NGSA - Unified AC - DC System
NGSA - Unified AC - DC System
TABLE OF CONTENTS
1.0 INTRODUCTION
2.0 OBJECTIVES FOR UNIFICATION OF AC/DC AUXILIARY SYSTEM
1.0 INTRODUCTION:
The auxiliary AC and DC system provide power to the critical infrastructure of the power system.
Reliability of auxiliary supply ensures safe, secure and reliable operation of the power system.
Keeping in view the importance of Auxiliary power system in the substation, the Unification and
Standardization of AC and DC system has been initiated with a focus on Single Point of Failure.
Typical HV Substation is selected for this unification process with following characteristics
1. 12 nos. HV GIS Bays
2. 03 nos. HV Power Transformers
3. 2 nos. Battery Chargers
4. 1 no. Battery Bank
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION
REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
TO BE USED FOR UNIFIED BATTERY AND BATTERY CHARGER SIZING
CONSTRUCTION OF
FOR ORDERING CALCULATIONS
MATERIALS UNTIL
CERTIFIED AND (COA & WOA)
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.
DMS EXCEL
Engineering and Design Department
1-4
Simultaneous operation of the following while restoring 13.8kV Circuits within 1 min before the end of discharge.
1-4.1 Closing of one HV Breaker
1-4.2 Closing of one Incomer and one Outgoing breaker and tripping of one breaker if fault persist.
1-4.3 One spring charging motor is in process of starting.
1-4.4 One motor is running,starting current assumed is 5 times normal current.
13.8KV SWITCHGEAR 2249 3893 2252 2445 2445 Military city-2 S/S
Telecommunication Load 2012 6661 1020 1663 4941 Provided By Telecom Unification Team
SAS Loads 2846 2990 3587 2704 4150 Provided By Telecom Unification Team
Power Transformer (HICO) 1548 2012 170 1500 2012 HICO Bulk Purchase for 3 Power Transformers
Control & Protection Loads (AES) 3121 1789 2709 3414 3414 Military city-2 S/S
Load Profile
800.00
700.00
Load current in A
600.00
500.00 A5
400.00 A4
A3
300.00
A2
200.00 A1
100.00
0.00
0 31 60 91 121 152 182 213 244 274 305 335 366 397 425 456 486 517 547 578
Duration in Min
1 A1 = L1+L2 751.44 1
2 A2 = L1 163.44 179
3 A3 = L1+L3 173.44 180
4 A4=L1 163.44 239
5 A5 = L1+L4 204.44 1
TOTAL
Section 2 - First 2 periods only - If A3 is greater than A2, go to Section 3- YES YES
1 751.44 751.44 1.0000 180.0000 3.8300 1.0500 3021.92 0.00
2 163.44 -588.00 179.0000 179.0000 3.8100 1.0500 0.00 -2352.29
Sub Total 3021.92 -2352.29
Total N/A
Total 1116.12
Section 4 - First 4 periods only - If A5 is greater than A4, go to Section 5 YES YES
1 751.44 751.44 1.0000 599.0000 9.5800 1.0400 7486.75 0.00
2 163.44 -588.00 179.0000 598.0000 9.56 1.0400 0.00 -5846.13
3 173.44 10.00 180.0000 419.0000 7.1800 1.0400 74.67 0.00
4 163.44 -10.00 239.0000 239.0000 4.6200 1.0400 0.00 -48.05
Sub Total 7561.42 -5894.18
Total N/A
Section 5 - First 5 periods only - If A6 is greater than A5, go to Section 6 YES YES
1 751.44 751.44 1.0000 600.0000 10.0500 1.0400 7854.05 0.00
2 163.44 -588.00 179.0000 599.0000 10.0300 1.0400 0.00 -6133.55
3 173.44 10.00 180.0000 420.0000 7.1900 1.0400 74.78 0.00
4 163.44 -10.00 239.0000 240.0000 4.6300 1.0400 0.00 -48.15
5 204.44 41.00 1.0000 1.0000 1.0900 1.1000 49.16 0.00
Sub Total 7977.99 -6181.70
Total 1796.29
* Values of Capacity Rating Factor (Kt) are based on the Manufacturer's standard Battery sheet.
* Values of Temperature Derating Factor (Tt) are based on TES-P-103.02 PARA 4.4.1
A1 A2 A3 A4 A5
0
0 751.44
1 751.44
1 163.44
180 163.44
180 173.440
360 173.4400
360 163.44
599 163.44
599 204.44
600 204.44
600
Engineering and Design Department
The ampere output rating of a charger for a DC Power System is determined by the following equation:
AR = 400.53 Amp
2. Design criteria
6)The simultaneous peak loading of the auxiliary transformer excluding power transformer oil
filtration socket load shall not exceed 80% of its rating; and with oil filtration socket, the load
shall not exceed the full rating of the station transformer.
7)The following loads need not be considered for estimating simultaneous peak loading:
b. Sump Motor
10)Typical Examples for loading calcualtions as per table 35-1 & sub tables TES-P-119.35.
= 365.61 KVA
The simultaneous peak load on Auxiliary
Transformer excluding Oil Filtration Socket
= 497.25 KVA
Max 80% Loading of the proposed auxiliary transformer size without transformer oil filtration
outlet load, i.e. a minimum capacity of ((365.61 / 0.8) =457 KVA ) is required.
Hence, based on the above selection criteria, the chosen size of station service transformer is :
(3) Impedance Z% 4% - 6%
Calculations
V2 = (13.8 kv)2
13.8kV Bus Fault level S= W = 597.56 MVA
Zs1 0.3187
Incomer Cable from 13.8kV SWGR to Station Service Transformer
No. of cables/phase = 1
Type of insulation = XLPE
No. of cores of cable = 1C
Size of selected cable = 300 sq.mm
So the selected cable = XLPE1CX300
Cable Resistance = 0.081200 Ω/km/Run
Cable Reactance = 0.096000 Ω/km/Run
Cable Length = 35 m
Cable Impedence = Sqrt(Rc2+Xc2) = 0.125736 Ω/km/Run
Total Cable Impedence (Zt) = 0.004401 W
13.8kV Source total Impedance = (Zt + Zs1) X (VLV)2 = 0.3231 x (400)2 0.000271
Introduction:
Impedance voltage (VI): Is that voltage which is applied through primary side such
that full load current is flowing in secondary side whenever it is short circuited.
It is also the percentage of the normal terminal voltage at the primary side required to
circulate full-load current under short circuit conditions on the secondary side.
CALCULATION:
Then, the Impedence Voltage of the selected auxiliary transformer 552 V and 828 V
equipment
(kVA) (c X
Operating
Total load
factor (d)
(VA) (c =
Load per
Diversity
(VA) (a)
QTY (b)
Load
aXb)
S.No. Load Description Remark
d)
1 Indoor Lighting Panel :ILP--1 12705 1 12705 1 12.71
10 Supply for Electrical Duct Heater -1(only one) 10000 1 10000 0.05 0.5
As per NGSABulk
12 Supply for Electrical Duct Heater -3
Purchase
Contract, TES-P-
125V Battery charger (including Spare &
13 65358 2 130716 0.5 65.36 119.35 & Running
Future)
Exercises
200A Power transformer oil filtration
14 receptacle for power trafo T1,T2 & T3 Area at 131640 3 394920 0 0.00
(BUS-A&B)
63A,400V Receptacle For
-Welding for Power TransformerT1,T2 ,T3 (3
Receptacle)
-Aux. Tr. T1,T2 (1 Receptacle)
15 -PACU Units at (3 Receptacle) 41465 12 497580 0 0.00
-Welding for Capacitor Area 1,2&3 (2
Receptacle)
40A Gas Filling at GIS room (3 Receptacle)
17 HVAC Control Panel (Smoke & Exhaust Fans) 34641 3 103923 0.05 5.20
21 400V,3PH Supply For External Telecom Shelter 16967 2 33934 0.5 17.0
equipment
Total load
factor (d)
(VA) (c =
Load per
Diversity
(VA) (a)
QTY (b)
Operating Load
aXb)
S.No. Load Description (KVA) (c X d)
QC.6 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-1 LCP (FANS , MK ) (MAIN) 11289 1 11289 0.50 5.64
QC.7 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-2 LCP (FANS , MK ) (MAIN) 11289 1 11289 0.50 5.64
QC.9 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-1 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00
QC.10 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-2 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00
QC.11 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-3 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00
QC.12 230V AC SUPPLY FOR BASEMENT SUMP PUMP-1 1529 1 1529 0.00 0.00
QC.13 230V AC SUPPLY FOR BASEMENT SUMP PUMP-2 1529 1 1529 0.00 0.00
QC.14 230V AC SUPPLY FOR BASEMENT SUMP PUMP-3 1529 1 1529 0.00 0.00
QC.15 230V AC SUPPLY FOR BASEMENT SUMP PUMP-4 1529 1 1529 0.00 0.00
QC.16 400V AC SUPPLY FOR SMOKE PURGE FAN-01 (SEF-01) 2858 1 2858 0.00 0.00
QC.17 400V AC SUPPLY FOR SMOKE PURGE FAN-02 (SEF-02) 4141 1 4141 0.00 0.00
QC.18 400V AC SUPPLY FOR SMOKE PURGE FAN-03(SEF-03) 3063 1 3063 0.00 0.00
QC.19 400V AC SUPPLY-1 FOR MISCELLANEOUS PORTABLE TOOLS 1176 1 1176 0.50 0.59
QC.20 230V AC SUPPLY-1 FOR 110/13.8 KV TR-1 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22
QC.21 230V AC SUPPLY-1 FOR 110/13.8 KV TR-2 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22
QC.22 230V AC SUPPLY-1 FOR 110/13.8 KV TR-3 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22
QC.23 400/230V AC SUPPLY FOR 110KV GIS LCC E10 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.24 400/230V AC SUPPLY FOR 110KV GIS LCC E08 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.25 400/230V AC SUPPLY FOR 110KV GIS LCC E06 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.26 400/230V AC SUPPLY FOR 110KV GIS LCC E04 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.27 400/230V AC SUPPLY FOR 110KV GIS LCC E02(HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.28 400/230V AC SUPPLY FOR 110KV GIS LCC E230 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.29 400/230V AC SUPPLY FOR 110KV GIS LCC E220 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.30 400/230V AC SUPPLY FOR 110KV GIS LCC E130 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.31 400/230V AC SUPPLY FOR 110KV GIS LCC E01 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.32 400/230V AC SUPPLY FOR 110KV GIS LCC E03 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.33 400/230V AC SUPPLY FOR 110KV GIS LCC E05 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.34 400/230V AC SUPPLY FOR 110KV GIS LCC E07(HTR,LTNG,SCKT) 588 1 588 0.06 0.04
QC.42 400 VAC SUPPLY FOR (DCDB ) PANEL 496 1 496 0.00 0.00
QC.43 400V,AC SUPPLY FOR GIS ROOM EXHAUST FAN 2747 1 2747 0.00 0.00
QC.47 230VAC SUPPLY FOR FUTURE PANELS 498 1 498 0.27 0.13
QC.48 230VAC SUPPLY FOR FUTURE PANELS 498 1 498 0.27 0.13
QC.49 230VAC SUPPLY-1 FOR SAS PANELS ROW (HTR,LTNG,SCKT) 2353 1 2353 0.00 0.00
QC.52 230V AC SUPPLY FOR BATTERY ROOM EXHAUST FANS. 211 2 422 1.00 0.42
QC.61 400V, AC SUPPLY FOR FM-200- ROOM-01 EXHAUST FAN 281 1 281 0.00 0.00
QC.63 400V, AC SUPPLY FOR BASEMENT EXHAUST FAN 02 2647 1 2647 1.00 2.65
QC.64 400V, AC SUPPLY FOR BASEMENT EXHAUST FAN 03 2647 1 2647 1.00 2.65
equipment
Total load
factor (d)
(VA) (c =
Load per
Diversity
(VA) (a)
QTY (b)
Operating Load
aXb)
S.No. Load Description (KVA) (c X d)
QD.07 400V,3PH SUPPLY-2 FOR TR-1 LCP (FANS MK )(STAND BY) 11289 1 11289 0.50 5.64
QD.08 400V, 3PH SUPPLY-2 FOR TR-2 LCP (FANS , MK ) (STAND BY) 11289 1 11289 0.50 5.64
QD.09 400V, 3PH SUPPLY-2 FOR TR-3 LCP (FANS , MK ) (MAIN) 11289 1 11289 0.50 5.64
QD.10 400V, 3PH SUPPLY-2 FOR TR-1 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00
QD.11 400V, 3PH SUPPLY-2 FOR TR-2 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00
QD.12 400V, 3PH SUPPLY-2 FOR TR-3 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00
QD.13 400V,AC SUPPLY FOR FAX/TELEPHONE EXCHANGE. 5882 1 5882 0.50 2.94
QD.14 400V, AC SUPPLY-2 FOR MISCELLANEOUS PORTABLE TOOLS 1176 1 1176 0.50 0.59
QD.16 400 VAC SUPPLY FOR (DCDB-1 ) PANELS 496 1 496 0.27 0.13
QD.17 400 VAC SUPPLY FOR (DCDB-2 ) PANELS 496 1 496 0.27 0.13
QD.18 230V AC SUPPLY FOR LCC'S ANNUNCIATION SYSTEM 3529 1 3529 0.18 0.64
QD.19 230V AC SUPPLY-2 FOR TR-1 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22
QD.20 230V AC SUPPLY-2 FOR TR-2 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22
QD.21 230V AC SUPPLY-2 FOR TR-3 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22
QD.22 230V AC SUPPLY FOR TR-1 ONLINE GAS/MOISTURE ANALYSER 176 1 176 1.00 0.18
QD.23 230V AC SUPPLY FOR TR-2 ONLINE GAS/MOISTURE ANALYSER 176 1 176 1.00 0.18
QD.24 230V AC SUPPLY FOR TR-3 ONLINE GAS/MOISTURE ANALYSER 176 1 176 1.00 0.18
QD.25 400V AC SUPPLY FOR TRANSFORMER PIT PUMP-1. 2353 1 2353 0.00 0.00
QD.26 400V AC SUPPLY FOR TRANSFORMER PIT PUMP-2. 2353 1 2353 0.00 0.00
QD.27 400V AC SUPPLY FOR TRANSFORMER PIT PUMP-3. 2353 1 2353 0.00 0.00
QD.28 400V AC SUPPLY FOR AUXILIARY TRANSFORMER-1 PIT PUMP. 2353 1 2353 0.00 0.00
QD.29 400V AC SUPPLY FOR AUXILIARY TRANSFORMER-2 PIT PUMP. 2353 1 2353 0.00 0.00
QD.30 230V AC SUPPLY FOR GATE MOTOR-1 1176 1 1176 0.00 0.00
QD.32 400V AC SUPPLY FOR WATER BOOSTER PUMP. 2941 1 2941 0.00 0.00
QD.34 230V AC SUPPLY FOR MFACB PANELS & PRINTERS 1035 1 1035 0.27 0.28
QD.38 230V AC SUPPLY FOR WATER TRANSFER PUMP 1294 1 1294 0.00 0.00
QD.43 230VAC SUPPLY-1 FOR AMI (RMR PANEL) 498 1 498 0.27 0.13
QD.44 230VAC SUPPLY-1 FOR AMI (SWITCH PANEL) 498 1 498 0.27 0.13
QD.45 230VAC SUPPLY-1 FOR SAS PANELS ROW (HTR,LTNG,SCKT) 1153 1 1153 0.00 0.00
QD.49 230V,1PH SUPPLY FM-200 RELEASING PANEL - HV GIS BASEMENT 440 1 440 0.00 0.00
QD.53 230V AC SUPPLY FOR BASEMENT SUMP PUMP-5 1529 1 1529 0.00 0.00
QD.54 230V AC SUPPLY FOR BASEMENT SUMP PUMP-6 1529 1 1529 0.00 0.00
QD.55 230V AC SUPPLY FOR BASEMENT SUMP PUMP-7 1529 1 1529 0.00 0.00
QD.56 230V AC SUPPLY FOR BASEMENT SUMP PUMP-8 1529 1 1529 0.00 0.00
QD.57 230V AC SUPPLY FOR HAND DRYER 1500 1 1500 1.00 1.50
QD.58 230V AC SUPPLY FOR GATE MOTOR-2 1176 1 1176 0.00 0.00
QD.59* 400V AC SUPPLY FOR SECURITY SYSTEM UPS IN CONTROL ROOM 1 0 1.00 0.00
QD.62 230V,1PH SUPPLY FOR ROLLING SHUTTER MOTOR DOOR 1176 1 1176 0.00 0.00
QD.63 400V,AC SUPPLY FOR BASEMENT EXHAUST FAN 01 2647 1 2647 1.00 2.65
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION
REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
TO BE USED FOR UNIFIED LV DC CIRCUIT BREAKER SIZING
CONSTRUCTION OF
FOR ORDERING CALCULATIONS
MATERIALS UNTIL
CERTIFIED AND (COA & WOA)
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.
DMS EXCEL
125V DC Fault Level Calculations:
System Data:
Calculations:
No of cells ( n ) = 92 Cell
DC voltage = 101.5 V
101.5
Short Circuit Current delivered by Battery String = Vmin/(Rmin* n * 10-3) =
0.11 x 92 x 10-3
= 600 A 2
Hence,
From 1 & 2
Total DC System Short Circuit Current = 20059.3 + 600
= 20659.3 A
= 20.7 kA
Conclusion:
As per clause 4.1.9.2 of TES-P-119.30 Rev 02, the rated short-time withstand current of main DC distribution panels
shall be minimum 25 kA, 1sec and rated short-time withstand current of sub DC distribution and Emergency lighting
panels shall be as per design calculations and NGSA approval.
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2
DIVERISITY
FACTOR
FACTOR
DEMAND
UNIT TOTAL
CB.No LOAD Volts
LOAD (W) LOAD (W) RATING NO OF SC
AMP AMP Type
AMP POLES Capacity
MAIN DCDB (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)
500AT/
Q.103 INCOMER-1 BREAKER FOR MAIN BUSBAR A 40600 1 1 40600 101.5 400.000 480.0 DP MCCB 25 KA
630AF
500AT/
Q.104 INCOMER-2 BREAKER FOR MAIN BUSBAR B 40600 1 1 40600 101.5 400.000 480.0 DP MCCB 25 KA
630AF
125AT/
Q.105 SUPPLY FOR PORTABLE BATTERY CHARGER 10150 1 1 10150 101.5 100.000 120.0 DP MCCB 25 KA
160AF
125AT/
Q.106 SUPPLY FOR PORTABLE BATTERY CHARGER 10150 1 1 10150 101.5 100.000 120.0 DP MCCB 25 KA
160AF
MAIN DCDB (BUS-A) (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)
225AT/
Q.A1 SUPPLY-1 FOR SUB DCDB-1 (BUS-A) 18016.0 1 1 18016.0 101.5 177.50 213.0 DP MCCB 25 KA
250AF
225AT/
Q.A2 SUPPLY-1 FOR SUB DCDB-2 (BUS-A) 18862.0 1 1 18862.0 101.5 185.83 223.0 DP MCCB 25 KA
250AF
60AT/
Q.A3 SUPPLY-1 FOR TELECOM DCPDB-1 4941.00 1 1 4941.0 101.5 48.68 58.4 DP MCCB 25 KA
63AF
75AT/
Q.A4 SUPPLY-1 FOR EMERGENCY LIGHTING PANEL 5800.0 1 1 5800.0 101.5 57.14 68.6 DP MCCB 25 KA
80AF
75AT/
Q.A5 SPARE DP MCCB 25 KA
80AF
225AT/
Q.A6 SPARE DP MCCB 25 KA
250AF
MAIN DCDB (BUS-B) (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)
225AT/
Q.B1 SUPPLY-2 FOR SUB DCDB-1 (BUS-B) 18016.0 1 1 18016.0 101.5 177.50 213.0 DP MCCB 25 KA
250AF
225AT/
Q.B2 SUPPLY-2 FOR SUB DCDB-2 (BUS-B) 18862.0 1 1 18862.0 101.5 185.83 223.0 DP MCCB 25 KA
250AF
60AT/
Q.B3 SUPPLY-2 FOR TELECOM DCPDB-1 4941.00 1 1 4941.0 101.5 48.68 58.4 DP MCCB 25 KA
63AF
75AT/
Q.B4 SUPPLY-2 FOR EMERGENCY LIGHTING PANEL 5800.0 1 1 5800.0 101.5 57.14 68.6 DP MCCB 25 KA
80AF
75AT/
Q.B5 SPARE DP MCCB 25 KA
80AF
225AT/
Q.B6 SPARE DP MCCB 25 KA
250AF
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
225AT/
Q.107 SUPPLY FOR SUB DCDB-1 (SEC-A) 18016.0 1 1 18016 101.5 177.50 213.00 DP MCCB 25 KA
250AF
225AT/
Q.108 SUPPLY FOR SUB DCDB-1 (SEC-B) 18016.0 1 1 18016 101.5 177.50 213.00 DP MCCB 25 KA
250AF
225AT/
Q.109 BUS TIE 18016.0 1 1 18016 101.5 177.50 213.00 DP MCCB 25 KA
250AF
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
QA1.94 SUPPLY-1 FOR AMI PANEL-1 118.0 1 1 118 101.5 1.16 1.395 20 DP MCB 25 KA
QA1.95 SUPPLY-1 FOR AMI PANEL-2 118.0 1 1 118 101.5 1.16 1.395 20 DP MCB 25 KA
QA1.98 SUPPLY FOR SECURITY SYSTEM AND CAMERAS 300.0 1 1 300 101.5 2.96 3.547 20 DP MCB 25 KA
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
SPARE
QB1.67 20 DP MCB 25 KA
QB1.73 SUPPLY-1 FOR SAS COMPUTER PANEL-1 1200 1 1 1200 101.5 11.82 14.19 20 DP MCB 25 KA
QB1.74 SUPPLY-1 FOR SAS COMPUTER PANEL-2 1200 1 1 1200 101.5 11.82 14.19 20 DP MCB 25 KA
QB1.75 SUPPLY-1 FOR SAS COMPUTER PANEL-3 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
QB1.80 SUPPLY-1 FOR COMMON ALARM PANEL-1 100 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
QB1.81 SUPPLY-1 FOR COMMON ALARM PANEL-2 50 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA
QB1.87 SUPPLY FOR SDB-1 (SUB ACDB-1) 50 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
QB1.97 SUPPLY FOR RECEPTACLES IN CONTROL ROOM 200 1 1 200 101.5 1.97 2.36 20 DP MCB 25 KA
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
DIVERISITY
UNIT TOTAL
FACTOR
FACTOR
DEMAND
CB.No LOAD LOAD LOAD Volts
(W) (W) RATING NO OF SC
AMP AMP Type
AMP POLES Capacity
225AT/
Q.110 SUPPLY FOR SUB DCDB-2 (SEC-A) 18862.0 1 1 18862 101.5 185.83 223.00 DP MCCB 25 KA
250AF
225AT/
Q.111 SUPPLY FOR SUB DCDB-2 (SEC-B) 18862.0 1 1 18862 101.5 185.83 223.00 DP MCCB 25 KA
250AF
225AT/
Q.112 BUS TIE 18862.0 1 1 18862 101.5 185.83 223.00 DP MCCB 25 KA
250AF
QA2.71 SUPPLY-2 FOR COMMON ALARM PANEL-2 50.0 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA
QA2.72 SUPPLY-2 FOR COMMON ALARM PANEL-1 100.0 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
QA2.77 SUPPLY-2 FOR SAS COMPUTER PANEL-3 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
QA2.78 SUPPLY-2 FOR SAS COMPUTER PANEL-2 1200.0 1 1 1200 101.5 11.82 14.19 20 DP MCB 25 KA
QA2.79 SUPPLY-2 FOR SAS COMPUTER PANEL-1 1200.0 1 1 1200 101.5 11.82 14.19 20 DP MCB 25 KA
QA2.81 SUPPLY FOR SDB-2 (SUB ACDB-2) 50.0 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA
QA2.85 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T01 78.0 1 1 78 101.5 0.77 0.92 20 DP MCB 25 KA
QA2.86 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T02 78.0 1 1 78 101.5 0.77 0.92 20 DP MCB 25 KA
QA2.87 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T03 78.0 1 1 78 101.5 0.77 0.92 20 DP MCB 25 KA
QA2.95 SUPPLY-2 FOR AMI PANEL-1 118.0 1 1 118 101.5 1.16 1.40 20 DP MCB 25 KA
QA2.96 SUPPLY-2 FOR AMI PANEL-2 118.0 1 1 118 101.5 1.16 1.40 20 DP MCB 25 KA
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2
QB2.104 13.8kV BBP(1A)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 25 KA
QB2.105 13.8kV BBP(1B)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 25 KA
QB2.106 13.8kV BBP(1C)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 25 KA
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
500AT/
Q.102 BREAKER FOR THE BATTERY- FROM CHARGERS 40600 1 1 40600 101.5 400.000 480.0 DP MCCB 25 KA
630AF
75AT/
QM1 SUPPLY FOR SUB DCDB-ELP (SEC-A) 5800.00 1 1 5800.00 101.5 57.14 68.57 DP MCCB 25 KA
80AF
75AT/
QM2 SUPPLY FOR SUB DCDB-ELP (SEC-B) 5800.0 1 1 5800.00 101.5 57.14 68.57 DP MCCB 25 KA
80AF
75AT/
QM3 BUS TIE 5800.0 1 1 5800.00 101.5 57.14 68.57 DP MCCB 25 KA
80AF
QA.011 PUSH BUTTON FOR GIS ROOM CABLE BASEMENT 100.0 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
QA.012 PUSH BUTTON FOR SWG ROOM 100.0 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2
DIVERISITY
TOTAL
FACTOR
FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity
QA.013 SWGR CABLE BASEMENT 100.0 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
QA.015 SWGR CABLE BASEMENT 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
QB.007 PUCH BUTTON FOR SWGR CABLE BASEMENT 100 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
QB.008 PUSH BUTTON FOR GIS ROOM 100 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
QB.009 PUSH BUTTON FOR CONTROL ROOM 100 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
CERT'D
APPR'D
CHK'D
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION
REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
TO BE USED FOR UNIFIED LV AC CIRCUIT BREAKER SIZING
CONSTRUCTION OF
FOR ORDERING CALCULATIONS
MATERIALS UNTIL
CERTIFIED AND (COA & WOA)
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.
DMS EXCEL
INDEX
1 Cover
2 Index& Legend
3 Design Basis for C.B
4-5 Short Circuit Calculation
6-9 AC C.B Sizing
LEGEND
MK : MASHALLING KIOSK
1- The current ratings given for C.B.'s are the thermal current rating requirement after ambient temperature
derating. ( Panel manufacturer should take care for temperature derating of this breakers) as per 31-TMSS-
02 (latest revision)
2- Circuit breakers ( number, rating ) are subject to change as per loads update.
3- Load power factor is taken as 0.85 for pump loads, rotating machinery, power sockets, cooling fans.
4- All circuit breakers interruption capacity shall be the same as that of bus short circuit withstand capacity.
5- MCCBs in main AC distribution panel shall be of triple pole with neutral link (TPN) as per TES-P-119.30 Rev.02,
Clause 3.2.3
6- Main AC Distribution panel Bus bars shall withstand full available short circuit current and shall not be less
than 25KA as per TES-P-119.30 Rev.02, Clause 3.2.2
7- ACB and MCCB shall be selected in accordance with load requirements and shall be rated for 120%
overloading capacity as per Technical Specification TES-P-119.30 Rev.02, Clause 3.2.6
8- MCCB shall be provided with overload, short circuit and earth fault release As per TES-P-119.30 Rev.02,
Clause 3.2.8
9- The incoming and bus-tie circuit breakers feeding the main distribution panel shall be ACB type and 4
pole. All the remaining feeder breakers shall be MCCB. However feeder circuit rated 32A and below may
be provided with MCB subject to SEC approval as per Materials Standard 31-TMSS-02, Rev.02 clause
4.4.1.b.(i).
10- Duration of short circuit interrupting capacity for MCCB & MCB shall be 1 Sec.
12- Short circuit current rating of AC sub Distribution panels shall be as per design calculations and NGSA
approval.
Reference Documents
DRAWING CONTROL SHEET
Calculations
V2 = (13.8 kv)2
13.8kV Bus Fault level S= Ω = 597.56 MVA
Zs1 0.3187
Incomer Cable from 13.8kV SWGR to Station Service Transformer
No. of cables/phase = 1
Type of insulation = XLPE
No. of cores of cable = 1C
Size of selected cable = 300 sq.mm
So the selected cable = XLPE1CX300
Cable Resistance = 0.081700 Ω/km/Run
Cable Reactance = 0.094000 Ω/km/Run
Cable Length = 50 m
Cable Impedence = Sqrt(Rc2+Xc2) = 0.124543 Ω/km/Run
Total Cable Impedence (Zt) = 0.006227 Ω
13.8kV Source total Impedance = (Zt + Zs1) X(VLV)² = 0.3249 x (400)2 0.000273 Ω
3 2
transferred to 400V side (VMV)² (13.8x10 )
2
Transformer Impedance = (VLV) X (Z%) = (400)² X 0.05 = 0.016000 Ω
KVA X 10
3 500X 10³
Cable from Station Service Transformer to Main ACDB
No. of cables/phase = 3
Type of insulation = XLPE
No. of cores of cable = 1C
Size of selected cable = 630 sq.mm
So the selected cable = XLPE1CX630
Cable Resistance R = 0.054500 Ω/km/Run
Cable Reactance X = 0.092000 Ω/km/Run
Cable Length = 44 m
Cable Impedence = Sqrt(Rc2+Xc2) = 0.106931 Ω/km/Run
Total Cable Impedence (Zt) = 0.001568 Ω
Then the selected Bus Bar Short Circuit shall be minimum 25 KA as per TES-P-119.30 R02
Conclusion:
"The Main BUSBAR shall withstand a minimmum short circuit of 25 kA," as per TES-P-119.30 R02 .
All circuit breakers used in 400V Main ACDB are having a minimum fault interrupting capacity of 25kA.
Hence, the above fault current is acceptable.
AC LOAD CALCULATION:-
DIVERSITY
FACTOR
C.B DATA
*
PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP
Q101 FROM AUX.T1 TO ACDB (BUS - A) 425.00 - 425.00 500 3 400 722 866 1000AT/1000AF ACB 4P -
Q102 FROM AUX.T2 TO ACDB (BUS - B) 425.00 - 425.00 500 3 400 722 866 1000AT/1000AF ACB 4P -
Q103 BUS TIE 425.00 - 425.00 500 3 400 722 866 1000AT/1000AF ACB 4P -
400/230V, 1000A, 25kA (1s), 60Hz, 3PH 4 WIRE MAIN ACDB - BUS A
Q.A1 400V,3PH SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU-1A (DUTY). 97.00 - 97.00 114.12 3 400 164.72 197.7 200AT/250AF MCCB TPN -
Q.A2 400V,3PH SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU-2B (STANDBY). 56.00 - 56.00 65.88 3 400 95.10 114.1 125AT/160AF MCCB TPN -
Q.A3 SUPPLY FOR SUB DISTRIBUTION PANEL-1 ( SDP-1). 70.48 - 70.48 82.92 3 400 119.68 143.6 160AT/250AF MCCB TPN -
Q.A4 SUPPLY FOR INDOOR LIGHTING PANEL (ILP-1). 10.80 - 10.80 12.70 3 400 18.34 22.0 32AT/160AF MCCB TPN -
Q.A5 SUPPLY FOR INDOOR LIGHTING PANEL (ILP-2) 4.47 - 4.47 5.26 3 400 7.59 9.1 20 MCB TPN -
Q.A6 SUPPLY FOR 125V DC NICAD BATTERY CHARGER-1. 55.00 - 55.00 65.00 3 400 93.82 112.6 200AT/250AF MCCB TPN -
200AMP,400V RECEPTACLE FOR OIL FILTRATION UNIT FOR POWER TRANSFORMERS AREA (T-
Q.A7 98.098 - 98.10 115.41 3 400 166.58 199.9 200AT/250AF MCCB TPN -
01)
200AMP,400V RECEPTACLE FOR OIL FILTRATION UNIT FOR POWER TRANSFORMERS AREA (T-02
Q.A8 98.098 - 98.10 115.41 3 400 166.58 199.9 200AT/250AF MCCB TPN -
)
Q.A9 63AMP,400V WELDING & MAINTENANCE RECEPTACLE FOR POWER TRANSFORMER AREA (T-01) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -
Q.A10 63AMP,400V WELDING & MAINTENANCE RECEPTACLE FOR POWER TRANSFORMER AREA (T-02) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN
Q.A11 63AMP,400V WELDING RECEPTACLE FOR CAPACITOR BANKS AREA (CAP-01 & CAP-02 ) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -
Q.A12 63AMP,400V WELDING RECEPTACLE FOR AUXILARY TRANSFORMERS (AUX-01 & AUX-02) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -
Q.A13 63AMP,400V WELDING RECEPTACLE FOR PACU UNITS (1A & 1B) ON THE ROOF. 30.50 - 30.50 35.88 3 400 51.79 62.2 63AT/160AF MCCB TPN -
Q.A14 40AMP,400V GAS FILLING RECEPTACLE-01 AT GIS ROOM. 19.00 - 19.00 22.35 3 400 32.26 38.7 40AT/160AF MCCB TPN -
Q.A15 40AMP,400V GAS FILLING RECEPTACLE-02 AT GIS ROOM. 19.00 - 19.00 22.35 3 400 32.26 38.7 40AT/160AF MCCB TPN -
Q.A16 400V,3PH SUPPLY-1 FOR EXTERNAL TELECOM SHELTER 34.05 - 34.05 40.06 3 400 57.82 69.4 125AT/160AF MCCB TPN -
Q.A18 SUPPLY FOR HVAC CONTROL PANEL-1 29.44 - 29.44 34.64 3 400 49.99 60.0 63AT/160AF MCCB TPN -
400/230V, 1000A, 25kA (1s), 60Hz, 3PH 4 WIRE MAIN ACDB - BUS B
Q.B1 SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU-1B (STANDBY). 97.00 - 97.00 114.12 3 400 164.72 197.7 200AT/250AF MCCB TPN -
Q.B2 SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU-2A (DUTY). 56.00 - 56.00 65.88 3 400 95.10 114.1 125AT/160AF MCCB TPN -
Q.B3 SUPPLY FOR SUB DISTRIBUTION PANEL-2 ( SDP-2). 62.76 - 62.76 73.83 3 400 106.57 127.9 160AT/250AF MCCB TPN -
Q.B4 SUPPLY FOR POWER RECEPTACLE PANEL 19.80 - 19.80 23.29 3 400 33.62 40.3 50AT/160AF MCCB TPN -
Q.B5 SUPPLY FOR OUTDOOR LIGHTING PANEL (OLP). 6.48 - 6.48 7.62 3 400 11.00 13.2 20 MCB TPN -
Q.B6 SUPPLY FOR 125V DC NICAD BATTERY CHARGER-2. 55.00 - 55.00 65.00 3 400 93.82 112.6 200AT/250AF MCCB TPN -
Q.B7 200AMP,400V RECEPTACLE FOR OIL FILTRATION UNIT FOR POWER TRANSFORMERS AREA (T-03) 98.10 - 98.10 115.41 3 400 166.58 199.9 200AT/250AF MCCB TPN -
Q.B8 63AMP,400V WELDING & MAINTENANCE RECEPTACLE FOR POWER TRANSFORMER AREA (T-03) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -
UNIT TOTAL TOTAL Load details of
DIVERSITY
FACTOR
C.B DATA
*
PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP
Q.B9 63AMP,400V WELDING RECEPTACLE FOR CAPACITOR BANKS AREA (CAP-03) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -
Q.B10 63AMP,400V WELDING RECEPTACLE FOR PACU UNITS (2A & 2B) ON THE ROOF. 30.50 - 30.50 35.88 3 400 51.79 62.2 63AT/160AF MCCB TPN -
Q.B12 40AMP,400V GAS FILLING RECEPTACLE-03 AT GIS ROOM. 19.00 - 19.00 22.35 3 400 32.26 38.7 40AT/160AF MCCB TPN -
Q.B13 HV TEST BUSHING RECEPTACLES FOR GIS 61.29 - 61.29 72.11 3 400 104.08 124.9 125AT/160AF MCCB TPN -
Q.B14 400V,3PH SUPPLY-2 FOR EXTERNAL TELECOM SHELTER. 30.50 - 30.50 35.88 3 400 51.79 62.2 125AT/160AF MCCB TPN -
Q.B16 SUPPLY FOR HVAC CONTROL PANEL-2 29.44 - 29.44 34.64 3 400 49.99 60.0 63AT/160AF MCCB TPN -
Q.B17 400V,3PH PORTABLE BATTERY CHARGER SUPPLY 30.50 - 30.50 35.88 3 400 51.79 62.2 63AT/160AF MCCB TPN -
Q.B18 400V,3PH SUPPLY FOR EOT CRANE. 9.84 - 9.84 11.58 3 400 16.71 20.1 32AT/160AF MCCB TPN -
Q.B19 400V,3PH SUPPLY FOR JIB CRANE. 9.84 - 9.84 11.58 3 400 16.71 20.1 32AT/160AF MCCB TPN -
QC SUPPLY FOR AC SDP-1 70.48 1 70.48 82.92 3 400 119.68 143.62 160AT/250AF MCCB TPN 70.48
QC.8 400V 3PH SUPPLY-1 FOR TR-1 LCP (FANS , MK ) (MAIN) 26.7 0.5 26.74 31.46 3 400 45.41 54.5 63AT/160AF MCCB TPN 13.37
QC.9 400V 3PH SUPPLY-1 FOR TR-2 LCP (FANS , MK ) (MAIN) 26.7 0.5 26.74 31.46 3 400 45.41 54.5 63AT/160AF MCCB TPN 13.37
QC.10 400V 3PH SUPPLY-1 FOR TR-3 LCP (FANS , MK ) (STANDBY) 26.7 0.5 26.74 31.46 3 400 45.41 54.5 63AT/160AF MCCB TPN 13.37
QC.11 400V 3PH SUPPLY-1 FOR TR-1 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00
QC.12 400V 3PH SUPPLY-1 FOR TR-2 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00
QC.13 400V 3PH SUPPLY-1 FOR TR-3 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00
QC.14 400V,AC SUPPLY FOR HV GIS ROOM EXHAUST FAN 2.33 0 2.33 2.74 3 400 3.96 4.7 20 MCB TPN 0.00
QC.15 400V, AC SUPPLY FOR FM-200- ROOM-01 EXHAUST FAN 0.24 0 0.24 0.28 3 400 0.41 0.5 20 MCB TPN 0.00
QC.16 400V, AC SUPPLY FOR SECURITY SYSTEM 3.17 1 3.17 3.730 3 400 5.38 6.5 20 MCB TPN 3.17
QC.17 400V, AC SUPPLY FOR BASEMENT EXHAUST FAN 03 2.24 1 2.24 4.748 3 400 6.85 8.2 20 MCB TPN 2.24
QC.18 400V, AC SUPPLY FOR BASEMENT EXHAUST FAN 02 2.24 1 2.24 3.677 3 400 5.31 6.4 20 MCB TPN 2.24
QC.19 400V AC SUPPLY FOR SMOKE PURGE FAN-01 (SEF-01) 2.43 0 2.43 2.86 3 400 4.13 5.0 20 MCB TPN 0.00
QC.20 400V AC SUPPLY FOR SMOKE PURGE FAN-02 (SEF-02) 3.50 0 3.50 4.12 3 400 5.94 7.1 20 MCB TPN 0.00
QC.21 ELECTRICAL DUCT HEATER 10.00 0 10.00 10.00 3 400 14.43 17.3 20 MCB TPN 0.00
QC.22 400V AC SUPPLY-1 FOR MISCELLANEOUS PORTABLE TOOLS 1.00 0.5 1.00 1.18 3 400 1.70 2.0 20 MCB TPN 0.50
UNIT TOTAL TOTAL Load details of
DIVERSITY
FACTOR
C.B DATA
*
PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP
QC.23 400V AC SUPPLY FOR HV GIS LCC E10 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.24 400V AC SUPPLY FOR HV GIS LCC E08 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.25 400V AC SUPPLY FOR HV GIS LCC E06 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.26 400V AC SUPPLY FOR HV GIS LCC E04 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.27 400V AC SUPPLY FOR HV GIS LCC E02 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.28 400V AC SUPPLY FOR HV GIS LCC E230 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.29 400V AC SUPPLY FOR HV GIS LCC E220 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.30 400V AC SUPPLY FOR HV GIS LCC E130 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.31 400V AC SUPPLY FOR HV GIS LCC E01 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.32 400V AC SUPPLY FOR HV GIS LCC E03 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.33 400V AC SUPPLY FOR HV GIS LCC E05 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.34 400V AC SUPPLY FOR HV GIS LCC E07 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05
QC.40 230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT) (+R230,+R220,+R130) 0.49 0.27 0.49 0.58 1 230 2.50 3.0 20 MCB SPN 0.13
QC.42 230V AC SUPPLY-1 FOR TR-1 OLTC LIGHTING & HEATER. 0.37 0.5 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19
QC.43 230V AC SUPPLY-1 FOR TR-2 OLTC LIGHTING & HEATER. 0.37 0.5 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19
QC.44 230V AC SUPPLY-1 FOR TR-3 OLTC LIGHTING & HEATER. 0.37 0.5 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19
QC.45 230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-1 (AH01 TO AH18) 4.94 1 4.94 5.81 1 230 25.24 30.3 32 MCB SPN 4.94
QC.46 230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-2 (AH19 TO AH36) 4.610 1 4.610 5.42 1 230 23.58 28.3 32 MCB SPN 4.61
QC.47 230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-3 (AH37 TO AH53) HTR,LTNG,SCKT) 4.840 1 4.840 5.69 1 230 24.76 29.7 32 MCB SPN 4.84
QC.50 230VAC SUPPLY-1 FOR SAS PANELS ROW (HTR,LTNG,SCKT) 0.87 0.27 0.87 1.02 1 230 4.45 5.3 20 MCB SPN 0.23
QC.51 230VAC SUPPLY FOR COMMUNICATION PANELS (LAN/WAN , SDH , DDF,DVM,MDF) 2.00 1.00 2.00 2.35 1 230 10.23 12.3 20 MCB SPN 2.00
QC.52 230VAC SUPPLY FOR COMMUNICATION PANELS (MCP , N01 ,N02,DC-DC CONVERTER -1&2) 2.00 1.00 2.00 2.35 1 230 10.23 12.3 20 MCB SPN 2.00
QC.53 230V AC SUPPLY FOR BATTERY ROOM EXHAUST FAN. 0.35 1.00 0.35 0.41 1 230 1.80 2.2 20 MCB SPN 0.35
QC.54 230V,1PH SUPPLY FM-200 RELEASING PANEL - CONTROL ROOM - FIRST FLOOR 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
QC.55 230V,1PH SUPPLY FM-200 RELEASING PANEL - COMMUNICATION ROOM -FIRST FLOOR 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
QC.56 230V,1PH SUPPLY FM-200 RELEASING PANEL - BATTERY ROOM -FIRST FLOOR 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
QC.57 230V,1PH SUPPLY FM-200 RELEASING PANEL - MV SWITCHGEAR ROOM -GROUND FLOOR 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - GIS HALL-GROUND FLOOR-
QC.58 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
SYSTEM#1
230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - GIS HALL-GROUND FLOOR-
QC.59 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
SYSTEM#2
230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - GIS HALL-GROUND FLOOR-
QC.60 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
SYSTEM#3
230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - GIS HALL-GROUND FLOOR-
QC.61 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
SYSTEM#4
QC.62 230V AC SUPPLY FOR GATE MOTOR-1 1.00 0.00 1.00 1.18 1 230 5.12 6.1 20 MCB SPN 0.00
QC.63 230V AC SUPPLY FOR BASEMENT SUMP PUMP-1 1.30 0.00 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
QC.64 230V AC SUPPLY FOR BASEMENT SUMP PUMP-2 1.30 0.00 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
QC.65 230V AC SUPPLY FOR BASEMENT SUMP PUMP-3 1.30 0.00 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
UNIT TOTAL TOTAL Load details of
DIVERSITY
FACTOR
C.B DATA
*
PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP
QC.66 230V AC SUPPLY FOR BASEMENT SUMP PUMP-4 1.30 0.00 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
QD SUPPLY FOR AC SDP-2 62.76 1 62.76 73.83 3 400 106.57 127.9 160AT/250AF MCCB TPN 62.76
QD.7 400V 3PH SUPPLY-2 FOR TR-1 LCP(FANS,MK) (STAND-BY). 26.74 0.5 26.74 31.46 3 400 45.41 54.5 63 MCCB TPN 13.37
QD.8 400V 3PH SUPPLY-2 FOR TR-2 LCP(FANS,MK) (STAND-BY). 26.74 0.5 26.74 31.46 3 400 45.41 54.5 63 MCCB TPN 13.37
QD.9 400V 3PH SUPPLY-2 FOR TR-3 LCP(FANS,MK) (MAIN). 26.74 0.5 26.74 31.46 3 400 45.41 54.5 63 MCCB TPN 13.37
QD.10 400V 3PH SUPPLY-2 FOR TR-1 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00
QD.11 400V 3PH SUPPLY-2 FOR TR-2 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00
QD.12 400V 3PH SUPPLY-2 FOR TR-3 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00
QD.13 400VAC SUPPLY FOR FAX/TELEPHONE EXCHANGE. 5.00 1 5.00 5.88 3 400 8.49 10.2 20 MCB TPN 5.00
QD.14 400V AC SUPPLY FOR MISCELLANEOUS PORTABLE SUPPLY-2 1.00 0.5 1.00 1.18 3 400 1.70 2.0 20 MCB TPN 0.50
QD.15 400V,AC SUPPLY 01 FOR SPLIT UNIT(WORKSHOP AND RECORD ROOM) 3.50 1 3.50 4.12 3 400 5.94 7.1 20 MCB TPN 3.50
QD.16 400 VAC SUPPLY FOR (DCDB-1 ) PANELS 0.42 0.5 0.42 0.49 3 400 0.71 0.9 20 MCB TPN 0.21
QD.17 400 VAC SUPPLY FOR (DCDB-2 ) PANELS 0.4 0.5 0.42 0.49 3 400 0.71 0.9 20 MCB TPN 0.21
QD.18 400 VAC SUPPLY FOR (DCDB ) PANEL 0.4 0.5 0.42 0.49 3 400 0.71 0.9 20 MCB TPN 0.21
QD.19 400V,AC SUPPLY FOR BASEMENT EXHAUST FAN 01 2.25 1 2.25 2.65 3 400 3.82 4.6 20 MCB TPN 2.25
QD.20 400V AC SUPPLY FOR SECURITY SYSTEM UPS IN CONTROL ROOM 0.3 1 0.32 0.38 3 400 0.54 0.7 32 MCB TPN 0.32
QD.21 400V,AC SUPPLY 02 FOR SPLIT UNIT(WORKSHOP AND RECORD ROOM) 3.50 1 3.50 4.12 3 400 5.94 7.1 20 MCB TPN 3.50
QD.22 400V AC SUPPLY FOR T01 TRANSFORMER PIT PUMP-1. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00
QD.23 400V AC SUPPLY FOR T02 TRANSFORMER PIT PUMP-2. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00
QD.24 400V AC SUPPLY FOR T03 TRANSFORMER PIT PUMP-3. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00
QD.25 400V AC SUPPLY FOR AUXILIARY TRANSFORMER-1 PIT PUMP. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00
QD.26 400V AC SUPPLY FOR AUXILIARY TRANSFORMER-2 PIT PUMP. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00
QD.27 400V AC SUPPLY FOR WATER BOOSTER PUMP. 2.50 0 2.50 2.94 3 400 4.25 5.1 20 MCB TPN 0.00
QD.29 230V,AC SUPPLY FOR KITCHEN EXHAUST FAN 0.02 0 0.02 0.03 1 230 0.11 0.1 20 MCB SPN 0.00
QD.30 230V AC SUPPLY FOR MFACP PANELS & PRINTERS 0.68 0.27 0.68 2.67 1 230 11.59 13.9 20 MCB SPN 0.18
QD.31 230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(RTCC-1,RTCC-2,RTCC-3) 0.81 0.27 0.81 2.74 1 230 11.90 14.3 20 MCB SPN 0.22
QD.32 230V AC SUPPLY FOR WATER HEATER FOR TOILET. 2.00 0 2.00 3.03 1 230 13.17 15.8 20 MCB SPN 0.00
QD.33 230V AC SUPPLY FOR TOILET EXHAUST FAN 0.13 0 0.13 0.16 1 230 0.68 0.8 20 MCB SPN 0.00
QD.34 230V AC SUPPLY FOR WATER TRANSFER PUMP 1.10 0 1.10 1.29 1 230 5.63 6.8 20 MCB SPN 0.00
UNIT TOTAL TOTAL Load details of
DIVERSITY
FACTOR
C.B DATA
*
PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP
QD.35 230V AC SUPPLY FOR CONTROL ROOM WORKSTATION (PC'S, MONITORS, PRINTERS…..ETC). 2.00 1 2.00 2.35 1 230 10.23 12.3 20 MCB SPN 2.00
QD.36 230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(ILPB,ILP,ELP,DCU,RMR,DDR) 1.01 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27
QD.38 230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(G12,G11,FUT,FUT,FUT,FUT) 1.01 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27
QD.39 230VAC SUPPLY FOR AMI (RMR PANEL) 0.42 0.27 0.42 0.49 1 230 2.15 2.6 20 MCB SPN 0.11
QD.40 230VAC SUPPLY FOR AMI (SWITCH PANEL) 0.42 0.27 0.42 0.49 1 230 2.15 2.6 20 MCB SPN 0.11
QD.41 230VAC SUPPLY-1 FOR SAS PANELS ROW (HTR,LTNG,SCKT) 0.98 0.27 0.98 1.15 1 230 5.01 6.0 20 MCB SPN 0.26
QD.42 230V,AC SUPPLY FOR FM-200-ROOM-02 EXHAUST FAN 2.25 0 2.25 2.65 1 230 11.51 13.8 20 MCB SPN 0.00
QD.43 230V,AC SUPPLY FOR FM-200-ROOM-03 EXHAUST FAN 2.25 0 2.25 2.65 1 230 11.51 13.8 20 MCB SPN 0.00
QD.44 230V,1PH SUPPLY FM-200 RELEASING PANEL - 13.8kV SWITCHGEAR BASEMENT 0.39 0 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
QD.45 230V,1PH SUPPLY FM-200 RELEASING PANEL - HV GIS BASEMENT 0.39 0 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
QD.46 230V,1PH SUPPLY FM-200 RELEASING PANEL - CABLE CORRIDOR-BASEMENT 0.39 0 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
QD.48 230V,1PH SUPPLY FM-200 RELEASING PANEL - BATTERY ROOM - EXTERNAL TELECOM SHELTER 0.39 0 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
QD.49 230V AC SUPPLY FOR BASEMENT SUMP PUMP-5 1.30 0 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
QD.50 230V AC SUPPLY FOR BASEMENT SUMP PUMP-6 1.30 0 1.300 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
QD.51 230V AC SUPPLY FOR BASEMENT SUMP PUMP-7 1.30 0 1.300 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
QD.52 230V AC SUPPLY FOR BASEMENT SUMP PUMP-8 1.30 0 1.300 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
QD.53 230V AC SUPPLY FOR HAND DRYER 1.28 1 1.28 1.51 1 230 6.55 7.9 20 MCB SPN 1.28
QD.54 230V AC SUPPLY FOR GATE MOTOR-2 1.00 0 1.00 1.18 1 230 5.12 6.1 20 MCB SPN 0.00
QD.55 230V AC SUPPLY FOR LCC'S ANNUNCIATION SYSTEM 3.00 0.18 3.00 3.53 1 230 15.35 18.4 20 MCB SPN 0.54
QD.56 230V,1PH SUPPLY FOR PARTIAL DISCHARGE MONITORING SYSTEM(PDMS) 0.14 1.00 0.14 0.16 1 230 0.72 0.9 20 MCB SPN 0.14
QD.57 230V,1PH SUPPLY FOR ROLLING SHUTTER MOTOR DOOR 2.00 0.00 2.00 2.35 1 230 10.23 12.3 20 MCB SPN 0.00
QD.58 230V AC SUPPLY-2 FOR TR-1 OLTC LIGHTING & HEATER. 0.37 0.50 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19
QD.59 230V AC SUPPLY-2 FOR TR-2 OLTC LIGHTING & HEATER. 0.37 0.50 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19
QD.60 230V AC SUPPLY-2 FOR TR-3 OLTC LIGHTING & HEATER. 0.37 0.50 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19
QD.61 230V AC SUPPLY FOR TR-1 ONLINE GAS/MOISTURE ANALYSER 0.15 1.00 0.15 0.18 1 230 0.77 0.9 20 MCB SPN 0.15
QD.62 230V AC SUPPLY FOR TR-2 ONLINE GAS/MOISTURE ANALYSER 0.15 1.00 0.15 0.18 1 230 0.77 0.9 20 MCB SPN 0.15
QD.63 230V AC SUPPLY FOR TR-3 ONLINE GAS/MOISTURE ANALYSER 0.15 1.00 0.15 0.18 1 230 0.77 0.9 20 MCB SPN 0.15
*
* Diversity factor is used only to calculate main C.B rating of SDP-1 and SDP-
2
20A Circuit breakers rating shall be as per design requirements and subject
to SEC approval.
CERT'D
APPR'D
CHK'D
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION
REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
DMS EXCEL
LV DC Cable sizing :-
IFL = KW x 1000 / V %VD = (Voltage Drop / Supply Voltage) x 100
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts 0 Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp40 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
Q.102 BATTERY CHARGER BREAKER FOR THE BATTERY- FROM CHARGER 40600 1 1 40600 101.5 400.000 480.0 500AT/ 630AF DP MCCB 1C 300 XLPE Duct 498 2 20 0.84 0.87 0.7308 727.88 0.0766 0.0007663 0.74 0.72 0.80
MAIN DCDB (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)
Q.103 BATTERY CHARGER-1 INCOMER-1 BREAKER FOR MAIN BUSBAR A 40600 1 1 40600 101.5 400.000 480.0 500AT/ 630AF DP MCCB 1C 240 XLPE Air 597 2 10 0.91 0.87 0.7917 945.29 0.0961 0.0004807 0.46 0.45 0.80
Q.104 BATTERY CHARGER-2 INCOMER-2 BREAKER FOR MAIN BUSBAR B 40600 1 1 40600 101.5 400.000 480.0 500AT/ 630AF DP MCCB 1C 240 XLPE Air 597 2 10 0.91 0.87 0.7917 945.29 0.0961 0.0004807 0.46 0.45 0.80
Q.105 SUPPLY FOR PORTABLE BATTERY CHARGER 10150 1 1 10150 101.5 100.0 120.0 125AT/ 160AF DP MCCB -
Q.106 SUPPLY FOR PORTABLE BATTERY CHARGER 10150 1 1 10150 101.5 100.0 120.0 125AT/ 160AF DP MCCB -
MAIN DCDB (BUS-A) (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)
225AT/ MCCB
Q.A1 MAIN DCDB SUPPLY-1 FOR SUB DCDB-1 (BUS-A) 18016.0 1 1 18016.0 101.5 177.50 213.0 DP 2C 35 XLPE Air 186 2 7 0.91 0.7 0.6 236.96 0.6682 0.0023385 1.00 0.98 4.20
250AF
225AT/ MCCB
Q.A2 MAIN DCDB SUPPLY-1 FOR SUB DCDB-2 (BUS-A) 18862.0 1 1 18862.0 101.5 185.83 223.0 DP 2C 35 XLPE Air 186 2 9 0.91 0.7 0.6 236.96 0.6682 0.0030067 1.34 1.32 4.20
250AF
Q.A3 MAIN DCDB SUPPLY-1 FOR TELECOM DCDB 4941.0 1 1 4941.0 101.5 48.68 58.4 60AT/ 63AF DP MCCB 2C 35 XLPE Air 186 1 14 0.91 0.7 0.6 118.48 0.6682 0.0093541 1.09 1.08 4.20
Q.A4 MAIN DCDB SUPPLY-1 FOR EMERGENCY LIGHTING PANEL 5800.0 1 1 5800.0 101.5 57.14 68.6 75AT/ 80AF DP MCCB 2C 35 XLPE Air 186 2 11 0.91 0.7 0.6 236.96 0.6682 0.0036748 0.50 0.50 4.20
225AT/ MCCB
Q.A6 MAIN DCDB SPARE DP SPARE
250AF
MAIN DCDB (BUS-B) (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)
225AT/
Q.B1 MAIN DCDB SUPPLY-2 FOR SUB DCDB-1 (BUS-B) 18016 1 1 18016.0 101.5 177.50 213.00 DP MCCB 2C 35 XLPE Air 186 2 7 0.91 0.7 0.6 236.96 0.6682 0.0023385 1.00 0.98 4.20
250AF
225AT/ MCCB
Q.B2 MAIN DCDB SUPPLY-2 FOR SUB DCDB-2 (BUS-B) 18862 1 1 18862.0 101.5 185.83 223.00 DP 2C 35 XLPE Air 186 2 9 0.91 0.7 0.6 236.96 0.6682 0.0030067 1.34 1.32 4.20
250AF
Q.B3 MAIN DCDB SUPPLY-2 FOR TELECOM DCDB 4941 1 1 4941.0 101.5 48.68 58.42 60AT/ 63AF DP MCCB 2C 35 XLPE Air 186 1 14 0.91 0.7 0.6 118.48 0.6682 0.0093541 1.09 1.08 4.20
Q.B4 MAIN DCDB SUPPLY-2 FOR EMERGENCY LIGHTING PANEL 5800 1 1 5800.0 101.5 57.14 68.57 75AT/ 80AF DP MCCB 2C 35 XLPE Air 186 2 11 0.91 0.7 0.6 236.96 0.6682 0.0036748 0.50 0.50 4.20
225AT/
Q.B6 MAIN DCDB SPARE DP MCCB SPARE
250AF
SUPPLY FOR LINE FEEDER-E05 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, MCB
QA1.2 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP 2C 4 XLPE Air 51 1 11 0.91 0.45 0.41 20.88 5.8782 0.0646603 0.02 0.02 4.20
IN/OUT RELAY CKT)
SUPPLY FOR TRANSFROMER T01-E03 PROTECTION PANEL SET-1 (MAIN-1 87 T-1 MCB
QA1.3 SUB DCDB-2 75.2 1 1 75.2 101.5 0.74 0.89 20 DP 2C 4 XLPE Air 51 1 11 0.91 0.45 0.41 20.88 5.8782 0.0646603 0.11 0.11 4.20
PROTN, IN/OUT RELAY )
SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, MCB
QA1.4 SUB DCDB-3 13.8 1 1 13.8 101.5 0.14 0.16 20 DP 2C 4 XLPE Air 51 1 11 0.91 0.45 0.41 20.88 5.8782 0.0646603 0.02 0.02 4.20
IN/OUT RELAY CKT)
QA1.5 SUB DCDB-4 SUPPLY FOR BUS COUPLER-A -E130 PROTECTION PANEL (O/C & E/F RELAY CKT) 36.3 1 1 36.3 101.5 0.36 0.43 20 DP MCB 2C 4 XLPE Air 51 1 12 0.91 0.45 0.41 20.88 5.8782 0.0705385 0.06 0.06 4.20
QA1.6 SUB DCDB-1 SUPPLY FOR BUS SECTION-E220 PROTECTION PANEL (O/C & E/F RELAY CKT) 36.3 1 1 36.3 101.5 0.36 0.43 20 DP MCB 2C 4 XLPE Air 51 1 12 0.91 0.45 0.41 20.88 5.8782 0.0705385 0.06 0.06 4.20
QA1.7 SUB DCDB-1 SUPPLY FOR BUS COUPLER-B -E230 PROTECTION PANEL (O/C & E/F RELAY CKT) 36.3 1 1 36.3 101.5 0.36 0.43 20 DP MCB 2C 4 XLPE Air 51 1 13 0.91 0.45 0.41 20.88 5.8782 0.0764167 0.07 0.06 4.20
2 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
SUPPLY FOR TRANSFORMER T02-E02 PROTECTION PANEL SET-1 (MAIN-1 87T-1 MCB
QA1.8 SUB DCDB-1 75.2 1 1 75.2 101.5 0.74 0.89 20 DP 2C 4 XLPE Air 51 1 13 0.91 0.45 0.41 20.88 5.8782 0.0764167 0.14 0.13 4.20
PROTN, IN/OUT RELAY )
SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, MCB
QA1.9 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP 2C 4 XLPE Air 51 1 14 0.91 0.45 0.41 20.88 5.8782 0.0822950 0.03 0.03 4.20
IN/OUT RELAY CKT)
SUPPLY FOR TRANSFORMER T03-E06 PROTECTION PANEL SET-1 (MAIN-1 87 T-1 MCB
QA1.10 SUB DCDB-1 75.2 1 1 75.2 101.5 0.74 0.89 20 DP 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.8782 0.0881732 0.16 0.15 4.20
PROTN, IN/OUT RELAY )
SUPPLY FOR LINE FEEDER-E08 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, MCB
QA1.11 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.8782 0.0940514 0.03 0.03 4.20
IN/OUT RELAY CKT)
SUPPLY FOR LINE FEEDER (FUTURE)-E10 PROTECTION PANEL SET-1 (MAIN-1 MCB FUTURE
QA1.12 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP
PROTN CKT, IN/OUT RELAY CKT)
QA1.13 SUB DCDB-1 SUPPLY-1 FOR HV LINE FEEDER (FUTURE)-E07 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB FUTURE
QA1.15 SUB DCDB-1 SUPPLY-1 FOR HV TRANSFORMER T01-E03 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20
QA1.17 SUB DCDB-1 SUPPLY-1 FOR HV BUS COUPLER-A -E130 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20
QA1.19 SUB DCDB-1 SUPPLY-1 FOR HV BUS COUPLER-B -E230 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20
QA1.20 SUB DCDB-1 SUPPLY-1 FOR HV TRANSFORMER T02-E02 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20
QA1.21 SUB DCDB-1 SUPPLY-1 FOR HV LINE FEEDER-E04 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.189 2.16 4.20
QA1.22 SUB DCDB-1 SUPPLY-1 FOR HV TRANSFORMER T03-E06 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20
QA1.23 SUB DCDB-1 SUPPLY-1 FOR HV LINE FEEDER S/S-E08 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.189 2.16 4.20
QA1.24 SUB DCDB-1 SUPPLY-1 FOR HV LINE FEEDER (FUTURE)-E10 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB FUTURE
QA1.25 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER (FUTURE)-E07 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB FUTURE
QA1.26 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER-E05 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 1.25 1.23 10.00
QA1.27 SUB DCDB-1 SUPPLY-2 FOR HV TRANSFORMER T01-E03 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 1.25 1.23 10.00
QA1.28 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER-E01 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 45 0.91 0.45 0.41 36.04 2.333433 0.1050045 1.24 1.22 10.00
QA1.29 SUB DCDB-1 SUPPLY-2 FOR HV BUS COUPLER-A -E130 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 44 0.91 0.45 0.41 36.04 2.333433 0.1026711 1.21 1.20 10.00
QA1.30 SUB DCDB-1 SUPPLY-2 FOR HV BUS SECTION-E220 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 43 0.91 0.45 0.41 36.04 2.333433 0.1003376 1.19 1.17 10.00
QA1.31 SUB DCDB-1 SUPPLY-2 FOR HV BUS COUPLER-B -E230 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 42 0.91 0.45 0.41 36.04 2.333433 0.0980042 1.16 1.14 10.00
QA1.32 SUB DCDB-1 SUPPLY-2 FOR HV TRANSFORMER T02-E02 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 41 0.91 0.45 0.41 36.04 2.333433 0.0956708 1.13 1.11 10.00
QA1.33 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER-E04 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 40 0.91 0.45 0.41 36.04 2.333433 0.0933373 1.10 1.09 10.00
QA1.34 SUB DCDB-1 SUPPLY-2 FOR HV TRANSFORMER T03-E06 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 39 0.91 0.45 0.41 36.04 2.333433 0.0910039 1.08 1.06 10.00
QA1.35 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER S/S-E08 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 38 0.91 0.45 0.41 36.04 2.333433 0.0886705 1.05 1.03 10.00
QA1.36 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER (FUTURE)-E10 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB FUTURE
QA1.37 SUB DCDB-1 SUPPLY-3 FOR HV LINE FEEDER (FUTURE)-E07 (DS/ES INTERLOCK CKT SUPPLY) 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB FUTURE
QA1.38 SUB DCDB-1 SUPPLY-3 FOR HV LINE FEEDER-E05 (DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 10 XLPE Air 88 1 40 0.91 0.45 0.41 36.04 2.333433 0.0933373 0.15 0.15 4.20
3 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QA1.39 SUB DCDB-1 SUPPLY-3 FOR HV TRANSFORMER T01-E03 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 10 XLPE Air 88 1 42 0.91 0.45 0.41 36.04 2.333433 0.0980042 0.16 0.16 4.20
QA1.40 SUB DCDB-1 SUPPLY-3 FOR HV LINE FEEDER -E01 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 0.44 0.43 4.20
QA1.41 SUB DCDB-1 SUPPLY-3 FOR HV BUS COUPLER-A -E130 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 0.43 0.42 4.20
QA1.42 SUB DCDB-1 SUPPLY-3 FOR HV BUS SECTION-E220 (DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 0.42 0.41 4.20
QA1.43 SUB DCDB-1 SUPPLY-3 FOR HV BUS COUPLER-B -E230 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.41 0.40 4.20
QA1.44 SUB DCDB-1 SUPPLY-3 FOR HV TRANSFORMER T02-E02 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 0.40 0.39 4.20
QA1.45 SUB DCDB-1 SUPPLY-3 FOR HV LINE FEEDER-E04 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 0.39 0.38 4.20
QA1.46 SUB DCDB-1 SUPPLY-3 FOR HV TRANSFORMER T03-E06 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 0.38 0.37 4.20
QA1.47 SUB DCDB-1 SUPPLY-3 FOR HV SPARE FEEDER S/S-E08 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 0.37 0.36 4.20
QA1.48 SUB DCDB-1 SUPPLY-3 FOR HV FUTURE FEEDER- E10 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB FUTURE
QA1.49 SUB DCDB-1 SUPPLY-1 FOR HV BUSBAR-A PROTECTION PANEL (ZONE 1A PROTN CKT) 13.0 1 1 13.0 101.5 0.13 0.15 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.04 0.04 4.20
SUPPLY-1 FOR HV BUSBAR-CH ZONE PROTECTION PANEL (BB-CHECK ZONE & MCB
QA1.50 SUB DCDB-1 13.0 1 1 13.0 101.5 0.13 0.15 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.08 0.07 4.20
IN/OUT RELAY CKT)
QA1.51 SUB DCDB-1 SUPPLY-1 FOR HV BUSBAR-B PROTECTION PANEL (ZONE-1B PROTN CKT) 13.0 1 1 13.0 101.5 0.13 0.15 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.08 0.07 4.20
SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE FEEDER BUS-1 (AH01) (TRIP CKT-1, MCB
QA1.52 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP FUTURE
CLOSE CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE FEEDER BUS-1 (AH02) (TRIP CKT-1, MCB
QA1.53 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP FUTURE
CLOSE CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR CAP. BANK-1 FEEDER (AH03) (TRIP CKT-1, CLOSE MCB
QA1.54 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH04) (TRIP CKT-1, CLOSE MCB
QA1.55 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH05) (TRIP CKT-1, CLOSE MCB
QA1.56 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH06) (TRIP CKT-1, CLOSE MCB
QA1.57 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH07) (TRIP CKT-1, CLOSE MCB
QA1.58 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH08) (TRIP CKT-1, CLOSE MCB
QA1.59 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV INCOMER T01 (AH09) (TRIP CKT-1, CLOSE CKT/CONTROL MCB
QA1.60 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.47 1.45 4.20
CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH10) (TRIP CKT-1, CLOSE MCB
QA1.61 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH11) (TRIP CKT-1, CLOSE MCB
QA1.62 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH12) (TRIP CKT-1, CLOSE MCB
QA1.63 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH13) (TRIP CKT-1, CLOSE
QA1.64 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.878211 0.0881732 0.49 0.48 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH14) (TRIP CKT-1, CLOSE
QA1.65 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 2C 4 XLPE Air 51 1 14 0.91 0.45 0.41 20.88 5.878211 0.0822950 0.46 0.45 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH15) (TRIP CKT-1, CLOSE MCB
QA1.66 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.52 0.51 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR AUX-01 FEEDER (AH16) (TRIP CKT-1, CLOSE MCB
QA1.67 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 17 0.91 0.45 0.41 20.88 5.878211 0.0999296 0.55 0.55 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8KV BUS METERING-01 (AH17) (EARTH SWITCH INTERLOCK, MCB
QA1.68 SUB DCDB-1 133.3 1 1 133.3 101.5 1.31 1.58 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.78 0.77 4.20
I/O BOX-1)
SUPPLY-1 FOR 13.8kV BUS SECTION-01 (AH18) (TRIP CKT-1, CLOSE MCB
QA1.69 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.47 1.45 4.20
CKT/CONTROL CKT, BCU)
4 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
SUPPLY-1 FOR 13.8KV BUS RISER-01 (AH19) (EARTH SWITCH INTERLOCK, I/O MCB
QA1.70 SUB DCDB-1 123.3 1 1 123.3 101.5 1.21 1.46 20 DP 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 0.77 0.76 4.20
BOX-1)
SUPPLY-1 FOR 13.8kV SWGR CAP. BANK-02 FEEDER (AH20) (TRIP CKT-1, CLOSE MCB
QA1.71 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 1.43 1.41 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH21) (TRIP CKT-1, CLOSE MCB
QA1.72 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 1.40 1.38 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH22) (TRIP CKT-1, CLOSE MCB
QA1.73 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH23) (TRIP CKT-1, CLOSE MCB
QA1.74 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 1.34 1.32 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH24) (TRIP CKT-1, CLOSE MCB
QA1.75 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.30 1.29 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH25) (TRIP CKT-1, CLOSE MCB
QA1.76 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 1.27 1.25 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH26) (TRIP CKT-1, CLOSE MCB
QA1.77 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 1.24 1.22 4.20
CKT/CONTROL CKT, BCU)
QA1.78 SUB DCDB-1 SUPPLY FOR 13.8 KV BUSBAR-1A PROTECTION PANEL(MAIN PROTN) 15.3 1 1 15.3 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 0.08 0.08 4.20
QA1.79 SUB DCDB-1 SUPPLY FOR 13.8 KV BUSBAR-1B PROTECTION PANEL(MAIN PROTN) 15.3 1 1 15.3 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.09 0.09 4.20
QA1.80 SUB DCDB-1 SUPPLY FOR 13.8 KV BUSBAR-1C PROTECTION PANEL(MAIN PROTN) 15.3 1 1 15.3 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.06 0.06 4.20
SUPPLY FOR 13.8KV AUTOMATIC BUS TRANSFER SCHEME (+ABTS) (IN/OUT MCB
QA1.81 SUB DCDB-1 80.0 1 1 80.0 101.5 0.79 0.95 20 DP 2C 4 XLPE Air 51 1 13 0.91 0.45 0.41 20.88 5.8782 0.0764167 0.14 0.14 4.20
MODULE & ALARM/ INDICATION CKT)
QA1.82 SUB DCDB-1 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-1 (SET-1) 61.3 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.8782 0.0881732 0.13 0.13 4.20
QA1.83 SUB DCDB-1 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-2 (SET-1) 61.3 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.14 0.13 4.20
QA1.84 SUB DCDB-1 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-3 (SET-1) 61.3 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.24 0.23 4.20
QA1.85 SUB DCDB-1 SUPPLY-1 FOR DC EMERGENCY LIGHTING FOR CONTROL PANELS 40.0 1 1 40.0 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QA1.86 SUB DCDB-1 SUPPLY FOR CHANGE OVER SCHEME-1 (ATS FOR DCDB-1) 50.0 1 1 50.0 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.19 0.19 4.20
QA1.88 SUB DCDB-1 SUPPLY FOR 13.8KV SWGR INCOMER T03 (AH45)(SYNCH TROLLEY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.31 0.31 4.20
QA1.89 SUB DCDB-1 SUPPLY FOR 13.8KV SWGR INCOMER T02 (AH29) (SYNCH TROLLEY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.31 0.31 4.20
QA1.90 SUB DCDB-1 SUPPLY FOR 13.8KV SWGR INCOMER T01 (AH09) (SYNCH TROLLEY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.31 0.31 4.20
QA1.91 SUB DCDB-1 SUPPLY FOR 13.8KV SWGR INCOMER T03 (AH45) (OPERATING MECHANISM) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 4.20
SUPPLY FOR 13.8KV SWGR INCOMER T02 (AH29) AND BUS SECTION-02
QA1.92 SUB DCDB-1 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 4.20
(AH36)(OPERATING MECHANISM)
SUPPLY FOR 13.8KV SWGR INCOMER T01 (AH09) AND BUS SECTION-01 (AH18) MCB
QA1.93 SUB DCDB-1 500.0 1 1 500.0 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 4.20
(OPERATING MECHANISM)
QA1.94 SUB DCDB-1 SUPPLY-1 FOR AMI PANEL-1 118.0 1 1 118.0 101.5 1.16 1.40 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.46 0.45 4.20
QA1.95 SUB DCDB-1 SUPPLY-1 FOR AMI PANEL-2 118.0 1 1 118.0 101.5 1.16 1.40 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.46 0.45 4.20
QA1.96 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-1 30.0 1 1 30.0 101.5 0.30 0.35 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.12 0.12 4.20
QA1.97 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-2 30.0 1 1 30.0 101.5 0.30 0.35 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.12 0.12 4.20
QA1.98 SUB DCDB-1 SUPPLY FOR SECURITY SYSTEM AND CAMERAS 300.0 1 1 300.0 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.17 1.15 4.20
5 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QA1.102 SUB DCDB-1 SUPPLY FOR LINE FEEDER(FUTURE)-E07 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB FUTURE
QA1.103 SUB DCDB-1 SUPPLY FOR LINE FEEDER-E05 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20
QA1.104 SUB DCDB-1 SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20
QA1.105 SUB DCDB-1 SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20
QA1.106 SUB DCDB-1 SUPPLY FOR LINE FEEDER-E08 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20
QA1.107 SUB DCDB-1 SUPPLY FOR LINE FEEDER(FUTURE)-E10 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB FUTURE
QB1.1 SUB DCDB-1 SUPPLY-4 FOR LINE FEEDER (FUTURE)-E07 (CB CLOSING CKT) 500 1 1 500 101.5 4.93 5.91 20 DP MCB FUTURE
6 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QB1.12 SUB DCDB-1 SUPPLY-4 FOR LINE FEEDER (FUTURE)-E10 (CB CLOSING CKT) 500 1 1 500 101.5 4.93 5.91 20 DP MCB FUTURE
QB1.13 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER (FUTURE)-E07 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB FUTURE
QB1.14 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER-E05 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 45 0.91 0.45 0.41 36.04 2.333433 0.1050045 0.09 0.09 4.20
QB1.15 SUB DCDB-1 SUPPLY-5 FOR TRANSFORMER T01-E03 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 44 0.91 0.45 0.41 36.04 2.333433 0.1026711 0.08 0.08 4.20
QB1.16 SUB DCDB-1 SUPPLY-4 FOR LINE FEEDER-E01 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 43 0.91 0.45 0.41 36.04 2.333433 0.1003376 0.08 0.08 4.20
QB1.17 SUB DCDB-1 SUPPLY-4 FOR BUS COUPLER-A-E130 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 42 0.91 0.45 0.41 36.04 2.333433 0.0980042 0.08 0.08 4.20
QB1.18 SUB DCDB-1 SUPPLY-5 FOR BUS SECTION-E220 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 41 0.91 0.45 0.41 36.04 2.333433 0.0956708 0.08 0.08 4.20
QB1.19 SUB DCDB-1 SUPPLY-5 FOR BUS COUPLER-B -E230 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 40 0.91 0.45 0.41 36.04 2.333433 0.0933373 0.08 0.08 4.20
QB1.20 SUB DCDB-1 SUPPLY-5 FOR TRANSFORMER T02-E02 (BCU POWER SUPPLY)) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 39 0.91 0.45 0.41 36.04 2.333433 0.0910039 0.08 0.07 4.20
QB1.21 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER-E04 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 38 0.91 0.45 0.41 36.04 2.333433 0.0886705 0.07 0.07 4.20
QB1.22 SUB DCDB-1 SUPPLY-5 FOR TRANSFORMER T03-E06 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 40 0.91 0.45 0.41 36.04 2.333433 0.0933373 0.08 0.08 4.20
QB1.23 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER S/S-E08 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 42 0.91 0.45 0.41 36.04 2.333433 0.0980042 0.08 0.08 4.20
QB1.24 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER (FUTURE)-E10 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB FUTURE
SUPPLY-6 FOR HV LINE FEEDER (FUTURE)-E07 (SF6 GAS COMPARTMENT& I/O MCB FUTURE
QB1.25 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP
MODULE , BCU AUXILIARY
SUPPLY-6 FOR HV LINE FEEDER-E05 (SF6 GAS COMPARTMENT& I/O MODULE , MCB
QB1.26 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 0.59 0.58 4.20
BCU AUXILIARY
SUPPLY-6 FOR HV LINE FEEDER-E01 (SF6 GAS COMPARTMENT& I/O MODULE , MCB
QB1.28 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 0.56 0.56 4.20
BCU AUXILIARY
SUPPLY-6 FOR HV BUS COUPLER-A -E130 (SF6 GAS COMPARTMENT& I/O MCB
QB1.29 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.55 0.54 4.20
MODULE , BCU AUXILIARY)
SUPPLY-6 FOR HV BUS SECTION-E220 (SF6 GAS COMPARTMENT& I/O MODULE MCB
QB1.30 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 0.54 0.53 4.20
AUXILIARY POWER SUPPLY)
SUPPLY-6 FOR HV BUS COUPLER-B -E230 (SF6 GAS COMPARTMENT& I/O MCB
QB1.31 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 0.53 0.52 4.20
MODULE , BCU AUXILIARY)
SUPPLY-6 FOR HV LINE FEEDER-E04 (SF6 GAS COMPARTMENT& I/O MODULE , MCB
QB1.33 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 0.50 0.49 4.20
BCU AUXILIARY
7 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
SUPPLY-6 FOR HV LINE FEEDER -E08 (SF6 GAS COMPARTMENT& I/O MODULE , MCB
QB1.35 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.55 0.54 4.20
BCU AUXILIARY
SUPPLY-6 FOR HV LINE FEEDER (FUTURE)-E10 (SF6 GAS COMPARTMENT& I/O MCB FUTURE
QB1.36 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP
MODULE , BCU AUXILIARY
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH27) (TRIP CKT-1, CLOSE MCB
QB1.37 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH28) (TRIP CKT-1, CLOSE MCB
QB1.38 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 1.47 1.45 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR INCOMER T02 (AH29) (TRIP CKT-1, CLOSE MCB
QB1.39 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 1.54 1.52 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH30) (TRIP CKT-1, CLOSE MCB
QB1.40 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 1.40 1.38 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH31) (TRIP CKT-1, CLOSE MCB
QB1.41 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH32) (TRIP CKT-1, CLOSE MCB
QB1.42 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 1.34 1.32 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH33) (TRIP CKT-1, CLOSE MCB
QB1.43 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.30 1.29 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH34) (TRIP CKT-1, CLOSE MCB
QB1.44 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 1.27 1.25 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH35) (TRIP CKT-1, CLOSE MCB
QB1.45 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 1.24 1.22 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV BUS SECTION-02 (AH36) (TRIP CKT-1, CLOSE MCB
QB1.46 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.40 1.38 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8KV BUS RISER-02 (AH37) (EARTH SWITCH INTERLOCK, I/O MCB
QB1.47 SUB DCDB-1 123.3 1 1 123.3 101.5 1.21 1.46 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.72 0.71 4.20
BOX-1)
SUPPLY-1 FOR 13.8kV SWGR AUX-02 FEEDER (AH38) (TRIP CKT-1, CLOSE MCB
QB1.48 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.30 1.29 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH39) (TRIP CKT-1, CLOSE MCB
QB1.49 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH40) (TRIP CKT-1, CLOSE MCB
QB1.50 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 1.47 1.45 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH41) (TRIP CKT-1, CLOSE MCB
QB1.51 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 1.43 1.41 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH42) (TRIP CKT-1, CLOSE MCB
QB1.52 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 1.40 1.38 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH43) (TRIP CKT-1, CLOSE MCB
QB1.53 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH44) (TRIP CKT-1, CLOSE MCB
QB1.54 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 1.34 1.32 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV INCOMER T03 (AH45) (TRIP CKT-1, CLOSE CKT/CONTROL MCB
QB1.55 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.40 1.38 4.20
CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH46) (TRIP CKT-1, CLOSE MCB
QB1.56 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 1.27 1.25 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH47) (TRIP CKT-1, CLOSE MCB
QB1.57 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 1.24 1.22 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH48) (TRIP CKT-1, CLOSE MCB
QB1.58 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.30 1.29 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH49) (TRIP CKT-1, CLOSE MCB
QB1.59 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH50) (TRIP CKT-1, CLOSE MCB
QB1.60 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY FOR 13.8kV SWGR CAP. BANK-03 FEEDER (AH51) (TRIP CKT-1, CLOSE MCB
QB1.61 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)
SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE FEEDER BUS-3 (AH52) (TRIP CKT-1, MCB FUTURE
QB1.62 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP
CLOSE CKT/CONTROL CKT, BCU)
QB1.63 SUB DCDB-1 SUPPLY-1 TO ACDB 700 1 1 700 101.5 6.90 8.28 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 1.56 1.53 4.20
SUPPLY FOR 13.8KV AUTOMATIC CAPACITOR CONTROL SYSTEM PANEL (+ACCS) MCB
QB1.64 SUB DCDB-1 96.4 1 1 96.4 101.5 0.95 1.14 20 DP 2C 4 XLPE Air 51 1 17 0.91 0.45 0.41 20.88 5.878211 0.0999296 0.23 0.22 4.20
(HMI & PLC MODULE)
QB1.65 SUB DCDB-1 SUPPLY FOR HV BUSBAR PROTECTION PANEL (INDICATION CKT) 12.5 1 1 12.5 101.5 0.12 0.15 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.878211 0.1058078 0.03 0.03 4.20
8 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
SPARE MCB
QB1.67 SUB DCDB-1 20 DP SPARE
SUPPLY FOR TRANSFORMER-1 +RTCC/AVC PANEL (RELAY CKT & AUX CONTROL MCB
QB1.68 SUB DCDB-1 83.5 1 1 83.5 101.5 0.82 0.99 20 DP 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.878211 0.1058078 0.21 0.21 4.20
CKT)
SUPPLY FOR TRANSFORMER-2 +RTCC/AVC PANEL (RELAY CKT & AUX CONTROL MCB
QB1.69 SUB DCDB-1 83.5 1 1 83.5 101.5 0.82 0.99 20 DP 2C 4 XLPE Air 51 1 17 0.91 0.45 0.41 20.88 5.878211 0.0999296 0.20 0.19 4.20
CKT)
SUPPLY FOR TRANSFORMER-3 +RTCC/AVC PANEL (RELAY CKT & AUX CONTROL MCB
QB1.70 SUB DCDB-1 83.5 1 1 83.5 101.5 0.82 0.99 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.32 0.32 4.20
CKT)
QB1.71 SUB DCDB-1 SUPPLY-2 FOR HV BUSBAR-A PROTECTION PANEL (ZONE-2A PROTN CKT) 13 1 1 13 101.5 0.13 0.15 20 DP MCB 2C 4 XLPE Air 51 1 12 0.91 0.45 0.41 20.88 5.878211 0.0705385 0.02 0.02 4.20
QB1.72 SUB DCDB-1 SUPPLY-2 FOR HV BUSBAR-B PROTECTION PANEL (ZONE-2B PROTN CKT) 13 1 1 13 101.5 0.13 0.15 20 DP MCB 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.878211 0.0881732 0.03 0.03 4.20
QB1.73 SUB DCDB-1 SUPPLY-1 FOR SAS COMPUTER PANEL-1 1200 1 1 1200 101.5 11.82 14.19 20 DP MCB 2C 4 XLPE Air 51 1 17 0.91 0.45 0.41 20.88 5.878211 0.0999296 2.84 2.79 4.20
QB1.74 SUB DCDB-1 SUPPLY-1 FOR SAS COMPUTER PANEL-2 1200 1 1 1200 101.5 11.82 14.19 20 DP MCB 2C 4 XLPE Air 51 1 13 0.91 0.45 0.41 20.88 5.878211 0.0764167 2.17 2.14 4.20
QB1.75 SUB DCDB-1 SUPPLY-1 FOR SAS COMPUTER PANEL-3 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.878211 0.0881732 1.04 1.03 4.20
QB1.76 SUB DCDB-1 SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-A PANEL-1 200 1 1 200 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.44 0.44 4.20
QB1.77 SUB DCDB-1 SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-B PANEL-1 200 1 1 200 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.44 0.44 4.20
QB1.78 SUB DCDB-1 SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-A PANEL-2 150 1 1 150 101.5 1.48 1.77 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.33 0.33 4.20
QB1.79 SUB DCDB-1 SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-B PANEL-2 150 1 1 150 101.5 1.48 1.77 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.33 0.33 4.20
QB1.80 SUB DCDB-1 SUPPLY-1 FOR COMMON ALARM PANEL-1 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.22 0.22 4.20
QB1.81 SUB DCDB-1 SUPPLY-1 FOR COMMON ALARM PANEL-2 50 1 1 50 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.11 0.11 4.20
QB1.82 SUB DCDB-1 SUPPLY-1 FOR SAS CONSOLE DESK (55" MONITOR, 27" MONITOR-2Nos) 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.89 0.88 4.20
QB1.83 SUB DCDB-1 SUPPLY-1 FOR DC EMERGENCY LIGHTING FOR PROTECTION PANELS 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.09 0.09 4.20
QB1.84 SUB DCDB-1 SUPPLY FOR CHANGE OVER SCHEME-2 (ATS FOR DCDB-2) 50 1 1 50 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.11 0.11 4.20
QB1.87 SUB DCDB-1 SUPPLY FOR SDB-1 (SUB ACDB-1) 50 1 1 50 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.11 0.11 4.20
SUPPLY FOR 13.8 KV SWGR O/G FEEDER SECTION-1(AH01 TO AH08, AH10 TO MCB
QB1.88 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.52 0.51 4.20
AH17)
SUPPLY FOR 13.8 KV SWGR O/G FEEDER SECTION-2(AH19 TO AH28, AH30 TO MCB
QB1.89 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.52 0.51 4.20
AH35)
SUPPLY FOR 13.8 KV SWGR O/G FEEDER SECTION-3(AH37 TO AH44, AH46 TO MCB
QB1.90 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.52 0.51 4.20
AH52)
QB1.91 SUB DCDB-1 SUPPLY FOR 13.8 KV SWGR BUS SECTION-1 (AH18)(SYNCH TROLLY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.18 0.17 4.20
QB1.92 SUB DCDB-1 SUPPLY FOR 13.8 KV SWGR BUS SECTION (AH36)(SYNCH TROLLY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.18 0.17 4.20
QB1.93 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-3 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.07 0.07 4.20
QB1.94 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-4 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.07 0.07 4.20
QB1.95 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-5 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.07 0.07 4.20
QB1.96 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-6 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.07 0.07 4.20
9 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QB1.97 SUB DCDB-1 SUPPLY FOR RECEPTACLES IN CONTROL ROOM 200 1 1 200 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.44 0.44 4.20
QB1.98 SUB DCDB-1 SUPPLY FOR TRANSFORMER-1 MECHANICAL PROTECTION PANNEL 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Duct 47 1 16 0.91 0.45 0.41 19.25 5.878211 0.0940514 0.28 0.28 4.20
QB1.99 SUB DCDB-1 SUPPLY FOR TRANSFORMER-2 MECHANICAL PROTECTION PANNEL 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Duct 48 1 16 0.91 0.45 0.41 19.66 5.878211 0.0940514 0.28 0.28 4.20
QB1.100 SUB DCDB-1 SUPPLY FOR TRANSFORMER-3 MECHANICAL PROTECTION PANNEL 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Duct 49 1 16 0.91 0.45 0.41 20.07 5.878211 0.0940514 0.28 0.28 4.20
QB1.101 SUB DCDB-1 SUPPLY FOR LINE FEEDER (FUTURE)-E10 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB FUTURE
QB1.102 SUB DCDB-1 SUPPLY FOR LINE FEEDER -E08 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.28 0.28 4.20
QB1.103 SUB DCDB-1 SUPPLY FOR LINE FEEDER -E04 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.28 0.28 4.20
QB1.104 SUB DCDB-1 SUPPLY FOR LINE FEEDER -E01 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.28 0.28 4.20
QB1.105 SUB DCDB-1 SUPPLY FOR LINE FEEDER -E05 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.28 0.28 4.20
QB1.106 SUB DCDB-1 SUPPLY FOR LINE FEEDER(FUTURE)-E07 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB FUTURE
QA2.1 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER (FUTURE)-E07 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB FUTURE
QA2.2 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER-E05 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.3 SUB DCDB-2 SUPPLY-10 FOR HV TRANSFORMER T01-E03 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
10 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QA2.4 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER -E01 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.5 SUB DCDB-2 SUPPLY-10 FOR HV BUS COUPLER-A -E130 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.6 SUB DCDB-2 SUPPLY-10 FOR HV BUS SECTION-E220 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.7 SUB DCDB-2 SUPPLY-10 FOR HV BUS COUPLER-B -E230 DS/ES & H-ES MOTOR CKT 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.8 SUB DCDB-2 SUPPLY-10 FOR HV TRANSFORMER T02-E02 DS/ES & H-ES MOTOR CKT() 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.9 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER-E04 DS/ES & H-ES MOTOR CKT() 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.10 SUB DCDB-2 SUPPLY-10 FOR HV TRANSFORMER T03-E06 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.11 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER -E08 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20
QA2.12 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER (FUTURE)-E10 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB FUTURE
QA2.14 SUB DCDB-2 SUPPLY-8 FOR HV LINE FEEDER-E05 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.15 SUB DCDB-2 SUPPLY-8 FOR HV TRANSFORMER T01-E03 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.16 SUB DCDB-2 SUPPLY-8 FOR HV LINE FEEDER-E01 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.17 SUB DCDB-2 SUPPLY-8 FOR HV BUS COUPLER-A -E130 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.18 SUB DCDB-2 SUPPLY-8 FOR HV BUS SECTION-E220 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.19 SUB DCDB-2 SUPPLY-8 FOR HV BUS COUPLER-B -E230 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.20 SUB DCDB-2 SUPPLY-8 FOR HV TRANSFORMER T02-E02 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.21 SUB DCDB-2 SUPPLY-8 FOR HV LINE FEEDER-E04 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.22 SUB DCDB-2 SUPPLY-8 FOR HV TRANSFORMER T03-E06 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.23 SUB DCDB-2 SUPPLY-8 FOR HV LINE FEEDER S/S-E08 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20
QA2.24 SUB DCDB-2 SUPPLY-8 FOR HV FUTURE FEEDER-E10 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB FUTURE
QA2.25 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER (FUTURE)-E07 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB FUTURE
QA2.26 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER-E05 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.27 SUB DCDB-2 SUPPLY-9 FOR TRANSFORMER T01-E03 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.28 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER-E01 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.29 SUB DCDB-2 SUPPLY-9 FOR BUS COUPLER-A-E130 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.30 SUB DCDB-2 SUPPLY-9 FOR BUS SECTION-E220 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.31 SUB DCDB-2 SUPPLY-9 FOR BUS COUPLER-B -E230 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.32 SUB DCDB-2 SUPPLY-9 FOR TRANSFORMER T02-E02 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.33 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER-E04 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.34 SUB DCDB-2 SUPPLY-9 FOR TRANSFORMER T03-E06 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
11 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QA2.35 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER S/S-E08 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20
QA2.36 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER (FUTURE)-E10 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB FUTURE
SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-1(AH01) (TRIP CKT-2, MCB FUTURE
QA2.37 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP
INDICATION CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-1(AH02) (TRIP CKT-2, MCB FUTURE
QA2.38 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP
INDICATION CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-1(AH03) (TRIP CKT-2, MCB
QA2.39 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
INDICATION CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH04) (TRIP CKT-2, INDICATION MCB
QA2.40 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH05) (TRIP CKT-2, INDICATION MCB
QA2.41 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH06) (TRIP CKT-2, INDICATION
QA2.42 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH07) (TRIP CKT-2, INDICATION MCB
QA2.43 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH08) (TRIP CKT-2, INDICATION MCB
QA2.44 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH10) (TRIP CKT-2, INDICATION MCB
QA2.46 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH11) (TRIP CKT-2, INDICATION MCB
QA2.47 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH12) (TRIP CKT-2, INDICATION MCB
QA2.48 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH13) (TRIP CKT-2, INDICATION MCB
QA2.49 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH14) (TRIP CKT-2, INDICATION MCB
QA2.50 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH15) (TRIP CKT-2, INDICATION MCB
QA2.51 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR AUX. TFR. FEEDER BUS-1(AH16) (TRIP CKT-2, MCB
QA2.52 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
INDICATION CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR BUS METERING-01 (AH17) (EARTH SWITCH MCB
QA2.53 SUB DCDB-2 127 1 1 127.2 101.5 1.25 1.50 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.92 0.91 10.00
INTERLOCK, I/O BOX-1)
SUPPLY-2 FOR 13.8kV SWGR BUS RISER-01 FEEDER BUS-1(AH19) (EARTH MCB
QA2.55 SUB DCDB-2 126 1 1 126.0 101.5 1.24 1.49 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.91 0.90 10.00
SWITCH INTERLOCK, I/O BOX-1)
SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-2 (AH20) (TRIP CKT-2, MCB
QA2.56 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
INDICATION CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH21) (TRIP CKT-2, INDICATION MCB
QA2.57 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH22) (TRIP CKT-2, INDICATION MCB
QA2.58 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH23) (TRIP CKT-2, INDICATION MCB
QA2.59 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH24) (TRIP CKT-2, INDICATION MCB
QA2.60 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH25) (TRIP CKT-2, INDICATION MCB
QA2.61 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH26) (TRIP CKT-2, INDICATION MCB
QA2.62 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)
QA2.63 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-1 (SET-2) 61 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.44 0.44 4.20
QA2.64 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-2 (SET-2) 61 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.44 0.44 4.20
QA2.65 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-3 (SET-2) 61 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.44 0.44 4.20
12 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
SUPPLY FOR 13.8KV UNDER VOLTAGE LOAD SHEDDING PROTECTION PANEL MCB
QA2.66 SUB DCDB-2 73 1 1 72.5 101.5 0.71 0.86 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.52 0.52 4.20
(SET-2)
SUPPLY FOR 13.8KV UNDER VOLTAGE LOAD SHEDDING PROTECTION PANEL MCB
QA2.67 SUB DCDB-2 15 1 1 15.0 101.5 0.15 0.18 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.11 0.11 4.20
(INDICATION CKT FOR SET-1 & SET-2)
QA2.70 SUB DCDB-2 SUPPLY-2 FOR SAS CONSOLE DESK (55" MONITOR, 27" MONITOR-2Nos) 400 1 1 400.0 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 2.89 2.85 4.20
QA2.71 SUB DCDB-2 SUPPLY-2 FOR COMMON ALARM PANEL-2 50 1 1 50.0 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.36 0.36 4.20
QA2.72 SUB DCDB-2 SUPPLY-2 FOR COMMON ALARM PANEL-1 100 1 1 100.0 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.72 0.71 4.20
QA2.73 SUB DCDB-2 SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-B PANEL-2 150 1 1 150.0 101.5 1.48 1.77 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 1.08 1.07 4.20
QA2.74 SUB DCDB-2 SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-A PANEL-2 150 1 1 150.0 101.5 1.48 1.77 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 1.08 1.07 4.20
QA2.75 SUB DCDB-2 SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-B PANEL-1 200 1 1 200.0 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 1.45 1.42 4.20
QA2.76 SUB DCDB-2 SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-A PANEL-1 200 1 1 200.0 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 1.45 1.42 4.20
QA2.77 SUB DCDB-2 SUPPLY-2 FOR SAS COMPUTER PANEL-3 500 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 6 XLPE Air 67 1 52 0.91 0.45 0.41 27.44 3.927308 0.2042200 2.41 2.38 4.20
QA2.78 SUB DCDB-2 SUPPLY-2 FOR SAS COMPUTER PANEL-2 1200 1 1 1200.0 101.5 11.82 14.19 20 DP MCB 2C 10 XLPE Air 88 1 52 0.91 0.45 0.41 36.04 2.333433 0.1213385 3.44 3.39 4.20
QA2.79 SUB DCDB-2 SUPPLY-2 FOR SAS COMPUTER PANEL-1 1200 1 1 1200.0 101.5 11.82 14.19 20 DP MCB 2C 10 XLPE Air 88 1 52 0.91 0.45 0.41 36.04 2.333433 0.1213385 3.44 3.39 4.20
QA2.81 SUB DCDB-2 SUPPLY FOR SDB-2 (SUB ACDB-2) 50 1 1 50.0 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.36 0.36 4.20
QA2.82 SUB DCDB-2 SUPPLY FOR CONTROL CABINET 110/13.8KV T01 (+MK) 593 1 1 592.8 101.5 5.84 7.01 20 DP MCB 2C 6 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 3.927308 0.2042200 2.86 2.82 4.20
QA2.83 SUB DCDB-2 SUPPLY FOR CONTROL CABINET 110/13.8KV T02 (+MK) 593 1 1 592.8 101.5 5.84 7.01 20 DP MCB 2C 6 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 3.927308 0.2042200 2.86 2.82 4.20
QA2.84 SUB DCDB-2 SUPPLY FOR CONTROL CABINET 110/13.8KV T03 (+MK) 593 1 1 592.8 101.5 5.84 7.01 20 DP MCB 2C 6 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 3.927308 0.2042200 2.86 2.82 4.20
QA2.85 SUB DCDB-2 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T01 78 1 1 78.0 101.5 0.77 0.92 20 DP MCB 2C 4 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 5.878211 0.3056670 0.56 0.56 4.20
QA2.86 SUB DCDB-2 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T02 78 1 1 78.0 101.5 0.77 0.92 20 DP MCB 2C 4 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 5.878211 0.3056670 0.56 0.56 4.20
QA2.87 SUB DCDB-2 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T03 78 1 1 78.0 101.5 0.77 0.92 20 DP MCB 2C 4 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 5.878211 0.3056670 0.56 0.56 4.20
QA2.91 SUB DCDB-2 SUPPLY-2 TO ACDB 50 1 1 50.0 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.36 0.36 4.20
QA2.95 SUB DCDB-2 SUPPLY-2 FOR AMI PANEL-1 118 1 1 118.0 101.5 1.16 1.40 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.85 0.84 4.20
QA2.96 SUB DCDB-2 SUPPLY-2 FOR AMI PANEL-2 118 1 1 118.0 101.5 1.16 1.40 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.85 0.84 4.20
13 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QA2.97 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-1 30 1 1 30.0 101.5 0.30 0.35 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.22 0.21 4.20
QA2.98 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-2 30 1 1 30.0 101.5 0.30 0.35 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.22 0.21 4.20
QA2.99 SUB DCDB-2 SUPPLY-2 FOR DC EMERGENCY LIGHTING FOR CONTROL PANELS 40 1 1 40.0 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.29 0.28 4.20
QA2.100 SUB DCDB-2 SUPPLY-2 FOR DC EMERGENCY LIGHTING FOR PROTECTION PANELS 40 1 1 40.0 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.29 0.28 4.20
QB2.1 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER (FUTURE)-E07 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB FUTURE
QB2.2 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER-E05 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.3 SUB DCDB-2 SUPPLY-7 FOR HV TRANSFORMER T01-E03 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.4 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER-E01 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.5 SUB DCDB-2 SUPPLY-7 FOR HV BUS COUPLER-A -E130 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.6 SUB DCDB-2 SUPPLY-7 FOR HV BUS SECTION-E220 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.7 SUB DCDB-2 SUPPLY-7 FOR HV BUS COUPLER-B -E230 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.8 SUB DCDB-2 SUPPLY-7 FOR HV TRANSFORMER T02-E02 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.9 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER-E04 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.10 SUB DCDB-2 SUPPLY-7 FOR HV TRANSFORMER T03-E06 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.11 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER S/S-E08 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00
QB2.12 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER (FUTURE)-E10 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB FUTURE
14 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QB2.13 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER FUTURE)-E07 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB FUTURE
QB2.14 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER-E05 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 0.21 0.21 4.20
QB2.15 SUB DCDB-2 SUPPLY-11 FOR HV TRANSFORMER T01-E03 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.16 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER-E01 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.17 SUB DCDB-2 SUPPLY-11 FOR HV BUS COUPLER-A-E130 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.18 SUB DCDB-2 SUPPLY-11 FOR HV BUS SECTION-E220 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.19 SUB DCDB-2 SUPPLY-11 FOR HV BUS COUPLER-B-E230 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.20 SUB DCDB-2 SUPPLY-11 FOR HV TRANSFORMER T02-E02 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.21 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER-E04 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.22 SUB DCDB-2 SUPPLY-11 FOR HV TRANSFORMER T03-E06 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.23 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER -E08 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.24 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER (FUTURE)-E10 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB FUTURE
QB2.25 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER (FUTURE)-E07 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB FUTURE
QB2.26 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER-E05 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.27 SUB DCDB-2 SUPPLY-12 FOR HV TRANSFORMER T01-E03 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.28 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER-E01 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.29 SUB DCDB-2 SUPPLY-12 FOR HV BUS COUPLER-A -E130 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.30 SUB DCDB-2 SUPPLY-12 FOR HV BUS SECTION-E220 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.31 SUB DCDB-2 SUPPLY-12 FOR HV BUS COUPLER-B -E230 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.32 SUB DCDB-2 SUPPLY-12 FOR HV TRANSFORMER T02-E02 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.33 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER-E04 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.34 SUB DCDB-2 SUPPLY-12 FOR HV TRANSFORMER T03-E06 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.35 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER S/S-E08 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20
QB2.36 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER (FUTURE)-E10 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB FUTURE
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH27) (TRIP CKT-2, INDICATION MCB
QB2.37 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH28) (TRIP CKT-2, INDICATION MCB
QB2.38 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR I/C FEEDER (AH29) (TRIP CKT-2, INDICATION CKT, MCB
QB2.39 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH30) (TRIP CKT-2, INDICATION MCB
QB2.40 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH31) (TRIP CKT-2, INDICATION MCB
QB2.41 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH32) (TRIP CKT-2, INDICATION MCB
QB2.42 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH33) (TRIP CKT-2, INDICATION MCB
QB2.43 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
15 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH34) (TRIP CKT-2, INDICATION MCB
QB2.44 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH35) (TRIP CKT-2, INDICATION MCB
QB2.45 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR BUS SECTION-02 (AH36) (TRIP CKT-2, INDICATION MCB
QB2.46 SUB DCDB-2 717.8 1 1 717.8 101.5 7.07 8.49 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.79 2.75 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR BUS RISER-01 FEEDER BUS-1(AH37) (EARTH MCB
QB2.47 SUB DCDB-2 126 1 1 126 101.5 1.24 1.49 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.48 4.20
SWITCH INTERLOCK, I/O BOX-1SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR AUX. TFR. FEEDER BUS-2(AH38) (TRIP CKT-2, MCB
QB2.48 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
INDICATION CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH39) (TRIP CKT-2, INDICATION MCB
QB2.49 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH40) (TRIP CKT-2, INDICATION MCB
QB2.50 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH41) (TRIP CKT-2, INDICATION MCB
QB2.51 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH42) (TRIP CKT-2, INDICATION MCB
QB2.52 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH43) (TRIP CKT-2, INDICATION MCB
QB2.53 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH44) (TRIP CKT-2, INDICATION MCB
QB2.54 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH45) (TRIP CKT-2, INDICATION MCB
QB2.55 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH46) (TRIP CKT-2, INDICATION MCB
QB2.56 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH47) (TRIP CKT-2, INDICATION MCB
QB2.57 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH48) (TRIP CKT-2, INDICATION MCB
QB2.58 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH49) (TRIP CKT-2, INDICATION MCB
QB2.59 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH50) (TRIP CKT-2, INDICATION MCB
QB2.60 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-3(AH51) (TRIP CKT-2, MCB
QB2.61 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
INDICATION CKT, BCU AUXILIARY SUPPLY)
SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-3(AH52) (TRIP CKT-2, MCB FUTURE
QB2.62 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP
INDICATION CKT, BCU AUXILIARY SUPPLY)
SUPPLY FOR FUTURE FEEDER-E07 PROTECTION PANEL SET-2 (MAIN-2 PROTN MCB FUTURE
QB2.63 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP
CKT & IN/OUT RELAY CKT)
SUPPLY FOR SPARE FEEDER -E05 PROTECTION PANEL SET-2 (MAIN-2 PROTN MCB
QB2.64 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
CKT & IN/OUT RELAY CKT)
SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL SET-2 (MAIN-2 PROTN CKT MCB
QB2.66 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
& IN/OUT RELAY CKT)
SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL SET-2 (MAIN-2 PROTN CKT MCB
QB2.68 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
& IN/OUT RELAY CKT)
SUPPLY FOR SPARE FEEDER-E08 PROTECTION PANEL SET-2 (MAIN-2 PROTN MCB
QB2.70 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
CKT & IN/OUT RELAY CKT)
SUPPLY FOR FUTURE FEEDER- E10 PROTECTION PANEL SET-2 (MAIN-2 PROTN MCB FUTURE
QB2.71 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP
CKT & IN/OUT RELAY CKT)
SUPPLY FOR FUTURE FEEDER-E07 PROTECTION PANEL SET-1 & SET- MCB FUTURE
QB2.72 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP
2(INDICATION CKT)
SUPPLY FOR SPARE FEEDER -E05 PROTECTION PANEL SET-1 & SET- MCB
QB2.73 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
2(INDICATION CKT)
SUPPLY FOR TRANSFROMER T01-E03 PROTECTION PANEL SET-1 & SET- MCB
QB2.74 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
2(INDIACTION CKT)
16 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL SET-1 & SET-2(INDICATION MCB
QB2.75 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
CKT)
SUPPLY FOR TRANSFORMER T02-E02 PROTECTION PANEL SET-1 & SET- MCB
QB2.76 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
2(INDIACTION CKT)
SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL SET-1 & SET-2(INDICATION MCB
QB2.77 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
CKT)
SUPPLY FOR TRANSFORMER T03-E06 PROTECTION PANEL SET-1 & SET- MCB
QB2.78 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
2(INDIACTION CKT)
SUPPLY FOR SPARE FEEDER-E08 PROTECTION PANEL SET-1 & SET-2 MCB
QB2.79 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
(INDICATION CKT)
SUPPLY FOR FUTURE FEEDER-E10 PROTECTION PANEL SET-1 & SET- MCB FUTURE
QB2.80 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP
2(INDICATION CKT)
QB2.84 SUB DCDB-2 SUPPLY FOR LINE FEEDER(FUTURE)-E10 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 105.5 1.20 1.44 20 DP MCB FUTURE
QB2.85 SUB DCDB-2 SUPPLY FOR LINE FEEDER-E08 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20
QB2.86 SUB DCDB-2 SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20
QB2.87 SUB DCDB-2 SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20
QB2.88 SUB DCDB-2 SUPPLY FOR LINE FEEDER-E05 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20
QB2.89 SUB DCDB-2 SUPPLY FOR LINE FEEDER(FUTURE)-E07 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB FUTURE
QB2.90 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-1 (INDICATION CKT) 2.25 1 1 2.25 101.5 0.02 0.03 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.01 0.01 4.20
QB2.91 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-2 (INDICATION CKT)" 2.25 1 1 2.25 101.5 0.02 0.03 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.01 0.01 4.20
QB2.92 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-3 (INDICATION CKT)" 2.25 1 1 2.25 101.5 0.02 0.03 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.01 0.01 4.20
SUPPLY FOR 13.8 KV BUSBAR PROTECTION PANEL (INDICATION SET-1 & SET-2 MCB
QB2.96 SUB DCDB-2 1.25 1 1 1.25 105.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 0.00 0.00 4.20
CKT)"
QB2.97 SUB DCDB-2 SUPPLY FOR 13.8 KV BUSBAR PROTECTION PANEL (INDICATION SET-3 CKT)" 1.25 1 1 1.25 101.5 0.01 0.01 20 DP MCB 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 0.00 0.00 4.20
QB2.100 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-3 31 1 1 31 103.5 0.30 0.36 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.08 0.08 4.20
QB2.101 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-4 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.09 0.08 4.20
QB2.102 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-5 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.09 0.08 4.20
QB2.103 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-6 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 21 0.91 0.45 0.41 20.88 5.878211 0.1234424 0.09 0.09 4.20
QB2.104 SUB DCDB-2 13.8kV BBP(1A)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 22 0.91 0.45 0.41 20.88 5.878211 0.1293206 0.05 0.05 4.20
QB2.105 SUB DCDB-2 13.8kV BBP(1B)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 23 0.91 0.45 0.41 20.88 5.878211 0.1351989 0.05 0.05 4.20
17 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QB2.106 SUB DCDB-2 13.8kV BBP(1C)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 0.05 0.05 4.20
QA.001 SUB DCDB-ELP HV GIS ROOM 800 1 1 800 101.5 7.881773 9.458128 20 DP MCB 2C 6 XLPE Air 67 1 52 0.91 0.45 0.41 27.44 3.927308 0.2042200 3.86 3.81 4.20
QA.002 SUB DCDB-ELP HV GIS ROOM 800 1 1 800 101.5 7.881773 9.458128 20 DP MCB 2C 6 XLPE Air 67 1 52 0.91 0.45 0.41 27.44 3.927308 0.2042200 3.86 3.81 4.20
QA.003 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 2.89 2.85 4.20
QA.004 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 2.89 2.85 4.20
QA.005 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 51 0.91 0.45 0.41 20.88 5.878211 0.2997888 2.84 2.79 4.20
QA.006 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 50 0.91 0.45 0.41 20.88 5.878211 0.2939106 2.78 2.74 4.20
QA.007 SUB DCDB-ELP STAIR CASE 300 1 1 300 101.5 2.955665 3.546798 20 DP MCB 2C 4 XLPE Air 51 1 49 0.91 0.45 0.41 20.88 5.878211 0.2880323 2.04 2.01 4.20
QA.008 SUB DCDB-ELP TELECOM ROOM 200 1 1 200 101.5 1.970443 2.364532 20 DP MCB 2C 4 XLPE Air 51 1 48 0.91 0.45 0.41 20.88 5.878211 0.2821541 1.33 1.31 4.20
QA.009 SUB DCDB-ELP FM ROOM 300 1 1 300 101.5 2.955665 3.546798 20 DP MCB 2C 4 XLPE Air 51 1 47 0.91 0.45 0.41 20.88 5.878211 0.2762759 1.96 1.93 4.20
QA.010 SUB DCDB-ELP RECORD ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 46 0.91 0.45 0.41 20.88 5.878211 0.2703977 2.56 2.52 4.20
QA.011 SUB DCDB-ELP PUSH BUTTON FOR GIS ROOM CABLE BASEMENT 100 1 1 100 101.5 0.985222 1.182266 20 DP MCB 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 0.63 0.62 4.20
QA.012 SUB DCDB-ELP PUSH BUTTON FOR SWG ROOM 100 1 1 100 101.5 0.985222 1.182266 20 DP MCB 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 0.61 0.60 4.20
QA.013 SUB DCDB-ELP SWGR CABLE BASEMENT 100 1 1 100 101.5 0.985222 1.182266 20 DP MCB 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 0.60 0.59 4.20
QA.014 SUB DCDB-ELP FM ROOM1 500 1 1 500 101.5 4.926108 5.91133 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 2.92 2.88 4.20
QA.015 SUB DCDB-ELP SWGR CABLE BASEMENT 500 1 1 500 101.5 4.926108 5.91133 20 DP MCB 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 2.85 2.81 4.20
QA.016 SUB DCDB-ELP BASEMENT CORRIDOOR 500 1 1 500 101.5 4.926108 5.91133 20 DP MCB 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 2.78 2.74 4.20
QA.017 SUB DCDB-ELP WORKSHOP 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 2.22 2.19 4.20
18 of 19
CB DATA Cable Data Derating Factors Permi.
DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage
Factor
Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C
QA.018 SUB DCDB-ELP EQUIPMENT ROOM 300 1 1 300 101.5 2.955665 3.546798 20 DP MCB 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 1.63 1.60 4.20
QB.001 SUB DCDB-ELP MV SWGR ROOM 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.56 1.53 4.20
QB.002 SUB DCDB-ELP MV SWGR ROOM 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 27 0.91 0.45 0.41 20.88 5.878211 0.1587117 1.50 1.48 4.20
QB.003 SUB DCDB-ELP STAIR CASE 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 26 0.91 0.45 0.41 20.88 5.878211 0.1528335 1.08 1.07 4.20
QB.004 SUB DCDB-ELP STAIR CASE 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 25 0.91 0.45 0.41 20.88 5.878211 0.1469553 1.04 1.03 4.20
QB.005 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 1.33 1.31 4.20
QB.006 SUB DCDB-ELP TOILET 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 23 0.91 0.45 0.41 20.88 5.878211 0.1351989 1.60 1.57 4.20
QB.007 SUB DCDB-ELP PUCH BUTTON FOR SWGR CABLE BASEMENT 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 22 0.91 0.45 0.41 20.88 5.878211 0.1293206 0.31 0.30 4.20
QB.008 SUB DCDB-ELP PUSH BUTTON FOR GIS ROOM 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 21 0.91 0.45 0.41 20.88 5.878211 0.1234424 0.29 0.29 4.20
QB.009 SUB DCDB-ELP PUSH BUTTON FOR CONTROL ROOM 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.28 0.27 4.20
QB.010 SUB DCDB-ELP GROUND ENTERANCE 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.11 1.10 4.20
QB.011 SUB DCDB-ELP GIS ROOM CABLE BASEMENT 600 1 1 600 101.5 5.91 7.09 20 DP MCB 2C 4 XLPE Air 51 1 21 0.91 0.45 0.41 20.88 5.878211 0.1234424 1.75 1.73 4.20
QB.012 SUB DCDB-ELP GIS ROOM CABLE BASEMENT 600 1 1 600 101.5 5.91 7.09 20 DP MCB 2C 4 XLPE Air 51 1 22 0.91 0.45 0.41 20.88 5.878211 0.1293206 1.83 1.81 4.20
QB.013 SUB DCDB-ELP BASEMENT LOBBY 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 23 0.91 0.45 0.41 20.88 5.878211 0.1351989 0.32 0.31 4.20
QB.014 SUB DCDB-ELP BATTERY ROOM 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 1.00 0.99 4.20
QB.015 SUB DCDB-ELP COMMUNICATION ROOM 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 25 0.91 0.45 0.41 20.88 5.878211 0.1469553 1.04 1.03 4.20
QB.016 SUB DCDB-ELP ENTRANCE LOBBY 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 26 0.91 0.45 0.41 20.88 5.878211 0.1528335 1.45 1.42 4.20
QB.017 SUB DCDB-ELP EXTERNAL BATTERY ROOM 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 27 0.91 0.45 0.41 20.88 5.878211 0.1587117 1.13 1.11 4.20
19 of 19
CERT'D
APPR'D
CHK'D
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION
REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF UNIFIED LV AC CABLE SIZING CALCULATIONS
FOR ORDERING
MATERIALS UNTIL (COA & WOA)
CERTIFIED AND
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.
DMS EXCEL
Design Basis for cables
1- Cables are sized based on SEC Standard TES-P-119.29 ( LV Cable Sizing & Selection )
2- Formula used within this sheet are that provided by SEC Standard TES-P-119.29
3- As per 01-TMSS-01, ambient temperature of 40˚C is considered for cable sizing
4- For main incomer cables, the short circuit withstand current for Cu. conductors, XLPE Insulated is
given by the formula:-
0.143 S
I SC =
t
Where:-
Isc : Short Time Rating Current in kA
S : Conductor Cross-Section Area in mm²
t : Current Duration in Seconds.
So, Isc for 1C X 630 mm² Cable, for 3 Second :-
0.143 X 630
Isc = = 52.015 KA
𝟑𝟑
The secondary side of neutral cable size will be the same size of phase cable (1Cx630mm2) and it will withstand
the S.C rating of 25 KA.
Thus, the given cable can withstand the system fault level (25 kA ).
5- Cable sizes given are subject to change as per load updates.
6- Indicated lengthes are approximate, the actual route length may increase/decrease as per actual site conditions.
7- As per SEC standard No ( TES-P-119.29 ),Clause(7.1.9),Page 11, voltage drops (Regulation in %) shall be limited as:-
a)Total voltage drop from Station Transformer to loads not exceed 5%
b) Station Transformer to main distribution board (MD 0.80%
c) MDB to various loads
4.20%
(Motor starting voltage drop limited to 12.5%)
8- As per SEC standard No ( TES-P-119.29 ),Clause(7.2),Page 10 , Grouping Correction Factor as below:-
a) Cables from Station Transformer to main distribution board
- 0.87 for single core cable with trefoil touching configuration
b) Cables from main distribution board to various loads
- 0.45 for cable up to 16 mm2
- 0.70 for cable above 25 mm2
9- Main AC Distribution panel Bus bars shall withstand full available short circuit current and shall not
be less than 25KA as per TES-P-119.30 Rev.02, Clause 3.2.2
10- Short circuit current rating of AC sub Distribution panels shall be as per design calculations and
NGSA approval.
Reference Documents
Permi
UNIT TOTAL TOTAL
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
CU / XLPE /
001 Q101 AUX.T1 ACDB BUS-A 425 1 425 500 3 400 722 866 1000AT/1000AF ACB 4P 722 0.85 0.53 1C 630 Duct 619 2 54 0.0454 0.092 1 0.87 1 1 0.87 1077.06 2.94 0.73 0.80
PVC
CU / XLPE /
002 Q102 AUX.T2 ACDB BUS-B 425 1 425 500 3 400 722 866 1000AT/1000AF ACB 4P 722 0.85 0.53 1C 630 Duct 619 2 57 0.0454 0.092 1 0.87 1 1 0.87 1077.06 3.10 0.78 0.80
PVC
MAIN ACDB
MDP.A17 Q.A17 SPARE 3 400 20 MCB TPN
BUS A
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
MAIN ACDB
MDP.A19 Q.A19 SPARE 3 400 32AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A20 Q.A20 SPARE 3 400 40AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A21 Q.A21 SPARE 3 400 63AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A22 Q.A22 SPARE 3 400 63AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A23 Q.A23 SPARE 3 400 125AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A24 Q.A24 SPARE 3 400 160AT/250AF MCCB TPN
BUS A
MAIN ACDB
MDP.A25 Q.A25 SPARE 3 400 200AT/250AF MCCB TPN
BUS A
MAIN ACDB
MDP.A26 Q.A26 SPARE 3 400 400AT/400AF MCCB TPN
BUS A
MAIN ACDB
MDP.B11 Q.B11 SPARE 0 3 400 63AT/160AF MCCB TPN
BUS B
MAIN ACDB
MDP.B15 Q.B15 SPARE 0 3 400 20 MCB TPN 1
BUS B
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
MAIN ACDB
MDP.B20 Q.B20 SPARE 3 400 32AT/160AF MCCB TPN
BUS B
MAIN ACDB
MDP.B21 Q.B21 SPARE 3 400 40AT/160AF MCCB TPN
BUS B
MAIN ACDB
MDP.B22 Q.B22 SPARE 3 400 50AT/160AF MCCB TPN
BUS B
MAIN ACDB
MDP.B23 Q.B23 SPARE 3 400 63AT/160AF MCCB TPN
BUS B
MAIN ACDB
MDP.B24 Q.B24 SPARE 3 400 125AT/160AF MCCB TPN
BUS B
MAIN ACDB
MDP.B25 Q.B25 SPARE 3 400 160AT/250AF MCCB TPN
BUS B
MAIN ACDB
MDP.B26 Q.B26 SPARE 3 400 200AT/250AF MCCB TPN
BUS B
MAIN ACDB
MDP.B27 Q.B27 SPARE 3 400 400AT/400AF MCCB TPN
BUS B
MDP.A3 QC ACDB SUPPLY FOR AC SDP-1 70.48 1 70.48 82.92 3 400 119.68 143.62 160AT/250AF MCCB TPN
CU / XLPE /
SDP.C14 Q.C14 SDP-1 400V,AC SUPPLY FOR GIS ROOM EXHAUST FAN 2.33 0 2.33 2.74 3 400 3.96 4.75 20 MCB TPN 3.96 0.85 0.53 4C 10 Duct 53 1 95 2.334 0.103 1 0.45 1 1 0.45 23.85 1.33 0.33 3.40
PVC
CU / XLPE /
SDP.C16 Q.C16 SDP-1 400V, AC SUPPLY FOR SECURITY SYSTEM 3.17 1 3.17 3.73 3 400 5.38 6.46 20 MCB TPN 5.38 0.85 0.53 4C 10 Air 70 1 30 2.334 0.103 1 0.45 1 1 0.45 31.50 0.57 0.14 3.40
PVC
Permi
UNIT TOTAL TOTAL
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
400V, AC SUPPLY FOR BASEMENT EXHAUST FAN CU / XLPE /
SDP.C17 Q.C17 SDP-1 2.24 1 2.24 2.64 3 400 3.80 4.56 20 MCB TPN 3.80 0.85 0.53 4C 10 Air 70 1 70 2.334 0.103 1 0.45 1 1 0.45 31.50 0.94 0.23 3.40
03 PVC
CU / XLPE /
SDP.C21 Q.C21 SDP-1 ELECTRICAL DUCT HEATER 10.00 0 10.00 10.00 3 400 14.43 17.32 20 MCB TPN 14.43 0.85 0.53 4C 4 Air 40 1 41 5.878 0.113 1 0.45 1 1 0.45 18.00 5.18 1.30 3.40
PVC
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
230VAC SUPPLY FOR CONTROL ROOM
PANELS(HTR,LTNG,SCKT) CU / XLPE /
SDP.C41 Q.C41 SDP-1 1.47 0.27 1.47 1.73 1 230 7.52 9.02 20 MCB SPN 7.52 0.85 0.53 2C 4 Air 48 1 20 5.878 0.113 1 0.45 1 1 0.45 21.60 1.52 0.66 3.40
(+R01.2,+R01.1,+R03.2,+R03.1,+R05.2,+R05.1,FUT,F PVC
UT)
230V AC SUPPLY-1 FOR TR-1 OLTC LIGHTING & CU / XLPE /
SDP.C42 Q.C42 SDP-1 0.37 0.5 0.37 0.44 1 230 1.89 2.27 20 MCB SPN 1.89 0.85 0.53 2C 4 Air 48 1 89 5.878 0.113 1 0.45 1 1 0.45 21.60 1.70 0.74 3.40
HEATER. PVC
SDP.C48 Q.C48 SDP-1 230VAC SUPPLY FOR FUTURE PANELS 0.00 0.00 1 230 20 MCB SPN
SDP.C49 Q.C49 SDP-1 230VAC SUPPLY FOR FUTURE PANELS 0.00 0.00 1 230 20 MCB SPN
CU / XLPE /
SDP.C63 Q.C63 SDP-1 230V AC SUPPLY FOR BASEMENT SUMP PUMP-1 1.30 0.00 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 32 5.878 0.113 1 0.45 1 1 0.45 21.60 2.15 0.94 3.40
PVC
CU / XLPE /
SDP.C64 Q.C64 SDP-1 230V AC SUPPLY FOR BASEMENT SUMP PUMP-2 1.30 0.00 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 35 5.878 0.113 1 0.45 1 1 0.45 21.60 2.35 1.02 3.40
PVC
CU / XLPE /
SDP.C65 Q.C65 SDP-1 230V AC SUPPLY FOR BASEMENT SUMP PUMP-3 1.30 0.00 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 65 5.878 0.113 1 0.45 1 1 0.45 21.60 4.37 1.90 3.40
PVC
CU / XLPE /
SDP.C66 Q.C66 SDP-1 230V AC SUPPLY FOR BASEMENT SUMP PUMP-4 1.30 0.00 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 74 5.878 0.113 1 0.45 1 1 0.45 21.60 4.97 2.16 3.40
PVC
Permi
UNIT TOTAL TOTAL
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
MDP.B3 QD ACDB SUPPLY FOR SDP-2 62.76 1 62.76 73.83 3 400 106.57 127.88 160AT/250AF MCCB TPN
CU / XLPE /
SDP.D16 QD.16 SDP-2 400 VAC SUPPLY FOR (DCDB-1 ) PANELS 0.42 0.5 0.42 0.49 3 400 0.71 0.86 20 MCB TPN 0.71 0.85 0.53 4C 4 Air 40 1 31 5.878 0.113 1 0.45 1 1 0.45 18.00 0.19 0.05 3.40
PVC
CU / XLPE /
SDP.D17 QD.17 SDP-2 400 VAC SUPPLY FOR (DCDB-2 ) PANELS 0.4 0.5 0.42 0.49 3 400 0.71 0.86 20 MCB TPN 0.71 0.85 0.53 4C 4 Air 40 1 30 5.878 0.113 1 0.45 1 1 0.45 18.00 0.19 0.05 3.40
PVC
Permi
UNIT TOTAL TOTAL
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
CU / XLPE /
SDP.D18 QD.18 SDP-2 400 VAC SUPPLY FOR (DCDB ) PANEL 0.4 0.5 0.42 0.49 3 400 0.71 0.86 20 MCB TPN 0.71 0.85 0.53 4C 4 Air 40 1 29 5.878 0.113 1 0.45 1 1 0.45 18.00 0.18 0.05 3.40
PVC
CU / XLPE /
SDP.D27 QD.27 SDP-2 400V AC SUPPLY FOR WATER BOOSTER PUMP. 2.50 0 2.50 2.94 3 400 4.25 5.09 20 MCB TPN 4.25 0.85 0.53 4C 4 Air 40 1 50 5.878 0.113 1 0.45 1 1 0.45 18.00 1.86 0.465 3.40
PVC
230VAC SUPPLY FOR CONTROL ROOM PANELS
CU / XLPE /
SDP.D28 QD.28 SDP-2 (HTR,LTNG,SCKT)(+RTM-1,+RTM-2,+RTM-3,+RTM- 1.01 0.27 1.01 1.19 1 230 5.17 6.20 20 MCB SPN 5.17 0.85 0.53 2C 4 Air 48 1 19 5.878 0.113 1 0.45 1 1 0.45 21.60 0.99 0.432 3.40
PVC
4,+RTM-5,+RTM-6)
CU / XLPE /
SDP.D29 QD.29 SDP-2 230V,AC SUPPLY FOR KITCHEN EXHAUST FAN 0.02 0 0.02 0.03 1 230 0.11 0.14 20 MCB SPN 0.11 0.85 0.53 2C 4 Air 48 1 34 5.878 0.113 1 0.45 1 1 0.45 21.60 0.04 0.02 3.40
PVC
CU / XLPE /
SDP.D33 QD.33 SDP-2 230V AC SUPPLY FOR TOILET EXHAUST FAN 0.13 0 0.13 0.16 1 230 0.68 0.81 20 MCB SPN 0.68 0.85 0.53 2C 4 Duct 38 1 30 5.878 0.113 1 0.45 1 1 0.45 17.10 0.20 0.09 3.40
PVC
CU / XLPE /
SDP.D34 QD.34 SDP-2 230V AC SUPPLY FOR WATER TRANSFER PUMP 1.10 0 1.10 1.29 1 230 5.63 6.75 20 MCB SPN 5.63 0.85 0.53 2C 10 Duct 63 1 48 2.334 0.103 1 0.45 1 1 0.45 28.35 1.10 0.48 3.40
PVC
CU / XLPE /
SDP.D39 QD.39 SDP-2 230VAC SUPPLY-1 FOR AMI (RMR PANEL) 0.42 0.27 0.42 0.49 1 230 2.15 2.58 20 MCB SPN 2.15 0.85 0.53 2C 4 Air 48 1 21 5.878 0.113 1 0.45 1 1 0.45 21.60 0.46 0.20 3.40
PVC
Permi
UNIT TOTAL TOTAL
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
CU / XLPE /
SDP.D40 QD.40 SDP-2 230VAC SUPPLY-1 FOR AMI (SWITCH PANEL) 0.42 0.27 0.42 0.49 1 230 2.15 2.58 20 MCB SPN 2.15 0.85 0.53 2C 4 Air 48 1 22 5.878 0.113 1 0.45 1 1 0.45 21.60 0.48 0.21 3.40
PVC
CU / XLPE /
SDP.D49 QD.49 SDP-2 230V AC SUPPLY FOR BASEMENT SUMP PUMP-5 1.30 0 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 82 5.878 0.113 1 0.45 1 1 0.45 21.60 5.51 2.40 3.40
PVC
CU / XLPE /
SDP.D50 QD.50 SDP-2 230V AC SUPPLY FOR BASEMENT SUMP PUMP-6 1.30 0 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 71 5.878 0.113 1 0.45 1 1 0.45 21.60 4.77 2.08 3.40
PVC
CU / XLPE /
SDP.D51 QD.51 SDP-2 230V AC SUPPLY FOR BASEMENT SUMP PUMP-7 1.30 0 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 65 5.878 0.113 1 0.45 1 1 0.45 21.60 4.37 1.90 3.40
PVC
CU / XLPE /
SDP.D52 QD.52 SDP-2 230V AC SUPPLY FOR BASEMENT SUMP PUMP-8 1.30 0 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 77 5.878 0.113 1 0.45 1 1 0.45 21.60 5.18 2.25 3.40
PVC
CU / XLPE /
SDP.D53 QD.53 SDP-2 230V AC SUPPLY FOR HAND DRYER 1.28 1 1.28 1.51 1 230 6.55 7.86 20 MCB SPN 6.55 0.85 0.53 2C 4 Air 48 1 30 5.878 0.113 1 0.45 1 1 0.45 21.60 1.99 0.86 3.40
PVC
CU / XLPE /
SDP.D54 QD.54 SDP-2 230V AC SUPPLY FOR GATE MOTOR-2 1.00 0 1.00 1.18 1 230 5.12 6.14 20 MCB SPN 5.12 0.85 0.53 2C 4 Air 48 1 100 5.878 0.113 1 0.45 1 1 0.45 21.60 5.17 2.25 3.40
PVC
DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible
FACTOR
PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
* Diversity Factor Used Only For Sizing The Sub Distribution Panels Incomer C.B.
Notes:
1) All the cable lengths shown here are tentative and shall vary according to the approved cable raceway layouts.
2) All the technical parameters of the cables mentioned here is for XLPE cables@90ºC
3) The ambient temperature is considerd as 40ºC as per 01-TMSS-01
4) Grouping Correction factors is considerd as per Clause 7.1.7 in TES-119-29