to 200 Hz, and 0.5 Hz if over 200 Hz.

Terminals 6 and 3
Analog Meter Output
This terminal provides a 0-1mA or 0-10V DC signal that may be used with
a user supplied analog meter. The minus signal is terminated at logic
common. Switch SW1, a 1mA/10V switch on the Control Board, sets the
output signal to either 0-1mA or 0-10V.
For a 0–1mA voltage output, the load impedance of the meter must be
10kΩ or less.
For a 0–10V voltage output, the load impedance of the meter must be
300Ω or less.
Parameter 55 is used to set the 1mA output signal to equal 75-125% of
maximum output frequency while the drive is running. Parameter 56 is
used to adjust the 10V to equal 75-125% of maximum output frequency
while the drive is running.
4-22

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Terminals 7 and 8
Start
This remote input will command the drive to start if all hardwired
interlocks are closed and Parameter 8 is set to 1 or 3. The drive will
continue to run until a stop command is received, an interlock is opened,
or a fault is detected.
Important: As shown in Figure 4-4, for external two wire start/stop
control, terminals 7 and 8 must be jumpered.

Terminals 9 and 8
Stop
This remote input will command the drive to stop if Parameter 8 is set to 1
or 3. The drive will then either ramp-to-stop or coast-to-stop as selected by
Parameter 11.

Important: If ramp-to-stop is selected, refer to Parameters 11 and 18 if


the drive will be subjected to an overhauling load. If Parameter 18 Decel
Frequency Hold is set to 1 (On), an overhauling load may cause the decel
ramp to hold at one frequency for an extended period, causing ramp-to-stop
commands to appear to be non-functional.

Terminals 10 and 8
Reverse
This remote input will command the drive to reverse direction if Parameter
8 is set to 1 or 3 and Parameter 10 is set to 0. Both the local and remote
reverse will be locked out if Parameter 10 is set to 1.

Terminals 12 and 11
Jog
This remote input will jog the drive if Parameter 8 is set to 1 or 3. When
jogged:
–– The drive will jog to the frequency range set by Parameter 26
–– Within the accel time set by Parameter 27
–– In the direction determined by Parameter 10.
When the jog pushbutton is released, the drive will decelerate within the
time set by Parameter 28.

4-23

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Terminals 13 and 14 -- S1/4SP


Terminals 15 and 14 -- S2/4SP
Switch SW2 on the Control Board is factory set to 4SP. When set to 4SP,
two external switches may be connected to the drive as shown in Figure
4-3. In addition to the standard accel and decel rates set by Parameters 1
and 2, these switches may then be used to select;
–– Three additional accel rates
–– Four preset speeds
As programmed by Parameters 19, 29-31 and 36-41.

Terminals 13 and 11 -- S1/8SP


Terminals 14 and 11 -- S2/8SP
Terminals 15 and 11 -- S3/8SP
When switch SW2 on the Control Board is set to 8SP, a total of three
external switches may be connected to the drive as shown in Figure 4-3. In
addition to the standard accel and decel rates set by Parameters 1 and 2,
these switches may then be used to select three additional accel rates, three
additional decel rates, and seven preset speeds, as programmed by
Parameters 19-20 and 29-41.
Important: If parameter 20 is set to 1, switch S1 and S2 will select the
four preset speeds defined by Parameters 29-31. Switch S3 is reserved for
remotely setting a drive fault.

Terminals 16 and 17
Auxiliary Interlock
These factory jumpered terminals are used to install an auxiliary external
interlock when the jumper is removed. The interlock contact must be
closed to allow the drive to operate. The contact must be open for a
minimum of 100mS to sense an auxiliary fault. Parameter 21 will allow an
open contact to generate either:
A no-fault coast-to-stop sequence displaying AS –– Auxiliary Stop.
A drive fault coast-to-stop sequence displaying AU –– Auxiliary Interlock
–– which will cause the CR3 fault contacts to change state.
Important: A 5V DC or 5mA signal requires a gold contact relay.

4-24

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Terminals 18 and 17
Reset Lockout
These terminals may be jumpered or not jumpered to determine how the
1333 is reset after a fault.
When the terminals are jumpered, a drive may only be reset and restarted
by removing then re-applying input power to the drive.
When these terminals are left open, the drive will be reset and restarted as
programmed by Parameters 47 and 48.

Terminals 19 and 20
Programmable Contact CR1
These terminals allow drive supplied relay contact CR1 to be used in
external circuits. When power is applied to the drive, the N.O. contact will
remain N.O. until a programmed signal is received. The contact is
programmed by Parameters 22 and 24 to signal that the drive is at the
programmed set speed or 140% of rated drive current. The contact is
isolated from Logic Common and other drive circuitry.
CR1 CR1

19 20 19 20

CR1 Out CR1 Out

Programmed Signal At Set Speed or


Not Present 140% of Rated Drive Current
Resistive rating: 120V AC or 30V DC, 1 Amp.
Inductive rating: 120V AC or 30V DC, 0.5 Amps.

4-25

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 4
Installation and Wiring

Terminals 21 and 20
Programmable Contact CR2
These terminals allow drive supplied relay contact CR2 to be used in
external circuits. When power is applied to the drive, the N.O. contact will
remain N.O. until a programmed signal is received. The contact is
programmed by Parameters 23 and 25 to signal that the drive is at the
programmed set speed or 140% of rated drive current. The contact is
isolated from Logic Common and other drive circuitry.
CR2 CR2

20 21 20 21

CR2 Out CR2 Out

Programmed Signal Running, At Set Speed, or


Not Present 140% of Rated Drive Current
Resistive rating: 120V AC or 30V DC, 1 Amp.
Inductive rating: 120V AC or 30V DC, 0.5 Amps.

Terminals 22 and 23
Terminals 24 and 23
Fault Contacts -- CR3
These terminals allow drive supplied CR3 relay contacts to be used in
external circuits. The contacts are shown with power applied to the drive.
When power is first applied to the drive, the contacts will change state ––
22 to 23 will close, 23 to 24 will open. Should a fault occur 22 to 23 will
open, 23 to 24 will close. The contacts are isolated from Logic Common
and other drive circuitry.
CR3 CR3 CR3 CR3

22 23 24 22 23 24

CR3 Out CR3 Out CR3 Out CR3 Out

Drive Not Faulted Drive Faulted


Resistive rating: 120V AC or 30V DC, 1 Amp.
Inductive rating: 120V AC or 30V DC, 0.5 Amps.

4-26

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

5
Chapter

Operation and Programming

Local Control and The Local Control and Programming Panel provides a convenient means to
Programming Panel locally control the operating functions of the Series D Bulletin 1333 drive
including start/stop, forward/reverse, and speed. The Local Control and
Programming Panel also contains two digital displays. A Main Display to
show drive running values, codes, and parameter values, and a Mode
Display to show the drive mode and control source. Finally, the Local
Control and Programming Panel includes the controls necessary to
program the various parameters that will define your drive.

Figure 51 -- The Bulletin 1333 Series D

With two exceptions, the drive must always be stopped to allow drive
programming.
• A 0-1 mA Analog Output Meter may be calibrated while the drive is
running by accessing Parameter 55.
• A 0-10V DC Analog Output Meter may be calibrated while the drive is
running by accessing Parameters 56.
5-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

The Controls The Main


Display

Hz LED
The Select Alternate
Pushbutton LED

The Lock The Enter


Switch Pushbutton

The Stop
Pushbutton

The Directional Start


Pushbutons

The Mode The The The Shift


Display Increment Decrement Pushbutton
Pushbutton Pushbutton
Figure 52 -- Bulletin 1333 Series D Controls

The Select Pushbutton


In the Programming Mode is used to toggle between the parameter number
and the parameter value.
In the Monitoring and Operating Mode is used to select the mode to be
monitored.
• Drive parameters.
• Drive output frequency.
• One of three alternate running displays.

The Lock Switch is used to switch between the Programming Mode and the
Monitoring Mode.

5-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

The Directional Start Pushbuttons


In the Programming Mode are not functional.
In the Monitoring and Operating Mode are used to start or jog the drive
whenever drive speed is controlled from the Local Control Panel.

The Increment and Decrement Pushbuttons


In the Programming Mode are used to select parameters or increase and
decrease parameter values.
In the Monitoring and Operating Mode are used to increment or decrement
drive speed whenever drive speed is controlled from the Local Control
Panel.

The Shift Pushbutton


In the Programming Mode is used to shift between display segments in both
the Main and Mode Displays.
In the Monitoring and Operating Mode is used to shift between segments in
the Main display, or between jog and run in the Mode display when the
drive is stopped.

The Stop Pushbutton


In the Programming Mode is not functional.
In the Monitoring and Operating Mode will always stop the drive as
described in The Displays section that follows.

The Enter Pushbutton


In the Programming Mode is used to enter the parameter value.
In the Monitoring and Operating Mode is used to enter changes.
• Enter changes in drive speed whenever drive speed is controlled from
the Local Control Panel.
• Enter adjustment values to calibrate a 0-1 mA or 0-10V DC analog
output meter.

5-3

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

The Displays The Main Display

In the programming mode this display will show the current value of the
parameter selected, flash when the value is being changed, and finally
remain steady once the new value is entered. Neither the Hz nor Alternate
LED will be lit in the programming mode.

In the monitoring and operating mode this display can be toggled to show
four operational modes. Either the Hz or Alternate LED will be lit or will
flash to indicate the monitoring or operational mode.

Your are:
• Monitoring drive output frequency when the Hz LED is lit.
• Changing drive output frequency when the Hz LED is flashing.
• Monitoring drive output current or equivalent motor RPM when the
Alternate LED is lit.
• Monitoring drive output parameters or viewing preset parameter value
when no LED is lit.

Should a drive operating error occur while the drive is running, OP will
be shown.

Should the drive receive an auxiliary stop while the drive is running, A5
will be shown.

Should a fault occur at any time, the Main Display will shown one of seven
faults that can be stored in drive memory.

1. OC A drive overcurrent or ground fault.


2. OL A drive overload fault.

3. OU A drive overvoltage fault.

4. AU A drive auxiliary interlock fault.

5. LU A drive low voltage fault.

6. OH A drive overtemperature fault.

7. CPU An internal software communications error.

5-4

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

The Mode Display

In the programming mode the smaller two-digit display shows the parameter
number selected –– 01 to 62. Whenever the drive is in the programming
mode, three display items will change.
1. The display will flash.
2. The decimal point normally shown in the lower right hand corner will
disappear.
3. Neither the Hz nor Alternate LED in the Main Display will be lit.

In the monitoring and operating mode the smaller two-digit display shows
the monitoring mode selected ––
• 01  62 View drive parameters.
• AO Monitor drive output current.
• A1 View equivalent motor RPM.
• A2 Monitor drive control frequency.
• LL, LE, LJ, EE, EL or EJ The local or remote control source
currently controlling the drive.

LL To indicate:
1. Drive start, jog, speed and forward/reverse is controlled from the
Local Control Panel.
2. The Local Control Panel stop pushbutton will stop the drive as
programmed by Parameters 11-14.
3. An auxiliary interlock wired to the Control and Signal Wiring
Terminal Block will stop the drive and display either AU or
A5, as set by Parameter 21.

LE To indicate:
1. Drive start, jog and forward/reverse is controlled from the Local
Control Panel.
2. The Local Control Panel stop pushbutton will stop the drive as
programmed by Parameters 11-14.
3. Drive speed is controlled from a remote reference signal wired
to the Control and Signal Wiring Terminal Block.
4. An external stop signal wired to the Control and Signal Wiring
Terminal Block will allow the drive to coast-to-stop and display
OP.
5-5

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

5. An auxiliary interlock wired to the Control and Signal Wiring


Terminal Block will stop the drive and display either AU or
A5, as set by Parameter 21.

LJ To indicate the local jog function has been selected.

EE To indicate:
1. Drive start, jog, speed and forward/reverse is controlled by
external devices or logic wired to the Control and Signal Wiring
Terminal Block.
2. An external stop signal wired to the Control and Signal Wiring
Terminal Block will stop the drive as programmed by
Parameters 11-14.
3. An auxiliary interlock wired to the Control and Signal Wiring
Terminal Block will stop the drive and display either AU or
A5, as set by Parameter 21.
4. The Local Control Panel stop pushbutton will allow the drive to
coast-to-stop and display OP.

EL To indicate:
1. Drive start, jog and forward/reverse is controlled by external
devices or logic wired to the Control and Signal Wiring
Terminal Block.
2. Drive speed is controlled from the Local Control Panel.
3. An external stop signal wired to the Control and Signal Wiring
Terminal Block will stop the drive as programmed by
Parameters 11-14.
4. The Local Control Panel stop pushbutton will allow the drive to
coast-to-stop and display OP.
5. An auxiliary interlock wired to the Control and Signal Wiring
Terminal Block will stop the drive and display either AU or
A5, as set by Parameter 21.

EJ To indicate an external jog signal is being sent.

5-6

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Programming the Drive 62 parameters are available for adjusting the drive. All Series D 1333
parameters interact with each other to provide optimum drive performance.
Some specific parameters however, require that other parameters be set to
coordinated values if they are to function. Others require that they be set to
specific values to function with Bulletin 1333 options.
All parameters along with a detailed explanation are listed in the remaining
pages of this chapter. Parameters are grouped under sub-headings by
function, such as Accel and Decel Settings or VoltsperHertz Curve Settings.
An interactive matrix has been provided in Appendix C to graphically
show which parameters must be set to provide coordinated control of the
Bulletin 1333.

5-7

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Accel and Decel Settings Parameter 01 -- Acceleration Time 1


Units = Seconds
Range = 0000/1600
Factory Setting = 005.0

This parameter determines the time that it will take the drive to accelerate
over a 60 Hz change in frequency. From 0 to 0.5 Hz, the accel rate is
effectively zero. From 0.5 Hz to maximum output frequency, the accel rate
set by Parameter 1 will remain constant. The total time it will take the drive
to accelerate from 0 to maximum drive output frequency is:
Total time = (Maximum Drive Output Frequency × Parameter 1) ÷ 60.

If set to 0000, the drive will enter 40 ms but display 0000.

From 00.10-1000 seconds, this parameter sets the accel time value in 0.1
second increments.

From 1000-1600 seconds, this parameter sets the accel time value in 1
second increments.

Output Frequency
120 Hz

Output Frequency Output Frequency


n
60 Hz 60 Hz 60 Hz a ti o
ler
50 Hz 50 Hz 50 Hz cce
A
n
on ti o
ati ra
ler ele
cc
e
Acc
A

0.5 0.5 0.5


Parameter 1 Parameter 1 Parameter 1
0 Time 0 Time 0 Time
40mS 40mS 40mS

Parameter 3 = 50Hz Parameter 3 = 60Hz Parameter 3 = FF


Parameter 15 = 120Hz

Accel Settings

5-8

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 02 -- Deceleration Time 1


Units = Seconds
Range = 0000 to 1600
Factory Setting = 005.0

Important: Parameter 11 must be set to 0 to allow the drive to


ramp-to-stop

This parameter determines the time that it will take the drive to decelerate
and ramp-to-stop over a 60 Hz change in frequency. From 0.5 to 0 Hz, the
accel rate is non-linear and set by either DC injection braking or the DC
dynamic brake if it is installed. From maximum output frequency to 0.5
Hz, the accel rate set by Parameter 2 will remain constant. The total time it
will take the drive to decelerate from maximum drive output frequency to
0.5 Hz is:
Total time = (Maximum Drive Output Frequency × Parameter 2) ÷ 60.

If set to 0000, the drive will enter 40 ms but display 0000.

From 00.10-1000 seconds, this parameter sets the decel time value in 0.1
second increments.

From 1000-1600 seconds, this parameter sets the decel time value in 1
second increments.

Output Frequency

De
ce
Output Frequency Output Frequency ler
ati
on
60 Hz 60 Hz 60 Hz
50 Hz 50 Hz 50 Hz
De De
ce ce
ler ler
ati ati
on on
➊ ➊ ➊

0.5 0.5 0.5


Parameter 2 Parameter 2 Parameter 2
0 Time 0 Time 0 Time
40mS 40mS 40mS

Parameter 3 = 50Hz Parameter 3 = 60Hz Parameter 3 = FF


Parameter 15 = 120Hz
➊ DC injection braking or DC dynamic braking (if installed).

Decel Settings
5-9

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

VoltsperHertz Curve Settings Important: The maximum allowable drive output frequency will be
determined by the lowest programmed value of any of the following
parameters:
• Parameter 3 Frequency Range
• Parameter 15 Maximum Frequency
• Parameter 51 Upper Frequency Clamp
• Parameter 53 Bias Frequency –– If Parameter 53 is Higher Than
Parameter 54
• Parameter 54 Gain Frequency –– If Parameter 54 is Higher Than
Parameter 53

Parameter 03 -- Frequency Range


Units = Code
Range = 50, 60 or FF
Factory Setting = 60

This parameter permits the selection of three linear volts-per-Hertz ramps.


The maximum frequency settings of these ramps are 50 Hz, 60 Hz, or FF.
If the BCD Interface option is installed, Parameter 3 must be set to match
the scaling jumper on the BCD Interface Board –– Either 60 for 60 Hz
operation, or FF for 120/200 Hz operation.

If set to 50, 50 Hz will be the maximum drive frequency –– The absolute


maximum output speed that the drive can reach. If set to 60, 60 Hz will be
the maximum drive frequency –– The absolute maximum output speed
that the drive can reach. Parameter 15 will have no effect on maximum
output speed, but Parameter 51 will. When Parameter 3 is set to 50 or 60,
the drive will use the lower of the values set by Parameter 3 and 51.
Parameter 16 will have no effect on base speed.

If set to FF, the value set by Parameter 15 or 51 will be the maximum drive
frequency –– The absolute maximum output speed that the drive can
reach. When Parameter 3 is set to FF, the drive will use the lower of the
values set by Parameters 15 and 51. The value set by Parameter 16 Base
Frequency will be the point where maximum output voltage is applied to
the motor.

Important: Applications where volts-per-Hertz curves are required to


reach maximum voltage other than at 50 or 60 Hz are primarily provisions
for operating custom motors. For application assistance in these special
ranges, contact your nearest Allen-Bradley representative.

5-10

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 04 -- Volts-per-Hertz Curve


Units = Code
Range = 0/1
Factory Setting = 0

This parameter sets the shape of the volts-per-Hertz ramp, either constant
or curved.

If set to 0, the volts-per-Hertz ramp will be linear producing a constant rate


of increase from 0 to base frequency. This setting will be the setting
required for most constant torque applications.

If set to 1, the volts-per-Hertz ramp will be curved, producing a rate of


increase that will gradually curve upward as it increases from 0 to base
frequency. This setting will be required for most variable torque
applications where full rated motor torque is not required at reduced
speeds.
Output Voltage Output Voltage

100% 100%

Parameter 4 = 0
Parameter 4 = 1

Parameter 5 Parameter 5
DC Boost
DC Boost

0% Output 0% Output
0 Hertz Parameter 3 Frequency 0 Hertz Parameter 3 Frequency

VoltsperHertz Curve Settings + DC Boost Settings

DC Boost Settings Parameter 05 -- DC Boost Select


Units = % of Output Voltage
Range = 00/40
Factory Setting = 00

This parameter adds from 0 to 40% of the drive output voltage to the motor
at low drive frequencies in 1% increments, boosting motor torque at
startup. DC boost can be added to any volts-per-Hertz curve. The optimum
DC boost setting is the lowest level that will permit satisfactory starting
torque for the motor and drive. Higher than optimum boost may produce
unnecessary motor current at low frequencies and contribute to motor
overheating. Excessive boost may even force the drive into an overcurrent
condition.
5-11

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Overload Protection Settings Important: Parameters 6 and 7 are intended for use on single motor
applications. For multiple motor applications, Parameter 6 must be set to 0
to help avoid nuisance tripping.

Parameter 06 -- Motor Duty


Units = Code
Range = 0/1/2/3
Factory Setting = 2

Parameter 6 provides three thermal overload functions. When used in


conjunction with Parameter 7, a thermal overload function that matches the
motor nameplate amps can be used.

If set to 0, the overload function will not include thermal protection and the
drive will trip at its standard setting of 140% of rated drive output current
after 60 seconds. If set to 1, 2 or 3, the thermal overload function is
enabled and will function as described below.

If set to 1, the drive will trip at 115% of the current set in Parameter 7, or
140% of rated drive output current (whichever is lower) after 60 seconds.
When set to 1, the thermal overload trip point is constant across the entire
speed range of the motor. This performance is typical with A-B Bulletin
1329 10:1 speed range motors.

If set to 2, the drive will trip at 115% of the current set in Parameter 7, or
140% of rated drive output current (whichever is lower) after 60 seconds.
When set to 2, the thermal overload curve generated is derated below
50 Hz for use with motors having a 4:1 speed range. This performance is
typical with A-B Bulletin 1329 4:1 speed range motors.

If set to 3, the drive will trip at 115% of the current set in Parameter 7, or
140% of rated drive output current (whichever is lower) after 60 seconds.
When set to 3, the thermal overload curve generated is derated below
15 Hz for use with motors having a 4:1 speed range. This performance is
typical with A-B Bulletin 1329 4:1 speed range motors.

Important: The National Electrical Code requires that motor overload


protection be provided in the motor branch circuit. Parameter 6 when used
with Parameter 7 provides motor overload protection. NEC however,
recognizes this protection as being provided by eutectic alloy or bi-metal
overload relays. If it necessary to meet NEC motor branch protection
approval, eutectic alloy, bi-metal overload relays or an equivalent should
be installed. Refer to article 430 of the NEC and any additional codes for
specific requirements and additional information.

5-12

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

% of Current
115% of Parameter 7 140% of Rated Drive Output Current

Overload Protection

0 Hz
0 25 Hz 50 Hz 60 Hz Maximum Frequency
Parameter 6 = 1

% of Current
115% of Parameter 7 140% of Rated Drive Output Current
104% of Parameter 7 96% of Rated Drive Output Current

69% of Parameter 7 84% of Rated Drive Output Current


Overload Protection

0 Hz
0 25 Hz 50 Hz 60 Hz Maximum Frequency
Parameter 6 = 2

% of Current
115% of Parameter 7 140% of Rated Drive Output Current

69% of Parameter 7 84% of Rated Drive Output Current


Overload Protection

0 Hz
0 15 Hz 50 Hz 60 Hz Maximum Frequency
Parameter 6 = 3

Overload Protection Settings


Parameter 07 -- Overload Current
Units = Amps
Range = 000.1/500.0
Factory Setting = None

Parameters 6 and 7 will work in conjunction if Parameter 7 matches the


rated amps located on the motor nameplate, and Parameter 6 is set to 1, 2
or 3. When Parameter 6 is set to 0, the setting of Parameter 7 will have no
effect on drive operation. The overload current value for Parameter 7 may
be set in 0.1A increments.

5-13

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Local/Remote Control Enable Important: If the Remote Operator Station option is installed, Parameter 8
must be set to 1 or 3 to allow remote control.
Parameter 08 -- Local/Remote Control
Units = Code
Range = 0/1/2/3
Factory Setting = 0

This parameter enables or disables the drive start, jog, and forward/reverse
functions as follows. The stop button on the Local Control and
Programming Panel will always be functional, but may generate an OP
error for certain settings detailed below. If installed at the Control and
Signal Wiring Terminal Block, auxiliary input switches S1, S2 and/or S3
will always function as programmed by Parameters 19 and 20 when a valid
start command is present.

If set to 0, local control has been selected. An L will be the left-hand letter
shown in the Mode Display. A maintained start command or jumper is not
required at terminals 7 and 8 of the Control and Signal Wiring Terminal
Block.
• Both directional start pushbuttons on the Local Control and
Programming Panel will be functional.
• Local jog can be selected by pressing the Shift button.
• If Parameter 10 Reverse Lockout is on, only one directional start
pushbutton will be available for jogging or running the drive.
• The local stop button will stop the drive as programmed by Parameters
11-14.
• An auxiliary interlock signal will stop the drive and display either AU or
AS as programmed by Parameter 21.

If set to 1, external 2-wire control has been selected. An E will be the


left-hand letter shown in the Mode Display.
• Drive start, jog and forward/reverse is controlled externally through the
Control and Signal Wiring Terminal block. Neither directional start
pushbutton on the Local Control and Programming Panel will be
functional.
• An external jog signal will jog the drive and display EJ. Local jog
cannot be selected.
• If Parameter 10 Reverse Lockout is on, only one direction is available
for jogging or running the drive.
• The local stop button will allow the drive to coast-to-stop and display
OP.
5-14

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

• An auxiliary interlock signal will stop the drive and display either AU or
AS as programmed by Parameter 21.

If set to 2, local control has been selected, but a maintained stop command
or jumper must also be present at terminals 8 and 9 of the Control and
Signal Wiring Terminal Block. If not present, all of the following
commands will generate an OP error. An L will be the left-hand letter
shown in the Mode Display.
• Both directional start pushbuttons on the Local Control and
Programming Panel will be functional.
• Local jog can be selected by pressing the Shift button.
• If Parameter 10 Reverse Lockout is on, only one directional start
pushbutton will be available for jogging or running the drive.
• The local stop button will stop the drive as programmed by Parameters
11-14.
• An auxiliary interlock signal will stop the drive and display either AU or
AS as programmed by Parameter 21.
• An external stop signal at terminals 8 and 9 of the Control and Signal
Wiring Terminal Block will allow the drive to coast-to-stop but display
an OP error.

If set to 3, external 3-wire control has been selected. An E will be the


left-hand letter shown in the Mode Display.
• Drive start, jog and forward/reverse is controlled externally through the
Control and Signal Wiring Terminal block. Neither directional start
pushbutton on the Local Control and Programming Panel will be
functional and local jog cannot be selected.
• An external jog signal will jog the drive and display EJ. Local jog
cannot be selected.
• If Parameter 10 Reverse Lockout is on, only one direction is available
for jogging or running the drive.
• The local stop button will allow the drive to coast-to-stop and display
OP.
• An auxiliary interlock signal will stop the drive and display either AU or
AS as programmed by Parameter 21.

5-15

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Local/Remote Speed Enable Important: If the Remote Operator Station option is installed, Parameter 9
must be set to a value other than 0 to allow remote control. If the BCD
Interface option is installed, Parameter 9 must be set to 2 to allow BCD
control.

Parameter 09 -- Local/Remote Frequency


Units = Code
Range = 0/1/2/3
Factory Setting = 0

Important: If installed at the Control and Signal Wiring Terminal Block,


auxiliary input switches S1, S2 and/or S3 will always function as
programmed by Parameters 19 and 20 to control drive speed when a valid
start command is present.

If set to 0, local control has been selected. An L will be the right-hand


letter shown in the Mode Display.

• Both the increment and decrement pushbuttons on the Local Control and
Programming Panel will set drive speed. The select and enter
pushbuttons are used to enter the drive set speed.

If set to 1, 2 or 3, external control has been selected. An E will be the


right-hand letter shown in the Mode Display. If an external speed pot is
connected, all other drive speed signals (except from auxiliary switches S1,
S2 and/or S3) will be ignored. Both the increment and decrement
pushbuttons on the Local Control and Programming Panel will be disabled.
The select and enter pushbuttons cannot be used to enter the set drive
speed.

• If set to 1, drive speed is controlled externally through the Control and


Signal Wiring Terminal Block. A 0-5V DC signal connected to the
Control and Signal Wiring Terminal Block will control drive speed
unless an external speed pot is connected.

• If set to 2, drive speed is controlled externally through the Control and


Signal Wiring Terminal Block. A 0-10V DC signal connected to the
Control and Signal Wiring Terminal Block will control drive speed
unless an external speed pot is connected.

• If set to 3, drive speed is controlled externally through the Control and


Signal Wiring Terminal Block. A 4-20 mA DC signal connected to the
Control and Signal Wiring Terminal Block will control drive speed
unless an external speed pot is connected.

5-16

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Reverse Enable Parameter 10 -- Reverse Lockout


Units = Off/On
Range = 0/1
Factory Setting = 0

This parameter enables or disables both local and remote drive direction
control.

If set to 0, both local and remote direction control is enabled and motor
rotation can be selected in either direction.

If set to 1, both local and remote direction control is locked out and motor
rotation in only one direction can be selected.

5-17

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Stop Settings Important: If the drive’s internal DC brake is enabled and/or if the Heavy
Duty Dynamic Brake option is installed, Parameter 11 must be set to 0.

Parameter 11 -- Stop Select


Units = Code
Range = 0/1
Factory Setting = 0

This parameter allows the motor to either ramp-to-stop or coast-to-stop


when a stop signal is received either from the Local Control and
Programming Panel, or from terminals 8 and 9 at the Control and Signal
Wiring Terminal Block.

If set to 0, a stop command will ramp the drive to a stop before shutting off
output frequency. The ramp followed is set by Parameter 2, Decel Time 1,
unless DC braking is used (Parameters 13-15).

Important: If ramp-to-stop is selected, refer to Parameter 18 if the drive


will be subjected to an overhauling load. If Parameter 18 Decel Frequency
Hold is set to 1 (On), an overhauling load may cause the decel ramp to hold
at one frequency for an extended period, causing ramp-to-stop commands
to appear to be non-functional.

If set to 1, a stop command will shut off drive output frequency to the
motor and the motor will coast to a stop.

ATTENTION: The user has the ultimate responsibility to


! determine which stopping mode is best suited to the application
and which stopping mode will meet applicable standards for
operator safety on a particular application

5-18

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

DC Brake Settings Parameters 12, 13 and 14 sets the DC braking action that will occur when
the drive is ramped-to-stop or programmed to change direction while the
drive is operating for both local and remote control. If DC braking is to be
used, Parameter 11 must be set to 0, ramp-to-stop.

Parameter 14
Parameter 12
Ra
mp
-to
-St
op Parameter 13

DC Break

Drive Stopped

DC Brake Settings
Parameter 12 -- DC Hold Frequency
Units = Hertz
Range = 00.50/60.00
Factory Setting = 00.50
Parameter 12 sets the braking frequency of the internal DC brake in .01 Hz
increments.

Parameter 13 -- DC Hold Time


Units = Seconds
Range = 000/10.0
Factory Setting = 000
Parameter 13 will set the braking time of the internal DC brake when used
in conjunction with parameters 12 and 14. Parameter 13 will set the
hold-at-zero time for changes in direction or stop commands when
Parameter 14 is set to 0 (disabled). Parameter 13 may be programmed in
0.1 second increments.

Parameter 14 -- DC Hold Volts


Units = Code
Range = 0/10
Factory Setting = 0
If set to 0, the DC brake function will be disabled and Parameters 12 and
14 will have no effect on drive operation.
If set to a value of 1-10, the DC brake function will be enabled. Parameters
12 and 13 along with Parameter 14 will then set the DC brake function.
The value of Parameter 14 determines the level or strength of the braking
that occurs, with 1 being the lowest, 10 the highest.
5-19

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Max Speed Settings Important: The maximum allowable drive output frequency will be
determined by the lowest programmed value of any of the following
parameters:
• Parameter 3 Frequency Range
• Parameter 15 Maximum Frequency
• Parameter 51 Upper Frequency Clamp
• Parameter 53 Bias Frequency –– If Parameter 53 is Higher Than
Parameter 54
• Parameter 54 Gain Frequency –– If Parameter 54 is Higher Than
Parameter 53

100% of Output Voltage

on
ati
ler
ce
Ac

0%
0% 100% of Output Frequency
Parameter 15 = Parameter 16

100% of Output Voltage

on
ati
ler
cce
A

0%
0% Parameter 16 100% of Output Frequency
Parameter 15
Max Speed Settings

5-20

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 15 -- Maximum Frequency


Units = Hertz
Range = 50.00/400.0
Factory Setting = 60.00

If Parameter 3 is set to 50 or 60, the drive will use the lower of the values
set by Parameters 3 and 51 as the maximum drive output frequency.
Parameter 15 will have no effect on drive operation.

If Parameter 3 is set to FF, the drive will use the lower of the values set by
Parameters 15 and 51 as the maximum drive output frequency.

From 50.00-100.0 Hz, this parameter sets the value of Maximum


Frequency in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Maximum
Frequency in 0.1 Hz increments.

Parameter 16 -- Base Frequency


Units = Hertz
Range = 50.00/250.0
Factory Setting = 60.00

The value set by Parameter 16 Base Frequency will be the point where
maximum output voltage is applied to the motor when Parameter 3 is set to
FF. If Parameter 3 is set to either 50 or 60 Hz, that will be the base
frequency that the drive uses.

From 50.00-100.0 Hz, this parameter sets the value of Base Frequency in
.01 Hz increments.
From 100.0-250.0 Hz, this parameter sets the value of Base Frequency in
0.1 Hz increments.

5-21

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Accel and Decel Hold Enable Important: If the Heavy Duty Dynamic Brake option is installed, decel
frequency hold must be disabled by setting Parameter 18 to 0.

Command Frequency
n
atio ➊➋
eler
Acc ➊➋
➊➋

Initial Frequency
Parameter 17 = 1

Time
0
➊ Drive output current = 140% of rated output current.
➋ Drive output current below 140% of rated output current.

Initial Frequency
Dec
e lera
➊➋ tion
➊➋
➊➋

Command Frequency
Parameter 18 = 1

Time
0
➊ Drive bus voltage = bus overvoltage trip.
➋ Drive bus voltage below bus overvoltage trip.

Accel and Decel Hold Enable

5-22

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 17 -- Accel Frequency Hold


Units = Off/On
Range = 0/1
Factory Setting = 1

To help avoid drive nuisance trips, this parameter enables or disables drive
acceleration during high current conditions.

When set to 0, accel stall protection is off. During drive acceleration,


should drive output current rise above 140% of rated drive output current,
the drive will trip.

When set to 1, accel stall protection is on. During acceleration, the drive
will hold the accel ramp for 60 seconds should drive output current rise
above 140% of rated drive output current. If output current does not fall
below 140% after 60 seconds, the drive will trip.

Parameter 18 -- Decel Frequency Hold


Units = Off/On
Range = 0/1
Factory Setting = 1

To help avoid drive nuisance trips, this parameter enables or disables drive
deceleration during overvoltage conditions.

When set to 0, decel stall protection is off. During drive deceleration,


should drive bus voltage rise above the Over Voltage values listed below,
the drive will trip.
Drive Input Voltage Decel Stall Over Voltage Trip
200/208/230V AC 380V DC 430V DC
380/415/460V AC 760V DC 820V DC

When set to 1, decel stall protection is on. During deceleration, the drive
will hold the decel ramp at one frequency until bus voltage drops below the
Decel Stall values listed above.
Important: If Parameter 18 Decel Frequency Hold is set to 1 (On), an
overhauling load may cause the decel ramp to hold at one frequency for an
extended period. This may cause ramp-to-stop commands to appear to be
non-functional.

5-23

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Preset Frequency and Parameter 19 -- Frequency Select


Aux Accel/Decel Enable Units = Code
Range = 0/1/2
Factory Setting = 0

This parameter enables or disables the selection of preset drive frequencies,


auxiliary drive preset accel and decel times, or both. To allow drive preset
frequencies and/or aux accel and decel times to be selected, external
switches must be connected to the Control and Signal Wiring Terminal
Block as detailed in Chapter 4.

Preset frequencies are set by Parameters 29-35. Auxiliary accel and decel
times are set by Parameters 36-41. External switches connected to the
Control and Signal Wiring Terminal Block are enabled or disabled as
explained below and in the Preset Frequency and Aux Accel/Decel Enable
Tables on pages 5-20 –– 5-22.
1. Switch SW2 on the Control Board is factory set to 4SP. When set to 4SP,
two external switches may be connected to the drive. In addition to the
standard accel and decel rates set by Parameters 1 and 2, switches S1
and S2 may then be used to select three additional accel rates, three
additional decel rates, and four preset speeds, as programmed by
Parameters 29-31 and 36-41.
2. When switch SW2 on the Control Board is set to 8SP, a total of three
external switches may be connected to the drive. In addition to the
standard accel and decel rates set by Parameters 1 and 2, switches S1, S2
and S3 may then be used to select three additional accel rates, three
additional decel rates, and seven preset speeds, as programmed by
Parameters 20 and 29-41.

Parameter 19 settings.
When set to 0, only the preset frequency function is enabled. External
switches connected to the Control and Signal Wiring Terminal Block can
only be used to select preset frequencies.

When set to 1, only the auxiliary accel and decel function is enabled.
External switches connected to the Control and Signal Wiring Terminal
Block can only be used to select auxiliary accel and decel times.

When set to 2, both the preset frequency function and the auxiliary accel
and decel function is enabled. External switches connected to the Control
and Signal Wiring Terminal Block can be used to select both preset
frequencies and auxiliary accel and decel times.

5-24

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 20 -- TB15 Preset/Reset


Units = Code
Range = 0/1
Factory Setting = 0

This parameter selects the control function of switch S3 when three


external switches are connected to the Control and Signal Wiring Terminal
Block.
Parameter 20 settings.
When set to 0, external switches S1, S2 and S3 connected to the Control
and Signal Wiring Terminal Block can be used to select Preset Frequencies
2-8 and Accel/Decel Times 2-4.
When set to 1, external switches S1 and S2 connected to the Control and
Signal Wiring Terminal Block can be used to select Preset Frequencies 2-4
and Accel/Decel Times 2-4. If a third switch is installed, switch S3 is used
to remotely reset the drive should a drive fault occur.

As shown in Figure 4-5 in Chapter 4 ––

If Parameter 19 = 0
When and and
Control Board External External
Switch SW2 Switch S1 Switch S2
is Set to is Set to is Set to The Parameters Selected are
4SP OFF OFF None
4SP ON OFF Preset Frequency 2
4SP OFF ON Preset Frequency 3
4SP ON ON Preset Frequency 4

If Parameter 19 = 1
When and and
Control Board External External
Switch SW2 Switch S1 Switch S2
is Set to is Set to is Set to The Parameters Selected are
4SP OFF OFF None
4SP ON OFF Accel Time 2 + Decel Time 2
4SP OFF ON Accel Time 3 + Decel Time 3
4SP ON ON Accel Time 4 + Decel Time 4

If Parameter 19 = 2
When and and
Control Board External External
Switch SW2 Switch S1 Switch S2
is Set to is Set to is Set to The Parameters Selected are
4SP OFF OFF None
4SP ON OFF Preset Frequency 2 + Accel Time 2 + Decel Time 2
4SP OFF ON Preset Frequency 3 + Accel Time 3 + Decel Time 3
4SP ON ON Preset Frequency 4 + Accel Time 4 + Decel Time 4

5-25

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

As shown in Figure 4-5 in Chapter 4 ––

If Parameter 19 = 0 and Parameter 20 = 0


When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Preset Frequency 2
8SP OFF ON OFF Preset Frequency 3
8SP ON ON OFF Preset Frequency 4
8SP OFF OFF ON Preset Frequency 5
8SP ON OFF ON Preset Frequency 6
8SP OFF ON ON Preset Frequency 7
8SP ON ON ON Preset Frequency 8

If Parameter 19 = 1 and Parameter 20 = 0


When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Accel Time 2 + Decel Time 2
8SP OFF ON OFF Accel Time 3 + Decel Time 3
8SP ON ON OFF Accel Time 4 + Decel Time 4
8SP OFF OFF ON Accel Time 1 + Decel Time 1
8SP ON OFF ON Accel Time 1 + Decel Time 1
8SP OFF ON ON Accel Time 1 + Decel Time 1
8SP ON ON ON Accel Time 1 + Decel Time 1

If Parameter 19 = 2 and Parameter 20 = 0


When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Preset Frequency 2 + Accel Time 2 + Decel Time 2
8SP OFF ON OFF Preset Frequency 3 + Accel Time 3 + Decel Time 3
8SP ON ON OFF Preset Frequency 4 + Accel Time 4 + Decel Time 4
8SP OFF OFF ON Preset Frequency 5 + Accel Time 1 + Decel Time 1
8SP ON OFF ON Preset Frequency 6 + Accel Time 1 + Decel Time 1
8SP OFF ON ON Preset Frequency 7 + Accel Time 1 + Decel Time 1
8SP ON ON ON Preset Frequency 8 + Accel Time 1 + Decel Time 1

5-26

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

As shown in Figure 4-5 in Chapter 4 ––

If Parameter 19 = 0 and Parameter 20 = 1


When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Preset Frequency 2
8SP OFF ON OFF Preset Frequency 3
8SP ON ON OFF Preset Frequency 4
8SP OFF OFF ON Remote Fault Reset
8SP ON OFF ON Preset Frequency 2 + Remote Fault Reset
8SP OFF ON ON Preset Frequency 3 + Remote Fault Reset
8SP ON ON ON Preset Frequency 4 + Remote Fault Reset

If Parameter 19 = 1 and Parameter 20 = 1


When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Accel Time 2 + Decel Time 2
8SP OFF ON OFF Accel Time 3 + Decel Time 3
8SP ON ON OFF Accel Time 4 + Decel Time 4
8SP OFF OFF ON Remote Fault Reset
8SP ON OFF ON Accel Time 2 + Decel Time 2 + Remote Fault Reset
8SP OFF ON ON Accel Time 3 + Decel Time 3 + Remote Fault Reset
8SP ON ON ON Accel Time 4 + Decel Time 4 + Remote Fault Reset

If Parameter 19 = 2 and Parameter 20 = 1


When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Preset Frequency 2 + Accel Time 2 + Decel Time 2
8SP OFF ON OFF Preset Frequency 3 + Accel Time 3 + Decel Time 3
8SP ON ON OFF Preset Frequency 4 + Accel Time 4 + Decel Time 4
8SP OFF OFF ON Remote Fault Reset
8SP ON OFF ON Preset Frequency 2 + Accel Time 2 + Decel Time 2 + Remote Fault Reset
8SP OFF ON ON Preset Frequency 3 + Accel Time 3 + Decel Time 3 + Remote Fault Reset
8SP ON ON ON Preset Frequency 4 + Accel Time 4 + Decel Time 4 + Remote Fault Reset

5-27

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Aux Interlock Enable Parameter 21 -- Auxiliary Interlock


Units = Code
Range = 0/1
Factory Setting = 0

To enable drive operation, terminal 16 and logic common at the Control


and Signal Wiring Terminal Block must be jumpered. This parameter sets
the function of terminal 16 and logic common when a normally closed
auxiliary interlock is installed in its place.

If set to 0, when the auxiliary contact opens:


• The drive will coast-to-stop, display fault AU, and store the fault in
Fault Buffer Parameters 59-62.
• Fault Contact CR3 on the Control Board will change state to provide a
fault signal at terminals 22-24 at the Control and Signal Wiring Terminal
Block.

If set to 1, when the auxiliary contact opens:


• The drive will coast-to-stop and display AS. Since AS is not a fault, it
will not be stored in Fault Buffer Parameters 59-62.
• Since AS is not a fault, Fault Contact CR3 on the Control Board will not
change state to provide a fault signal at terminals 22-24.

5-28

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Drive Supplied Contact Settings Parameter 22 -- CR1 Select


Units = Code
Range = 1/2/3
Factory Setting = 1

This parameter sets the function of drive supplied contact CR1. CR1 is a
normally open contact located at terminals 19 and 20 on the Control and
Signal Wiring Terminal Block.

If set to 1, the N.O contact will close when the drive is within ± 2 Hz of the
run or jog set speed.

If set to 2, the N.O contact will close when the drive is at 140% of rated
drive output current or 125% of the current set in Parameter 7.

If set to 3, the N.O contact will close when the run or jog output frequency
is greater than the CR1 Frequency set by Parameter 24.

Parameter 23 -- CR2 Select


Units = Code
Range = 0/1/2/3
Factory Setting = 0

This parameter sets the function of drive supplied contact CR2. CR2 is a
normally open contact located at terminals 20 and 21 on the Control and
Signal Wiring Terminal Block.

If set to 0, the N.O contact will close when the drive receives a run or jog
start signal.

If set to 1, the N.O contact will close when the drive is within ± 2 Hz of
run or jog set speed.

If set to 2, the N.O contact will close when the drive is at 140% of rated
drive output current or 125% of the current set in Parameter 7.

If set to 3, the N.O contact will close when the run or jog output frequency
is greater than the CR2 Frequency set by Parameter 25.

5-29

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 24 -- CR1 Frequency


Units = Hertz
Range = 00.50/400.0
Factory Setting = 00.50

This parameter sets the frequency that will cause drive supplied contact
CR1 to close when Parameter 22 is set to 3.

From 00.50-100.0 Hz, this parameter sets the value of CR1 Frequency in
.01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of CR1 Frequency in
.1 Hz increments.

Parameter 25 -- CR2 Frequency


Units = Hertz
Range = 00.50/400.0
Factory Setting = 00.50

This parameter sets the frequency that will cause drive supplied contact
CR2 to close when Parameter 23 is set to 3.

From 00.50-100.0 Hz, this parameter sets the value of CR2 Frequency in
.01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of CR2 Frequency in
.1 Hz increments.

5-30

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Jog Settings Parameter 26 -- Jog Frequency


Units = Hertz
Range = 00.50/20.00
Factory Setting = 10.00

This parameter sets the jog frequency (speed) that the drive will use when
it receives either a local or remote jog command. Jog frequency may be set
in .01 Hz increments. Whenever the drive receives a jog command, Accel
Frequency Hold, Decel Frequency Hold, and Current Limit functions are
disabled.

Parameter 27 -- Jog Accel Time


Units = Seconds
Range = 0000/1600
Factory Setting = 00.50

This parameter sets the time it takes the drive to accelerate to the jog
frequency set in Parameter 26. If set to 0000, the drive will enter 40 ms but
display 0000.

From 000.1-1000 seconds, sets the Jog Accel Time in 0.1 second
increments.
From 1000-1600 seconds, sets the Jog Accel Time in 1 second increments.

Parameter 28 -- Jog Decel Time


Units = Seconds
Range = 0000/1600
Factory Setting = 00.50

This parameter sets the time it takes the drive to decelerate to 0. If set to
0000, the drive will enter 40 ms but display 0000.

From 000.1-1000 seconds, sets the Jog Decel Time in 0.1 second
increments.
From 1000-1600 seconds, sets the Jog Decel Time in 1 second increments.

5-31

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Preset Frequency Settings Auxiliary Preset Frequencies are enabled or disabled by Parameters 19 and
20. Individual Preset Frequency settings are selected by setting switches
S1, S2 and/or S3 as shown in Parameters 19 and 20.

Parameter 29 -- Preset Frequency 2


Units = Hertz
Range = 00.50/400.0
Factory Setting = 20.00

From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 2
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 2
in 0.1 Hz increments.

Parameter 30 -- Preset Frequency 3


Units = Hertz
Range = 00.50/400.0
Factory Setting = 30.00

From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 3
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 3
in 0.1 Hz increments.

Parameter 31 -- Preset Frequency 4


Units = Hertz
Range = 00.50/400.0
Factory Setting = 40.00

From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 4
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 4
in 0.1 Hz increments.

5-32

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 32 -- Preset Frequency 5


Units = Hertz
Range = 00.50/400.0
Factory Setting = 15.00

From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 5
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 5
in 0.1 Hz increments.

Parameter 33 -- Preset Frequency 6


Units = Hertz
Range = 00.50/400.0
Factory Setting = 25.00

From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 6
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 6
in 0.1 Hz increments.

Parameter 34 -- Preset Frequency 7


Units = Hertz
Range = 00.50/400.0
Factory Setting = 35.00

From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 7
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 7
in 0.1 Hz increments.

5-33

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 35 -- Preset Frequency 8


Units = Hertz
Range = 00.50/400.0
Factory Setting = 45.00

From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 8
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 8
in 0.1 Hz increments.

Typical Remote Command Profile

8
r3 3
Pa ccel
Par el 4

Par
Dec

Dece
ce 8
41

Ac r 3
Ac r 36

l1

2
2

Pa

l1
Par
cel
a

Dec 2
P

el 1
Pa
r2
De
cel
Acc 1
el 1

1
Par

Output
Frequency

Command Par 29 Par 30 Par 31 Par 32 Par 33 Par 34 Par 35


Frequency Preset 2 Preset 3 Preset 4 Preset 5 Preset 6 Preset 7 Preset 8
Switch SW2 Set to 4SP or 8SP Switch SW2 Set to 8SP

Preset Frequency Settings


Auxiliary Accel and Decel Settings

5-34

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Auxiliary Accel and Decel Settings Auxiliary Accel and Decel Times are enabled or disabled by Parameters 19
and 20. Individual Accel and Decel Parameter settings are selected by
setting switches S1, S2 and/or S3 as shown in Parameters 19 and 20

Parameters 36, 38 and 40 -- Accel Times 2, 3 and 4


Units = Seconds
Range = 000.1/1600
Factory Setting = 005.0

Each auxiliary accel time determines a time that it will take the drive to
accelerate over a 60 Hz frequency change. From 0 to 0.5 Hz, any auxiliary
accel rate set is effectively zero. From 0.5 Hz to maximum output
frequency, the accel rate set by each auxiliary accel time will remain
constant. For each accel time, the total time it will take the drive to
accelerate from an initial frequency to a new command frequency is:
Total time = (New Command Frequency – Initial Frequency) × (Accel
Time) ÷ 60.

From 000.1-1000 seconds, these parameters set the values of Accel Time 2,
3 and 4 in 0.1 second increments.

From 1000-1600 seconds, these parameters set the value of Accel Time 2,
3 and 4 in 1 second increments.

Parameters 37, 39 and 41 -- Decel Times 2, 3 and 4


Units = Seconds
Range = 000.1/1600
Factory Setting = 005.0

Each auxiliary decel time determines a time that it will take the drive to
decelerate and ramp-to-stop over a 60 Hz change in frequency. From 0.5 to
0 Hz, the accel rate is non-linear and set by either DC injection braking or
the DC dynamic brake if it is installed. From maximum output frequency
to 0.5 Hz, the accel rate set by Parameter 2 will remain constant. For each
decel time, the total time it will take the drive to decelerate from an initial
frequency to a new command frequency is:
Total time = (New Command Frequency – Initial Frequency) × (Accel
Time) ÷ 60.

From 000.1-1000 seconds, these parameters set the values of Decel Time 2,
3 and 4 in 0.1 second increments.

From 1000-1600 seconds, these parameters set the value of Decel Time 2,
3 and 4 in 1 second increments.

5-35

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Skip Frequency Settings Parameters 42, 43 and 44 -- Skip Frequencies 1, 2 and 3


Units = Hertz
Range = 0000/400.0
Factory Setting = 0000

To help avoid undesirable mechanical resonance, Parameters 42-44


prevents the drive from running at one, two or three specific frequencies.
Although the drive will use these frequencies when accelerating or
decelerating, they cannot be set as ”running” frequencies by any drive
parameter. The drive will stay slightly above or slightly below these
frequencies if the frequency values are entered. If a Skip Frequency value
of 0000 is selected, the skip frequency function of that parameter is
disabled.

From 00.50-100.0 Hz, Parameters 42-44 sets the Skip Frequencies in .01
Hz increments.

From 100.0-400.0 Hz, Parameters 42-44 sets the Skip Frequencies in 0.1
Hz increments.

Parameter 45 Parameter 45

De
at ion ce
ler
e ler ati
cc on
A

Parameter Parameter Parameter Command Parameter Parameter Parameter


44 42 43 Frequency 43 42 44

Skip Frequency Settings

5-36

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 45 -- Skip Frequency Band


Units = Code
Range = 0/10
Factory Setting = 0

Parameter 45 allows each of the individual Skip Frequencies set in


Parameters 42-44 to be expanded into three bands of skip frequencies in
2-20 Hz increments.

Setting a Skip Frequency Band value of 0 will disable the Skip Frequency
Band function, but not individual Skip Frequency values set by Parameters
42-44.

Setting a Skip Frequency Band value other than 0 will enable Skip
Frequency values and expand their range by 2 Hz. For example, if
Parameter 45 is set to 1, a Skip Frequency value set by Parameter 42, 43 or
44 will expand to a band that includes the Skip Frequency value with an
additional 1 Hz band on either side. If set to 10, a Skip Frequency value set
by Parameter 42, 43 or 44 will expand to a band that includes the Skip
Frequency value with an additional 10 Hz band on either side.

Important:
1. If the drive is programmed with a Parameter 3 Frequency Range and/or
Parameter 15 Maximum Frequency value that falls within a skip
frequency bandwidth, the drive will operate only through the non-skip
frequencies below Parameters 3 and 15.
2. If the drive is programmed with a Parameter 51Upper Frequency Clamp
value that falls within a skip frequency bandwidth, the drive will operate
only through the non-skip frequencies below Parameter 51, then jump to
the Parameter 51 value at a maximum speed command.
3. If Parameters 3, 15 and 51 are all within the skip frequency bandwidth,
the drive will operate only though the non-skip frequencies below the
lowest value set by Parameters 3, 15 and 51.

5-37

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Current Limit Setting Parameter 46 -- Current Limit


Units = Seconds
Range = 00/1.5
Factory Setting = 00

Should drive current rise above 140% of rated drive output current, the
drive will attempt to limit current for one minute. Parameter 46 sets the
frequency foldback rate used to decrease current in .1 second increments.
Frequency foldback allows the drive to ramp output frequency down far
enough to temporarily eliminate an overcurrent condition. When Parameter
46 is set to 00, the Current Limit function set by Parameter 46 is disabled
and the drive’s overcurrent feature will trip the drive should current rise
above 200%.

Drive Output Current ➋ ➋



➊ ➊ ➊ ➏ Drive Trips at 200%
200%

➌ ➍ ➎

140%
O O O
V V V
E E E
Drive R Drive R Drive R Drive
C C C
Operating U Operating U Operating U Operating
Range R Range R Range R Range
R R R
E E E
N N N
T T T
0 Time

➊ % of Drive Overcurrent
➋ Drive Output Frequency Decel Ramp
➌ Parameter 46 = 0.5 Seconds
➍ Parameter 46 = 1.0 Seconds
➎ Parameter 46 = 1.5 Seconds
➏ Parameter 46 = 0.0 Seconds

Current Limit Setting

5-38

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Auto Restart Settings ATTENTION: Auto restart operation may only be used as
! outlined in NFPA79, Paragraph 6-14 (exceptions 1-3) for
specialized applications. Equipment damage and/or personal injury
may result if the settings of Parameters 47-49 are used in an
inappropriate application.

Parameter 47 -- Power Loss Restart


Units = Code
Range = 0/1/2/3
Factory Setting = 1

This parameter selects the drive restart action taken if input power is
interrupted and restored within 100 ms –– However –– restart settings 1
and 2 in Parameter 48 will override any settings made in Parameter 47.

• When set to 0, the drive will restart and ramp to the last selected speed
–– but only for 2-wire external control.
• When set to 1, Power Loss Restart is disabled for both 2 and 3-wire
control schemes. The drive will not restart until the fault is cleared by
first issuing a stop command, then a start command. The drive will then
restart and ramp to the last selected speed.
• 2 defines the drive restart action for 2-wire external control. Once the
drive receives a start command, the drive will start and ramp to the last
selected speed but only after the initial waiting time set by Parameter 49.
Should an LU fault occur or OP message appear, the drive will restart
and ramp to the last selected speed after the initial waiting time set by
Parameter 49 without reissuing a start command.
• 3 defines the drive restart action for both 2 and 3-wire control. Once the
drive receives a start command, the drive will start and ramp to the last
selected speed but only after the initial waiting time set by Parameter 49.
Should an LU fault occur or OP message appear, the drive will not
restart until the fault or message has been cleared by first issuing a stop
command, then a start command. Once cleared, the drive will start and
ramp to the last selected speed after the initial waiting time set by
Parameter 49.

5-39

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Parameter 48 -- RideThru Restart


Units = Code
Range = 0/1/2
Factory Setting = 0

For all control schemes, this parameter selects the drive restart action taken
if input power is interrupted and restored within 100 ms. Restart settings 1
and 2 in Parameter 48 will override any settings made in Parameter 47.
• When set to 0, if power is removed for 15 ms, Ride-Thru Restart is
disabled and the drive will generate an LU fault. The drive will not
restart until the fault is cleared by first issuing a drive stop command,
then a start command. The drive will then restart and ramp to the last
selected speed.
• When set to 1, if power is removed for 15 ms, the drive will generate an
LU fault. If power is restored within 100 ms (or longer depending on
load), the drive will restart from zero speed, then ramp to the last
selected speed after the initial waiting time set by Parameter 49.
• When set to 2, if power is removed for 15 ms, the drive will generate an
LU fault. If power is restored within 100 ms (or longer depending on
load), the drive will continue to operate at the selected speed. If longer
than 100 ms, the drive will restart only after the initial waiting time set
by Parameter 49.

Parameter 49 -- Restart Time Select


Units = Seconds
Range = 000.1/100.0
Factory Setting = 000.1
This parameter sets the time the drive will wait before acting on a restart
command after an LU fault has occurred. The value of Parameter 49 is
selectable in 0.1 second increments.

5-40

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Lower and Upper Important: The maximum allowable drive output frequency will be
Frequency Clamp Settings determined by the lowest value programmed into the following parameters:
• Parameter 3 Frequency Range
• Parameter 15 Maximum Frequency
• Parameter 51 Upper Frequency Clamp
• Parameter 53 Bias Frequency –– If Parameter 53 is Higher Than
Parameter 54
• Parameter 54 Gain Frequency –– If Parameter 54 is Higher Than
Parameter 53

Parameter 50 -- Lower Frequency Clamp


Units = Hertz
Range = 00.50/400.0
Factory Setting = 00.50

This parameter sets the minimum frequency or speed that the drive can be
set to by any input control signal.

From 00.50-100.0 Hz, Parameter 50 sets the Lower Frequency Clamp in


.01 Hz increments.

From 100.0-400.0 Hz, Parameter 50 sets the Lower Frequency Clamp in


0.1 Hz increments.

Important: If an external potentiometer, a 0-5V DC, a 0-10V DC or a


4-20mA frequency reference is required:
• For directly proportional applications, enable Parameter 52 and enter a
minimum value of 00.50 for Parameter 53 if the Lower Frequency
Clamp is to set the minimum frequency.
• For inverse follower applications, enable Parameter 52 and enter a
minimum value of 00.50 for Parameter 54 if the Lower Frequency
Clamp is to set the minimum frequency.

5-41

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

➊ Maximum Output Frequency

Parameter 51

ra tion
ele
Acc

Parameter 50

Minimimum Frequency = 0.5


0
0% 100% of Input Frequency Signal

➊ Maximum Output Frequency

Parameter 51
De
cel
er a
tion

Parameter 50

Minimimum Frequency = 0.5


0
0% 100% of Input Frequency Signal

➊ Maximum Output Frequency = 50 Hz if Parameter 3 = 50


60 Hz if Parameter 3 = 60
Parameter 15 if Parameter 3 = FF

Lower and Upper Frequency Clamp Settings

Parameter 51 -- Upper Frequency Clamp


Units = Hertz
Range = 00.50/400.0
Factory Setting = 400.0

This parameter sets the highest frequency or speed that the drive can be set
to by any input control signal, unless Parameter 15 (Maximum Frequency)
or Parameter 3 (Frequency Range) has been set lower. If set to a value
higher than Parameter 3 or 15, the value will be entered, but the drive will
default to the lowest value set by Parameter 3 or 15 when operating.
From 00.50-100.0 Hz, Parameter 51 sets the Upper Frequency Clamp in
.01 Hz increments.
From 100.0-400.0 Hz, Parameter 51 sets the Upper Frequency Clamp in
0.1 Hz increments.

5-42

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Bias and Gain Settings Important: The maximum allowable drive output frequency will be
determined by the lowest programmed value of any of the following
parameters:
• Parameter 3 Frequency Range
• Parameter 15 Maximum Frequency
• Parameter 51 Upper Frequency Clamp
• Parameter 53 Bias Frequency –– If Parameter 53 is Higher Than
Parameter 54
• Parameter 54 Gain Frequency –– If Parameter 54 is Higher Than
Parameter 53

Parameter 52 -- Bias and Gain Enable


Units = Code
Range = 0/1
Factory Setting = 0

This parameter enables or disables both the Bias and Gain Frequencies set
by Parameters 53 and 54. Bias and Gain Frequencies allows a remote speed
signal to be used within a specific minimum and maximum frequency
range. The Bias and Gain Frequencies may be used to provide a directly or
inversely proportional 0-5V DC, 0-10V DC, 4-20 mA, or external speed
pot signal at the Control and Signal Wiring Terminal Block.
If set to 0, the bias and gain function is disabled.
If set to 1, the bias and gain function is enabled.

If the 1333 is to produce 0 output speed at 0 external input signal:


• Parameter 9 Local/Remote Frequency must be set to remote.
• Parameter 52 Bias and Gain Enabled must be enabled.
• Parameter 53 Bias Frequency must be set to the minimum output
frequency required.
• Parameter 54 Gain Frequency must be set to the maximum output
frequency required.

If the 1333 is to produce maximum output speed at 0 external input signal:


• Parameter 9 Local/Remote Frequency must be set to remote.
• Parameter 52 Bias and Gain Enabled must be enabled.
• Parameter 53 Bias Frequency must be set to the maximum output
frequency required.
• Parameter 54 Gain Frequency must be set to the minimum output
frequency required.
5-43

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

➊ 100% of Output Frequency

Parameter 54

n When Bias Frequency


tio
era is Less Than Gain
c cel
A a Directly Proportional
Input Frequency Signal
is Produced
Bias Frequency Less Than Gain

Parameter 53 = 0%
0% 100% of Input Frequency Signal

➊ 100% of Output Frequency

Parameter 53

Dece
le r a ti o
n

Parameter 54
When Bias Frequency
Bias Frequency Greater Than Gain is Greater Than Gain
an Inversely Proportional
Input Frequency Signal
is Produced
0%
0% 100% of Input Frequency Signal

➊ 100% of Output Frequency = 50 Hz if Parameter 3 = 50


60 Hz if Parameter 3 = 60
Paramer 15 if Parameter 3 = FF

Bias and Gain Settings


Parameter 53 -- Bias Frequency
Units = Hertz
Range = 00.00/400.0
Factory Setting = 00.00
From 00.50-400.0 Hz, Parameter 53 sets the Bias Frequency in .01 Hz
increments.
From 100.0-400.0 Hz, Parameter 53 sets the Bias Frequency in 0.1 Hz
increments.
Parameter 54 -- Gain Frequency
Units = Hertz
Range = 00.50/400.0
Factory Setting = 60.00
From 00.50-400.0 Hz, Parameter 54 sets the Gain Frequency in .01 Hz
increments.
From 100.0-400.0 Hz, Parameter 54 sets the Gain Frequency in 0.1 Hz
increments.
5-44

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Output Meter Settings Parameter 55 -- Frequency Output (Amps)


Units = % of Maximum Output Signal
Range = 075/125
Factory Setting = 100

This parameter is used to calibrate an output frequency ammeter while the


drive is running. It may be set from 75-125% of the maximum output
signal, 1 mA. The 1 mA signal is selected by setting switch SW1 on the
Control Board to the 1 mA position.

Parameter 56 -- Frequency Output (Volts)


Units = % of Maximum Output Signal
Range = 075/125
Factory Setting = 100

This parameter is used to calibrate an output frequency voltmeter while the


drive is running. It may be set from 75-125% of the maximum output
signal, 10V DC. The 10V DC signal is selected by setting switch SW1 on
the Control Board to the 10V DC position.

Monitoring Mode Settings Parameter 57 -- Monitor Display Select


Units = Code
Range = 0/1/2
Factory Setting = 0

This parameter sets one of three alternate monitoring modes that may be
selected while the drive is running.
When set to 0, A0 –– monitor equivalent drive output current.
When set to 1, A1 –– monitor equivalent motor RPM.
When set to 2, A2 –– monitor drive control frequency.

Parameter 58 -- Motor Pole Select


Units = Code
Range = 2/4/6/8/10
Factory Setting = 4

To allow motor RPM to be calculated and displayed when monitoring


mode A1 is selected, this parameter is used to enter the number of motor
poles.
5-45

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 5
Operation and Programming

Drive Fault Memory Parameters 59, 60, 61 and 62 -- Fault Buffer 0, 1, 2, and 3
Units = None
Range = None
Factory Setting = None

Parameters 59-62 will store the last (4) faults that the drive has encountered
in a cascading mode.
• Fault Buffer 0 will store the new fault.
• Fault Buffer 1 will store the fault from Fault Buffer 0.
• Fault Buffer 2 will store the fault from Fault Buffer 1.
• Fault Buffer 3 will store the fault from Fault Buffer 2.

5-46

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

6
Chapter

Startup

The Startup Process The following startup procedure uses the Local Control and Programming
Panel to setup the drive. To guard against damage to equipment caused by
incorrect or inappropriate parameter settings, steps 1-28 must be followed
in order. Step 29 is provided to allow you to incorporate an external 2 or
3-wire control scheme into your application.

ATTENTION: Power must be applied to the drive with the cover


! removed to perform certain startup procedures. Voltages on many
components are at incoming line potential or bus voltage. To avoid
electric shock hazard or damage to equipment, do not touch any
drive component other than those specified in the startup
procedure.

ATTENTION: Become familiar with the equipment and read


! through the wiring, speed selection and adjustment sections before
attempting to perform the startup procedures. Adjustments may be
required to meet specific load characteristics or operator
preference.
Exercise extreme care when performing any task on the drive.
Failure to do so may result in electric shock or equipment damage.
As shown on the next page, a DC bus neon light at the top of the
1333 has been provided to provide visual indication that bus
voltage is present. Bus voltage may be verified by using a
voltmeter and measuring the voltage between +BUS and –BUS on
the Power Terminal Block. Do not attempt to service the drive until
2 minutes after the neon light has extinguished and bus voltage has
discharged to zero volts.

6-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Important:
1. Power must be applied to the drive when viewing or changing 1333
parameters. Previous programming may effect the drive status when
power is applied.
2. Remote circuits may be connected to the Control and Signal Wiring
Terminal Block on the Main Control Board. Confirm that all circuits are
in a de-energized state before applying power.
3. User supplied voltages may exist at the Control and Signal Wiring
Terminal Block even when power is not applied to the drive.
4. If you cannot complete a procedure, immediately refer to Appendix B
— Preventive Maintenance and Troubleshooting Common Drive
Problems. Do not proceed. Determine the cause of the problem and
correct the problem first, then return to the startup procedure.

DC Bus Neon Light

Drive Control Board Switches


SW2
SW1

Control and Signal Wiring Terminal Block

Power Terminal Block

Auxiliary Interlock
Drive Nameplate
Drive Cover Thumbscrews

Figure 61 -- 3/45HP (.554kW) Drive

6-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

DC Bus Neon Light

Drive Control Board Switches


SW2
SW1

Control and Signal Wiring Terminal Block

Power Terminal Block

Auxiliary Interlock
Drive Cover Thumbscrews
Drive Nameplate

Figure 62 -- 71/220HP (5.515kW) Drive

1333 parts, switches and terminal blocks shown in Figures 6-1, 6-2 and 6-3
are referenced throughout the Initial Operation, Function Checks, Function
and Final Settings Sections of this chapter.

6-3

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Initial Operation Step 1


- Motor Disconnected Verify that AC line power at the disconnect device is within the rated value
of the drive nameplate data. Drive nameplate and alternate voltage ratings
are explained in Chapter 2 — Drive Identification.

Step 2
Remove and lock out all incoming power to the drive. Remove the drive
cover and disconnect the motor leads from terminals U/T1, V/T2, W/T3 at
the Power Terminal Block. Insulate the exposed wires to prevent accidental
contact with other drive components.

Step 3
If an auxiliary interlock is not installed at the Control and Signal Wiring
Terminal Block, verify that the spare jumper provided with the drive is
installed between terminals 16 and 17.

Step 4
Replace the drive cover and tighten both thumbscrews. Apply power to the
drive and verify that no faults are displayed.
• Both the main and mode displays should immediately light.
• The main display should read 0000. If the main display indicates OU or
LU, an incorrect voltage is being applied to the drive.
• The mode display should read LL. to allow control of the drive from the
Local Control and Programming Panel. If not, refer to Chapter 5 ––
Operation and Programming to change Parameters 8 and 9 to local
control.

Important: Steps 5-15d are Function Checks based on factory parameter


settings. The function groups listed, reference the same parameters as
grouped in Chapter 5 and Appendix C. If the drive has been previously
commissioned, parameter settings may not be compatible with this startup
procedure. Drive status and fault conditions will be unpredictable when
power is first applied.
To obtain the proper results, initially change all parameter values to the
factory settings listed on the drive cover label. If it is required to change a
parameter, you will be instructed to do so.

6-4

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Function Checks The Main Display


- Motor Disconnected
Hz LED
The Select Pushbutton Alternate LED

The Lock Switch The Enter Pushbutton

The Stop Pushbutton

The Directional Start Pushbutons

The Mode Display The Shift Pushbutton


The Increment Pushbutton The Decrement Pushbutton

Figure 63 -- 3/420HP (.5515kW) Controls

Step 5 -- Local/Remote Control Enable Check


Max Speed Settings Check
Start the drive by pressing either directional start pushbutton. The
pushbutton will light. Press and hold the increment pushbutton and watch
the display increase. Release thew pushbutton when the display reaches
60.00 Hz or maximum speed.

Step 6 -- Monitor Mode Settings Check


Press the select pushbutton once. The main display will flash and show the
last manual set speed entered.
Press the select pushbutton again. A0. will be shown in the mode display,
drive output amps in the main display, as set by Parameter 57.
Press the select pushbutton again. The mode display will flash and show
0I. to indicate the parameter being viewed, and the main display will show
005.0, the accel time set by Parameter 1.
Press the pushbutton again and 60.00Hz will again be displayed.

Step 7 -- Reverse Enable Check


Accel and Decel Settings Check
Press the other directional start pushbutton. The pushbutton will light and
the drive display will ramp down to 0.00 Hz within the decel time set by
Parameter 2, then immediately ramp up to 60.00 Hz, the maximum speed
presently programmed by Parameter 3, within the accel time set by
Parameter 1. Reversing is enabled or disabled by Parameter 10.

6-5

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Function Checks Step 8 -- Local/Remote Speed Enable Check


- Motor Disconnected Lower and Upper Frequency Clamp Settings Check
Press the select pushbutton once. The main display will again flash and
show the last manual set speed entered. Using the increment, decrement
and shift pushbuttons, any value between 00.50 (the lower frequency clamp
set by Parameter 50), and 60.00 Hz can be selected.
Select a value and press the enter key. The drive will either accel within the
accel time set by Parameter 1, or decel within the decel time set by
Parameter 2, to a value within these limits. Had Parameter 51 been set to a
value lower than 60.00 Hz, the upper frequency clamp would be the
highest frequency the drive could reach.

Step 9 -- Stop Setting Check


Press the stop pushbutton to stop the drive. The drive display will ramp
down to zero within the decel time set by Parameter 2. Had Parameter 11
been set to 1, the drive would have been set to coast-to-stop and Parameter
2 would have no affect on stopping time.

Step 10 -- Jog Settings Check


Press the shift pushbutton once and LJ. will be shown in the mode display.
Press and hold either directional start pushbutton. The pushbutton will light
and the drive display will ramp up to I0.00 Hz, or the maximum jog speed
set by Parameter 26, within the jog accel time set by Parameter 27. Release
the directional start pushbutton and the drive will ramp back down to
0.00 Hz at the jog decel time set by Parameter 28. Once fully stopped, the
drive will display 0000 .

Step 11 -- Auxiliary Interlock Enable Check


Drive Fault Memory Check
Start the drive. If an external auxiliary interlock has been installed between
terminals 16 and 17 at the Control and Signal Wiring Terminal Block, open
the interlock. AU will be shown at the main display, indicating an auxiliary
interlock fault.
• Press the stop pushbutton to clear the fault.
• Press the select pushbutton three times to access the parameter display.
• Select Parameter 59. Fault Buffer 0 will display AU, the last fault
received by the drive.
If Parameter 21 had been set to 1, the drive would have displayed AS at
the main display, indicating an auxiliary stop. An AS is not a fault, and
therefore not stored in memory.

6-6

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Function Checks Step 12 -- Drive Supplied Contact Settings Check


- Motor Disconnected Stop the drive. Remove and lock out all incoming power to the drive, then
remove the drive cover.
Reapply power and start the drive. N.O. contact CR2 (terms. 20 & 21 on
the Control and Signal Wiring Terminal Block) will close as presently
programmed by Parameter 23. Once the drive is within ± 2 Hz of set speed,
N.O. contact CR1 (terminals 19 & 20 on the Control and Signal Wiring
Terminal Block) will close since Parameter 24 is presently set to 1.

Step 13a -- Auto Restart Settings Check

ATTENTION: Auto restart operation may only be used as


! outlined in NFPA79, Paragraph 6-14 (exceptions 1-3) for
specialized applications. Equipment damage and/or personal injury
may result if the settings of Parameters 47-49 are used in an
inappropriate application.

To properly program the drive to restart when required demands that


Parameters 47-49 be coordinated correctly. When Parameter 48 is set to 1
or 2, it will override any setting made in Parameter 47. Likewise the restart
time set in Parameter 49 will affect the restart actions taken by both
Parameters 47 and 48.

Step 13b -- Auto Restart Settings Check


If Power Loss Restart is required, set Parameters 1 and 3.
Stop the drive.
• Change Parameter 47 from 1 to 3.
• Change Parameter 49 from 000.1 seconds to 10.00 seconds.
Press the start pushbutton. The directional start pushbutton LED will
immediately light. After 10 seconds the drive will ramp up to 60 Hz and
the main display will show 60.00.

Remove then reapply incoming power to the drive at the disconnect device
within 100 ms. LU will be shown at the main display indicating a power
fault. Press the stop pushbutton to clear the fault, then the start pusbutton to
start the drive. Since Parameter 49 has been changed, the drive will not
restart for 10 seconds.
• Had the drive been configured for 2-wire control and Parameter 47 set to
0, without clearing the fault, the drive would have automatically
restarted and ramped up to 60 Hz without a waiting time.
• Had the drive been configured for 2-wire control and Parameter 47 set to
3, without clearing the fault, the drive would have automatically
restarted and ramped up to 60 Hz after 10 seconds.
6-7

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Function Checks Step 13c -- Auto Restart Settings Check


- Motor Disconnected If Ride-Thru Restart is required, set Parameters 1 and 3.
Stop the drive.
• Change Parameter 48 from 0 to 1.
Remove then reapply incoming power to the drive at the disconnect device
within 100 ms. LU will be shown at the main display indicating a power
fault. The directional start pushbutton LED will immediately light. After
10 seconds, the drive will ramp up to 60 Hz and the main display will
show 60.00.

Stop the drive.


• Change Parameter 48 from 1 to 2.
Remove then reapply incoming power to the drive at the disconnect device
within 100 ms. LU will be shown at the main display indicating a power
fault. The directional start pushbutton LED will immediately light. After
10 seconds, the main display will immediately show 60.00. The drive
accel ramp has been eliminated and the drive will restart at the last
commanded speed, 60 Hz.

Stop the drive and return Parameters 47-49 to their factory settings.

Step 14 -- Bias and Gain Settings Check


If an external 10kΩ, 2W potentiometer, 0-5V DC, 0-10V DC or 4-20 mA
signal is connected to the drive, the bias and gain settings should be
verified.
• Change Parameter 52 from 0 to 1 to enable the bias and gain function.
• Change Parameter 53 from 00.50 to 60.00.
• Change Parameter 54 from 60.00 to 00.50.
With zero speed signal applied to the drive, start the drive. Apply the
smallest speed signal possible. The drive display will immediately ramp up
to 60.00 Hz. Apply maximum signal to the drive. The drive display will
ramp down to 0.50 Hz. This is because an inversely proportional signal
has been sent to the drive. Stop the drive and return Parameters 52-54 to
their factory settings.

6-8

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Step 15a -- Preset Frequency and Aux Accel/Decel Enable Check


If external switches have been connected to the Control and Signal Wiring
Terminal Block as detailed in Chapter 5, preset frequencies as well as
auxiliary accel and decel times can be checked.

Step 15b -- Preset Frequency and Aux Accel/Decel Enable Check


Enable Auxiliary Accel/Decel Settings
Stop the drive and depress the lock button to allow programming. Set
Parameter 19 to 2. By setting Parameter 19 to 2, auxiliary accel/decel times
will be enabled and can be checked simultaneously with preset speeds.

Step 15c -- Preset Frequency and Aux Accel/Decel Enable Check


If two preset speed switches have been installed, verify that switch
SW2 is set to 4SP.
• Closing switch S1 and opening switch S2 will force the drive to
20.00 Hz, the Preset Frequency 2 value set by Parameter 29, within the
2nd auxiliary accel time set by Parameter 36, or the 2nd auxiliary decel
time set by Parameter 37.
• Opening switch S1 and closing switch S2 will force the drive to
30.00 Hz, the Preset Frequency 3 value set by Parameter 30, within the
3rd auxiliary accel time set by Parameter 38, or the 3rd auxiliary decel
time set by Parameter 39.
• Closing switches S1 and S2 will force the drive to 40.00 Hz, the Preset
Frequency 4 value set by Parameter 31, within the 4th auxiliary accel
time set by Parameter 40, or the 4th auxiliary decel time set by
Parameter 41.

6-9

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Function Checks Step 15d -- Preset Frequency and Aux Accel/Decel Enable Check
- Motor Disconnected If three preset speed switches have been installed, verify that switch
SW2 is set to 8SP.
• Closing switch S1 and opening switches S2 and S3 will force the drive
to 20.00 Hz, the Preset Frequency 2 value set by Parameter 29, within
the 2nd auxiliary accel time set by Parameter 36, or the 2nd auxiliary
decel time set by Parameter 37.
• Opening switches S1 and S3 and closing switch S2 will force the drive
to 30.00 Hz, the Preset Frequency 3 value set by Parameter 30, within
the 3rd auxiliary accel time set by Parameter 38, or the 3rd auxiliary
decel time set by Parameter 39.
• Closing switches S1 and S2 and opening switch S3 will force the drive
to 40.00 Hz, the Preset Frequency 4 value set by Parameter 31, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.
• Opening switches S1 and S2 and closing switch S3 will force the drive
to 15.00 Hz, the Preset Frequency 5 value set by Parameter 32, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.
• Opening switch S2 and closing switches S1 and S3 will force the drive
to 25.00 Hz, the Preset Frequency 6 value set by Parameter 33, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.
• Opening switch S2 and closing switches S1 and S3 will force the drive
to 35.00 Hz, the Preset Frequency 7 value set by Parameter 34, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.
• Closing switches S1, S2 and S3 will force the drive to 45.00 Hz, the
Preset Frequency 8 value set by Parameter 35, within the 4th auxiliary
accel time set by Parameter 40, or the 4th auxiliary decel time set by
Parameter 41.

6-10

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Function Settings ATTENTION: The following steps may cause motor rotation in
- Motor Connected ! an unknown direction. To guard against equipment damage, always
- NoLoad Condition disconnect the motor from the load before proceeding.

Important: The remaining steps are Function Settings that reference the
same parameters as grouped in Chapter 5 –– Operation and Programming.

Step 16
Stop the drive and remove and lock out all incoming power to the drive.
Remove the drive cover and reconnect the motor leads at terminals U/T1,
V/ W
T2, /T3 at the Power Terminal Block.

Step 17
Replace the drive cover and tighten both thumbscrews. Apply power to the
drive and verify that no faults are displayed.
• Both the main and mode displays should immediately light.
• The main display should read 0000. If the main display indicates OU or
LU, an incorrect voltage is being applied to the drive.
• The mode display should read LL. to allow control of the drive from the
Local Control and Programming Panel. If not, refer to Chapter 5 to
change Parameters 8 and 9 to local control.

Step 18 -- VoltsperHertz Curve Settings


Overload Protection Settings
Set Parameters 3 and 4 to match your volts-per-Hertz curve and drive
frequency range requirements as detailed in Chapter 5.
If overload protection is not required, leave Parameter 6 set to 0. If
overload protection is required:
• Set Parameter 6 to correspond to the motor duty as outlined in Chapter 5.
• Set Parameter 7 to correspond to the rated amps on your motor
nameplate.

6-11

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Function Settings Step 19


- Motor Connected Press the shift pushbutton once and LJ. will be shown in the mode display.
- NoLoad Condition Press and release the directional start pushbutton that will be your forward
motor direction. If the direction of motor rotation is incorrect:
• Remove input power, wait until the displays are no longer lit, then
remove the drive cover.
• Verify that the DC bus neon light is no longer lit and that bus voltage at
the +Bus and –Bus terminals of the power terminal block is zero.
• Interchange any two of the three motor leads at terminals U/T1, V/T2,
W/ at the Power Terminal Block.
T3
• Replace the drive cover and tighten both thumbscrews. Apply power to
the drive and verify that no faults are displayed.

Step 20 -- Output Meter Settings


If an external output ammeter or voltmeter is connected to the Control and
Signal Wiring terminal block, the meter should be calibrated and switch
SW1 should be set as detailed by Parameters 55 or 56 in Chapter 5.

6-12

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Final Settings ATTENTION: To avoid hazards of electrical shock or injury


- Motor Connected ! from moving equipment, product, or process ingredients:

- Load Connected • Alert all personnel.


• Install all guards.
• Check operation of all safety devices.
• Be prepared to stop the motor immediately.

Step 21
Disconnect and lock-out all power. Connect the motor to the load.
Before applying power, review the parameter descriptions in Chapter 5.
Each parameter may have a significant effect on fundamental drive and
motor operation regardless of the control method used.
Apply power. Prepare to operate the drive and motor under actual control
and load conditions. It is recommended to begin at low torque and speed.
Start the motor and run the machine or process to determine if parameter
settings are acceptable for the application. If not, stop the drive and reset
parameters. Refer to Chapter 5 to make parameter changes and record the
changes in Appendix C.

Step 22
If Increased Motor Torque is Required at Startup
Increase the value of Parameter 5 in small increments.
Parameter 5 adds from 0 to 40% of the drive output voltage to the motor at
low drive frequencies, boosting motor torque at startup. DC boost can be
added to any volts-per-Hertz curve. The optimum DC boost setting is the
lowest level that will permit satisfactory starting torque for the motor and
drive. Higher than optimum boost may produce unnecessary motor current
at low frequencies and contribute to motor overheating. Excessive boost
may even force the drive into an overcurrent condition.

Step 23
If DC Braking is Required for Speed Changes, Reversing or to Stop
the Motor
Set Parameter 14 to 1 first.
When Parameter 14 is set to a value of 1-10, the drive’s DC brake function
will be enabled. Parameters 12 and 13 along with Parameter 14 will then
set the DC brake function. The value of Parameter 14 determines the level
or strength of the braking that occurs, with 1 being the lowest, 10 the
highest.
6-13

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Chapter 6
Startup

Final Settings Step 24


- Motor Connected If Heavy Duty Dynamic Braking is to be Installed
- Load Connected If Heavy Duty Dynamic braking is required, set Parameters 11 and 14 to 0.

Step 25
If Machine Resonance is Encountered
Set Parameters 42-45 to skip those frequencies which cause the machine to
resonate.

Step 26
If Nuisance Tripping is Encountered
Enable Parameters 17 and/or 18 to disable drive acceleration or
deceleration during high Bus current or voltage conditions.

Step 27
If the Connected Load is an Overhauling Load
Set Parameter 18 to 0 to disable Decel Frequency Hold.

Step 28
If a Different Running Monitor Mode is Required
Change Parameter 57 to:
• 0 to monitor drive output current.
• 1 to monitor equivalent motor RPM.
• 2 to monitor drive control frequency.

Step 29
If an External 2 or 3-Wire Control Scheme is to be Used
• Connect the 2 or 3-wire controls as shown in Figure 4-3 and described in
Chapter 4.
• Set Parameter 8 to 1 for 2-wire control, 3 for 3-wire control.
• Repeat the startup procedure starting from step 1.

6-14

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

A
Appendix

Bulletin 1333 Options

Using Bulletin 1332 and Bulletin 1332 and 1333 Options can be used with Series D drives.
1333 Options with Point-to-point interconnections and the required Series D parameter
Bulletin 1333 Series D Drives settings are detailed below and on the following pages. Refer to the
individual option kit instructions for installation procedures and the
additional information required to setup each option.

1332MODF Bulletin 1333 Series D 1332MODF


Control and Signal Wiring Terminal Block Remote Operator Station
Remote Operator Station
Term 1

Term 2

Term 3 Term 3

Term 4

Term 5

Term 6

Term 7 Term 7

Term 8 Term 8

Term 3 Term 9

Term 10

Term 11 Term 11

Term 12

Term 13

Start/Stop and Forward/Reverse Control


To allow the 1333 Series D to accept 1332-MOD-F start/stop and
forward/reverse commands, Parameter 8 Local/Remote Control Enable
must be set to 1 or 3.

Speed Control
To allow the 1333 Series D to accept the 1332-MOD-F speed
potentiometer signal, Parameter 9 Local/Remote Speed Enable must be set
to 1, 2 or 3.

A-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix A
Bulletin 1333 Options

1333MODG4 1333MODG4
Bulletin 1333 Series D BCD Interface Board
BCD Interface Control and Signal Wiring Terminal Block Terminal Block TB3
Drive Ratings ZABCAA
Term 1 Customer Supplied
Components
Term 2

Term 3 Term 3
Remote
Term 4 Term 4 Manual
Term 5 Speed Pot

Term 6 Remote
Manual
Term 7
Direction Switch
Term 8

Term 9

Term 10

Term 11
1333MODG4
BCD Interface Board
Terminal Block TB2
115V AC
Term 1
Supply Signal
Term 2 Remote
Auto/Man Switch
1333MODG4
BCD Interface Board
Jumper J3 set for 230V

1333MODG4
Bulletin 1333 Series D BCD Interface Board
Power Terminal Block Terminal Block TB4

Term 1

Term L2/S Term 2

Term L3/T Term 3

VoltsperHertz, Maximum Frequency and Base Frequency


The frequency range of the 1333-MOD-G4 BCD Interface Board and the
Bulletin 1333 Series D drive must match. Once the scaling jumper on the
BCD Interface Board has been set, Parameter 3 Frequency Range must be
set to either 60 or FF. If set to FF, both Parameter 15 Maximum Frequency
and Parameter 16 Base Frequency must also be set.
BCD Interface
Scaling Jumper Parameter 3 Parameter 15 Parameter 16
60Hz 60 -- --
120Hz FF 60Hz 120Hz
200Hz FF 60Hz 200Hz

Important: When Parameter 3 is set to FF, the drive volts-per-Hertz output


will reach the maximum voltage at the value set by Parameter 16.
Applications where volts-per-Hertz curves are required to reach maximum
voltage other than at 50 or 60 Hz are primarily provisions for operating
custom motors. For application assistance in these special ranges, contact
your nearest Allen-Bradley representative.
A-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix A
Bulletin 1333 Options

1333MODG4 1333MODG4
BCD Interface Bulletin 1333 Series D BCD Interface Board
Drive Ratings AABCAB Control and Signal Wiring Terminal Block Terminal Block TB3

Term 1 Customer Supplied


Components
Term 2

Term 3 Term 3
Remote
Term 4 Term 4 Manual
Term 5 Speed Pot

Term 6 Remote
Manual
Term 7
Direction Switch
Term 8

Term 9

Term 10

Term 11
1333MODG4
BCD Interface Board
Terminal Block TB2
115V AC
Term 1
Supply Signal
Term 2 Remote
Auto/Man Switch
1333MODG4
BCD Interface Board
Jumper J3 set for 115V

1333MODG4
BCD Interface Board
Terminal Block TB4

Term 1 Remote
Term 2 115V AC
1Phase
Term 3 AC Supply

Speed Control
To allow the 1333 Series D to accept the 1333-MOD-G4 0-10V DC speed
signal, Parameter 9 Local/Remote Speed Enable must be set to 2.

Forward/Reverse Control
If the 1333 Series D is to have its forward/reverse operation controlled
from the Local Control and Programming Panel, Parameter 8
Local/Remote Control Enable must be set to 0 or 2.
If the 1333 Series D is to have its forward/reverse operation controlled by
the BCD Interface Board, Parameter 8 Local/Remote Control Enable must
be set to 1 or 3.
Important: If Parameter 8 is set to 1 or 3, an external means of start/stop
control must be connected to the Control and Signal Wiring Terminal
Block. Refer to Chapter 4 for additional information.

A-3

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix A
Bulletin 1333 Options

1333MODKA1, KA2, KB1, KB2 Bulletin 1333 Series D


Power Terminal Block
Heavy Duty Dynamic Braking
Term +BUS P Dynamic
Brake
Term -BUS N Unit

Stop Setting
If Heavy Duty Dynamic Braking is installed, Parameters 11 and 14 must be
set to 0.

A-4

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

B
Appendix

Preventive Maintenance and


Troubleshooting Common Drive Problems

Preventive Maintenance The Bulletin 1333 is convection cooled by air flowing through the heat
sink slots. The slots must never be allowed to become obstructed with dirt
or foreign matter. Periodically check and clean the heat sink slots.

Problems with Your Drive? The following descriptions indicate the operation of protective circuitry in
Check the Following First the Series D Bulletin 1333. What is thought to be a drive operational
problem, may in reality be normal protection circuit operation. Refer to the
following precheck procedures and Chapter 5 –– Operation and
Programming before attempting to troubleshoot your drive.

Precheck Procedures Acceleration Stall Protection -- No Fault is Displayed


The Reason During motor acceleration, if current exceeds 140% of rated
Drive current or 125% of Parameter 7, the overcurrent stall protection
circuit operates. In order to guard against currents in excess of these values
and prevent an overcurrent trip, this circuit temporarily stops drive
acceleration. When load current is again below these values, the circuit lets
the drive continue to accelerate to set frequency.

Precheck Procedure If the application does not require this function it can
be deactivated by setting Parameter 17 to 0.

Deceleration Stall Protection -- No Fault is Displayed


The Reason During motor deceleration, if current exceeds 140% of rated
Drive current or 125% of Parameter 7, the overcurrent stall protection
circuit operates. In order to guard against currents in excess of these values
and prevent an overcurrent trip, this circuit temporarily stops drive
deceleration. When load current is again below these values, the circuit lets
the drive continue to decelerate to set frequency.

Precheck Procedure Both Parameters 18 and 46 will protect the drive from
nuisance trips during motor deceleration. If the application does not
require this function it can be deactivated by setting Parameters 18 and/or
46 to 0.

B-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

Over Current Protection -- OC is Displayed


The Reason If overcurrent exceeds 200% of rated Drive current or if a
ground fault occurs at the drive output leads, this protective circuit will
shut off the drive transistors.

Precheck Procedure
1. Load inertia is excessively large and programmed acceleration time is
extremely short. Setting Parameter 17 to 1 or increasing the value of
Parameter 1 will guard against OC nuisance trips.
2. The motor experienced an excessive overload condition. If the drive
tripped on acceleration, setting Parameter 7 to a higher current limit
setting may avoid OC nuisance trips. If the drive trips only on
deceleration, enabling Parameter 46 may avoid OC nuisance trips on
deceleration.
3. A short circuit exists in the drive output leads or in the motor windings.
4. A ground fault exists in the drive output leads or in the motor windings.
5. A device in the Drive output inverter section has shorted.

Over Load Protection -- OL is Displayed


The Reason If Parameter 6 is set to 0 and current exceeds 140% of rated
Drive current for 60 seconds, this protective circuit will shut off the drive
transistors.
If Parameter 6 is set to a value other than 0 and current exceeds 115% of
Parameter 7 for 60 seconds, this protective circuit will shut off the drive
transistors.

Precheck Procedure
1. The starting load is above 140%. The Drive is attempting to start the
load, but Parameter 17 is preventing it. Disable Parameter 17.
2. The running load has been above 140% for one minute. The Drive may
be in accel frequency hold if below the current limit set by Parameter 7,
or in accel frequency hold if at the current limit set by Parameter 7.
Check Parameters 17 and 6. If neither accel frequency hold nor overload
protection is selected, the Drive has been between 140% and 180% of
rated current for one minute, tripped out, and is functioning normally.
3. The running load has been above 115% of Parameter 7 for 60 seconds
causing the motor to overheat and the drive to trip. Check Parameters 17
and 7, then check to see if Parameter 6 is set to a value other than 0.

B-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

Over Voltage Protection -- OU Displayed


The Reason When DC bus voltage rises above a preset level due to high
incoming line voltage or excessive regenerative energy, this protective
circuit stops transistor operation and annunciates the condition as shown.

Precheck Procedure
1. Check and correct the incoming line voltage. Refer to Chapter 3 ––
Specifications for acceptable voltage levels.
2. An extremely short deceleration time is the primary cause of excessive
regenerative line energy. Setting Parameter 18 to 1 or increasing
Parameter 2 will guard against OU nuisance trips. It may also be
necessary to add the Heavy Duty Dynamic Braking option.

Low Voltage Protection -- LU is Displayed


The Reason When incoming line voltage falls below 90% for 15 ms, this
protective circuit stops transistor operation to guard against incorrect drive
operation.

Precheck Procedure If the momentary power failure is less than 15 ms,


operation is not interrupted. If more than 15 ms, the drive will trip and line
voltage must be restored by cycling power. If automatic restart of the drive
is required, set Parameter 48 to 1 or 2 as detailed in Chapter 5.

Over Temperature Protection -- OH is Displayed

The Reason When heat sink temperature rises above + 50°C, this protective
circuit stops transistor operation and annunciates the condition as shown.

Precheck Procedure Check the drive ambient temperature. For 7 1/2-20 HP


(5.5-15 kW) units, check the cooling fan.

B-3

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

Auxiliary Interlock Trip -- AU is Displayed


The Reason It is possible that the drive was stopped by an external
interlock. External interlocks (a thermal overload relay or an external
sequence circuit for example), are connected to terminals 16 and 17 at the
Control and Signal Wiring Terminal Block.

Precheck Procedure Refer to Chapter 4 Installation and Wiring for a


detailed explanation of external interlocks.

Operating Error -- OP is Displayed


The Reason The drive must always receive a valid stop command before it
can run. This fault will be displayed and the drive will not start if:
1. The local stop pushbutton is pressed to stop the drive and Parameter 8 is
set to 1 or 3.
2. A remote stop signal is sent and Parameter 8 is set to 2.
3. Parameter 8 is set to 1 or 3 and an external stop signal is not present
when power is applied to the drive.

Precheck Procedure
1. Send an external stop signal to clear the fault, then try again.
2. Press the local stop pushbutton to clear the fault, then try again.
3. Ensure that an external stop signal is present before reapplying power to
the drive, then try again.

Operating Error -- CPU is Displayed


The Reason CPU is an internal software communications error. A CPU
error will not be stored in the drive fault buffers.

Precheck Procedure
Clear the fault by removing then reapplying power to the drive.

B-4

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

Troubleshooting Eight common problems that may be experienced when operating the
Common Drive Problems Series D Bulletin 1333 and their solutions are listed in the remaining pages
of this section.
1. The motor will not run.

2. The motor will not run continuously.

3. The motor generates an excessive amount of heat

4. The drive will not reverse in local control.

5. The drive will not ramp-to-stop.

6. The drive will not accelerate to maximum speed.

7. The drive will not decelerate to minimum speed.

8. An input line fuse has blown.

ATTENTION: Power must be applied to the drive with the cover


! removed to perform certain troubleshooting checks. Voltages on
many components are at incoming line potential or bus voltage. To
avoid electric shock or damage to equipment, do not touch any
drive components with power applied.

ATTENTION: Become familiar with the equipment and read


! through the wiring, speed selection and adjustment sections before
attempting to perform the startup procedures. Adjustments may be
required to meet specific load characteristics or operator
preference.
Exercise extreme care when performing any task on the drive.
Failure to do so may result in electric shock or equipment damage.
As shown in Figures B-1 and B-2, a DC bus neon light at the top of
the 1333 has been provided to provide visual indication that bus
voltage is present. Bus voltage may be verified by using a
voltmeter and measuring the voltage between +BUS and –BUS on
the Power Terminal Block. Do not attempt to service the drive until
2 minutes after the neon light has extinguished and bus voltage has
discharged to zero volts.

B-5

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

DC Bus Neon Light

Lock Switch

Control and Signal Wiring Terminal Block

Power Terminal Block

Auxiliary Interlock
Drive Nameplate

Figure B1 -- 3/45HP (.554kW)

1333 parts, switches and terminal blocks shown in Figures B-1 and B-2 are
referenced throughout the remainder of this chapter.

1. The motor will not run -- AU is displayed.


Are Terms 16 and 17 at the Control and Signal Wiring Terminal Block No Remove the cause of the interlock fault or jumper terminals 16 and 17 if an
jumpered? Is an auxiliary interlock installed between Terms 16 and 17? auxiliary interlock is not required.

Yes

Contact your nearest AB representative for application assistance.

B-6

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

DC Bus Neon Light

Lock Switch

Control and Signal Wiring Terminal Block


Auxiliary Interlock

Power Terminal Block

Drive Nameplate

Figure B2 -- 71/220HP (5.515kW)

1. The motor will not run -- OH is displayed.


Is ambient temperature above the rated limit of 505C? Are the cooling fins No Lower the ambient temperature, clean the heat sink, or replace the cooling
clogged or is the heat sink dirty? For 71/220HP (5.515kW) units, is the fan.
cooling fan rotating?

Yes

Contact your nearest AB representative for application assistance.

B-7

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

1. The motor will not run -- No fault is displayed.

Is rated input voltage present at terminals R/L1, S/L2, and T/L3?


No Check input side for circuit breaker trip, contactor coil malfunction, blown
fuse, etc.

Yes

Is the decimal point in the mode display lit? No The drive is in the programming mode. Give the drive a valid stop command
and press the lock switch. The decimal point in the mode display will light and
the local or remote control source currently controlling the drive will be
displayed.
Yes

Is Parameter 8 set correctly?


No Parameter 8 settings.
0 = Local start/stop control without maintained external stop.
1 = Remote 2wire start/stop control at the Control and Signal Wiring
Terminal Block.
2 = Local start/stop control with maintained external stop.
3 = Remote 3wire start/stop control at the Control and Signal Wiring
Yes Terminal Block.

Is Parameter 9 set correctly?


No Parameter 9 settings.
0 = Local speed control.
1, 2 or 3 = Remote speed control only at the Control and Signal Wiring
Terminal Block -- Terms 1, 2 and 3.
1 = External speed pot or 05V DC.
2 = External speed pot or 010V DC.
Yes 3 = External speed pot or 420mA.

Are Parameters 6 and 7 set correctly?


No If Parameter 6 is set to a value other than 0, Parameter 7 is active. Parameter
7 must then be set to the motors nameplate current rating.

Yes

Are the motor leads securely connected to drive output terminals U/T1, V/T2 No
Verify and change connections if necessary.
and W/T3?

Yes

Contact your nearest AB representative for application assistance.

B-8

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

1. The motor will not run -- OP is displayed.

Is Parameter 8 Local/Remote Control set to 1 (external control)?


Yes The drive is set for 2wire external control. Check for correct wiring at the
Control and Signal Wiring Terminal Block. Reset the drive with an external
stop command.
No

Is Parameter 8 Local/Remote Control set to 2 (local control)?


Yes An external maintained stop signal must first be present to start the drive.
Check for correct wiring at the Control and Signal Wiring Terminal Block
Reset the drive by pressing the local stop button.
No

Is Parameter 8 Local/Remote Control set to 3 (external control)?


Yes The drive is set for 3wire external control. Check for correct wiring at the
Control and Signal Wiring Terminal Block. Reset the drive with an external
stop command.

2. The motor will not run continuously -- LU is displayed.

Has incoming line voltage dropped below 90% of rated voltage?


Yes Monitor the incoming line voltage and correct the condition.

No

Contact your nearest AB representative for application assistance.

B-9

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

2. The motor will not run continuously -- OC is displayed.

Does a short circuit exist in the output leads or motor windings?


Yes Remove the cause of the short circuit.

No

Does a ground fault exist between the drive output leads and the motor or in Yes
Remove the cause of the ground fault.
the motor windings?

No

Does the drive trip when the speed reference is below 5.0Hz?
Yes Is the application a fan or pump system?

No Yes

Reduce the boost setting Change the V/Hz ramp to


in Parameter 5. variable by setting
Parameter 4 to 1, then
No reduce the boost level
setting in Parameter 5 if
required.

Is the acceleration time too short? Is Parameter 17, Accel Frequency Hold Yes Increase the value of Accel Time 1 Parameter 1, or set Parameter 17 Accel
off? Frequency Hold on.

No

Is the load within the rated current of the drive?


No Program Parameter 46 Current Limit to eliminate nuisance tripping, lighten
the load, or resize the drive and motor to meet your application.

Yes

Is OC displayed even if the drive output leads are disconnected?


No Verify motor operation by line operating the motor or repeating the above. Is
the motor now operating correctly?

Yes
Yes No

Contact your nearest AB representative for application assistance.

B-10

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

2. The motor will not run continuously -- OL is displayed.

Is the load current equal to the motor nameplate rating? Is the load current No An OL trip occurs when the load current is greater than 140% for one minute.
within the rated current of the drive? Lighten the load or resize the drive and motor to meet your application.

Yes

Is Parameter 6 set to 1, 2 or 3?
No When set to 1, 2 or 3, the thermal overload function is enabled. Check for the
correct setting as detailed in Chapter 5.

Yes

Is Parameter 7 set to the rated motor nameplate value?


Yes An OL trip occurs when the load current is greater than 125% of the overload
current value set in Parameter 7 for one minute. Lighten the load or resize the
drive and motor to meet your application.
No

Set Parameter 7 to the rated motor nameplate value.

2. The motor will not run continuously -- OU is displayed.

Is the incoming AC power line high?


Yes Monitor and correct the AC line.

No

Is the deceleration time too short? Is Parameter 18, the Decel Frequency Yes Increase the value of Decel Time 1 Parameter 2, or set Parameter 18 Decel
Hold off? Frequency Hold on.

No

Is an overhauling load present -- Does the load increase the motor speed Yes Increase the value of Parameter 14 DC Hold Volts. Install the Heavy Duty
beyond the drive set speed? Dynamic Brake Option. Does the problem still exist?

No Yes

Contact your nearest AB representative for application assistance.

B-11

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

3. The motor generates an excessive amount of heat -- No fault is displayed.

Is full load demanded continuously at low frequency? Yes An OL trip occurs when the load current is greater than 140% for one minute.
Lighten the load or resize the drive and motor to meet your application.

No

Is the motor operating above the full load current?


Yes The load is beyond the motor capacity. Check the mechanical installation. If
the motor and drive are undersized, resize them for your application.

No

Check the motor and wiring connections for an open phase condition.

4. The drive will not reverse in local control -- No fault is displayed.

Has the drive been programmed to lockout reverse operation (Parameter 10 No Set Parameter 10 to 0.
set to 1)?

Yes

Contact your nearest AB representative for application assistance.

B-12

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

5. The drive will not ramptostop -- No fault is displayed.

No
Is Parameter 11 Stop Select set to ramptostop? Set Parameter 11 to 0.

Yes

Does Parameter 59 show an OU fault stored?


Yes The drive is tripping on overvoltage during decel. Refer to page B3.

No

Is the DC Hold Frequency set to high -- Is parameter 12 set to 00.50 Hz?


No Set Parameter 12 to 00.50 Hz.

Yes

Yes If Parameter 18 Decel Frequency Hold is set to 1 (On), an overhauling load


Is Parameter 18 Decel Frequency Hold on -- Does the motor have an
overhauling load? may cause the decel ramp to hold at one frequency for an extended period.
This may cause ramptostop commands to appear to be nonfunctional.

No

Contact your nearest AB representative for application assistance.

B-13

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

6. The drive will not accelerate to maximum speed -- No fault is displayed.

The maximum allowable drive output frequency will be determined by the No


Reset Parameters 3 and/or 15.
lowest programmed value of any of the following parameters:
• Parameter 3 Frequency Range
• Parameter 15 Maximum Frequency
• Parameter 51 Upper Frequency Clamp
• Parameter 53 Bias Frequency -- If Parameter 53 is Higher Than
Parameter 54
• Parameter 54 Gain Frequency -- If Parameter 54 is Higher Than
Parameter 53
Is Parameters 3 Frequency Range and/or 15 Maximum Frequency set high
enough to allow the drive to accelerate to maximum speed?

Yes

Is Parameter 51 Upper Frequency Clamp set to a value lower than the No


Reset Parameter 51 to maximum frequency.
required maximum frequency?

Yes

Yes
Is this an inverse speed follower application? To program the drive for an inverse speed follower application, set Parameter
53 to the maximum frequency required and Parameter 54 to the minimum
frequency required.
Yes

Is Parameter 53 Bias Frequency set to a higher value than Parameter 54 Gain Yes If an inverse speed follower is required, reprogram Parameter 53 to maximum
Frequency (standard setting for inverse speed follower applications)? frequency. If an inverse follower is not required, reprogram Parameters 53
and 54 as required.

No

Is Parameter 53 Bias Frequency set to a lower value than the required Yes Reset Parameter 53 to maximum Frequency.
maximum frequency?

No

Are Parameters 4245 programmed to exclude maximum frequency?


Yes Reprogram Parameters 42, 43 and/or 44 to a value below the maximum
frequency. Reprogram Parameter 45 to a bandwidth that will not include the
maximum frequency value.
No

Contact your nearest AB representative for application assistance.

B-14

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix B
Preventive Maintenance and
Troubleshooting Common Drive Problems

7. The drive will not decelerate to minimum speed -- No fault is displayed.

The priority used by the 1333 to limit minimum output frequency is: No
Reset Parameter 50 to minimum frequency.
1. For local speed control, use Parameter 50.
2 If an external potentiometer, 05VDC, 010VDC or 420mA signal is to
control drive speed, use the higher of the values set by Parameters 15
and 51.
Is Parameter 50 Lower Frequency Clamp set to a value higher than the
required minimum frequency?

Yes

Is 0 output speed required at a 0 external input signal? Yes


To program the drive for a directly proportional input signal, set Parameter 53
to the minimum frequency required and Parameter 54 to the maximum
frequency required.
No

Are Parameters 4244 Skip Frequencies 1, 2 and 3 and/or Parameter 45 Yes Reprogram Parameters 42, 43 and/or 44 to a value above minimum
programmed to exclude minimum frequency? frequency. Reprogram Parameter 45 to a bandwidth that will not include the
minimum frequency.

No

Contact your nearest AB representative for application assistance.

8. An input line fuse has blown -- No fault is displayed.

Are the drive input fuses sized in accordance with the values given in Chapter No
Replace with the correct fuses.
4 Installation and Wiring?

Yes

Are the drive input and output terminals wired as shown in Chapter 4 No
Wire as shown. Do the input fuses still blow?
Installation and Wiring.

Yes Yes

Contact your nearest AB representative for application assistance.

B-15

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

C
Appendix

Factory and Field Parameter Settings

Parameters Grouped by Function The following tables in Appendix C provide parameter data grouped by
function. The function groups listed, reference the same parameters as
grouped in Chapters 5 and 6 and Appendix B.

Factory and Field Parameter Settings -- Pages C2 and C3


The table on the left provides parameter units, min/max values, factory
settings and room to record field settings.

Coordinated Parameter Settings -- Pages C4 and C5


The table on the right graphically shows which of the remaining
parameters must be checked to provide coordinated control of the Bulletin
1333 for each parameter.

For each parameter (numbered 0 I – 62 ) in the first column, a ■ in the


remaining columns (numbered 01-62) will indicate parameters that should
be checked to provide coordinated drive control.

C-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix C
Factory and Field Parameter Settings

Factory and Field Parameter Settings -- Parameters 0128

Function Parameter Parameter Factory Field


Group Number Name Units Range Setting Setting
Accel and Decel 0I ACCEL TIME 1 Seconds 0000/1600 005.0
Settings 02 DECEL TIME 1 Seconds 0000/1600 005.0

VoltsperHertz Curve 03 FREQUENCY RANGE Code 50/60/FF 60


Settings 04 VOLTSPERHERTZ CURVE Code 0/1 0

DC Boost Setting 05 DC BOOST SELECT % of Output Voltage 00/40 00

Overload Protection 06 MOTOR DUTY Code 0/1/2/3 2


Settings 07 OVERLOAD CURRENT Amps 000.1/500.0 ❶

Local/Remote Control Enable 08 LOCAL/REMOTE CONTROL Code 0/1/2/3 0

Local/Remote Speed Enable 09 LOCAL/REMOTE FREQUENCY Code 0/1/2/3 0

Reverse Enable I0 REVERSE LOCKOUT Off/On 0/1 0

Stop Setting II STOP SELECT Code 0/1 0

DC Brake I2 DC HOLD FREQUENCY Hertz 00.50/60.00 00.50


Settings I3 DC HOLD TIME Seconds 000/10.0 000
I4 DC HOLD VOLTS Code 0/10 0

Max Speed I5 MAXIMUM FREQUENCY Hertz 50.00/400.0 60.00


Settings I6 BASE FREQUENCY Hertz 50.00/250.0 60.00

Accel and Decel Hold I7 ACCEL FREQUENCY HOLD Off/On 0/1 1
Enable I8 DECEL FREQUENCY HOLD Off/On 0/1 1

Preset Frequency and I9 FREQUENCY SELECT Code 0/1/2 0


Aux Accel/Decel Enable 20 TB15 PRESET/RESET Code 0/1 0

Aux Interlock Enable 2I AUXILIARY INTERLOCK Code 0/1 0

Drive Supplied Contact 22 CR1 SELECT Code 1/2/3 1


Settings 23 CR2 SELECT Code 0/1/2/3 0
24 CR1 FREQUENCY Hertz 00.50/400.0 00.50
25 CR2 FREQUENCY Hertz 00.50/400.0 00.50

Jog 26 JOG FREQUENCY Hertz 00.50/20.00 10.00


Settings 27 JOG ACCEL TIME Seconds 0000/1600 005.0
28 JOG DECEL TIME Seconds 0000/1600 005.0

❶ Factory setting is determined by the output current rating shown on the drive nameplate.

C-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix C
Factory and Field Parameter Settings

Coordinated Parameter Settings -- Parameters 0128

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62

0I
02
03
04
05
06
07
08
09
I0
II
I2
I3
I4
I5
I6
I7
I8
I9
20
2I
22
23
24
25
26
27
28

C-3

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix C
Factory and Field Parameter Settings

Factory and Field Parameter Settings -- Parameters 2962

Function Parameter Parameter Factory Field


Group Number Name Units Range Setting Setting
Preset Frequency 29 PRESET FREQUENCY 2 Hertz 00.50/400.0 20.00
Settings 30 PRESET FREQUENCY 3 Hertz 00.50/400.0 30.00
3I PRESET FREQUENCY 4 Hertz 00.50/400.0 40.00
32 PRESET FREQUENCY 5 Hertz 00.50/400.0 15.00
33 PRESET FREQUENCY 6 Hertz 00.50/400.0 25.00
34 PRESET FREQUENCY 7 Hertz 00.50/400.0 35.00
35 PRESET FREQUENCY 8 Hertz 00.50/400.0 45.00

Auxiliary Accel and Decel 36 ACCEL TIME 2 Seconds 000.1/1600 005.0


Settings 37 DECEL TIME 2 Seconds 000.1/1600 005.0
38 ACCEL TIME 3 Seconds 000.1/1600 005.0
39 DECEL TIME 3 Seconds 000.1/1600 005.0
40 ACCEL TIME 4 Seconds 000.1/1600 005.0
4I DECEL TIME 4 Seconds 000.1/1600 005.0

Skip Frequency 42 SKIP FREQUENCY 1 Hertz 0000/400.0 0000


Settings 43 SKIP FREQUENCY 2 Hertz 0000/400.0 0000
44 SKIP FREQUENCY 3 Hertz 0000/400.0 0000
45 SKIP FREQUENCY BAND Hertz 0/10 0

Current Limit Setting 46 CURRENT LIMIT Seconds 00/1.5 00

Auto Restart Settings 47 POWER LOSS RESTART Code 0/1/2/3 1


48 RIDETHRU RESTART Code 0/1/2 0
49 RESTART TIME SELECT Seconds 000.1/100.0 000.1

Lower and Upper 50 LOWER FREQUENCY CLAMP Hertz 00.50/400.0 00.50


Frequency Clamp Settings 5I UPPER FREQUENCY CLAMP Hertz 00.50/400.0 400.0

Bias and Gain 52 BIAS AND GAIN ENABLE Off/On 0/1 0


Settings 53 BIAS FREQUENCY Hertz 00.00/400.0 00.00
54 GAIN FREQUENCY Hertz 00.50/400.0 60.00

Output Meter 55 FREQUENCY OUTPUT (AMPS) % of Max Output Signal 075/125 100
Settings 56 FREQUENCY OUTPUT (VOLTS) % of Max Output Signal 075/125 100

Monitoring Mode 57 MONITOR DISPLAY SELECT Code 0/1/2 0


Settings 58 MOTOR POLE SELECT Units 2/4/6/8/10 4

Drive Fault Memory 59 FAULT BUFFER 0 Code -- -- --


60 FAULT BUFFER 1 Code -- -- --
6I FAULT BUFFER 2 Code -- -- --
62 FAULT BUFFER 3 Code -- -- --

C-4

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix C
Factory and Field Parameter Settings

Coordinated Parameter Settings -- Parameters 2962

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62

29
30
3I
32
33
34
35
36
37
38
39
40
4I
42
43
44
45
46
47
48
49
50
5I
52
53
54
55
56
57
58
59
60
6I
62

C-5

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

D
Appendix

Application Data

Important User Information


Because of the variety of uses for this equipment and because of the
differences between this solid state equipment and electromechanical
equipment, the user of and those responsible for applying this equipment
must satisfy themselves as to the acceptability of each application and use
of the equipment. In no event will Allen-Bradley Company be responsible
or legal for indirect or consequential damages resulting form the use or
application of this equipment.
The illustrations shown are intended solely to illustrate the accompanying
text. Because of the many variables and requirements associated with any
particular installation, the Allen-Bradley Company cannot assume
responsibility or liability for actual use based upon the illustrative uses and
applications.

Remote Manual and Remote Auto The Bulletin 1333 Series D may use the Directional Pushbuttons on the
Speed Reference Switching Local Control and Programming Panel or an external source as its speed
reference. The method of speed control that is used is determined by
parameter programming as explained in Chapter 5.
Four types of signals may be used as the external speed reference.
1. A 10kΩ, 2W potentiometer.
2. A 0-5V DC reference signal.
3. A 0-10V DC reference signal.
4. A 4-20 mA DC reference signal.

As explained in the Control and Signal Wiring section of Chapter 4, only


one of these signals should be connected to the Control and Signal Wiring
Terminal Block at any time.

There are times however, when a user may want the option of switching
between a remote analog speed reference and a remote manual speed
reference. The 1333 Series D normally will require reprogramming and
reconnection to accomplish this. This application describes an alternate
method of external speed selection. Users must satisfy themselves that this
alternate method is safe in their particular application and that its use
complies with applicable codes and standards.

D-1

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix D
Application Data

The 1333 Series D has the ability to allow a single external 10kΩ, 2W
manual speed potentiometer and one other reference signal to be connected
to the drive at the same time. The drive may be switched from the manual
potentiometer to the alternate reference signal by means of a selector
switch. As shown in the Control and Signal Wiring section of Chapter 4,
only one of these signals should be connected to the Control and Signal
Wiring Terminal Block at any time.

Shown below is a method of switching between an external speed pot and


one alternate reference signal.

Logic Logic
Common Common
1 2 3 4
or 1 2 3 4 5

05V/Speed Pot
420mA/Speed Pot
010V/Speed Pot

Drive Drive
End End
Shield Shield

Pot Pot
Pot Wiper Pot Pot Wiper Pot
High Low High Low

- + - +
4-20mA
05V
External or External
Speed Pot 0-10V Speed Pot

Earth Earth
Ground Ground

The Bulletin 1333 Series D must be programmed for external speed control
by setting Parameter 9 to:
• 1 if drive speed is to be controlled by a 0-5V DC signal or an external
speed pot.
• 2 if drive speed is to be controlled by a 0-10V DC signal or an external
speed pot.
• 3 if drive speed is to be controlled by a 4-20 mA DC signal or an
external speed pot.

When the selector switch in series with the potentiometer is open, the drive
will use the 0-5V DC, 0-10V DC, or 4-20 mA DC signal as the speed
reference.
When the selector switch is closed, the drive will use the potentiometer
signal as the speed reference.
If the selector switch is toggled while the drive is running, the drive will
accelerate or decelerate to the new speed reference at the programmed
accel or decel rate.
D-2

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix D
Application Data

Bulletin 1333 The Bulletin 1333 Adjustable Frequency Drive has the ability to let a
Heavy Duty Dynamic Braking connected motor generate braking torque. This ability however, is limited
to approximately 20% of the drive rated braking torque. The braking
torque can be increased by adding one or more Bulletin 1333 heavy duty
dynamic braking kits to the drive. Typically the braking torque can be
increased to 100% for 20 seconds at a duty cycle of 20%.

The following evaluation can help determine if heavy duty dynamic


braking may be required for your application.

Brake Specifications Braking Torque: 100% Torque for 20 Seconds (typical)


Duty Cycle: 20% (typical)
Input Power: Power from Drive DC Bus
Temperature: –10 to + 50°C (+14 to +122°F).
Humidity: 5 to 95% Non-Condensing
Atmosphere: No Corrosive Gas or Non-Hazardous Dust
Humidity: 3,300 Feet (1,000 Meters) Maximum without Derating
Enclosure Type: NEMA Type 1 (IP20)

How to Select a Brake To begin selection, the following application information must be obtained.
The nameplate horsepower of the motor HP.
The nameplate base speed of the motor N in RPM.
The speed profile of the motor N2
RPM

N1
RPM t2
t1

where: N1 = The motor’s minimum speed in RPM.


N2 = The motor’s maximum speed in RPM.
t1 = The motor’s cycle time in seconds.
t2 = The motor’s decel time in seconds.
The motor inertia, Motor Gear Load
Inertia Ratio Inertia
the nameplate gear reduction wk2M GR wk2L
ratio, and the load inertia. Input Output
RPM RPM

D-3

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix D
Application Data

Step 1 -- Determine the Rated Motor Torque

TQM = 5250 × HP HP = The nameplate horsepower of the motor


N = The nameplate base speed of the motor
N
TQM = 5250 × TQM = LBFT

Step 2 -- Determine the Total Inertia

wk2t = wk2M + [wk2L × (GR)2] wk2M = The motor inertia


wk2L = The load inertia
GR = The total reduction ratio Output RPM
Input RPM

wk2t = + [ ×( )2 ] wk2t = LBFT2

Step 3 -- Determine the Required Braking Torque

TQB = wk2t × [N2 - N1] wk2t = The total inertia


N2 = The motor's maximum speed
308 × t2
N1 = The motor's minimum speed
t2 = The motor's decel time

TQB = [ ] ×[ - ] TQB = LBFT


308 × [ ]

Step 4 -- Determine the Required Percent of Braking Torque

TQ% = TQB × 100 TQB = The required braking torque


TQM = The rated motor torque
TQM
TQ% = [ ] × 100 TQ% = %
[ ]

If TQ% is less than 20%, heavy duty dynamic braking is not required. The
inherent braking of the drive should be sufficient to handle the application
requirements.
If TQ% is 20% or more, a heavy duty braking kit is required. Continue to
Step 5.

D-4

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix D
Application Data

Step 5 -- Determine the Maximum Generated Braking Torque


Three factors limit the application of Heavy Duty Dynamic Braking.
The first is the brake assembly rating PT –– The peak power the brake
assembly can absorb at any instant regardless of the time limit.
The second is the average power that the break assembly can absorb
during one braking duty cycle –– PA.
The third is the duty cycle or the number of times the brake assembly can
be operated over a given period of time –– DC.

PM = TQB × N2 TQB = The required braking torque


N2 = The motor's maximum speed
7,000
PM = [ ] ×[ ] PM = kW
7,000

PM must be less than or equal to the Brake Assembly Rating listed in table 1.
If PM exceeds the PT value shown, the corresponding drive/brake
configuration will not be able to produce the braking torque required for
your application, and the drive will trip on an overvoltage fault. Increasing
the decel time t2, reducing the load inertia wk2L, or doing both will lower
TQB and PM.

table 1
Nominal To provide the maximum To provide a
Drive HP amount of braking torque use brake assembly rating (PT) of
3/4 (1) KA1 for a 208/230VAC Unit 1.2kW
(1) KB1 for a 460VAC Unit
1 (1) KA1 for a 208/230VAC Unit 1.2kW
(1) KB1 for a 460VAC Unit
2 (1) KA2 for a 208/230VAC Unit 2.4kW
(1) KB2 for a 460VAC Unit
3 (1) KA3 for a 208/230VAC Unit 6kW
(1) KB3 for a 460VAC Unit
5 (1) KA3 for a 208/230VAC Unit 6kW
(1) KB3 for a 460VAC Unit
71/2 (1) KA4 12kW
10 (1) KA4 12kW
15 (1) KA5 24kW
20 (1) KA5 24kW

D-5

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix D
Application Data

Step 6 -- Determine the Average Power Generated in One Cycle

PA = TQB × [N1 + N2] TQB = The required braking torque


N1 = The motor's minimum speed
14,000 N2 = The motor's maximum speed

PA = [ ] ×[ + ] PA = kW
14,000

Step 7 -- Determine the Ratio of the Average Power to the Brake


Assembly Rating

P% = PA PA = The average power generated in one cycle


PT = The brake assembly rating from table 1
PT
P% = [ ] P% = %
[ ]

Find the intersection of P% and the motor’s decel time t2 in the chart below.
If the point of intersection is below the curve, the average power of one
cycle is within the brake’s limits. If the point is above the curve, the
average power is beyond the brake’s limits but may be reduced by
increasing the motor’s decel time t2, reducing the load inertia wk2L, or
doing both.
P% 100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
0 10 20 30 40 50 60 70 80 90 100

Decel Time t2 in Seconds

D-6

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix D
Application Data

Step 8 -- Determine if the Duty Cycle is within the Brake's Capability

DC = t2 × 100 T1 = The motor's cycle time


T2 = The motor's decel time
t1
DC = [ ] × 100 DC = %
[ ]

Find the intersection of P% and the motor’s decel time DC in the chart
below. If the point of intersection is below the curve, the duty cycle is
within the brake’s limits. If the point is above the curve, the duty cycle is
beyond the brake’s limits but may be modified by increasing the motor’s
cycle time t1.

P% 100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
0 5 10 15 20 25 30 35 40 45 50

Duty Cycle DC in %

D-7

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Appendix D
Application Data

Notes

D-8

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

We Want Our Manuals to be the Best!


You can help! Our manuals must meet the needs of you, the user. This is your opportunity to make sure they do just
that. By filling out this form you can help us provide the most useful, thorough, and accurate manuals available. Please
take a few minutes to tell us what you think. Then mail this form, FAX it, or send comments via E-Mail.
FAX: to your local Allen-Bradley Sales Office or 414/242-8201
E-Mail: via Internet to “[email protected]

PUBLICATION NAME

PUBLICATION NUMBER, DATE AND PART NUMBER (IF PRESENT)

3 CHECK THE FUNCTION THAT MOST CLEARLY DESCRIBES YOUR JOB.


o SUGGEST / RESPONSIBLE FOR THE PURCHASE OF EQUIPMENT
o MAINTAIN / OPERATE PROGRAMMABLE MACHINERY
o DESIGN / IMPLEMENT ELECTRICAL SYSTEMS o TRAIN / EDUCATE MACHINE USERS
o SUPERVISE FLOOR OPERATIONS

3 WHAT LEVEL OF EXPERIENCE DO YOU HAVE WITH EACH OF THE FOLLOWING PRODUCTS?
NONE LITTLE MODERATE EXTENSIVE
PROGRAMMABLE CONTROL o o o o
AC / DC DRIVES o o o o
PERSONAL COMPUTERS o o o o
NC / CNC CONTROLS o o o o
DATA COMMUNICATIONS / LAN o o o o

3 RATE THE OVERALL QUALITY OF THIS MANUAL BY CIRCLING YOUR RESPONSE BELOW. (1) = POOR (5) = EX-
CELLENT
HELPFULNESS OF INDEX / TABLE OF CONTENTS 1 2 3 4 5
CLARITY 1 2 3 4 5
EASE OF USE 1 2 3 4 5
ACCURACY AND COMPLETENESS 1 2 3 4 5
QUALITY COMPARED TO OTHER COMPANIES’ MANUALS 1 2 3 4 5
QUALITY COMPARED TO OTHER ALLEN-BRADLEY MANUALS 1 2 3 4
5

3 WHAT DID YOU LIKE MOST ABOUT THIS MANUAL?

3 WHAT DID YOU LIKE LEAST ABOUT THIS MANUAL?

3 PLEASE LIST ANY ERRORS YOU FOUND IN THIS MANUAL (REFERENCE PAGE, TABLE, OR FIGURE NUMBERS).

3 DO YOU HAVE ANY ADDITIONAL COMMENTS?


CUT ALONG DOTTED LINE

3 COMPLETE THE FOLLOWING.

NAME COMPANY

TITLE DEPARTMENT

STREET CITY STATE ZIP

[email protected] [email protected] [email protected]


TELEPHONE DATE
IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

FOLD HERE

FOLD HERE

NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES

BUSINESS REPLY MAIL


FIRST CLASS PERMIT NO. 413 MEQUON, WI

POSTAGE WILL BE PAID BY ADDRESSEE

ALLEN-BRADLEY
Attn: Marketing Communications
P.O. Box 760
Mequon, WI 53092-9907

[email protected] [email protected] [email protected]


IF YOU HAVE PROBLEM CALL PRADIPGIRI GOSWAMI @ +91 942 775 5191 FOR SOLUTION AND SUPPLY

Publication 1333-5.2  July 1994 P/N 152783


Supersedes February 1994 and 1333-5.2DU1DU2 April 1994 Copyright 1994, AllenBradley Company, Inc. Printed in USA

[email protected] [email protected] [email protected]

You might also like