Pipe SUPPORTCALC
Pipe SUPPORTCALC
Input Details
Support
Type of Supporting Member : ISMC
Size : MC75
Distance between two consecutive support : 2 M
INSULA
Span of support (L) : 2.15 M
Duct
Width (W) : 2000 mm
Height (H) : 1100 mm
Insulation
Acoustic - Density : 0 Kg/m3
Thermal(1) - Density : 36 Kg/m3
Thermal(2) - Density : 0 Kg/m3
Acoustic - Thickness : Not applicable mm
Thermal(1) - Thickness : 12 mm
Thermal(2) - Thickness : Not applicable mm
Safety % 25 %
Output Details
Moment of Inertia of the Member : 785000 mm⁴
Young's Modulus(E) for Steel : 200 KN/mm2
Duct Weight for specified gauge : 8 Kg/m2
Weight of Duct : 99.2 Kg.
Total weight of Insulation : 5.36 Kg. m
Self weight of member : 15.35 Kg.
Total weight : 119.91 Kg.
With 25% margin : 149.88 Kg.
Uniformly distributed load (p) : 0.68 KN/m
Deflection,δ 5 x W x L⁴
:
384 x E x I
δmax : 1.21 mm
THE MEMBER IS SAFE
CONCLUSION :
support (Horizontal Member) for UDL
DUCT
H
W
L
Calculation for PIPES on Simply Supported Beam
Input Details
Type of Horizontal Supporting Member : ISMC Pipe 1
Size of Horizontal Member : MC100 IS Code
Type of Vertical Supporting Member : ISMC IS:3589
Size of Vetical Member : MC100 Pipe 2
Distance between two consecutive support : 3 M IS Code
Span of support (L) : 3 M IS:3589
Height of Column : 4 M Pipe 3
No of Columns in the structure : 2 nos IS Code
Insulation IS:3589
Insulation 1 - Density : 50 Kg/m3 Pipe 4
Insulation 2 - Density : 0 Kg/m3 IS Code
Insulation 3 - Density : 0 Kg/m3 IS:3589
CONCLUSION :
The Horizontal Member is Unsafe, Select a Higher Member
Safety % 25 MEMB
: %
Output Details
WALL/COLUMN
C
Moment of Inertia of the Member A : 0.00000788 m⁴
Young's Modulus(E) for Steel : 200000000000 N/m2
Pipe1 Weight for specified thickness : 493.476 Kg
Pipe2 Weight for specified thickness : 0 Kg
Total Weight of Insulaiton for PIPE1 : 30.19 N/m2
Total Weight of Insulaiton for PIPE2 : 0.00 Kg
Total Force acting at 'a for PIPE 1 : 16079.32 N
Total Force acting at 'b for PIPE 2 : 1775.10 N
Self weight of Member : 10.668 Kg
R : 24267.75 N
A : 11246.33 N
B : 1127.19 N/m
K1 : 1053.45 N
C : 695.57 N
x1 : Err:502 mm
x2 : Err:502 mm
x : Err:502 mm
Deflection due to pipe with support B : Err:502 mm Do you want to consider self weight of
Deflection due to self weight : 0.000 mm
Maximum Deflection(δtotal) with support B : Err:502 mm Do you want to consider support mem
Err:502
CONCLUSION :
Err:502
er with support
SADDLE SADDLE
MEMBER 'A'
WALL/COLUMN
C
Safety % : 100 %
Output Details
Moment of Inertia of the Horizontal Member : 0.000007880 m⁴
Moment of Inertia of the Vertical Member : 0.000007880 m⁴
Young's Modulus(E) for Steel : 200000000000 N/m2
Pipe1 Weight for specified thickness : 222.81 Kg
Pipe2 Weight for specified thickness : 9.39 Kg
Pipe3 Weight for specified thickness : 11.46 Kg
Pipe4 Weight for specified thickness : 11.46 Kg
Pipe5 Weight for specified thickness : 0 Kg
Pipe6 Weight for specified thickness : 0 Kg
Total Force acting at 'a' for Pipe 1** : 15985.16 N Do you want to consider self weight of member
Total Force acting at 'b' for Pipe 2** : 239.23 N
Total Force acting at 'c' for Pipe 3** : 279.80 N
Total Force acting at 'd' for Pipe 4** : 279.80 N
Total Force acting at 'e' for Pipe 6** : 0.00 N
Total Force acting at 'f' for Pipe 6** : 0.00 N
Self weight of Member : 638.80 N ** Weight of water also has been considered
Load on Column B(Vb) : 1076.17 N
Load on Column A(Va) : 15707.83 N
Load on Column A : 1602.84 Kgf
Load on Column B : 109.81 Kgf
Max allowable Load on Column A / B* : 44088.71 Kgf *Assuming both the columns are of same members
Deflection due to self weight : 0.43 mm
Deflection of beam : 2.929 mm
THE HORIZONTAL MEMBER IS SAFE.
CONCLUSION :
H
Distance between two consecutive: 3 M W
Span of support (L) : 0.3556 M
Height of Column (H) : 1.9304 M
No of Columns in the structure : 4 nos
Duct
Width (W) : 1500 mm
Height (H) : 800 mm
Insulation
Acoustic - Density : 30 Kg/m3
Thermal(1) - Density : 40 Kg/m3
Thermal(2) - Density : 1858 Kg/m3
Safety (%) : 20 %
Output Details
Moment of Inertia of the Member : 129000 mm⁴
Young's Modulus(E) for Steel : 200 KN/mm2
Duct Weight for specified gauge : 6 Kg/m2
Weight of Duct : 82.8 Kg.
Total weight of Insulation : 5.52 Kg.
Self weight of member : 1.6 Kg.
Total weight : 89.9 Kg.
Total weight with safety factor : 107.9 Kg.
Uniformly distributed load (p) : 3.0 KN/m
Critical Load,F(cr) : 1743.2 Kgf
THE COLUMN IS SAFE
CONCLUSION :
GUIDELINES FOR USING THIS HVAC SUPPORT CALCULATOR
1 Select the appropriate tab e.g. "Overhung duct" or "Pipe on Cant. Beam" related to your selecti
3 Always use the "drop down list" to select the members and pipe sizes.
4 Preferably select one member size higher rather than selecting a meber near to "unsafe" zone.
5 Never modify any cell manually other than inputs as it may give wrong result.
6 For selecting pipes on "Simply supported beam" select first the IS code from drop down list and
Note: Please note that all max. allowable deflection has been considered as L/325 as per IS
RT CALCULATOR
e from drop down list and also do not forget to select "NA" where pipes are not used.
Note: Please give more preference to the above sections as it is readily available with vend
elected for use: