Technical Data Electric Fire

Modbus Communication Pump Controllers

MARKIII+ Electric Fire Pump Controllers


TECHNICAL DATA - MODBUS COMMUNICATION
FOR ELECTRIC FIRE PUMP CONTROLLER
To modify IP and SubNet Mask: Go to Config / Advanced / Network Config. Check the "Manual" box. Enter the desired IP address and SubNet Mask. Press Apply. The Modbus node
Generals Characteristics adress is 1.
Connection Type Shielded female connector RJ45 BINARY 16 boolean (1 = TRUE, 0 = FALSE)
10.0.1.0 – 10.255.255.255 (Class A private)
16 bits representing a number. The result refers to a list
Possible IP adress 172.16.0.0 – 172.31.255.255 (Class B private) DIGITAL VALUES
of values
192.168.0.0 – 192.168.255.255 (Class C private)
Frame Format TCP/IP
16 bits representing a number. Analog signals values
ANALOG VALUES are multiply by 10 for communication purpose, unless
otherwise specified.

Controller Info

WORDS 40001-40040 Serial Number WORDS 40041-40080 Model


String String

WORDS 40081-40120 Package Name WORDS 40121-40160 Software Version


String String

WORD 40161 Nominal Voltage WORD 40162 Nominal Current


ANALOG VALUES (V) ANALOG VALUES (A)

WORD 40163 Nominal Frequency WORD 40164 Custom Locked Rotor Current
BINARY (0 = 60Hz, 1 = 50Hz) ANALOG VALUES (A)

Alarms Activation

Alarms Activation 1 0 Normal Phase Reversal Alarms Activation 2 0 Faulty Pressure Transducer
BINARY 1 Phase Loss L1 BINARY 1 Overpressure
2 Phase Loss L2 2 Underpressure
WORD 41001 3 Phase Loss L3 WORD 41002 3 Low Suction Pressure (option)
4 Lock Rotor Current 4 Flow Start (option)
5 Fail to Start 5 NA
6 NA 6 NA
7 Power Loss 7 NA
8 Service Required 8 I/O Electric Board Communication Loss
9 Undercurrent 9 NA
10 Overcurrent 10 Weekly Test Required (option)
11 Undervoltage 11 NA
12 Overvoltage 12 Low Ambient Temperature (Internal Sensor)
13 Phase Unbalanced 13 High Ambient Temperature (Internal Sensor)
14 Weekly Test Cut-In not reached 14 Control Voltage Not Healthy
15 Weekly Test Check Solenoid Valve 15 Soft Starter Fault (Soft Sarter only)

Alarms Activation 3 0 Motor Trouble Alarms Activation 4 0 High Water Level (option)
BINARY 1 Pump Room Alarm BINARY 1 Main Relief Valve Open (option)
2 Motor Run (option) 2 High Motor Temperature (option)
WORD 41003 3 CANBUS Communication System Failure WORD 41004 3 High Motor Vibration (option)
4 Pump On Demand 4 Flow Meter On (option)
5 Invalid Cut-In 5 User Alarm 1 (option)
6 Test Mode 6 User Alarm 2 (option)
7 Low Zone Not Running (option) 7 User Alarm 3 (option)
8 I/O Expansion 1 Communication Loss (option) 8 User Alarm 4 (option)
9 I/O Expansion 2 Communication Loss (option) 9 User Alarm 5 (option)
10 I/O Expansion 3 Communication Loss (option) 10 User Alarm 6 (option)
11 I/O Expansion 4 Communication Loss (option) 11 User Alarm 7 (option)
12 Ground Fault 12 User Alarm 8 (option)
13 Low Water Level 13 User Alarm 9 (option)
14 Low Spare Temperature (option) 14 User Alarm 10 (option)
15 Water Reservoir Empty (option) 15 User Alarm 11 (option)

Alarms Activation 5 0 User Alarm 12 (option) Alarms Activation 6 0 Bypass Contactor Module Failure (option)
BINARY 1 User Alarm 13 (option) BINARY 1 I/O Expansion 5 Communication Loss (option)
2 User Alarm 14 (option) 2 I/O Expansion 6 Communication Loss (option)
WORD 41005 3 User Alarm 15 (option) WORD 41006 3 I/O Expansion 7 Communication Loss (option)
4 User Alarm 16 (option) 4 I/O Expansion 8 Communication Loss (option)
5 User Alarm 17 (option) 5 Low Foam Level (option)
6 User Alarm 18 (option) 6 Low Foam Pressure (option)
7 User Alarm 19 (option) 7 Dry Run From Flow Switch (option)
8 User Alarm 20 (option) 8 Jockey Pump Trouble (option)
9 Bell Silenced (option) 9 Jockey Pump Running (option)
10 NA 10 NA
11 NA 11 VFD Fault (option)
12 NA 12 VFD Bypass Mode (option)
13 NA 13 VFD Constant Speed Mode (option)
14 NA 14 VFD Underpressure (option)
15 Main Contactor Module Failure (option) 15 VFD Not Ready (option)

Alarms Activation 7 0 VFD Invalid Setpoint (option)


BINARY 1 VFD Reforming Required (option)
2 NA
WORD 41007 3 NA
4 NA
5 NA
6 NA
7 NA
8 NA
9 NA
10 NA
11 NA
12 NA
13 NA
14 NA
15 NA
WORDS 40201-40300

WORD 40201 0 MODBUS Remote Manual Start


BINARY 1 MODBUS Automatic Start

NFPA Registers

WORD 42001 Line Voltage L12 WORD 42002 Line Voltage L23
ANALOG VALUES (V) ANALOG VALUES (V)

WORD 42003 Line Voltage L31 WORD 42004 Current L1


ANALOG VALUES (V) ANALOG VALUES (A)

WORD 42005 Current L2 WORD 42006 Current L3


ANALOG VALUES (A) ANALOG VALUES (A)

WORD 42007 System Pressure WORD 42008 Suction Pressure


ANALOG VALUES (10X) (PSI) ANALOG VALUES (10X) (PSI)

WORD 42009 NA WORD 42010 NA

WORD 42011 NA

NFPA Alarms 1 0 Minimum run delay timing high NFPA Alarms 2 0 Pressure start demand high
BINARY 1 NA BINARY 1 Remote start demand high
2 High zone delay timing high (option) 2 Deluge start demand high (option)
WORD 42012 3 Sequence delay timing high (option) WORD 42013 3 Weekly test start demand high
4 Load shed active high (option) 4 Local start PB demand high
5 NA 5 Manual operator start demand high
6 Low suction alarm high (option) 6 Audible alarm high
7 Low suction shutdown active high (option) 7 NA
8 System over pressure alarm high (option) 8 NA
9 Restart delay timing high 9 Load shedding delay timing high (option)
10 Weekly test demand active high 10 NA
11 Failure to start alarm high 11 NA
12 Lockout active high (option) 12 Pressure transducer fault high
13 VFD ready high (option) 13 NA
14 VFD forward command active high (option) 14 NA
15 NA 15 Controller in bypass mode (soft start/VFD only high)

NFPA Alarms 3 0 Timed trip timing high NFPA Alarms 4 0 Pump trouble #1 input high
BINARY 1 Motor running high BINARY 1 Pump trouble #2 input high
2 Motor overload alarm high 2 Pump trouble #3 input high
WORD 42014 3 NA WORD 42015 3 Pump trouble #4 input high
4 Phase reversal alarm high 4 Pump trouble #5 input high (option)
5 AC voltage low alarm high 5 NA
6 NA 6 NA
7 NA 7 NA
8 NA 8 NA
9 AC power available high 9 NA
10 NA 10 NA
11 NA 11 NA
12 NA 12 NA
13 NA 13 NA
14 NA 14 NA
15 NA 15 NA

WORD 42016 Start Count WORD 42017 Run Time


ANALOG VALUES ANALOG VALUES (Hours)

WORD 42018 Hours since last run WORD 42019 NA


ANALOG VALUES (Hours)

WORD 43029 Cut-In WORD 43030 Cut-Out


ANALOG VALUES (PSI) ANALOG VALUES (PSI)

3362 Apex Peakway


Apex, North Carolina 27502
P 919 460 5200
F 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages resulting
from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2024 Firetrol, Inc., All Rights Reserved.
Publication TD1000-01(D)+