Samsung Klime Errors
Samsung Klime Errors
E201 Communication error between indoor unit and outdoor unit (Pre tracking failure or when
actual number of indoor units are different from the indoor unit quantity setting on the outdoor
unit) Error due to communication tracking failure after initial power supply (The error occurs with
the failure regardless of the number of devices)
E202 Communication error between indoor and outdoor unit (When not received in every room
after completing the tracking)
E203 Communication error between outdoor unit inv - main micom (For PF #4~#6 controller, error
will be determined from the time when compressor turns on)
E265 Digital compl Sump temperature sensor breakaway. Fixed compl Sump temperature sensor
breakaway
E440 Heating operation restricted at outdoor temperature overheating value (default: 30 °C)
E441 Cooling operation restricted at outdoor temperature below cool value (default 0°Q
E442 Forbid an operation during heat mode with refrigerant charging operation when outdoor
temperature is over 15°C
E467 Error due to abnormal rotation of the compressor or unconnected wire of compressor
*5 Indoor unit pipe thermistor sensor error Indoor unit pipe thermistor sensor
Drain system
DIP switch (SW2) of the indoor unit (The No.2 and No.4 switches must be at “ON” position.)
*A A Indoor and Outdoor communication error Communication cables of indoor and outdoor
units
*C Wired remote controller communication error Wired remote controller cables, Wired
remote controller
Operation LED and reservation LED flickering (1Hz period) Indoor pipe temperature sensor
abnormal
Operation LED and filter LED flickering (1 Hz period) Outdoor temperature sensor abnormal
Reservation LED filter LED alternating flickering (1Hz period) Float switch open abnormal
Reservation LED and filter LED flickering (1Hz period) Indoor and outdoor communication
abnormal
Operation LED and reservation LED alternating flickering (1Hz period) Wired remote controller
communication abnormal
Filter LED flickering (1Hz period) Outdoor pipe temperature sensor abnormal
Is your problem not in this list? Maybe it's a common aircon problem we've already encountered.
Read more about it here.
Open of indoor heat exchanger sensor Check of indoor exchanger sensor departure
Replacement of sensor
Open of outdoor heat exchanger sensor Check of outdoor exchanger sensor departure
Replacement of sensor
Replacement of sensor
Error of temperature sensor in the indoor unit (Open/Short) OFF OFF Flickering OFF
OFF
Error of the discharge temperature sensor Flickering OFF OFF Flickering OFF
1. No communication for 2 minutes between indoor units (Communication error for more than 2
minutes)
4. When sending the communication error from the outdoor unit, the mismatching of the
communication numbers and installed numbers after completion of tracking (Communication error
for more than 2 minutes) OFF OFF Flickering Flickering OFF
6. Compressor down due to 6th detection of freezing OFF OFF Flickering Flickering
Flickering
Error of setting option switches for optional accessories OFF OFF Flickering OFF
Flickering
102 Indoor/Outdoor unit Communication Time Out Error 60 Packet Over data
203 Communication Error between Outdoor Main and Inverter Micom (Occurred after 1 minute
detection in Main and Inverter)
460 Outdoor unit - indoor unit communication wire miss connection (Connected to Power
terminal)
601 Communication error between Indoor unit and wired remote control
602 Communication error between Master and Slave wired remote control
601 Communication error between wired remote control < -> indoor unit/ventilation system
(ERV) (When communication has stopped for 3 minutes after detecting indoor unit/ventilation
system (ERV) and wired remote control)
602 Communication error between wired remote control < -> indoor unit/ventilation system
(ERV) (When communication has stopped for 3 minutes after detecting indoor unit/ventilation
system (ERV) and wired remote control)
604 Tracking 10 or more errors between wired remote control < -> indoor unit/ventilation
system (ERV)
- When wired remote control is connected to indoor unit COM 1 (F1,F2) terminal
- Error occurred during installation when two wired remote controls are both set as masters in one
communication line (This is not possible to detect if the communication polarity is connected in
reversed polarity.)
609 Indoor unit is not installed in case of outside gearing (when the indoor unit is not detected
after outside gearing option setting and tracking are finished).
618 - Exceeded maximum no. of installation for indoor unit/ventilation system (ERV) (16
equipment devices)
- A reset is required after checking the number of indoor unit/ventilation system (ERV) installations
- Error occurs when mixed indoor units of °C and "F settings are installed
621 This error occurs when the option settings of the master and slave wired remote controls are
different from each other.
627 Slave wired remote control installation error (when two slave wired remote controls are
installed)
630 Normal operation option setting error (when normal operation is selected with the wired
remote control for a ventilation system (ERV) that does not support the normal operation option)
631 Automatic operation option setting error (when automatic operation is selected with the
wired remote control for a ventilation system (ERV) that does not support the automatic operation
option)
- Damper error [error is detected when there is no input for 100 seconds (time for about 5
revolutions) during damper output]
LED BLINK LED OFF LED BLINK Outdoor temperature sensor error
LED BLINK LED BLINK LED OFF Discharge temperature sensor error
LED OFF LED BLINK LED BLINK Test Operation at Cooling Mode
LED BLINK LED BLINK LED BLINK Test Operation at Heating Mode
EEPROM error Lamp blink Lamp blink Lamp blink Option Setting
Option error (option wasn't set up or option data error) Lamp blink Lamp blink Lamp
blink Option Setting
Outdoor unit error Lamp blink Lamp on Lamp blink Remote Control on/off
Outdoor Unit Power Reset