Calculation for deflection of duct support (Horizontal

Input Details
Support
Type of Supporting Member : ISMC
Size : MC75
Distance between two consecutive support : 2 M
INSULA
Span of support (L) : 2.15 M
Duct
Width (W) : 2000 mm
Height (H) : 1100 mm
Insulation
Acoustic - Density : 0 Kg/m3
Thermal(1) - Density : 36 Kg/m3
Thermal(2) - Density : 0 Kg/m3
Acoustic - Thickness : Not applicable mm
Thermal(1) - Thickness : 12 mm
Thermal(2) - Thickness : Not applicable mm

Safety % 25 %
Output Details
Moment of Inertia of the Member : 785000 mm⁴
Young's Modulus(E) for Steel : 200 KN/mm2
Duct Weight for specified gauge : 8 Kg/m2
Weight of Duct : 99.2 Kg.
Total weight of Insulation : 5.36 Kg. m
Self weight of member : 15.35 Kg.
Total weight : 119.91 Kg.
With 25% margin : 149.88 Kg.
Uniformly distributed load (p) : 0.68 KN/m
Deflection,δ 5 x W x L⁴
:
384 x E x I
δmax : 1.21 mm
THE MEMBER IS SAFE
CONCLUSION :
support (Horizontal Member) for UDL

INSULATION (T1 THICKNESS)

DUCT

H
W

L
Calculation for PIPES on Simply Supported Beam
Input Details
Type of Horizontal Supporting Member : ISMC Pipe 1
Size of Horizontal Member : MC100 IS Code
Type of Vertical Supporting Member : ISMC IS:3589
Size of Vetical Member : MC100 Pipe 2
Distance between two consecutive support : 3 M IS Code
Span of support (L) : 3 M IS:3589
Height of Column : 4 M Pipe 3
No of Columns in the structure : 2 nos IS Code
Insulation IS:3589
Insulation 1 - Density : 50 Kg/m3 Pipe 4
Insulation 2 - Density : 0 Kg/m3 IS Code
Insulation 3 - Density : 0 Kg/m3 IS:3589

Insulation 1 - Thickness : 25 mm Pipe1 insulation


Insulation 2 - Thickness : 25 mm Pipe2 insulation
Insulation 3 - Thickness : Not applicable mm Pipe3insulation
Dimensional Pipe4 insulation
Distance a : 0.4 m
Distance b : 1.2 m
Distance c : 1.8 m d
Distance d : 2.4 m c
b
a
Safety % : 25 %
Output Details
Moment of Inertia of the Horizontal Member : 0.000001920 m⁴ L
Moment of Inertia of the Vertical Member : 0.000001920 m⁴
Young's Modulus(E) for Steel : 200000000000 N/m2 COLUMN B
H

Pipe1 Weight for specified thickness : 259.44 Kg COLUMN A


Pipe2 Weight for specified thickness : 259.44 Kg
Pipe3 Weight for specified thickness : 206.82 Kg
Pipe4 Weight for specified thickness : 206.82 Kg
Total Weight of Insulaiton for PIPE1 : 0.00 Kg
Total Weight of Insulaiton for PIPE2 : 0.00 Kg
Total Weight of Insulaiton for PIPE3 : 2.43 Kg
Total Weight of Insulaiton for PIPE4 : 2.43 Kg
Total Force acting at 'a' for Pipe 1** : 10393.99 N Do you want to consider self weight of member
Total Force acting at 'b' for Pipe 2** : 10393.99 N
Total Force acting at 'c' for Pipe 3** : 7181.45 N
Total Force acting at 'd' for Pipe 4** : 7181.45 N
Self weight of Member : 281.06 N ** Weight of water also has been considered
Load on Column B(Vb) : 15597.49 N
Load on Column A(Va) : 19553.38 N
Load on Column A : 1995.24 Kgf
Load on Column B : 1591.58 Kgf
Max allowable Load on Column A / B* : 6042.61 Kgf *Assuming both the columns are of same members
Deflection due to self weight : 0.77 mm
Deflection of beam : 35.166 mm

CONCLUSION :
The Horizontal Member is Unsafe, Select a Higher Member

Click the cell and select available from drop-down list


Calculation for Pipes on Cantilever with support
Input Details
Support Pipe
Type of Supporting Members : ISMC Pipe 1
Size : MC150 IS Code
Distance between two consecutive support : 8.2 M IS:3589
Span of support (L) : 0.635 M Pipe 2
Insulation IS Code
Insulation 1 - Density : 125 Kg/m3 NA
Insulation 2 - Density : 0 Kg/m3
Insulation 3 - Density : 0 Kg/m3 Pipe1 insulation
Pipe2 insulation
Insulation 1 - Thickness : 50 mm
Insulation 2 - Thickness : Not applicable mm
Insulation 3 - Thickness : Not applicable mm a
Dimensional mm
Distance a : 0.86 M
Distance b : 0 M
Distance c : 0.367 m SADDLE

Safety % 25 MEMB
: %
Output Details

WALL/COLUMN
C
Moment of Inertia of the Member A : 0.00000788 m⁴
Young's Modulus(E) for Steel : 200000000000 N/m2
Pipe1 Weight for specified thickness : 493.476 Kg
Pipe2 Weight for specified thickness : 0 Kg
Total Weight of Insulaiton for PIPE1 : 30.19 N/m2
Total Weight of Insulaiton for PIPE2 : 0.00 Kg
Total Force acting at 'a for PIPE 1 : 16079.32 N
Total Force acting at 'b for PIPE 2 : 1775.10 N
Self weight of Member : 10.668 Kg
R : 24267.75 N
A : 11246.33 N
B : 1127.19 N/m
K1 : 1053.45 N
C : 695.57 N
x1 : Err:502 mm
x2 : Err:502 mm
x : Err:502 mm
Deflection due to pipe with support B : Err:502 mm Do you want to consider self weight of
Deflection due to self weight : 0.000 mm
Maximum Deflection(δtotal) with support B : Err:502 mm Do you want to consider support mem
Err:502
CONCLUSION :
Err:502
er with support

Dia Thickness Unit weight


350 7mm 60.18

Dia NA Unit weight 5


150 Heavy(C) 0

Pipe1 insulation To be considered 3


Pipe2 insulation NA
L
b #REF!
a

SADDLE SADDLE

MEMBER 'A'
WALL/COLUMN
C

ant to consider self weight of member Yes

ant to consider support member 'B' Yes


4900
2085.278
0.009319
0.050114
0.053318
0.006116
Calculation for PIPES on Simply Supported Beam
Input Details
Type of Horizontal Supporting Member : ISMC Pipe 1
Size of Horizontal Member : MC150 IS Code
Type of Vertical Supporting Member : ISMC IS:3589
Size of Vetical Member : MC150 Pipe 2
Distance between two consecutive support : 3 M IS Code
Span of support (L) : 3.88 M IS:1239
Height of Column : 3 M Pipe 3
No of Columns in the structure : 2 nos IS Code
Insulation IS:1239
Insulation 1 - Density : 30 Kg/m3 Pipe 4
Insulation 2 - Density : 0 Kg/m3 IS Code
Insulation 3 - Density : 0 Kg/m3 IS:1239
Pipe 5
IS Code
Insulation 1 - Thickness : 50 mm NA
Insulation 2 - Thickness : 12 mm Pipe 6
Insulation 3 - Thickness : 19 mm IS Code
NA
Dimensional
Distance a : 0.216 m Pipe1 insulation
Distance b : 0.448 m Pipe2 insulation
Distance c : 1 m Pipe3 insulation
Distance d : 1.2 m Pipe4 insulation
Distance e : 0 m Pipe5 insulation
Distance f : 0 m Pipe6 insulation

Safety % : 100 %
Output Details
Moment of Inertia of the Horizontal Member : 0.000007880 m⁴
Moment of Inertia of the Vertical Member : 0.000007880 m⁴
Young's Modulus(E) for Steel : 200000000000 N/m2
Pipe1 Weight for specified thickness : 222.81 Kg
Pipe2 Weight for specified thickness : 9.39 Kg
Pipe3 Weight for specified thickness : 11.46 Kg
Pipe4 Weight for specified thickness : 11.46 Kg
Pipe5 Weight for specified thickness : 0 Kg
Pipe6 Weight for specified thickness : 0 Kg

Total Weight of Insulaiton for PIPE1 : 3.71 Kg


Total Weight of Insulaiton for PIPE2 : 0.40 Kg
Total Weight of Insulaiton for PIPE3 : 0.40 Kg
Total Weight of Insulaiton for PIPE4 : 0.40 Kg
Total Weight of Insulaiton for PIPE5 : 0.00 Kg
Total Weight of Insulaiton for PIPE6 : 0.00 Kg

Total Force acting at 'a' for Pipe 1** : 15985.16 N Do you want to consider self weight of member
Total Force acting at 'b' for Pipe 2** : 239.23 N
Total Force acting at 'c' for Pipe 3** : 279.80 N
Total Force acting at 'd' for Pipe 4** : 279.80 N
Total Force acting at 'e' for Pipe 6** : 0.00 N
Total Force acting at 'f' for Pipe 6** : 0.00 N
Self weight of Member : 638.80 N ** Weight of water also has been considered
Load on Column B(Vb) : 1076.17 N
Load on Column A(Va) : 15707.83 N
Load on Column A : 1602.84 Kgf
Load on Column B : 109.81 Kgf
Max allowable Load on Column A / B* : 44088.71 Kgf *Assuming both the columns are of same members
Deflection due to self weight : 0.43 mm
Deflection of beam : 2.929 mm
THE HORIZONTAL MEMBER IS SAFE.
CONCLUSION :

Click the cell and select available from drop-down list


Calculation for Column Critical Load for duct support
Input Details
Support
Type of Supporting Member : ISA
Size : 50X50X6

H
Distance between two consecutive: 3 M W
Span of support (L) : 0.3556 M
Height of Column (H) : 1.9304 M
No of Columns in the structure : 4 nos
Duct
Width (W) : 1500 mm
Height (H) : 800 mm
Insulation
Acoustic - Density : 30 Kg/m3
Thermal(1) - Density : 40 Kg/m3
Thermal(2) - Density : 1858 Kg/m3

Acoustic - Thickness : Not applicable mm


Thermal(1) - Thickness : 10 mm
Thermal(2) - Thickness : Not applicable mm

Safety (%) : 20 %
Output Details
Moment of Inertia of the Member : 129000 mm⁴
Young's Modulus(E) for Steel : 200 KN/mm2
Duct Weight for specified gauge : 6 Kg/m2
Weight of Duct : 82.8 Kg.
Total weight of Insulation : 5.52 Kg.
Self weight of member : 1.6 Kg.
Total weight : 89.9 Kg.
Total weight with safety factor : 107.9 Kg.
Uniformly distributed load (p) : 3.0 KN/m
Critical Load,F(cr) : 1743.2 Kgf
THE COLUMN IS SAFE
CONCLUSION :
GUIDELINES FOR USING THIS HVAC SUPPORT CALCULATOR

1 Select the appropriate tab e.g. "Overhung duct" or "Pipe on Cant. Beam" related to your selecti

2 Use "Input Details" section to insert all the data.

3 Always use the "drop down list" to select the members and pipe sizes.

4 Preferably select one member size higher rather than selecting a meber near to "unsafe" zone.

5 Never modify any cell manually other than inputs as it may give wrong result.

6 For selecting pipes on "Simply supported beam" select first the IS code from drop down list and

Note: Please note that all max. allowable deflection has been considered as L/325 as per IS
RT CALCULATOR

m" related to your selection.

er near to "unsafe" zone.

e from drop down list and also do not forget to select "NA" where pipes are not used.

dered as L/325 as per IS:800.


The most commonly available sections to be selected for use:
ISA 25*25*3 ISMC 75 ISMB 150 ISMC-BOX 100 Box
25*25*5 100 200 150 Box
40*40*3 125 250 200 Box
40*40*4 150 300
40*40*5 200 350
50*50*3 250 400
50*50*4 450
50*50*5 500
50*50*6 600
65*65*5

Note: Please give more preference to the above sections as it is readily available with vend
elected for use:

vailable with vendors.