APPENDIX - XX

THE UNIFICATION OF SUBSTATION AC/DC AUXILIARY SYSTEM

ENGINEERING & DESIGN DIVISION- WOA


ENGINEERING & DESIGN DEPARTMENT
NATIONAL GRID SAUDI ARABIA
Unification of Auxiliary AC/DC
System

ISSUE DATE REPLACE


04-04-2019 NEW

ISSUING ORGANIZATION APPROVAL PAGE NO.


Engineering and Design Department Engineering Manager 2 of 3

TABLE OF CONTENTS

1.0 INTRODUCTION
2.0 OBJECTIVES FOR UNIFICATION OF AC/DC AUXILIARY SYSTEM

APPENDIX I : Team Member List

APPENDIX II : Unification of DC SLD

APPENDIX III : Unification of AC SLD

APPENDIX IV : Unification of Battery & Charger Sizing Calculation

APPENDIX V : Unification of Auxiliary Transformer Sizing Calculation

APPENDIX VI : Unification of LV DC Circuit Breaker Sizing Calculation

APPENDIX VII : Unification of LV AC Circuit Breaker Sizing Calculation

APPENDIX VIII : Unification of LV DC Cable Sizing Calculation

APPENDIX IX : Unification of LV AC Cable Sizing Calculation


Unification of Auxiliary AC/DC
System

ISSUE DATE REPLACE


04-04-2019 NEW

ISSUING ORGANIZATION APPROVAL PAGE NO.


Engineering and Design Department Engineering Manager 3 of 3

1.0 INTRODUCTION:

The auxiliary AC and DC system provide power to the critical infrastructure of the power system.
Reliability of auxiliary supply ensures safe, secure and reliable operation of the power system.
Keeping in view the importance of Auxiliary power system in the substation, the Unification and
Standardization of AC and DC system has been initiated with a focus on Single Point of Failure.
Typical HV Substation is selected for this unification process with following characteristics
1. 12 nos. HV GIS Bays
2. 03 nos. HV Power Transformers
3. 2 nos. Battery Chargers
4. 1 no. Battery Bank

2.0 OBJECTIVES FOR UNIFICATION OF AC/DC AUXILIARY SYSTEM:

· Implementation of Unified AC/DC Auxiliary system for future projects.


· To upgrade Company’s Standard and Specification for Substation Auxiliary System based on
the recommendations of AC/DC Unification Team.
· To identify Single point of failures and economize the design.
· Schemes should be incorporated as a part of Project Technical Scope (PTS) in order
to reduce the time of Design review.
TEAM MEMBER LIST

S. No. Engineer Name Department E-mail Address


1. Mohammed Ali Al Ghamdi ED&D-WOA [email protected]

2. Abdullah S. Al-Qarni ED&D-WOA [email protected]

3. Abdulmanam I. Bushujaa ED&D-EOA [email protected]

4. Salim S. Abdulkhaleq ED&D-SOA [email protected]

5. Faris Ali Ahmad Al-Qahtani ED&D-COA [email protected]

6. Shah Narendra ED&D-COA [email protected]

7. Mohand Saleh Mohammed Ba-Azzim S&SD [email protected]

8. Teofilo C. Bitoon TESAD [email protected]

9. Mohammed Abdelaziz Saeed PED [email protected]

10. Turki Abdullah Turki Al-Madhi TSD [email protected]

11. Riyad Abdullah Al-Shareef TESAD [email protected]

12. Mohammad Gad Abdelkader CSD [email protected]

13. Khalid Hassan Gharib CSD [email protected]

14. Tarig A. Mohammed PED [email protected]

15. Muhammad S. AlOtaibi TSM [email protected]


CERT'D
APPR'D
CHK'D

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION

UNIFIED BATTERY AND BATTERY CHARGER SIZING


CALCULATIONS
(COA & WOA)
BY
DATE
NO

REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
TO BE USED FOR UNIFIED BATTERY AND BATTERY CHARGER SIZING
CONSTRUCTION OF
FOR ORDERING CALCULATIONS
MATERIALS UNTIL
CERTIFIED AND (COA & WOA)
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.

DMS EXCEL
Engineering and Design Department

125V BATTERY AND CHARGER SIZING CALCULATIONS

1 Assumptions and design criteria.

1-1 Continuous Loads


1-1.1 The duration of continuous loads is taken as 10Hr.

1-2 Momentary Loads occuring @ 1Min duration.


1-2.1 Simultaneous tripping of four Nos HV Circuit breakers and two sections of 13.8KV Switchgears are to be considered.

1-3 Non-continous loads


1-3.1 Non continuous loads (Emergency Lighting load) is considered for 3 Hr.

1-4
Simultaneous operation of the following while restoring 13.8kV Circuits within 1 min before the end of discharge.
1-4.1 Closing of one HV Breaker
1-4.2 Closing of one Incomer and one Outgoing breaker and tripping of one breaker if fault persist.
1-4.3 One spring charging motor is in process of starting.
1-4.4 One motor is running,starting current assumed is 5 times normal current.

1-5 Design Criteria

1-5.1 DC System Rated Voltage, Vdc =125Volts


1-5.2 Design Margin Dm =1.10 TES-P-103.02 PARA 4.4.2
1-5.3 Aging Factor Af =1.25 TES-P-103.02 PARA 4.4.3
1-5.4 Minimum Operating Temp. = 100C TES-P-103.02 PARA 4.4.1
1-5.6 End of Discharge Voltage/Cell =1.10 TES-P-103.02 PARA 4.1.2d
1-5.7 Discharge Period 600.00min
1-5.8 Min. Battery Bank Voltage =101.50 TES-P-103.02 PARA 2.0
1-5.9 Maximum Permissible Voltage =136.30 TES-P-103.02 PARA 2.0
1-5.10 Float charge voltage/Cell =1.40 TES-P-103.02 PARA 2.0
1-5.11 Equalizing voltage/Cell =1.60 TES-P-103.02 PARA 2.0
1-5.12 Number of Cells =92.00 TES-P-103.02 PARA 4.2b
Engineering and Design Department

125V BATTERY AND CHARGER SIZING CALCULATIONS

Equipment Loads (Watts) Final Considered Load REMARKS

COA WOA EOA SOA

HICO Bulk Purchase for 12 Bays (BCU Load Considered = 50W/bay)


GIS (HICO) + BCU 3288 3288 3288 3060 3468
2868 + (12*50) = 3468W

13.8KV SWITCHGEAR 2249 3893 2252 2445 2445 Military city-2 S/S

Telecommunication Load 2012 6661 1020 1663 4941 Provided By Telecom Unification Team

SAS Loads 2846 2990 3587 2704 4150 Provided By Telecom Unification Team

Power Transformer (HICO) 1548 2012 170 1500 2012 HICO Bulk Purchase for 3 Power Transformers

Control & Protection Loads (AES) 3121 1789 2709 3414 3414 Military city-2 S/S

TOTAL 15064 20633 13026 14786 20430

Total Continuous Load (A) 163.44


Engineering and Design Department

125V BATTERY AND CHARGER SIZING CALCULATIONS

Load Profile

800.00

700.00
Load current in A

600.00

500.00 A5

400.00 A4
A3
300.00
A2
200.00 A1

100.00

0.00
0 31 60 91 121 152 182 213 244 274 305 335 366 397 425 456 486 517 547 578

Duration in Min

L1 = Continous Load for 10 hours = 163.44 A


L2 = Momentary Load for 1 min = 588.00 A
L3 = Non continous Load for 3 hours = 10.00 A
L4 = Momentry load for 1 min = 41.00 A

5- Selection Of Battery Size

5-1 Initial Cell size calculation

Period Loads Total Ampere Duration (Min)

1 A1 = L1+L2 751.44 1
2 A2 = L1 163.44 179
3 A3 = L1+L3 173.44 180
4 A4=L1 163.44 239
5 A5 = L1+L4 204.44 1
TOTAL

5-2 Cell Size Calculation


Note: We have used method of interpolation to get mid values for Kt factor (SAFT). However, for more accurate results, battery manufacturer
should be consulted for Kt and Temperature factor values. It varies from manufacturer to manufacturer.
Duration Temp.
Load in Change in Capacity Rating Positive Negative
Period Of Period Time to end of section (Min) derating
(A) Load Factor, Kt * Values Values
(Min) factor for
Section 1 - First period only - If A2 is greater than A1, go to Section 2 -NO NO
1 751.44 751.44 1.0000 1.0000 1.090 1.1000 900.98 0.00
Total 900.98

Section 2 - First 2 periods only - If A3 is greater than A2, go to Section 3- YES YES
1 751.44 751.44 1.0000 180.0000 3.8300 1.0500 3021.92 0.00
2 163.44 -588.00 179.0000 179.0000 3.8100 1.0500 0.00 -2352.29
Sub Total 3021.92 -2352.29
Total N/A

Section 3 - First 3 periods only - If A4 is greater than A3, go to Section 4- NO NO


1 751.44 751.44 1.0000 360.0000 6.2600 1.0400 4892.17 0.00
2 163.44 -588.00 179.0000 359.0000 6.2400 1.0400 0.00 -3815.88
3 173.44 10.00 180.0000 180.0000 3.8300 1.0400 39.83 0.00
Sub Total 4932.01 -3815.88
Engineering and Design Department

125V BATTERY AND CHARGER SIZING CALCULATIONS

Total 1116.12

Section 4 - First 4 periods only - If A5 is greater than A4, go to Section 5 YES YES
1 751.44 751.44 1.0000 599.0000 9.5800 1.0400 7486.75 0.00
2 163.44 -588.00 179.0000 598.0000 9.56 1.0400 0.00 -5846.13
3 173.44 10.00 180.0000 419.0000 7.1800 1.0400 74.67 0.00
4 163.44 -10.00 239.0000 239.0000 4.6200 1.0400 0.00 -48.05
Sub Total 7561.42 -5894.18
Total N/A

Section 5 - First 5 periods only - If A6 is greater than A5, go to Section 6 YES YES
1 751.44 751.44 1.0000 600.0000 10.0500 1.0400 7854.05 0.00
2 163.44 -588.00 179.0000 599.0000 10.0300 1.0400 0.00 -6133.55
3 173.44 10.00 180.0000 420.0000 7.1900 1.0400 74.78 0.00
4 163.44 -10.00 239.0000 240.0000 4.6300 1.0400 0.00 -48.15
5 204.44 41.00 1.0000 1.0000 1.0900 1.1000 49.16 0.00
Sub Total 7977.99 -6181.70
Total 1796.29

* Values of Capacity Rating Factor (Kt) are based on the Manufacturer's standard Battery sheet.
* Values of Temperature Derating Factor (Tt) are based on TES-P-103.02 PARA 4.4.1

5-3 Selection of Battery Size


Uncorrected Size 1796.288 AH
Design Margin, Dm 1.1
Ageing Factor, Af 1.25
Required Capacity = Ah x Dm x Af
= 2469.90 AH Battery rating shall be selected as per available
Manufacturer's catalogue
5.4 Number of Cells Calculation

Nominal battery bank DC voltage (Vdc) 125 V


Minimum battery bank voltage based on 101.2 V
end of discharge cell voltage, (Vdc)
Lowest Permissible voltage (Vdc) 101.5 V
Maximum permitted system voltage (Vdc) 136.3 V
(during Equalizing)
Cell nominal voltage (Vdc) 1.4 V/cell
Equalizing voltage (Vdc/cell) 1.6 V/cell
End cell voltage 1.1 V/cell

Number of cell (Ncell)


( Ncell ) = Lowest Permissible voltage
End cell voltage
( Ncell ) = 92

A1 A2 A3 A4 A5
0
0 751.44
1 751.44
1 163.44
180 163.44
180 173.440
360 173.4400
360 163.44
599 163.44
599 204.44
600 204.44
600
Engineering and Design Department

125V BATTERY AND CHARGER SIZING CALCULATIONS

6- Battery Charger Calculation

The ampere output rating of a charger for a DC Power System is determined by the following equation:

I = (A/T) x e + Ic) x (D) x (k)

Where: I : Ampere Rating of Charger


A : Ampere-hours removed during discharge perio = 2469.90
T : Battery Recharging Time (Hours) = 16h
e : Recharge Factor = 1.3
Ic : Continuous DC Load Current = 163.44
D : Design Margin Factor = 1.1
k : Altitude Correction Factor = 1

AR = 400.53 Amp

Selected Battery Charger


= 400.53 Amp
Size

Battery Charger rating shall be selected as per available Manufacturer's catalogue


1. Reference Drawings / Documents:-

1 Unified DC Auxiliary One Line Diagram

2 Unified Auxiliary One Line Diagram

3 Unified LV AC CB Sizing Calculation.

4 SEC Standard TES-P-119.35Rev.00 Station Aux Transformer sizing "

2. Design criteria

The following loads details are considered

1) Two feeders are feeding the same panel.

2) Assuming 50% of Indoor or outdoor receptacles are loaded.

3) Assuming one receptacle in each group of panels/Lighting pole is loaded continuously.

4) All Cubicle lighting loads are included in the calculation.

5) Diversity Factor for PACU-3 is considered as 0 in the sizing calculations

6)The simultaneous peak loading of the auxiliary transformer excluding power transformer oil
filtration socket load shall not exceed 80% of its rating; and with oil filtration socket, the load
shall not exceed the full rating of the station transformer.

7)The following loads need not be considered for estimating simultaneous peak loading:

a. Transformer OLTC motors

b. Sump Motor

c. All other short duration motor.

8)The diversity factor of all lighting load shall be considered as 1.0.

9)Calculations of all AC loads are based on substation Actual Auxiliary loads.

10)Typical Examples for loading calcualtions as per table 35-1 & sub tables TES-P-119.35.

Unified Auxiliary Transformer Sizing


3. 13.8kV / 400 - 230V Station Transformer Sizing Calculation:

From load details attached

Summation of peak-simultaneous occurring loads can be summarized as follows ( refer to


detailed panel-loads as attached in Main ACBD) :-

= 365.61 KVA
The simultaneous peak load on Auxiliary
Transformer excluding Oil Filtration Socket

The simultaneous peak load on Auxiliary


Transformer including one Oil Filtration = (365.61+131.64)
Socket

= 497.25 KVA

Max 80% Loading of the proposed auxiliary transformer size without transformer oil filtration
outlet load, i.e. a minimum capacity of ((365.61 / 0.8) =457 KVA ) is required.

Hence, based on the above selection criteria, the chosen size of station service transformer is :

(1) Rated (KVA) 500

(2) Cooling ONAN

(3) Impedance Z% 4% - 6%

(4) System Primary (HV) Nominal 13.8 KV , 3 phase 60 HZ


(5) System Secondary (LV) Nominal 400 / 230 with solidly earthed neutral

(6) Steps "Off load taps" ±5% ± 2 steps of 2.5%


(7) Vector group Dyn 11
(8) BIL: H.V: 125 / 50kV
L.V: 6 / 2 kV
(9) Temperature rise 45 / 50 / 63 K
(10) Termination HV side: Dry type enclosures, equipped with
outdoor bushings shall be provided to take multiple
single core, copper or aluminum XLPE cables.
Cable entry shall be through suitable glands in the
bottom panel of the enclosure.

LV side- A cable box shall be provided equipped


with terminals to take PVC insulated PVC sheathed
cables

Unified Auxiliary Transformer Sizing


4-Short circuit calculation :
System Data:

Medium Voltage Level 13.8 kV

Low Voltage Level 0.4 kV

13.8kV Bus-1 Fault level = 25 KA


(with two Transformers)

13.8kV/400V Transformer Data = 500 KVA Z= 5%

Calculations

13.8kV Source impedance(Zs1) = 13.8 x 103 = 0.3187 W


sqrt(3) x 25 x 103

V2 = (13.8 kv)2
13.8kV Bus Fault level S= W = 597.56 MVA
Zs1 0.3187
Incomer Cable from 13.8kV SWGR to Station Service Transformer
No. of cables/phase = 1
Type of insulation = XLPE
No. of cores of cable = 1C
Size of selected cable = 300 sq.mm
So the selected cable = XLPE1CX300
Cable Resistance = 0.081200 Ω/km/Run
Cable Reactance = 0.096000 Ω/km/Run
Cable Length = 35 m
Cable Impedence = Sqrt(Rc2+Xc2) = 0.125736 Ω/km/Run
Total Cable Impedence (Zt) = 0.004401 W

13.8kV Source total Impedance = Zt + Zs1 = 0.323098 W

13.8kV Source total Impedance = (Zt + Zs1) X (VLV)2 = 0.3231 x (400)2 0.000271

transferred to 400V side (VMV)2 (13.8x103)2

Transformer Impedance = (VLV)2 X (Z%) = (400)2 X 0.05 = 0.016000


KVA X 103 500X 103

Total Impedance on 400 V side = 0.00027 + 0.016000


= 0.01627 W

Fault level,400 V side = 400 = 14.19 kA


0.01627 x sqrt(3)

Note: Impedance value is chosen as 5%.

Unified Auxiliary Transformer Sizing Calculations


5-Impedance voltage calculation :

Introduction:

Impedance voltage (VI): Is that voltage which is applied through primary side such
that full load current is flowing in secondary side whenever it is short circuited.

The percentage impedance of a transformer(%Z): is the volt drop on full load


due to the winding resistance and leakage reactance expressed as a percentage of the
rated voltage.

It is also the percentage of the normal terminal voltage at the primary side required to
circulate full-load current under short circuit conditions on the secondary side.

CALCULATION:

Refering to the above defintion ,the percentage impedence(%Z) can be


expressed in terms of impedence voltage(VI) as follow:

%Z = VI / nominal primary voltage


so,

VI = %Z X nominal primary voltage

from the selected auxiliary transformer sizing,


%Z=4% TO 6%

Percentage Nominal primary Impedence


4% 13.8 KV 552
6% 13.8 KV 828

Then, the Impedence Voltage of the selected auxiliary transformer 552 V and 828 V

Unified Auxiliary Transformer Sizing Calculations


Main ACDB Loads
Location: Control & Protection Room

equipment

(kVA) (c X
Operating
Total load

factor (d)
(VA) (c =
Load per

Diversity
(VA) (a)

QTY (b)

Load
aXb)
S.No. Load Description Remark

d)
1 Indoor Lighting Panel :ILP--1 12705 1 12705 1 12.71

2 Indoor Lighting Panel :ILP-2 5255 1 5255 1 5.26

3 Power receptacles Panel(PP) 19518 1 19518 0.25 4.88

4 Outdoor Lighting Panel :OLP 7623 1 7623 1 7.62

5 Supply for Sub Distribution Panel-1 SDP-1 30672 1 30672 1 30.67

6 Supply for Sub Distribution Panel-2 SDP-2 35537 1 35537 1 35.54

Supply for Package Compressor Unit PACU -


7 114270 2 228540 0.5 114.27
1A & PACU -1B (Main & Standby Unit )
Supply for Package Compressor Unit PACU -
8 66647 2 133294 0.5 66.65
2A & PACU -2B (Main & Standby Unit )
Supply for Package Compressor Unit PACU -
9
3A & PACU -3B (Main & Standby Unit )

10 Supply for Electrical Duct Heater -1(only one) 10000 1 10000 0.05 0.5

11 Supply for Electrical Duct Heater -2 26000 1 26000 0 0.0

As per NGSABulk
12 Supply for Electrical Duct Heater -3
Purchase
Contract, TES-P-
125V Battery charger (including Spare &
13 65358 2 130716 0.5 65.36 119.35 & Running
Future)
Exercises
200A Power transformer oil filtration
14 receptacle for power trafo T1,T2 & T3 Area at 131640 3 394920 0 0.00
(BUS-A&B)
63A,400V Receptacle For
-Welding for Power TransformerT1,T2 ,T3 (3
Receptacle)
-Aux. Tr. T1,T2 (1 Receptacle)
15 -PACU Units at (3 Receptacle) 41465 12 497580 0 0.00
-Welding for Capacitor Area 1,2&3 (2
Receptacle)
40A Gas Filling at GIS room (3 Receptacle)

16 HV Test Bushing Receptacle for GIS 72109 1 72109 0.00 0.00

17 HVAC Control Panel (Smoke & Exhaust Fans) 34641 3 103923 0.05 5.20

18 Supply for EOT Crane 11580 1 11580 0 0.00

19 400V,3 Phase Portable Battery Charger 35882 1 35882 0 0.00

20 400V,3PH supply for JIB Crane 11580 1 11580 0 0.00

21 400V,3PH Supply For External Telecom Shelter 16967 2 33934 0.5 17.0

TOTAL (kVA) 365.61

Unified Auxiliary Transformer Sizing Calculations


Detail Load calculations of AC SDP-1 panel

Location: Control & Protection Room

equipment

Total load

factor (d)
(VA) (c =
Load per

Diversity
(VA) (a)

QTY (b)
Operating Load

aXb)
S.No. Load Description (KVA) (c X d)

QC.6 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-1 LCP (FANS , MK ) (MAIN) 11289 1 11289 0.50 5.64

QC.7 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-2 LCP (FANS , MK ) (MAIN) 11289 1 11289 0.50 5.64

400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-3 LCP (FANS , MK ) (STAND


QC.8
BY)
11289 1 11289 0.50 5.64

QC.9 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-1 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00

QC.10 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-2 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00

QC.11 400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-3 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00

QC.12 230V AC SUPPLY FOR BASEMENT SUMP PUMP-1 1529 1 1529 0.00 0.00

QC.13 230V AC SUPPLY FOR BASEMENT SUMP PUMP-2 1529 1 1529 0.00 0.00

QC.14 230V AC SUPPLY FOR BASEMENT SUMP PUMP-3 1529 1 1529 0.00 0.00

QC.15 230V AC SUPPLY FOR BASEMENT SUMP PUMP-4 1529 1 1529 0.00 0.00

QC.16 400V AC SUPPLY FOR SMOKE PURGE FAN-01 (SEF-01) 2858 1 2858 0.00 0.00

QC.17 400V AC SUPPLY FOR SMOKE PURGE FAN-02 (SEF-02) 4141 1 4141 0.00 0.00

QC.18 400V AC SUPPLY FOR SMOKE PURGE FAN-03(SEF-03) 3063 1 3063 0.00 0.00

QC.19 400V AC SUPPLY-1 FOR MISCELLANEOUS PORTABLE TOOLS 1176 1 1176 0.50 0.59

QC.20 230V AC SUPPLY-1 FOR 110/13.8 KV TR-1 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22

QC.21 230V AC SUPPLY-1 FOR 110/13.8 KV TR-2 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22

QC.22 230V AC SUPPLY-1 FOR 110/13.8 KV TR-3 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22

QC.23 400/230V AC SUPPLY FOR 110KV GIS LCC E10 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.24 400/230V AC SUPPLY FOR 110KV GIS LCC E08 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.25 400/230V AC SUPPLY FOR 110KV GIS LCC E06 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.26 400/230V AC SUPPLY FOR 110KV GIS LCC E04 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.27 400/230V AC SUPPLY FOR 110KV GIS LCC E02(HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.28 400/230V AC SUPPLY FOR 110KV GIS LCC E230 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.29 400/230V AC SUPPLY FOR 110KV GIS LCC E220 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.30 400/230V AC SUPPLY FOR 110KV GIS LCC E130 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.31 400/230V AC SUPPLY FOR 110KV GIS LCC E01 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.32 400/230V AC SUPPLY FOR 110KV GIS LCC E03 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.33 400/230V AC SUPPLY FOR 110KV GIS LCC E05 (HTR,LTNG,SCKT) 588 1 588 0.06 0.04

QC.34 400/230V AC SUPPLY FOR 110KV GIS LCC E07(HTR,LTNG,SCKT) 588 1 588 0.06 0.04

230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(


QC.35
+PSE,+CBP-3,+CBP-2,+CBP-1,+ACCS,+ABTS )
2982 1 2982 0.27 0.81

230VAC SUPPLY FOR CONTROL ROOM PANELS


QC.36
(HTR,LTNG,SCKT)(BBA,BBB.BBCH,BBZ1,BBZ2,BBZ3)
2982 1 2982 0.27 0.81

Unified Auxiliary Transformer Sizing Calculations


230VAC SUPPLY FOR CONTROL ROOM PANELS
QC.37
(HTR,LTNG,SCKT)(+3SYN,+UFP-1,+UVP-1,+UFP-2,UVP- 2)
2485 1 2485 0.18 0.45

230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT)


QC.38
(+R07.2,+R07.1,+R10.2F,+R10.1F,FUT,FUT+R08.2,+R08.1)
3976 1 3976 0.27 1.07

230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT)


QC.39
(+R06.2,+R06.1,+R4.2,+R4.1,+R02.2,+R02.1)
2982 1 2982 0.27 0.81

230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT)


QC.40
(+R230,+R220,+R130)
1491 1 1491 0.27 0.40

230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT)


QC.41
(+R01.2,+R01.1,+R03.2,+R03.1,+R05.2,+R05.1,FUT,FUT)
3976 1 3976 0.27 1.07

QC.42 400 VAC SUPPLY FOR (DCDB ) PANEL 496 1 496 0.00 0.00

QC.43 400V,AC SUPPLY FOR GIS ROOM EXHAUST FAN 2747 1 2747 0.00 0.00

230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-1 (AH01 TO


QC.44
AH18)
5806 1 5806 0.04 0.23

230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-2 (AH19 TO


QC.45
AH36)
5429 1 5429 0.04 0.22

230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-3 (AH37 TO


QC.46
AH53) HTR,LTNG,SCKT)
5694 1 5694 0.04 0.23

QC.47 230VAC SUPPLY FOR FUTURE PANELS 498 1 498 0.27 0.13

QC.48 230VAC SUPPLY FOR FUTURE PANELS 498 1 498 0.27 0.13

QC.49 230VAC SUPPLY-1 FOR SAS PANELS ROW (HTR,LTNG,SCKT) 2353 1 2353 0.00 0.00

230VAC SUPPLY FOR COMMUNICATION PANELS (LAN/WAN , SDH ,


QC.50
DDF,DVM,MDF)
1176 1 1176 0.00 0.00

230VAC SUPPLY FOR COMMUNICATION PANELS (MCP , N01 ,N02,DC-


QC.51
DC CONVERTER -1&2)
498 1 498 0.00 0.00

QC.52 230V AC SUPPLY FOR BATTERY ROOM EXHAUST FANS. 211 2 422 1.00 0.42

230V,1PH SUPPLY FM-200 RELEASING PANEL - CONTROL ROOM - FIRST


QC.53
FLOOR
460 1 460 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - COMMUNICATION


QC.54
ROOM -FIRST FLOOR
460 1 460 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - BATTERY ROOM -FIRST


QC.55
FLOOR
460 1 460 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - 13.8kV SWITCHGEAR


QC.56
ROOM -GROUND FLOOR
460 1 460 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - HV GIS


QC.57
HALL-GROUND FLOOR-SYSTEM#1
460 1 460 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - HV GIS


QC.58
HALL-GROUND FLOOR-SYSTEM#2
460 1 460 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - HV GIS


QC.59
HALL-GROUND FLOOR-SYSTEM#3
460 1 460 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - HV GIS


QC.60
HALL-GROUND FLOOR-SYSTEM#4
460 1 460 0.00 0.00

QC.61 400V, AC SUPPLY FOR FM-200- ROOM-01 EXHAUST FAN 281 1 281 0.00 0.00

QC.62* 400V, AC SUPPLY FOR SECURITY SYSTEM 1 0 1.00 0.00

QC.63 400V, AC SUPPLY FOR BASEMENT EXHAUST FAN 02 2647 1 2647 1.00 2.65

QC.64 400V, AC SUPPLY FOR BASEMENT EXHAUST FAN 03 2647 1 2647 1.00 2.65

TOTAL (KVA) 30.672

Unified Auxiliary Transformer Sizing Calculations


Detail Load calculations of AC SDP-2 panel
Location: Control & Protection Room

equipment

Total load

factor (d)
(VA) (c =
Load per

Diversity
(VA) (a)

QTY (b)
Operating Load

aXb)
S.No. Load Description (KVA) (c X d)

QD.07 400V,3PH SUPPLY-2 FOR TR-1 LCP (FANS MK )(STAND BY) 11289 1 11289 0.50 5.64

QD.08 400V, 3PH SUPPLY-2 FOR TR-2 LCP (FANS , MK ) (STAND BY) 11289 1 11289 0.50 5.64

QD.09 400V, 3PH SUPPLY-2 FOR TR-3 LCP (FANS , MK ) (MAIN) 11289 1 11289 0.50 5.64

QD.10 400V, 3PH SUPPLY-2 FOR TR-1 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00

QD.11 400V, 3PH SUPPLY-2 FOR TR-2 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00

QD.12 400V, 3PH SUPPLY-2 FOR TR-3 OLTC MOTOR DRIVE UNIT. 882 1 882 0.00 0.00

QD.13 400V,AC SUPPLY FOR FAX/TELEPHONE EXCHANGE. 5882 1 5882 0.50 2.94

QD.14 400V, AC SUPPLY-2 FOR MISCELLANEOUS PORTABLE TOOLS 1176 1 1176 0.50 0.59

400V,AC SUPPLY 01 FOR SPLIT UNIT(WORKSHOP AND RECORD


QD.15
ROOM)
2352 1 2352 1.00 2.35

QD.16 400 VAC SUPPLY FOR (DCDB-1 ) PANELS 496 1 496 0.27 0.13

QD.17 400 VAC SUPPLY FOR (DCDB-2 ) PANELS 496 1 496 0.27 0.13

QD.18 230V AC SUPPLY FOR LCC'S ANNUNCIATION SYSTEM 3529 1 3529 0.18 0.64

QD.19 230V AC SUPPLY-2 FOR TR-1 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22

QD.20 230V AC SUPPLY-2 FOR TR-2 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22

QD.21 230V AC SUPPLY-2 FOR TR-3 OLTC LIGHTING & HEATER. 435 1 435 0.50 0.22

QD.22 230V AC SUPPLY FOR TR-1 ONLINE GAS/MOISTURE ANALYSER 176 1 176 1.00 0.18

QD.23 230V AC SUPPLY FOR TR-2 ONLINE GAS/MOISTURE ANALYSER 176 1 176 1.00 0.18

QD.24 230V AC SUPPLY FOR TR-3 ONLINE GAS/MOISTURE ANALYSER 176 1 176 1.00 0.18

QD.25 400V AC SUPPLY FOR TRANSFORMER PIT PUMP-1. 2353 1 2353 0.00 0.00

QD.26 400V AC SUPPLY FOR TRANSFORMER PIT PUMP-2. 2353 1 2353 0.00 0.00

QD.27 400V AC SUPPLY FOR TRANSFORMER PIT PUMP-3. 2353 1 2353 0.00 0.00

QD.28 400V AC SUPPLY FOR AUXILIARY TRANSFORMER-1 PIT PUMP. 2353 1 2353 0.00 0.00

QD.29 400V AC SUPPLY FOR AUXILIARY TRANSFORMER-2 PIT PUMP. 2353 1 2353 0.00 0.00

QD.30 230V AC SUPPLY FOR GATE MOTOR-1 1176 1 1176 0.00 0.00

230VAC SUPPLY-1 FOR CONTROL ROOM PANELS


QD.31
(HTR,LTNG,SCKT)(+RTM-1,+RTM-2,+RTM-3,+RTM-4,+RTM-5,+RTM-6)
2982 1 2982 0.27 0.81

QD.32 400V AC SUPPLY FOR WATER BOOSTER PUMP. 2941 1 2941 0.00 0.00

QD.33 230V,AC SUPPLY FOR KITCHEN EXHAUST FAN 26 1 26 0.00 0.00

QD.34 230V AC SUPPLY FOR MFACB PANELS & PRINTERS 1035 1 1035 0.27 0.28

230VAC SUPPLY FOR CONTROL ROOM PANELS


QD.35
(HTR,LTNG,SCKT)(RTCC-1,RTCC-2,RTCC-3)
1491 1 1491 0.18 0.27

Unified Auxiliary Transformer Sizing Calculations


QD.36 230V AC SUPPLY FOR WATER HEATER FOR TOILET. 2353 1 2353 0.00 0.00

QD.37 230V AC SUPPLY FOR TOILET EXHAUST FAN 70 1 70 0.00 0.00

QD.38 230V AC SUPPLY FOR WATER TRANSFER PUMP 1294 1 1294 0.00 0.00

230V AC SUPPLY FOR CONTROL ROOM WORKSTATION (PC'S,


QD.39
MONITORS, PRINTERS…..ETC).
2353 1 2353 1.00 2.35

230VAC SUPPLY FOR CONTROL ROOM PANELS


QD.40
(HTR,LTNG,SCKT)(ILPB,ILP,ELP,DCU,RMR,DDR)
2982 1 2982 0.00 0.00

230VAC SUPPLY FOR CONTROL ROOM PANELS


QD.41
(HTR,LTNG,SCKT)(MAIN ACDB,PP-1,PP-2,OLP,HVAC1,HVAC2)
2353 1 2353 0.00 0.00

230VAC SUPPLY FOR CONTROL ROOM PANELS


QD.42
(HTR,LTNG,SCKT)(G12,G11,FUT,FUT,FUT,FUT)
2353 1 2353 0.00 0.00

QD.43 230VAC SUPPLY-1 FOR AMI (RMR PANEL) 498 1 498 0.27 0.13

QD.44 230VAC SUPPLY-1 FOR AMI (SWITCH PANEL) 498 1 498 0.27 0.13

QD.45 230VAC SUPPLY-1 FOR SAS PANELS ROW (HTR,LTNG,SCKT) 1153 1 1153 0.00 0.00

QD.46 230V,AC SUPPLY FOR FM-200-ROOM-02 EXHAUST FAN 86 1 86 0.00 0.00

QD.47 230V,AC SUPPLY FOR FM-200-ROOM-03 EXHAUST FAN 90 1 90 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - 13.8 KV SWITCHGEAR


QD.48
BASEMENT
440 1 440 0.00 0.00

QD.49 230V,1PH SUPPLY FM-200 RELEASING PANEL - HV GIS BASEMENT 440 1 440 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - CABLE CORRIDOR-


QD.50
BASEMENT
440 1 440 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - COMMUNICATION


QD.51
ROOM - EXTERNAL TELECOM SHELTER
440 1 440 0.00 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - BATTERY ROOM -


QD.52
EXTERNAL TELECOM SHELTER
440 1 440 0.00 0.00

QD.53 230V AC SUPPLY FOR BASEMENT SUMP PUMP-5 1529 1 1529 0.00 0.00

QD.54 230V AC SUPPLY FOR BASEMENT SUMP PUMP-6 1529 1 1529 0.00 0.00

QD.55 230V AC SUPPLY FOR BASEMENT SUMP PUMP-7 1529 1 1529 0.00 0.00

QD.56 230V AC SUPPLY FOR BASEMENT SUMP PUMP-8 1529 1 1529 0.00 0.00

QD.57 230V AC SUPPLY FOR HAND DRYER 1500 1 1500 1.00 1.50

QD.58 230V AC SUPPLY FOR GATE MOTOR-2 1176 1 1176 0.00 0.00

QD.59* 400V AC SUPPLY FOR SECURITY SYSTEM UPS IN CONTROL ROOM 1 0 1.00 0.00

400V,AC SUPPLY 02 FOR SPLIT UNIT(WORKSHOP AND RECORD


QD.60
ROOM)
2352 1 2352 1.00 2.35

230V,1PH SUPPLY FOR PARTIAL DISCHARGE MONITORING


QD.61
SYSTEM(PDMS)
165 1 165 1.00 0.17

QD.62 230V,1PH SUPPLY FOR ROLLING SHUTTER MOTOR DOOR 1176 1 1176 0.00 0.00

QD.63 400V,AC SUPPLY FOR BASEMENT EXHAUST FAN 01 2647 1 2647 1.00 2.65

TOTAL (KVA) 35.537

Unified Auxiliary Transformer Sizing Calculations


CERT'D
APPR'D
CHK'D

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION

UNIFIED LV DC CIRCUIT BREAKER SIZING


CALCULATIONS
(COA & WOA)
BY
DATE
NO

REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
TO BE USED FOR UNIFIED LV DC CIRCUIT BREAKER SIZING
CONSTRUCTION OF
FOR ORDERING CALCULATIONS
MATERIALS UNTIL
CERTIFIED AND (COA & WOA)
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.

DMS EXCEL
125V DC Fault Level Calculations:

System Data:

Battery = NiCd stationary Battery

Rated Voltage = 125 V DC

Battery Charger Rating = 400 A

Calculations:

Short Circuit Current for DC system is calculated as given below.

Total Short Circuit Current = Short Circuit Current delivered by Batteries


+ Short Circuit Current delivered by Battery
Chargers

Internal resistance of battery ( Rmin ) = 0.11 mΩ

No of cells ( n ) = 92 Cell
DC voltage = 101.5 V
101.5
Short Circuit Current delivered by Battery String = Vmin/(Rmin* n * 10-3) =
0.11 x 92 x 10-3

Short Circuit Current delivered by Battery String = 10029.6 A

Short Circuit Current delivered by Battery Set (2 Battery String) = 20059.3 A 1

Total Short Circuit Current delivered by = 1.5 * Icharger = 1.5 X 400


Battery Chargers

= 600 A 2
Hence,
From 1 & 2
Total DC System Short Circuit Current = 20059.3 + 600

= 20659.3 A
= 20.7 kA
Conclusion:

As per clause 4.1.9.2 of TES-P-119.30 Rev 02, the rated short-time withstand current of main DC distribution panels
shall be minimum 25 kA, 1sec and rated short-time withstand current of sub DC distribution and Emergency lighting
panels shall be as per design calculations and NGSA approval.
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
FACTOR

FACTOR
DEMAND
UNIT TOTAL
CB.No LOAD Volts
LOAD (W) LOAD (W) RATING NO OF SC
AMP AMP Type
AMP POLES Capacity

MAIN DCDB (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)

500AT/
Q.103 INCOMER-1 BREAKER FOR MAIN BUSBAR A 40600 1 1 40600 101.5 400.000 480.0 DP MCCB 25 KA
630AF
500AT/
Q.104 INCOMER-2 BREAKER FOR MAIN BUSBAR B 40600 1 1 40600 101.5 400.000 480.0 DP MCCB 25 KA
630AF
125AT/
Q.105 SUPPLY FOR PORTABLE BATTERY CHARGER 10150 1 1 10150 101.5 100.000 120.0 DP MCCB 25 KA
160AF
125AT/
Q.106 SUPPLY FOR PORTABLE BATTERY CHARGER 10150 1 1 10150 101.5 100.000 120.0 DP MCCB 25 KA
160AF

MAIN DCDB (BUS-A) (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)

225AT/
Q.A1 SUPPLY-1 FOR SUB DCDB-1 (BUS-A) 18016.0 1 1 18016.0 101.5 177.50 213.0 DP MCCB 25 KA
250AF
225AT/
Q.A2 SUPPLY-1 FOR SUB DCDB-2 (BUS-A) 18862.0 1 1 18862.0 101.5 185.83 223.0 DP MCCB 25 KA
250AF
60AT/
Q.A3 SUPPLY-1 FOR TELECOM DCPDB-1 4941.00 1 1 4941.0 101.5 48.68 58.4 DP MCCB 25 KA
63AF
75AT/
Q.A4 SUPPLY-1 FOR EMERGENCY LIGHTING PANEL 5800.0 1 1 5800.0 101.5 57.14 68.6 DP MCCB 25 KA
80AF
75AT/
Q.A5 SPARE DP MCCB 25 KA
80AF
225AT/
Q.A6 SPARE DP MCCB 25 KA
250AF

MAIN DCDB (BUS-B) (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)

225AT/
Q.B1 SUPPLY-2 FOR SUB DCDB-1 (BUS-B) 18016.0 1 1 18016.0 101.5 177.50 213.0 DP MCCB 25 KA
250AF
225AT/
Q.B2 SUPPLY-2 FOR SUB DCDB-2 (BUS-B) 18862.0 1 1 18862.0 101.5 185.83 223.0 DP MCCB 25 KA
250AF
60AT/
Q.B3 SUPPLY-2 FOR TELECOM DCPDB-1 4941.00 1 1 4941.0 101.5 48.68 58.4 DP MCCB 25 KA
63AF
75AT/
Q.B4 SUPPLY-2 FOR EMERGENCY LIGHTING PANEL 5800.0 1 1 5800.0 101.5 57.14 68.6 DP MCCB 25 KA
80AF
75AT/
Q.B5 SPARE DP MCCB 25 KA
80AF
225AT/
Q.B6 SPARE DP MCCB 25 KA
250AF
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

225AT/
Q.107 SUPPLY FOR SUB DCDB-1 (SEC-A) 18016.0 1 1 18016 101.5 177.50 213.00 DP MCCB 25 KA
250AF
225AT/
Q.108 SUPPLY FOR SUB DCDB-1 (SEC-B) 18016.0 1 1 18016 101.5 177.50 213.00 DP MCCB 25 KA
250AF
225AT/
Q.109 BUS TIE 18016.0 1 1 18016 101.5 177.50 213.00 DP MCCB 25 KA
250AF

SEC-A (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY FOR LINE FEEDER (FUTURE)-E07


QA1.1 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, 13.8 1 1 13.8 101.5 0.14 0.163 20 DP MCB 25 KA
IN/OUT RELAY CKT)

SUPPLY FOR LINE FEEDER-E05 PROTECTION


QA1.2 PANEL SET-1 (MAIN-1 PROTN CKT, IN/OUT 13.8 1 1 13.8 101.5 0.14 0.163 20 DP MCB 25 KA
RELAY CKT)

SUPPLY FOR TRANSFROMER T01-E03


QA1.3 PROTECTION PANEL SET-1 (MAIN-1 87 T-1 75.2 1 1 75.2 101.5 0.74 0.889 20 DP MCB 25 KA
PROTN, IN/OUT RELAY )

SUPPLY FOR LINE FEEDER-E01 PROTECTION


QA1.4 PANEL SET-1 (MAIN-1 PROTN CKT, IN/OUT 13.8 1 1 13.8 101.5 0.14 0.163 20 DP MCB 25 KA
RELAY CKT)

SUPPLY FOR BUS COUPLER-A -E130


QA1.5 36.25 1 1 36.25 101.5 0.36 0.429 20 DP MCB 25 KA
PROTECTION PANEL (O/C & E/F RELAY CKT)

SUPPLY FOR BUS SECTION-E220 PROTECTION


QA1.6 36.25 1 1 36.25 101.5 0.36 0.429 20 DP MCB 25 KA
PANEL (O/C & E/F RELAY CKT)

SUPPLY FOR BUS COUPLER-B -E230


QA1.7 36.25 1 1 36.25 101.5 0.36 0.429 20 DP MCB 25 KA
PROTECTION PANEL (O/C & E/F RELAY CKT)

SUPPLY FOR TRANSFORMER T02-E02


QA1.8 PROTECTION PANEL SET-1 (MAIN-1 87T-1 75.2 1 1 75.2 101.5 0.74 0.889 20 DP MCB 25 KA
PROTN, IN/OUT RELAY )

SUPPLY FOR LINE FEEDER-E04 PROTECTION


QA1.9 PANEL SET-1 (MAIN-1 PROTN CKT, IN/OUT 13.8 1 1 13.8 101.5 0.14 0.163 20 DP MCB 25 KA
RELAY CKT)

SUPPLY FOR TRANSFORMER T03-E06


QA1.10 PROTECTION PANEL SET-1 (MAIN-1 87 T-1 75.2 1 1 75.2 101.5 0.74 0.889 20 DP MCB 25 KA
PROTN, IN/OUT RELAY )

SUPPLY FOR LINE FEEDER-E08 PROTECTION


QA1.11 PANEL SET-1 (MAIN-1 PROTN CKT, IN/OUT 13.8 1 1 13.8 101.5 0.14 0.163 20 DP MCB 25 KA
RELAY CKT)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY FOR LINE FEEDER (FUTURE)-E10


QA1.12 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, 13.8 1 1 13.8 101.5 0.14 0.163 20 DP MCB 25 KA
IN/OUT RELAY CKT)

SUPPLY-1 FOR HV LINE FEEDER (FUTURE)-E07


QA1.13 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
(CB MOTOR CKT)

SUPPLY-1 FOR HV LINE FEEDER-E05


QA1.14 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
(CB MOTOR CKT)

SUPPLY-1 FOR HV TRANSFORMER T01-E03 (CB


QA1.15 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
MOTOR CKT)

SUPPLY-1 FOR HV LINE FEEDER-E01


QA1.16 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
(CB MOTOR CKT)

SUPPLY-1 FOR HV BUS COUPLER-A -E130 (CB


QA1.17 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
MOTOR CKT)

SUPPLY-1 FOR HV BUS SECTION 220


QA1.18 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
(CB MOTOR CKT)

SUPPLY-1 FOR HV BUS COUPLER-B -E230 (CB


QA1.19 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
MOTOR CKT)

SUPPLY-1 FOR HV TRANSFORMER T02-E02 (CB


QA1.20 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
MOTOR CKT)

SUPPLY-1 FOR HV LINE FEEDER-E04 (CB MOTOR


QA1.21 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
CKT)

SUPPLY-1 FOR HV TRANSFORMER T03-E06 (CB


QA1.22 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
MOTOR CKT)

SUPPLY-1 FOR HV LINE FEEDER S/S-E08 (CB


QA1.23 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
MOTOR CKT)

SUPPLY-1 FOR HV LINE FEEDER (FUTURE)-E10


QA1.24 875 1 1 875 101.5 8.62 10.345 20 DP MCB 25 KA
(CB MOTOR CKT)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-2 FOR HV LINE FEEDER (FUTURE)-E07


QA1.25 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
(CB TRIP CKT-2)

SUPPLY-2 FOR HV LINE FEEDER-E05 (CB TRIP


QA1.26 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
CKT-2)

SUPPLY-2 FOR HV TRANSFORMER T01-E03 (CB


QA1.27 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
TRIP CKT-2)

SUPPLY-2 FOR HV LINE FEEDER-E01 (CB TRIP


QA1.28 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
CKT-2)

SUPPLY-2 FOR HV BUS COUPLER-A -E130 (CB


QA1.29 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
TRIP CKT-2)

SUPPLY-2 FOR HV BUS SECTION-E220 (CB TRIP


QA1.30 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
CKT-2)

SUPPLY-2 FOR HV BUS COUPLER-B -E230 (CB


QA1.31 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
TRIP CKT-2)

SUPPLY-2 FOR HV TRANSFORMER T02-E02 (CB


QA1.32 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
TRIP CKT-2)

SUPPLY-2 FOR HV LINE FEEDER-E04 (CB TRIP


QA1.33 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
CKT-2)

SUPPLY-2 FOR HV TRANSFORMER T03-E06 (CB


QA1.34 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
TRIP CKT-2)

SUPPLY-2 FOR HV LINE FEEDER S/S-E08 (CB TRIP


QA1.35 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
CKT-2)

SUPPLY-2 FOR HV LINE FEEDER (FUTURE)-E10


QA1.36 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
(CB TRIP CKT-2)

SUPPLY-3 FOR HV LINE FEEDER (FUTURE)-E07


QA1.37 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
(DS/ES INTERLOCK CKT SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-3 FOR HV LINE FEEDER-E05 (DS/ES


QA1.38 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV TRANSFORMER T01-E03 DS/ES


QA1.39 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV LINE FEEDER -E01 DS/ES


QA1.40 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV BUS COUPLER-A -E130 DS/ES


QA1.41 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV BUS SECTION-E220 (DS/ES


QA1.42 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV BUS COUPLER-B -E230 DS/ES


QA1.43 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV TRANSFORMER T02-E02 DS/ES


QA1.44 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV LINE FEEDER-E04 DS/ES


QA1.45 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV TRANSFORMER T03-E06 DS/ES


QA1.46 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV SPARE FEEDER S/S-E08 DS/ES


QA1.47 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-3 FOR HV FUTURE FEEDER- E10 DS/ES


QA1.48 70.0 1 1 70 101.5 0.69 0.828 20 DP MCB 25 KA
INTERLOCK CKT SUPPLY

SUPPLY-1 FOR HV BUSBAR-A PROTECTION


QA1.49 13 1 1 13 101.5 0.13 0.154 20 DP MCB 25 KA
PANEL (ZONE 1A PROTN CKT)

SUPPLY-1 FOR HV BUSBAR-CH ZONE


QA1.50 PROTECTION PANEL (BB-CHECK ZONE & 13 1 1 13 101.5 0.13 0.154 20 DP MCB 25 KA
IN/OUT RELAY CKT)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-1 FOR HV BUSBAR-B PROTECTION


QA1.51 13 1 1 13 101.5 0.13 0.154 20 DP MCB 25 KA
PANEL (ZONE-1B PROTN CKT)

SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE


QA1.52 FEEDER BUS-1 (AH01) (TRIP CKT-1, CLOSE 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE


QA1.53 FEEDER BUS-1 (AH02) (TRIP CKT-1, CLOSE 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR CAP. BANK-1


QA1.54 FEEDER (AH03) (TRIP CKT-1, CLOSE 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.55 (AH04) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.56 (AH05) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.57 (AH06) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-


QA1.58 1 (AH07) (TRIP CKT-1, CLOSE CKT/CONTROL 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.59 (AH08) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV INCOMER T01 (AH09)


QA1.60 252.6 1 1 252.6 101.5 2.49 2.986 20 DP MCB 25 KA
(TRIP CKT-1, CLOSE CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.61 (AH10) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.62 (AH11) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.63 (AH12) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.64 (AH13) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.65 (AH14) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1


QA1.66 (AH15) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR AUX-01 FEEDER


QA1.67 (AH16) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8KV BUS METERING-01 (AH17)


QA1.68 133.3 1 1 133.3 101.5 1.31 1.576 20 DP MCB 25 KA
(EARTH SWITCH INTERLOCK, I/O BOX-1)

SUPPLY-1 FOR 13.8kV BUS SECTION-01 (AH18)


QA1.69 252.6 1 1 252.6 101.5 2.49 2.986 20 DP MCB 25 KA
(TRIP CKT-1, CLOSE CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8KV BUS RISER-01 (AH19)


QA1.70 123.3 1 1 123.3 101.5 1.21 1.458 20 DP MCB 25 KA
(EARTH SWITCH INTERLOCK, I/O BOX-1)

SUPPLY-1 FOR 13.8kV SWGR CAP. BANK-02


QA1.71 FEEDER (AH20) (TRIP CKT-1, CLOSE 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QA1.72 (AH21) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QA1.73 (AH22) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QA1.74 (AH23) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QA1.75 (AH24) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QA1.76 (AH25) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QA1.77 (AH26) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.774 20 DP MCB 25 KA
BCU)

SUPPLY FOR 13.8 KV BUSBAR-1A PROTECTION


QA1.78 15.25 1 1 15.25 101.5 0.15 0.180 20 DP MCB 25 KA
PANEL(MAIN PROTN)

SUPPLY FOR 13.8 KV BUSBAR-1B PROTECTION


QA1.79 15.25 1 1 15.25 101.5 0.15 0.180 20 DP MCB 25 KA
PANEL(MAIN PROTN)

SUPPLY FOR 13.8 KV BUSBAR-1C PROTECTION


QA1.80 15.25 1 1 15.25 101.5 0.15 0.180 20 DP MCB 25 KA
PANEL(MAIN PROTN)

SUPPLY FOR 13.8KV AUTOMATIC BUS TRANSFER


QA1.81 SCHEME (+ABTS) (IN/OUT MODULE & ALARM/ 80 1 1 80 101.5 0.79 0.946 20 DP MCB 25 KA
INDICATION CKT)

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QA1.82 61.25 1 1 61.25 101.5 0.60 0.724 20 DP MCB 25 KA
PANEL-1 (SET-1)

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QA1.83 61.25 1 1 61.25 101.5 0.60 0.724 20 DP MCB 25 KA
PANEL-2 (SET-1)

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QA1.84 61.25 1 1 61.25 101.5 0.60 0.724 20 DP MCB 25 KA
PANEL-3 (SET-1)

SUPPLY-1 FOR DC EMERGENCY LIGHTING FOR


QA1.85 40.0 1 1 40 101.5 0.39 0.473 20 DP MCB 25 KA
CONTROL PANELS

SUPPLY FOR CHANGE OVER SCHEME-1 (ATS


QA1.86 50 1 1 50 101.5 0.49 0.591 20 DP MCB 25 KA
FOR DCDB-1)

SUPPLY FOR 13.8kV UNDER VOLTAGE LOAD


QA1.87 72.5 1 1 72.5 101.5 0.71 0.857 20 DP MCB 25 KA
SHEDDING PROTECTION PANEL(SET-1)

SUPPLY FOR 13.8KV SWGR INCOMER T03


QA1.88 79.7 1 1 79.7 101.5 0.79 0.942 20 DP MCB 25 KA
(AH45)(SYNCH TROLLEY SUPPLY)

SUPPLY FOR 13.8KV SWGR INCOMER T02


QA1.89 79.7 1 1 79.7 101.5 0.79 0.942 20 DP MCB 25 KA
(AH29) (SYNCH TROLLEY SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY FOR 13.8KV SWGR INCOMER T01


QA1.90 79.7 1 1 79.7 101.5 0.79 0.942 20 DP MCB 25 KA
(AH09) (SYNCH TROLLEY SUPPLY)

SUPPLY FOR 13.8KV SWGR INCOMER T03


QA1.91 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
(AH45) (OPERATING MECHANISM)

SUPPLY FOR 13.8KV SWGR INCOMER T02


QA1.92 (AH29) AND BUS SECTION-02 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
(AH36)(OPERATING MECHANISM)

SUPPLY FOR 13.8KV SWGR INCOMER T01


QA1.93 (AH09) AND BUS SECTION-01 (AH18) 500 1 1 500 101.5 4.93 5.911 20 DP MCB 25 KA
(OPERATING MECHANISM)

QA1.94 SUPPLY-1 FOR AMI PANEL-1 118.0 1 1 118 101.5 1.16 1.395 20 DP MCB 25 KA

QA1.95 SUPPLY-1 FOR AMI PANEL-2 118.0 1 1 118 101.5 1.16 1.395 20 DP MCB 25 KA

QA1.96 SUPPLY-1 FOR RM PANEL-1 30.0 1 1 30 101.5 0.30 0.355 20 DP MCB 25 KA

QA1.97 SUPPLY-1 FOR RM PANEL-2 30.0 1 1 30 101.5 0.30 0.355 20 DP MCB 25 KA

QA1.98 SUPPLY FOR SECURITY SYSTEM AND CAMERAS 300.0 1 1 300 101.5 2.96 3.547 20 DP MCB 25 KA

QA1.99 SPARE 20 DP MCB 25 KA

QA1.100 SPARE 20 DP MCB 25 KA

LOAD SHEDDING PROTECTION PANEL(BUS-


QA1.101 18.8 1 1 18.75 101.5 0.18 0.222 20 DP MCB 25 KA
B)SUPPLY FOR 13.8KV UNDER FREQUENCY

SUPPLY FOR LINE FEEDER(FUTURE)-E07


QA1.102 127.0 1 1 127 101.5 1.25 1.501 20 DP MCB 25 KA
PROTECTION PANEL(INTERTRIP-1)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY FOR LINE FEEDER-E05 PROTECTION


QA1.103 127.0 1 1 127 101.5 1.25 1.501 20 DP MCB 25 KA
PANEL(INTERTRIP-1)

SUPPLY FOR LINE FEEDER-E01 PROTECTION


QA1.104 127.0 1 1 127 101.5 1.25 1.501 20 DP MCB 25 KA
PANEL(INTERTRIP-1)

SUPPLY FOR LINE FEEDER-E04 PROTECTION


QA1.105 127.0 1 1 127 101.5 1.25 1.501 20 DP MCB 25 KA
PANEL(INTERTRIP-1)

SUPPLY FOR LINE FEEDER-E08 PROTECTION


QA1.106 127.0 1 1 127 101.5 1.25 1.501 20 DP MCB 25 KA
PANEL(INTERTRIP-1)

SUPPLY FOR LINE FEEDER(FUTURE)-E10


QA1.107 127.0 1 1 127 101.5 1.25 1.501 20 DP MCB 25 KA
PROTECTION PANEL(INTERTRIP-1)

QA1.108 SPARE 20 DP MCB 25 KA

QA1.109 SPARE 20 DP MCB 25 KA

QA1.110 SPARE 20 DP MCB 25 KA

QA1.111 SPARE 20 DP MCB 25 KA

QA1.112 SPARE 20 DP MCB 25 KA

QA1.113 SPARE 20 DP MCB 25 KA

QA1.114 SPARE 20 DP MCB 25 KA

QA1.115 SPARE 20 DP MCB 25 KA

QA1.116 SPARE 20 DP MCB 25 KA

QA1.117 SPARE 20 DP MCB 25 KA

QA1.118 SPARE 20 DP MCB 25 KA

QA1.119 SPARE 20 DP MCB 25 KA

QA1.120 SPARE 20 DP MCB 25 KA


DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

QA1.121 SPARE 20 DP MCB 25 KA

QA1.122 SPARE 20 DP MCB 25 KA

QA1.123 SPARE 20 DP MCB 25 KA

QA1.124 SPARE 20 DP MCB 25 KA

QA1.125 SPARE 20 DP MCB 25 KA

QA1.126 SPARE 20 DP MCB 25 KA

SEC-B (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-4 FOR LINE FEEDER (FUTURE)-E07 (CB


QB1.1 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
CLOSING CKT)

SUPPLY-4 FOR LINE FEEDER-E05


QB1.2 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR TRANSFORMER T01-E03


QB1.3 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR LINE FEEDER-E01


QB1.4 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR BUS COUPLER-A-E130


QB1.5 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR BUS SECTION 220


QB1.6 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR BUS COUPLER-B -E230


QB1.7 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR TRANSFORMER T02-E02


QB1.8 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR LINE FEEDER-E04


QB1.9 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-4 FOR TRANSFORMER T03-E06


QB1.10 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR LINE FEEDER S/S-E08


QB1.11 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
(CB CLOSING CKT)

SUPPLY-4 FOR LINE FEEDER (FUTURE)-E10 (CB


QB1.12 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
CLOSING CKT)

SUPPLY-5 FOR LINE FEEDER (FUTURE)-E07 (BCU


QB1.13 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
POWER SUPPLY)

SUPPLY-5 FOR LINE FEEDER-E05 (BCU POWER


QB1.14 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
SUPPLY)

SUPPLY-5 FOR TRANSFORMER T01-E03 (BCU


QB1.15 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
POWER SUPPLY)

SUPPLY-4 FOR LINE FEEDER-E01 (BCU POWER


QB1.16 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
SUPPLY)

SUPPLY-4 FOR BUS COUPLER-A-E130 (BCU


QB1.17 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
POWER SUPPLY)

SUPPLY-5 FOR BUS SECTION-E220 (BCU POWER


QB1.18 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
SUPPLY)

SUPPLY-5 FOR BUS COUPLER-B -E230 (BCU


QB1.19 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
POWER SUPPLY)

SUPPLY-5 FOR TRANSFORMER T02-E02 (BCU


QB1.20 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
POWER SUPPLY))

SUPPLY-5 FOR LINE FEEDER-E04 (BCU POWER


QB1.21 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
SUPPLY)

SUPPLY-5 FOR TRANSFORMER T03-E06 (BCU


QB1.22 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
POWER SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-5 FOR LINE FEEDER S/S-E08 (BCU


QB1.23 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
POWER SUPPLY)

SUPPLY-5 FOR LINE FEEDER (FUTURE)-E10 (BCU


QB1.24 35 1 1 35 101.5 0.34 0.41 20 DP MCB 25 KA
POWER SUPPLY)

SUPPLY-6 FOR HV LINE FEEDER (FUTURE)-E07


QB1.25 (SF6 GAS COMPARTMENT& I/O MODULE , BCU 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
AUXILIARY

SUPPLY-6 FOR HV LINE FEEDER-E05 (SF6 GAS


QB1.26 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
COMPARTMENT& I/O MODULE , BCU AUXILIARY

SUPPLY-6 FOR HV TRANSFORMER T01-E03 (SF6


QB1.27 GAS COMPARTMENT& I/O MODULE , BCU 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
AUXILIARY)

SUPPLY-6 FOR HV LINE FEEDER-E01 (SF6 GAS


QB1.28 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
COMPARTMENT& I/O MODULE , BCU AUXILIARY

SUPPLY-6 FOR HV BUS COUPLER-A -E130 (SF6


QB1.29 GAS COMPARTMENT& I/O MODULE , BCU 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
AUXILIARY)

SUPPLY-6 FOR HV BUS SECTION-E220 (SF6 GAS


QB1.30 COMPARTMENT& I/O MODULE AUXILIARY 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
POWER SUPPLY)

SUPPLY-6 FOR HV BUS COUPLER-B -E230 (SF6


QB1.31 GAS COMPARTMENT& I/O MODULE , BCU 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
AUXILIARY)

SUPPLY-6 FOR HV TRANSFORMER T02-E02 (SF6


QB1.32 GAS COMPARTMENT& I/O MODULE , BCU 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
AUXILIARY)

SUPPLY-6 FOR HV LINE FEEDER-E04 (SF6 GAS


QB1.33 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
COMPARTMENT& I/O MODULE , BCU AUXILIARY

SUPPLY-6 FOR HV TRANSFORMER T03-E06 (SF6


QB1.34 GAS COMPARTMENT& I/O MODULE , BCU 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
AUXILIARY)

SUPPLY-6 FOR HV LINE FEEDER -E08 (SF6 GAS


QB1.35 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
COMPARTMENT& I/O MODULE , BCU AUXILIARY
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-6 FOR HV LINE FEEDER (FUTURE)-E10


QB1.36 (SF6 GAS COMPARTMENT& I/O MODULE , BCU 94.5 1 1 94.5 101.5 0.93 1.12 20 DP MCB 25 KA
AUXILIARY

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QB1.37 (AH27) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QB1.38 (AH28) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR INCOMER T02


QB1.39 (AH29) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 252.6 1 1 252.6 101.5 2.49 2.99 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QB1.40 (AH30) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QB1.41 (AH31) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QB1.42 (AH32) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QB1.43 (AH33) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QB1.44 (AH34) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2


QB1.45 (AH35) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV BUS SECTION-02 (AH36)


QB1.46 252.6 1 1 252.6 101.5 2.49 2.99 20 DP MCB 25 KA
(TRIP CKT-1, CLOSE CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8KV BUS RISER-02 (AH37)


QB1.47 123.3 1 1 123.3 101.5 1.21 1.46 20 DP MCB 25 KA
(EARTH SWITCH INTERLOCK, I/O BOX-1)

SUPPLY-1 FOR 13.8kV SWGR AUX-02 FEEDER


QB1.48 (AH38) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.49 (AH39) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.50 (AH40) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.51 (AH41) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.52 (AH42) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.53 (AH43) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.54 (AH44) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV INCOMER T03 (AH45)


QB1.55 252.6 1 1 252.6 101.5 2.49 2.99 20 DP MCB 25 KA
(TRIP CKT-1, CLOSE CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.56 (AH46) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.57 (AH47) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.58 (AH48) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.59 (AH49) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3


QB1.60 (AH50) (TRIP CKT-1, CLOSE CKT/CONTROL CKT, 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
BCU)

SUPPLY FOR 13.8kV SWGR CAP. BANK-03


QB1.61 FEEDER (AH51) (TRIP CKT-1, CLOSE 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
CKT/CONTROL CKT, BCU)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE


QB1.62 FEEDER BUS-3 (AH52) (TRIP CKT-1, CLOSE 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
CKT/CONTROL CKT, BCU)

QB1.63 SUPPLY-1 TO ACDB 700 1 1 700 101.5 6.90 8.28 20 DP MCB 25 KA

SUPPLY FOR 13.8KV AUTOMATIC CAPACITOR


QB1.64 CONTROL SYSTEM PANEL (+ACCS) (HMI & PLC 96.4 1 1 96.4 101.5 0.95 1.14 20 DP MCB 25 KA
MODULE)

SUPPLY FOR HV BUSBAR PROTECTION PANEL


QB1.65 12.5 1 1 12.5 101.5 0.12 0.15 20 DP MCB 25 KA
(INDICATION CKT)

QB1.66 SPARE 20 DP MCB 25 KA

SPARE
QB1.67 20 DP MCB 25 KA

SUPPLY FOR TRANSFORMER-1 +RTCC/AVC


QB1.68 83.5 1 1 83.5 101.5 0.82 0.99 20 DP MCB 25 KA
PANEL (RELAY CKT & AUX CONTROL CKT)

SUPPLY FOR TRANSFORMER-2 +RTCC/AVC


QB1.69 83.5 1 1 83.5 101.5 0.82 0.99 20 DP MCB 25 KA
PANEL (RELAY CKT & AUX CONTROL CKT)

SUPPLY FOR TRANSFORMER-3 +RTCC/AVC


QB1.70 83.5 1 1 83.5 101.5 0.82 0.99 20 DP MCB 25 KA
PANEL (RELAY CKT & AUX CONTROL CKT)

SUPPLY-2 FOR HV BUSBAR-A PROTECTION


QB1.71 13 1 1 13 101.5 0.13 0.15 20 DP MCB 25 KA
PANEL (ZONE-2A PROTN CKT)

SUPPLY-2 FOR HV BUSBAR-B PROTECTION


QB1.72 13 1 1 13 101.5 0.13 0.15 20 DP MCB 25 KA
PANEL (ZONE-2B PROTN CKT)

QB1.73 SUPPLY-1 FOR SAS COMPUTER PANEL-1 1200 1 1 1200 101.5 11.82 14.19 20 DP MCB 25 KA

QB1.74 SUPPLY-1 FOR SAS COMPUTER PANEL-2 1200 1 1 1200 101.5 11.82 14.19 20 DP MCB 25 KA

QB1.75 SUPPLY-1 FOR SAS COMPUTER PANEL-3 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA

SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-A


QB1.76 200 1 1 200 101.5 1.97 2.36 20 DP MCB 25 KA
PANEL-1
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-B


QB1.77 200 1 1 200 101.5 1.97 2.36 20 DP MCB 25 KA
PANEL-1

SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-A


QB1.78 150 1 1 150 101.5 1.48 1.77 20 DP MCB 25 KA
PANEL-2

SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-B


QB1.79 150 1 1 150 101.5 1.48 1.77 20 DP MCB 25 KA
PANEL-2

QB1.80 SUPPLY-1 FOR COMMON ALARM PANEL-1 100 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA

QB1.81 SUPPLY-1 FOR COMMON ALARM PANEL-2 50 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA

SUPPLY-1 FOR SAS CONSOLE DESK (55"


QB1.82 400 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA
MONITOR, 27" MONITOR-2Nos)

SUPPLY-1 FOR DC EMERGENCY LIGHTING FOR


QB1.83 40 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
PROTECTION PANELS

SUPPLY FOR CHANGE OVER SCHEME-2 (ATS


QB1.84 50 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA
FOR DCDB-2)

QB1.85 SPARE 20 DP MCB 25 KA

QB1.86 SPARE 20 DP MCB 25 KA

QB1.87 SUPPLY FOR SDB-1 (SUB ACDB-1) 50 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA

SUPPLY FOR 13.8 KV SWGR O/G FEEDER


QB1.88 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
SECTION-1(AH01 TO AH08, AH10 TO AH17)

SUPPLY FOR 13.8 KV SWGR O/G FEEDER


QB1.89 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
SECTION-2(AH19 TO AH28, AH30 TO AH35)

SUPPLY FOR 13.8 KV SWGR O/G FEEDER


QB1.90 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 25 KA
SECTION-3(AH37 TO AH44, AH46 TO AH52)

SUPPLY FOR 13.8 KV SWGR BUS SECTION-1


QB1.91 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 25 KA
(AH18)(SYNCH TROLLY SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY FOR 13.8 KV SWGR BUS SECTION


QB1.92 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 25 KA
(AH36)(SYNCH TROLLY SUPPLY)

QB1.93 SUPPLY-1 FOR RM PANEL-3 31 1 1 31 101.5 0.31 0.37 20 DP MCB 25 KA

QB1.94 SUPPLY-1 FOR RM PANEL-4 31 1 1 31 101.5 0.31 0.37 20 DP MCB 25 KA

QB1.95 SUPPLY-1 FOR RM PANEL-5 31 1 1 31 101.5 0.31 0.37 20 DP MCB 25 KA

QB1.96 SUPPLY-1 FOR RM PANEL-6 31 1 1 31 101.5 0.31 0.37 20 DP MCB 25 KA

QB1.97 SUPPLY FOR RECEPTACLES IN CONTROL ROOM 200 1 1 200 101.5 1.97 2.36 20 DP MCB 25 KA

SUPPLY FOR TRANSFORMER-1 MECHANICAL


QB1.98 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PROTECTION PANNEL

SUPPLY FOR TRANSFORMER-2 MECHANICAL


QB1.99 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PROTECTION PANNEL

SUPPLY FOR TRANSFORMER-3 MECHANICAL


QB1.100 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PROTECTION PANNEL

SUPPLY FOR LINE FEEDER (FUTURE)-E10


QB1.101 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PROTECTION PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER -E08 PROTECTION


QB1.102 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER -E04 PROTECTION


QB1.103 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER -E01 PROTECTION


QB1.104 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER -E05 PROTECTION


QB1.105 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER(FUTURE)-E07


QB1.106 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PROTECTION PANEL(INTERTRIP-2)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

QB1.107 SPARE 20 DP MCB 25 KA

QB1.108 SPARE 20 DP MCB 25 KA

QB1.109 SPARE 20 DP MCB 25 KA

QB1.110 SPARE 20 DP MCB 25 KA

QB1.111 SPARE 20 DP MCB 25 KA

QB1.112 SPARE 20 DP MCB 25 KA

QB1.113 SPARE 20 DP MCB 25 KA

QB1.114 SPARE 20 DP MCB 25 KA

QB1.115 SPARE 20 DP MCB 25 KA

QB1.116 SPARE 20 DP MCB 25 KA

QB1.117 SPARE 20 DP MCB 25 KA

QB1.118 SPARE 20 DP MCB 25 KA

QB1.119 SPARE 20 DP MCB 25 KA

QB1.120 SPARE 20 DP MCB 25 KA

QB1.121 SPARE 20 DP MCB 25 KA

QB1.122 SPARE 20 DP MCB 25 KA

QB1.123 SPARE 20 DP MCB 25 KA


DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
UNIT TOTAL

FACTOR

FACTOR
DEMAND
CB.No LOAD LOAD LOAD Volts
(W) (W) RATING NO OF SC
AMP AMP Type
AMP POLES Capacity

SUB-DCDB-2 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

225AT/
Q.110 SUPPLY FOR SUB DCDB-2 (SEC-A) 18862.0 1 1 18862 101.5 185.83 223.00 DP MCCB 25 KA
250AF
225AT/
Q.111 SUPPLY FOR SUB DCDB-2 (SEC-B) 18862.0 1 1 18862 101.5 185.83 223.00 DP MCCB 25 KA
250AF
225AT/
Q.112 BUS TIE 18862.0 1 1 18862 101.5 185.83 223.00 DP MCCB 25 KA
250AF

SEC-A (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-10 FOR HV LINE FEEDER (FUTURE)-E07


QA2.1 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
(DS/ES & H-ES MOTOR CKT)

SUPPLY-10 FOR HV LINE FEEDER-E05 (DS/ES & H-


QA2.2 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
ES MOTOR CKT)

SUPPLY-10 FOR HV TRANSFORMER T01-E03


QA2.3 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
(DS/ES & H-ES MOTOR CKT)

SUPPLY-10 FOR HV LINE FEEDER -E01 (DS/ES & H-


QA2.4 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
ES MOTOR CKT)

SUPPLY-10 FOR HV BUS COUPLER-A -E130


QA2.5 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
(DS/ES & H-ES MOTOR CKT)

SUPPLY-10 FOR HV BUS SECTION-E220 (DS/ES &


QA2.6 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
H-ES MOTOR CKT)

SUPPLY-10 FOR HV BUS COUPLER-B -E230 DS/ES


QA2.7 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
& H-ES MOTOR CKT

SUPPLY-10 FOR HV TRANSFORMER T02-E02


QA2.8 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
DS/ES & H-ES MOTOR CKT()

SUPPLY-10 FOR HV LINE FEEDER-E04 DS/ES & H-


QA2.9 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
ES MOTOR CKT()

SUPPLY-10 FOR HV TRANSFORMER T03-E06


QA2.10 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
(DS/ES & H-ES MOTOR CKT)

SUPPLY-10 FOR HV LINE FEEDER -E08 (DS/ES & H-


QA2.11 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
ES MOTOR CKT)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY-10 FOR HV LINE FEEDER (FUTURE)-E10


QA2.12 650 1 1 650 101.5 6.40 7.68 20 DP MCB 25 KA
(DS/ES & H-ES MOTOR CKT)

SUPPLY-8 FOR HV LINE FEEDER (FUTURE)-E07


QA2.13 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
(LAMP, INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV LINE FEEDER-E05 (LAMP,


QA2.14 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV TRANSFORMER T01-E03


QA2.15 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
(LAMP, INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV LINE FEEDER-E01 (LAMP,


QA2.16 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV BUS COUPLER-A -E130 (LAMP,


QA2.17 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV BUS SECTION-E220 (LAMP,


QA2.18 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV BUS COUPLER-B -E230 (LAMP,


QA2.19 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV TRANSFORMER T02-E02


QA2.20 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
(LAMP, INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV LINE FEEDER-E04 (LAMP,


QA2.21 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV TRANSFORMER T03-E06


QA2.22 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
(LAMP, INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV LINE FEEDER S/S-E08 (LAMP,


QA2.23 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
INDICATOR, ANNUNCIATOR )

SUPPLY-8 FOR HV FUTURE FEEDER-E10 (LAMP,


QA2.24 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 25 KA
INDICATOR, ANNUNCIATOR )

SUPPLY-9 FOR LINE FEEDER (FUTURE)-E07 (DS/ES


QA2.25 20.0 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR LINE FEEDER-E05 (DS/ES


QA2.26 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR TRANSFORMER T01-E03 (DS/ES


QA2.27 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY-9 FOR LINE FEEDER-E01 (DS/ES


QA2.28 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR BUS COUPLER-A-E130 (DS/ES


QA2.29 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR BUS SECTION-E220 (DS/ES


QA2.30 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR BUS COUPLER-B -E230 (DS/ES


QA2.31 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR TRANSFORMER T02-E02 (DS/ES


QA2.32 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR LINE FEEDER-E04 (DS/ES


QA2.33 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR TRANSFORMER T03-E06 (DS/ES


QA2.34 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR LINE FEEDER S/S-E08 (DS/ES


QA2.35 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-9 FOR LINE FEEDER (FUTURE)-E10 (DS/ES


QA2.36 20 1 1 20 101.5 0.20 0.24 20 DP MCB 25 KA
CONTROL CIRCUIT)

SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-


QA2.37 1(AH01) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-


QA2.38 1(AH02) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-


QA2.39 1(AH03) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.40 1(AH04) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.41 1(AH05) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.42 1(AH06) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.43 1(AH07) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.44 1(AH08) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR I/C FEEDER


QA2.45 (AH09) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.46 1(AH10) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.47 1(AH11) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.48 1(AH12) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.49 1(AH13) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.50 1(AH14) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.51 1(AH15) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR AUX. TFR. FEEDER


QA2.52 BUS-1(AH16) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR BUS METERING-01


QA2.53 127.2 1 1 127.2 101.5 1.25 1.50 20 DP MCB 25 KA
(AH17) (EARTH SWITCH INTERLOCK, I/O BOX-1)

SUPPLY-2 FOR 13.8kV SWGR BUS SECTION-1


QA2.54 (AH18) (TRIP CKT-2, INDICATION CKT, BCU 717.8 1 1 717.8 101.5 7.07 8.49 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR BUS RISER-01


QA2.55 FEEDER BUS-1(AH19) (EARTH SWITCH 126 1 1 126 101.5 1.24 1.49 20 DP MCB 25 KA
INTERLOCK, I/O BOX-1)

SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-2


QA2.56 (AH20) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2


QA2.57 (AH21) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2


QA2.58 (AH22) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.59 2(AH23) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.60 2(AH24) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.61 2(AH25) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QA2.62 2(AH26) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QA2.63 61.25 1 1 61.25 101.5 0.60 0.72 20 DP MCB 25 KA
PANEL-1 (SET-2)

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QA2.64 61.25 1 1 61.25 101.5 0.60 0.72 20 DP MCB 25 KA
PANEL-2 (SET-2)

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QA2.65 61.25 1 1 61.25 101.5 0.60 0.72 20 DP MCB 25 KA
PANEL-3 (SET-2)

SUPPLY FOR 13.8KV UNDER VOLTAGE LOAD


QA2.66 72.5 1 1 72.5 101.5 0.71 0.86 20 DP MCB 25 KA
SHEDDING PROTECTION PANEL (SET-2)

SUPPLY FOR 13.8KV UNDER VOLTAGE LOAD


QA2.67 SHEDDING PROTECTION PANEL (INDICATION 15.0 1 1 15 101.5 0.15 0.18 20 DP MCB 25 KA
CKT FOR SET-1 & SET-2)

SUPPLY FOR 13.8kV UNDER FREQUENCY LOAD


QA2.68 18.75 1 1 18.75 101.5 0.18 0.22 20 DP MCB 25 KA
SHEDDING PROTECTION PANEL(BUS-A)

QA2.69 SPARE 20 DP MCB 25 KA

SUPPLY-2 FOR SAS CONSOLE DESK (55"


QA2.70 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA
MONITOR, 27" MONITOR-2Nos)

QA2.71 SUPPLY-2 FOR COMMON ALARM PANEL-2 50.0 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA

QA2.72 SUPPLY-2 FOR COMMON ALARM PANEL-1 100.0 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA

SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-B


QA2.73 150.0 1 1 150 101.5 1.48 1.77 20 DP MCB 25 KA
PANEL-2

SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-A


QA2.74 150.0 1 1 150 101.5 1.48 1.77 20 DP MCB 25 KA
PANEL-2

SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-B


QA2.75 200.0 1 1 200 101.5 1.97 2.36 20 DP MCB 25 KA
PANEL-1

SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-A


QA2.76 200.0 1 1 200 101.5 1.97 2.36 20 DP MCB 25 KA
PANEL-1
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

QA2.77 SUPPLY-2 FOR SAS COMPUTER PANEL-3 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA

QA2.78 SUPPLY-2 FOR SAS COMPUTER PANEL-2 1200.0 1 1 1200 101.5 11.82 14.19 20 DP MCB 25 KA

QA2.79 SUPPLY-2 FOR SAS COMPUTER PANEL-1 1200.0 1 1 1200 101.5 11.82 14.19 20 DP MCB 25 KA

QA2.80 SPARE 20 DP MCB 25 KA

QA2.81 SUPPLY FOR SDB-2 (SUB ACDB-2) 50.0 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA

SUPPLY FOR CONTROL CABINET 110/13.8KV T01


QA2.82 592.8 1 1 592.8 101.5 5.84 7.01 20 DP MCB 25 KA
(+MK)

SUPPLY FOR CONTROL CABINET 110/13.8KV T02


QA2.83 592.8 1 1 592.8 101.5 5.84 7.01 20 DP MCB 25 KA
(+MK)

SUPPLY FOR CONTROL CABINET 110/13.8KV T03


QA2.84 592.8 1 1 592.8 101.5 5.84 7.01 20 DP MCB 25 KA
(+MK)

QA2.85 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T01 78.0 1 1 78 101.5 0.77 0.92 20 DP MCB 25 KA

QA2.86 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T02 78.0 1 1 78 101.5 0.77 0.92 20 DP MCB 25 KA

QA2.87 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T03 78.0 1 1 78 101.5 0.77 0.92 20 DP MCB 25 KA

SUPPLY FOR 13.8kV UNDER FREQUENCY LOAD


QA2.88 18.75 1 1 18.75 101.5 0.18 0.22 20 DP MCB 25 KA
SHEDDING PROTECTION PANEL(BUS-C)

SUPPLY FOR 13.8KV UNDER FREQUENCY LOAD


QA2.89 SHEDDING PROTECTION PANEL(INDICATION OF 10.0 1 1 10 101.5 0.10 0.12 20 DP MCB 25 KA
BUS-A,B & C)

QA2.90 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA

QA2.91 SUPPLY-2 TO ACDB 50.0 1 1 50 101.5 0.49 0.59 20 DP MCB 25 KA

QA2.92 SPARE 20 DP MCB 25 KA

QA2.93 SPARE 20 DP MCB 25 KA

QA2.94 SPARE 20 DP MCB 25 KA

QA2.95 SUPPLY-2 FOR AMI PANEL-1 118.0 1 1 118 101.5 1.16 1.40 20 DP MCB 25 KA

QA2.96 SUPPLY-2 FOR AMI PANEL-2 118.0 1 1 118 101.5 1.16 1.40 20 DP MCB 25 KA
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

QA2.97 SUPPLY-2 FOR RM PANEL-1 30.0 1 1 30 101.5 0.30 0.35 20 DP MCB 25 KA

QA2.98 SUPPLY-2 FOR RM PANEL-2 30.0 1 1 30 101.5 0.30 0.35 20 DP MCB 25 KA

SUPPLY-2 FOR DC EMERGENCY LIGHTING FOR


QA2.99 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
CONTROL PANELS

SUPPLY-2 FOR DC EMERGENCY LIGHTING FOR


QA2.100 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
PROTECTION PANELS

SUPPLY FOR 13.8kV UNDER VOLTAGE LOAD


QA2.101 72.50 1 1 72.5 101.5 0.71 0.86 20 DP MCB 25 KA
SHEDDING PROTECTION PANEL(TRIP CKT)

QA2.102 SPARE 20 DP MCB 25 KA

QA2.103 SPARE 20 DP MCB 25 KA

QA2.104 SPARE 20 DP MCB 25 KA

QA2.105 SPARE 20 DP MCB 25 KA

QA2.106 SPARE 20 DP MCB 25 KA

QA2.107 SPARE 20 DP MCB 25 KA

QA2.108 SPARE 20 DP MCB 25 KA

QA2.109 SPARE 20 DP MCB 25 KA

QA2.110 SPARE 20 DP MCB 25 KA

QA2.111 SPARE 20 DP MCB 25 KA

QA2.112 SPARE 20 DP MCB 25 KA

QA2.113 SPARE 20 DP MCB 25 KA

QA2.114 SPARE 20 DP MCB 25 KA

SEC-B (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY-7 FOR HV LINE FEEDER (FUTURE)-E07 (CB


QB2.1 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
TRIP CKT-1)

SUPPLY-7 FOR HV LINE FEEDER-E05 (CB TRIP CKT-


QB2.2 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
1)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY-7 FOR HV TRANSFORMER T01-E03 (CB


QB2.3 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
TRIP CKT-1)

SUPPLY-7 FOR HV LINE FEEDER-E01 (CB TRIP CKT-


QB2.4 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
1)

SUPPLY-7 FOR HV BUS COUPLER-A -E130 (CB


QB2.5 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
TRIP CKT-1)

SUPPLY-7 FOR HV BUS SECTION-E220 (CB TRIP


QB2.6 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
CKT-1)

SUPPLY-7 FOR HV BUS COUPLER-B -E230 (CB


QB2.7 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
TRIP CKT-1)

SUPPLY-7 FOR HV TRANSFORMER T02-E02 (CB


QB2.8 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
TRIP CKT-1)

SUPPLY-7 FOR HV LINE FEEDER-E04 (CB TRIP CKT-


QB2.9 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
1)

SUPPLY-7 FOR HV TRANSFORMER T03-E06 (CB


QB2.10 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
TRIP CKT-1)

SUPPLY-7 FOR HV LINE FEEDER S/S-E08 (CB TRIP


QB2.11 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
CKT-1)

SUPPLY-7 FOR HV LINE FEEDER (FUTURE)-E10 (CB


QB2.12 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA
TRIP CKT-1)

SUPPLY-11 FOR HV LINE FEEDER FUTURE)-E07


QB2.13 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(I/O MODULE POWER SUPPLY)

SUPPLY-11 FOR HV LINE FEEDER-E05 (I/O


QB2.14 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV TRANSFORMER T01-E03 (I/O


QB2.15 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV LINE FEEDER-E01 (I/O


QB2.16 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV BUS COUPLER-A-E130 (I/O


QB2.17 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV BUS SECTION-E220 (I/O


QB2.18 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY-11 FOR HV BUS COUPLER-B-E230 (I/O


QB2.19 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV TRANSFORMER T02-E02 (I/O


QB2.20 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV LINE FEEDER-E04 (I/O


QB2.21 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV TRANSFORMER T03-E06 (I/O


QB2.22 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV LINE FEEDER -E08 (I/O


QB2.23 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
MODULE POWER SUPPLY)

SUPPLY-11 FOR HV LINE FEEDER (FUTURE)-E10


QB2.24 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(I/O MODULE POWER SUPPLY)

SUPPLY-12 FOR HV LINE FEEDER (FUTURE)-E07


QB2.25 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)

SUPPLY-12 FOR HV LINE FEEDER-E05 (SYNCHRO


QB2.26 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
TROLLEY SUPPLY)

SUPPLY-12 FOR HV TRANSFORMER T01-E03


QB2.27 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)

SUPPLY-12 FOR HV LINE FEEDER-E01 (SYNCHRO


QB2.28 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
TROLLEY SUPPLY)

SUPPLY-12 FOR HV BUS COUPLER-A -E130


QB2.29 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)

SUPPLY-12 FOR HV BUS SECTION-E220


QB2.30 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)

SUPPLY-12 FOR HV BUS COUPLER-B -E230


QB2.31 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)

SUPPLY-12 FOR HV TRANSFORMER T02-E02


QB2.32 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)

SUPPLY-12 FOR HV LINE FEEDER-E04 (SYNCHRO


QB2.33 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
TROLLEY SUPPLY)

SUPPLY-12 FOR HV TRANSFORMER T03-E06


QB2.34 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY-12 FOR HV LINE FEEDER S/S-E08


QB2.35 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)

SUPPLY-12 FOR HV LINE FEEDER (FUTURE)-E10


QB2.36 40.0 1 1 40 101.5 0.39 0.47 20 DP MCB 25 KA
(SYNCHRO TROLLEY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.37 2(AH27) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.38 2(AH28) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR I/C FEEDER (AH29)


QB2.39 (TRIP CKT-2, INDICATION CKT, BCU AUXILIARY 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.40 2(AH30) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.41 2(AH31) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.42 2(AH32) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.43 2(AH33) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.44 2(AH34) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.45 2(AH35) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR BUS SECTION-02


QB2.46 (AH36) (TRIP CKT-2, INDICATION CKT, BCU 717.8 1 1 717.8 101.5 7.07 8.49 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR BUS RISER-01


QB2.47 FEEDER BUS-1(AH37) (EARTH SWITCH 126.0 1 1 126 101.5 1.24 1.49 20 DP MCB 25 KA
INTERLOCK, I/O BOX-1SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR AUX. TFR. FEEDER


QB2.48 BUS-2(AH38) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.49 3(AH39) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.50 3(AH40) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.51 3(AH41) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.52 3(AH42) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.53 3(AH43) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.54 3(AH44) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.55 3(AH45) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.56 3(AH46) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.57 3(AH47) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.58 3(AH48) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.59 3(AH49) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-


QB2.60 3(AH50) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-


QB2.61 3(AH51) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-


QB2.62 3(AH52) (TRIP CKT-2, INDICATION CKT, BCU 722.6 1 1 722.6 101.5 7.12 8.54 20 DP MCB 25 KA
AUXILIARY SUPPLY)

SUPPLY FOR FUTURE FEEDER-E07 PROTECTION


QB2.63 PANEL SET-2 (MAIN-2 PROTN CKT & IN/OUT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
RELAY CKT)

SUPPLY FOR SPARE FEEDER -E05 PROTECTION


QB2.64 PANEL SET-2 (MAIN-2 PROTN CKT & IN/OUT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
RELAY CKT)

SUPPLY FOR TRANSFORMER T01-E03


QB2.65 PROTECTION PANEL SET-2 (MAIN-2 PROTN CKT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
& IN/OUT RELAY CKT)

SUPPLY FOR LINE FEEDER-E01 PROTECTION


QB2.66 PANEL SET-2 (MAIN-2 PROTN CKT & IN/OUT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
RELAY CKT)
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY FOR TRANSFORMER T02-E02


QB2.67 PROTECTION PANEL SET-2 (MAIN-2 PROTN CKT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
& IN/OUT RELAY CKT)

SUPPLY FOR LINE FEEDER-E04 PROTECTION


QB2.68 PANEL SET-2 (MAIN-2 PROTN CKT & IN/OUT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
RELAY CKT)

SUPPLY FOR TRANSFORMER T03-E06


QB2.69 PROTECTION PANEL SET-2 (MAIN-2 PROTN CKT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
& IN/OUT RELAY CKT)

SUPPLY FOR SPARE FEEDER-E08 PROTECTION


QB2.70 PANEL SET-2 (MAIN-2 PROTN CKT & IN/OUT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
RELAY CKT)

SUPPLY FOR FUTURE FEEDER- E10 PROTECTION


QB2.71 PANEL SET-2 (MAIN-2 PROTN CKT & IN/OUT 11.9 1 1 11.9 101.5 0.12 0.14 20 DP MCB 25 KA
RELAY CKT)

SUPPLY FOR FUTURE FEEDER-E07 PROTECTION


QB2.72 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
PANEL SET-1 & SET-2(INDICATION CKT)

SUPPLY FOR SPARE FEEDER -E05 PROTECTION


QB2.73 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
PANEL SET-1 & SET-2(INDICATION CKT)

SUPPLY FOR TRANSFROMER T01-E03


QB2.74 PROTECTION PANEL SET-1 & SET-2(INDIACTION 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
CKT)

SUPPLY FOR LINE FEEDER-E01 PROTECTION


QB2.75 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
PANEL SET-1 & SET-2(INDICATION CKT)

SUPPLY FOR TRANSFORMER T02-E02


QB2.76 PROTECTION PANEL SET-1 & SET-2(INDIACTION 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
CKT)

SUPPLY FOR LINE FEEDER-E04 PROTECTION


QB2.77 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
PANEL SET-1 & SET-2(INDICATION CKT)

SUPPLY FOR TRANSFORMER T03-E06


QB2.78 PROTECTION PANEL SET-1 & SET-2(INDIACTION 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
CKT)

SUPPLY FOR SPARE FEEDER-E08 PROTECTION


QB2.79 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
PANEL SET-1 & SET-2 (INDICATION CKT)

SUPPLY FOR FUTURE FEEDER-E10 PROTECTION


QB2.80 1.0 1 1 1 101.5 0.01 0.01 20 DP MCB 25 KA
PANEL SET-1 & SET-2(INDICATION CKT)

QB2.81 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA

QB2.82 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA

QB2.83 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA


DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

SUPPLY FOR LINE FEEDER(FUTURE)-E10


QB2.84 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PROTECTION PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER-E08 PROTECTION


QB2.85 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER-E04 PROTECTION


QB2.86 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER-E01 PROTECTION


QB2.87 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER-E05 PROTECTION


QB2.88 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PANEL(INTERTRIP-2)

SUPPLY FOR LINE FEEDER(FUTURE)-E07


QB2.89 127.0 1 1 127 101.5 1.25 1.50 20 DP MCB 25 KA
PROTECTION PANEL(INTERTRIP-2)

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QB2.90 2.3 1 1 2.25 101.5 0.02 0.03 20 DP MCB 25 KA
PANEL-1 (INDICATION CKT)

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QB2.91 2.3 1 1 2.25 101.5 0.02 0.03 20 DP MCB 25 KA
PANEL-2 (INDICATION CKT)"

SUPPLY FOR 13.8KV CAPACITOR PROTECTION


QB2.92 2.3 1 1 2.25 101.5 0.02 0.03 20 DP MCB 25 KA
PANEL-3 (INDICATION CKT)"

QB2.93 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA

QB2.94 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA

QB2.95 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA

SUPPLY FOR 13.8 KV BUSBAR PROTECTION


QB2.96 1.3 1 1 1.25 101.5 0.01 0.01 20 DP MCB 25 KA
PANEL (INDICATION SET-1 & SET-2 CKT)"

SUPPLY FOR 13.8 KV BUSBAR PROTECTION


QB2.97 1.3 1 1 1.25 101.5 0.01 0.01 20 DP MCB 25 KA
PANEL (INDICATION SET-3 CKT)"

QB2.98 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA

QB2.99 SPARE 1 1 0 101.5 0.00 0.00 20 DP MCB 25 KA

QB2.100 SUPPLY-2 FOR RM PANEL-3 31.0 1 1 31 101.5 0.31 0.37 20 DP MCB 25 KA

QB2.101 SUPPLY-2 FOR RM PANEL-4 31.0 1 1 31 101.5 0.31 0.37 20 DP MCB 25 KA

QB2.102 SUPPLY-2 FOR RM PANEL-5 31.0 1 1 31 101.5 0.31 0.37 20 DP MCB 25 KA


DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

QB2.103 SUPPLY-2 FOR RM PANEL-6 31.0 1 1 31 101.5 0.31 0.37 20 DP MCB 25 KA

QB2.104 13.8kV BBP(1A)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 25 KA

QB2.105 13.8kV BBP(1B)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 25 KA

QB2.106 13.8kV BBP(1C)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 25 KA

QB2.107 SPARE 20 DP MCB 25 KA

QB2.108 SPARE 20 DP MCB 25 KA

QB2.109 SPARE 20 DP MCB 25 KA

QB2.110 SPARE 20 DP MCB 25 KA

QB2.111 SPARE 20 DP MCB 25 KA

QB2.112 SPARE 20 DP MCB 25 KA

QB2.113 SPARE 20 DP MCB 25 KA

QB2.114 SPARE 20 DP MCB 25 KA

QB2.115 SPARE 20 DP MCB 25 KA

QB2.116 SPARE 20 DP MCB 25 KA

QB2.117 SPARE 20 DP MCB 25 KA

QB2.118 SPARE 20 DP MCB 25 KA


DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

BREAKER FOR BATTERY FROM CHARGERS

500AT/
Q.102 BREAKER FOR THE BATTERY- FROM CHARGERS 40600 1 1 40600 101.5 400.000 480.0 DP MCCB 25 KA
630AF

EMERGENCY LIGHTING PANEL- (125 VDC, 2WIRES SYSTEM, 80A @40°C)

75AT/
QM1 SUPPLY FOR SUB DCDB-ELP (SEC-A) 5800.00 1 1 5800.00 101.5 57.14 68.57 DP MCCB 25 KA
80AF
75AT/
QM2 SUPPLY FOR SUB DCDB-ELP (SEC-B) 5800.0 1 1 5800.00 101.5 57.14 68.57 DP MCCB 25 KA
80AF
75AT/
QM3 BUS TIE 5800.0 1 1 5800.00 101.5 57.14 68.57 DP MCCB 25 KA
80AF

SEC-A (125 VDC , 2WIRES SYSTEM, 80A @40°C)

QA.001 HV GIS ROOM 800.0 1 1 800 101.5 7.88 9.46 20 DP MCB 25 KA

QA.002 HV GIS ROOM 800.0 1 1 800 101.5 7.88 9.46 20 DP MCB 25 KA

QA.003 CONTROL ROOM 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QA.004 CONTROL ROOM 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QA.005 CONTROL ROOM 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QA.006 CONTROL ROOM 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QA.007 STAIR CASE 300.0 1 1 300 101.5 2.96 3.55 20 DP MCB 25 KA

QA.008 TELECOM ROOM 200.0 1 1 200 101.5 1.97 2.36 20 DP MCB 25 KA

QA.009 FM ROOM 300.0 1 1 300 101.5 2.96 3.55 20 DP MCB 25 KA

QA.010 RECORD ROOM 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QA.011 PUSH BUTTON FOR GIS ROOM CABLE BASEMENT 100.0 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA

QA.012 PUSH BUTTON FOR SWG ROOM 100.0 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
DC C.B SIZING :-
System Voltage = 125 VDC IFL = LOAD(W) / V
Total Load= Demand Factor x Diversity Factor x Unit Load
V = 101.5 End Of Discharge Voltage IOLC = IFL x1.2

IFL IOLC C.B DATA

DIVERISITY
TOTAL

FACTOR

FACTOR
DEMAND
UNIT
CB.No LOAD LOAD Volts
LOAD (W) RATING NO OF SC
(W) AMP AMP Type
AMP POLES Capacity

QA.013 SWGR CABLE BASEMENT 100.0 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA

QA.014 FM ROOM1 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA

QA.015 SWGR CABLE BASEMENT 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA

QA.016 BASEMENT CORRIDOOR 500.0 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA

QA.017 WORKSHOP 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QA.018 EQUIPMENT ROOM 300.0 1 1 300 101.5 2.96 3.55 20 DP MCB 25 KA

QA.019 SPARE 20 DP MCB 25 KA

QA.020 SPARE 20 DP MCB 25 KA

QA.021 SPARE 20 DP MCB 25 KA

QA.022 SPARE 20 DP MCB 25 KA

SEC-B (125 VDC , 2WIRES SYSTEM, 80A @40°C)

QB.001 MV SWGR ROOM 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QB.002 MV SWGR ROOM 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QB.003 STAIR CASE 300.0 1 1 300 101.5 2.96 3.55 20 DP MCB 25 KA

QB.004 STAIR CASE 300.0 1 1 300 101.5 2.96 3.55 20 DP MCB 25 KA

QB.005 CONTROL ROOM 400.0 1 1 400 101.5 3.94 4.73 20 DP MCB 25 KA

QB.006 TOILET 500 1 1 500 101.5 4.93 5.91 20 DP MCB 25 KA

QB.007 PUCH BUTTON FOR SWGR CABLE BASEMENT 100 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA

QB.008 PUSH BUTTON FOR GIS ROOM 100 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA

QB.009 PUSH BUTTON FOR CONTROL ROOM 100 1 1 100 101.5 0.99 1.18 20 DP MCB 25 KA
CERT'D
APPR'D
CHK'D

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION

UNIFIED LV AC CIRCUIT BREAKER SIZING CALCULATIONS


(COA & WOA)
BY
DATE
NO

REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
TO BE USED FOR UNIFIED LV AC CIRCUIT BREAKER SIZING
CONSTRUCTION OF
FOR ORDERING CALCULATIONS
MATERIALS UNTIL
CERTIFIED AND (COA & WOA)
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.

DMS EXCEL
INDEX

SHEET NO. CONTENT

1 Cover
2 Index& Legend
3 Design Basis for C.B
4-5 Short Circuit Calculation
6-9 AC C.B Sizing

LEGEND

IFL : FULL LOAD CURRENT

IOLC : OVER LOAD CURRENT

ACB : AIR CIRCUIT BREAKER

MCCB : MOULDED CASE CIRCUIT BREAKER

MCB : MINIATURE CIRCUIT BREAKER

SDP : SUB DISTRIBUTION PANEL

ACDB : AC DISTRIBUTION BOARD

MK : MASHALLING KIOSK

MFACP : MAIN FIRE ALARM CONTROL PANEL

SPF :SMOKE PURGE FAN

LCC : LOCAL CONTROL CUBICLE


Design Basis:

1- The current ratings given for C.B.'s are the thermal current rating requirement after ambient temperature
derating. ( Panel manufacturer should take care for temperature derating of this breakers) as per 31-TMSS-
02 (latest revision)

2- Circuit breakers ( number, rating ) are subject to change as per loads update.

3- Load power factor is taken as 0.85 for pump loads, rotating machinery, power sockets, cooling fans.

4- All circuit breakers interruption capacity shall be the same as that of bus short circuit withstand capacity.

5- MCCBs in main AC distribution panel shall be of triple pole with neutral link (TPN) as per TES-P-119.30 Rev.02,
Clause 3.2.3

6- Main AC Distribution panel Bus bars shall withstand full available short circuit current and shall not be less
than 25KA as per TES-P-119.30 Rev.02, Clause 3.2.2

7- ACB and MCCB shall be selected in accordance with load requirements and shall be rated for 120%
overloading capacity as per Technical Specification TES-P-119.30 Rev.02, Clause 3.2.6

8- MCCB shall be provided with overload, short circuit and earth fault release As per TES-P-119.30 Rev.02,
Clause 3.2.8

9- The incoming and bus-tie circuit breakers feeding the main distribution panel shall be ACB type and 4
pole. All the remaining feeder breakers shall be MCCB. However feeder circuit rated 32A and below may
be provided with MCB subject to SEC approval as per Materials Standard 31-TMSS-02, Rev.02 clause
4.4.1.b.(i).
10- Duration of short circuit interrupting capacity for MCCB & MCB shall be 1 Sec.

11- The Indoor Ambient temperature (According to 01-TMSS-01 Rev.03) for:

1- Air-Conditioned building : 25 °C.


2- Ventilated building : 40 °C.

12- Short circuit current rating of AC sub Distribution panels shall be as per design calculations and NGSA
approval.

Reference Documents
DRAWING CONTROL SHEET

UNIFIED OVERALL SUBSTATION GENERAL LAYOUT

UNIFIED SWITCHING SINGLE LINE DIAGRAM

UNIFIED AUXILARY TRANSFORMER SIZING CALCULATIONS

UNIFIED AC AUXILARY ONE LINE DIAGRAM


Short circuit calculation :
System Data:

Medium Voltage Level 13.8 kV

Low Voltage Level 0.4 kV

13.8kV Bus-1 Fault level = 25 KA


(with two Transformers)

13.8kV/400V Transformer Data = 500 KVA Z= 5 %

Calculations

13.8kV Source impedance(Zs1) = 13.8 x 103 = 0.3187 Ω


3
sqrt(3) x 25 x 10

V2 = (13.8 kv)2
13.8kV Bus Fault level S= Ω = 597.56 MVA
Zs1 0.3187
Incomer Cable from 13.8kV SWGR to Station Service Transformer
No. of cables/phase = 1
Type of insulation = XLPE
No. of cores of cable = 1C
Size of selected cable = 300 sq.mm
So the selected cable = XLPE1CX300
Cable Resistance = 0.081700 Ω/km/Run
Cable Reactance = 0.094000 Ω/km/Run
Cable Length = 50 m
Cable Impedence = Sqrt(Rc2+Xc2) = 0.124543 Ω/km/Run
Total Cable Impedence (Zt) = 0.006227 Ω

13.8kV Source total Impedance = Zt + Zs1 = 0.324924 Ω

13.8kV Source total Impedance = (Zt + Zs1) X(VLV)² = 0.3249 x (400)2 0.000273 Ω
3 2
transferred to 400V side (VMV)² (13.8x10 )

2
Transformer Impedance = (VLV) X (Z%) = (400)² X 0.05 = 0.016000 Ω
KVA X 10
3 500X 10³
Cable from Station Service Transformer to Main ACDB
No. of cables/phase = 3
Type of insulation = XLPE
No. of cores of cable = 1C
Size of selected cable = 630 sq.mm
So the selected cable = XLPE1CX630
Cable Resistance R = 0.054500 Ω/km/Run
Cable Reactance X = 0.092000 Ω/km/Run
Cable Length = 44 m
Cable Impedence = Sqrt(Rc2+Xc2) = 0.106931 Ω/km/Run
Total Cable Impedence (Zt) = 0.001568 Ω

Total Impedance on 400 V side = 0.00027 + 0.016000 + 0.001568


= 0.01784 Ω

Fault level,400 V side = 400 = 12.94 kA


0.01784 x sqrt(3)

Proposed BB Short Circuit Rating 25 kA

Then the selected Bus Bar Short Circuit shall be minimum 25 KA as per TES-P-119.30 R02

Conclusion:
"The Main BUSBAR shall withstand a minimmum short circuit of 25 kA," as per TES-P-119.30 R02 .
All circuit breakers used in 400V Main ACDB are having a minimum fault interrupting capacity of 25kA.
Hence, the above fault current is acceptable.
AC LOAD CALCULATION:-

System Voltage = 400 / 230 VAC


IFL 3ᵩ = KWx1000/(√3 xVxPF) POWER FACTOR : 0.85
IFL 1ᵩ = Kw x 1000 / (VxPF) TPN : TRIPLE POLE WITH NEUTRAL LINK
IOLC = 1.20 x IFL SPN : SINGLE POLE WITH NEUTRAL LINK
4P : FOUR POLE
UNIT TOTAL TOTAL Load details of

DIVERSITY
FACTOR
C.B DATA
*

PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP

ACDB (CONTROL ROOM)

Q101 FROM AUX.T1 TO ACDB (BUS - A) 425.00 - 425.00 500 3 400 722 866 1000AT/1000AF ACB 4P -

Q102 FROM AUX.T2 TO ACDB (BUS - B) 425.00 - 425.00 500 3 400 722 866 1000AT/1000AF ACB 4P -

Q103 BUS TIE 425.00 - 425.00 500 3 400 722 866 1000AT/1000AF ACB 4P -

400/230V, 1000A, 25kA (1s), 60Hz, 3PH 4 WIRE MAIN ACDB - BUS A

Q.A1 400V,3PH SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU-1A (DUTY). 97.00 - 97.00 114.12 3 400 164.72 197.7 200AT/250AF MCCB TPN -

Q.A2 400V,3PH SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU-2B (STANDBY). 56.00 - 56.00 65.88 3 400 95.10 114.1 125AT/160AF MCCB TPN -

Q.A3 SUPPLY FOR SUB DISTRIBUTION PANEL-1 ( SDP-1). 70.48 - 70.48 82.92 3 400 119.68 143.6 160AT/250AF MCCB TPN -

Q.A4 SUPPLY FOR INDOOR LIGHTING PANEL (ILP-1). 10.80 - 10.80 12.70 3 400 18.34 22.0 32AT/160AF MCCB TPN -

Q.A5 SUPPLY FOR INDOOR LIGHTING PANEL (ILP-2) 4.47 - 4.47 5.26 3 400 7.59 9.1 20 MCB TPN -

Q.A6 SUPPLY FOR 125V DC NICAD BATTERY CHARGER-1. 55.00 - 55.00 65.00 3 400 93.82 112.6 200AT/250AF MCCB TPN -

200AMP,400V RECEPTACLE FOR OIL FILTRATION UNIT FOR POWER TRANSFORMERS AREA (T-
Q.A7 98.098 - 98.10 115.41 3 400 166.58 199.9 200AT/250AF MCCB TPN -
01)
200AMP,400V RECEPTACLE FOR OIL FILTRATION UNIT FOR POWER TRANSFORMERS AREA (T-02
Q.A8 98.098 - 98.10 115.41 3 400 166.58 199.9 200AT/250AF MCCB TPN -
)

Q.A9 63AMP,400V WELDING & MAINTENANCE RECEPTACLE FOR POWER TRANSFORMER AREA (T-01) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -

Q.A10 63AMP,400V WELDING & MAINTENANCE RECEPTACLE FOR POWER TRANSFORMER AREA (T-02) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN

Q.A11 63AMP,400V WELDING RECEPTACLE FOR CAPACITOR BANKS AREA (CAP-01 & CAP-02 ) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -

Q.A12 63AMP,400V WELDING RECEPTACLE FOR AUXILARY TRANSFORMERS (AUX-01 & AUX-02) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -

Q.A13 63AMP,400V WELDING RECEPTACLE FOR PACU UNITS (1A & 1B) ON THE ROOF. 30.50 - 30.50 35.88 3 400 51.79 62.2 63AT/160AF MCCB TPN -

Q.A14 40AMP,400V GAS FILLING RECEPTACLE-01 AT GIS ROOM. 19.00 - 19.00 22.35 3 400 32.26 38.7 40AT/160AF MCCB TPN -

Q.A15 40AMP,400V GAS FILLING RECEPTACLE-02 AT GIS ROOM. 19.00 - 19.00 22.35 3 400 32.26 38.7 40AT/160AF MCCB TPN -

Q.A16 400V,3PH SUPPLY-1 FOR EXTERNAL TELECOM SHELTER 34.05 - 34.05 40.06 3 400 57.82 69.4 125AT/160AF MCCB TPN -

Q.A17 SPARE 3 400 20 MCB TPN -

Q.A18 SUPPLY FOR HVAC CONTROL PANEL-1 29.44 - 29.44 34.64 3 400 49.99 60.0 63AT/160AF MCCB TPN -

Q.A19 SPARE 3 400 32AT/160AF MCCB TPN -

Q.A20 SPARE 3 400 40AT/160AF MCCB TPN -

Q.A21 SPARE 3 400 63AT/160AF MCCB TPN -

Q.A22 SPARE 3 400 63AT/160AF MCCB TPN -

Q.A23 SPARE 3 400 125AT/160AF MCCB TPN -

Q.A24 SPARE 3 400 160AT/250AF MCCB TPN -

Q.A25 SPARE 3 400 200AT/250AF MCCB TPN -

Q.A26 SPARE 3 400 200AT/250AF MCCB TPN -

400/230V, 1000A, 25kA (1s), 60Hz, 3PH 4 WIRE MAIN ACDB - BUS B

Q.B1 SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU-1B (STANDBY). 97.00 - 97.00 114.12 3 400 164.72 197.7 200AT/250AF MCCB TPN -

Q.B2 SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU-2A (DUTY). 56.00 - 56.00 65.88 3 400 95.10 114.1 125AT/160AF MCCB TPN -

Q.B3 SUPPLY FOR SUB DISTRIBUTION PANEL-2 ( SDP-2). 62.76 - 62.76 73.83 3 400 106.57 127.9 160AT/250AF MCCB TPN -

Q.B4 SUPPLY FOR POWER RECEPTACLE PANEL 19.80 - 19.80 23.29 3 400 33.62 40.3 50AT/160AF MCCB TPN -

Q.B5 SUPPLY FOR OUTDOOR LIGHTING PANEL (OLP). 6.48 - 6.48 7.62 3 400 11.00 13.2 20 MCB TPN -

Q.B6 SUPPLY FOR 125V DC NICAD BATTERY CHARGER-2. 55.00 - 55.00 65.00 3 400 93.82 112.6 200AT/250AF MCCB TPN -

Q.B7 200AMP,400V RECEPTACLE FOR OIL FILTRATION UNIT FOR POWER TRANSFORMERS AREA (T-03) 98.10 - 98.10 115.41 3 400 166.58 199.9 200AT/250AF MCCB TPN -

Q.B8 63AMP,400V WELDING & MAINTENANCE RECEPTACLE FOR POWER TRANSFORMER AREA (T-03) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -
UNIT TOTAL TOTAL Load details of

DIVERSITY
FACTOR
C.B DATA
*

PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP

Q.B9 63AMP,400V WELDING RECEPTACLE FOR CAPACITOR BANKS AREA (CAP-03) 30.05 - 30.05 35.35 3 400 51.03 61.2 63AT/160AF MCCB TPN -

Q.B10 63AMP,400V WELDING RECEPTACLE FOR PACU UNITS (2A & 2B) ON THE ROOF. 30.50 - 30.50 35.88 3 400 51.79 62.2 63AT/160AF MCCB TPN -

Q.B11 SPARE 3 400 63AT/160AF MCCB TPN -

Q.B12 40AMP,400V GAS FILLING RECEPTACLE-03 AT GIS ROOM. 19.00 - 19.00 22.35 3 400 32.26 38.7 40AT/160AF MCCB TPN -

Q.B13 HV TEST BUSHING RECEPTACLES FOR GIS 61.29 - 61.29 72.11 3 400 104.08 124.9 125AT/160AF MCCB TPN -

Q.B14 400V,3PH SUPPLY-2 FOR EXTERNAL TELECOM SHELTER. 30.50 - 30.50 35.88 3 400 51.79 62.2 125AT/160AF MCCB TPN -

Q.B15 SPARE 3 400 20 MCB TPN -

Q.B16 SUPPLY FOR HVAC CONTROL PANEL-2 29.44 - 29.44 34.64 3 400 49.99 60.0 63AT/160AF MCCB TPN -

Q.B17 400V,3PH PORTABLE BATTERY CHARGER SUPPLY 30.50 - 30.50 35.88 3 400 51.79 62.2 63AT/160AF MCCB TPN -

Q.B18 400V,3PH SUPPLY FOR EOT CRANE. 9.84 - 9.84 11.58 3 400 16.71 20.1 32AT/160AF MCCB TPN -

Q.B19 400V,3PH SUPPLY FOR JIB CRANE. 9.84 - 9.84 11.58 3 400 16.71 20.1 32AT/160AF MCCB TPN -

Q.B20 SPARE 3 400 32AT/160AF MCCB TPN -

Q.B21 SPARE 3 400 40AT/160AF MCCB TPN -

Q.B22 SPARE 3 400 50AT/160AF MCCB TPN -

Q.B23 SPARE 3 400 63AT/160AF MCCB TPN -

Q.B24 SPARE 3 400 125AT/160AF MCCB TPN -

Q.B25 SPARE 3 400 160AT/250AF MCCB TPN -

Q.B26 SPARE 3 400 200AT/250AF MCCB TPN -

Q.B27 SPARE 3 400 200AT/250AF MCCB TPN -

400/230V, 250A, 60Hz, 3PH 4 WIRE AC SDP-1 (CONTROL ROOM)

QC SUPPLY FOR AC SDP-1 70.48 1 70.48 82.92 3 400 119.68 143.62 160AT/250AF MCCB TPN 70.48

QC.1 SPARE 3 400 20 MCB TPN 0.00

QC.2 SPARE 3 400 20 MCB TPN 0.00

QC.3 SPARE 3 400 20 MCB TPN 0.00

QC.4 SPARE 3 400 20 MCB TPN 0.00

QC.5 SPARE 3 400 20 MCB TPN 0.00

QC.6 SPARE 3 400 32 MCB TPN 0.00

QC.7 SPARE 3 400 63AT/160AF MCCB TPN 0.00

QC.8 400V 3PH SUPPLY-1 FOR TR-1 LCP (FANS , MK ) (MAIN) 26.7 0.5 26.74 31.46 3 400 45.41 54.5 63AT/160AF MCCB TPN 13.37

QC.9 400V 3PH SUPPLY-1 FOR TR-2 LCP (FANS , MK ) (MAIN) 26.7 0.5 26.74 31.46 3 400 45.41 54.5 63AT/160AF MCCB TPN 13.37

QC.10 400V 3PH SUPPLY-1 FOR TR-3 LCP (FANS , MK ) (STANDBY) 26.7 0.5 26.74 31.46 3 400 45.41 54.5 63AT/160AF MCCB TPN 13.37

QC.11 400V 3PH SUPPLY-1 FOR TR-1 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00

QC.12 400V 3PH SUPPLY-1 FOR TR-2 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00

QC.13 400V 3PH SUPPLY-1 FOR TR-3 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00

QC.14 400V,AC SUPPLY FOR HV GIS ROOM EXHAUST FAN 2.33 0 2.33 2.74 3 400 3.96 4.7 20 MCB TPN 0.00

QC.15 400V, AC SUPPLY FOR FM-200- ROOM-01 EXHAUST FAN 0.24 0 0.24 0.28 3 400 0.41 0.5 20 MCB TPN 0.00

QC.16 400V, AC SUPPLY FOR SECURITY SYSTEM 3.17 1 3.17 3.730 3 400 5.38 6.5 20 MCB TPN 3.17

QC.17 400V, AC SUPPLY FOR BASEMENT EXHAUST FAN 03 2.24 1 2.24 4.748 3 400 6.85 8.2 20 MCB TPN 2.24

QC.18 400V, AC SUPPLY FOR BASEMENT EXHAUST FAN 02 2.24 1 2.24 3.677 3 400 5.31 6.4 20 MCB TPN 2.24

QC.19 400V AC SUPPLY FOR SMOKE PURGE FAN-01 (SEF-01) 2.43 0 2.43 2.86 3 400 4.13 5.0 20 MCB TPN 0.00

QC.20 400V AC SUPPLY FOR SMOKE PURGE FAN-02 (SEF-02) 3.50 0 3.50 4.12 3 400 5.94 7.1 20 MCB TPN 0.00

QC.21 ELECTRICAL DUCT HEATER 10.00 0 10.00 10.00 3 400 14.43 17.3 20 MCB TPN 0.00

QC.22 400V AC SUPPLY-1 FOR MISCELLANEOUS PORTABLE TOOLS 1.00 0.5 1.00 1.18 3 400 1.70 2.0 20 MCB TPN 0.50
UNIT TOTAL TOTAL Load details of

DIVERSITY
FACTOR
C.B DATA
*

PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP

QC.23 400V AC SUPPLY FOR HV GIS LCC E10 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.24 400V AC SUPPLY FOR HV GIS LCC E08 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.25 400V AC SUPPLY FOR HV GIS LCC E06 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.26 400V AC SUPPLY FOR HV GIS LCC E04 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.27 400V AC SUPPLY FOR HV GIS LCC E02 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.28 400V AC SUPPLY FOR HV GIS LCC E230 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.29 400V AC SUPPLY FOR HV GIS LCC E220 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.30 400V AC SUPPLY FOR HV GIS LCC E130 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.31 400V AC SUPPLY FOR HV GIS LCC E01 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.32 400V AC SUPPLY FOR HV GIS LCC E03 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.33 400V AC SUPPLY FOR HV GIS LCC E05 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

QC.34 400V AC SUPPLY FOR HV GIS LCC E07 (HTR,LTNG,SCKT) 0.81 0.06 0.81 0.95 3 400 1.38 1.7 20 MCB TPN 0.05

230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(


QC.35 1.0100 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27
+PSE,+CBP-3,+CBP-2,+CBP-1,+ACCS,+ABTS )
230VAC SUPPLY FOR CONTROL ROOM PANELS
QC.36 1.01 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27
(HTR,LTNG,SCKT)(BBA,BBB.BBCH,BBZ1,BBZ2,BBZ3)
230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(+3SYN,+UFP-1,+UVP-1,+UFP-
QC.37 1.01 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27
2,UVP- 2)
230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT)
QC.38 1.47 0.27 1.47 1.73 1 230 7.52 9.0 20 MCB SPN 0.40
(+R07.2,+R07.1,+R10.2F,+R10.1F,FUT,FUT+R08.2,+R08.1)
230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT)
QC.39 1.36 0.27 1.36 1.60 1 230 6.96 8.3 20 MCB SPN 0.37
(+R06.2,+R06.1,+R4.2,+R4.1,+R02.2,+R02.1)

QC.40 230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT) (+R230,+R220,+R130) 0.49 0.27 0.49 0.58 1 230 2.50 3.0 20 MCB SPN 0.13

230VAC SUPPLY FOR CONTROL ROOM PANELS(HTR,LTNG,SCKT)


QC.41 1.47 0.27 1.47 1.73 1 230 7.52 9.0 20 MCB SPN 0.40
(+R01.2,+R01.1,+R03.2,+R03.1,+R05.2,+R05.1,FUT,FUT)

QC.42 230V AC SUPPLY-1 FOR TR-1 OLTC LIGHTING & HEATER. 0.37 0.5 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19

QC.43 230V AC SUPPLY-1 FOR TR-2 OLTC LIGHTING & HEATER. 0.37 0.5 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19

QC.44 230V AC SUPPLY-1 FOR TR-3 OLTC LIGHTING & HEATER. 0.37 0.5 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19

QC.45 230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-1 (AH01 TO AH18) 4.94 1 4.94 5.81 1 230 25.24 30.3 32 MCB SPN 4.94

QC.46 230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-2 (AH19 TO AH36) 4.610 1 4.610 5.42 1 230 23.58 28.3 32 MCB SPN 4.61

QC.47 230VAC SUPPLY 13.8KV SWGR. PANELS OF SECTION-3 (AH37 TO AH53) HTR,LTNG,SCKT) 4.840 1 4.840 5.69 1 230 24.76 29.7 32 MCB SPN 4.84

QC.48 230VAC SUPPLY FOR FUTURE PANELS 1 230 20 MCB SPN

QC.49 230VAC SUPPLY FOR FUTURE PANELS 1 230 20 MCB SPN -

QC.50 230VAC SUPPLY-1 FOR SAS PANELS ROW (HTR,LTNG,SCKT) 0.87 0.27 0.87 1.02 1 230 4.45 5.3 20 MCB SPN 0.23

QC.51 230VAC SUPPLY FOR COMMUNICATION PANELS (LAN/WAN , SDH , DDF,DVM,MDF) 2.00 1.00 2.00 2.35 1 230 10.23 12.3 20 MCB SPN 2.00

QC.52 230VAC SUPPLY FOR COMMUNICATION PANELS (MCP , N01 ,N02,DC-DC CONVERTER -1&2) 2.00 1.00 2.00 2.35 1 230 10.23 12.3 20 MCB SPN 2.00

QC.53 230V AC SUPPLY FOR BATTERY ROOM EXHAUST FAN. 0.35 1.00 0.35 0.41 1 230 1.80 2.2 20 MCB SPN 0.35

QC.54 230V,1PH SUPPLY FM-200 RELEASING PANEL - CONTROL ROOM - FIRST FLOOR 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00

QC.55 230V,1PH SUPPLY FM-200 RELEASING PANEL - COMMUNICATION ROOM -FIRST FLOOR 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00

QC.56 230V,1PH SUPPLY FM-200 RELEASING PANEL - BATTERY ROOM -FIRST FLOOR 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00

QC.57 230V,1PH SUPPLY FM-200 RELEASING PANEL - MV SWITCHGEAR ROOM -GROUND FLOOR 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - GIS HALL-GROUND FLOOR-
QC.58 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
SYSTEM#1
230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - GIS HALL-GROUND FLOOR-
QC.59 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
SYSTEM#2
230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - GIS HALL-GROUND FLOOR-
QC.60 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
SYSTEM#3
230V,1PH SUPPLY FM-200 RELEASING PANEL - LCC CUBICLES - GIS HALL-GROUND FLOOR-
QC.61 0.39 0.00 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00
SYSTEM#4

QC.62 230V AC SUPPLY FOR GATE MOTOR-1 1.00 0.00 1.00 1.18 1 230 5.12 6.1 20 MCB SPN 0.00

QC.63 230V AC SUPPLY FOR BASEMENT SUMP PUMP-1 1.30 0.00 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00

QC.64 230V AC SUPPLY FOR BASEMENT SUMP PUMP-2 1.30 0.00 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00

QC.65 230V AC SUPPLY FOR BASEMENT SUMP PUMP-3 1.30 0.00 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00
UNIT TOTAL TOTAL Load details of

DIVERSITY
FACTOR
C.B DATA
*

PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP

QC.66 230V AC SUPPLY FOR BASEMENT SUMP PUMP-4 1.30 0.00 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00

QC.67 SPARE 1 230 20 MCB SPN -

QC.68 SPARE 1 230 20 MCB SPN -

QC.69 SPARE 1 230 20 MCB SPN

QC.70 SPARE 1 230 20 MCB SPN

QC.71 SPARE 1 230 20 MCB SPN

QC.72 SPARE 1 230 20 MCB SPN -

400/230V, 250A, 60Hz, 3PH 4 WIRE AC SDP-2 (CONTROL ROOM)

QD SUPPLY FOR AC SDP-2 62.76 1 62.76 73.83 3 400 106.57 127.9 160AT/250AF MCCB TPN 62.76

QD.1 SPARE 3 400 20 MCB TPN

QD.2 SPARE 3 400 20 MCB TPN

QD.3 SPARE 3 400 32 MCB TPN

QD.4 SPARE 3 400 20 MCB TPN

QD.5 SPARE 3 400 20 MCB TPN

QD.6 SPARE 3 400 63 MCCB TPN

QD.7 400V 3PH SUPPLY-2 FOR TR-1 LCP(FANS,MK) (STAND-BY). 26.74 0.5 26.74 31.46 3 400 45.41 54.5 63 MCCB TPN 13.37

QD.8 400V 3PH SUPPLY-2 FOR TR-2 LCP(FANS,MK) (STAND-BY). 26.74 0.5 26.74 31.46 3 400 45.41 54.5 63 MCCB TPN 13.37

QD.9 400V 3PH SUPPLY-2 FOR TR-3 LCP(FANS,MK) (MAIN). 26.74 0.5 26.74 31.46 3 400 45.41 54.5 63 MCCB TPN 13.37

QD.10 400V 3PH SUPPLY-2 FOR TR-1 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00

QD.11 400V 3PH SUPPLY-2 FOR TR-2 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00

QD.12 400V 3PH SUPPLY-2 FOR TR-3 OLTC MOTOR DRIVE UNIT. 0.75 0 0.75 0.88 3 400 1.27 1.5 20 MCB TPN 0.00

QD.13 400VAC SUPPLY FOR FAX/TELEPHONE EXCHANGE. 5.00 1 5.00 5.88 3 400 8.49 10.2 20 MCB TPN 5.00

QD.14 400V AC SUPPLY FOR MISCELLANEOUS PORTABLE SUPPLY-2 1.00 0.5 1.00 1.18 3 400 1.70 2.0 20 MCB TPN 0.50

QD.15 400V,AC SUPPLY 01 FOR SPLIT UNIT(WORKSHOP AND RECORD ROOM) 3.50 1 3.50 4.12 3 400 5.94 7.1 20 MCB TPN 3.50

QD.16 400 VAC SUPPLY FOR (DCDB-1 ) PANELS 0.42 0.5 0.42 0.49 3 400 0.71 0.9 20 MCB TPN 0.21

QD.17 400 VAC SUPPLY FOR (DCDB-2 ) PANELS 0.4 0.5 0.42 0.49 3 400 0.71 0.9 20 MCB TPN 0.21

QD.18 400 VAC SUPPLY FOR (DCDB ) PANEL 0.4 0.5 0.42 0.49 3 400 0.71 0.9 20 MCB TPN 0.21

QD.19 400V,AC SUPPLY FOR BASEMENT EXHAUST FAN 01 2.25 1 2.25 2.65 3 400 3.82 4.6 20 MCB TPN 2.25

QD.20 400V AC SUPPLY FOR SECURITY SYSTEM UPS IN CONTROL ROOM 0.3 1 0.32 0.38 3 400 0.54 0.7 32 MCB TPN 0.32

QD.21 400V,AC SUPPLY 02 FOR SPLIT UNIT(WORKSHOP AND RECORD ROOM) 3.50 1 3.50 4.12 3 400 5.94 7.1 20 MCB TPN 3.50

QD.22 400V AC SUPPLY FOR T01 TRANSFORMER PIT PUMP-1. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00

QD.23 400V AC SUPPLY FOR T02 TRANSFORMER PIT PUMP-2. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00

QD.24 400V AC SUPPLY FOR T03 TRANSFORMER PIT PUMP-3. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00

QD.25 400V AC SUPPLY FOR AUXILIARY TRANSFORMER-1 PIT PUMP. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00

QD.26 400V AC SUPPLY FOR AUXILIARY TRANSFORMER-2 PIT PUMP. 2.00 0.0 2.00 2.35 3 400 3.40 4.1 20 MCB TPN 0.00

QD.27 400V AC SUPPLY FOR WATER BOOSTER PUMP. 2.50 0 2.50 2.94 3 400 4.25 5.1 20 MCB TPN 0.00

230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(+RTM-1,+RTM-2,+RTM-3,+RTM-


QD.28 1.01 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27
4,+RTM-5,+RTM-6)

QD.29 230V,AC SUPPLY FOR KITCHEN EXHAUST FAN 0.02 0 0.02 0.03 1 230 0.11 0.1 20 MCB SPN 0.00

QD.30 230V AC SUPPLY FOR MFACP PANELS & PRINTERS 0.68 0.27 0.68 2.67 1 230 11.59 13.9 20 MCB SPN 0.18

QD.31 230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(RTCC-1,RTCC-2,RTCC-3) 0.81 0.27 0.81 2.74 1 230 11.90 14.3 20 MCB SPN 0.22

QD.32 230V AC SUPPLY FOR WATER HEATER FOR TOILET. 2.00 0 2.00 3.03 1 230 13.17 15.8 20 MCB SPN 0.00

QD.33 230V AC SUPPLY FOR TOILET EXHAUST FAN 0.13 0 0.13 0.16 1 230 0.68 0.8 20 MCB SPN 0.00

QD.34 230V AC SUPPLY FOR WATER TRANSFER PUMP 1.10 0 1.10 1.29 1 230 5.63 6.8 20 MCB SPN 0.00
UNIT TOTAL TOTAL Load details of

DIVERSITY
FACTOR
C.B DATA
*

PHASE
LOAD LOAD LOAD IFL IOLC panels
C.B NO. Equipment VOLT CB RATING AMP
AMP AMP RATING (loadxdiversity
TYPE factor)
KW KW KVA AMP

QD.35 230V AC SUPPLY FOR CONTROL ROOM WORKSTATION (PC'S, MONITORS, PRINTERS…..ETC). 2.00 1 2.00 2.35 1 230 10.23 12.3 20 MCB SPN 2.00

QD.36 230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(ILPB,ILP,ELP,DCU,RMR,DDR) 1.01 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27

230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(MAIN ACDB,PP-1,PP-


QD.37 1.01 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27
2,OLP,HVAC1,HVAC2)

QD.38 230VAC SUPPLY FOR CONTROL ROOM PANELS (HTR,LTNG,SCKT)(G12,G11,FUT,FUT,FUT,FUT) 1.01 0.27 1.01 1.19 1 230 5.17 6.2 20 MCB SPN 0.27

QD.39 230VAC SUPPLY FOR AMI (RMR PANEL) 0.42 0.27 0.42 0.49 1 230 2.15 2.6 20 MCB SPN 0.11

QD.40 230VAC SUPPLY FOR AMI (SWITCH PANEL) 0.42 0.27 0.42 0.49 1 230 2.15 2.6 20 MCB SPN 0.11

QD.41 230VAC SUPPLY-1 FOR SAS PANELS ROW (HTR,LTNG,SCKT) 0.98 0.27 0.98 1.15 1 230 5.01 6.0 20 MCB SPN 0.26

QD.42 230V,AC SUPPLY FOR FM-200-ROOM-02 EXHAUST FAN 2.25 0 2.25 2.65 1 230 11.51 13.8 20 MCB SPN 0.00

QD.43 230V,AC SUPPLY FOR FM-200-ROOM-03 EXHAUST FAN 2.25 0 2.25 2.65 1 230 11.51 13.8 20 MCB SPN 0.00

QD.44 230V,1PH SUPPLY FM-200 RELEASING PANEL - 13.8kV SWITCHGEAR BASEMENT 0.39 0 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00

QD.45 230V,1PH SUPPLY FM-200 RELEASING PANEL - HV GIS BASEMENT 0.39 0 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00

QD.46 230V,1PH SUPPLY FM-200 RELEASING PANEL - CABLE CORRIDOR-BASEMENT 0.39 0 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00

230V,1PH SUPPLY FM-200 RELEASING PANEL - COMMUNICATION ROOM - EXTERNAL TELECOM


QD.47 0.39 0 0.39 0.46 1 230 5.73 6.9 20 MCB SPN 0.00
SHELTER

QD.48 230V,1PH SUPPLY FM-200 RELEASING PANEL - BATTERY ROOM - EXTERNAL TELECOM SHELTER 0.39 0 0.39 0.46 1 230 2.00 2.4 20 MCB SPN 0.00

QD.49 230V AC SUPPLY FOR BASEMENT SUMP PUMP-5 1.30 0 1.30 1.53 1 230 6.65 8.0 20 MCB SPN 0.00

QD.50 230V AC SUPPLY FOR BASEMENT SUMP PUMP-6 1.30 0 1.300 1.53 1 230 6.65 8.0 20 MCB SPN 0.00

QD.51 230V AC SUPPLY FOR BASEMENT SUMP PUMP-7 1.30 0 1.300 1.53 1 230 6.65 8.0 20 MCB SPN 0.00

QD.52 230V AC SUPPLY FOR BASEMENT SUMP PUMP-8 1.30 0 1.300 1.53 1 230 6.65 8.0 20 MCB SPN 0.00

QD.53 230V AC SUPPLY FOR HAND DRYER 1.28 1 1.28 1.51 1 230 6.55 7.9 20 MCB SPN 1.28

QD.54 230V AC SUPPLY FOR GATE MOTOR-2 1.00 0 1.00 1.18 1 230 5.12 6.1 20 MCB SPN 0.00

QD.55 230V AC SUPPLY FOR LCC'S ANNUNCIATION SYSTEM 3.00 0.18 3.00 3.53 1 230 15.35 18.4 20 MCB SPN 0.54

QD.56 230V,1PH SUPPLY FOR PARTIAL DISCHARGE MONITORING SYSTEM(PDMS) 0.14 1.00 0.14 0.16 1 230 0.72 0.9 20 MCB SPN 0.14

QD.57 230V,1PH SUPPLY FOR ROLLING SHUTTER MOTOR DOOR 2.00 0.00 2.00 2.35 1 230 10.23 12.3 20 MCB SPN 0.00

QD.58 230V AC SUPPLY-2 FOR TR-1 OLTC LIGHTING & HEATER. 0.37 0.50 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19

QD.59 230V AC SUPPLY-2 FOR TR-2 OLTC LIGHTING & HEATER. 0.37 0.50 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19

QD.60 230V AC SUPPLY-2 FOR TR-3 OLTC LIGHTING & HEATER. 0.37 0.50 0.37 0.44 1 230 1.89 2.3 20 MCB SPN 0.19

QD.61 230V AC SUPPLY FOR TR-1 ONLINE GAS/MOISTURE ANALYSER 0.15 1.00 0.15 0.18 1 230 0.77 0.9 20 MCB SPN 0.15

QD.62 230V AC SUPPLY FOR TR-2 ONLINE GAS/MOISTURE ANALYSER 0.15 1.00 0.15 0.18 1 230 0.77 0.9 20 MCB SPN 0.15

QD.63 230V AC SUPPLY FOR TR-3 ONLINE GAS/MOISTURE ANALYSER 0.15 1.00 0.15 0.18 1 230 0.77 0.9 20 MCB SPN 0.15

QD.64 SPARE 1 230 20 MCB SPN

QD.65 SPARE 1 230 20 MCB SPN

QD.66 SPARE 1 230 20 MCB SPN

QD.67 SPARE 1 230 20 MCB SPN

QD.68 SPARE 1 230 20 MCB SPN

QD.69 SPARE 1 230 20 MCB SPN

QD.70 SPARE 1 230 20 MCB SPN

QD.71 SPARE 1 230 20 MCB SPN

QD.72 SPARE 1 230 20 MCB SPN -

*
* Diversity factor is used only to calculate main C.B rating of SDP-1 and SDP-
2
20A Circuit breakers rating shall be as per design requirements and subject
to SEC approval.
CERT'D
APPR'D
CHK'D

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION

UNIFIED LV DC CABLE SIZING CALCULATIONS


(COA & WOA)
BY
DATE
NO

REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT

UNIFIED LV DC CABLE SIZING CALCULATIONS


TO BE USED FOR
CONSTRUCTION OF
FOR ORDERING
MATERIALS UNTIL (COA & WOA)
CERTIFIED AND
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.

DMS EXCEL
LV DC Cable sizing :-
IFL = KW x 1000 / V %VD = (Voltage Drop / Supply Voltage) x 100

System Voltage = 125 VDC IOLC = 1.20 x IFL VOLTAGE DROP = 2 x I x L x R


V= End of discharge voltage=101.5

CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts 0 Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp40 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

Q.102 BATTERY CHARGER BREAKER FOR THE BATTERY- FROM CHARGER 40600 1 1 40600 101.5 400.000 480.0 500AT/ 630AF DP MCCB 1C 300 XLPE Duct 498 2 20 0.84 0.87 0.7308 727.88 0.0766 0.0007663 0.74 0.72 0.80

MAIN DCDB (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)

Q.103 BATTERY CHARGER-1 INCOMER-1 BREAKER FOR MAIN BUSBAR A 40600 1 1 40600 101.5 400.000 480.0 500AT/ 630AF DP MCCB 1C 240 XLPE Air 597 2 10 0.91 0.87 0.7917 945.29 0.0961 0.0004807 0.46 0.45 0.80

Q.104 BATTERY CHARGER-2 INCOMER-2 BREAKER FOR MAIN BUSBAR B 40600 1 1 40600 101.5 400.000 480.0 500AT/ 630AF DP MCCB 1C 240 XLPE Air 597 2 10 0.91 0.87 0.7917 945.29 0.0961 0.0004807 0.46 0.45 0.80

Q.105 SUPPLY FOR PORTABLE BATTERY CHARGER 10150 1 1 10150 101.5 100.0 120.0 125AT/ 160AF DP MCCB -

Q.106 SUPPLY FOR PORTABLE BATTERY CHARGER 10150 1 1 10150 101.5 100.0 120.0 125AT/ 160AF DP MCCB -

MAIN DCDB (BUS-A) (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)

225AT/ MCCB
Q.A1 MAIN DCDB SUPPLY-1 FOR SUB DCDB-1 (BUS-A) 18016.0 1 1 18016.0 101.5 177.50 213.0 DP 2C 35 XLPE Air 186 2 7 0.91 0.7 0.6 236.96 0.6682 0.0023385 1.00 0.98 4.20
250AF

225AT/ MCCB
Q.A2 MAIN DCDB SUPPLY-1 FOR SUB DCDB-2 (BUS-A) 18862.0 1 1 18862.0 101.5 185.83 223.0 DP 2C 35 XLPE Air 186 2 9 0.91 0.7 0.6 236.96 0.6682 0.0030067 1.34 1.32 4.20
250AF

Q.A3 MAIN DCDB SUPPLY-1 FOR TELECOM DCDB 4941.0 1 1 4941.0 101.5 48.68 58.4 60AT/ 63AF DP MCCB 2C 35 XLPE Air 186 1 14 0.91 0.7 0.6 118.48 0.6682 0.0093541 1.09 1.08 4.20

Q.A4 MAIN DCDB SUPPLY-1 FOR EMERGENCY LIGHTING PANEL 5800.0 1 1 5800.0 101.5 57.14 68.6 75AT/ 80AF DP MCCB 2C 35 XLPE Air 186 2 11 0.91 0.7 0.6 236.96 0.6682 0.0036748 0.50 0.50 4.20

Q.A5 MAIN DCDB SPARE 75AT/ 80AF DP MCCB SPARE

225AT/ MCCB
Q.A6 MAIN DCDB SPARE DP SPARE
250AF

MAIN DCDB (BUS-B) (125 VDC, 2WIRES SYSTEM, 630A @40°C, 25KA/1 SEC.)

225AT/
Q.B1 MAIN DCDB SUPPLY-2 FOR SUB DCDB-1 (BUS-B) 18016 1 1 18016.0 101.5 177.50 213.00 DP MCCB 2C 35 XLPE Air 186 2 7 0.91 0.7 0.6 236.96 0.6682 0.0023385 1.00 0.98 4.20
250AF

225AT/ MCCB
Q.B2 MAIN DCDB SUPPLY-2 FOR SUB DCDB-2 (BUS-B) 18862 1 1 18862.0 101.5 185.83 223.00 DP 2C 35 XLPE Air 186 2 9 0.91 0.7 0.6 236.96 0.6682 0.0030067 1.34 1.32 4.20
250AF

Q.B3 MAIN DCDB SUPPLY-2 FOR TELECOM DCDB 4941 1 1 4941.0 101.5 48.68 58.42 60AT/ 63AF DP MCCB 2C 35 XLPE Air 186 1 14 0.91 0.7 0.6 118.48 0.6682 0.0093541 1.09 1.08 4.20

Q.B4 MAIN DCDB SUPPLY-2 FOR EMERGENCY LIGHTING PANEL 5800 1 1 5800.0 101.5 57.14 68.57 75AT/ 80AF DP MCCB 2C 35 XLPE Air 186 2 11 0.91 0.7 0.6 236.96 0.6682 0.0036748 0.50 0.50 4.20

Q.B5 MAIN DCDB SPARE 75AT/ 80AF DP MCCB SPARE

225AT/
Q.B6 MAIN DCDB SPARE DP MCCB SPARE
250AF

SUB-DCDB-1 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

SUPPLY FOR LINE FEEDER (FUTURE)-E07 PROTECTION PANEL SET-1 (MAIN-1


QA1.1 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP MCB FUTURE
PROTN CKT, IN/OUT RELAY CKT)

SUPPLY FOR LINE FEEDER-E05 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, MCB
QA1.2 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP 2C 4 XLPE Air 51 1 11 0.91 0.45 0.41 20.88 5.8782 0.0646603 0.02 0.02 4.20
IN/OUT RELAY CKT)

SUPPLY FOR TRANSFROMER T01-E03 PROTECTION PANEL SET-1 (MAIN-1 87 T-1 MCB
QA1.3 SUB DCDB-2 75.2 1 1 75.2 101.5 0.74 0.89 20 DP 2C 4 XLPE Air 51 1 11 0.91 0.45 0.41 20.88 5.8782 0.0646603 0.11 0.11 4.20
PROTN, IN/OUT RELAY )

SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, MCB
QA1.4 SUB DCDB-3 13.8 1 1 13.8 101.5 0.14 0.16 20 DP 2C 4 XLPE Air 51 1 11 0.91 0.45 0.41 20.88 5.8782 0.0646603 0.02 0.02 4.20
IN/OUT RELAY CKT)

QA1.5 SUB DCDB-4 SUPPLY FOR BUS COUPLER-A -E130 PROTECTION PANEL (O/C & E/F RELAY CKT) 36.3 1 1 36.3 101.5 0.36 0.43 20 DP MCB 2C 4 XLPE Air 51 1 12 0.91 0.45 0.41 20.88 5.8782 0.0705385 0.06 0.06 4.20

QA1.6 SUB DCDB-1 SUPPLY FOR BUS SECTION-E220 PROTECTION PANEL (O/C & E/F RELAY CKT) 36.3 1 1 36.3 101.5 0.36 0.43 20 DP MCB 2C 4 XLPE Air 51 1 12 0.91 0.45 0.41 20.88 5.8782 0.0705385 0.06 0.06 4.20

QA1.7 SUB DCDB-1 SUPPLY FOR BUS COUPLER-B -E230 PROTECTION PANEL (O/C & E/F RELAY CKT) 36.3 1 1 36.3 101.5 0.36 0.43 20 DP MCB 2C 4 XLPE Air 51 1 13 0.91 0.45 0.41 20.88 5.8782 0.0764167 0.07 0.06 4.20

2 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

SUPPLY FOR TRANSFORMER T02-E02 PROTECTION PANEL SET-1 (MAIN-1 87T-1 MCB
QA1.8 SUB DCDB-1 75.2 1 1 75.2 101.5 0.74 0.89 20 DP 2C 4 XLPE Air 51 1 13 0.91 0.45 0.41 20.88 5.8782 0.0764167 0.14 0.13 4.20
PROTN, IN/OUT RELAY )

SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, MCB
QA1.9 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP 2C 4 XLPE Air 51 1 14 0.91 0.45 0.41 20.88 5.8782 0.0822950 0.03 0.03 4.20
IN/OUT RELAY CKT)

SUPPLY FOR TRANSFORMER T03-E06 PROTECTION PANEL SET-1 (MAIN-1 87 T-1 MCB
QA1.10 SUB DCDB-1 75.2 1 1 75.2 101.5 0.74 0.89 20 DP 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.8782 0.0881732 0.16 0.15 4.20
PROTN, IN/OUT RELAY )

SUPPLY FOR LINE FEEDER-E08 PROTECTION PANEL SET-1 (MAIN-1 PROTN CKT, MCB
QA1.11 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.8782 0.0940514 0.03 0.03 4.20
IN/OUT RELAY CKT)

SUPPLY FOR LINE FEEDER (FUTURE)-E10 PROTECTION PANEL SET-1 (MAIN-1 MCB FUTURE
QA1.12 SUB DCDB-1 13.8 1 1 13.8 101.5 0.14 0.16 20 DP
PROTN CKT, IN/OUT RELAY CKT)

QA1.13 SUB DCDB-1 SUPPLY-1 FOR HV LINE FEEDER (FUTURE)-E07 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB FUTURE

SUPPLY-1 FOR HV LINE FEEDER-E05


QA1.14 SUB DCDB-1 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20
(CB MOTOR CKT)

QA1.15 SUB DCDB-1 SUPPLY-1 FOR HV TRANSFORMER T01-E03 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20

SUPPLY-1 FOR HV LINE FEEDER-E01


QA1.16 SUB DCDB-1 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20
(CB MOTOR CKT)

QA1.17 SUB DCDB-1 SUPPLY-1 FOR HV BUS COUPLER-A -E130 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20

SUPPLY-1 FOR HV BUS SECTION 220 MCB


QA1.18 SUB DCDB-1 875.0 1 1 875.0 101.5 8.62 10.34 20 DP 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20
(CB MOTOR CKT)

QA1.19 SUB DCDB-1 SUPPLY-1 FOR HV BUS COUPLER-B -E230 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20

QA1.20 SUB DCDB-1 SUPPLY-1 FOR HV TRANSFORMER T02-E02 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20

QA1.21 SUB DCDB-1 SUPPLY-1 FOR HV LINE FEEDER-E04 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.189 2.16 4.20

QA1.22 SUB DCDB-1 SUPPLY-1 FOR HV TRANSFORMER T03-E06 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.19 2.16 4.20

QA1.23 SUB DCDB-1 SUPPLY-1 FOR HV LINE FEEDER S/S-E08 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 2.189 2.16 4.20

QA1.24 SUB DCDB-1 SUPPLY-1 FOR HV LINE FEEDER (FUTURE)-E10 (CB MOTOR CKT) 875.0 1 1 875.0 101.5 8.62 10.34 20 DP MCB FUTURE

QA1.25 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER (FUTURE)-E07 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB FUTURE

QA1.26 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER-E05 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 1.25 1.23 10.00

QA1.27 SUB DCDB-1 SUPPLY-2 FOR HV TRANSFORMER T01-E03 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.8782 0.1058078 1.25 1.23 10.00

QA1.28 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER-E01 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 45 0.91 0.45 0.41 36.04 2.333433 0.1050045 1.24 1.22 10.00

QA1.29 SUB DCDB-1 SUPPLY-2 FOR HV BUS COUPLER-A -E130 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 44 0.91 0.45 0.41 36.04 2.333433 0.1026711 1.21 1.20 10.00

QA1.30 SUB DCDB-1 SUPPLY-2 FOR HV BUS SECTION-E220 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 43 0.91 0.45 0.41 36.04 2.333433 0.1003376 1.19 1.17 10.00

QA1.31 SUB DCDB-1 SUPPLY-2 FOR HV BUS COUPLER-B -E230 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 42 0.91 0.45 0.41 36.04 2.333433 0.0980042 1.16 1.14 10.00

QA1.32 SUB DCDB-1 SUPPLY-2 FOR HV TRANSFORMER T02-E02 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 41 0.91 0.45 0.41 36.04 2.333433 0.0956708 1.13 1.11 10.00

QA1.33 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER-E04 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 40 0.91 0.45 0.41 36.04 2.333433 0.0933373 1.10 1.09 10.00

QA1.34 SUB DCDB-1 SUPPLY-2 FOR HV TRANSFORMER T03-E06 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 39 0.91 0.45 0.41 36.04 2.333433 0.0910039 1.08 1.06 10.00

QA1.35 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER S/S-E08 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 10 XLPE Air 88 1 38 0.91 0.45 0.41 36.04 2.333433 0.0886705 1.05 1.03 10.00

QA1.36 SUB DCDB-1 SUPPLY-2 FOR HV LINE FEEDER (FUTURE)-E10 (CB TRIP CKT-2) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB FUTURE

QA1.37 SUB DCDB-1 SUPPLY-3 FOR HV LINE FEEDER (FUTURE)-E07 (DS/ES INTERLOCK CKT SUPPLY) 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB FUTURE

QA1.38 SUB DCDB-1 SUPPLY-3 FOR HV LINE FEEDER-E05 (DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 10 XLPE Air 88 1 40 0.91 0.45 0.41 36.04 2.333433 0.0933373 0.15 0.15 4.20

3 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QA1.39 SUB DCDB-1 SUPPLY-3 FOR HV TRANSFORMER T01-E03 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 10 XLPE Air 88 1 42 0.91 0.45 0.41 36.04 2.333433 0.0980042 0.16 0.16 4.20

QA1.40 SUB DCDB-1 SUPPLY-3 FOR HV LINE FEEDER -E01 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 0.44 0.43 4.20

QA1.41 SUB DCDB-1 SUPPLY-3 FOR HV BUS COUPLER-A -E130 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 0.43 0.42 4.20

QA1.42 SUB DCDB-1 SUPPLY-3 FOR HV BUS SECTION-E220 (DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 0.42 0.41 4.20

QA1.43 SUB DCDB-1 SUPPLY-3 FOR HV BUS COUPLER-B -E230 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.41 0.40 4.20

QA1.44 SUB DCDB-1 SUPPLY-3 FOR HV TRANSFORMER T02-E02 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 0.40 0.39 4.20

QA1.45 SUB DCDB-1 SUPPLY-3 FOR HV LINE FEEDER-E04 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 0.39 0.38 4.20

QA1.46 SUB DCDB-1 SUPPLY-3 FOR HV TRANSFORMER T03-E06 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 0.38 0.37 4.20

QA1.47 SUB DCDB-1 SUPPLY-3 FOR HV SPARE FEEDER S/S-E08 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 0.37 0.36 4.20

QA1.48 SUB DCDB-1 SUPPLY-3 FOR HV FUTURE FEEDER- E10 DS/ES INTERLOCK CKT SUPPLY 70.0 1 1 70.0 101.5 0.69 0.83 20 DP MCB FUTURE

QA1.49 SUB DCDB-1 SUPPLY-1 FOR HV BUSBAR-A PROTECTION PANEL (ZONE 1A PROTN CKT) 13.0 1 1 13.0 101.5 0.13 0.15 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.04 0.04 4.20

SUPPLY-1 FOR HV BUSBAR-CH ZONE PROTECTION PANEL (BB-CHECK ZONE & MCB
QA1.50 SUB DCDB-1 13.0 1 1 13.0 101.5 0.13 0.15 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.08 0.07 4.20
IN/OUT RELAY CKT)

QA1.51 SUB DCDB-1 SUPPLY-1 FOR HV BUSBAR-B PROTECTION PANEL (ZONE-1B PROTN CKT) 13.0 1 1 13.0 101.5 0.13 0.15 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.08 0.07 4.20

SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE FEEDER BUS-1 (AH01) (TRIP CKT-1, MCB
QA1.52 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP FUTURE
CLOSE CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE FEEDER BUS-1 (AH02) (TRIP CKT-1, MCB
QA1.53 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP FUTURE
CLOSE CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR CAP. BANK-1 FEEDER (AH03) (TRIP CKT-1, CLOSE MCB
QA1.54 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH04) (TRIP CKT-1, CLOSE MCB
QA1.55 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH05) (TRIP CKT-1, CLOSE MCB
QA1.56 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH06) (TRIP CKT-1, CLOSE MCB
QA1.57 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH07) (TRIP CKT-1, CLOSE MCB
QA1.58 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH08) (TRIP CKT-1, CLOSE MCB
QA1.59 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV INCOMER T01 (AH09) (TRIP CKT-1, CLOSE CKT/CONTROL MCB
QA1.60 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.47 1.45 4.20
CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH10) (TRIP CKT-1, CLOSE MCB
QA1.61 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH11) (TRIP CKT-1, CLOSE MCB
QA1.62 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH12) (TRIP CKT-1, CLOSE MCB
QA1.63 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH13) (TRIP CKT-1, CLOSE
QA1.64 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.878211 0.0881732 0.49 0.48 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH14) (TRIP CKT-1, CLOSE
QA1.65 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP MCB 2C 4 XLPE Air 51 1 14 0.91 0.45 0.41 20.88 5.878211 0.0822950 0.46 0.45 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-1 (AH15) (TRIP CKT-1, CLOSE MCB
QA1.66 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.52 0.51 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR AUX-01 FEEDER (AH16) (TRIP CKT-1, CLOSE MCB
QA1.67 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 17 0.91 0.45 0.41 20.88 5.878211 0.0999296 0.55 0.55 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8KV BUS METERING-01 (AH17) (EARTH SWITCH INTERLOCK, MCB
QA1.68 SUB DCDB-1 133.3 1 1 133.3 101.5 1.31 1.58 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.78 0.77 4.20
I/O BOX-1)

SUPPLY-1 FOR 13.8kV BUS SECTION-01 (AH18) (TRIP CKT-1, CLOSE MCB
QA1.69 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.47 1.45 4.20
CKT/CONTROL CKT, BCU)

4 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

SUPPLY-1 FOR 13.8KV BUS RISER-01 (AH19) (EARTH SWITCH INTERLOCK, I/O MCB
QA1.70 SUB DCDB-1 123.3 1 1 123.3 101.5 1.21 1.46 20 DP 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 0.77 0.76 4.20
BOX-1)

SUPPLY-1 FOR 13.8kV SWGR CAP. BANK-02 FEEDER (AH20) (TRIP CKT-1, CLOSE MCB
QA1.71 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 1.43 1.41 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH21) (TRIP CKT-1, CLOSE MCB
QA1.72 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 1.40 1.38 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH22) (TRIP CKT-1, CLOSE MCB
QA1.73 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH23) (TRIP CKT-1, CLOSE MCB
QA1.74 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 1.34 1.32 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH24) (TRIP CKT-1, CLOSE MCB
QA1.75 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.30 1.29 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH25) (TRIP CKT-1, CLOSE MCB
QA1.76 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 1.27 1.25 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH26) (TRIP CKT-1, CLOSE MCB
QA1.77 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 1.24 1.22 4.20
CKT/CONTROL CKT, BCU)

QA1.78 SUB DCDB-1 SUPPLY FOR 13.8 KV BUSBAR-1A PROTECTION PANEL(MAIN PROTN) 15.3 1 1 15.3 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 0.08 0.08 4.20

QA1.79 SUB DCDB-1 SUPPLY FOR 13.8 KV BUSBAR-1B PROTECTION PANEL(MAIN PROTN) 15.3 1 1 15.3 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.09 0.09 4.20

QA1.80 SUB DCDB-1 SUPPLY FOR 13.8 KV BUSBAR-1C PROTECTION PANEL(MAIN PROTN) 15.3 1 1 15.3 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.06 0.06 4.20

SUPPLY FOR 13.8KV AUTOMATIC BUS TRANSFER SCHEME (+ABTS) (IN/OUT MCB
QA1.81 SUB DCDB-1 80.0 1 1 80.0 101.5 0.79 0.95 20 DP 2C 4 XLPE Air 51 1 13 0.91 0.45 0.41 20.88 5.8782 0.0764167 0.14 0.14 4.20
MODULE & ALARM/ INDICATION CKT)

QA1.82 SUB DCDB-1 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-1 (SET-1) 61.3 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.8782 0.0881732 0.13 0.13 4.20

QA1.83 SUB DCDB-1 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-2 (SET-1) 61.3 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.14 0.13 4.20

QA1.84 SUB DCDB-1 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-3 (SET-1) 61.3 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.24 0.23 4.20

QA1.85 SUB DCDB-1 SUPPLY-1 FOR DC EMERGENCY LIGHTING FOR CONTROL PANELS 40.0 1 1 40.0 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QA1.86 SUB DCDB-1 SUPPLY FOR CHANGE OVER SCHEME-1 (ATS FOR DCDB-1) 50.0 1 1 50.0 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.19 0.19 4.20

SUPPLY FOR 13.8kV UNDER VOLTAGE LOAD SHEDDING PROTECTION MCB


QA1.87 SUB DCDB-1 72.5 1 1 72.5 101.5 0.71 0.86 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.28 0.28 4.20
PANEL(SET-1)

QA1.88 SUB DCDB-1 SUPPLY FOR 13.8KV SWGR INCOMER T03 (AH45)(SYNCH TROLLEY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.31 0.31 4.20

QA1.89 SUB DCDB-1 SUPPLY FOR 13.8KV SWGR INCOMER T02 (AH29) (SYNCH TROLLEY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.31 0.31 4.20

QA1.90 SUB DCDB-1 SUPPLY FOR 13.8KV SWGR INCOMER T01 (AH09) (SYNCH TROLLEY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.31 0.31 4.20

QA1.91 SUB DCDB-1 SUPPLY FOR 13.8KV SWGR INCOMER T03 (AH45) (OPERATING MECHANISM) 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 4.20

SUPPLY FOR 13.8KV SWGR INCOMER T02 (AH29) AND BUS SECTION-02
QA1.92 SUB DCDB-1 500.0 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 4.20
(AH36)(OPERATING MECHANISM)

SUPPLY FOR 13.8KV SWGR INCOMER T01 (AH09) AND BUS SECTION-01 (AH18) MCB
QA1.93 SUB DCDB-1 500.0 1 1 500.0 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 4.20
(OPERATING MECHANISM)

QA1.94 SUB DCDB-1 SUPPLY-1 FOR AMI PANEL-1 118.0 1 1 118.0 101.5 1.16 1.40 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.46 0.45 4.20

QA1.95 SUB DCDB-1 SUPPLY-1 FOR AMI PANEL-2 118.0 1 1 118.0 101.5 1.16 1.40 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.46 0.45 4.20

QA1.96 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-1 30.0 1 1 30.0 101.5 0.30 0.35 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.12 0.12 4.20

QA1.97 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-2 30.0 1 1 30.0 101.5 0.30 0.35 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.12 0.12 4.20

QA1.98 SUB DCDB-1 SUPPLY FOR SECURITY SYSTEM AND CAMERAS 300.0 1 1 300.0 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.17 1.15 4.20

QA1.99 SUB DCDB-1 SPARE 20 DP MCB SPARE

5 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QA1.100 SUB DCDB-1 SPARE 20 DP MCB SPARE

LOAD SHEDDING PROTECTION PANEL(BUS-B)SUPPLY FOR 13.8KV UNDER MCB


QA1.101 SUB DCDB-1 18.8 1 1 18.8 101.5 0.18 0.22 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.07 0.07 4.20
FREQUENCY

QA1.102 SUB DCDB-1 SUPPLY FOR LINE FEEDER(FUTURE)-E07 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB FUTURE

QA1.103 SUB DCDB-1 SUPPLY FOR LINE FEEDER-E05 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20

QA1.104 SUB DCDB-1 SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20

QA1.105 SUB DCDB-1 SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20

QA1.106 SUB DCDB-1 SUPPLY FOR LINE FEEDER-E08 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20

QA1.107 SUB DCDB-1 SUPPLY FOR LINE FEEDER(FUTURE)-E10 PROTECTION PANEL(INTERTRIP-1) 127.0 1 1 127.0 101.5 1.25 1.50 20 DP MCB FUTURE

QA1.108 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.109 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.110 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.111 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.112 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.113 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.114 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.115 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.116 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.117 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.118 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.119 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.120 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.121 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.122 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.123 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.124 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.125 SUB DCDB-1 SPARE 20 DP MCB SPARE

QA1.126 SUB DCDB-1 SPARE 20 DP MCB SPARE

SEC-B (125 VDC, 2WIRES SYSTEM, 250A @40°C)

QB1.1 SUB DCDB-1 SUPPLY-4 FOR LINE FEEDER (FUTURE)-E07 (CB CLOSING CKT) 500 1 1 500 101.5 4.93 5.91 20 DP MCB FUTURE

SUPPLY-4 FOR LINE FEEDER-E05


QB1.2 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 3.13 3.08 4.20
(CB CLOSING CKT)

SUPPLY-4 FOR TRANSFORMER T01-E03 MCB


QB1.3 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 3.06 3.01 4.20
(CB CLOSING CKT)

6 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

SUPPLY-4 FOR LINE FEEDER-E01 MCB


QB1.4 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 2.99 2.94 4.20
(CB CLOSING CKT)

SUPPLY-4 FOR BUS COUPLER-A-E130 MCB


QB1.5 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 2.92 2.88 4.20
(CB CLOSING CKT)

SUPPLY-4 FOR BUS SECTION 220 MCB


QB1.6 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 2.85 2.81 4.20
(CB CLOSING CKT)

SUPPLY-4 FOR BUS COUPLER-B -E230 MCB


QB1.7 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 2.78 2.74 4.20
(CB CLOSING CKT)

SUPPLY-4 FOR TRANSFORMER T02-E02 MCB


QB1.8 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 2.71 2.67 4.20
(CB CLOSING CKT)

SUPPLY-4 FOR LINE FEEDER-E04 MCB


QB1.9 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 2.64 2.60 4.20
(CB CLOSING CKT)

SUPPLY-4 FOR TRANSFORMER T03-E06 MCB


QB1.10 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 2.78 2.74 4.20
(CB CLOSING CKT)

SUPPLY-4 FOR LINE FEEDER S/S-E08 MCB


QB1.11 SUB DCDB-1 500 1 1 500 101.5 4.93 5.91 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 2.92 2.88 4.20
(CB CLOSING CKT)

QB1.12 SUB DCDB-1 SUPPLY-4 FOR LINE FEEDER (FUTURE)-E10 (CB CLOSING CKT) 500 1 1 500 101.5 4.93 5.91 20 DP MCB FUTURE

QB1.13 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER (FUTURE)-E07 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB FUTURE

QB1.14 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER-E05 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 45 0.91 0.45 0.41 36.04 2.333433 0.1050045 0.09 0.09 4.20

QB1.15 SUB DCDB-1 SUPPLY-5 FOR TRANSFORMER T01-E03 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 44 0.91 0.45 0.41 36.04 2.333433 0.1026711 0.08 0.08 4.20

QB1.16 SUB DCDB-1 SUPPLY-4 FOR LINE FEEDER-E01 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 43 0.91 0.45 0.41 36.04 2.333433 0.1003376 0.08 0.08 4.20

QB1.17 SUB DCDB-1 SUPPLY-4 FOR BUS COUPLER-A-E130 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 42 0.91 0.45 0.41 36.04 2.333433 0.0980042 0.08 0.08 4.20

QB1.18 SUB DCDB-1 SUPPLY-5 FOR BUS SECTION-E220 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 41 0.91 0.45 0.41 36.04 2.333433 0.0956708 0.08 0.08 4.20

QB1.19 SUB DCDB-1 SUPPLY-5 FOR BUS COUPLER-B -E230 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 40 0.91 0.45 0.41 36.04 2.333433 0.0933373 0.08 0.08 4.20

QB1.20 SUB DCDB-1 SUPPLY-5 FOR TRANSFORMER T02-E02 (BCU POWER SUPPLY)) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 39 0.91 0.45 0.41 36.04 2.333433 0.0910039 0.08 0.07 4.20

QB1.21 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER-E04 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 38 0.91 0.45 0.41 36.04 2.333433 0.0886705 0.07 0.07 4.20

QB1.22 SUB DCDB-1 SUPPLY-5 FOR TRANSFORMER T03-E06 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 40 0.91 0.45 0.41 36.04 2.333433 0.0933373 0.08 0.08 4.20

QB1.23 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER S/S-E08 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB 2C 10 XLPE Air 88 1 42 0.91 0.45 0.41 36.04 2.333433 0.0980042 0.08 0.08 4.20

QB1.24 SUB DCDB-1 SUPPLY-5 FOR LINE FEEDER (FUTURE)-E10 (BCU POWER SUPPLY) 35 1 1 35 101.5 0.34 0.41 20 DP MCB FUTURE

SUPPLY-6 FOR HV LINE FEEDER (FUTURE)-E07 (SF6 GAS COMPARTMENT& I/O MCB FUTURE
QB1.25 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP
MODULE , BCU AUXILIARY

SUPPLY-6 FOR HV LINE FEEDER-E05 (SF6 GAS COMPARTMENT& I/O MODULE , MCB
QB1.26 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 0.59 0.58 4.20
BCU AUXILIARY

SUPPLY-6 FOR HV TRANSFORMER T01-E03 (SF6 GAS COMPARTMENT& I/O MCB


QB1.27 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 0.58 0.57 4.20
MODULE , BCU AUXILIARY)

SUPPLY-6 FOR HV LINE FEEDER-E01 (SF6 GAS COMPARTMENT& I/O MODULE , MCB
QB1.28 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 0.56 0.56 4.20
BCU AUXILIARY

SUPPLY-6 FOR HV BUS COUPLER-A -E130 (SF6 GAS COMPARTMENT& I/O MCB
QB1.29 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.55 0.54 4.20
MODULE , BCU AUXILIARY)

SUPPLY-6 FOR HV BUS SECTION-E220 (SF6 GAS COMPARTMENT& I/O MODULE MCB
QB1.30 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 0.54 0.53 4.20
AUXILIARY POWER SUPPLY)

SUPPLY-6 FOR HV BUS COUPLER-B -E230 (SF6 GAS COMPARTMENT& I/O MCB
QB1.31 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 0.53 0.52 4.20
MODULE , BCU AUXILIARY)

SUPPLY-6 FOR HV TRANSFORMER T02-E02 (SF6 GAS COMPARTMENT& I/O MCB


QB1.32 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 0.51 0.50 4.20
MODULE , BCU AUXILIARY)

SUPPLY-6 FOR HV LINE FEEDER-E04 (SF6 GAS COMPARTMENT& I/O MODULE , MCB
QB1.33 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 0.50 0.49 4.20
BCU AUXILIARY

SUPPLY-6 FOR HV TRANSFORMER T03-E06 (SF6 GAS COMPARTMENT& I/O MCB


QB1.34 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 0.53 0.52 4.20
MODULE , BCU AUXILIARY)

7 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

SUPPLY-6 FOR HV LINE FEEDER -E08 (SF6 GAS COMPARTMENT& I/O MODULE , MCB
QB1.35 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.55 0.54 4.20
BCU AUXILIARY

SUPPLY-6 FOR HV LINE FEEDER (FUTURE)-E10 (SF6 GAS COMPARTMENT& I/O MCB FUTURE
QB1.36 SUB DCDB-1 94.5 1 1 94.5 101.5 0.93 1.12 20 DP
MODULE , BCU AUXILIARY

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH27) (TRIP CKT-1, CLOSE MCB
QB1.37 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH28) (TRIP CKT-1, CLOSE MCB
QB1.38 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 1.47 1.45 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR INCOMER T02 (AH29) (TRIP CKT-1, CLOSE MCB
QB1.39 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 1.54 1.52 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH30) (TRIP CKT-1, CLOSE MCB
QB1.40 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 1.40 1.38 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH31) (TRIP CKT-1, CLOSE MCB
QB1.41 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH32) (TRIP CKT-1, CLOSE MCB
QB1.42 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 1.34 1.32 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH33) (TRIP CKT-1, CLOSE MCB
QB1.43 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.30 1.29 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH34) (TRIP CKT-1, CLOSE MCB
QB1.44 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 1.27 1.25 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH35) (TRIP CKT-1, CLOSE MCB
QB1.45 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 1.24 1.22 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV BUS SECTION-02 (AH36) (TRIP CKT-1, CLOSE MCB
QB1.46 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.40 1.38 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8KV BUS RISER-02 (AH37) (EARTH SWITCH INTERLOCK, I/O MCB
QB1.47 SUB DCDB-1 123.3 1 1 123.3 101.5 1.21 1.46 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 0.72 0.71 4.20
BOX-1)

SUPPLY-1 FOR 13.8kV SWGR AUX-02 FEEDER (AH38) (TRIP CKT-1, CLOSE MCB
QB1.48 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.30 1.29 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH39) (TRIP CKT-1, CLOSE MCB
QB1.49 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH40) (TRIP CKT-1, CLOSE MCB
QB1.50 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 1.47 1.45 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH41) (TRIP CKT-1, CLOSE MCB
QB1.51 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 1.43 1.41 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH42) (TRIP CKT-1, CLOSE MCB
QB1.52 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 1.40 1.38 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH43) (TRIP CKT-1, CLOSE MCB
QB1.53 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH44) (TRIP CKT-1, CLOSE MCB
QB1.54 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 1.34 1.32 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV INCOMER T03 (AH45) (TRIP CKT-1, CLOSE CKT/CONTROL MCB
QB1.55 SUB DCDB-1 252.6 1 1 252.6 101.5 2.49 2.99 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.40 1.38 4.20
CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH46) (TRIP CKT-1, CLOSE MCB
QB1.56 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 1.27 1.25 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH47) (TRIP CKT-1, CLOSE MCB
QB1.57 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 1.24 1.22 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH48) (TRIP CKT-1, CLOSE MCB
QB1.58 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 1.30 1.29 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH49) (TRIP CKT-1, CLOSE MCB
QB1.59 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FEEDER BUS-3 (AH50) (TRIP CKT-1, CLOSE MCB
QB1.60 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY FOR 13.8kV SWGR CAP. BANK-03 FEEDER (AH51) (TRIP CKT-1, CLOSE MCB
QB1.61 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 1.37 1.35 4.20
CKT/CONTROL CKT, BCU)

SUPPLY-1 FOR 13.8kV SWGR O/G FUTURE FEEDER BUS-3 (AH52) (TRIP CKT-1, MCB FUTURE
QB1.62 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP
CLOSE CKT/CONTROL CKT, BCU)

QB1.63 SUB DCDB-1 SUPPLY-1 TO ACDB 700 1 1 700 101.5 6.90 8.28 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 1.56 1.53 4.20

SUPPLY FOR 13.8KV AUTOMATIC CAPACITOR CONTROL SYSTEM PANEL (+ACCS) MCB
QB1.64 SUB DCDB-1 96.4 1 1 96.4 101.5 0.95 1.14 20 DP 2C 4 XLPE Air 51 1 17 0.91 0.45 0.41 20.88 5.878211 0.0999296 0.23 0.22 4.20
(HMI & PLC MODULE)

QB1.65 SUB DCDB-1 SUPPLY FOR HV BUSBAR PROTECTION PANEL (INDICATION CKT) 12.5 1 1 12.5 101.5 0.12 0.15 20 DP MCB 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.878211 0.1058078 0.03 0.03 4.20

8 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QB1.66 SUB DCDB-1 SPARE 20 DP MCB SPARE

SPARE MCB
QB1.67 SUB DCDB-1 20 DP SPARE

SUPPLY FOR TRANSFORMER-1 +RTCC/AVC PANEL (RELAY CKT & AUX CONTROL MCB
QB1.68 SUB DCDB-1 83.5 1 1 83.5 101.5 0.82 0.99 20 DP 2C 4 XLPE Air 51 1 18 0.91 0.45 0.41 20.88 5.878211 0.1058078 0.21 0.21 4.20
CKT)

SUPPLY FOR TRANSFORMER-2 +RTCC/AVC PANEL (RELAY CKT & AUX CONTROL MCB
QB1.69 SUB DCDB-1 83.5 1 1 83.5 101.5 0.82 0.99 20 DP 2C 4 XLPE Air 51 1 17 0.91 0.45 0.41 20.88 5.878211 0.0999296 0.20 0.19 4.20
CKT)

SUPPLY FOR TRANSFORMER-3 +RTCC/AVC PANEL (RELAY CKT & AUX CONTROL MCB
QB1.70 SUB DCDB-1 83.5 1 1 83.5 101.5 0.82 0.99 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.32 0.32 4.20
CKT)

QB1.71 SUB DCDB-1 SUPPLY-2 FOR HV BUSBAR-A PROTECTION PANEL (ZONE-2A PROTN CKT) 13 1 1 13 101.5 0.13 0.15 20 DP MCB 2C 4 XLPE Air 51 1 12 0.91 0.45 0.41 20.88 5.878211 0.0705385 0.02 0.02 4.20

QB1.72 SUB DCDB-1 SUPPLY-2 FOR HV BUSBAR-B PROTECTION PANEL (ZONE-2B PROTN CKT) 13 1 1 13 101.5 0.13 0.15 20 DP MCB 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.878211 0.0881732 0.03 0.03 4.20

QB1.73 SUB DCDB-1 SUPPLY-1 FOR SAS COMPUTER PANEL-1 1200 1 1 1200 101.5 11.82 14.19 20 DP MCB 2C 4 XLPE Air 51 1 17 0.91 0.45 0.41 20.88 5.878211 0.0999296 2.84 2.79 4.20

QB1.74 SUB DCDB-1 SUPPLY-1 FOR SAS COMPUTER PANEL-2 1200 1 1 1200 101.5 11.82 14.19 20 DP MCB 2C 4 XLPE Air 51 1 13 0.91 0.45 0.41 20.88 5.878211 0.0764167 2.17 2.14 4.20

QB1.75 SUB DCDB-1 SUPPLY-1 FOR SAS COMPUTER PANEL-3 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 15 0.91 0.45 0.41 20.88 5.878211 0.0881732 1.04 1.03 4.20

QB1.76 SUB DCDB-1 SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-A PANEL-1 200 1 1 200 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.44 0.44 4.20

QB1.77 SUB DCDB-1 SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-B PANEL-1 200 1 1 200 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.44 0.44 4.20

QB1.78 SUB DCDB-1 SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-A PANEL-2 150 1 1 150 101.5 1.48 1.77 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.33 0.33 4.20

QB1.79 SUB DCDB-1 SUPPLY-1 FOR SAS ETHERNET SWITCH LAN-B PANEL-2 150 1 1 150 101.5 1.48 1.77 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.33 0.33 4.20

QB1.80 SUB DCDB-1 SUPPLY-1 FOR COMMON ALARM PANEL-1 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.22 0.22 4.20

QB1.81 SUB DCDB-1 SUPPLY-1 FOR COMMON ALARM PANEL-2 50 1 1 50 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.11 0.11 4.20

QB1.82 SUB DCDB-1 SUPPLY-1 FOR SAS CONSOLE DESK (55" MONITOR, 27" MONITOR-2Nos) 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.89 0.88 4.20

QB1.83 SUB DCDB-1 SUPPLY-1 FOR DC EMERGENCY LIGHTING FOR PROTECTION PANELS 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.09 0.09 4.20

QB1.84 SUB DCDB-1 SUPPLY FOR CHANGE OVER SCHEME-2 (ATS FOR DCDB-2) 50 1 1 50 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.11 0.11 4.20

QB1.85 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.86 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.87 SUB DCDB-1 SUPPLY FOR SDB-1 (SUB ACDB-1) 50 1 1 50 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.11 0.11 4.20

SUPPLY FOR 13.8 KV SWGR O/G FEEDER SECTION-1(AH01 TO AH08, AH10 TO MCB
QB1.88 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.52 0.51 4.20
AH17)

SUPPLY FOR 13.8 KV SWGR O/G FEEDER SECTION-2(AH19 TO AH28, AH30 TO MCB
QB1.89 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.52 0.51 4.20
AH35)

SUPPLY FOR 13.8 KV SWGR O/G FEEDER SECTION-3(AH37 TO AH44, AH46 TO MCB
QB1.90 SUB DCDB-1 234.6 1 1 234.6 101.5 2.31 2.77 20 DP 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.52 0.51 4.20
AH52)

QB1.91 SUB DCDB-1 SUPPLY FOR 13.8 KV SWGR BUS SECTION-1 (AH18)(SYNCH TROLLY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.18 0.17 4.20

QB1.92 SUB DCDB-1 SUPPLY FOR 13.8 KV SWGR BUS SECTION (AH36)(SYNCH TROLLY SUPPLY) 79.7 1 1 79.7 101.5 0.79 0.94 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.18 0.17 4.20

QB1.93 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-3 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.07 0.07 4.20

QB1.94 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-4 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.07 0.07 4.20

QB1.95 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-5 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.07 0.07 4.20

QB1.96 SUB DCDB-1 SUPPLY-1 FOR RM PANEL-6 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.07 0.07 4.20

9 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QB1.97 SUB DCDB-1 SUPPLY FOR RECEPTACLES IN CONTROL ROOM 200 1 1 200 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.44 0.44 4.20

QB1.98 SUB DCDB-1 SUPPLY FOR TRANSFORMER-1 MECHANICAL PROTECTION PANNEL 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Duct 47 1 16 0.91 0.45 0.41 19.25 5.878211 0.0940514 0.28 0.28 4.20

QB1.99 SUB DCDB-1 SUPPLY FOR TRANSFORMER-2 MECHANICAL PROTECTION PANNEL 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Duct 48 1 16 0.91 0.45 0.41 19.66 5.878211 0.0940514 0.28 0.28 4.20

QB1.100 SUB DCDB-1 SUPPLY FOR TRANSFORMER-3 MECHANICAL PROTECTION PANNEL 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Duct 49 1 16 0.91 0.45 0.41 20.07 5.878211 0.0940514 0.28 0.28 4.20

QB1.101 SUB DCDB-1 SUPPLY FOR LINE FEEDER (FUTURE)-E10 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB FUTURE

QB1.102 SUB DCDB-1 SUPPLY FOR LINE FEEDER -E08 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.28 0.28 4.20

QB1.103 SUB DCDB-1 SUPPLY FOR LINE FEEDER -E04 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.28 0.28 4.20

QB1.104 SUB DCDB-1 SUPPLY FOR LINE FEEDER -E01 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.28 0.28 4.20

QB1.105 SUB DCDB-1 SUPPLY FOR LINE FEEDER -E05 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 16 0.91 0.45 0.41 20.88 5.878211 0.0940514 0.28 0.28 4.20

QB1.106 SUB DCDB-1 SUPPLY FOR LINE FEEDER(FUTURE)-E07 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB FUTURE

QB1.107 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.108 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.109 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.110 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.111 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.112 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.113 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.114 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.115 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.116 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.117 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.118 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.119 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.120 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.121 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.122 SUB DCDB-1 SPARE 20 DP MCB SPARE

QB1.123 SUB DCDB-1 SPARE 20 DP MCB SPARE

SUB-DCDB-2 (125 VDC, 2WIRES SYSTEM, 250A @40°C)

QA2.1 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER (FUTURE)-E07 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB FUTURE

QA2.2 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER-E05 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.3 SUB DCDB-2 SUPPLY-10 FOR HV TRANSFORMER T01-E03 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

10 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QA2.4 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER -E01 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.5 SUB DCDB-2 SUPPLY-10 FOR HV BUS COUPLER-A -E130 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.6 SUB DCDB-2 SUPPLY-10 FOR HV BUS SECTION-E220 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.7 SUB DCDB-2 SUPPLY-10 FOR HV BUS COUPLER-B -E230 DS/ES & H-ES MOTOR CKT 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.8 SUB DCDB-2 SUPPLY-10 FOR HV TRANSFORMER T02-E02 DS/ES & H-ES MOTOR CKT() 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.9 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER-E04 DS/ES & H-ES MOTOR CKT() 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.10 SUB DCDB-2 SUPPLY-10 FOR HV TRANSFORMER T03-E06 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.11 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER -E08 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.81 1.78 4.20

QA2.12 SUB DCDB-2 SUPPLY-10 FOR HV LINE FEEDER (FUTURE)-E10 (DS/ES & H-ES MOTOR CKT) 650 1 1 650.0 101.5 6.40 7.68 20 DP MCB FUTURE

SUPPLY-8 FOR HV LINE FEEDER (FUTURE)-E07 (LAMP, INDICATOR, MCB FUTURE


QA2.13 SUB DCDB-2 122.5 1 1 122.5 101.5 1.21 1.45 20 DP
ANNUNCIATOR )

QA2.14 SUB DCDB-2 SUPPLY-8 FOR HV LINE FEEDER-E05 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.15 SUB DCDB-2 SUPPLY-8 FOR HV TRANSFORMER T01-E03 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.16 SUB DCDB-2 SUPPLY-8 FOR HV LINE FEEDER-E01 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.17 SUB DCDB-2 SUPPLY-8 FOR HV BUS COUPLER-A -E130 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.18 SUB DCDB-2 SUPPLY-8 FOR HV BUS SECTION-E220 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.19 SUB DCDB-2 SUPPLY-8 FOR HV BUS COUPLER-B -E230 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.20 SUB DCDB-2 SUPPLY-8 FOR HV TRANSFORMER T02-E02 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.21 SUB DCDB-2 SUPPLY-8 FOR HV LINE FEEDER-E04 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.22 SUB DCDB-2 SUPPLY-8 FOR HV TRANSFORMER T03-E06 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.23 SUB DCDB-2 SUPPLY-8 FOR HV LINE FEEDER S/S-E08 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.34 0.34 4.20

QA2.24 SUB DCDB-2 SUPPLY-8 FOR HV FUTURE FEEDER-E10 (LAMP, INDICATOR, ANNUNCIATOR ) 122.5 1 1 122.5 101.5 1.21 1.45 20 DP MCB FUTURE

QA2.25 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER (FUTURE)-E07 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB FUTURE

QA2.26 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER-E05 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.27 SUB DCDB-2 SUPPLY-9 FOR TRANSFORMER T01-E03 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.28 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER-E01 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.29 SUB DCDB-2 SUPPLY-9 FOR BUS COUPLER-A-E130 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.30 SUB DCDB-2 SUPPLY-9 FOR BUS SECTION-E220 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.31 SUB DCDB-2 SUPPLY-9 FOR BUS COUPLER-B -E230 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.32 SUB DCDB-2 SUPPLY-9 FOR TRANSFORMER T02-E02 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.33 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER-E04 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.34 SUB DCDB-2 SUPPLY-9 FOR TRANSFORMER T03-E06 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

11 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QA2.35 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER S/S-E08 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.06 0.05 4.20

QA2.36 SUB DCDB-2 SUPPLY-9 FOR LINE FEEDER (FUTURE)-E10 (DS/ES CONTROL CIRCUIT) 20 1 1 20.0 101.5 0.20 0.24 20 DP MCB FUTURE

SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-1(AH01) (TRIP CKT-2, MCB FUTURE
QA2.37 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP
INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-1(AH02) (TRIP CKT-2, MCB FUTURE
QA2.38 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP
INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-1(AH03) (TRIP CKT-2, MCB
QA2.39 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH04) (TRIP CKT-2, INDICATION MCB
QA2.40 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH05) (TRIP CKT-2, INDICATION MCB
QA2.41 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH06) (TRIP CKT-2, INDICATION
QA2.42 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH07) (TRIP CKT-2, INDICATION MCB
QA2.43 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH08) (TRIP CKT-2, INDICATION MCB
QA2.44 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR I/C FEEDER MCB


QA2.45 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
(AH09) (TRIP CKT-2, INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH10) (TRIP CKT-2, INDICATION MCB
QA2.46 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH11) (TRIP CKT-2, INDICATION MCB
QA2.47 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH12) (TRIP CKT-2, INDICATION MCB
QA2.48 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH13) (TRIP CKT-2, INDICATION MCB
QA2.49 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH14) (TRIP CKT-2, INDICATION MCB
QA2.50 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-1(AH15) (TRIP CKT-2, INDICATION MCB
QA2.51 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR AUX. TFR. FEEDER BUS-1(AH16) (TRIP CKT-2, MCB
QA2.52 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR BUS METERING-01 (AH17) (EARTH SWITCH MCB
QA2.53 SUB DCDB-2 127 1 1 127.2 101.5 1.25 1.50 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.92 0.91 10.00
INTERLOCK, I/O BOX-1)

SUPPLY-2 FOR 13.8kV SWGR BUS SECTION-1 MCB


QA2.54 SUB DCDB-2 718 1 1 717.8 101.5 7.07 8.49 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.19 5.11 10.00
(AH18) (TRIP CKT-2, INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR BUS RISER-01 FEEDER BUS-1(AH19) (EARTH MCB
QA2.55 SUB DCDB-2 126 1 1 126.0 101.5 1.24 1.49 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.91 0.90 10.00
SWITCH INTERLOCK, I/O BOX-1)

SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-2 (AH20) (TRIP CKT-2, MCB
QA2.56 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH21) (TRIP CKT-2, INDICATION MCB
QA2.57 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2 (AH22) (TRIP CKT-2, INDICATION MCB
QA2.58 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH23) (TRIP CKT-2, INDICATION MCB
QA2.59 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH24) (TRIP CKT-2, INDICATION MCB
QA2.60 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH25) (TRIP CKT-2, INDICATION MCB
QA2.61 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH26) (TRIP CKT-2, INDICATION MCB
QA2.62 SUB DCDB-2 723 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 5.22 5.15 10.00
CKT, BCU AUXILIARY SUPPLY)

QA2.63 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-1 (SET-2) 61 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.44 0.44 4.20

QA2.64 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-2 (SET-2) 61 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.44 0.44 4.20

QA2.65 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-3 (SET-2) 61 1 1 61.3 101.5 0.60 0.72 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.44 0.44 4.20

12 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

SUPPLY FOR 13.8KV UNDER VOLTAGE LOAD SHEDDING PROTECTION PANEL MCB
QA2.66 SUB DCDB-2 73 1 1 72.5 101.5 0.71 0.86 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.52 0.52 4.20
(SET-2)

SUPPLY FOR 13.8KV UNDER VOLTAGE LOAD SHEDDING PROTECTION PANEL MCB
QA2.67 SUB DCDB-2 15 1 1 15.0 101.5 0.15 0.18 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.11 0.11 4.20
(INDICATION CKT FOR SET-1 & SET-2)

SUPPLY FOR 13.8kV UNDER FREQUENCY LOAD SHEDDING PROTECTION MCB


QA2.68 SUB DCDB-2 19 1 1 18.8 101.5 0.18 0.22 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.14 0.13 4.20
PANEL(BUS-A)

QA2.69 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.70 SUB DCDB-2 SUPPLY-2 FOR SAS CONSOLE DESK (55" MONITOR, 27" MONITOR-2Nos) 400 1 1 400.0 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 2.89 2.85 4.20

QA2.71 SUB DCDB-2 SUPPLY-2 FOR COMMON ALARM PANEL-2 50 1 1 50.0 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.36 0.36 4.20

QA2.72 SUB DCDB-2 SUPPLY-2 FOR COMMON ALARM PANEL-1 100 1 1 100.0 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.72 0.71 4.20

QA2.73 SUB DCDB-2 SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-B PANEL-2 150 1 1 150.0 101.5 1.48 1.77 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 1.08 1.07 4.20

QA2.74 SUB DCDB-2 SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-A PANEL-2 150 1 1 150.0 101.5 1.48 1.77 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 1.08 1.07 4.20

QA2.75 SUB DCDB-2 SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-B PANEL-1 200 1 1 200.0 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 1.45 1.42 4.20

QA2.76 SUB DCDB-2 SUPPLY-2 FOR SAS ETHERNET SWITCH LAN-A PANEL-1 200 1 1 200.0 101.5 1.97 2.36 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 1.45 1.42 4.20

QA2.77 SUB DCDB-2 SUPPLY-2 FOR SAS COMPUTER PANEL-3 500 1 1 500.0 101.5 4.93 5.91 20 DP MCB 2C 6 XLPE Air 67 1 52 0.91 0.45 0.41 27.44 3.927308 0.2042200 2.41 2.38 4.20

QA2.78 SUB DCDB-2 SUPPLY-2 FOR SAS COMPUTER PANEL-2 1200 1 1 1200.0 101.5 11.82 14.19 20 DP MCB 2C 10 XLPE Air 88 1 52 0.91 0.45 0.41 36.04 2.333433 0.1213385 3.44 3.39 4.20

QA2.79 SUB DCDB-2 SUPPLY-2 FOR SAS COMPUTER PANEL-1 1200 1 1 1200.0 101.5 11.82 14.19 20 DP MCB 2C 10 XLPE Air 88 1 52 0.91 0.45 0.41 36.04 2.333433 0.1213385 3.44 3.39 4.20

QA2.80 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.81 SUB DCDB-2 SUPPLY FOR SDB-2 (SUB ACDB-2) 50 1 1 50.0 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.36 0.36 4.20

QA2.82 SUB DCDB-2 SUPPLY FOR CONTROL CABINET 110/13.8KV T01 (+MK) 593 1 1 592.8 101.5 5.84 7.01 20 DP MCB 2C 6 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 3.927308 0.2042200 2.86 2.82 4.20

QA2.83 SUB DCDB-2 SUPPLY FOR CONTROL CABINET 110/13.8KV T02 (+MK) 593 1 1 592.8 101.5 5.84 7.01 20 DP MCB 2C 6 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 3.927308 0.2042200 2.86 2.82 4.20

QA2.84 SUB DCDB-2 SUPPLY FOR CONTROL CABINET 110/13.8KV T03 (+MK) 593 1 1 592.8 101.5 5.84 7.01 20 DP MCB 2C 6 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 3.927308 0.2042200 2.86 2.82 4.20

QA2.85 SUB DCDB-2 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T01 78 1 1 78.0 101.5 0.77 0.92 20 DP MCB 2C 4 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 5.878211 0.3056670 0.56 0.56 4.20

QA2.86 SUB DCDB-2 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T02 78 1 1 78.0 101.5 0.77 0.92 20 DP MCB 2C 4 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 5.878211 0.3056670 0.56 0.56 4.20

QA2.87 SUB DCDB-2 SUPPLY FOR OLTC MDU CABINET 110/13.8KV T03 78 1 1 78.0 101.5 0.77 0.92 20 DP MCB 2C 4 XLPE Duct 47 1 52 0.91 0.45 0.41 19.25 5.878211 0.3056670 0.56 0.56 4.20

SUPPLY FOR 13.8kV UNDER FREQUENCY LOAD SHEDDING PROTECTION MCB


QA2.88 SUB DCDB-2 19 1 1 18.8 101.5 0.18 0.22 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.14 0.13 4.20
PANEL(BUS-C)

SUPPLY FOR 13.8KV UNDER FREQUENCY LOAD SHEDDING PROTECTION MCB


QA2.89 SUB DCDB-2 10 1 1 10.0 101.5 0.10 0.12 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.07 0.07 4.20
PANEL(INDICATION OF BUS-A,B & C)

QA2.90 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.91 SUB DCDB-2 SUPPLY-2 TO ACDB 50 1 1 50.0 101.5 0.49 0.59 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.36 0.36 4.20

QA2.92 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.93 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.94 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.95 SUB DCDB-2 SUPPLY-2 FOR AMI PANEL-1 118 1 1 118.0 101.5 1.16 1.40 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.85 0.84 4.20

QA2.96 SUB DCDB-2 SUPPLY-2 FOR AMI PANEL-2 118 1 1 118.0 101.5 1.16 1.40 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.85 0.84 4.20

13 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QA2.97 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-1 30 1 1 30.0 101.5 0.30 0.35 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.22 0.21 4.20

QA2.98 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-2 30 1 1 30.0 101.5 0.30 0.35 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.22 0.21 4.20

QA2.99 SUB DCDB-2 SUPPLY-2 FOR DC EMERGENCY LIGHTING FOR CONTROL PANELS 40 1 1 40.0 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.29 0.28 4.20

QA2.100 SUB DCDB-2 SUPPLY-2 FOR DC EMERGENCY LIGHTING FOR PROTECTION PANELS 40 1 1 40.0 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.29 0.28 4.20

SUPPLY FOR 13.8kV UNDER VOLTAGE LOAD SHEDDING PROTECTION MCB


QA2.101 SUB DCDB-2 73 1 1 72.5 101.5 0.71 0.86 20 DP 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 0.52 0.52 4.20
PANEL(TRIP CKT)

QA2.102 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.103 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.104 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.105 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.106 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.107 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.108 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.109 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.110 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.111 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.112 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.113 SUB DCDB-2 SPARE 20 DP MCB SPARE

QA2.114 SUB DCDB-2 SPARE 20 DP MCB SPARE

SEC-B (125 VDC, 2WIRES SYSTEM, 250A @40°C)

QB2.1 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER (FUTURE)-E07 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB FUTURE

QB2.2 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER-E05 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.3 SUB DCDB-2 SUPPLY-7 FOR HV TRANSFORMER T01-E03 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.4 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER-E01 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.5 SUB DCDB-2 SUPPLY-7 FOR HV BUS COUPLER-A -E130 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.6 SUB DCDB-2 SUPPLY-7 FOR HV BUS SECTION-E220 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.7 SUB DCDB-2 SUPPLY-7 FOR HV BUS COUPLER-B -E230 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.8 SUB DCDB-2 SUPPLY-7 FOR HV TRANSFORMER T02-E02 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.9 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER-E04 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.10 SUB DCDB-2 SUPPLY-7 FOR HV TRANSFORMER T03-E06 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.11 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER S/S-E08 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.95 1.92 10.00

QB2.12 SUB DCDB-2 SUPPLY-7 FOR HV LINE FEEDER (FUTURE)-E10 (CB TRIP CKT-1) 500 1 1 500 101.5 4.93 5.91 20 DP MCB FUTURE

14 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QB2.13 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER FUTURE)-E07 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB FUTURE

QB2.14 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER-E05 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 38 0.91 0.45 0.41 20.88 5.878211 0.2233720 0.21 0.21 4.20

QB2.15 SUB DCDB-2 SUPPLY-11 FOR HV TRANSFORMER T01-E03 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.16 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER-E01 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.17 SUB DCDB-2 SUPPLY-11 FOR HV BUS COUPLER-A-E130 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.18 SUB DCDB-2 SUPPLY-11 FOR HV BUS SECTION-E220 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.19 SUB DCDB-2 SUPPLY-11 FOR HV BUS COUPLER-B-E230 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.20 SUB DCDB-2 SUPPLY-11 FOR HV TRANSFORMER T02-E02 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.21 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER-E04 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.22 SUB DCDB-2 SUPPLY-11 FOR HV TRANSFORMER T03-E06 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.23 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER -E08 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.24 SUB DCDB-2 SUPPLY-11 FOR HV LINE FEEDER (FUTURE)-E10 (I/O MODULE POWER SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB FUTURE

QB2.25 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER (FUTURE)-E07 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB FUTURE

QB2.26 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER-E05 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.27 SUB DCDB-2 SUPPLY-12 FOR HV TRANSFORMER T01-E03 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.28 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER-E01 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.29 SUB DCDB-2 SUPPLY-12 FOR HV BUS COUPLER-A -E130 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.30 SUB DCDB-2 SUPPLY-12 FOR HV BUS SECTION-E220 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.31 SUB DCDB-2 SUPPLY-12 FOR HV BUS COUPLER-B -E230 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.32 SUB DCDB-2 SUPPLY-12 FOR HV TRANSFORMER T02-E02 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.33 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER-E04 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.34 SUB DCDB-2 SUPPLY-12 FOR HV TRANSFORMER T03-E06 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.35 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER S/S-E08 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.16 0.15 4.20

QB2.36 SUB DCDB-2 SUPPLY-12 FOR HV LINE FEEDER (FUTURE)-E10 (SYNCHRO TROLLEY SUPPLY) 40 1 1 40 101.5 0.39 0.47 20 DP MCB FUTURE

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH27) (TRIP CKT-2, INDICATION MCB
QB2.37 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH28) (TRIP CKT-2, INDICATION MCB
QB2.38 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR I/C FEEDER (AH29) (TRIP CKT-2, INDICATION CKT, MCB
QB2.39 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH30) (TRIP CKT-2, INDICATION MCB
QB2.40 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH31) (TRIP CKT-2, INDICATION MCB
QB2.41 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH32) (TRIP CKT-2, INDICATION MCB
QB2.42 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH33) (TRIP CKT-2, INDICATION MCB
QB2.43 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

15 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH34) (TRIP CKT-2, INDICATION MCB
QB2.44 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-2(AH35) (TRIP CKT-2, INDICATION MCB
QB2.45 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR BUS SECTION-02 (AH36) (TRIP CKT-2, INDICATION MCB
QB2.46 SUB DCDB-2 717.8 1 1 717.8 101.5 7.07 8.49 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.79 2.75 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR BUS RISER-01 FEEDER BUS-1(AH37) (EARTH MCB
QB2.47 SUB DCDB-2 126 1 1 126 101.5 1.24 1.49 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.48 4.20
SWITCH INTERLOCK, I/O BOX-1SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR AUX. TFR. FEEDER BUS-2(AH38) (TRIP CKT-2, MCB
QB2.48 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH39) (TRIP CKT-2, INDICATION MCB
QB2.49 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH40) (TRIP CKT-2, INDICATION MCB
QB2.50 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH41) (TRIP CKT-2, INDICATION MCB
QB2.51 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH42) (TRIP CKT-2, INDICATION MCB
QB2.52 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH43) (TRIP CKT-2, INDICATION MCB
QB2.53 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH44) (TRIP CKT-2, INDICATION MCB
QB2.54 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH45) (TRIP CKT-2, INDICATION MCB
QB2.55 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH46) (TRIP CKT-2, INDICATION MCB
QB2.56 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH47) (TRIP CKT-2, INDICATION MCB
QB2.57 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH48) (TRIP CKT-2, INDICATION MCB
QB2.58 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH49) (TRIP CKT-2, INDICATION MCB
QB2.59 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR O/G FEEDER BUS-3(AH50) (TRIP CKT-2, INDICATION MCB
QB2.60 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR CAP. FEEDER BUS-3(AH51) (TRIP CKT-2, MCB
QB2.61 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 2.81 2.77 4.20
INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY-2 FOR 13.8kV SWGR FUTURE FEEDER BUS-3(AH52) (TRIP CKT-2, MCB FUTURE
QB2.62 SUB DCDB-2 722.6 1 1 722.6 101.5 7.12 8.54 20 DP
INDICATION CKT, BCU AUXILIARY SUPPLY)

SUPPLY FOR FUTURE FEEDER-E07 PROTECTION PANEL SET-2 (MAIN-2 PROTN MCB FUTURE
QB2.63 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP
CKT & IN/OUT RELAY CKT)

SUPPLY FOR SPARE FEEDER -E05 PROTECTION PANEL SET-2 (MAIN-2 PROTN MCB
QB2.64 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
CKT & IN/OUT RELAY CKT)

SUPPLY FOR TRANSFORMER T01-E03 PROTECTION PANEL SET-2 (MAIN-2 MCB


QB2.65 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
PROTN CKT & IN/OUT RELAY CKT)

SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL SET-2 (MAIN-2 PROTN CKT MCB
QB2.66 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
& IN/OUT RELAY CKT)

SUPPLY FOR TRANSFORMER T02-E02 PROTECTION PANEL SET-2 (MAIN-2 MCB


QB2.67 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
PROTN CKT & IN/OUT RELAY CKT)

SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL SET-2 (MAIN-2 PROTN CKT MCB
QB2.68 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
& IN/OUT RELAY CKT)

SUPPLY FOR TRANSFORMER T03-E06 PROTECTION PANEL SET-2 (MAIN-2 MCB


QB2.69 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
PROTN CKT & IN/OUT RELAY CKT)

SUPPLY FOR SPARE FEEDER-E08 PROTECTION PANEL SET-2 (MAIN-2 PROTN MCB
QB2.70 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.05 0.05 4.20
CKT & IN/OUT RELAY CKT)

SUPPLY FOR FUTURE FEEDER- E10 PROTECTION PANEL SET-2 (MAIN-2 PROTN MCB FUTURE
QB2.71 SUB DCDB-2 11.9 1 1 11.9 101.5 0.12 0.14 20 DP
CKT & IN/OUT RELAY CKT)

SUPPLY FOR FUTURE FEEDER-E07 PROTECTION PANEL SET-1 & SET- MCB FUTURE
QB2.72 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP
2(INDICATION CKT)

SUPPLY FOR SPARE FEEDER -E05 PROTECTION PANEL SET-1 & SET- MCB
QB2.73 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
2(INDICATION CKT)

SUPPLY FOR TRANSFROMER T01-E03 PROTECTION PANEL SET-1 & SET- MCB
QB2.74 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
2(INDIACTION CKT)

16 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL SET-1 & SET-2(INDICATION MCB
QB2.75 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
CKT)

SUPPLY FOR TRANSFORMER T02-E02 PROTECTION PANEL SET-1 & SET- MCB
QB2.76 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
2(INDIACTION CKT)

SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL SET-1 & SET-2(INDICATION MCB
QB2.77 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
CKT)

SUPPLY FOR TRANSFORMER T03-E06 PROTECTION PANEL SET-1 & SET- MCB
QB2.78 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
2(INDIACTION CKT)

SUPPLY FOR SPARE FEEDER-E08 PROTECTION PANEL SET-1 & SET-2 MCB
QB2.79 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.00 0.00 4.20
(INDICATION CKT)

SUPPLY FOR FUTURE FEEDER-E10 PROTECTION PANEL SET-1 & SET- MCB FUTURE
QB2.80 SUB DCDB-2 1 1 1 1 101.5 0.01 0.01 20 DP
2(INDICATION CKT)

QB2.81 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.82 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.83 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.84 SUB DCDB-2 SUPPLY FOR LINE FEEDER(FUTURE)-E10 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 105.5 1.20 1.44 20 DP MCB FUTURE

QB2.85 SUB DCDB-2 SUPPLY FOR LINE FEEDER-E08 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20

QB2.86 SUB DCDB-2 SUPPLY FOR LINE FEEDER-E04 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20

QB2.87 SUB DCDB-2 SUPPLY FOR LINE FEEDER-E01 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20

QB2.88 SUB DCDB-2 SUPPLY FOR LINE FEEDER-E05 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.49 0.49 4.20

QB2.89 SUB DCDB-2 SUPPLY FOR LINE FEEDER(FUTURE)-E07 PROTECTION PANEL(INTERTRIP-2) 127 1 1 127 101.5 1.25 1.50 20 DP MCB FUTURE

QB2.90 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-1 (INDICATION CKT) 2.25 1 1 2.25 101.5 0.02 0.03 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.01 0.01 4.20

QB2.91 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-2 (INDICATION CKT)" 2.25 1 1 2.25 101.5 0.02 0.03 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.01 0.01 4.20

QB2.92 SUB DCDB-2 SUPPLY FOR 13.8KV CAPACITOR PROTECTION PANEL-3 (INDICATION CKT)" 2.25 1 1 2.25 101.5 0.02 0.03 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 0.01 0.01 4.20

QB2.93 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.94 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.95 SUB DCDB-2 SPARE 20 DP MCB SPARE

SUPPLY FOR 13.8 KV BUSBAR PROTECTION PANEL (INDICATION SET-1 & SET-2 MCB
QB2.96 SUB DCDB-2 1.25 1 1 1.25 105.5 0.01 0.01 20 DP 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 0.00 0.00 4.20
CKT)"

QB2.97 SUB DCDB-2 SUPPLY FOR 13.8 KV BUSBAR PROTECTION PANEL (INDICATION SET-3 CKT)" 1.25 1 1 1.25 101.5 0.01 0.01 20 DP MCB 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 0.00 0.00 4.20

QB2.98 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.99 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.100 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-3 31 1 1 31 103.5 0.30 0.36 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.08 0.08 4.20

QB2.101 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-4 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.09 0.08 4.20

QB2.102 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-5 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.09 0.08 4.20

QB2.103 SUB DCDB-2 SUPPLY-2 FOR RM PANEL-6 31 1 1 31 101.5 0.31 0.37 20 DP MCB 2C 4 XLPE Air 51 1 21 0.91 0.45 0.41 20.88 5.878211 0.1234424 0.09 0.09 4.20

QB2.104 SUB DCDB-2 13.8kV BBP(1A)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 22 0.91 0.45 0.41 20.88 5.878211 0.1293206 0.05 0.05 4.20

QB2.105 SUB DCDB-2 13.8kV BBP(1B)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 23 0.91 0.45 0.41 20.88 5.878211 0.1351989 0.05 0.05 4.20

17 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QB2.106 SUB DCDB-2 13.8kV BBP(1C)IN & OUT CKT 15.25 1 1 15.25 101.5 0.15 0.18 20 DP MCB 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 0.05 0.05 4.20

QB2.107 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.108 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.109 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.110 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.111 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.112 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.113 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.114 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.115 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.116 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.117 SUB DCDB-2 SPARE 20 DP MCB SPARE

QB2.118 SUB DCDB-2 SPARE 20 DP MCB SPARE

EMERGENCY LIGHTING PANEL- (125 VDC, 2WIRES SYSTEM, 80A @40°C)

QA.001 SUB DCDB-ELP HV GIS ROOM 800 1 1 800 101.5 7.881773 9.458128 20 DP MCB 2C 6 XLPE Air 67 1 52 0.91 0.45 0.41 27.44 3.927308 0.2042200 3.86 3.81 4.20

QA.002 SUB DCDB-ELP HV GIS ROOM 800 1 1 800 101.5 7.881773 9.458128 20 DP MCB 2C 6 XLPE Air 67 1 52 0.91 0.45 0.41 27.44 3.927308 0.2042200 3.86 3.81 4.20

QA.003 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 2.89 2.85 4.20

QA.004 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 52 0.91 0.45 0.41 20.88 5.878211 0.3056670 2.89 2.85 4.20

QA.005 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 51 0.91 0.45 0.41 20.88 5.878211 0.2997888 2.84 2.79 4.20

QA.006 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 50 0.91 0.45 0.41 20.88 5.878211 0.2939106 2.78 2.74 4.20

QA.007 SUB DCDB-ELP STAIR CASE 300 1 1 300 101.5 2.955665 3.546798 20 DP MCB 2C 4 XLPE Air 51 1 49 0.91 0.45 0.41 20.88 5.878211 0.2880323 2.04 2.01 4.20

QA.008 SUB DCDB-ELP TELECOM ROOM 200 1 1 200 101.5 1.970443 2.364532 20 DP MCB 2C 4 XLPE Air 51 1 48 0.91 0.45 0.41 20.88 5.878211 0.2821541 1.33 1.31 4.20

QA.009 SUB DCDB-ELP FM ROOM 300 1 1 300 101.5 2.955665 3.546798 20 DP MCB 2C 4 XLPE Air 51 1 47 0.91 0.45 0.41 20.88 5.878211 0.2762759 1.96 1.93 4.20

QA.010 SUB DCDB-ELP RECORD ROOM 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 46 0.91 0.45 0.41 20.88 5.878211 0.2703977 2.56 2.52 4.20

QA.011 SUB DCDB-ELP PUSH BUTTON FOR GIS ROOM CABLE BASEMENT 100 1 1 100 101.5 0.985222 1.182266 20 DP MCB 2C 4 XLPE Air 51 1 45 0.91 0.45 0.41 20.88 5.878211 0.2645195 0.63 0.62 4.20

QA.012 SUB DCDB-ELP PUSH BUTTON FOR SWG ROOM 100 1 1 100 101.5 0.985222 1.182266 20 DP MCB 2C 4 XLPE Air 51 1 44 0.91 0.45 0.41 20.88 5.878211 0.2586413 0.61 0.60 4.20

QA.013 SUB DCDB-ELP SWGR CABLE BASEMENT 100 1 1 100 101.5 0.985222 1.182266 20 DP MCB 2C 4 XLPE Air 51 1 43 0.91 0.45 0.41 20.88 5.878211 0.2527631 0.60 0.59 4.20

QA.014 SUB DCDB-ELP FM ROOM1 500 1 1 500 101.5 4.926108 5.91133 20 DP MCB 2C 4 XLPE Air 51 1 42 0.91 0.45 0.41 20.88 5.878211 0.2468849 2.92 2.88 4.20

QA.015 SUB DCDB-ELP SWGR CABLE BASEMENT 500 1 1 500 101.5 4.926108 5.91133 20 DP MCB 2C 4 XLPE Air 51 1 41 0.91 0.45 0.41 20.88 5.878211 0.2410067 2.85 2.81 4.20

QA.016 SUB DCDB-ELP BASEMENT CORRIDOOR 500 1 1 500 101.5 4.926108 5.91133 20 DP MCB 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 2.78 2.74 4.20

QA.017 SUB DCDB-ELP WORKSHOP 400 1 1 400 101.5 3.940887 4.729064 20 DP MCB 2C 4 XLPE Air 51 1 40 0.91 0.45 0.41 20.88 5.878211 0.2351284 2.22 2.19 4.20

18 of 19
CB DATA Cable Data Derating Factors Permi.

DiverIsity
Demand
Unit load Total IFL IOLC Derated Unit R Voltage

Factor

Factor
CB.No From TO Volts Net R (Ω) % VD
(W) load (W) AMP AMP NO OF Type No.Of Length Temp400 AMP (Ω/km) drop (V)
Rating (A) Core mm2 Type Laid in AMP Group Overall % VD
POLES Runs (m) C

QA.018 SUB DCDB-ELP EQUIPMENT ROOM 300 1 1 300 101.5 2.955665 3.546798 20 DP MCB 2C 4 XLPE Air 51 1 39 0.91 0.45 0.41 20.88 5.878211 0.2292502 1.63 1.60 4.20

QA.019 SUB DCDB-ELP SPARE 20 DP MCB SPARE

QA.020 SUB DCDB-ELP SPARE 20 DP MCB SPARE

QA.021 SUB DCDB-ELP SPARE 20 DP MCB SPARE

QA.022 SUB DCDB-ELP SPARE 20 DP MCB SPARE

SEC-B (125 VDC , 2WIRES SYSTEM, 80A @40°C)

QB.001 SUB DCDB-ELP MV SWGR ROOM 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 28 0.91 0.45 0.41 20.88 5.878211 0.1645899 1.56 1.53 4.20

QB.002 SUB DCDB-ELP MV SWGR ROOM 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 27 0.91 0.45 0.41 20.88 5.878211 0.1587117 1.50 1.48 4.20

QB.003 SUB DCDB-ELP STAIR CASE 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 26 0.91 0.45 0.41 20.88 5.878211 0.1528335 1.08 1.07 4.20

QB.004 SUB DCDB-ELP STAIR CASE 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 25 0.91 0.45 0.41 20.88 5.878211 0.1469553 1.04 1.03 4.20

QB.005 SUB DCDB-ELP CONTROL ROOM 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 1.33 1.31 4.20

QB.006 SUB DCDB-ELP TOILET 500 1 1 500 101.5 4.93 5.91 20 DP MCB 2C 4 XLPE Air 51 1 23 0.91 0.45 0.41 20.88 5.878211 0.1351989 1.60 1.57 4.20

QB.007 SUB DCDB-ELP PUCH BUTTON FOR SWGR CABLE BASEMENT 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 22 0.91 0.45 0.41 20.88 5.878211 0.1293206 0.31 0.30 4.20

QB.008 SUB DCDB-ELP PUSH BUTTON FOR GIS ROOM 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 21 0.91 0.45 0.41 20.88 5.878211 0.1234424 0.29 0.29 4.20

QB.009 SUB DCDB-ELP PUSH BUTTON FOR CONTROL ROOM 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 0.28 0.27 4.20

QB.010 SUB DCDB-ELP GROUND ENTERANCE 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 20 0.91 0.45 0.41 20.88 5.878211 0.1175642 1.11 1.10 4.20

QB.011 SUB DCDB-ELP GIS ROOM CABLE BASEMENT 600 1 1 600 101.5 5.91 7.09 20 DP MCB 2C 4 XLPE Air 51 1 21 0.91 0.45 0.41 20.88 5.878211 0.1234424 1.75 1.73 4.20

QB.012 SUB DCDB-ELP GIS ROOM CABLE BASEMENT 600 1 1 600 101.5 5.91 7.09 20 DP MCB 2C 4 XLPE Air 51 1 22 0.91 0.45 0.41 20.88 5.878211 0.1293206 1.83 1.81 4.20

QB.013 SUB DCDB-ELP BASEMENT LOBBY 100 1 1 100 101.5 0.99 1.18 20 DP MCB 2C 4 XLPE Air 51 1 23 0.91 0.45 0.41 20.88 5.878211 0.1351989 0.32 0.31 4.20

QB.014 SUB DCDB-ELP BATTERY ROOM 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 24 0.91 0.45 0.41 20.88 5.878211 0.1410771 1.00 0.99 4.20

QB.015 SUB DCDB-ELP COMMUNICATION ROOM 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 25 0.91 0.45 0.41 20.88 5.878211 0.1469553 1.04 1.03 4.20

QB.016 SUB DCDB-ELP ENTRANCE LOBBY 400 1 1 400 101.5 3.94 4.73 20 DP MCB 2C 4 XLPE Air 51 1 26 0.91 0.45 0.41 20.88 5.878211 0.1528335 1.45 1.42 4.20

QB.017 SUB DCDB-ELP EXTERNAL BATTERY ROOM 300 1 1 300 101.5 2.96 3.55 20 DP MCB 2C 4 XLPE Air 51 1 27 0.91 0.45 0.41 20.88 5.878211 0.1587117 1.13 1.11 4.20

QB.018 SUB DCDB-ELP SPARE 20 DP MCB SPARE

QB.019 SUB DCDB-ELP SPARE 20 DP MCB SPARE

QB.020 SUB DCDB-ELP SPARE 20 DP MCB SPARE

QB.021 SUB DCDB-ELP SPARE 20 DP MCB SPARE

19 of 19
CERT'D
APPR'D
CHK'D

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
DESCRIPTION

UNIFIED LV AC CABLE SIZING CALCULATIONS


(COA & WOA)
BY
DATE
NO

REVISIONS
DESIGNED
BY:
DATE:
CHECKED
BY:
DATE:
OPRG. DEPT
BY: ………………
DATE: ……….
ENG'G. DEPT.
BY:- …………….
DATE: ………..
CERTIFIED.
BY: …………….
DATE: ……….. AS BUILT BY …………. DATE ………….
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF UNIFIED LV AC CABLE SIZING CALCULATIONS
FOR ORDERING
MATERIALS UNTIL (COA & WOA)
CERTIFIED AND
DATED
JEDDAH SAUDI ARABIA JOB ORDER NO DWG. CONT. SHT.

DMS EXCEL
Design Basis for cables
1- Cables are sized based on SEC Standard TES-P-119.29 ( LV Cable Sizing & Selection )
2- Formula used within this sheet are that provided by SEC Standard TES-P-119.29
3- As per 01-TMSS-01, ambient temperature of 40˚C is considered for cable sizing
4- For main incomer cables, the short circuit withstand current for Cu. conductors, XLPE Insulated is
given by the formula:-

0.143 S
I SC =
t
Where:-
Isc : Short Time Rating Current in kA
S : Conductor Cross-Section Area in mm²
t : Current Duration in Seconds.
So, Isc for 1C X 630 mm² Cable, for 3 Second :-
0.143 X 630
Isc = = 52.015 KA
𝟑𝟑
The secondary side of neutral cable size will be the same size of phase cable (1Cx630mm2) and it will withstand
the S.C rating of 25 KA.
Thus, the given cable can withstand the system fault level (25 kA ).
5- Cable sizes given are subject to change as per load updates.
6- Indicated lengthes are approximate, the actual route length may increase/decrease as per actual site conditions.

7- As per SEC standard No ( TES-P-119.29 ),Clause(7.1.9),Page 11, voltage drops (Regulation in %) shall be limited as:-
a)Total voltage drop from Station Transformer to loads not exceed 5%
b) Station Transformer to main distribution board (MD 0.80%
c) MDB to various loads
4.20%
(Motor starting voltage drop limited to 12.5%)
8- As per SEC standard No ( TES-P-119.29 ),Clause(7.2),Page 10 , Grouping Correction Factor as below:-
a) Cables from Station Transformer to main distribution board
- 0.87 for single core cable with trefoil touching configuration
b) Cables from main distribution board to various loads
- 0.45 for cable up to 16 mm2
- 0.70 for cable above 25 mm2

9- Main AC Distribution panel Bus bars shall withstand full available short circuit current and shall not
be less than 25KA as per TES-P-119.30 Rev.02, Clause 3.2.2

10- Short circuit current rating of AC sub Distribution panels shall be as per design calculations and
NGSA approval.

Reference Documents

Unified AC Auxiliary One Line Diagram


Unified Overall Substation General Layout
Unified Auxiliary Transformer Sizing Calculations
Unified LV AC CB Sizing Calculation
LV AC Cable sizing :-

System Voltage = 400 / 230 VAC


IFL 3ᵩ = w x 1000/(√3 x V x P %VD = (Voltage Drop / Supply Voltage) x 100
IFL 1ᵩ = Kw x 1000 / ( V x PF VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
IOLC = 1.20 x IFL VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying

ACDB(AT CONTROL ROOM)

CU / XLPE /
001 Q101 AUX.T1 ACDB BUS-A 425 1 425 500 3 400 722 866 1000AT/1000AF ACB 4P 722 0.85 0.53 1C 630 Duct 619 2 54 0.0454 0.092 1 0.87 1 1 0.87 1077.06 2.94 0.73 0.80
PVC

CU / XLPE /
002 Q102 AUX.T2 ACDB BUS-B 425 1 425 500 3 400 722 866 1000AT/1000AF ACB 4P 722 0.85 0.53 1C 630 Duct 619 2 57 0.0454 0.092 1 0.87 1 1 0.87 1077.06 3.10 0.78 0.80
PVC

400/230V, 1000A, 25kA(1s), 60Hz, 3PH 4WIRE MAIN ACDB-BUS A

MAIN ACDB 400V,3PH SUPPLY FOR PACKAGE COMPRESSOR CU / XLPE /


MDP.A1 Q.A1 97.00 0.5 97.00 114.118 3 400 165 198 200AT/250AF MCCB TPN 164.72 0.85 0.53 4C 120 Air 317 1 95 0.198 0.087 1 0.7 1 1 0.70 221.90 5.79 1.45 4.20
BUS A UNIT PACU-1A (DUTY). PVC

MAIN ACDB 400V,3PH SUPPLY FOR PACKAGE COMPRESSOR CU / XLPE /


MDP.A2 Q.A2 56.00 0.5 56.00 65.8824 3 400 95 114 125AT/160AF MCCB TPN 95.10 0.85 0.53 4C 50 Air 173 1 70 0.494 0.092 1 0.7 1 1 0.70 121.10 5.40 1.35 4.20
BUS A UNIT PACU-2B (STANDBY). PVC

MAIN ACDB SUPPLY FOR SUB DISTRIBUTION PANEL-1 ( SDP- CU / XLPE /


MDP.A3 Q.A3 70.48 1 70.48 82.9161 3 400 120 144 160AT/250AF MCCB TPN 119.68 0.85 0.53 4C 70 Air 220 1 13 0.343 0.090 1 0.7 1 1 0.70 154.00 0.91 0.23 0.80
BUS A 1). PVC

MAIN ACDB CU / XLPE /


MDP.A4 Q.A4 SUPPLY FOR INDOOR LIGHTING PANEL (ILP-1). 10.80 1 10.80 12.7047 3 400 18 22 32AT/160AF MCCB TPN 18.34 0.85 0.53 4C 25 Air 126 1 24 0.928 0.099 1 0.7 1 1 0.70 88.20 0.64 0.16 0.80
BUS A PVC

MAIN ACDB CU / XLPE /


MDP.A5 Q.A5 SUPPLY FOR INDOOR LIGHTING PANEL (ILP-2) 4.47 1.0 4.47 5.255 3 400 8 9 20 MCB TPN 7.59 0.85 0.53 4C 25 Air 126 1 25 0.928 0.099 1 0.7 1 1 0.70 88.20 0.28 0.07 0.80
BUS A PVC

MAIN ACDB SUPPLY FOR 125V DC NICAD BATTERY CHARGER- CU / XLPE /


MDP.A6 Q.A6 141.33 0.5 141.33 166.272 3 400 240 288 400AT/400AF MCCB TPN 240.00 0.85 0.53 4C 185 Air 416 1 23 0.130 0.088 1 0.7 1 1 0.70 291.20 1.50 0.38 4.20
BUS A 1. PVC

MAIN ACDB 200AMP,400V RECEPTACLE FOR OIL FILTRATION CU / XLPE /


MDP.A7 Q.A7 98.098 0 98.10 115.409 3 400 167 200 200AT/250AF MCCB TPN 166.58 0.85 0.53 4C 185 Duct 288 1 76 0.130 0.088 1 0.7 1 1 0.70 201.60 3.44 0.86 4.20
BUS A UNIT FOR POWER TRANSFORMERS AREA (T-01) PVC

MAIN ACDB 200AMP,400V RECEPTACLE FOR OIL FILTRATION CU / XLPE /


MDP.A8 Q.A8 98.098 0 98.10 115.409 3 400 167 200 200AT/250AF MCCB TPN 166.58 0.85 0.53 4C 185 Duct 288 1 84 0.130 0.088 1 0.7 1 1 0.70 201.60 3.81 0.95 4.20
BUS A UNIT FOR POWER TRANSFORMERS AREA (T-02 ) PVC

63AMP,400V WELDING & MAINTENANCE


MAIN ACDB CU / XLPE /
MDP.A9 Q.A9 RECEPTACLE FOR POWER TRANSFORMER AREA 30.05 0 30.05 35.3529 3 400 51 61 63AT/160AF MCCB TPN 51.03 0.85 0.53 4C 25 Duct 92 1 76 0.928 0.099 1 0.7 1 1 0.70 64.40 5.65 1.41 4.20
BUS A PVC
(T-01)
63AMP,400V WELDING & MAINTENANCE
MAIN ACDB CU / XLPE /
MDP.A10 Q.A10 RECEPTACLE FOR POWER TRANSFORMER AREA 30.05 0 30.05 35.3529 3 400 51 61 63AT/160AF MCCB TPN 51.03 0.85 0.53 4C 25 Duct 92 1 84 0.928 0.099 1 0.7 1 1 0.70 64.40 6.24 1.56 4.20
BUS A PVC
(T-02)
MAIN ACDB 63AMP,400V WELDING RECEPTACLE FOR CU / XLPE /
MDP.A11 Q.A11 30.05 0 30.05 35.3529 3 400 51 61 63AT/160AF MCCB TPN 51.03 0.85 0.53 4C 25 Duct 92 1 51 0.928 0.099 1 0.7 1 1 0.70 64.40 3.79 0.95 4.20
BUS A CAPACITOR BANKS AREA (CAP-01 & CAP-02 ) PVC

MAIN ACDB 63AMP,400V WELDING RECEPTACLE FOR CU / XLPE /


MDP.A12 Q.A12 30.05 0 30.05 35.3529 3 400 51 61 63AT/160AF MCCB TPN 51.03 0.85 0.53 4C 25 Duct 92 1 40 0.928 0.099 1 0.7 1 1 0.70 64.40 2.97 0.74 4.20
BUS A AUXILARY TRANSFORMERS (AUX-01 & AUX-02) PVC

MAIN ACDB 63AMP,400V WELDING RECEPTACLE FOR PACU CU / XLPE /


MDP.A13 Q.A13 30.50 0 30.50 35.8824 3 400 52 62 63AT/160AF MCCB TPN 51.79 0.85 0.53 4C 25 Air 126 1 60 0.928 0.099 1 0.7 1 1 0.70 88.20 4.52 1.13 4.20
BUS A UNITS (1A & 1B) ON THE ROOF. PVC

MAIN ACDB 40AMP,400V GAS FILLING RECEPTACLE-01 AT GIS CU / XLPE /


MDP.A14 Q.A14 19.00 0 19.00 22.3529 3 400 32 39 40AT/160AF MCCB TPN 32.26 0.85 0.53 4C 25 Air 126 1 87 0.928 0.099 1 0.7 1 1 0.70 88.20 4.09 1.02 4.20
BUS A ROOM. PVC

MAIN ACDB 40AMP,400V GAS FILLING RECEPTACLE-02 AT GIS CU / XLPE /


MDP.A15 Q.A15 19.00 0 19.00 22.3529 3 400 32 39 40AT/160AF MCCB TPN 32.26 0.85 0.53 4C 25 Air 126 1 80 0.928 0.099 1 0.7 1 1 0.70 88.20 3.76 0.94 4.20
BUS A ROOM. PVC

MAIN ACDB 400V,3PH SUPPLY-1 FOR EXTERNAL TELECOM CU / XLPE /


MDP.A16 Q.A16 34.05 0.50 34.05 40.0588 3 400 58 69 125AT/160AF MCCB TPN 57.82 0.85 0.53 4C 70 Duct 159 1 80 0.343 0.090 1 0.7 1 1 0.70 111.30 2.72 0.68 0.80
BUS A SHELTER PVC

MAIN ACDB
MDP.A17 Q.A17 SPARE 3 400 20 MCB TPN
BUS A

MAIN ACDB CU / XLPE /


MDP.A18 Q.A18 SUPPLY FOR HVAC CONTROL PANEL-1 29.44 0.05 29.44 34.6353 3 400 50 60 63AT/160AF MCCB TPN 49.99 0.85 0.53 4C 25 Air 126 1 16 0.928 0.099 1 0.7 1 1 0.70 88.20 1.16 0.29 4.20
BUS A PVC
Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying

MAIN ACDB
MDP.A19 Q.A19 SPARE 3 400 32AT/160AF MCCB TPN
BUS A

MAIN ACDB
MDP.A20 Q.A20 SPARE 3 400 40AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A21 Q.A21 SPARE 3 400 63AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A22 Q.A22 SPARE 3 400 63AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A23 Q.A23 SPARE 3 400 125AT/160AF MCCB TPN
BUS A
MAIN ACDB
MDP.A24 Q.A24 SPARE 3 400 160AT/250AF MCCB TPN
BUS A
MAIN ACDB
MDP.A25 Q.A25 SPARE 3 400 200AT/250AF MCCB TPN
BUS A
MAIN ACDB
MDP.A26 Q.A26 SPARE 3 400 400AT/400AF MCCB TPN
BUS A

400/230V, 1000A, 25kA(1s), 60Hz, 3PH 4WIRE MAIN ACDB-BUS B


MAIN ACDB SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU- CU / XLPE /
MDP.B1 Q.B1 97.00 0.5 97.00 114.118 3 400 164.72 197.6634 200AT/250AF MCCB TPN 164.72 0.85 0.53 4C 120 Air 317 1 60 0.198 0.087 1 0.7 1 1 0.70 221.90 3.66 0.91 4.20
BUS B 1B (STANDBY). PVC

MAIN ACDB SUPPLY FOR PACKAGE COMPRESSOR UNIT PACU- CU / XLPE /


MDP.B2 Q.B2 56.00 0.5 56.00 65.8824 3 400 95.096 114.1149 125AT/160AF MCCB TPN 95.10 0.85 0.53 4C 50 Air 173 1 45 0.494 0.092 1 0.7 1 1 0.70 121.10 3.47 0.87 4.20
BUS B 2A (DUTY). PVC

MAIN ACDB SUPPLY FOR SUB DISTRIBUTION PANEL-2 ( SDP- CU / XLPE /


MDP.B3 Q.B3 62.76 1 62.76 73.832 3 400 106.57 127.8844 160AT/250AF MCCB TPN 106.57 0.85 0.53 4C 70 Air 220 1 14 0.343 0.090 1 0.7 1 1 0.70 154.00 0.88 0.22 0.80
BUS B 2). PVC

MAIN ACDB CU / XLPE /


MDP.B4 Q.B4 SUPPLY FOR POWER RECEPTACLE PANEL 19.70 1 19.70 23.1765 3 400 33.453 40.144 50AT/160AF MCCB TPN 33.45 0.85 0.53 4C 25 Air 126 1 25 0.928 0.099 1 0.7 1 1 0.70 88.20 1.22 0.30 0.80
BUS B PVC

MAIN ACDB CU / XLPE /


MDP.B5 Q.B5 SUPPLY FOR OUTDOOR LIGHTING PANEL (OLP). 6.48 1 6.48 7.62235 3 400 11.002 13.20269 20 MCB TPN 11.00 0.85 0.53 4C 25 Air 126 1 15 0.928 0.099 1 0.7 1 1 0.70 88.20 0.24 0.06 0.80
BUS B PVC

MAIN ACDB SUPPLY FOR 125V DC NICAD BATTERY CHARGER- CU / XLPE /


MDP.B6 Q.B6 141.33 0.5 141.33 166.272 3 400 240 288 400AT/400AF MCCB TPN 240.00 0.85 0.53 4C 185 Air 416 1 26 0.130 0.088 1 0.7 1 1 0.70 291.20 1.70 0.42 4.20
BUS B 2. PVC

MAIN ACDB 200AMP,400V RECEPTACLE FOR OIL FILTRATION CU / XLPE /


MDP.B7 Q.B7 98.10 0 98.10 115.409 3 400 166.58 199.9008 200AT/250AF MCCB TPN 166.58 0.85 0.53 4C 185 Duct 288 1 76 0.130 0.088 1 0.7 1 1 0.70 201.60 3.44 0.86 4.20
BUS B UNIT FOR POWER TRANSFORMERS AREA (T-03) PVC

63AMP,400V WELDING & MAINTENANCE


MAIN ACDB CU / XLPE /
MDP.B8 Q.B8 RECEPTACLE FOR POWER TRANSFORMER AREA 30.05 0 30.05 35.3529 3 400 51.029 61.23489 63AT/160AF MCCB TPN 51.03 0.85 0.53 4C 25 Duct 92 1 76 0.928 0.099 1 0.7 1 1 0.70 64.40 5.65 1.41 4.20
BUS B PVC
(T-03)

MAIN ACDB 63AMP,400V WELDING RECEPTACLE FOR CU / XLPE /


MDP.B9 Q.B9 30.05 0 30.05 35.3529 3 400 51.029 61.23489 63AT/160AF MCCB TPN 51.03 0.85 0.53 4C 25 Duct 92 1 50 0.928 0.099 1 0.7 1 1 0.70 64.40 3.71 0.93 4.20
BUS B CAPACITOR BANKS AREA (CAP-03) PVC

MAIN ACDB 63AMP,400V WELDING RECEPTACLE FOR PACU CU / XLPE /


MDP.B10 Q.B10 30.50 0 30.50 35.8824 3 400 51.793 62.15188 63AT/160AF MCCB TPN 51.79 0.85 0.53 4C 25 Duct 92 1 45 0.928 0.099 1 0.7 1 1 0.70 64.40 3.39 0.85 4.20
BUS B UNITS (2A & 2B) ON THE ROOF. PVC

MAIN ACDB
MDP.B11 Q.B11 SPARE 0 3 400 63AT/160AF MCCB TPN
BUS B

MAIN ACDB 40AMP,400V GAS FILLING RECEPTACLE-03 AT GIS CU / XLPE /


MDP.B12 Q.B12 19.00 0 19.00 22.3529 3 400 32.265 38.71757 40AT/160AF MCCB TPN 32.26 0.85 0.53 4C 25 Air 126 1 70 0.928 0.099 1 0.7 1 1 0.70 88.20 3.29 0.82 4.20
BUS B ROOM. PVC

MAIN ACDB CU / XLPE /


MDP.B13 Q.B13 HV TEST BUSHING RECEPTACLES FOR GIS 61.29 0 61.29 72.1059 3 400 104.08 124.8947 125AT/160AF MCCB TPN 104.08 0.85 0.53 4C 120 Air 317 1 80 0.198 0.087 1 0.7 1 1 0.70 221.90 3.08 0.77 4.20
BUS B PVC

MAIN ACDB 400V,3PH SUPPLY-2 FOR EXTERNAL TELECOM CU / XLPE /


MDP.B14 Q.B14 30.50 0.5 30.50 35.8824 3 400 51.793 62.15188 125AT/160AF MCCB TPN 51.79 0.85 0.53 4C 70 Duct 159 1 80 0.343 0.090 1 0.7 1 1 0.70 111.30 2.43 0.61 0.80
BUS B SHELTER. PVC

MAIN ACDB
MDP.B15 Q.B15 SPARE 0 3 400 20 MCB TPN 1
BUS B

MAIN ACDB CU / XLPE /


MDP.B16 Q.B16 SUPPLY FOR HVAC CONTROL PANEL-2 29.44 0.05 29.44 34.6353 3 400 49.993 59.99185 63AT/160AF MCCB TPN 49.99 0.85 0.53 4C 25 Air 126 1 14 0.928 0.099 1 0.7 1 1 0.70 88.20 1.02 0.25 4.20
BUS B PVC

MAIN ACDB CU / XLPE /


MDP.B17 Q.B17 400V,3PH PORTABLE BATTERY CHARGER SUPPLY 30.50 0 30.50 35.8824 3 400 51.793 62.15188 63AT/160AF MCCB TPN 51.79 0.85 0.53 4C 25 Air 126 1 40 0.928 0.099 1 0.7 1 1 0.70 88.20 3.02 0.75 4.20
BUS B PVC

MAIN ACDB CU / XLPE /


MDP.B18 Q.B18 400V,3PH SUPPLY FOR EOT CRANE. 9.84 0 9.84 11.5765 3 400 16.71 20.05162 32AT/160AF MCCB TPN 16.71 0.85 0.53 4C 25 Air 126 1 90 0.928 0.099 1 0.7 1 1 0.70 88.20 2.19 0.55 4.20
BUS B PVC

MAIN ACDB CU / XLPE /


MDP.B19 Q.B19 400V,3PH SUPPLY FOR JIB CRANE. 9.84 0 9.84 11.5765 3 400 16.71 20.05162 32AT/160AF MCCB TPN 16.71 0.85 0.53 4C 10 Air 70 1 65 2.334 0.103 1 0.45 1 1 0.45 31.50 3.83 0.96 4.20
BUS B PVC
Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
MAIN ACDB
MDP.B20 Q.B20 SPARE 3 400 32AT/160AF MCCB TPN
BUS B

MAIN ACDB
MDP.B21 Q.B21 SPARE 3 400 40AT/160AF MCCB TPN
BUS B

MAIN ACDB
MDP.B22 Q.B22 SPARE 3 400 50AT/160AF MCCB TPN
BUS B

MAIN ACDB
MDP.B23 Q.B23 SPARE 3 400 63AT/160AF MCCB TPN
BUS B

MAIN ACDB
MDP.B24 Q.B24 SPARE 3 400 125AT/160AF MCCB TPN
BUS B

MAIN ACDB
MDP.B25 Q.B25 SPARE 3 400 160AT/250AF MCCB TPN
BUS B

MAIN ACDB
MDP.B26 Q.B26 SPARE 3 400 200AT/250AF MCCB TPN
BUS B

MAIN ACDB
MDP.B27 Q.B27 SPARE 3 400 400AT/400AF MCCB TPN
BUS B

400/230V, 160A, 25kA(1s), 60Hz, 3PH 4WIRE AC SDP-1(CONTROL ROOM)

MDP.A3 QC ACDB SUPPLY FOR AC SDP-1 70.48 1 70.48 82.92 3 400 119.68 143.62 160AT/250AF MCCB TPN

SDP.C1 Q.C1 SDP-1 SPARE 3 400 20 MCB TPN

SDP.C2 Q.C2 SDP-1 SPARE 3 400 20 MCB TPN

SDP.C3 Q.C3 SDP-1 SPARE 3 400 20 MCB TPN

SDP.C4 Q.C4 SDP-1 SPARE 3 400 20 MCB TPN

SDP.C5 Q.C5 SDP-1 SPARE 3 400 20 MCB TPN

SDP.C6 Q.C6 SDP-1 SPARE 3 400 32 MCB TPN

SDP.C7 Q.C7 SDP-1 SPARE 3 400 63AT/160AF MCCB TPN

400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-1 LCP CU / XLPE /


SDP.C8 Q.C8 SDP-1 26.739 0.5 26.74 31.46 3 400 45.41 54.49 63AT/160AF MCCB TPN 45.41 0.85 0.53 4C 25 Duct 92 1 95 0.928 0.099 1 0.7 1 1 0.70 64.40 6.28 1.57 3.40
(FANS , MK ) (MAIN) PVC

400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-2 LCP CU / XLPE /


SDP.C9 Q.C9 SDP-1 26.739 0.5 26.74 31.46 3 400 45.41 54.49 63AT/160AF MCCB TPN 45.41 0.85 0.53 4C 25 Duct 92 1 81 0.928 0.099 1 0.7 1 1 0.70 64.40 5.35 1.34 3.40
(FANS , MK ) (MAIN) PVC

400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-3 LCP CU / XLPE /


SDP.C10 Q.C10 SDP-1 26.739 0.5 26.74 31.46 3 400 45.41 54.49 63AT/160AF MCCB TPN 45.41 0.85 0.53 4C 25 Duct 92 1 78 0.928 0.099 1 0.7 1 1 0.70 64.40 5.16 1.29 3.40
(FANS , MK ) (STANDBY) PVC

400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-1 OLTC CU / XLPE /


SDP.C11 Q.C11 SDP-1 0.75 0 0.75 0.88 3 400 1.27 1.53 20 MCB TPN 1.27 0.85 0.53 4C 10 Duct 53 1 89 2.334 0.103 1 0.45 1 1 0.45 23.85 0.40 0.10 3.40
MOTOR DRIVE UNIT. PVC

400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-2 OLTC CU / XLPE /


SDP.C12 Q.C12 SDP-1 0.75 0 0.75 0.88 3 400 1.27 1.53 20 MCB TPN 1.27 0.85 0.53 4C 10 Duct 53 1 75 2.334 0.103 1 0.45 1 1 0.45 23.85 0.34 0.08 3.40
MOTOR DRIVE UNIT. PVC

400V 3PH SUPPLY-1 FOR 110/13.8 KV TR-3 OLTC CU / XLPE /


SDP.C13 Q.C13 SDP-1 0.75 0 0.75 0.88 3 400 1.27 1.53 20 MCB TPN 1.27 0.85 0.53 4C 10 Duct 53 1 85 2.334 0.103 1 0.45 1 1 0.45 23.85 0.38 0.10 3.40
MOTOR DRIVE UNIT. PVC

CU / XLPE /
SDP.C14 Q.C14 SDP-1 400V,AC SUPPLY FOR GIS ROOM EXHAUST FAN 2.33 0 2.33 2.74 3 400 3.96 4.75 20 MCB TPN 3.96 0.85 0.53 4C 10 Duct 53 1 95 2.334 0.103 1 0.45 1 1 0.45 23.85 1.33 0.33 3.40
PVC

400V, AC SUPPLY FOR FM-200- ROOM-01 EXHAUST CU / XLPE /


SDP.C15 Q.C15 SDP-1 0.24 0 0.24 0.28 3 400 0.41 0.49 20 MCB TPN 0.41 0.85 0.53 4C 10 Duct 53 1 52 2.334 0.103 1 0.45 1 1 0.45 23.85 0.07 0.02 3.40
FAN PVC

CU / XLPE /
SDP.C16 Q.C16 SDP-1 400V, AC SUPPLY FOR SECURITY SYSTEM 3.17 1 3.17 3.73 3 400 5.38 6.46 20 MCB TPN 5.38 0.85 0.53 4C 10 Air 70 1 30 2.334 0.103 1 0.45 1 1 0.45 31.50 0.57 0.14 3.40
PVC
Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
400V, AC SUPPLY FOR BASEMENT EXHAUST FAN CU / XLPE /
SDP.C17 Q.C17 SDP-1 2.24 1 2.24 2.64 3 400 3.80 4.56 20 MCB TPN 3.80 0.85 0.53 4C 10 Air 70 1 70 2.334 0.103 1 0.45 1 1 0.45 31.50 0.94 0.23 3.40
03 PVC

400V, AC SUPPLY FOR BASEMENT EXHAUST FAN CU / XLPE /


SDP.C18 Q.C18 SDP-1 2.24 1 2.24 2.64 3 400 3.80 4.56 20 MCB TPN 3.80 0.85 0.53 4C 10 Air 70 1 75 2.334 0.103 1 0.45 1 1 0.45 31.50 1.01 0.25 3.40
02 PVC

400V AC SUPPLY FOR SMOKE PURGE FAN-01 (SEF- CU / XLPE /


SDP.C19 Q.C19 SDP-1 3.60 0 3.60 4.24 3 400 6.11 7.34 20 MCB TPN 6.11 0.85 0.53 4C 4 Air 40 1 58 5.878 0.113 1 0.45 1 1 0.45 18.00 3.11 0.78 3.40
01) PVC

400V AC SUPPLY FOR SMOKE PURGE FAN-02 (SEF- CU / XLPE /


SDP.C20 Q.C20 SDP-1 3.19 0 3.19 3.75 3 400 5.42 6.50 20 MCB TPN 5.42 0.85 0.53 4C 4 Air 40 1 41 5.878 0.113 1 0.45 1 1 0.45 18.00 1.95 0.49 3.40
02) PVC

CU / XLPE /
SDP.C21 Q.C21 SDP-1 ELECTRICAL DUCT HEATER 10.00 0 10.00 10.00 3 400 14.43 17.32 20 MCB TPN 14.43 0.85 0.53 4C 4 Air 40 1 41 5.878 0.113 1 0.45 1 1 0.45 18.00 5.18 1.30 3.40
PVC

400V AC SUPPLY-1 FOR MISCELLANEOUS CU / XLPE /


SDP.C22 Q.C22 SDP-1 1.00 0.5 1.00 1.18 3 400 1.70 2.04 20 MCB TPN 1.70 0.85 0.53 4C 10 Air 70 1 100 2.334 0.103 1 0.45 1 1 0.45 31.50 0.60 0.15 3.40
PORTABLE TOOLS PVC

400V AC SUPPLY FOR HV GIS LCC E10 CU / XLPE /


SDP.C23 Q.C23 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 90 5.878 0.113 1 0.45 1 1 0.45 18.00 1.08 0.27 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E08 CU / XLPE /


SDP.C24 Q.C24 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 88 5.878 0.113 1 0.45 1 1 0.45 18.00 1.06 0.27 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E06 CU / XLPE /


SDP.C25 Q.C25 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 88 5.878 0.113 1 0.45 1 1 0.45 18.00 1.06 0.27 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E04 CU / XLPE /


SDP.C26 Q.C26 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 86 5.878 0.113 1 0.45 1 1 0.45 18.00 1.04 0.26 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E02 CU / XLPE /


SDP.C27 Q.C27 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 84 5.878 0.113 1 0.45 1 1 0.45 18.00 1.01 0.25 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E230 CU / XLPE /


SDP.C28 Q.C28 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 84 5.878 0.113 1 0.45 1 1 0.45 18.00 1.01 0.25 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E220 CU / XLPE /


SDP.C29 Q.C29 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 82 5.878 0.113 1 0.45 1 1 0.45 18.00 0.99 0.25 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E130 CU / XLPE /


SDP.C30 Q.C30 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 81 5.878 0.113 1 0.45 1 1 0.45 18.00 0.98 0.24 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E01 CU / XLPE /


SDP.C31 Q.C31 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 81 5.878 0.113 1 0.45 1 1 0.45 18.00 0.98 0.24 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E03 CU / XLPE /


SDP.C32 Q.C32 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 83 5.878 0.113 1 0.45 1 1 0.45 18.00 1.00 0.25 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E05 CU / XLPE /


SDP.C33 Q.C33 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 85 5.878 0.113 1 0.45 1 1 0.45 18.00 1.02 0.26 3.40
(HTR,LTNG,SCKT) PVC

400V AC SUPPLY FOR HV GIS LCC E07 CU / XLPE /


SDP.C34 Q.C34 SDP-1 0.81 0.06 0.81 0.95 3 400 1.38 1.65 20 MCB TPN 1.38 0.85 0.53 4C 4 Air 40 1 87 5.878 0.113 1 0.45 1 1 0.45 18.00 1.05 0.26 3.40
(HTR,LTNG,SCKT) PVC

230VAC SUPPLY FOR CONTROL ROOM PANELS


CU / XLPE /
SDP.C35 Q.C35 SDP-1 (HTR,LTNG,SCKT)( 1.0100 0.27 1.01 1.19 1 230 5.17 6.20 20 MCB SPN 5.17 0.85 0.53 2C 4 Air 48 1 20 5.878 0.113 1 0.45 1 1 0.45 21.60 1.04 0.45 3.40
PVC
+PSE,+CBP-3,+CBP-2,+CBP-1,+ACCS,+ABTS )
230VAC SUPPLY FOR CONTROL ROOM PANELS
CU / XLPE /
SDP.C36 Q.C36 SDP-1 (HTR,LTNG,SCKT)(BBA,BBB.BBCH,BBZ1,BBZ2,BBZ3 1.01 0.27 1.01 1.19 1 230 5.17 6.20 20 MCB SPN 5.17 0.85 0.53 2C 4 Air 48 1 20 5.878 0.113 1 0.45 1 1 0.45 21.60 1.04 0.45 3.40
PVC
)
230VAC SUPPLY FOR CONTROL ROOM PANELS
CU / XLPE /
SDP.C37 Q.C37 SDP-1 (HTR,LTNG,SCKT)(+3SYN,+UFP-1,+UVP-1,+UFP- 1.01 0.27 1.01 1.19 1 230 5.17 6.20 20 MCB SPN 5.17 0.85 0.53 2C 4 Air 48 1 14 5.878 0.113 1 0.45 1 1 0.45 21.60 0.73 0.32 3.40
PVC
2,UVP- 2)
230VAC SUPPLY FOR CONTROL ROOM
PANELS(HTR,LTNG,SCKT) CU / XLPE /
SDP.C38 Q.C38 SDP-1 1.47 0.27 1.47 1.73 1 230 7.52 9.02 20 MCB SPN 7.52 0.85 0.53 2C 4 Air 48 1 21 5.878 0.113 1 0.45 1 1 0.45 21.60 1.60 0.69 3.40
(+R07.2,+R07.1,+R10.2F,+R10.1F,FUT,FUT+R08.2,+R PVC
08.1)
230VAC SUPPLY FOR CONTROL ROOM
CU / XLPE /
SDP.C39 Q.C39 SDP-1 PANELS(HTR,LTNG,SCKT) 1.36 0.27 1.36 1.60 1 230 6.96 8.35 20 MCB SPN 6.96 0.85 0.53 2C 4 Air 48 1 21 5.878 0.113 1 0.45 1 1 0.45 21.60 1.48 0.64 3.40
PVC
(+R06.2,+R06.1,+R4.2,+R4.1,+R02.2,+R02.1)

230VAC SUPPLY FOR CONTROL ROOM CU / XLPE /


SDP.C40 Q.C40 SDP-1 0.49 0.27 0.49 0.58 1 230 2.50 3.00 20 MCB SPN 2.50 0.85 0.53 2C 4 Air 48 1 19 5.878 0.113 1 0.45 1 1 0.45 21.60 0.48 0.21 3.40
PANELS(HTR,LTNG,SCKT) (+R230,+R220,+R130) PVC
Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
230VAC SUPPLY FOR CONTROL ROOM
PANELS(HTR,LTNG,SCKT) CU / XLPE /
SDP.C41 Q.C41 SDP-1 1.47 0.27 1.47 1.73 1 230 7.52 9.02 20 MCB SPN 7.52 0.85 0.53 2C 4 Air 48 1 20 5.878 0.113 1 0.45 1 1 0.45 21.60 1.52 0.66 3.40
(+R01.2,+R01.1,+R03.2,+R03.1,+R05.2,+R05.1,FUT,F PVC
UT)
230V AC SUPPLY-1 FOR TR-1 OLTC LIGHTING & CU / XLPE /
SDP.C42 Q.C42 SDP-1 0.37 0.5 0.37 0.44 1 230 1.89 2.27 20 MCB SPN 1.89 0.85 0.53 2C 4 Air 48 1 89 5.878 0.113 1 0.45 1 1 0.45 21.60 1.70 0.74 3.40
HEATER. PVC

230V AC SUPPLY-1 FOR TR-2 OLTC LIGHTING & CU / XLPE /


SDP.C43 Q.C43 SDP-1 0.37 0.5 0.37 0.44 1 230 1.89 2.27 20 MCB SPN 1.89 0.85 0.53 2C 4 Air 48 1 75 5.878 0.113 1 0.45 1 1 0.45 21.60 1.44 0.62 3.40
HEATER. PVC

230V AC SUPPLY-1 FOR TR-3 OLTC LIGHTING & CU / XLPE /


SDP.C44 Q.C44 SDP-1 0.37 0.5 0.37 0.44 1 230 1.89 2.27 20 MCB SPN 1.89 0.85 0.53 2C 4 Duct 38 1 85 5.878 0.113 1 0.45 1 1 0.45 17.10 1.63 0.71 3.40
HEATER. PVC

230VAC SUPPLY 13.8KV SWGR. PANELS OF CU / XLPE /


SDP.C45 Q.C45 SDP-1 4.94 1 4.94 5.81 1 230 25.24 30.29 32 MCB SPN 25.24 0.85 0.53 2C 10 Air 82 1 45 2.334 0.103 1 0.45 1 1 0.45 36.90 4.63 2.01 3.40
SECTION-1 (AH01 TO AH18) PVC

230VAC SUPPLY 13.8KV SWGR. PANELS OF CU / XLPE /


SDP.C46 Q.C46 SDP-1 4.610 1 4.61 5.42 1 230 23.58 28.30 32 MCB SPN 23.58 0.85 0.53 2C 10 Air 82 1 30 2.334 0.103 1 0.45 1 1 0.45 36.90 2.88 1.25 3.40
SECTION-2 (AH19 TO AH36) PVC

230VAC SUPPLY 13.8KV SWGR. PANELS OF CU / XLPE /


SDP.C47 Q.C47 SDP-1 4.840 1 4.84 5.69 1 230 24.76 29.71 32 MCB SPN 24.76 0.85 0.53 2C 10 Air 82 1 47 2.334 0.103 1 0.45 1 1 0.45 36.90 4.74 2.06 3.40
SECTION-3 (AH37 TO AH53) HTR,LTNG,SCKT) PVC

SDP.C48 Q.C48 SDP-1 230VAC SUPPLY FOR FUTURE PANELS 0.00 0.00 1 230 20 MCB SPN

SDP.C49 Q.C49 SDP-1 230VAC SUPPLY FOR FUTURE PANELS 0.00 0.00 1 230 20 MCB SPN

230VAC SUPPLY-1 FOR SAS PANELS ROW CU / XLPE /


SDP.C50 Q.C50 SDP-1 0.87 0.27 0.87 1.02 1 230 4.45 5.34 20 MCB SPN 4.45 0.85 0.53 2C 4 Air 48 1 23 5.878 0.113 1 0.45 1 1 0.45 21.60 1.04 0.45 3.40
(HTR,LTNG,SCKT) PVC

230VAC SUPPLY FOR COMMUNICATION PANELS CU / XLPE /


SDP.C51 Q.C51 SDP-1 2.00 1.00 2.00 2.35 1 230 10.23 12.28 20 MCB SPN 10.23 0.85 0.53 2C 4 Air 48 1 16 5.878 0.113 1 0.45 1 1 0.45 21.60 1.66 0.72 3.40
(LAN/WAN , SDH , DDF,DVM,MDF) PVC

230VAC SUPPLY FOR COMMUNICATION PANELS CU / XLPE /


SDP.C52 Q.C52 SDP-1 2.00 1.00 2.00 2.35 1 230 10.23 12.28 20 MCB SPN 10.23 0.85 0.53 2C 4 Air 48 1 14 5.878 0.113 1 0.45 1 1 0.45 21.60 1.45 0.63 3.40
(MCP , N01 ,N02,DC-DC CONVERTER -1&2) PVC

230V AC SUPPLY FOR BATTERY ROOM EXHAUST CU / XLPE /


SDP.C53 Q.C53 SDP-1 0.35 1.00 0.35 0.41 1 230 1.80 2.15 20 MCB SPN 1.80 0.85 0.53 2C 4 Air 48 1 27 5.878 0.113 1 0.45 1 1 0.45 21.60 0.49 0.21 3.40
FAN. PVC

230V,1PH SUPPLY FM-200 RELEASING PANEL - CU / XLPE /


SDP.C54 Q.C54 SDP-1 0.39 0.00 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 31 5.878 0.113 1 0.45 1 1 0.45 21.60 0.63 0.27 3.40
CONTROL ROOM - FIRST FLOOR PVC

230V,1PH SUPPLY FM-200 RELEASING PANEL - CU / XLPE /


SDP.C55 Q.C55 SDP-1 0.39 0.00 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 22 5.878 0.113 1 0.45 1 1 0.45 21.60 0.44 0.19 3.40
COMMUNICATION ROOM -FIRST FLOOR PVC

230V,1PH SUPPLY FM-200 RELEASING PANEL - CU / XLPE /


SDP.C56 Q.C56 SDP-1 0.39 0.00 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 33 5.878 0.113 1 0.45 1 1 0.45 21.60 0.67 0.29 3.40
BATTERY ROOM -FIRST FLOOR PVC

230V,1PH SUPPLY FM-200 RELEASING PANEL - MV CU / XLPE /


SDP.C57 Q.C57 SDP-1 0.39 0.00 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 48 5.878 0.113 1 0.45 1 1 0.45 21.60 0.97 0.42 3.40
SWITCHGEAR ROOM -GROUND FLOOR PVC
230V,1PH SUPPLY FM-200 RELEASING PANEL -
CU / XLPE /
SDP.C58 Q.C58 SDP-1 LCC CUBICLES - GIS HALL-GROUND FLOOR- 0.39 0.00 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 46 5.878 0.113 1 0.45 1 1 0.45 21.60 0.93 0.40 3.40
PVC
SYSTEM#1
230V,1PH SUPPLY FM-200 RELEASING PANEL -
CU / XLPE /
SDP.C59 Q.C59 SDP-1 LCC CUBICLES - GIS HALL-GROUND FLOOR- 0.39 0.00 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 48 5.878 0.113 1 0.45 1 1 0.45 21.60 0.97 0.42 3.40
PVC
SYSTEM#2
230V,1PH SUPPLY FM-200 RELEASING PANEL -
CU / XLPE /
SDP.C60 Q.C60 SDP-1 LCC CUBICLES - GIS HALL-GROUND FLOOR- 0.39 0.00 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 50 5.878 0.113 1 0.45 1 1 0.45 21.60 1.01 0.44 3.40
PVC
SYSTEM#3
230V,1PH SUPPLY FM-200 RELEASING PANEL -
CU / XLPE /
SDP.C61 Q.C61 SDP-1 LCC CUBICLES - GIS HALL-GROUND FLOOR- 0.39 0.00 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 51 5.878 0.113 1 0.45 1 1 0.45 21.60 1.03 0.45 3.40
PVC
SYSTEM#4
CU / XLPE /
SDP.C62 Q.C62 SDP-1 230V AC SUPPLY FOR GATE MOTOR-1 1.00 0.00 1.00 1.18 1 230 5.12 6.14 20 MCB SPN 5.12 0.85 0.53 2C 4 Air 48 1 95 5.878 0.113 1 0.45 1 1 0.45 21.60 4.91 2.14 3.40
PVC

CU / XLPE /
SDP.C63 Q.C63 SDP-1 230V AC SUPPLY FOR BASEMENT SUMP PUMP-1 1.30 0.00 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 32 5.878 0.113 1 0.45 1 1 0.45 21.60 2.15 0.94 3.40
PVC

CU / XLPE /
SDP.C64 Q.C64 SDP-1 230V AC SUPPLY FOR BASEMENT SUMP PUMP-2 1.30 0.00 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 35 5.878 0.113 1 0.45 1 1 0.45 21.60 2.35 1.02 3.40
PVC

CU / XLPE /
SDP.C65 Q.C65 SDP-1 230V AC SUPPLY FOR BASEMENT SUMP PUMP-3 1.30 0.00 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 65 5.878 0.113 1 0.45 1 1 0.45 21.60 4.37 1.90 3.40
PVC

CU / XLPE /
SDP.C66 Q.C66 SDP-1 230V AC SUPPLY FOR BASEMENT SUMP PUMP-4 1.30 0.00 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 74 5.878 0.113 1 0.45 1 1 0.45 21.60 4.97 2.16 3.40
PVC
Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying

SDP.C67 Q.C67 SDP-1 SPARE 1 230 20 MCB SPN

SDP.C68 Q.C68 SDP-1 SPARE 1 230 20 MCB SPN

SDP.C69 Q.C69 SDP-1 SPARE 1 230 20 MCB SPN

SDP.C70 Q.C70 SDP-1 SPARE 1 230 20 MCB SPN

SDP.C71 Q.C71 SDP-1 SPARE 1 230 20 MCB SPN

SDP.C72 Q.C72 SDP-1 SPARE 1 230 20 MCB SPN

400/230V, 160A, 25kA(1s), 60Hz, 3PH 4WIRE AC SDP-2(CONTROL ROOM)

MDP.B3 QD ACDB SUPPLY FOR SDP-2 62.76 1 62.76 73.83 3 400 106.57 127.88 160AT/250AF MCCB TPN

SDP.D1 QD.1 SDP-2 SPARE 3 400 20 MCB TPN

SDP.D2 QD.2 SDP-2 SPARE 3 400 20 MCB TPN

SDP.D3 QD.3 SDP-2 SPARE 3 400 32 MCB TPN

SDP.D4 QD.4 SDP-2 SPARE 3 400 20 MCB TPN

SDP.D5 QD.5 SDP-2 SPARE 3 400 20 MCB TPN

SDP.D6 QD.6 SDP-2 SPARE 3 400 63AT/160AF MCCB TPN

400V 3PH SUPPLY-2 FOR TR-1 LCP(FANS,MK) CU / XLPE /


SDP.D7 QD.7 SDP-2 26.739 0.5 26.74 31.46 3 400 45.41 54.49 63AT/160AF MCCB TPN 45.41 0.85 0.53 4C 25 Duct 92 1 96 0.928 0.099 1 0.7 1 1 0.70 64.40 6.35 1.59 3.40
(STAND-BY). PVC

400V 3PH SUPPLY-2 FOR TR-2 LCP(FANS,MK) CU / XLPE /


SDP.D8 QD.8 SDP-2 26.739 0.5 26.74 31.46 3 400 45.41 54.49 63AT/160AF MCCB TPN 45.41 0.85 0.53 4C 25 Duct 92 1 82 0.928 0.099 1 0.7 1 1 0.70 64.40 5.42 1.36 3.40
(STAND-BY). PVC

400V 3PH SUPPLY-2 FOR TR-3 LCP(FANS,MK) CU / XLPE /


SDP.D9 QD.9 SDP-2 26.739 0.5 26.74 31.46 3 400 45.41 54.49 63AT/160AF MCCB TPN 45.41 0.85 0.53 4C 25 Duct 92 1 79 0.928 0.099 1 0.7 1 1 0.70 64.40 5.22 1.31 3.40
(MAIN). PVC

400V 3PH SUPPLY-2 FOR TR-1 OLTC MOTOR CU / XLPE /


SDP.D10 QD.10 SDP-2 0.75 0 0.75 0.88 3 400 1.27 1.53 20 MCB TPN 1.27 0.85 0.53 4C 10 Duct 53 1 90 2.334 0.103 1 0.45 1 1 0.45 23.85 0.40 0.10 3.40
DRIVE UNIT. PVC

400V 3PH SUPPLY-2 FOR TR-2 OLTC MOTOR CU / XLPE /


SDP.D11 QD.11 SDP-2 0.75 0 0.75 0.88 3 400 1.27 1.53 20 MCB TPN 1.27 0.85 0.53 4C 10 Duct 53 1 76 2.334 0.103 1 0.45 1 1 0.45 23.85 0.34 0.09 3.40
DRIVE UNIT. PVC

400V 3PH SUPPLY-2 FOR TR-3 OLTC MOTOR CU / XLPE /


SDP.D12 QD.12 SDP-2 0.75 0 0.75 0.88 3 400 1.27 1.53 20 MCB TPN 1.27 0.85 0.53 4C 10 Duct 53 1 86 2.334 0.103 1 0.45 1 1 0.45 23.85 0.39 0.10 3.40
DRIVE UNIT. PVC

400VAC SUPPLY FOR FAX/TELEPHONE CU / XLPE /


SDP.D13 QD.13 SDP-2 5.00 1 5.00 5.88 3 400 8.49 10.19 20 MCB TPN 8.49 0.85 0.53 4C 10 Air 70 1 34 2.334 0.103 1 0.45 1 1 0.45 31.50 1.02 0.25 3.40
EXCHANGE. PVC

400V AC SUPPLY FOR MISCELLANEOUS CU / XLPE /


SDP.D14 QD.14 SDP-2 1.00 0.5 1.00 1.18 3 400 1.70 2.04 20 MCB TPN 1.70 0.85 0.53 4C 10 Air 70 1 100 2.334 0.103 1 0.45 1 1 0.45 31.50 0.60 0.15 3.40
PORTABLE SUPPLY-2 PVC

400V,AC SUPPLY 01 FOR SPLIT UNIT(WORKSHOP CU / XLPE /


SDP.D15 QD.15 SDP-2 3.50 1 3.50 4.12 3 400 5.94 7.13 20 MCB TPN 5.94 0.85 0.53 4C 10 Air 70 1 59 2.334 0.103 1 0.45 1 1 0.45 31.50 1.24 0.31 3.40
AND RECORD ROOM) PVC

CU / XLPE /
SDP.D16 QD.16 SDP-2 400 VAC SUPPLY FOR (DCDB-1 ) PANELS 0.42 0.5 0.42 0.49 3 400 0.71 0.86 20 MCB TPN 0.71 0.85 0.53 4C 4 Air 40 1 31 5.878 0.113 1 0.45 1 1 0.45 18.00 0.19 0.05 3.40
PVC

CU / XLPE /
SDP.D17 QD.17 SDP-2 400 VAC SUPPLY FOR (DCDB-2 ) PANELS 0.4 0.5 0.42 0.49 3 400 0.71 0.86 20 MCB TPN 0.71 0.85 0.53 4C 4 Air 40 1 30 5.878 0.113 1 0.45 1 1 0.45 18.00 0.19 0.05 3.40
PVC
Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
CU / XLPE /
SDP.D18 QD.18 SDP-2 400 VAC SUPPLY FOR (DCDB ) PANEL 0.4 0.5 0.42 0.49 3 400 0.71 0.86 20 MCB TPN 0.71 0.85 0.53 4C 4 Air 40 1 29 5.878 0.113 1 0.45 1 1 0.45 18.00 0.18 0.05 3.40
PVC

400V,AC SUPPLY FOR BASEMENT EXHAUST FAN CU / XLPE /


SDP.D19 QD.19 SDP-2 2.25 1 2.25 2.65 3 400 3.82 4.58 20 MCB TPN 3.82 0.85 0.53 4C 4 Air 40 1 75 5.878 0.113 1 0.45 1 1 0.45 18.00 2.51 0.63 3.40
01 PVC

400V AC SUPPLY FOR SECURITY SYSTEM UPS IN CU / XLPE /


SDP.D20 QD.20 SDP-2 0.32 1 0.32 0.38 3 400 0.54 0.65 32 MCB TPN 0.54 0.85 0.53 4C 4 Air 40 1 22 5.878 0.113 1 0.45 1 1 0.45 18.00 0.10 0.03 3.40
CONTROL ROOM PVC

400V,AC SUPPLY 02 FOR SPLIT UNIT(WORKSHOP CU / XLPE /


SDP.D21 QD.21 SDP-2 3.50 1 3.50 4.12 3 400 5.94 7.13 20 MCB TPN 5.94 0.85 0.53 4C 4 Air 40 1 55 5.878 0.113 1 0.45 1 1 0.45 18.00 2.86 0.72 3.40
AND RECORD ROOM) PVC

400V AC SUPPLY FOR T01 TRANSFORMER PIT CU / XLPE /


SDP.D22 QD.22 SDP-2 2.00 0.0 2.00 2.35 3 400 3.40 4.08 20 MCB TPN 3.40 0.85 0.53 4C 4 Air 40 1 98 5.878 0.113 1 0.45 1 1 0.45 18.00 2.91 0.73 3.40
PUMP-1. PVC

400V AC SUPPLY FOR T02 TRANSFORMER PIT CU / XLPE /


SDP.D23 QD.23 SDP-2 2.00 0.0 2.00 2.35 3 400 3.40 4.08 20 MCB TPN 3.40 0.85 0.53 4C 4 Air 40 1 85 5.878 0.113 1 0.45 1 1 0.45 18.00 2.53 0.63 3.40
PUMP-2. PVC

400V AC SUPPLY FOR T03 TRANSFORMER PIT CU / XLPE /


SDP.D24 QD.24 SDP-2 2.00 0.0 2.00 2.35 3 400 3.40 4.08 20 MCB TPN 3.40 0.85 0.53 4C 4 Air 40 1 79 5.878 0.113 1 0.45 1 1 0.45 18.00 2.35 0.59 3.40
PUMP-3. PVC

400V AC SUPPLY FOR AUXILIARY TRANSFORMER- CU / XLPE /


SDP.D25 QD.25 SDP-2 2.00 0.0 2.00 2.35 3 400 3.40 4.08 20 MCB TPN 3.40 0.85 0.53 4C 4 Air 40 1 38 5.878 0.113 1 0.45 1 1 0.45 18.00 1.13 0.28 3.40
1 PIT PUMP. PVC

400V AC SUPPLY FOR AUXILIARY TRANSFORMER- CU / XLPE /


SDP.D26 QD.26 SDP-2 2.00 0.0 2.00 2.35 3 400 3.40 4.08 20 MCB TPN 3.40 0.85 0.53 4C 4 Air 40 1 40 5.878 0.113 1 0.45 1 1 0.45 18.00 1.19 0.30 3.40
2 PIT PUMP. PVC

CU / XLPE /
SDP.D27 QD.27 SDP-2 400V AC SUPPLY FOR WATER BOOSTER PUMP. 2.50 0 2.50 2.94 3 400 4.25 5.09 20 MCB TPN 4.25 0.85 0.53 4C 4 Air 40 1 50 5.878 0.113 1 0.45 1 1 0.45 18.00 1.86 0.465 3.40
PVC
230VAC SUPPLY FOR CONTROL ROOM PANELS
CU / XLPE /
SDP.D28 QD.28 SDP-2 (HTR,LTNG,SCKT)(+RTM-1,+RTM-2,+RTM-3,+RTM- 1.01 0.27 1.01 1.19 1 230 5.17 6.20 20 MCB SPN 5.17 0.85 0.53 2C 4 Air 48 1 19 5.878 0.113 1 0.45 1 1 0.45 21.60 0.99 0.432 3.40
PVC
4,+RTM-5,+RTM-6)
CU / XLPE /
SDP.D29 QD.29 SDP-2 230V,AC SUPPLY FOR KITCHEN EXHAUST FAN 0.02 0 0.02 0.03 1 230 0.11 0.14 20 MCB SPN 0.11 0.85 0.53 2C 4 Air 48 1 34 5.878 0.113 1 0.45 1 1 0.45 21.60 0.04 0.02 3.40
PVC

230V AC SUPPLY FOR MFACB PANELS & CU / XLPE /


SDP.D30 QD.30 SDP-2 0.68 0.27 0.68 0.81 1 230 3.50 4.20 20 MCB SPN 3.50 0.85 0.53 2C 4 Air 48 1 28 5.878 0.113 1 0.45 1 1 0.45 21.60 0.99 0.43 3.40
PRINTERS PVC

230VAC SUPPLY FOR CONTROL ROOM PANELS CU / XLPE /


SDP.D31 QD.31 SDP-2 0.81 0.27 0.81 0.95 1 230 4.14 4.97 20 MCB SPN 4.14 0.85 0.53 2C 4 Air 48 1 20 5.878 0.113 1 0.45 1 1 0.45 21.60 0.84 0.36 3.40
(HTR,LTNG,SCKT)(RTCC-1,RTCC-2,RTCC-3) PVC

230V AC SUPPLY FOR WATER HEATER FOR CU / XLPE /


SDP.D32 QD.32 SDP-2 2.00 0 2.00 2.35 1 230 10.23 12.28 20 MCB SPN 10.23 0.85 0.53 2C 4 Air 48 1 28 5.878 0.113 1 0.45 1 1 0.45 21.60 2.90 1.26 3.40
TOILET. PVC

CU / XLPE /
SDP.D33 QD.33 SDP-2 230V AC SUPPLY FOR TOILET EXHAUST FAN 0.13 0 0.13 0.16 1 230 0.68 0.81 20 MCB SPN 0.68 0.85 0.53 2C 4 Duct 38 1 30 5.878 0.113 1 0.45 1 1 0.45 17.10 0.20 0.09 3.40
PVC

CU / XLPE /
SDP.D34 QD.34 SDP-2 230V AC SUPPLY FOR WATER TRANSFER PUMP 1.10 0 1.10 1.29 1 230 5.63 6.75 20 MCB SPN 5.63 0.85 0.53 2C 10 Duct 63 1 48 2.334 0.103 1 0.45 1 1 0.45 28.35 1.10 0.48 3.40
PVC

230V AC SUPPLY FOR CONTROL ROOM


CU / XLPE /
SDP.D35 QD.35 SDP-2 WORKSTATION (PC'S, MONITORS, 2.00 1 2.00 2.35 1 230 10.23 12.28 20 MCB SPN 10.23 0.85 0.53 2C 4 Air 48 1 31 5.878 0.113 1 0.45 1 1 0.45 21.60 3.21 1.39 3.40
PVC
PRINTERS…..ETC).
230VAC SUPPLY FOR CONTROL ROOM PANELS CU / XLPE /
SDP.D36 QD.36 SDP-2 1.01 0.27 1.01 1.19 1 230 5.17 6.20 20 MCB SPN 5.17 0.85 0.53 2C 4 Air 48 1 32 5.878 0.113 1 0.45 1 1 0.45 21.60 1.67 0.73 3.40
(HTR,LTNG,SCKT)(ILPB,ILP,ELP,DCU,RMR,DDR) PVC
230VAC SUPPLY FOR CONTROL ROOM PANELS
CU / XLPE /
SDP.D37 QD.37 SDP-2 (HTR,LTNG,SCKT)(MAIN ACDB,PP-1,PP- 1.01 0.27 1.01 1.19 1 230 5.17 6.20 20 MCB SPN 5.17 0.85 0.53 2C 4 Air 48 1 18 5.878 0.113 1 0.45 1 1 0.45 21.60 0.94 0.41 3.40
PVC
2,OLP,HVAC1,HVAC2)
230VAC SUPPLY FOR CONTROL ROOM PANELS CU / XLPE /
SDP.D38 QD.38 SDP-2 1.01 0.27 1.01 1.19 1 230 5.17 6.20 20 MCB SPN 5.17 0.85 0.53 2C 4 Air 48 1 27 5.878 0.113 1 0.45 1 1 0.45 21.60 1.41 0.61 3.40
(HTR,LTNG,SCKT)(G12,G11,FUT,FUT,FUT,FUT) PVC

CU / XLPE /
SDP.D39 QD.39 SDP-2 230VAC SUPPLY-1 FOR AMI (RMR PANEL) 0.42 0.27 0.42 0.49 1 230 2.15 2.58 20 MCB SPN 2.15 0.85 0.53 2C 4 Air 48 1 21 5.878 0.113 1 0.45 1 1 0.45 21.60 0.46 0.20 3.40
PVC
Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying
CU / XLPE /
SDP.D40 QD.40 SDP-2 230VAC SUPPLY-1 FOR AMI (SWITCH PANEL) 0.42 0.27 0.42 0.49 1 230 2.15 2.58 20 MCB SPN 2.15 0.85 0.53 2C 4 Air 48 1 22 5.878 0.113 1 0.45 1 1 0.45 21.60 0.48 0.21 3.40
PVC

230VAC SUPPLY-1 FOR SAS PANELS ROW CU / XLPE /


SDP.D41 QD.41 SDP-2 0.98 0.27 0.98 1.15 1 230 5.01 6.02 20 MCB SPN 5.01 0.85 0.53 2C 4 Air 48 1 25 5.878 0.113 1 0.45 1 1 0.45 21.60 1.27 0.55 3.40
(HTR,LTNG,SCKT) PVC

230V,AC SUPPLY FOR FM-200-ROOM-02 EXHAUST CU / XLPE /


SDP.D42 QD.42 SDP-2 2.25 0 2.25 2.65 1 230 11.51 13.81 20 MCB SPN 11.51 0.85 0.53 2C 10 Air 82 1 35 2.334 0.103 1 0.45 1 1 0.45 36.90 1.64 0.71 3.40
FAN PVC

230V,AC SUPPLY FOR FM-200-ROOM-03 EXHAUST CU / XLPE /


SDP.D43 QD.43 SDP-2 2.25 0 2.25 2.65 1 230 11.51 13.81 20 MCB SPN 11.51 0.85 0.53 2C 10 Air 82 1 21 2.334 0.103 1 0.45 1 1 0.45 36.90 0.98 0.43 3.40
FAN PVC

230V,1PH SUPPLY FM-200 RELEASING PANEL - MV CU / XLPE /


SDP.D44 QD.44 SDP-2 0.39 0 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 49 5.878 0.113 1 0.45 1 1 0.45 21.60 0.99 0.43 3.40
SWITCHGEAR BASEMENT PVC

230V,1PH SUPPLY FM-200 RELEASING PANEL - HV CU / XLPE /


SDP.D45 QD.45 SDP-2 0.39 0 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 53 5.878 0.113 1 0.45 1 1 0.45 21.60 1.07 0.47 3.40
GIS BASEMENT PVC

230V,1PH SUPPLY FM-200 RELEASING PANEL - CU / XLPE /


SDP.D46 QD.46 SDP-2 0.39 0 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 54 5.878 0.113 1 0.45 1 1 0.45 21.60 1.09 0.47 3.40
CABLE CORRIDOR-BASEMENT PVC

230V,1PH SUPPLY FM-200 RELEASING PANEL -


CU / XLPE /
SDP.D47 QD.47 SDP-2 COMMUNICATION ROOM - EXTERNAL TELECOM 0.39 0 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 50 5.878 0.113 1 0.45 1 1 0.45 21.60 1.01 0.44 3.40
PVC
SHELTER
230V,1PH SUPPLY FM-200 RELEASING PANEL - CU / XLPE /
SDP.D48 QD.48 SDP-2 0.39 0 0.39 0.46 1 230 2.00 2.40 20 MCB SPN 2.00 0.85 0.53 2C 4 Air 48 1 53 5.878 0.113 1 0.45 1 1 0.45 21.60 1.07 0.47 3.40
BATTERY ROOM - EXTERNAL TELECOM SHELTER PVC

CU / XLPE /
SDP.D49 QD.49 SDP-2 230V AC SUPPLY FOR BASEMENT SUMP PUMP-5 1.30 0 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 82 5.878 0.113 1 0.45 1 1 0.45 21.60 5.51 2.40 3.40
PVC

CU / XLPE /
SDP.D50 QD.50 SDP-2 230V AC SUPPLY FOR BASEMENT SUMP PUMP-6 1.30 0 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 71 5.878 0.113 1 0.45 1 1 0.45 21.60 4.77 2.08 3.40
PVC

CU / XLPE /
SDP.D51 QD.51 SDP-2 230V AC SUPPLY FOR BASEMENT SUMP PUMP-7 1.30 0 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 65 5.878 0.113 1 0.45 1 1 0.45 21.60 4.37 1.90 3.40
PVC

CU / XLPE /
SDP.D52 QD.52 SDP-2 230V AC SUPPLY FOR BASEMENT SUMP PUMP-8 1.30 0 1.30 1.53 1 230 6.65 7.98 20 MCB SPN 6.65 0.85 0.53 2C 4 Air 48 1 77 5.878 0.113 1 0.45 1 1 0.45 21.60 5.18 2.25 3.40
PVC

CU / XLPE /
SDP.D53 QD.53 SDP-2 230V AC SUPPLY FOR HAND DRYER 1.28 1 1.28 1.51 1 230 6.55 7.86 20 MCB SPN 6.55 0.85 0.53 2C 4 Air 48 1 30 5.878 0.113 1 0.45 1 1 0.45 21.60 1.99 0.86 3.40
PVC

CU / XLPE /
SDP.D54 QD.54 SDP-2 230V AC SUPPLY FOR GATE MOTOR-2 1.00 0 1.00 1.18 1 230 5.12 6.14 20 MCB SPN 5.12 0.85 0.53 2C 4 Air 48 1 100 5.878 0.113 1 0.45 1 1 0.45 21.60 5.17 2.25 3.40
PVC

230V AC SUPPLY FOR LCC'S ANNUNCIATION CU / XLPE /


SDP.D55 QD.55 SDP-2 3.00 0.18 3.00 3.53 1 230 15.35 18.41 20 MCB SPN 15.35 0.85 0.53 2C 6 Air 61 1 65 3.927 0.106 1 0.45 1 1 0.45 27.45 6.77 2.94 3.40
SYSTEM PVC

230V,1PH SUPPLY FOR PARTIAL DISCHARGE CU / XLPE /


SDP.D56 QD.56 SDP-2 0.14 1.00 0.14 0.16 1 230 0.72 0.86 20 MCB SPN 0.72 0.85 0.53 2C 4 Air 48 1 75 5.878 0.113 1 0.45 1 1 0.45 21.60 0.54 0.24 3.40
MONITORING SYSTEM(PDMS) PVC

230V,1PH SUPPLY FOR ROLLING SHUTTER CU / XLPE /


SDP.D57 QD.57 SDP-2 2.00 0.00 2.00 2.35 1 230 10.23 12.28 20 MCB SPN 10.23 0.85 0.53 2C 6 Air 61 1 85 3.927 0.106 1 0.45 1 1 0.45 27.45 5.90 2.57 3.40
MOTOR DOOR PVC

230V AC SUPPLY-2 FOR TR-1 OLTC LIGHTING & CU / XLPE /


SDP.D58 QD.58 SDP-2 0.37 0.50 0.37 0.44 1 230 1.89 2.27 20 MCB SPN 1.89 0.85 0.53 2C 4 Air 48 1 90 5.878 0.113 1 0.45 1 1 0.45 21.60 1.72 0.75 3.40
HEATER. PVC

230V AC SUPPLY-2 FOR TR-2 OLTC LIGHTING & CU / XLPE /


SDP.D59 QD.59 SDP-2 0.37 0.50 0.37 0.44 1 230 1.89 2.27 20 MCB SPN 1.89 0.85 0.53 2C 4 Air 48 1 76 5.878 0.113 1 0.45 1 1 0.45 21.60 1.45 0.63 3.40
HEATER. PVC

230V AC SUPPLY-2 FOR TR-3 OLTC LIGHTING & CU / XLPE /


SDP.D60 QD.60 SDP-2 0.37 0.50 0.37 0.44 1 230 1.89 2.27 20 MCB SPN 1.89 0.85 0.53 2C 4 Air 48 1 86 5.878 0.113 1 0.45 1 1 0.45 21.60 1.65 0.72 3.40
HEATER. PVC

230V AC SUPPLY FOR TR-1 ONLINE CU / XLPE /


SDP.D61 QD.61 SDP-2 0.15 1.00 0.15 0.18 1 230 0.77 0.92 20 MCB SPN 0.77 0.85 0.53 2C 4 Duct 38 1 96 5.878 0.113 1 0.45 1 1 0.45 17.10 0.74 0.32 3.40
GAS/MOISTURE ANALYSER PVC

230V AC SUPPLY FOR TR-2 ONLINE CU / XLPE /


SDP.D62 QD.62 SDP-2 0.15 1.00 0.15 0.18 1 230 0.77 0.92 20 MCB SPN 0.77 0.85 0.53 2C 4 Duct 38 1 82 5.878 0.113 1 0.45 1 1 0.45 17.10 0.64 0.28 3.40
GAS/MOISTURE ANALYSER PVC

230V AC SUPPLY FOR TR-3 ONLINE CU / XLPE /


SDP.D63 QD.63 SDP-2 0.15 1.00 0.15 0.18 1 230 0.77 0.92 20 MCB SPN 0.77 0.85 0.53 2C 4 Duct 38 1 79 5.878 0.113 1 0.45 1 1 0.45 17.10 0.61 0.27 3.40
GAS/MOISTURE ANALYSER PVC

SDP.D64 QD.64 SDP-2 SPARE 1 230 20 MCB SPN


Permi
UNIT TOTAL TOTAL

DIVERSITY
CB DATA Selected Cable DERATING FACTORS ssible

FACTOR

PHASE
CABLE C.B LOAD LOAD LOAD ILC IOLC IReq Derated VD
From Equipment VOLT COSQ SINQ Soil %VD
NO. NO. AMP AMP AMP Depth Over AMP (volt)
No. of Length R X Temp. Grp. Thermal % VD
KW KW KVA CB Rating TYPE Core mm² Type Laid in AMP of
Resistivity
ALL
Run (m) (Ω/km) (Ω/km) Laying

SDP.D65 QD.65 SDP-2 SPARE 1 230 20 MCB SPN

SDP.D66 QD.66 SDP-2 SPARE 1 230 20 MCB SPN

SDP.D67 QD.67 SDP-2 SPARE 1 230 20 MCB SPN

SDP.D68 QD.68 SDP-2 SPARE 1 230 20 MCB SPN

SDP.D69 QD.69 SDP-2 SPARE 1 230 20 MCB SPN

SDP.D70 QD.70 SDP-2 SPARE 1 230 20 MCB SPN

SDP.D71 QD.71 SDP-2 SPARE 1 230 20 MCB SPN

SDP.D72 QD.72 SDP-2 SPARE 1 230 20 MCB SPN

* Diversity Factor Used Only For Sizing The Sub Distribution Panels Incomer C.B.
Notes:
1) All the cable lengths shown here are tentative and shall vary according to the approved cable raceway layouts.
2) All the technical parameters of the cables mentioned here is for XLPE cables@90ºC
3) The ambient temperature is considerd as 40ºC as per 01-TMSS-01
4) Grouping Correction factors is considerd as per Clause 7.1.7 in TES-119-29