SFS-1000 User Manual V11
SFS-1000 User Manual V11
2010-8-13
Version 1.1
1/20
Safe-Fire Inc
Contents
2/20
Safe-Fire Inc
1 IMPORTANT DECLARATION
The SFS-1000 communication software is used for on-line debugging and testing the Flame Detector
SA-3000/SU-2000/SP-1000 produced by Safe-Fire Pty. Ltd.
2 COMPONENT
3 SYSTEM REQUIREMENTS
4 INSTALLATION
Step I: Insert the SFS-1000 installation CD into CD-Rom of the PC and run the installation file
Setup.exe. The installation procedure starts (Figure 4-1). Click “Next” button to next step.
3/20
Safe-Fire Inc
Figure 4-1
Figure 4-2
The installation files will be displayed one by one in the Install textbox during the installation procedure,
You can choose not to install SFS-1000 by clicking “Cancel” button to exit Setup.
4/20
Safe-Fire Inc
Step III: Click “Finish” button to complete the installation. Figure 4-3 shows the SFS-1000 has been
successfully installed.
Figure 4-3
5 SFS-1000 CONFIGURATION
5.1 START
Click the shortcut icon to run SFS-1000 along the path: start menu\All Program\sfs_1000\
SFS_1000.exe.
Click “OK”.
Figure 5-1
5/20
Safe-Fire Inc
The password must be input for the first run. The default password is 888888 (Figure 5-2).
Figure 5-2
Click “OK” to get to the database setting interface of SFS-1000 (Figure 5-3).
Figure 5-3
6/20
Safe-Fire Inc
● If the remote communication with scanner uses a RS232-RS485 converter to communicate with
● If the remote communication with the scanner uses an USB-RS485 converter to communicates,
you will first find out which communication port is available in USB-RS485 converter
Figure 5-4
Next you can configure communication port for SFS-1000. The port must be the same as the Comm
Port which is available when the USB-RS485 converter is connected. You can set the port as shown
in Figure 5-5.
7/20
Safe-Fire Inc
Figure 5-5
Figure 5-3 shows the database setting interface. You can connect to the existing database or create
● New---Create a database.
Click “New” to create a database. The file name can be anything (Figure 5-6).
8/20
Safe-Fire Inc
Figure 5-6
Create a database.
You should add the scanner parameters into the database including “Address”, “Description” and
“Remark” and select the “Scanner Type” (SA-3000/SP-1000/SU-2000), after the database has been
created(Figure 5-7).
Figure 5-7
9/20
Safe-Fire Inc
Note:If the buttons are not available, you should login first from “System” menu.
● Connect---Connect a database.
Click the folder to select an existed database, and then click “connect”. When the database is
● Delete---Delete a database.
Remove the selected database.
Figure 5-8
The Toolbar consists of six shortcut buttons: “Setting’”, “Overview”, “Bar”, “History”, “Study”, and
“Exit”. If the buttons are not available, you should login first from “system” menu.
5.4.1 Setting
Click “Setting” to show the configuration of the database and three types of scanner (Figure 5-3).
You can export the history data into txt file. To complete the operation, follow these steps:
10/20
Safe-Fire Inc
2. Select the folder to save the exported data, click “OK” (Figure 5-9).
Figure 5-9
Caution: To avoid unnecessary file loss, we suggest you to keep a backup of the database as the
system will automatically delete the data previously exported.
5.4.2 Overview
Overview interface shows the brief information of each Flame Scanner including current status
([FLAME ON - red] / [FLAME OFF - green] / [OFF-LINE - yellow]) and FR [FLAME RATIO] of
11/20
Safe-Fire Inc
Figure 5-10
You can browse the detailed information of the scanners after login. Click the scanner you want to
Figure 5-11
12/20
Safe-Fire Inc
Notes:
1. The logogram of the Curve Field is C.F.
2. The logogram of the Status Display Field is S.D.F.
3. The logogram of the Parameter Edit Field is P.E.F.
Flame Signal
When the flame is on, the icon is red. When the flame is off, the icon is green.
Error Signal
When the Flame Scanner status is normal, the alarm light is white. When the Flame Detector goes
out of order, the alarm light becomes yellow.
Address
This parameter represents the remote communication address of the flame detector. The range of the
address is 0-127. Each flame detectors has a separate address, as any two flame detectors in a
communication circuit are not allowed to get the same address.
Description
File
This parameter represents the mode of the “Remote File Select”, which may be Key, Comm or Line.
When one of these modes is selected, the other two will be disabled.
Key: select the remote file via the keypad on the SA-3000/SP1000/SU2000 amplifier board.
Comm: select the remote file via the software SFS-1000 on the PC.
Line: select the remote file via the external switch or relay of amplifier board.
File Access
Parameters of each file can be accessed by clicking the File-access-option-button in the Parameter
Edit Fields (Figure 5-12).
13/20
Safe-Fire Inc
Figure 5-12
Gain
Gain is selectable from 1 to 50 and the gradient is 1. The system automatically stores this value into
the RAM after the gain changed. At the same time, the Flame Intensity value and the Flame Ratio
will be reflected immediately in the FI and FR curve graph.
Frequency
The Flame Flicker Frequency is selectable from 3Hz to 126Hz and the gradient is 3. The system
automatically stores this value into the RAM after the frequency changed. At the same time, the
Flame Intensity value and the Flame Ratio will be reflected immediately in the FI and FR curve
graph.
Band
The band is selectable from 3Hz to15Hz and the gradient is 3.The system automatically stores this
value into the RAM after the band changed. At the same time, the Flame Intensity value and the
Flame Ratio will be reflected immediately in the FI and FR curve graph.
ON Threshold
This refers to the “pull-up” threshold of the internal flame relay. The ON Threshold can be set from
10 to 1999. The ON Threshold must be at least 10 units higher than the OFF Threshold. When the
Flame Intensity value is equal to or greater than the ON Threshold, the flame relay will be energized.
OFF Threshold
This refers to the “drop-out” threshold of the internal flame relay. The OFF Threshold can be set
from 0 to 1989.The OFF Threshold must be at least 10 units lower than the ON threshold. When the
Flame Intensity value is equal to or less than the OFF Threshold, the flame relay will be
de-energized.
Max
This parameter is the maximum value of the Flame Ratio. The Max can be set from 1 to 1999.The
Max must be at least one unit higher than the Min.
When the Flame Intensity value is equal to or greater than the Max, it represents that the output
current is 20mA.
Min
This parameter is the minimum value of the Flame Ratio. The Min can be set from 0 to 1998. The
Min must be set at least one unit lower than the Max.
14/20
Safe-Fire Inc
When the Flame Intensity value is equal to or less than the Min, it represents that the output current
is 4mA.
OTD
When Flame Intensity value rises to or is above the Flame Relay ON Threshold, the Flame Relay
will be energized after the On Time Delay (OTD). The OTD can be set from 1 to 6 seconds.
FFRT
When the Flame Intensity value drops to or is below the Flame Relay OFF Threshold, the Flame
Relay will be de-energized after the Flame Failure Response Time (FFRT). The FFRT can be set
from 1 to 6 seconds.
Quick Set
Quick Set is another way to set the value of gain, freq and band. Click “Quick Set” to show the
Quick Setting interface (Figure 5-13).
Figure 5-13
File Select
You can manually choose the file to run or edit when “Comm” is selected at Remote File Select. You
should select a file, then click “File Select” button to change the current file.
Restore
Download
Download the parameters of file that you have selected into flash. The system will automatically
prompt “Operate Successfully” when the download is successful.
Copy
15/20
Safe-Fire Inc
Copy the parameters of the current scanner to corresponding file of the selected Address.
● Curve Fields
This is a Fast Fourier Transform curve tendency graph. The top of the vertical coordinate can be
adjusted with the default value of 15000. The horizontal coordinate represents the various frequency
points within the range of 6-120HZ.
FR Tendency Graph
This is a Flame Ratio tendency graph. The Maximum value of the Flame Ratio is 100 and the
minimum value is 0. The top point of the vertical coordinate is set as 120 in order to make it easy to
browse the tendency graph in case of full-load. The horizontal coordinate presents the real-time
point.
FI Tendency Graph
This is a Flame Intensity tendency graph. The Maximum value of the Flame Intensity is 1999 and
the minimum value is 0. The top point of the vertical coordinate is set as 2020 in order to make it
easy to browse the tendency graph in case of full-load. The horizontal coordinate presents the
real-time point.
5.4.3 Bar
Click “Bar” button to show the bar-graph of the Flame Scanner (Figure 5-14).
Bar shows the information of each scanner: online/offline, Flame ratio, Flame intensity, current file
and description.
Figure 5-14
16/20
Safe-Fire Inc
5.4.4 History
Click “History” button to browse the Flame Scanner Historical Data Browse screen if you want to
browse the historical data curves of various Flame Scanners (Figure 5-15).
The screen can display up to 8 curves of different detectors historical data or real-time data. The
curves are real-time when the option of Runtime Wave is selected, or else the curves are historical.
Figure 5-15
17/20
Safe-Fire Inc
Add (FR)
Select the Detector address at the pull-down list box of the Address and click the Add (FR) button to
browse the Flame Ratio real-time tendency graph of the Flame Detector.
Add (FI)
Select the Detector address at the pull-down list box of the Address and click the Add (FI) button to
browse the Flame Intensity real-time tendency graph of the Flame Detector.
Add (FR&FI)
Select the Detector address at the pull-down list box of the Address and click the Add (FR&FI)
button to browse the Flame Ratio real-time tendency graph and Flame Intensity real-time tendency
graph of the Flame Detector.
Add (FR)
Select the Detector address at the pull-down list box of the Address and click the “Add (FR)” button
to browse the Flame Ratio historical tendency graph of the Flame Detector.
Add (FI)
Select the Detector address at the pull-down list box of the Address and click on the “Add (FI)”
button to browse the Flame Intensity historical tendency graph of the Flame Detector.
Add (FR&FI)
Select the Detector address at the pull-down list box of the Address and click on the “Add (FR&FI)”
button to browse the Flame Ratio historical tendency graph and Flame Intensity historical tendency
graph of the Flame Detector.
Delete
Select the Detector address at the pull-down list box of the Address and then click the button to
delete.
After selecting the Address, you must set the starting time and the ending time, then click “Start”
button. The system will automatically search the historical data.
“<-”/“->”: The “<-” item can roll the historical data forward and the “->” one can roll the historical
data backward.
18/20
Safe-Fire Inc
5.4.5 Study
You can click the “Study” button at the detail interface (Figure 5-11) to start the Flame Detector
Study mode (Figure 5-16). The Detector can figure out the characteristic frequency by scanning the
flame spectrum of “Flame On” and “Flame Off”.
Figure 5-16
Aim Scanner: Click on the Aim Scanner button and “I XX” will be displayed. The “XX” is range
from 0 to 99, which represents flicker intensity of the flame. The value should be at its highest peak
when the scanner is aimed at the primary combustion zone of the flame.
Learn On: Click the “Learn On” button and the progress bar will display “Wait”. The progress bar
keeps refreshing, which will temporarily store the spectrum frequency of the flame. The box
displays “Over” when Learn on completes (Figure 5-17).
Learn OFF: Turn off the flame and click the “Learn OFF” button. The progress bar will display
“Wait” and keeps refreshing. The “Learn On” spectrum will then be compared to the “Learn OFF”
spectrum and the characteristic frequency will be recommended when Learn OFF is completed
(Figure 5-18).
Note: Learn On and Learn OFF must be operated in pair before the characteristic frequency value
is recommended, which may not be in sequence.
19/20
Safe-Fire Inc
5.4.6 Exit
Click this button to exit the system.
20/20