DATA SHEET

125 VDC / 230 VAC UNINTERRUPTABLE POWER SUPPLIES (UPS) - TYPE 2

No. DESCRIPTION REQUIREMENT / SPEC VENDOR'S RESPONSE


1 GENERAL SPECIFICATION
STANDARD AND LABEL IEC
UPS STANDARD IEC 62040 (All part)
TEMPERATURE RANGE 0 …..+40OC (For Operation)
INSTALLATION ALTITUDE ≥ 1000 m ASL
RELIABILITY MTBF ≥ 185000 Hours
2 SYSTEM CONFIGURATION consist of :
A. 1 X 100% Rectifier with isolation transformer min. 6 pulse; THDI ≤ 28%
B. 1 X 100% PWM Inverter with IGBT's
C. 1 unit of Bypass transformer
D. 1 unit of AC Distribution Board
E. 1 unit of Outgoing to "existing Battery"
3 ELECTRIC SPECIFICATION
RECTIFIER (11BTL10)
Input - Voltage and Freq 3x400 VAC ± 15% , 50 Hz ± 5%
Input - Min. Power (Current) 27.2 KVA (63A upstream protection)
Output - Voltage 125 VDC (Max. 144 VDC) ; Ripple voltage ≤ 2% rms with connected battery
Output - Total current 145 A
Output - Rated Icc 35 kA
BYPASS MAINS (11BRA10)
Input - Voltage and Freq 1x230 VAC ± 10% , 50 Hz ± 5% - 1 phase and 2 wires
Bypass nominal power 5 KVA
Upstream protection Fuse or MCCB (40A -35 kA)
INVERTER (11BRU10)
Input DC voltage 125 VDC (96 -157 VDC)
Output voltage 1x230 VAC ± 1% , 50 Hz ± 0.1%, 2 Wires
Output Rating 5 KVA ( 0.7 Ind… 0.9 Cap) -
Transient voltage recovery ≤ 25ms to ±1 %
Overload Capabilty 125% x I-output For 10 min; 150% x I-output For 1 min;
Short Circuit 200% x I-output For 100ms
Distortion Factor Total at linear load : < 4%, Individual Harmonics : < 3 % ; at non-linear load: < 8% OR (VTA)
INTERNAL WIRING Halogen-free, flame retardant and non toxic.
OVERALL EFFICIENCY >75 %
SPACE HEATERS In UPS, incoming / Bypass panels
230 VAC DB (11BRA10) (subject to existing)
Input Fuse 240V, 63A (F021, At outgoing Inverter) Fuse 660V, 350A (F028, At outgoing bypass)
Output 2A, 2P MCB + PE : 3 Units 6A, 2P MCB + PE : 9 Units
4A, 2P MCB + PE : 1 Unit (For metering)
4 OPERATING AND COMMUNICATION
RECTIFIER -PARAMETERS Float Charge : 133.8 V; Boost Charge: 135V Current Limitation Battery : VTA
Low Battery Voltage: Warning: 109 V ; Shutdown: 96 V
INVERTER- PARAMETERS DC Voltage High - Warning : 139V - Shutdown: 150V
Synchronization range: ± 0.5/1/2/4/6/8 %
Slewrate: 0.5/1/2/4/8 Hz/sec Setting : 4 Hz/sec
CONTROL AND MONITORING It's shall be based on Microprocessor controlled system logic with real time fault analysis
able recording and memorisation of the last events..
Having Battery management system (temperature sensor) and also able to test capacity of
Battries.
INDICATION Front-panel with mimic diagram and detailed LED Indication
EXTERNAL CONNECTION Yes, fail safe open/close contacts
(Common fault, and also individual alarm battery operation, external bypass contactor,
inhibition external bypass, etc,)
COMMUNICATION INTERFACE Yes, minimum MODBUS TCP (VTA)

5 MECHANICAL SPECIFICATION Free standing cabinet - Front door, side and rear removable
PROTECTION CLASS min. 30 (close door) ; IP 20 / NEMA 1 (Open door)
Bottom cable entry
VENTILATION Self-Contained blowers, air inlet in front below, outlet on the top
Notes
1. BATTERY (Existing) Lead Acid : FIAMM - TYPE 2 // 6PMF300 (600 AH)
No's of Cells 60 pcs - Mounted on a steel rack.
Autonomy 360 Min at load 3 kva, 0.8 pf
SINGLE LINE DIAGRAM

GENERAL ARRANGEMENT

Notes:
Existing dimension is about 800 x 2200 x 600 mm,; Vendor to consider the available space