(TD) 2 Technical Data Technical Data P391

4 TECHNICAL DATA P391

4.1 Mechanical Specifications

4.1.1 Design
80TE case. Mounting options are, wall mounting, front of panel flush mounting, or 19”
rack mounted (ordering options)

4.1.2 Enclosure Protection


Per IEC 60529: 1992
IP 20 (Safety) Protection for the case with the terminal
Rack and Panel Mounting Options:
safety cover fitted.
IP 20 (Safety) Protection for the P391 unit with the terminal
Wall Mounting Option:
safety cover fitted.

4.1.3 Weight
P391 (80TE): 5kg

4.2 Terminals

4.2.1 AC Voltage Measuring Inputs


Located on general purpose (grey) terminal blocks:
Threaded M4 terminals, for insulated ring crimped connectors.

4.2.2 Protective Conductor (Earth) Terminal


Two rear stud connections, threaded M4.
Must be earthed (grounded) for safety, using the protective (earth) conductor, of minimum
wire size 2.5 mm2.

4.2.3 Current Loop Output


Located on general purpose (grey) terminal blocks:
Threaded M4 terminals, for insulated ring crimped connectors.

4.3 Ratings

4.3.1 Low Frequency Measuring Inputs


Nominal frequency: 0.25, 0.5, 1 Hz (settable with an internal jumper link)

4.3.2 DC Field Voltage Inputs


1200 V dc maximum

Page (TD) 2-18 P34x/EN TD/J96


Technical Data P391 (TD) 2 Technical Data

4.4 Power Supply

4.4.1 Auxiliary Voltage (Vx)


60-250 V dc, or 100-230 V ac (rms) 50/60 Hz

4.4.2 Operating Range


48-300 V dc, or 85-253 V ac (rms) 50/60 Hz
With a tolerable ac ripple of up to 12% for a dc supply, per IEC 60255-11: 1979.

4.4.3 Nominal Burden


Auxiliary Supply Input burden: 11 W or 24 VA.

4.4.4 Power Supply Interruption


The relay will withstand a 20 ms interruption in the DC auxiliary
Per IEC 60255-11: 1979
supply, without De-energizing.
The relay will withstand a 20 ms interruption in an AC auxiliary
Per IEC 61000-4-11: 2004
supply, without de-energizing.

4.5 Output Contacts

4.5.1 Watchdog Contacts


Non-programmable contacts for relay healthy/relay fail indication:
Breaking capacity: DC: 30 W resistive
DC: 15 W inductive (L/R = 40 ms)
AC: 375 VA inductive (cos I = 0.7)
Loaded contact: 10 000 operations Minimum,
Unloaded contact: 10 000 operations Minimum.

4.6 Environmental Conditions

4.6.1 Ambient Temperature Range


Per IEC 60068-2-1: 2007: cold; IEC 60068-2-2: 2007: dry heat
Operating temperature range: -25°C to +55°C (or -13°F to +131°F)
Storage and transit: -25°C to +70°C (or -13°F to +158°F)

4.6.2 Ambient Humidity Range


Per IEC 60068-2-78: 2001 56 days at 93% relative humidity and +40 °C

4.7 Type Tests

4.7.1 Insulation
Per IEC 60255-27: 2005:
Insulation resistance > 100 M: at 500 Vdc
(Using only electronic/brushless insulation tester).

P34x/EN TD/J96 Page (TD) 2-19


(TD) 2 Technical Data Technical Data P391

4.7.2 Creepage Distances and Clearances


Per IEC 60664-1: 2007
Pollution degree 2,
Impulse 9.6 kVp between injection resistor inputs and protective (case earth) conductor
terminal.
Minimum of 10.5 mm clearance and 12 mm creepage distance.

4.7.3 High Voltage (Dielectric) Withstand


(i) Per IEC 60255-27: 2005, 2 kV rms ac, 1 minute:
Between all independent circuits.
Between independent circuits and protective (case earth) conductor terminal.
1 kV rms ac for 1 minute, across open watchdog contacts.
(ii) Per ANSI/IEEE C37.90: 2005
1 kV rms ac for 1 minute across open watchdog contacts.
(iii) Per 60664-1: 2007
5.8 kV rms 1 minute between injection resistor inputs and protective (case earth)
conductor terminal.

4.7.4 Impulse Voltage Withstand Test


Per IEC 60255-27 2005
Front time: 1.2 μs
Time to half-value: 50 μs,
Peak value: 5 kV, 0.5 J
Between all independent circuits.
Between all independent circuits and protective (case earth) conductor terminal.
Between the terminals of independent circuits.
Normally open contacts of output relays excepted.
IEC 60664-1: 2007
Impulse 9.6 kV between injection resistor inputs and protective (case earth) conductor terminal

4.8 ElectroMagnetic Compatibility (EMC)

4.8.1 1 MHz Burst High Frequency Disturbance Test


Per IEC 60255-22-1: 2005, Class III,
Common-mode test voltage: 2.5 kV,
Differential test voltage: 1.0 kV,
Test duration: 2 s, Source impedance: 200 :

4.8.2 100 kHz Damped Oscillatory Test


Per EN61000-4-18: 2007: Level 3
Common mode test voltage: 2.5 kV
Differential mode test voltage: 1 kV

4.8.3 Electrical Fast Transient or Burst Requirements


Per IEC 60255-22-4: 2002 and EN61000-4-4:2004. Test severity Class III and IV:
Amplitude: 2 kV, burst frequency 5 kHz (Class III),

Page (TD) 2-20 P34x/EN TD/J96


Technical Data P391 (TD) 2 Technical Data

4 kV, burst frequency 2.5 kHz (Class IV). Applied directly to auxiliary supply,
Amplitude:
and applied to all other inputs. (EIA(RS)232 ports excepted).
Amplitude: 4 kV, burst frequency 5 kHz (Class IV) applied directly to auxiliary.

4.8.4 Surge Withstand Capability


Per IEEE/ANSI C37.90.1: 2002
4 kV fast transient and 2.5 kV oscillatory applied directly across each output contact, optically
isolated input, and power supply circuit.
4 kV fast transient and 2.5 kV oscillatory applied common mode to communications, IRIG-B.

4.8.5 Surge Immunity Test


(EIA(RS)232 ports excepted).
Per EN 61000-4-5: 2006 Level 4, EN 60255-22-5: 2002
Time to half-value: 1.2 / 50 μs,
Amplitude: 4 kV between all groups and protective (earth) conductor terminal,
Amplitude: 2 kV between terminals of each group.
Level 3: 1 kV between terminals of injection resistor inputs

4.8.6 Immunity to Radiated Electromagnetic Energy


Per IEC 60255-22-3: 2007, Class III: (EN61000-4-3: 2006, Level 3)
Test field strength, frequency
10 V/m,
band 80 to 1000 MHz:
Test using AM: 1 kHz / 80%,
Spot tests at 80, 160, 450, 900 MHz
80 MHz to 1000 MHz, 1 kHz 80% am and am pulsed
Per IEEE/ANSI C37.90.2: 2004:
modulated. Field strength of 35 V/m.

4.8.7 Radiated Immunity from Digital Communications


Test field strength, frequency band 800 to 960 MHz, and 1.4 to
Per EN61000-4-3: 2002, Level 4:
2.0 GHz: 30 V/m,
Test using AM: 1 kHz/80%.

4.8.8 Radiated Immunity from Digital Radio Telephones


Per IEC61000-4-3: 2002: 10 V/m, 900 MHz and 1.89 GHz.

4.8.9 Immunity to Conducted Disturbances Induced by Radio Frequency Fields


Per IEC 61000-4-6: 2007, Level 3, IEC60255-22-6: 2001
Disturbing test voltage: 10 V.

4.8.10 Power Frequency Magnetic Field Immunity


Per IEC 61000-4-8: 1994, Level 5, 100 A/m applied continuously,
1000 A/m applied for 3 s.
Per IEC 61000-4-9: 1993, Level 5, 1000 A/m applied in all planes.
100 A/m applied in all planes at 100 kHz/1MHz with a burst
Per IEC 61000-4-10: 1993, Level 5,
duration of 2 s.

P34x/EN TD/J96 Page (TD) 2-21


(TD) 2 Technical Data Technical Data P391

4.8.11 Conducted Emissions


Per EN 55022: 1998 Class A: 0.15 - 0.5 MHz, 79 dBPV (quasi peak) 66 dBPV (average)
0.5 - 30 MHz, 73 dBPV (quasi peak) 60 dBPV (average).

4.8.12 Radiated Emissions


Per EN 55022: 1998 Class A: 30 - 230 MHz, 40 dBPV/m at 10 m measurement distance
230 - 1 GHz, 47 dBPV/m at 10 m measurement distance.

4.9 EU Directives

4.9.1 EMC Compliance


Per 2004/108/EC: Compliance to the European Commission Directive on EMC is
demonstrated using a Technical File route. Product Specific Standards were used to
establish conformity:
EN 50263: 2000

4.9.2 Product Safety


Per 2006/95/EC: Compliance with European Commission Low Voltage Directive (LVD).
A Product Specific Standard was used to establish conformity:

EN 60255-27: 2005

4.10 Mechanical Robustness

4.10.1 Vibration Test


Per IEC 60255-21-1: 1996: Response Class 2 and Endurance Class 2

4.10.2 Shock and Bump


Per IEC 60255-21-2: 1996: Shock response Class 2
Shock withstand Class 1
Bump Class 1

4.10.3 Seismic Test


Per IEC 60255-21-3: 1995: Class 2

Page (TD) 2-22 P34x/EN TD/J96


P391 Rotor Earth Fault Unit (REFU) Mounting ,1 ,QVWDOODWLRQ


 352725($57+)$8/781,7 5()8 02817,1*


The P391 unit is dispatched either individually or as part of a panel/rack/wall assembly.
Sufficient airflow must be maintained around the P391 at all times. For this reason it is
essential that a minimum clearance from other equipment of 2U (89 mm) above and 1U
(44.5 mm) below the P391 is maintained.
The Rotor Earth Fault Unit (REFU) is normally supplied with an outline diagram showing
the dimensions for panel cut-outs and hole centers. This information can also be found in
the product publication.

 5DFN0RXQWLQJ
The P391 unit can be rack mounted into a rack with M6 x16 slotted pan head screws
provided.

 3DQHO0RXQWLQJ
The P391 unit can be flush mounted into panels using M4 x 8 Pan head Taptite self-
tapping screws provided. These fastenings are available in packs of 5 (Schneider
Electric part number ZA0005 104).
Alternatively tapped holes can be used if the panel has a minimum thickness of 2.5 mm.

 :DOO0RXQWLQJ
The P391 unit can be wall mounted using M6 anchor bolts or similar (not provided).

P34x/EN IN/J96 Page (IN) 15-23


,1 ,QVWDOODWLRQ P391 Rotor Earth Fault Unit (REFU) Mounting

 352725($57+)$8/781,7 5()8 02817,1*


This section serves as a guide to selecting the appropriate cable and connector type for
each terminal on the P391 unit.

&DXWLRQ <RXPXVWEHIDPLOLDUZLWKDOOVDIHW\VWDWHPHQWVOLVWHGLQ
WKH&RPPLVVLRQLQJFKDSWHUDQGWKH6DIHW\,QIRUPDWLRQ
VHFWLRQ6)7</0* RUODWHULVVXH EHIRUHXQGHUWDNLQJ
DQ\ZRUNRQWKH3

&DXWLRQ 8QGHUQRFLUFXPVWDQFHVVKRXOGWKHKLJKYROWDJH'&URWRU
ZLQGLQJVXSSO\EHFRQQHFWHGYLD00/*RU3WHVW
EORFNV%RWK00/*DQG3WHVWEORFNVDUHQRWUDWHGIRU
FRQWLQXRXVZRUNLQJYROWDJHVJUHDWHUWKDQ9UPV
7KHVHWHVWEORFNVDUHQRWGHVLJQHGWRZLWKVWDQGWKH
LQGXFWLYH(0)YROWDJHVZKLFKZLOOEHH[SHULHQFHGRQ
GLVFRQQHFWLRQRUGHHQHUJL]DWLRQRIWKH'&URWRUZLQGLQJ
VXSSO\

 0HGLXP'XW\7HUPLQDO%ORFN&RQQHFWLRQV
Loose relays are supplied with sufficient M4 screws for making connections to the rear
mounted terminal blocks using ring terminals, with a recommended maximum of two ring
terminals per relay terminal.
If required, Schneider Electric can supply M4 90° crimp ring terminals in three different
sizes depending on wire size (see Table 5). Each type is available in bags of 100.
3DUWQXPEHU :LUHVL]H ,QVXODWLRQFRORU
2
ZB9124 901 0.25 – 1.65 mm (22 - 16 AWG) Red
ZB9124 900 1.04 – 2.63 mm2 (16 - 14 AWG) Blue
2
ZB9124 904 2.53 – 6.64 mm (12 - 10 AWG) Uninsulated*

*Note To maintain the terminal block insulation requirements for safety, an


insulating sleeve should be fitted over the ring terminal after crimping.

7DEOH0ƒFULPSULQJWHUPLQDOV
The following minimum wire sizes are recommended:
Auxiliary Supply, Vx 1.5 mm2
Rotor winding to P391 1.0 mm2
Other Circuits 1.0 mm2

&DXWLRQ :LULQJEHWZHHQWKH'&URWRUZLQGLQJDQGWKH3VKDOO
EHVXLWDEO\UDWHGWRZLWKVWDQGDWOHDVWWZLFHWKHURWRU
ZLQGLQJVXSSO\YROWDJHWRHDUWK7KLVLVWRHQVXUHWKDW
WKHZLULQJLQVXODWLRQFDQZLWKVWDQGWKHLQGXFWLYH(OHFWUR
0RWLYH)RUFH (0) YROWDJHZKLFKZLOOEHH[SHULHQFHGRQ
GLVFRQQHFWLRQRUGHHQHUJL]DWLRQRIWKH'&URWRUZLQGLQJ
VXSSO\

Due to the limitations of the ring terminal, the maximum wire size that can be used for any
of the medium terminals is 6.0 mm2 using ring terminals that are not pre-insulated
(protective conductor terminal (PCT) only). All P391 terminals, except PCT shall be pre-

Page (IN) 15-24 P34x/EN IN/J96


P391 Rotor Earth Fault Unit (REFU) Mounting ,1 ,QVWDOODWLRQ


insulated ring terminals, the maximum wire size that can be used is reduced to 2.63 mm2
per ring terminal. If a larger wire size is required, two wires can be used in parallel, each
terminated in a separate pre-insulated ring terminal.
Wiring between the DC rotor winding and the P391 shall be suitably rated to withstand at
least twice the rotor winding supply voltage to earth. The wire used for other P391
connections to the medium duty terminal blocks should have a minimum voltage rating of
300 Vrms.
The dielectric withstand of P391 injection resistor connections (A16, B16, A8, B8) to earth
is 5.8 kV rms, 1 minute.
It is recommended that the auxiliary supply wiring should be protected by a High Rupture
Capacity (HRC) fuse of type NIT or TIA, rated between 2 A and 16 A. Other circuits
should be appropriately fused to protect the wire used.

 &XUUHQW/RRS,QSXW2XWSXW &/,2 &RQQHFWLRQV LIDSSOLFDEOH 


A current loop output is available on the P391 relay, the connections are made using
screw clamp connectors, on the rear of the relay which can accept wire sizes between
0.1 mm2 and 1.5 mm2. It is recommended that connections between the relay and the
current loop inputs and outputs are made using a screened cable, connection of the
screen is discussed in section 6.4 - RTD Connections (if applicable). The wire should
have a minimum voltage rating of 300 Vrms.

 3URWHFWLYH&RQGXFWRU (DUWK &RQQHFWLRQ 3&7 


Every relay must be connected to the local earth bar using the M4 earth studs in the
bottom left hand corner of the relay case. The minimum recommended wire size is 2.5
mm2 and should have a ring terminal at the relay end. Due to the limitations of the ring
terminal, the maximum wire size that can be used for the PCT is 6.0 mm2 per wire. If a
greater cross-sectional area is required, two parallel connected wires, each terminated in
a separate ring terminal at the relay, or a metal earth bar could be used.
As DC currents of up to 29 mA will appear in the earth circuit under rotor earth fault
conditions, the P391 shall be permanently connected to the local earth via the protective
conductor terminal provided.

Note To prevent any possibility of electrolytic action between brass or copper


earth conductors and the rear panel of the relay, precautions should be
taken to isolate them from one another. This could be achieved in a
number of ways, including placing a nickel-plated or insulating washer
between the conductor and the relay case, or using tinned ring terminals.

P34x/EN IN/J96 Page (IN) 15-25




Page (IN) 15-26


427
4
84.0 142.5
B B A B
B
,1 ,QVWDOODWLRQ

407
1 2
6 ‘A’ HOLES
WIRING ENTRY THROUGH Dia 3.4 FIT M4
GROMMETS TOP & BOTTOM TAPT ITE
SCREWS
SEE NOTE 1

07 1
26 1
25.9 ‘B’ HOLES
Dia 4.4
17 18
B A B A B A B ‘B’ HOLES ARE
63.5 100 100 100 CLEARANCE FOR
FRONT COVER TERMINAL
F LUSH MOUNTING PANEL CUT OUT DETAIL FITTINGS BLOCK
DETAIL
95 162 38.5

MiCOM P39 1
ROT OR EARTH
PERFORATED FAULT DET ECT OR
TOP & BOTTOM
(SEE NOTE 3)

TOP VIEW
NOTES
1. MOUNTING SCREWS: M4 x 8 PAN HEAD TAPTITE SCREWS OR *M4 x 10 SLOTTED CH HED SCREWS WITH
NUTS & WASHERS ARE PROVIDED, (PRE PACK ZA0005106 – 2 PACKS)
* REQUIRES M4 CLEARANCE HOLE IN PANEL DIA 4.5/4.4.
ALT ERNATIVELY TAPPED HOLES CAN BE USED IF PANEL IS MINIMUM 2.5 THICK.
3&$6(',0(16,216

2. TERMINAL SCREWS: M4 x 7 BRASS CHEESE HEAD SCREWS WITH LOCK WASHERS PROVIDED.
(PRE-PACK ZA0005060 – 1 PACK) EARTH BLOCK ‘A’ BLOCK ‘B’ BLOCK ‘C’
CONNECTION M4 REAR TERMINAL BLOCK POSITIONS

)LJXUH3RXWOLQHDQGSDQHOPRXQWLQJGHWDLOV 7(FDVH 
3. TO ACHIEVE ADEQUATE VENTILATION A MINIMUM AIR GAP OF 90mm (2U NOM) BETWEEN THE TOP OF
THE CASE & 45MM (1U NOM) AT THE BOTTOM OF THE CASE IS REQUIRED TO ANY ADJACENT EQUIPMENT
430
PANEL WIRING ENTRY

MiCOM P391 REMOVABLE TERMINAL


ROTO R EARTH F AULT DETECTOR
COVER T O BE RE-
177.6
ASSEMBLED AFTER
4U NOM
WIRING

FRONT VIEW SIDE VIEW WIRING ENTRY


4
U = 44.45
OUTLINE FOR GN0461001

P4658ENe
P391 Case Dimensions

P34x/EN IN/J96


407

465 1.6
WIRING ENTRY THROUGH

P34x/EN IN/J96
450 MIN
GROMMETS TOP & BOTTOM

10.6
NOM 2U & 1U MINIMUM HEIGHT BLANK PANEL REQUIRED
P391 Case Dimensions

HEIGHT ABOVE AND BELOW P391 AS SHOWN TO PROVIDE


2U
AN AIR GAP FOR VENTILATION.

249

DETAIL A
SCALE 2 : 1

NOM
HEIGHT
PERFORATIONS 1U
TOP & BOTTOM
(SEE NOTE 3)
483 (19") RACK DETAIL
3 TO IEC 297
TOP VIEW
NOTES
1. MOUNTING SCREWS : M6 x 16 PAN HD SCREWS AND CAGE NUTS (NOT PROVIDED) REFER TO SHEET 1 FOR
DETAILS OF REAR TERMINAL
2. TERMINAL SCREWS : M4 x 7 BRASS CHEESE HEAD SCREWS WITH LOCK WASHERS PROVIDED. COVER AND POSITION OF
(PRE PACK ZA0005060 - 1 PACK) TERMINAL BLOCKS

)LJXUH3RXWOLQHDQGUDFNPRXQWLQJGHWDLOV 7(FDVH 
3. TO ACHIEVE ADEQUATE VENTILATION A MINIMUM AIR GAP OF 90mm (2U NOM) BETWEEN THE
TOP OF THE CASE & 45mm (1U NOM) AT THE BOTTOM OF THE CASE IS REQUIRED TO ANY
ADJACENT EQUIPMENT.
483
9 465

101.6 177.6
4 U NOM

57.1
44.5
ISOMETRIC VIEW

38

FRONT VIEW U=44.45

P4657ENb
OUTLINE FOR GN0461002
,1 ,QVWDOODWLRQ

Page (IN) 15-27


407

Page (IN) 15-28


WIRIN G ENTRY T HROUG H
GRO MM ETS T OP & BOT TOM

WIRING ENTRY
,1 ,QVWDOODWLRQ

254
'A

266
'

WIRING ENTRY
ISOM ETRI C VIEW

T ERMIN AL COVER REMOVED VI EW ON ARROW 'A'


BEFO RE WIRING AND MUST
BE RE-F IT TED ON
COM PLET ION O F WIRI NG M OUNT ING ARRANGEM ENT

TO P & BOTT OM REFER T O SHEET 1 F OR DET AI LS


NO TES PERFO RAT ED OF REAR TERM INAL CO VER AND
1 . MO UNTI NG SCREWS : M 6 ANCHOR BO LT OR SIM ILAR ( NOT PROVIDED). (SEE NOT E 3) POSIT IONS OF T ERM INAL BL OCKS

2. TERM INAL SCREWS : M4 x 7 BRASS CHEESE HEAD SCREWS WIT H LO CK WASHERS PROVIDED.
( PRE PACK Z A0 005 06 0 - 1 PACK)

3. TO ACHIEVE ADEQ UAT E VENTIL ATIO N A MIN IMUM AIR GAP O F 9 0mm (2 U NOM ) BET WEEN T HE T OP OF
TH E C ASE & 45 mm (1 U NOM ) AT THE BO TT OM OF THE CASE IS REQUIRED TO ANY ADJACENT EQUIPMENT .

)LJXUH3RXWOLQHDQGZDOOPRXQWLQJGHWDLOV 7(FDVH 
430

278

232
218
9. 0
7 .0

6 2.5 0 6 2.5 0 U = 44 .45


B DETAIL B
SCALE 2 : 1
P391 Case Dimensions

P34x/EN IN/J96