Lecture 5-Transformer Tests & Efficiency
Lecture 5-Transformer Tests & Efficiency
TRANSFORMER TESTS
The circuit constants, efficiency and voltage regulation of a transformer
can be determined by two simple tests i.e.:
✓ open-circuit test
✓ short-circuit lest.
These tests are very convenient as they provide the required information
without actually loading the transformer.
Further, the power required to carry out these tests is very small as
compared with full-load output of the transformer.
These tests consist of measuring the input voltage, current and power to
the primary first with secondary open-circuited (open-circuit test) and
then with the secondary short-circuited (short circuit test).
2
Open-Circuit or No-Load Test
This test is conducted to determine the iron losses (or core losses) and parameters
R0 and X0 of the transformer.
In this test, the rated voltage is applied to the primary (usually low-voltage
winding) while the secondary is left open-circuited.
The applied primary voltage V1 is measured by the voltmeter, the no-load current I0
by ammeter and no-load input power W0 by wattmeter as shown in Figure (i).
As the normal rated voltage is applied to the primary, therefore, normal iron losses
will occur in the transformer core.
Hence wattmeter will record the iron losses and small copper loss in the primary. 3
Open-Circuit or No-Load Test
4
Short-Circuit or Impedance Test
This test is conducted to determine R01 (or R02), X01 (or X02) and
full-load copper losses of the transformer.
The low input voltage is gradually raised till at voltage VSC, full-
load current I1 flows in the primary.
5
Short-Circuit or Impedance Test
There is no output from the transformer under short-circuit conditions.
Therefore, input power is all loss and this loss is almost entirely copper
loss.
It is because iron loss in the core is negligibly small since the voltage VSC
is very small.
6
Short-Circuit or Impedance Test
• Note: The SC test will give full-load Cu loss only if the applied
voltage VSC is such so as to circulate full-load currents in the
windings.
7
Advantages of Transformer Tests
1. The power required to carry out these tests is very small as compared
to the full-load output of the transformer. In case of open-circuit lest,
power required is equal to the iron loss whereas for a short-circuit test,
power required is equal to full-load copper loss.
3. The short-circuit test enables us to determine R01 and X01 (or R02 and
X02). We can thus find the total voltage drop in the transformer as
referred to primary or secondary. This permits us to calculate voltage
regulation of the transformer.
8
Practice Question
side
9
Solution
10
Efficiency of a Transformer
Like any other electrical machine, the efficiency of a transformer is defined
as the ratio of output power (in watts or kW) to input power (watts or kW)
12
Efficiency from Transformer Tests
13
Efficiency of a Transformer
14
Conditions for Maximum Efficiency of a Transformer
15
Hence efficiency of a transformer will be maximum when copper losses are
equal to constant or iron losses.
From (ii) above, the load current I2 corresponding to maximum efficiency is
given by:
The relative value of these losses is in the control of the designer of the
transformer according to the relative amount of copper and iron used.
A transformer which is to operate continuously on full-load would, therefore,
be designed to have-maximum efficiency at full-load.
However, distribution transformers operate for long periods on light load.
Therefore, their point of maximum efficiency is usually arranged to be
between three-quarter and half lull-load.
Note. In a transformer, iron losses are constant whereas copper losses are
variable. In order to obtain maximum efficiency, the load current should be
such that total Cu losses become equal to iron losses.
16
Output kVA Corresponding to Maximum Efficiency
17
18
Practice Question
a voltage rating of 8 kV: 78 kV. Open circuit test and short circuit test
19
Solution
20
Conti…Solution
21
Practice Question
Qn. A 5 kVA, 500/250V, 50Hz, single phase transformer gave the
following readings,
Determine
iv. Draw the equivalent circuit referred to primary and insert all
values in it.
22
All-Day (or Energy) Efficiency
The ordinary or commercial efficiency of a transformer is defined
as the ratio of output power to the input power i.e.,
Commercial efficiency = Power Output/Power Input
There are certain types of transformers whose performance cannot
be judged by this efficiency.
For instance, distribution transformers used for supplying lighting
loads have their primaries energized all the 24 hours in a day but
the secondaries supply little or no load during the major portion of
the day.
Constant loss (i.e., iron loss) occurs during the whole day but
copper loss occurs only when the transformer is loaded and would
depend upon the magnitude of load.
23
All-Day (or Energy) Efficiency
Consequently, the copper loss varies considerably during the day
and the commercial efficiency of such transformers will vary from a
low value (or even zero) to a high value when the load is high.
24
All-Day (or Energy) Efficiency
Qn 2.: In a 25 kVA, 2000/200 V power transformer the iron and full load
copper losses are 350 W and 400 W, respectively. Calculate the efficiency
at unity power factor at (i) full load and (ii) half load.
27
Solution Qn 2
28
Practice Question
A 400kVA, distribution transformer has full load iron loss of
2.5kW and copper loss of 3.5kW. During a day, its load cycle
for 24hours is,
4 hours No load
29
Practice Question
Qn.1 In a 50 kVA transformer has iron loss is 500 W and full load
copper loss is 800W. Find the efficiency at full load and half full load at
0.8 p.f. lagging. [full load = 96.85%; Half full load = 96.6%]
Qn.2 A 40 kVA transformer has iron loss of 450W and full load copper
loss of 850W. If the full load p.f. of the load is 0.8 lagging, calculate
(i)full-load efficiency
30
Practice Question
31
Self Assessment
• What is voltage regulation of a transformer?
• Why does voltage drop in a transformer?
• Is the regulation at rated load of a transformer same at 0.8 p.f. lagging
and 0.8 p.f. leading?
• Is the percentage impedance of a transformer same on primary and on
secondary?
• Obtain the equivalent circuit of a 200/400V, 50Hz, single phase
transformer from the following test data:
O.C test: 200V, 0.7A, 70W-on LV side
SC test:15V, 10A, 85W-on HV side
Calculate the secondary voltage when delivering 5kW at 0.8 p.f. lagging.
32
Self Study
ODAF etc
33