tgs5042 - Application Note (En) - Rev03
tgs5042 - Application Note (En) - Rev03
an ISO9001 company
electrochemical CO sensor which is
provided with individual sensitivity
data printed on the sensor’s housing,
allowing users to eliminate the
process of calibration using CO
gas. This document offers example
circuits and important technical
advice for design and manufacture
of detectors.
Page
Sensor Marking.................................................................................2
Circuit Design
Basic Circuit.................................................................................2
Op-Amp Selection..........................................................3
Baseline Design of Sensor Output......................................................4
Microprocessor.......................................................................4
Anti-polarization Circuit........................................................4
Amplification Circuit..............................................................6
Amplification Factor (gain)................................................................6
Leak Prevention Circuit...................................................................7
Electric Noise Prevention....................................................................7
Temperature Compensation Circuit..........................................7
Self Diagnosis Circuit.....................................................7
Proposed Circuit Using Vcc=3V......................................................9
Proposed Circuit for 5000ppm CO Exposure Test........................10
PCB and Housing Design
Position Dependency of the Sensor..............................................12
Thermistor Location.....................................................................12
Housing Design for Quick Response..............................................12
Sensor Lead Configuration.............................................................12
Calibration
Calibration Using CO Gas..................................................13
Calibration Using Individual Sensor Data.....................................13
Temperature Compensation.........................................13
Calculation of CO Concentration...........................................14
Manufacturing Process
Handling and Storage of Sensors..........................................14
PCB Assembly.....................................................14
Sensor Assembly..........................................................15
F i n a l A s s e m b l y. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 5
Gas Test.......................................................................15
Storage of Finished Products..............................................15
Packaging.................................................................16
Quality Control......................................................................................17
Expected Performance......................................................................................17
Frequently Asked Questions..............................................................................17
IMPORTANT NOTE: OPERATING CONDITIONS IN WHICH FIGARO SENSORS ARE USED WILL VARY
WITH EACH CUSTOMER’S SPECIFIC APPLICATIONS. FIGARO STRONGLY RECOMMENDS CONSULT-
ING OUR TECHNICAL STAFF BEFORE DEPLOYING FIGARO SENSORS IN YOUR APPLICATION AND,
IN PARTICULAR, WHEN CUSTOMER’S TARGET GASES ARE NOT LISTED HEREIN. FIGARO CANNOT
ASSUME ANY RESPONSIBILITY FOR ANY USE OF ITS SENSORS IN A PRODUCT OR APPLICATION FOR
WHICH SENSOR HAS NOT BEEN SPECIFICALLY TESTED BY FIGARO.
Revised 07/15 1
APPLICATION NOTES FOR TGS5042
Revised 07/15 2
APPLICATION NOTES FOR TGS5042
load resistor. 3
CO400ppm Resitor type (1.0k_)
Circuit). 1.2MΩ
R2
to stabilize sensor output (refer to 3-5 Influence of Figure 8 - Anti-polarization circuit using
an N-channel JFET
Storage in TGS5042 Technical Information).
Revised 07/15 4
APPLICATION NOTES FOR TGS5042
amp with very low leak current (such as AD708 Figure 10 - Circuit for extending effective
or OPA2355). Op-amps with large leak current voltage range using N-channel JFET
may cause offset voltage to fall outside of the
adjustable range. It is necessary to choose a P-channel or N-channel
FET, depending on the required effective output
To avoid polarization on the sensor during
range, gain, and the variation range of Vcc.
power-off, Figaro recommends that both of
Figures 8 and 9 show the basic circuit for each
electrodes of the sensor be shorted by using
type.
a JFET (see Item 2-5.1 above). Alternatively,
adding a fixed resistor (10~100kΩ) between The advantage of a P-channel FET is a wider
both electrodes will have a similar effect for effective voltage range. However P-channel
anti-polarization. However, since this effect FETs have higher cost, weakness against
will be smaller than in case of using a JFET, the applied voltage fluctuation, and they require
recovery time after powering on may be longer. higher operating voltage than 5V (making them
Furthermore, resistors between both sensor unsuitable for applications which need <5V).
electrodes may cause a large shift from the base Recommended P-channel FETs are J177, J270
amplified signal. (Fair Child), and 2SJ103 (Toshiba).
3) External switch (Fig. 7) N-channel JFETs are widely available in many
This method is normally used for CO analyzers models, have lower cost, and are more stable
where there is an external switch to control to voltage fluctuation of power supply. Their
power on/off. By using an external switch, the disadvantage is their narrower effective voltage
connection between the W and C electrodes can range. However, one option to extend their
be controlled, whether open or short (<1kΩ) effective voltage range is to shift baseline to Vcc
circuit. as shown in Fig.10. In the example circuit, output
Revised 07/15 5
APPLICATION NOTES FOR TGS5042
(Toshiba). 100kΩ
V1= - (I xR1) R3
-
2-6 Amplification Circuit (see Figs. 11 and 12) Working 1kΩ +
IC
AD708
- 10 bit microprocessor
- Accuracy: ±20% of reading
Figure 13 - Leak current measure
- Detection range: 0 ~ 750ppm using a voltage follower
To extend the detection range, it is necessary
to increase Vcc or to use a microprocessor with circuit design. For example, if a circuit voltage
higher resolution. For conformity to EN50291, (Vcc) would be 5V, the appropriate gain value
Figaro recommends at least a 10bit A/D converter is obtained as follows:
with 1.2M to 1.4M times as a gain value. - full scale of CO conc.: 1000ppm
- baseline of sensor output (in 0ppm CO): +1V
To meet EN50291 requirements, a CO alarm
- max CO sensitivity of TGS5042: 2.4nA/ppm
must be able to distinguish the output signal - temp dependency of TGS5042: I(60˚C)/I(20˚C)=1.2
(voltage) between 30ppm and 50ppm of CO.
For obtaining an appropriate gain value which Gain: 1.38*106 -times =
[5V-1V] / [2.4*1.2 * 10-9(V/ppm) * 1000(ppm)]
can meet with this requirement, the full scale of
CO concentration and baseline of output signal In the above conditions, since a 10bit A/D
in a CO alarm should be decided before starting converter can distinguish the difference in sensor
Revised 07/15 6
APPLICATION NOTES FOR TGS5042
electrical noise.
2SK117
VCC B: 3380
D1
1 680JT VCC
06P 10k
1
VR2
T33u/16V
2 0.1u
REG1
3 DINS4 +
C1
1
2 2 NJU7031D
8
AD708JN
5
- 1 R4 - 6
CN1 5
1.5V 3 IC1A + R8 IC2
VR1
7 3
7
- 10k
10.0k
4
AD708JN
9.1k
10k 0.1u
R6
2) Use a voltage follower (see Sec. 2-8 Leak Current
VCC
capacitor in place of the feedback resistor of the Figure 15 - Temperature compensation circuit
op-amp. The recommended time constant (T)
of RC circuit for power input is 2~2.5 seconds 1) Input the thermistor ’s signal into the
since the value in the basic recommended circuit microprocessor and compensate it with the
is 2.2 seconds. temperature compensation table which is also
To prevent external electrical noise, setting a stored inside microprocessor (refer to Item
noise filter inside the detector, making a noise 3-Calibration for details of the compensation process,
prevention circuit pattern, and averaging the and refer to Appendix 1 for temperature compensation
output signal are recommended. factors).
In addition to reduce electrical noise due to 2) Make an analog circuit with a negative
radio waves, adding fixed resistors (R3 and R4 temperature coefficient (NTC) thermistor and
as shown in Figure 14) on the input terminal resistors in place of the feedback resistor of IC2
of the op-amp is also effective. Please not that (see Fig.15)
the capacitor between the output and input
terminals (C2 on Figure 14) should not be added 2-11 Self Diagnosis Circuit (patented by Figaro)
when a CMOS type op-amp is used. Sensitivity to CO would be lost in case
several failure modes were to occur, such as
2-10 Temperature Compensation Circuit wire breakage, short circuit, or in case the
Temperature compensation can be done in one sensor’s water reservoir were to dry up. By
of two ways: using Figaro’s patented self diagnosis circuit,
Revised 07/15 7
APPLICATION NOTES FOR TGS5042
malfunctions involving loss of CO sensitivity the sensor from the circuit so that self test may
can be detected. be conducted without activating an alarm.
Please note that this method cannot detect CO 2) Apply a minute current to the sensor
sensitivity loss caused by lack of gas diffusion Activate a transistor (TR1) and apply about
when dust or water droplets cover the pin 1µA (absolute maximum rating: 5µA), which
holes for gas diffusion. In addition, slight loss simulates exposure to about 1000ppm CO. This
of CO sensitivity cannot be detected by self- current should be applied for 2~5 seconds. If the
diagnosis. sensor is normal, sensor current will be output
and then quickly recover to its base level.
Depending on the user’s circuit design, factors
for self diagnosis such as current value, self 3) Reconnect the sensor to the circuit
diagnosis period, measurement timing, and 1~2 seconds after self diagnosis current is
voltage range for judgement may vary. Therefore, terminated (TR3 is reset), activate TR2 and
it is recommended that experimentation with the reconnect the sensor to the circuit. Then current
user’s circuit be conducted for fine tuning these applied to the sensor will be discharged.
factors in self diagnosis.
4) Self diagnosis determination is carried out
Figs. 16, 17, and 18 show examples of the circuit, Approx. 5 seconds after the sensor is reconnected
timing chart, and process chart. to the circuit, if the sensor output falls within the
range of 2.3 ~ 3.8V (normal output expected in
The basic steps of self-diagnosis are:
1000ppm of CO), which corresponds to 0.4 to
1) Temporarily cut the sensor off from the circuit 2µA of sensor current, the sensor can be judged
Activate a transistor (TR2) to temporarily isolate to have normal CO sensitivity. If the sensor
D1
DINS4 Tr 3
1 VCC1
680JT
5V 2SK117 VCC1
2 C3
C3
33µ/50V
+
T1µ/16V
REG1
3
+
C1
5
1.0k
R5 67W 10k R6
2
8
- 1
CN1 IC1 +
2.0V 7
VR1
MB5P-90S + 5
3 IC1
A
4
-
6
4
3.0k
MCP6042
Revised 07/15 8
APPLICATION NOTES FOR TGS5042
H-Z (on)
is judged to be open circuited. Please refer to
Drive
Fig. 19 (see following page) for the Vout pattern control
0V (off)
corresponding to each of these cases. approx. 1 min.
VCC (on)
Note: The above Vout range is valid only Self test
current/shorter duration). However, the smaller Current control: 0V (off) to VCC (on)
This small gain value may not meet EN50291 Figure 18 - Self diagnosis flow chart
Drive : H-Z
0V
5 - 7 sec.
Current: VCC
0V 5 sec.
5
4
Normal range
3
Vout/V
2.3 - 3.8 V
2
0
0 10 20 30 40 50 60
Time/sec.
Normal sensor
Drive : H-Z Drive : H-Z
0V 0V
Current: VCC Current: VCC
0V 0V
5 5
4 4
Normal range
Vout/V
Vout/V
3 Normal range 3
2.3 ~ 3.8V 2.3 ~ 3.8V
2 2
1 1
0 0
0 10 20 30 40 50 60 0 10 20 30 40 50 60
Time/sec. Time/sec.
Open circuit No sensitivity
Drive : H-Z Drive : H-Z
0V 0V
Current: VCC Current: VCC
0V 0V
5 5
4 4
Normal range
Vout/V
Vout/V
Normal range 3
3 2.3 ~ 3.8V
2.3 ~ 3.8V
2 2
1 1
0 0
0 10 20 30 40 50 60 0 10 20 30 40 50 60
Time/sec. Time/sec.
Short circuit Water/electrolyte dried up
between 30ppm and 50ppm CO. As a solution, during the powering-on period. As a result, the
Figaro suggests the following three types of acceptable detection range of sensor output falls
circuits: between 0 and 3V.
1) Gain switching circuit (Fig. 20) 3) Change-baseline circuit (Fig. 21a)
The gain value of a second amplifier (IC2) is In the circuit shown in Figure x, the baseline
switched by the micro controller according to and gain values can be changed according to
the output signal of the micro controller. By application of voltage in V1 and V2. As shown in
setting a large gain value while the sensor is in Figure 21b, when Vcc of 3.0V and 0V are applied
low CO concentration range, adequate detection to V1 and V2 respectively during a short time,
resolution is achieved even if Vcc is 3.0V. the baseline of sensor output changes to lower
voltage. Gain value is also increased before
2) Opposite-baseline circuit (Fig. 10)
applying V1 and V2. Thus, by controlling both
In this circuit, the sensor is set up in the opposite
V1 and V2, a detector can achieve high detection
direction (i.e. the working electrode is connected
resolution when the detector is exposed to a low
to the positive input terminal of the op-amp
concentration of CO.
rather than the negative). Since the voltage
between the source and gate of the JFET is fixed 2-13 Proposed circuit for 5000ppm CO exposure test
at 3.0V only during power-on, the JFET can Most electrochemical CO sensors show very
make a short circuit for anti-polarization except long recovery time after high CO gas exposure.
Revised 07/15 10
APPLICATION NOTES FOR TGS5042
Figure 20 - Gain switching circuit
Figure 21a - Change baseline circuit Figure 22 - Basic circuit condition using a diode
Revised 07/15 11
APPLICATION NOTES FOR TGS5042
Revised 07/15 12
APPLICATION NOTES FOR TGS5042
TGS5042-A00: Sensor with SUS lead pins output corresponding to CO a concentration less
The hard pins enables the sensor to be mounted than 10ppm after subtracting detector output
directly to the PCB, simplifying the assembly without sensor.
process.
4-2 Calibration Using Individual Sensor Data
TGS5042-B00: Sensor with flexible nickel ribbon Using individual data printed on sensor, which
The flexible nickel ribbon allows for a variety of is measured at Figaro factory before shipping,
methods for connection to the PCB. This type can considerably simplify the calibration
is also suitable for insertion into a socket. The process. Though the expected accuracy of ±15%
flexible nickel ribbon may be broken by strong accuracy in this method is less than that for using
mechanical shock, drop, or vibration, so it is CO gas, this method can achieve significant
recommended that the sensor body be affixed reduction in handling costs while achieving
onto the PCB by using two-sided tape or wire, acceptable accuracy.
for example.
4-2-1 Input sensitivity data into microprocessor
Sensor data from the label can be read into the
4. Sensor Calibration
microprocessor in one of two ways:
4-1 Calibration Using CO Gas
1) Manually input the user readable value on the
1) After powering the circuit, wait 5 minutes to
label, located beneath the one dimensional bar
stabilize sensor output in clean air (see Note 1)
code (this value is nA/ppm and contains three
2) Measure sensor output in clean air (V0) (See
decimal places).
Note 2)
2) Using a barcode reader which can read Code-
3) Inject C1ppm of CO gas
128, read the one dimensional barcode and input
4) After stabilizing sensor output (e.g. 3 to 4 min),
directly to the microprocessor (this value is nA/
measure sensor output (V1)
ppm and contains three decimal places).
5) Calculate sensor sensitivity α from V0 and
V1 values:
4-2-2 Compensation of offset voltage (zero
α = (V1-V0) / C1 adjustment)
To compensate for offset voltage which is created
Using this method, accuracy of ±5% can be
by the sensor and operational amplifier, measure
obtained for display readings. Please note that
the offset voltage (V0) in clean air (0ppm of CO)
temperature should be in the range of 20°C±2°C
and write into an EEPROM or a microprocessor.
during the calibration process since the sensor
This value should be read from the finished
has dependency on temperature.
detector (after installation of sensor, op-amp,
Note 1: In principle, due to the nature of etc.).
electrochemical cells, pre-heating before
To obtain higher accuracy, keep ambient
calibration is not required. However, in actual
temperature in a range of 20±10°C and be sure
manufacturing, it is recommended to wait 5~10
that the ambient air is completely free of CO.
min. before calibration to stabilize sensor output
in the circuit.
4-3 Temperature Compensation
Note 2: If CO gas is present during the zero There are two methods for temperature
adjustment process, a correct zero adjustment compensation:
cannot be carried out. A detector should be
1) Using a microprocessor
checked in advance to verify that it generates
In case of using a microprocessor, it is necessary
Revised 07/15 13
APPLICATION NOTES FOR TGS5042
temperature
2) Without using a microprocessor
-30
-20 -10 0 10 20 30 40 50 60 70
Temperature (˚C)
In case of not using a microprocessor, this Figure 25 - Temperature dependency of offset voltage
process can be eliminated. for op-amps
Suppress CO alarm
5. Manufacturing Process
Figure 26 - Signal processing
5-1 Handling and storage of sensors flowchart
Revised 07/15 14
APPLICATION NOTES FOR TGS5042
ULF-20
1 H63E Sn/37Pb 183˚C Tamura Kaken Corp
(Cl free)
LLS219A-
Sn/3.0Ag/0.5CuNi/ Soldus line: 271˚C
4 B18 Tamura Kaken Corp EC-19S-8
Ge Liquidus line: 221˚C
(Pb free)
Revised 07/15 15
APPLICATION NOTES FOR TGS5042
Revised 07/15 16
APPLICATION NOTES FOR TGS5042
Q: How long does it take to stabilize sensor output the sensor is easily influenced by external electric
after storage when the sensor electrodes are open- noise since sensor output current is very small.
circuited? Power-supply noise should be minimized, an anti-
A: According to Figaro’s test results, short-circuiting electrical noise circuit pattern should be made, and
the sensor for one hour should be sufficient to stabilize a CR circuit should be used to prevent influence of
sensor output after as much as 6 months storage in electrical noise.
fresh air. Nevertheless, the period to reset the sensor’s
If incoming noise is too large to be prevented by
polarization depends on the type(s) of gases existing
the above measures, these additional steps should
in ambient air, ambient conditions, storage period,
be taken:
and the customer’s circuit. For achieving the best
- coat the detector case with a copper board
results, Figaro recommends that users conduct tests
- use anti-EMI material
at their production facility to determine the optimal
- place metal mesh around the electric circuit
stabilization period for sensor output in air.
Q: Are any special precautions needed to use
TGS5042 for a simple CO analyzer? Figaro USA Inc. and the manufacturer, Figaro
A: To obtain quick response, the gas inlet of sensor Engineering Inc. (together referred to as Figaro)
of the sensor should be located nearest to the detector reserve the right to make changes without notice
to any products herein to improve reliability,
slits or opening. For this application, TGS5042-B00 is
functioning or design. Information contained in
recommended. Please cut the Nickel ribbon as short this document is believed to be reliable. However,
as possible and connect an insulated copper wire by Figaro does not assume any liability arising out of the
soldering. In addition, it is recommended to make application or use of any product or circuit described
small compartment with slits at least in two sides herein; neither does it convey any license under its
around the sensor. Refer to Sec. 3-3 Housing Design patent rights, nor the rights of others.
for Quick Response.
Figaro’s products are not authorized for use as critical
Q: How can electric noise be prevented? components in life support applications wherein a
A: Since sensor impedance is 10Ω or less, the sensor failure or malfunction of the products may result in
itself will not be a source of electric noise. However, injury or threat to life.
FIGARO GROUP
Revised 07/15 17
APPLICATION NOTES FOR TGS5042
Revised 07/15 18