MX Series
Intelligent Fire Alarm Systems
MX320
Addressable Sounder
Features and Benefits
EN54-3 Compliance
Built-in MCU Processor with Digital Addressing
17 tones Programmable Sound Output
Programmable Evacuate or Pre-alarm/Evacuate signal
Low and Normal consumption mode
One or Two addresses mode
Onsite Adjustable Parameters
Loop or External Power input
Aesthetically pleasing design
Surface mounting with Base for ease of installation
Overview
The MX320 Addressable Sounder is an Audio alarm warning device used to notify personnel in the vicinity during
the occurrence of fire, in order that appropriate measures could be taken. The unit adopt multi- application
configuration starting from the types, parameters and wiring layout in a single unit. In addition, parameters can
be configured according to the requirement which include alarm tone from 17 different tones, single address or
dual address mode and also setting of power mode to low current consumption by means of simple
programming.
Manufactured in compliance to European Standards, EN 54 Part 3, the unit is aesthetically pleasing with
unobtrusive design that will complement modern building designs. . The Plug-in type construction enables ease
of installation and maintenance.
The MX320 Addressable Sounder is compatible to the MX Series Intelligent Addressable Fire Alarm System,
produced by single manufacturer to avoid addressable communication compatibility problem.
Multron Systems Pte Ltd DATA SHEET
217 Kallang Bahru, Multron Building Copyright © The information contained in this
Data Sheets remains the property of Multron
Singapore 339 347 Systems Pte Ltd, and is not to be altered or
: (65) 6395 6868 reproduce without permission.
Multron reserves the right to change any
: (65) 6395 6869 specification without prior notice.
: info @ multron.com.sg Version : 31-03-2018
MX Series
Intelligent Fire Alarm Systems
Technical Specification
Approvals and Standards LPCB Pending, EN54-3
Input Voltage Loop Power: 24VDC (18V to 27.5V)
Loop with External PSU: 24VDC
Power Source Loop Powered
(20V to 27.5V)
Standby : 0.6mA Standby : 0.6mA
Typical Current
Alarm : 1.5mA Alarm : 10mA
Saving Current Standby : 1.2mA, Alarm : 4mA
Protocol/Addressing Proprietary Value range from 1 to 254
Address Sequence Single Single
Address:
Address:
Evacuate
Evacuate toneAddress: 1st Alert Tone / 2nd Eva
tone Dual
Dual Address 1st Alert
1st Tone
Alert Tone / 2nd Evacuate tone
2nd Evacuate tone
Material / Colour ABS RED Glossy finishing
Dimension Ø 110mm x 39.6mm (with Base)
Weight 180g (with Base) 114g (without Base)
Class Type A, Indoors
Operating Temperature -10°C to +50°C
Ingress Protection Rating IP21
Humidity 0 to 95% Relative Humidity, Non condensing
Termination Description
1 Signal In (+)
Loop Powered Wiring Details
2 Signal Out (+)
Details
3 Optional Ext. PSU In (+)
4 Optional Ext. PSU Out (+)
5 Signal In (-)
6 Signal Out (-)
7 Optional Ext. PSU In (-)
8 Optional Ext. PSU Out (-)
With External PSU Wiring Details
Details