Dados ssw05
Dados ssw05
Drive
Address: 01
Model: SSW-05
Firmware Version: 2.32
Rated Voltage: -----
Rated Current: 85
Tag:
|NOTE |PXXX |FUNCTION |ADJUSTABLE RANGE |FACTORY SETTING |USER'S SETTIN |UNIT |COMPA |
| | |READ ONLY PARAMETERS | | | | | |
|(2) |P000 |Parameter Access |0 ... 4, 6 ... 9999 = read |0 |0 | | |
| | | |5 = Alteration | | | | |
| |P002 |Motor Current Indication (%) |000.0 ... 999.9 | |0,0 |% In | |
| |P003 |Motor Current Indication (A) |000.0 ... 999.9 | |0,0 |A | |
| |P023 |Software Version |x.yz | |2,32 | | |
| |P030 |R Phase Current |000.0 ... 999.9 | |0,0 |A | |
| |P031 |S Phase Current |000.0 ... 999.9 | |0,0 |A | |
| |P032 |T Phase Current |000.0 ... 999.9 | |0,0 |A | |
| |P050 |Status Indication of the Motor Overload Prot |0 ... 250 | |146 | | |
| | | |250 = Error | | | | |
| | |READING AND WRITING PARAMETERS | | | | | |
| |P101 |Initial Voltage |30 ... 80 |30 |67 |% Un |Change |
| |P102 |Time of the Acceleration Ramp |1 ... 20 |10 |7 |s |Change |
| |P104 |Time of the Deceleration Ramp |0 ... 20 |0 |0 |s | |
| | | |0 = off | | | | |
|(1) |P105 |Motor Current Setting |30 ... 100 |100 |47 |% |Change |
|(1) |P106 |Protection Configuration |0 ... 3F hexadec.(0 ... 63 d |31 |23 | |Change |
|(1) |P204 |Load Factoring Setting |0 = No function |0 |0 | | |
| | | |1 = No function | | | | |
| | | |2 = No function | | | | |
| | | |3 = No function | | | | |
| | | |4 = No function | | | | |
| | | |5 = Load factory default | | | | |
| |P206 |Auto-Reset Time |1 ... 1200 |900 |900 |s | |
|(1) |P215 |Keypad Copy Function |0 = Off |0 |0 | | |
| | | |1 = Copy (SSW -> Keypa | | | | |
| | | |2 = Paste (Keypad -> SS | | | | |
|(1) |P220 |HMI / (Trimpots and Dip Switch) selection |0 = Trimpots and Dip Swit |0 |0 | | |
| | | |1 = HMI | | | | |
|(1) |P264 |Programmable Digital Input DI1 |0 = Not used |1 |1 | | |
| | | |1 = Enable/Disable | | | | |
| | | |2 = External Fault | | | | |
|(1) |P277 |Programmable Relay Output (14/23-24) |1 = Full Voltage |1 |1 | | |
| | | |2 = Error | | | | |
| | | |3 = Serial com. | | | | |
|(1)(2) |P295 |Rated Current of the Soft Starter |0 = 3 A |According to |7 | | |
| | | |1 = 10 A |the Type | | | |
| | | |2 = 16 A | | | | |
| | | |3 = 23 A | | | | |
| | | |4 = 30 A | | | | |
| | | |5 = 45 A | | | | |
| | | |6 = 60 A | | | | |
| | | |7 = 85 A | | | | |
|(1) |P308 |Network Address |1 ... 30 |1 |1 | | |
| |P313 |Action of the Serial Communication Verificati |1 = only Error |1 |1 | | |
| | | |2 = ramp disabling | | | | |
| | | |3 = General disabling | | | | |
| | | |4 = P264=1 | | | | |
| |P314 |Verification Time of the Serial Communicatio |0 ... 5 |0 |0 |s | |
| | | |0 = OFF | | | | |
| |P610 |Immediate Undercurrent |30 ... 100 |30 |30 |% | |
| |P611 |Immediate Undercurrent Time |1 ... 99 |0 |0 |s | |
| | | |0 = Disabled | | | | |
| | | | | | | | |