PPU 300

4921240563U
Paralleling and Protection Unit

Data sheet
1. Product description
1.1 About...................................................................................................................................................................................................................................................4
1.2 Software versions...................................................................................................................................................................................................................... 4
1.3 Functions and features........................................................................................................................................................................................................... 5
1.3.1 General functions and features.................................................................................................................................................................................. 5
1.3.2 Alarm functions...................................................................................................................................................................................................................8
1.4 Alarms and protections.......................................................................................................................................................................................................... 8
1.4.1 Alternating current (AC) protections........................................................................................................................................................................8
1.4.2 General controller alarms.............................................................................................................................................................................................11

2. Controller types
2.1 About the controller types..................................................................................................................................................................................................15
2.2 About the hardware modules.......................................................................................................................................................................................... 15
2.3 About the display unit DU 300........................................................................................................................................................................................16
2.4 GENSET controller.................................................................................................................................................................................................................. 16
2.4.1 Functions.............................................................................................................................................................................................................................. 17
2.4.2 Alarms and protections............................................................................................................................................................................................... 18
2.5 HYBRID controller................................................................................................................................................................................................................... 19
2.5.1 Functions............................................................................................................................................................................................................................. 20
2.5.2 Alarms and protections...............................................................................................................................................................................................20
2.6 BUS TIE breaker controller.................................................................................................................................................................................................21
2.6.1 Functions............................................................................................................................................................................................................................. 22
2.6.2 Alarms and protections...............................................................................................................................................................................................22
2.7 SHAFT generator controller..............................................................................................................................................................................................22
2.7.1 Functions..............................................................................................................................................................................................................................23
2.7.2 Alarms and protections............................................................................................................................................................................................... 23
2.8 SHORE connection controller..........................................................................................................................................................................................24
2.8.1 Functions............................................................................................................................................................................................................................. 25
2.8.2 Alarms and protections...............................................................................................................................................................................................25

3. Technical specifications
3.1 General technical specifications................................................................................................................................................................................... 26
3.1.1 Electrical specifications................................................................................................................................................................................................26
3.1.2 Mechanical specifications..........................................................................................................................................................................................26
3.1.3 Environment specifications........................................................................................................................................................................................27
3.1.4 Approvals.............................................................................................................................................................................................................................27
3.2 Rack specifications............................................................................................................................................................................................................... 27
3.2.1 Rack R4.1..............................................................................................................................................................................................................................27
3.2.2 Rack R7.1............................................................................................................................................................................................................................. 28
3.3 Hardware module specifications.................................................................................................................................................................................. 29
3.3.1 Power supply module PSM3.1 (Controller)........................................................................................................................................................29
3.3.2 Power supply module PSM3.2 (Extension)...................................................................................................................................................... 31
3.3.3 Alternating current module ACM3.1.....................................................................................................................................................................33
3.3.4 Differential current module ACM3.2....................................................................................................................................................................34
3.3.5 Engine interface module EIM3.1.............................................................................................................................................................................36
3.3.6 Governor and AVR module GAM3.1......................................................................................................................................................................39
3.3.7 Governor and AVR module GAM3.2......................................................................................................................................................................41
3.3.8 Input/output module IOM3.1.................................................................................................................................................................................... 43
3.3.9 Input/output module IOM3.2................................................................................................................................................................................... 44

4921240563U EN Page 2 of 58
3.3.10 Input/output module IOM3.3................................................................................................................................................................................. 46
3.3.11 Input/output module IOM3.4.................................................................................................................................................................................. 48
3.3.12 Processor and communication module PCM3.1.......................................................................................................................................... 50
3.3.13 Blind module....................................................................................................................................................................................................................51
3.4 Display unit DU 300 specifications............................................................................................................................................................................. 52
3.4.1 Display unit DU 300.......................................................................................................................................................................................................52
3.5 Accessory specifications..................................................................................................................................................................................................53
3.5.1 Ethernet cable.................................................................................................................................................................................................................. 53

4. Ordering
4.1 PPU 300 controller ordering.............................................................................................................................................................................................54
4.2 Extension rack ordering..................................................................................................................................................................................................... 55
4.3 Modules for controller configuration......................................................................................................................................................................... 56

5. Legal information
5.1 Disclaimer and copyright....................................................................................................................................................................................................58

4921240563U EN Page 3 of 58
1. Product description

1.1 About
The PPU 300 Paralleling and Protection Unit is a highly configurable controller designed for marine use. The controller
contains the functions required to protect and control a generator or inverter and its breaker (specifically, a diesel
generator, an inverter with power source, a shaft generator, a shore connection, or a bus tie breaker). You can connect up
to 32 controllers to create one system, with load sharing sections.

The PPU 300 can be ordered with a PLC environment (CODESYS) as an add-on option. CODESYS can be used to extend
the controller functionality and/or create custom CODESYS projects for the controller.

Typically, CODESYS or an operator will send commands to the PPU 300 to close or open the breaker. CODESYS or an
operator can also send commands to start or stop the generator or inverter, change the regulation mode, and change the
regulation set points.

You can also use an alternative PLC to send commands to the PPU 300.

AC measurements can be configured with average filters for use on noisy or oscillating systems. This is only for the
displayed values. All calculations and protections continue to use the actual values. *

The controller display unit can have push-buttons for the operator to change the controller mode, close and open the
breaker, and start and stop a generator or inverter. The colour graphic screen shows status and info messages. Visual
synchronisation screen shows the synchronisation state and values. The screen also allows access to live data, and alarm
management. With the right authorisation, the operator can also check and/or change the input/output and parameter
configuration. The light indicators of the display unit show the system status.

Each controller includes processors and high-speed internal communication. This provides fast protection functions.

The controller design is modular, and hardware modules may be replaced or added in the field.

PICUS is a proprietary, free PC software interface to the controller. The designer can use PICUS to create a flexible
application diagram for the system, and configure the inputs, outputs, and parameters for all the controllers in the system.
PICUS also offers system emulation, supervision, management of permissions, backups, trending, and firmware updates.

The network communication can be configured for IP address settings and for type of Ethernet port and connection node.

Engine communication with CAN bus J1939 can be configured to communicate with an ECU.

More information
See the Engine interface communication manual for supported engines, protocols, and functions.

NOTE * Measurement averaging is not enabled in the default configuration. It may not be allowed for some Maritime
classification approval societies.

More information
You can find additional technical documentation at www.deif.com/documentation/ppu-300/

1.2 Software versions


The information in this document relates to software versions:

4921240563U EN Page 4 of 58
Software Details Version

PCM APPL Controller application 1.0.21.x

DU APPL Display unit application 1.0.20.x

PICUS PC software 1.0.20.x

1.3 Functions and features


1.3.1 General functions and features

General functions for all PPU 300 controllers


Functions

• Compact, all-in-one controller


◦ All necessary 3-phase measurements
• Optional I/O extension rack
• Configurable hardware modules (printed circuit boards)
◦ Placement flexibility in the controller
◦ Remove, replace, or add on-site
◦ Automatically recognised
◦ Customisable arrangement (during ordering and/or on-site)
• Configurable input and output functions (digital and analogue)
◦ Digital input functions: Commands from operators or 3rd party equipment, changing
configuration, operating information
Modular and configurable
◦ Digital output functions: Alarm status, commands to 3rd party equipment, operating
design
information
◦ Analogue input functions: External set points, operating information, supervised binary
inputs
◦ Analogue output functions: Regulation *, operating information
• Up to 4 sets of nominal settings
◦ Select a different set of nominal settings at any time
• Configurable parameters for controller functions
• Power transformer settings for AC measurements (ACM3.1)
◦ Configurable step-up or step-down settings
• Several ways to start controller sequences
◦ Automatically, display unit, digital input, PICUS, Modbus, and/or CustomLogic

• Automatic network configuration (uses static IPv6)


• Default parameter and input-output configuration for each controller type
Plug and play
• Automatic date and time synchronisation between all controllers in the system
• NTP time synchronisation with NTP servers

• Up to 2 display units (with interlock) per controller


• Intuitive, one-touch operator-initiated sequences
• 5-inch colour graphic display
◦ Initial configuration
◦ Status and info messages
Display unit
◦ Live data monitoring and alarm management
◦ Visual synchronisation
◦ Configure live data screens
◦ Tier 4 support and after-treatment dashboard
◦ Input, output, and parameter configuration

4921240563U EN Page 5 of 58
Functions

◦ View/configure counters
◦ View/configure tags
◦ Log, info and tools
◦ Show or hide Tags for Alarm pop-up, alarms, log, and parameters.
◦ Manage backup and restore
◦ Soft keys, and virtual keyboard
◦ Context-sensitive help
◦ Configurable brightness
• Supports multiple languages
◦ American English
◦ British English
◦ Chinese
◦ French
◦ German
◦ Russian
◦ Spanish

• Controller hardware self-test


Advanced troubleshooting • Event and alarm log, with real-time clock
• Access to 24-hour service and support

• Free-of-charge PC software to connect to one or more controllers


• Single-line diagram tool for design, configuration and broadcast
• Manage permissions and passwords (groups and users)
• For each controller:
◦ Configure controller inputs, outputs, and parameters
◦ Manage alarms
◦ View status, live data, and log
◦ Manage backup and restore
◦ Use offline projects to view or edit a controller configuration
◦ Projects can be restored or broadcast.
• System emulation:
◦ Safely mimic the environment that the controller connects to (loads, inputs, and failure
PICUS scenarios)
◦ Test the application, get approvals, minimise site time, optimise training
• System supervision
• Input / output status
◦ See an overview for all input and output values for the controller, extension racks, or
ECUs.
• Trending
◦ Record and save operational values over a period of time
◦ Export recorded trace values to a .csv file
• Tags
◦ Show or hide Tags for Alarm pop-up, alarms, log, parameters, and reports.
• Manage controller and display unit software
• Supports multiple controller languages

• User-friendly logic configuration tool, based on ladder logic and function blocks
CustomLogic • Up to 20 selectable input events and 20 output commands per controller
• Inter-controller communication

4921240563U EN Page 6 of 58
Functions

◦ Up to 16 outputs per controller


◦ Up to 16 inputs from each controller in the system
• Up to 20 Modbus signals (inputs and/or outputs) per controller

• Option: Extended controller functionality with soft PLC


• Custom information pop-up messages and status texts.
CODESYS ◦ Provide better user experience by delivering messaging and status information from
the CODESYS application.
• View CODESYS license key information in PICUS or display

• Static Internet Protocol version 6 (IPv6)


• Configurable Internet Protocol version 4 (IPv4)
• Configurable Ethernet port settings on PCM3.1
• Multi-master system. All vital data is broadcast to all controllers:
◦ Each controller performs all calculations, then acts accordingly
◦ Load sharing communication
• DEIF internal network
◦ Controller display unit
◦ PICUS
◦ Other controllers
• Internal communication
Communication ◦ Extension rack(s)
• External network
◦ PICUS
◦ Modbus
• Controllers connected in a ring for communication redundancy:
◦ If there is a failure: Communication path changed within 100 milliseconds.
• CAN bus communication to an ECU:
◦ Generic J1939.
◦ Supported engine protocols.
• Authentication (other equipment cannot disrupt communication)
• Password protection
◦ Customisable permission levels

• Supports multiple Modbus protocols


◦ Standard protocol: Modbus TCP/IP
◦ Supports use and creation of custom protocols
Modbus
◦ Import and export Modbus protocols
• Convert data units and scaling
• Configure Modbus server settings

• Synchronisation and breaker closing


◦ Dynamic synchronisation: With slip frequency, for fast load acceptance
◦ Static synchronisation: Phases match kept within a phase window
• De-load before opening
• Automatic synchronisation and de-loading
Breaker control
• Operator-initiated synchronisation and de-loading possible
• Breaker types (with configurable parameters)
◦ Pulse breaker, Compact breaker, Continuous breaker
• Breaker position detection and alarms
• Attempt to open breaker even with a position failure detection

4921240563U EN Page 7 of 58
Functions

• True multi-master control


• Busbar can have a ring connection
• DEIF network ring connection
Redundancy
• Internal communication ring connection
• Controller commands and operation using the display unit, inputs, PICUS, and/or Modbus
• Redundant breaker feedback on bus tie breakers and externally controlled breakers

• Hardware/software features: Power supply voltage measurement diode offset


• Relay configuration (function, coil state)
• Analogue input sensor failure (below and above range)
• Analogue input pre-configured curves, plus up to 20 customisable curves
• Analogue output pre-configured curves, plus up to 20 customisable curves
• AC measurements can be configured with average filters for use on noisy or oscillating
systems for displayed information. Controller data and calculations are not affected.
Actual values are always used for the calculations and protections. **

Additional hardware/ ◦ No filters, or average over a selected time.


software features ◦ 200 or 800 milliseconds
• Configurable Idle run (supported engines only)
◦ Protect the engine with additional warm-up or cooldown periods
• Display unit lamp test
• CPU load overview
◦ Currently
◦ Average over 10 seconds
◦ Average over 1 minute
◦ Average over 10 minutes

NOTE * Only for the GENSET, and HYBRID controllers.


NOTE ** Measurement averaging is not enabled in the default configuration. It may not be allowed for some Maritime
classification approval societies.

1.3.2 Alarm functions

• Pre-defined alarms, alarm actions, and alarm inhibits.


• Alarm management: Alarm state, Acknowledgement, Latching, Resetting, Shelving, Out of service.
• Customised alarm parameters: Enable, set point, delay, reset hysteresis, auto acknowledge, trigger level, suppress
action.
• Three customisable inhibits per controller.
• Configurable horn output.
• Alarm test.

More information
See the chapter Alarms in the Designer's handbook for more information about alarms.

1.4 Alarms and protections


1.4.1 Alternating current (AC) protections

The controllers include the following alternating current (AC) protections, according to IEEE Std. C37.2-2008.

The operate time is defined in IEV 447-05-05 (from the instant when the need for the protection arises, to when the
controller output has responded). For each protection, the operate time is given for the minimum user-defined time delay.

4921240563U EN Page 8 of 58
All AC alarms are available on all controllers, unless specifically stated in the notes.

Controller type [Source] [Busbar]

GENSET Generator Busbar

HYBRID Inverter Busbar

SHAFT generator Generator Busbar

SHORE connection Shore busbar Ship busbar

BUS TIE breaker Busbar A Busbar B

AC protections for the [source]

IEC
symbol ANSI (IEEE
Protection Operate time Based on Alarms Note
(IEC C37.2)
60617)

The highest phase-to-phase (or


Over-voltage U>, U>> 59 < 100 ms 2 1
phase-to-neutral) voltage

The lowest phase-to-phase (or


Under-voltage U<, U<< 27 < 100 ms 2 1
phase-to-neutral) voltage

The highest difference between


any of the 3 phase-to-phase (or
Voltage unbalance
UUB> 47 < 200 ms * phase-to-neutral) voltage true 1 1
(voltage asymmetry)
RMS values, and the average
value

Negative sequence The estimated phase-to-neutral


47 < 200 ms * 1 2
voltage voltage phasors

Zero sequence The estimated phase-to-neutral


59U0 < 200 ms * 1 2
voltage voltage phasors

The highest phase current true


Over-current 3I>, 3I>> 50TD < 100 ms 2 1
RMS values

Fast over-current The highest phase current true


3I>>> 50/50TD < 50 ms 2 1
(short circuit) RMS values

The highest difference between


Current unbalance ** IUB> 46 < 200 ms * any of the 3 phase currents and 2 1
the average, or nominal value

The highest phase current true


Inverse time over-
It> 51 - RMS values, based on IEC 60255 1 1
current
part 151

The highest phase current true


Directional over-
67 < 100 ms RMS value, with the direction from 2 2
current
the active power

Negative sequence
46 < 200 ms * The estimated current phasors 1 3
current

Zero sequence
51I0 < 200 ms * The estimated current phasors 1 3
current

The lowest fundamental frequency


Over-frequency f>, f>> 81O < 100 ms 2 1
of a phase voltage

The highest fundamental


Under-frequency f<, f<< 81U < 100 ms 2 1
frequency of a phase voltage

4921240563U EN Page 9 of 58
IEC
symbol ANSI (IEEE
Protection Operate time Based on Alarms Note
(IEC C37.2)
60617)

Overload *** P>, P>> 32 < 100 ms The active power (all phases) 2 1

Reverse power *** P<, P<< 32R < 100 ms The active power (all phases) 2 4

Overload reverse
32R < 100 ms The active power (all phases) 2 6
power

Over-excitation
(reactive power Q>, Q>> 40O < 100 ms The reactive power (all phases) 2 1
export)

Under-excitation
(reactive power
Q<, Q<< 40U < 100 ms The reactive power (all phases) 2 1
import/loss of
excitation)

Synchronisation check The frequency difference, the


Not an
(including blackout - 25 - voltage difference, and the phase 1
alarm
close) angle across the breaker

The RMS value of the fundamental


frequency part of the sum/
difference of the neutral side and
consumer side currents,
< 40ms (When dependent on the operating
Stabilized differential characteristic
the measured
current protection
value increases
(ACM3.2 differential Id> 87G 1 5
from zero to two Operate value accuracy:
current module
times the alarm Based on the largest secondary
required)
set point) current
• Isecondary ≤ 20 A: 1.5 % of
Isecondary or ±15 mA
• 20 A < Isecondary ≤ 250 A: 2.5 %
of Isecondary

The RMS value of the fundamental


frequency part of the sum/
difference of the neutral side and
consumer side currents,
< 40 ms (When independent of the restraint
High set differential current
the measured
current protection
value increases
(ACM3.2 differential Id>> 87G 1 5
from zero to two Operate value accuracy:
current module
times the alarm Based on the largest secondary
required)
set point) current
• Isecondary ≤ 20 A: 1.5 % of
Isecondary or ±15 mA
• 20 A < Isecondary ≤ 250 A: 2.5 %
of Isecondary

Note 1: All controller types.

Note 2: Only GENSET and HYBRID controller.

Note 3: Only GENSET, HYBRID and BUS TIE breaker controllers.

Note 4: Only GENSET, HYBRID, SHAFT generator and SHORE connection controllers.

4921240563U EN Page 10 of 58
Note 5: Only GENSET, HYBRID and SHAFT generator controllers with ACM3.2 installed.

Note 6: Only HYBRID controllers for overload protection.

NOTE * These operate times include the minimum user-defined delay of 100 ms.
** Available as both current unbalance average calculation or current unbalance nominal calculation.
*** On BUS TIE breaker controller, Overload is Power export and Reverse power is Power import.

AC protections for the [busbar]

IEC symbol ANSI (IEEE


Protection Operate time Based on Alarms Note
(IEC 60617) C37.2)

The highest phase-to-neutral (or phase-


Over-voltage U>, U>> 59 < 50 ms 2 1
to-phase) voltage

The lowest phase-to-neutral (or phase-


Under-voltage U<, U<< 27 < 50 ms 2 1
to-phase) voltage

The highest difference between any of


Voltage unbalance
the 3 phase-to-phase (or phase-to-
(voltage UUB> 47 < 200 ms* 1 1
neutral) voltage true RMS values, and the
asymmetry)
average value

The lowest fundamental frequency of a


Over-frequency f>, f>> 81O < 50 ms 2 1
phase voltage

The highest fundamental frequency of a


Under-frequency f<, f<< 81U < 50 ms 2 1
phase voltage

Note 1: All controller types.

NOTE * This operate time includes the minimum user-defined delay of 100 ms.

Other AC protections

IEC symbol ANSI (IEEE


Protection Operate time Based on Alarms
(IEC 60617) C37.2)

Lockout relay 86 - Protected equipment 1

The current RMS value, measured by the 4th


Earth inverse time
51G - current measurement on ACM3.1, filtered to 1
over-current
attenuate the third harmonic (at least 18 dB)

Neutral inverse time The current RMS value, measured by the 4th
51N - 1
over-current current measurement on ACM3.1

1.4.2 General controller alarms

All controllers
Each controller includes the AC protections, the alarms listed here, and the alarms specific to the controller type.

[*B] refers to the breaker that the controller controls. For example, GB for a GENSET controller.

# represents a number that is related to that type of alarm.

4921240563U EN Page 11 of 58
Protections Alarms

[*B] closing failure 1*

[*B] opening failure 1*

[*B] position failure 1*

[*B] configuration failure 1*

Breaker [*B] synchronisation failure 1*

[*B] de-load failure 1*

[*B] tripped (external) 1*

[*B] short circuit 1*

[*B] vector mismatch alarm 1*

Modbus communication timeout 1

DEIF network redundancy broken 1

DEIF network top ring redundancy broken 1

No NTP server time synchronisation 1

No NTP server(s) connected 1


Communication
NTP server # could not connect 2

NTP server # is not responding 2

Fieldbus conflict 1

Fieldbus connection missing 1

ECU communication failure 1

Phase sequence error [Source] 1


Synchronisation
Phase sequence error [Busbar] 1

Breaker # feedback position failure 1

Live power detected (Emulation) 1

Emulation disabled (Live power) 1

Application initialisation error 1

Controller not part of system 1

Single-line missing/none active 1

Missing any controller 1

Missing all controllers 1

System monitoring Missing controllers 1

System not OK 1

Critical process error 1

Different single-line configurations 1

Controller type mismatch 1

Controller ID not configured 1

Duplicate controller ID 1

Missing controller ID # 1 for each controller (up to 12)

Configuration update delayed 1

4921240563U EN Page 12 of 58
Protections Alarms

Digital inputs Up to 50 customisable alarms per controller


Inputs
Analogue inputs Up to 200 customisable alarms per controller

PSM3.1 # supply voltage high 1

PSM3.1 # supply voltage low 1

PCM clock battery failure 1


General
Controller temperature too high 1

Required I/O card(s) not found 1

Software mismatch on hardware module(s) 1

ACM measurement error protections


Protections

[Source] L1-L2-L3 wire break *

[Busbar] L1-L2-L3 wire break *

[Source] L1 wire break *

[Source] L2 wire break *

[Source] L3 wire break *


ACM measurement error
[Busbar] L1 wire break *

[Busbar] L2 wire break *

[Busbar] L3 wire break *

ACM 1 protections not running

ACM 1 data is missing

NOTE * These alarms only work when the breaker is closed. These alarms are only on GENSET, SHAFT generator,
SHORE connection, and BUS TIE breaker controllers.

The following table shows the names for [Source] and [Busbar] for the controllers with ACM measurement error protections.

Controller type [Source] [Busbar]

GENSET Generator Busbar

HYBRID Inverter Busbar

SHAFT generator Generator Busbar

SHORE connection Shore busbar Ship busbar

BUS TIE breaker Busbar A Busbar B

Optional alarms for the EIM3.1 hardware


Protections Alarms

EIM3.1 # supply voltage high 1


Power supply
EIM3.1 # supply voltage low or missing 1

Wire break EIM3.1 # relay 4 wire break 1

Standalone ** EIM3.1 # hardware revision does not support stand-alone 1

EIM3.1 # safety shutdown configuration is not correct 1


Safety shutdown
EIM3.1 # safety shutdown still has control 1

4921240563U EN Page 13 of 58
NOTE ** Standalone is only available on the first installed EIM3.1 hardware module.

Optional alarms for GAM3.2 hardware


Protections Alarms

GAM3.2 # status not OK 1

GAM3.2 # supply voltage high 1


General
GAM3.2 # supply voltage low or
1
missing

Optional alarms for the extension rack


Protections Alarms

PSM3.2 # status not OK 1

General PSM3.2 # supply voltage high 1

PSM3.2 # supply voltage low 1

4921240563U EN Page 14 of 58
2. Controller types

2.1 About the controller types


Each controller is assigned a type from the factory.

The assigned controller type from the factory can be either:


• Generator controller (GENSET controller, standard)
• Generator controller with CODESYS (GENSET controller, with built-in PLC)
• HYBRID controller

The GENSET controller type can be changed from the Application drawing (Single-line diagram) for the associated
controller ID. *

Possible controller types selectable from a GENSET controller with or without CODESYS:

Controller type Controls and protects

GENSET controller An engine and generator, and the generator breaker.


BUS TIE breaker controller One bus tie breaker.
SHAFT generator controller The system when a shaft generator is connected.
The system and the shore connection breaker, when a shore
SHORE connection controller
connection is connected.

2.2 About the hardware modules


The Multi-line 300 (ML 300) hardware modules are printed circuit boards that slot in to either a rack R7.1 or rack R4.1.
Depending on the type of module, they can provide measurement connections, inputs, outputs and communication
indicators.

Example rack R7.1 Example rack R4.1

PSM3.1 ACM3.1 IOM3.1 EIM3.1 GAM3.1 IOM3.1 PCM3.1 PSM3.2 ACM3.1 IOM3.1 EIM3.1
1
L1 L1
2
+ +
L2 L2
- H -
L3 CAN-A L3
L
+ N + N
H
- -
CAN-B
L1 L1
L

L2 L2
CAN-A

L3 CAN-B L3

N N
* *
P
S1 COM S1

L1 Q L1

S2 S2

S1 S1

L2 COM L2 COM
S2 S2

S1 COM S1 COM
Multi-line 300

Multi-line 300

L3 3 L3
W W
S2 R S2 R
I I
S1 R S1 R
I I
*4 R
I 4
*4 R
I
S2 S2
COM COM COM 5 COM COM

The hardware modules feature:


• Placement flexibility in the rack.

4921240563U EN Page 15 of 58
• Remove, replace, or add on-site.
• Automatically recognised.
• Configurable input and output functions (digital and analogue):
◦ Digital input functions: Commands from operators or 3rd party equipment, changing configuration, operating
information.
◦ Digital output functions: Alarm status, commands to 3rd party equipment, operating information.
◦ Analogue input functions: External set points, operating information, supervised binary inputs.
◦ Analogue output functions: Regulation *, operating information.

NOTE * Only available on certain types of controller.

All slots must be covered during operation and blind modules can be used to cover unused slots.

2.3 About the display unit DU 300


The controller can run with or without a display, but we recommend to use the DU 300 display unit. Alternatively, you can
use a touch display from the DEIF AGI 400 series.

The display unit is the operator's interface to the controller. The 5-inch colour graphic display shows real-time operating
information, and it supports all languages with UTF-8 fonts.

The power supply terminals include circuit protection against load dump transients and JEM177 surge transients (rugged
design).

1. Top part
Switchboard control P1
Home 12:00
• Same for all DU 300 display units
2. Bottom strip with control
Configure Tools Info
• Different for each controller type
1
(shown for GENSET controller)
Log on Alarm Log Live data

2.4 About the GENSET controller


A GENSET controller controls and protects a diesel engine and generator (that is, a genset), as well as the generator
breaker. A system can include a number of GENSET controllers.

Each GENSET controller can connect up to three non-essential load groups (NEL).

4921240563U EN Page 16 of 58
Example application with non-essential loads

N N N
E E E
L L L

Busbar

GB
Controller
Display

PLC

PPU 300 Display unit bottom strip with control (DG + CB CTRL)

2.4.1 Functions

Functions

• Genset start and stop sequences


Pre-programmed
• Breaker sequences
sequences
• Generator breaker blackout close

• PID regulators for analogue outputs


• P regulators for relay outputs
• Set point selection using digital input, Modbus, and/or CustomLogic or CODESYS
• Governor:
◦ Active power load sharing
◦ Fixed frequency
Regulation
◦ Fixed active power
◦ Frequency droop
• AVR:
◦ Reactive power load sharing
◦ Fixed voltage
◦ Fixed reactive power

4921240563U EN Page 17 of 58
Functions

◦ Fixed cos phi


◦ Voltage droop
• External set point from analogue input or Modbus
• Configurable power ramp up/down
• Three sets of temperature-dependent power derate settings

4th current • Measurement for earth or neutral protections

• Local mode:
◦ Generator start/stop with the start/stop push-buttons
◦ The breaker is controlled by the close/open push-buttons
Control modes
• Remote mode:
◦ Generator and breaker controlled from a PLC (or integrated CODESYS) combined with
parameter settings

2.4.2 Alarms and protections

These alarms are in addition to the AC protections and general alarms for PPU 300 controllers.

Alarms and protections

Emergency stop

Overspeed (2 alarms)

Under-speed (2 alarms)

Crank failure

Primary running feedback failure

Start failure

Engine Stop failure

Engine stop (external)

Engine start (external)

Start enable removed during start

Total running hours notification

Trip running hours notification

Magnetic pickup wire break

Generator Voltage or frequency not OK

GOV regulation error

GOV regulation mode not selected

GOV stand-alone configuration error*

GOV relay setup incomplete

P load sharing failure


Regulation
AVR regulation error

AVR regulation mode not selected

AVR stand-alone configuration error*

AVR relay setup incomplete

Q load sharing failure

4921240563U EN Page 18 of 58
Alarms and protections

• Up to 3 non-essential loads per controller


• Can connect each controller to the same 3 non-essential load breakers

NEL # over-current (1 alarm for each non-essential load)


Non-essential load (NEL)
NEL # under-frequency (1 alarm for each non-essential load)

NEL # overload 1 and 2 (2 alarms for each non-essential load)

NEL # reactive overload (1 alarm for each non-essential load)

Other Trip AVR output not configured

NOTE * Only in GAM3.2.

2.5 About the HYBRID controller


A HYBRID controller controls an inverter with power source, and the inverter breaker. A system can include a number of
HYBRID controllers.

The HYBRID controller only directly controls an inverter and the inverter breaker. It does not control or provide any
management of the actual power source, for example a Battery Management System (BMS). The customer must ensure
that the necessary management system for the power source is installed and approved, according to the applicable
Maritime classification societies.

Each HYBRID controller can control up to three non-essential load groups (NEL).

Example application with non-essential loads

N N N
E E E
L L L

Busbar

Breaker
Controller
Display

PLC

4921240563U EN Page 19 of 58
PPU 300 Display unit bottom strip

2.5.1 Functions

Functions

• Inverter start and stop sequences


Pre-programmed
• Breaker sequences
sequences
• Inverter breaker blackout close
• Power Take Off (PTO)
Inverter modes • Power Take In (PTI)
• Standby
• Display unit counters, to edit or reset:
◦ Start attempts
◦ Running hours (total and trip)
Counters ◦ Inverter breaker operations and trips
◦ Power export (active and reactive)
◦ External breaker operations
• Energy counters with configurable digital outputs for external counters
• Local mode:
◦ Inverter start/stop with the start/stop push-buttons
◦ The breaker is controlled by the close/open push-buttons
Control modes
• Remote mode:
◦ Inverter and breaker controlled from a PLC (or integrated CODESYS) combined with
parameter settings

2.5.2 Alarms and protections

These alarms are in addition to the AC protections and general alarms for PPU 300 controllers.

Alarms and protections

Emergency stop

Start sequence failure

Stop sequence failure

Total running hours notification

Trip running hours notification

Inverter Standby request failure

Standby acknowledge timeout

PTI request failure

PTI acknowledge failure

PTO request failure

PTO acknowledge failure

4921240563U EN Page 20 of 58
Alarms and protections

GOV regulation error

GOV regulation mode not selected

GOV stand-alone configuration error *

GOV relay setup incomplete

P load sharing failure


Regulation
AVR regulation error

AVR regulation mode not selected

AVR stand-alone configuration error *

AVR relay setup incomplete

Q load sharing failure

• Up to 3 non-essential loads per controller


• Can connect each controller to the same 3 non-essential load breakers

NEL # over-current (1 alarm for each non-essential load)


Non-essential load (NEL)
NEL # under-frequency (1 alarm for each non-essential load)

NEL # overload 1 and 2 (2 alarms for each non-essential load)

NEL # reactive overload (1 alarm for each non-essential load)

Other Trip AVR output not configured

NOTE * Only in GAM3.2.

2.6 About the BUS TIE breaker controller


Each BUS TIE breaker controller controls one bus tie breaker.

There can be a ring busbar connection.

Busbar B

BTB
Controller
Display

PLC

Busbar A

4921240563U EN Page 21 of 58
PPU 300 Display unit bottom strip with control (CB CTRL)

2.6.1 Functions

Functions

Synchronisation and
• Broadcast the set point for GENSET controllers (busbar A and busbar B sections)
deloading

• Display unit counters, to edit or reset:


◦ Bus tie breaker operations and trips
◦ Busbar B energy export/import (active and reactive)
Counters
◦ Energy differential (active and reactive)
◦ External breaker operations
• Energy counters with configurable digital outputs (for external counters)

2.6.2 Alarms and protections

All the BUS TIE breaker controller alarms are included in the AC protections and general alarms for PPU 300 controllers.

2.7 About the SHAFT generator controller


A SHAFT generator controller controls and protects the system when a shaft generator is connected. The SHAFT
generator controller also controls and protects the shaft generator breaker.

Example application with non-essential loads

N N N
E E E
L L L

Busbar

SGB
Controller
Display

PLC

4921240563U EN Page 22 of 58
PPU 300 Display unit bottom strip with control (CB CTRL)

2.7.1 Functions

Functions

Running detection • Multiple feedback options: Frequency, MPU/W/NPN/PNP (RPM), Digital input

Synchronisation and
• Broadcast the set point for GENSET controllers
deloading

• Display unit counters, to edit or reset:


◦ Running hours (total, and trip)
◦ Shaft generator breaker operations and trips
Counters
◦ Energy export/import (active and reactive)
◦ External breaker operations
• Energy counters with configurable digital outputs for external counters

• Regulators for relay outputs and analogue outputs


• Governor regulation:
◦ Fixed power
◦ Active power load sharing
◦ Active power ramp down
◦ Frequency-dependent power droop
Regulation
• AVR regulation:
◦ Reactive power load sharing
◦ Fixed reactive power
◦ Fixed cos phi
◦ Voltage droop
• Configurable power ramp up/down

2.7.2 Alarms and protections

These alarms are in addition to the AC protections and general alarms for PPU 300 controllers.

Alarms and protections

Running feedback Primary running feedback failure

SG-DG maximum parallel time

Maximum parallel time SG-SG maximum parallel time

SG-Hybrid maximum parallel time

• GOV regulation error


• GOV regulation mode not selected
• GOV stand-alone configuration error *
Regulation
• P load sharing failure
• AVR regulation error
• AVR regulation mode not selected

4921240563U EN Page 23 of 58
Alarms and protections

• AVR stand-alone configuration error *


• Q load sharing failure

• Up to 3 non-essential loads per controller


• Can connect each controller to the same 3 non-essential load breakers

NEL # over-current (1 alarm for each non-essential load)


Non-essential load (NEL)
NEL # under-frequency (1 alarm for each non-essential load)

NEL # overload 1 and 2 (2 alarms for each non-essential load)

NEL # reactive overload (1 alarm for each non-essential load)

Other Trip AVR output not configured

NOTE * Only in GAM3.2.

2.8 SHORE connection controller


When the shore connection is in use, it is normally the ship's only power source. However, the gensets may run in parallel
with the shore connection for a limited time.

There is no restriction on the number of SHORE connection controllers.

Example application with non-essential loads

N N N
E E E
L L L

Busbar

SCB
Controller
Display

PLC

Shore connection

4921240563U EN Page 24 of 58
PPU 300 Display unit bottom strip with control (CB CTRL)

2.8.1 Functions

Functions

Synchronisation and
• Broadcast the set point for GENSET controllers
deloading

• Display unit counters, to edit or reset:


◦ Shore connection breaker operations and trips
Counters ◦ Power export/import (active and reactive)
◦ External breaker operations
• Energy counters with configurable digital outputs for external counters

2.8.2 Alarms and protections

These alarms are in addition to the AC protections and general alarms for PPU 300 controllers.

Alarms and protections

SC-DG maximum parallel time

SC-SC maximum parallel time


Maximum parallel time
SC-SG maximum parallel time

SC-Hybrid maximum parallel time

• Up to 3 non-essential loads per controller


Non-essential load (NEL)
• Can connect each controller to the same 3 non-essential load breakers

NEL # over-current (1 alarm for each non-essential load)

NEL # under-frequency (1 alarm for each non-essential load)

NEL # overload 1 and 2 (2 alarms for each non-essential load)

NEL # reactive overload (1 alarm for each non-essential load)

4921240563U EN Page 25 of 58
3. Technical specifications

The general technical specifications apply to all hardware. Refer to the other sections for the specific technical
specifications for specific hardware.

The specifications and approvals apply to the rack with all the hardware modules properly installed.

3.1 General technical specifications


3.1.1 Electrical specifications

Category Specification

EN 61010-1, CAT III, 600V, pollution degree 2


IEC/EN 60255-27, CAT III, 600V, pollution degree 2
UL508
Safety
UL6200
CSA C22.2 No. 14-13
CSA C22.2 No. 142 M1987

EN 61000-6-3 Residential, commercial and light-industrial environments


EN 61000-6-2 Industrial environments
Electromagnetic IEC/EN 60255-26
compatibility (EMC) IEC 60533 power distribution zone
IACS UR E10 power distribution zone for controller rack
IEC 60945 for display unit

Load dump ISO 7637-2 pulse 5a

3.1.2 Mechanical specifications

Category Specification

3 to 8 Hz: 17 mm peak-to-peak
Operation 8 to 100 Hz: 4 g
100 to 500 Hz: 2 g

10 to 58.1 Hz: 0.15 mm peak-to-peak


Response
58.1 to 150 Hz: 1 g
Vibration
Endurance 10 to 150 Hz: 2 g

3 to 8.15 Hz: 15 mm peak-to-peak


Seismic
8.15 to 35 Hz: 2 g

IEC 60068-2-6, IACS UR E10, IEC 60255-21-1 (class 2), IEC 60255-21-3 (class 2)

10 g, 11 ms, half sine IEC 60255-21-2 Response class 2


Shock (base mounted) 30 g, 11 ms, half sine IEC 60255-21-2 Endurance class 2
50 g, 11 ms, half sine IEC 60068-2-27

Bump 20 g, 16 ms, half sine IEC 60255-21-2 class 2

Material All plastic materials are self-extinguishing according to UL94 (V0)

NOTE g = gravitational force (g-force).

4921240563U EN Page 26 of 58
3.1.3 Environment specifications

Category Specification

Humidity 97 % relative humidity condensing, to IEC 60068-2-30

Operating temperature, -40 to 70 °C (-40 to 158 °F)


rack and modules UL/cUL Listed: maximum surrounding air temperature: 55 °C (131 °F)

Operating temperature, -20 to 70 °C (-4 to 158 °F)


display unit UL/cUL Listed: maximum surrounding air temperature: 55 °C (131 °F)

Storage temperature, rack


-40 to 80 °C (-40 to 176 °F)
and modules

Storage temperature,
-30 to 80 °C (-22 to 176 °F)
display unit

Up to 4,000 m (13,123 ft)


Operating altitude Refer to the module specifications for information on altitude derating over 2,000 m (6,562
ft)

3.1.4 Approvals

These approvals apply to the controller rack (with all the modules properly installed), and to the display unit.

Standards

CE

UL/cUL Listed to UL508 - Industrial Control Equipment, and CSA C22.2 No. 142 M1987 - Process Control Equipment

UL/cUL Recognised to UL6200 - Controls for stationary engine driven assemblies, and CSA C22.2 No. 14-13 - Industrial
Control Equipment

NOTE For marine approvals, refer to www.deif.com for the most recent approvals.

3.2 Rack specifications


3.2.1 Rack R4.1

Rack R4.1 technical specifications

Category Specification

Ingress protection IP20 (all slots must have modules or blind modules mounted) according to IEC/EN 60529

UL/cUL Listed Type Complete Device, Open Type 1

Material Rack frame: Aluminium

Base mount, using four M6 bolts with self-locking washers (or self-locking screws).

The bolts and self-locking washers (or self-locking screws) are not included with the rack.
Mounting

UL/cUL Listed: For use on a flat surface of a type 1 enclosure


UL/cUL Listed: To be installed in accordance with the NEC (US) or the CEC (Canada)

Tightening torque Mounting bolts: 4 N·m (35 lb-in)

4921240563U EN Page 27 of 58
Rack 4.1 dimension and weight specifications

Category Specification

L 146.1 mm x H 199.9 mm x D 157.5 mm (5.75 in x 7.87 in x 6.20 in) (outer frame, includes
Dimensions
cable strain relief plates)

Weight Without any hardware modules: 994 g (2.2 lb)

146.1 mm (5.75 in)

Ø 17.2 mm (0.68 in) 128.9 mm (5.07 in)


Ø 7.0 mm (0.28 in)
PSM3.2

172.0 mm (6.77 in)


190.2 mm (7.49 in)
168.0 mm (6.61 in)

199.9 mm (7.87 in)


Multi-line 300
157.5 mm (6.20 in)

137.3 mm (5.40 in)


139.3 mm (5.48 in)

155.0 mm (6.10 in)

3.2.2 Rack R7.1

Rack 7.1 technical specifications

Category Specification

Ingress protection IP20 (all slots must have modules or blind modules mounted) according to IEC/EN 60529

UL/cUL Listed Type Complete Device, Open Type 1

Material Rack frame: Aluminium

Base mount, using four M6 bolts with self-locking washers (or self-locking screws).

The bolts and self-locking washers (or self-locking screws) are not included with the rack.
Mounting

UL/cUL Listed: For use on a flat surface of a type 1 enclosure


UL/cUL Listed: To be installed in accordance with the NEC (US) or the CEC (Canada)

Tightening torque Mounting bolts: 4 N·m (35 lb-in)

4921240563U EN Page 28 of 58
Rack 7.1 dimensions and weight specifications

Category Specification

L 230.1 mm x H 199.9 mm x D 157.5 mm (9.06 in x 7.87 in x 6.20 in) (outer frame, includes
Dimensions
cable strain relief plates)

Weight Without any hardware modules: 1330 g (2.9 lb)

230.1 mm (9.06 in)

Ø 17.2 mm (0.68 in) 212.9 mm (8.38 in)

Ø 7.0 mm (0.28 in)


PSM3.1

172.0 mm (6.77 in)


190.2 mm (7.49 in)
168.0 mm (6.61 in)

199.9 mm (7.87 in)


Multi-line 300
157.5 mm (6.20 in)

137.3 mm (5.40 in)


139.3 mm (5.48 in)

155.0 mm (6.10 in)

3.3 Hardware module specifications


3.3.1 Power supply module PSM3.1 (Controller)

The power supply module provides power to all hardware modules in the rack. The rack status and alarms activate the three
relay outputs. There are two ports for internal communication (EtherCAT) only with extension racks.

The PSM3.1 must to be powered by a power supply with Power Boost function.

The PSM3.1 manages the hardware module self-checks for the rack and includes a power LED. The power supply terminals
include circuit protection against load dump transients and JEM177 surge transients (rugged design). These terminals also
include battery voltage measurement.

4921240563U EN Page 29 of 58
PSM3.1 terminals
Module Count Symbol Type/Info Name

1 Ground Frame ground


PSM3.1
1
12 or 24 V Power supply

3 1 × Status OK (fixed)
Relay output
2 × configurable
+
- 1 Off : No power supply Power supply indication

Red flash : PSM is starting or module failure


Green : Power supply
Green flash : Controller identification

1 Off : No EtherCAT communication EtherCAT communication


connections (to connect to
Green : EtherCAT Communication
extension racks).
1 EtherCAT communication (RJ45) input
Off : No communication LEDs are on the module
Multi-line 300

front, connections are at the


Green : Communication connected
module bottom.
Green flash : Active communication

1 EtherCAT communication (RJ45) output


Off : No communication
Green : Communication connected
Green flash : Active communication

PSM3.1 technical specifications


Category Specification

Voltage withstand: ±36 V DC to the power supply positive (terminal 1) and negative (terminal
Frame ground
2)

Input voltage: 12 or 24 V DC nominal (8 to 36 V DC continuously)


UL/cUL Listed: 10 to 32.5 V DC
0 V DC for 50 ms when coming from at least 8 V DC (cranking dropout)
Consumption: Typical 20 W, maximum 35 W
Voltage measurement accuracy: 0 to 30 V: ±1 V; 30 to 36 V: +1/-2 V
Internal protection: 12 A fuse (not replaceable) (fuse size determined by load dump
requirements)
Controller power supply Voltage withstand: ±36 V DC
Load dump protected by TVS diodes

Start current
• Power supply current limiter
◦ 24 V: 4 A minimum
◦ 12 V: 8 A minimum
• Battery: No limit

Relay outputs Relay type: Solid state


Electrical rating and UL/cUL Listed: 30 V DC and 1 A, resistive
Voltage withstand: ±36 V DC

Frame ground and power supply:


• Terminals: Standard 45° plug, 2.5 mm2
Terminal connections
• Wiring: 1.5 to 2.5 mm2 (16 to 12 AWG), multi-stranded
Other connections:

4921240563U EN Page 30 of 58
Category Specification

• Terminals: Standard 45° plug, 2.5 mm2


• Wiring: 0.5 to 2.5 mm2 (22 to 12 AWG), multi-stranded

Communication EtherCAT communication: RJ45. Use an Ethernet cable that meets or exceeds the SF/UTP
connections CAT5e specifications

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Torques and terminals Connection of wiring to terminals: 0.5 N·m (4.4 lb-in)
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

Between power supply and other I/Os: 600 V, 50 Hz for 60 s


Galvanic isolation Between relay groups and other I/Os: 600 V, 50 Hz for 60 s
Between internal communication ports and other I/Os: 600 V, 50 Hz for 60 s

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 43.3 × 162 × 150 mm (1.5 × 6.4 × 5.9 in)

Weight 331 g (0.7 lb)

3.3.2 Power supply module PSM3.2 (Extension)

The power supply module provides power to all hardware modules in the extension rack. There are two ports for internal
communication with the main controller. The internal communication (EtherCAT) connections are only used to communicate
with the main controller. The rack status and alarms activate the three relay outputs.

The PSM3.2 must to be powered by a power supply with Power Boost function.

The PSM3.2 manages the hardware module self-checks for the rack and includes a power LED. The power supply terminals
include circuit protection against load dump transients and JEM177 surge transients (rugged design). These terminals also
include battery voltage measurement.

4921240563U EN Page 31 of 58
PSM3.2 terminals
Module Count Symbol Type/Info Name

1 Ground Frame ground


PSM3.2
1 12 or 24 V Power supply

3 1 × Status OK (fixed)
Relay output
2 × configurable
+
- 1 Off : No power supply Power supply indication

Red flash : PSM is starting or module failure


Green : Power supply
Green flash : Rack identification

1 Off : No EtherCAT communication EtherCAT communication


connections (to connect to
Green : EtherCAT Communication
the racks).
1 EtherCAT communication (RJ45) input LEDs are on the module
front, connections are at the
Off : No communication
module bottom.
Multi-line 300

Green : Communication connected


Green flash : Active communication

1 EtherCAT communication (RJ45) output


Off : No communication
Green : Communication connected
Green flash : Active communication

PSM3.2 technical specifications


Category Specification

Voltage withstand: ±36 V DC to the power supply positive (terminal 1) and negative (terminal
Frame ground
2)

Input voltage: 12 or 24 V DC nominal (8 to 36 V DC continuously)


UL/cUL Listed: 10 to 32.5 V DC
0 V DC for 50 ms when coming from at least 8 V DC (cranking dropout)
Consumption: Typical 20 W, maximum 35 W
Voltage measurement accuracy: 0 to 30 V: ±1 V; 30 to 36 V: +1/-2 V
Internal protection: 12 A fuse (not replaceable) (fuse size determined by load dump
requirements)
Controller power supply Voltage withstand: ±36 V DC
Load dump protected by TVS diodes

Start current
• Power supply current limiter
◦ 24 V: 4 A minimum
◦ 12 V: 8 A minimum
• Battery: No limit

Relay outputs Relay type: Solid state


Electrical rating and UL/cUL Listed: 30 V DC and 1 A, resistive
Voltage withstand: ±36 V DC

Frame ground and power supply:


• Terminals: Standard 45° plug, 2.5 mm2
Terminal connections
• Wiring: 1.5 to 2.5 mm2 (16 to 12 AWG), multi-stranded
Other connections:

4921240563U EN Page 32 of 58
Category Specification

• Terminals: Standard 45° plug, 2.5 mm2


• Wiring: 0.5 to 2.5 mm2 (22 to 12 AWG), multi-stranded

Communication EtherCAT communication: RJ45. Use an Ethernet cable that meets or exceeds the SF/UTP
connections CAT5e specifications

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Torques and terminals Connection of wiring to terminals: 0.5 N·m (4.4 lb-in)
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

Between power supply and other I/Os: 600 V, 50 Hz for 60 s


Galvanic isolation Between relay groups and other I/Os: 600 V, 50 Hz for 60 s
Between internal communication ports and other I/Os: 600 V, 50 Hz for 60 s

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 43.3 × 162 × 150 mm (1.5 × 6.4 × 5.9 in)

Weight 331 g (0.7 lb)

3.3.3 Alternating current module ACM3.1

The alternating current module ACM3.1 measures the voltage and current on one side of a breaker, and the voltage on the
other side. The hardware module responds when the measurements exceed the AC alarm parameters.

ACM3.1 provides robust frequency detection in environments with electrical noise. ACM3.1 allows extended measurement
bandwidth up to 40 times the nominal frequency. ACM3.1 includes a configurable 4th current measurement.

ACM3.1 terminals
Module Count Symbol Type Name

2 × (L1, L2, L3 and N) L1/L2/L3/N Voltage 3-phase voltage measurements


ACM3.1
1 × (L1, L2, L3 and 4th) Current 3-phase current measurement
L1

L2
4th current measurement
L3

L1

L2

L3

S1

L1

S2

S1

L2

S2

S1

L3

S2

S1

*4
S2

4921240563U EN Page 33 of 58
ACM3.1 technical specifications
Category Specification

Nominal value: 100 to 690 V AC phase-to-phase


Measurement range: 2 to 897 V AC phase-to-phase
Accuracy: Class 0.2
Phase angle accuracy: 0.1° (within nominal voltage range and nominal frequency range)
Voltage measurements Altitude derating from 2,000 to 4,000 m (6,562 to 13,123 ft): 100 to 480 V AC phase-to-
phase
UL/cUL Listed: 100 to 600 V AC phase-to-phase
Load on external voltage transformer: Maximum 0.2 VA/phase
Voltage withstand: 1.2 × Nominal voltage continuously; 1.3 × Nominal voltage for 10 s

Nominal value: 1 or 5 A AC from current transformer


Measurement range: 0.02 to 17.5 A AC from current transformer; Truncation level: 11 mA
Accuracy: Class 0.2
Current measurements Earth current: 18 dB attenuation of third harmonic of the nominal frequency
UL/cUL Listed: From listed or R/C (XODW2.8) current transformers 1 or 5 A
Load on external current transformer: Maximum 0.3 VA/phase
Current withstand: 10 A continuously; 17.5 A for 60 s; 100 A for 10 s; 250 A for 1 s

Nominal value: 50 Hz or 60 Hz
Measurement range: 35 to 78 Hz
Frequency measurements
Accuracy: Class 0.1 of nominal value (35 to 78 Hz) (-40 to 70 °C) (-40 to 158 °F)
Class 0.02 of nominal value (40 to 70 Hz) (15 to 30 °C) (59 to 86 °F)

Power measurements Accuracy: Class 0.5

Unless otherwise specified for the above measurements:


Nominal range: -40 to 70 °C (-40 to 158 °F)
Accuracy and temperature Reference range: 15 to 30 °C (59 to 86 °F)
Accuracy: Measurement type specific within reference range
Additional 0.2 % error of full scale per 10 °C (18 °F) outside reference range

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Secure the current measurement terminal block to the module faceplate: 0.25 N·m (2.2 lb-in)
Torques and terminals
Connection of wiring to terminals: 0.5 N·m (4.4 lb-in)
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

AC voltage and current terminals: Standard 45º plugs, 2.5 mm2


Terminal connections
Wiring: 2.5 mm2 (13 AWG), multi-stranded

Between AC voltage and other I/Os: 3310 V, 50 Hz for 60 s


Galvanic isolation
Between AC current and other I/Os: 2210 V, 50 Hz for 60 s

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 28 × 162 × 150 mm (1.1 × 6.4 × 5.9 in)

• One roundel with 6 J-shaped voltage encoding pins (for the hardware module)
Accessories (included)
• One roundel with 6 flat voltage encoding pins (for the voltage terminal blocks)

Weight 232 g (0.5 lb)

3.3.4 Differential current module ACM3.2

The differential current module ACM3.2 measures the generator outgoing 3-phase currents (consumer side) and star point
3-phase currents. The ACM3.2 uses the measurements to detect phase-to-phase faults or phase-to-earth faults (star point
earthed generator stator only) in the generator stator, and dependent on the mounting of the CT’s on the outgoing side,
possibly also the cable between the generator and the main switchboard.

The protection consists of:


• A stabilised stage that uses a fixed + 2 × sloped operating characteristic. This current restraint approach is also known
as biased differential protection.

4921240563U EN Page 34 of 58
• A high set fixed differential stage (non-stabilised).

Differential
current [%]

Trip area

Restraint
Stabilized, Stabilized, Stabilized, High set current [%]
region 1 region 2 region 3 Region
Fixed Sloped Sloped Fixed

ACM3.2 terminals
Module Count Symbol Type Name

ACM3.2 1 × (L1, L2 and L3) Current 3-phase current measurement - Consumer side

S1

L1

S2

S1

L2

S2

S1

L3

S2

S1 1 × (L1, L2 and L3) Current 3-phase current measurement - Neutral side


L1

S2

S1

L2

S2

S1

L3

S2

ACM3.2 technical specifications


Category Specification

Current: Nominal value: 1 or 5 A AC from current transformer


Frequency:
• Nominal value: 50 or 60 Hz
Nominal, reference and
• Reference range: 40 to 70 Hz
operating values
• Operating range: 20 to 78 Hz
Temperature:
• Reference range: 15 to 30 °C (59 to 86 °F)

4921240563U EN Page 35 of 58
Category Specification

• Operating range: -40 to 70 °C (-40 to 158 °F)

Measurement range: 0.025 to 250 A AC. Truncation level: 20 mA


Accuracy:
• 0.025 to 20 A: ±1 % or ±10 mA of measured current (whichever is greater)
• 20 to 250 A: ±1.5 % of measured current
UL/cUL Listed: From listed or R/C (XODW2.8) current transformers 1 or 5 A
Current measurements Load on external current transformer: < 4 mΩ, including the terminal block
Current withstand:
• 20 A continuously
• 100 A for 10 s
• 400 A for 1 s
• 1250 A for 10 ms (half wave)

Frequency measurement Accuracy (within operating range): > 0.1 A: ±0.1 % of actual frequency

Current measurement accuracy temperature coefficient: ±0.25 %, or ±2.5 mA per 10 °C (18


Temperature
°F) outside reference range (whichever is greater)

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Secure the current measurement terminal block to the module faceplate: 0.25 N·m (2.2 lb-in)
Connection of wiring to terminals:
Torques and terminals
• ≤ 4 mm2: 0.5 N·m (4.4 lb-in) to 0.6 N·m (5.3 lb-in)
• > 4 mm2: 0.7 N·m (6.2 lb-in) to 0.8 N·m (7.1 lb-in)
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

AC current terminals: Standard 0º plugs, 6 mm2 with securing screws


Terminal connections
Wiring: 2.5 to 6 mm2 (13 to 10 AWG), multi-stranded

Galvanic isolation Between AC current and other I/Os: 2210 V, 50 Hz for 60 s

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 28 × 162 mm × 152 mm (1.1 × 6.4 × 5.9 in)

Weight 230 g (0.5 lb) (including terminal blocks)

Accessories (included) One roundel with 6 encoding pins (for the hardware module and terminal block)

3.3.5 Engine interface module EIM3.1

The engine interface module has its own power supply and a tacho input to measure speed. It also has four relay outputs,
four digital inputs, and three analogue inputs. These I/Os are configurable.

The power supply terminals include circuit protection against load dump transients and JEM177 surge transients (rugged
design). These terminals also include battery voltage measurement.

EIM3.1 has its own microprocessor. If the rack power supply fails, or connection to the application is lost, the EIM3.1 can
continue to operate independent of the application.

4921240563U EN Page 36 of 58
EIM3.1 terminals
Module Count Symbol Type Name

1 Ground Frame ground


EIM3.1
1 12 or 24 V DC Power supply
+
-
3 Relay output Configurable

1 * Relay output (with wire break detection) Configurable

4 Digital input Configurable


* 1 MPU input (with wire break detection)* Magnetic pickup

Generator tacho output or NPN/PNP


1 W W input (no wire break detection)*
sensor

3 Analogue current or resistance measurement input Configurable


COM
(RMI)
COM

W
R
I
R
I
R
I

COM

NOTE *These inputs cannot both be used at the same time.


EIM3.1 technical specifications
Category Specification

Voltage withstand: ±36 V DC to the power supply positive (terminal 1) and negative (terminal
Frame ground
2)

Input voltage: 12 or 24 V DC nominal (8 to 36 V DC continuously)


UL/cUL Listed: 10 to 32.5 V DC
0 V DC for 50 ms when coming from at least 8 V DC (cranking dropout)
Consumption: Typical 3 W, maximum 5 W
Internal protection: by 12 A fuse (not replaceable) (fuse size determined by load dump
requirements)
Auxiliary power supply Voltage withstand: ±36 V DC
Load dump protected by TVS diodes

Start current
• Power supply current limiter
◦ 24 V: 0.6 A minimum
◦ 12 V: 1.2 A minimum
• Battery: No limit

Relay outputs Relay type: Electromechanical


Electrical rating and UL/cUL Listed: 30 V DC and 6 A, resistive
Voltage withstand: ±36 V DC

Relay output with wire Relay type: Electromechanical


break detection Electrical rating and UL/cUL Listed: 30 V DC and 6 A, resistive
Includes wire break detection
* Voltage withstand: ±36 V DC

Magnetic pickup Voltage: 3 to 70 V AC peak


Frequency: 2 to 20,000 Hz

4921240563U EN Page 37 of 58
Category Specification

Accuracy: 2 to 99 Hz: 0.5 Hz; 100 to 20,000 Hz: ±0.5 % of measurement


Cable supervision: Resistance maximum 100 kΩ
Includes wire break detection
Voltage withstand: 70 V AC

Voltage: 8 to 36 V DC
Frequency: 2 to 20,000 Hz
Generator tacho (W)
W
Accuracy: 2 to 99 Hz: 0.5 Hz; 100 to 20,000 Hz: ±0.5 % of measurement
No wire break detection
Voltage withstand: ±36 V DC

Voltage: 8 to 36 V DC
Frequency: 2 to 20,000 Hz
NPN/PNP
W
Accuracy: 2 to 99 Hz: 0.5 Hz; 100 to 20,000 Hz: ±0.5 % of measurement
No wire break detection
Voltage withstand: ±36 V DC

Bipolar inputs
• ON: -36 to -8 V DC, and 8 to 36 V DC
Digital inputs • OFF: -2 to 2 V DC
Minimum pulse length: 50 ms
Impedance: 4.7 kΩ
Voltage withstand: ±36 V DC

Current input
• From active transmitter: 0 to 20 mA, 4 to 20 mA, or any custom range between 0 and 25
mA
• Accuracy: 1 % of selected range
Pt100/1000
• -40 to 250 °C (-40 to 482 °F)
• Accuracy: 1 % of full scale (to IEC/EN60751)
• Maximum sensor self-heating: 0.5 °C/mW (1 °F/mW)
Analogue multi-functional
Resistance measurement
inputs
• Any custom range between 0 and 2.5 kΩ
• Accuracy: 1 % over ranges: 0 to 200 Ω, 0 to 300 Ω, 0 to 500 Ω, 0 to 1000 Ω, and 0 to
2500 Ω
Digital input
• Dry contact with cable supervision
• Maximum circuit resistance: 330 Ω
• Minimum current rating for the connected relay: 2.5 mA
Voltage withstand: ±36 V DC
All analogue multi-functional inputs for EIM3.1 have a common ground

Frame ground and power supply


• Terminals: Standard 45° plug, 2.5 mm2
• Wiring: 1.5 to 2.5 mm2 (16 to 12 AWG), multi-stranded
Terminal connections
Other connections
• Terminals: Standard 45° plug, 2.5 mm2
• Wiring: 0.5 to 2.5 mm2 (22 to 12 AWG), multi-stranded

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Torques and terminals Connection of wiring to terminals: 0.5 N·m (4.4 lb-in)
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

Between relay groups and other I/Os: 600 V, 50 Hz for 60 s


Between digital input groups and other I/Os: 600 V, 50 Hz for 60 s
Galvanic isolation
Between MPU and W inputs and other I/Os: 600 V, 50 Hz for 60 s
Between analogue inputs and other I/Os: 600 V, 50 Hz for 60 s

4921240563U EN Page 38 of 58
Category Specification

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 28 × 162 × 150 mm (1.1 × 6.4 × 5.9 in)

Weight 250 g (0.5 lb)

3.3.6 Governor and AVR module GAM3.1

This governor and AVR module has four relay outputs, two analogue outputs and a pulse width modulation output, and two
analogue inputs. These I/Os are configurable.

GAM3.1 also has terminals for analogue load sharing (future use).

GAM3.1 terminals
Module Count Symbol Type Name

4 Relay output Configurable


GAM3.1

P
1 Load sharing Active power (P) (kW) load sharing (future use)
Q
1 Load sharing Reactive power (Q) (kvar) sharing (future use)

2 Analogue current or voltage output GOV/AVR/configurable

1 Pulse width modulation (PWM) output PWM output (with PWM ground)

2 Analogue current or voltage input Configurable

COM
Q

GAM3.1 technical specifications


Category Specification

Relay type: Electromechanical


Relay outputs Electrical rating and UL/cUL Listed: 250 V AC or 30 V DC, and 6 A, resistive; B300, pilot duty (B300 is
a power limit specification for inductive loads)
Altitude derating from 2,000 to 4,000 m (6,562 to 13,123 ft): Maximum 150 V AC phase-to-phase
Voltage withstand: 250 V AC

Load sharing Voltage input/output: -5 to 5 V DC


(future use) Impedance: 23.5 kΩ
P
Accuracy: 1 % of full scale, for both inputs and outputs
Q Voltage withstand: ±36 V DC

Analogue multi- Current output


functional outputs • -20 to 20 mA, or 0 to 20 mA, or 4 to 20 mA, or any custom range between -25 and 25 mA
• Accuracy: 1 % of the selected range (minimum range: 5 mA)

4921240563U EN Page 39 of 58
Category Specification

• 16-bit resolution over the range -25 to 25 mA


• Active output (internal supply)
• Maximum load: 400 Ω
Voltage output (DC)
• -10 to 10 V, 0 to 10 V, 0 to 5 V, -5 to 5 V, 0 to 3 V, -3 to 3 V, or 0 to 1 V, or any custom range
between -10 and 10 V
• Accuracy: 1 % of the selected range (minimum range: 1 V)
• 16-bit resolution over the range -10 to 10 V
• Minimum load: 600 Ω. Voltage output internal resistance: < 1 Ω
Voltage withstand: ±36 V DC
Controller power off: Internal resistance > 10 MΩ

Frequency: 500 Hz ±50 Hz


Resolution: 43,200 levels
Voltage:
• Low level: < 0.5 V
• High level: > 5.5 V
Pulse width
modulation • Maximum: 6.85 V
(PWM) output Output impedance: 100 Ω
Nominal temperature range: -40 to 70 °C (-40 to 158 °F)
Reference temperature range: 15 to 30 °C (59 to 86 °F)
Duty cycle accuracy (5 to 95 %): 0.25 % within reference temperature range
0.2 % of full scale additional error per 10 °C (18 °F) outside the reference range
Example: At 70 °C (158 °F) the accuracy of the PWM output is 0.25 % + 4 × 0.2 % = 1.05 %
Voltage withstand: ±30 V DC

Current inputs
• From active transmitter: 0 to 20 mA, 4 to 20 mA, or any custom range between 0 and 24 mA
Analogue multi- • Accuracy: 1 % of selected range
functional inputs Voltage inputs (DC)
• -10 to 10 V, 0 to 10 V, or any custom range between -10 and 10 V
• Accuracy: 1 % of selected range
Voltage withstand: ±36 V DC

Terminal Terminals: Standard 45° plug, 2.5 mm2


connections Wiring: 0.5 to 2.5 mm2 (22 to 12 AWG), multi-stranded

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Torques and
Connection of wiring to terminals: 0.5 N·m (4.4 lb-in)
terminals
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

Between individual relays and other I/Os: 2210 V, 50 Hz for 60 s


Between load sharing and other I/Os: 600 V, 50 Hz for 60 s
Between terminals 12 to 15 (analogue output 1, PWM output), and other I/Os: 600 V, 50 Hz for 60 s
Galvanic isolation • Analogue output 1 and the PWM output are galvanically connected
Between terminals 16, 17 (analogue output 2) and other I/Os: 600 V, 50 Hz for 60 s
Between terminals 18 to 21 (analogue inputs) and other I/Os: 600 V, 50 Hz for 60 s
• Analogue inputs 1 and 2 are galvanically connected

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 28 × 162 × 150 mm (1.1 × 6.4 × 5.9 in)

Weight 224 g (0.5 lb)

4921240563U EN Page 40 of 58
3.3.7 Governor and AVR module GAM3.2

This governor and AVR module has its own power supply, two analogue outputs and a pulse width modulation output, five
digital inputs, a status relay output, and four relay outputs. Apart from the status relay, all these I/Os are configurable.

GAM3.2 has its own microprocessor. If the rack power supply fails, GAM3.2 can continue to be used for manual operation if
it has its own, independent power supply. The power supply terminals include circuit protection against load dump
transients and JEM177 surge transients (rugged design). These terminals also include battery voltage measurement.

GAM3.2 terminals
Module Count Symbol Type Name

1 Ground Frame ground


GAM3.2
1 12 or 24 V Power supply
+
- 2 Analogue current or voltage output GOV/AVR/configurable

1 Pulse width modulation (PWM) output PWM output


COM
5 Digital input Configurable

1 Relay output GAM3.2 status

COM

4 Relay output Configurable

GAM3.2 technical specifications


Category Specification

Input voltage: 12 or 24 V DC nominal (8 to 36 V DC continuously)


UL/cUL Listed: 10 to 32.5 V DC
0 V DC for 50 ms when coming from at least 8 V DC (cranking dropout)
Consumption: Typical 3 W, maximum 5 W
Voltage measurement accuracy: ±0.1 V (measurement range 8 to 36 V DC)
Internally protection: 12 A fuse (not replaceable) (fuse size determined by load dump requirements)
Auxiliary power Voltage withstand: ±36 V DC
supply Load dump protected by TVS diodes

Start current
• Power supply current limiter
◦ 24 V: 0.6 A minimum
◦ 12 V: 1.2 A minimum
• Battery: No limit

Analogue multi- Current output


functional
• Any custom range between -25 and 25 mA
outputs
• Accuracy: 1 % of the selected range (minimum range: 5 mA)

4921240563U EN Page 41 of 58
Category Specification

• 16-bit resolution
• Active output (internal supply)
• Maximum load: 400 Ω
Voltage output (DC)
• Any custom range between -10 and 10 V
• Accuracy: 1 % of the selected range (minimum range: 1 V)
• 16-bit resolution
• Minimum load: 600 Ω. Voltage output internal resistance: < 1 Ω.
Voltage withstand: ±36 V DC
Controller power off: Internal resistance > 10 MΩ

Frequency: 500 Hz ±50 Hz


Resolution: 43,200 levels
Voltage:
• Low level: < 0.5 V
• High level: > 5.5 V
Pulse width
modulation • Maximum: 6.85 V
(PWM) output Output impedance: 100 Ω
Nominal temperature range: -40 to 70 °C (-40 to 158 °F)
Reference temperature range: 15 to 30 °C (59 to 86 °F)
Duty cycle accuracy (5 to 95 %): 0.25 % within reference temperature range
0.2 % of full scale additional error per 10 °C (18 °F) outside the reference range
Example: At 70 °C (158 °F) the accuracy of the PWM output is 0.25 % + 4 × 0.2 % = 1.05 %
Voltage withstand: ±30 V DC

Bipolar inputs
• ON: -36 to -8 V DC, and 8 to 36 V DC
Digital inputs • OFF: -2 to 2 V DC
Minimum pulse length: 50 ms
Impedance: 4.7 kΩ
Voltage withstand: ±36 V DC

Relay output
Relay type: Solid state
(GAM3.2 status)
Electrical rating and UL/cUL Listed: 30 V DC and 1 A, resistive
Voltage withstand: ±36 V DC

Relay type: Electromechanical


Relay outputs Electrical rating and UL/cUL Listed: 250 V AC or 30 V DC, and 6 A, resistive; B300, pilot duty (B300 is
a power limit specification for inductive loads)
Altitude derating from 2,000 to 4,000 m (6,562 to 13,123 ft): Maximum 150 V AC phase-to-phase
Voltage withstand: 250 V AC

Frame ground and power supply


• Terminals: Standard 45° plug, 2.5 mm2
• Wiring: 1.5 to 2.5 mm2 (16 to 12 AWG), multi-stranded
Analogue inputs, PWM, digital inputs and the status relay
Terminal
• Terminals: Standard 45° plug, 1.5 mm2
connections
• Wiring: 0.5 to 1.5 mm2 (28 to 16 AWG), multi-stranded
Relay outputs
• Terminals: Standard 45° plug, 2.5 mm2
• Wiring: 0.5 to 2.5 mm2 (22 to 12 AWG), multi-stranded

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Torques and Connection of wiring to frame ground and power supply terminals: 0.5 N·m (4.4 lb-in)
terminals Connection of wiring to analogue inputs, PWM, digital inputs, and the status relay terminals: 0.25 N·m
(2.2 lb-in)

4921240563U EN Page 42 of 58
Category Specification

Connection of wiring to relay output terminals: 0.5 N·m (4.4 lb-in)


UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

Between power supply and other I/Os: 600 V, 50 Hz for 60 s


Between analogue inputs, PWM, digital inputs, and the status relay, and other I/Os: 600 V, 50 Hz for
60 s
Galvanic isolation
The analogue output on terminals 5 and 6 is galvanically connected to the PWM output (terminals 6
and 7)
Between relay groups and other I/Os: 2210 V, 50 Hz for 60 s

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 28 × 162 × 150 mm (1.1 × 6.4 × 5.9 in)

Weight 246 g (0.5 lb)

3.3.8 Input/output module IOM3.1

The input output module has 4 changeover relay outputs, and 10 digital inputs. These I/Os are all configurable.

IOM3.1 terminals
Module Count Symbol Type Name

IOM3.1 4 Relay output Configurable

10 Digital input Configurable

COM

IOM3.1 technical specifications


Category Specification

Relay type: Electromechanical


Relay outputs Electrical rating and UL/cUL Listed: 250 V AC or 30 V DC, and 6 A, resistive; B300, pilot duty
(B300 is a power limit specification for inductive loads)
Altitude derating from 3,000 to 4,000 m (9,842 to 13,123 ft): Maximum 150 V AC phase-to-
phase
Voltage withstand: 250 V AC

Digital inputs Bipolar inputs

4921240563U EN Page 43 of 58
Category Specification

• ON: -36 to -8 V DC, and 8 to 36 V DC


• OFF: -2 to 2 V DC
Minimum pulse length: 50 ms
Impedance: 4.7 kΩ
Voltage withstand: ±36 V DC

Relay outputs: Terminals: Standard 45° plug, 2.5 mm2


Wiring: 0.5 to 2.5 mm2 (22 to 12 AWG), multi-stranded
Terminal connections
Digital inputs: Terminals: Standard 45° plug, 1.5 mm2
Wiring: 0.1 to 1.5 mm2 (28 to 16 AWG), multi-stranded

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Connection of wiring to relay output terminals: 0.5 N·m (4.4 lb-in)
Torques and terminals
Connection of wiring to digital input terminals: 0.25 N·m (2.2 lb-in)
UL/cUL Listed: Wiring must be minimum 90 ºC (194 °F) copper conductors only

Between relay groups and other I/Os: 2210 V, 50 Hz for 60 s


Galvanic isolation
Between digital input groups and other I/Os: 600 V, 50 Hz for 60 s

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 28 × 162 × 150 mm (1.1 × 6.4 × 5.9 in)

Weight 196 g (0.4 lb)

3.3.9 Input/output module IOM3.2

The input output module has 4 relay outputs, 4 analogue multifunctional outputs (including 2 pulse width modulation PWM
outputs), 4 digital inputs, and 4 analogue multifunctional inputs. These I/Os are all configurable.

Internal cold junction compensation is not available on IOM3.2

IOM3.2 terminals
Module Count Symbol Type Name

4 Relay output Configurable


IOM3.2

2 Analogue multifunctional output (mA, V DC, PWM) Configurable

2 Analogue multifunctional output (mA, V DC) Configurable

4 Digital input Configurable

4 Analogue multifunctional input (mA, V DC, RMI) Configurable

COM

4921240563U EN Page 44 of 58
IOM3.2 technical specifications
Category Specification

Relay type: Solidestate relay


Relay outputs
Electrical rating and UL/cUL Listed: 30 V DC, and 6 A, resistive; B300, pilot duty (B300 is a
power limit specification for inductive loads)
Voltage withstand: ±36 V DC

Current output:
• Range: Any custom range between -25 to 25 mA DC
• Accuracy: 1 % of range
• Resolution: 16 bits (< 2 uA / bit)
• Type: Active output (internal supply)
• Load: Maximum ±25 mA -> 400 Ω
Voltage output:
Analogue multifunctional
• Range: Any custom range between -10 to 10 V DC
outputs
• Accuracy: 1 % of range
• Resolution: 16 bits (< 0,7 mV / bit)
• Load: Minimum ±10V -> 600 Ω
• Internal resistance, power ON: < 1 Ω
• Internal resistance, power OFF: > 10 MΩ
General information for all outputs:
• Refresh rate (max): 50ms (input to output)
• Voltage withstand: ±36 V DC

PWM output:
• Frequency range: 1 to 2500 Hz ±5 Hz
• Duty cycle accuracy (5 to 95 %): 0.5 % within reference temperature range
Analogue multifunctional • Resolution: 12 bits (4096 steps)
PWM outputs • Voltage: Low level: < 0.5 V. High level: > adjustable 1 to 10 V. Maximum: 10.2 V
• Output impedance: 25 Ω
General information for all outputs:
• Refresh rate (max): 50 ms (input to output)
• Voltage withstand: ±36 V DC

Bipolar inputs
• ON: -36 to -8 V DC, and 8 to 36 V DC
Digital inputs • OFF: -2 to 2 V DC
Minimum pulse length: 50 ms
Impedance: 3.9 kΩ
Voltage withstand: ±36 V DC

Digital inputs with wire break detection:


• Dry contact inputs, 3 V DC internal supply
• Wire-break detection with maximum resistance for ON detection: 100 Ω to 400 Ω
Current inputs:
• From active transmitter: 0 to 20 mA, or 4 to 20 mA
Analogue multifunctional
• Accuracy: ±10 uA ±0.25 % of actual reading
inputs
Voltage inputs (DC):
• Range: ±10 V DC / 0 to 10 V DC
• Accuracy: ±10 mV ±0.25 % of actual reading
Resistance measurement inputs, 2 wire (RMI):
• Resistance measurement: 0 to 4.5 kΩ
• Accuracy: ±1 Ω ±0.25 % of actual reading

4921240563U EN Page 45 of 58
Category Specification

Resistance measurement inputs, 1 wire (RMI):


• Resistance measurement: 0 to 4.5 kΩ
• Accuracy: ±2 Ω ±0.25 % of actual reading
Pt100:
• Range: -200 to 850 °C
• Accuracy: ±1 °C ±0.25 % of actual reading
Pt1000:
• Range: -200 to 850 °C
• Accuracy: ±0.5 °C ±0.25 % of actual reading
Thermocouple type, range and accuracy:
• E: -200 to 1000 °C ( ±2 °C ±0.25 % of actual reading)
• J: -210 to 1200 °C ( ±2 °C ±0.25 % of actual reading)
• K: -200 to 1372 °C ( ±2 °C ±0.25 % of actual reading)
• N: -200 to 1300 °C ( ±2 °C ±0.25 % of actual reading)
• R: -50 to 1768 °C ( ±2 °C ±0.25 % of actual reading)
• S: -50 to 1768 °C ( ±2 °C ±0.25 % of actual reading)
• T: -200 to 400 °C ( ±2 °C ±0.25 % of actual reading)
Note: Twisted pair and shielded cable is recommended to achieve specification and
optimisation of noise immunity.
General information for all outputs:
• Refresh rate (max): 50 ms (input to output)
• Voltage withstand: ±36 V DC
• All analogue multi-functional inputs have a common ground

Relay outputs: Terminals: Standard 45° plug, 2.5 mm2


Wiring: 0.5 to 2.5 mm2 (22 to 14 AWG), multi-stranded
Terminal connections
Other inputs: Terminals: Standard 45° plug, 1.5 mm2
Wiring: 0.1 to 1.5 mm2 (28 to 16 AWG), multi-stranded

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Connection of wiring to relay output terminals: 0.5 N·m (4.4 lb-in)
Torques and terminals
Connection of wiring to digital input terminals: 0.25 N·m (2.2 lb-in)
UL/cUL Listed: Wiring must be minimum 90 ºC (194 °F) copper conductors only

Between relay groups and other I/Os: 2210 V, 50 Hz for 60 s


Galvanic isolation
Between other input groups and other I/Os: 600 V, 50 Hz for 60 s

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 28 × 162 × 150 mm (1.1 × 6.4 × 5.9 in)

Weight 188 g (0.4 lb)

3.3.10 Input/output module IOM3.3

The input output module has 10 analogue multifunctional inputs. These I/Os are all configurable.

4921240563U EN Page 46 of 58
IOM3.3 terminals
Module Count Symbol Type Name

IOM3.3

A
B
C
A
B
C
A
B
C
A
B
C
A
B A
C
10 B Analogue multifunctional inputs (mA, V DC, RMI) Configurable
A
B C
C
A
B
C
A
B
C
A
B
C
A
B
C

IOM3.3 technical specifications


Category Specification

Digital inputs with wire break detection:


• Dry contact inputs, 3 V DC internal supply
• Wire-break detection with maximum resistance for ON detection: 100 Ω to 400 Ω
Current inputs:
• From active transmitter: 0 to 20 mA, or 4 to 20 mA
• Accuracy: ±10 uA ±0.25 % of actual reading
Voltage inputs (DC):
• Range: ±10 V DC / 0 to 10 V DC
• Accuracy: ±10 mA ±0.25 % of actual reading
Resistance measurement inputs, 2 or 3 wire (RMI):
Analogue multifunctional • Resistance measurement: 0 to 4.5 kΩ
inputs
• Accuracy: ±1 Ω ±0.25 % of actual reading *
A
B Resistance measurement inputs, 1 wire (RMI):
C • Resistance measurement: 0 to 4.5 kΩ
• Accuracy: ±2 Ω ±0.25 % of actual reading
Pt100:
• Range: -200 to 850 °C
• Accuracy: ±1 °C ±0.25 % of actual reading
Pt1000:
• Range: -200 to 850 °C
• Accuracy: ±0.5 °C ±0.25 % of actual reading
Thermocouple type, range and accuracy:
• E: -200 to 1000 °C ( ±2 °C ±0.25 % of actual reading)
• J: -210 to 1200 °C ( ±2 °C ±0.25 % of actual reading)

4921240563U EN Page 47 of 58
Category Specification

• K: -200 to 1372 °C ( ±2 °C ±0.25 % of actual reading)


• N: -200 to 1300 °C ( ±2 °C ±0.25 % of actual reading)
• R: -50 to 1768 °C ( ±2 °C ±0.25 % of actual reading)
• S: -50 to 1768 °C ( ±2 °C ±0.25 % of actual reading)
• T: -200 to 400 °C ( ±2 °C ±0.25 % of actual reading)
Note: Twisted pair and shielded cable is recommended to achieve specification and
optimisation of noise immunity.
General information for all inputs:
• Voltage withstand: ±36 V DC

Internal temperature sensor:


• Range: 0 to 70 °C
◦ Accuracy: ±1.0 °C
• Range: -40 to 0 °C
◦ Accuracy: ±2.0 °C
Mathematical compensation:
• If non channels are configured as 4-20 mA
◦ Accuracy: ±1.0 °C
• If any channels are configured as 4-20 mA
Internal cold junction ◦ Accuracy: ±1.5 °C
compensation (CJC)
If it is needed to have 4-20 mA channels on the same card, it is recommended to use the top
channels for 4-20 mA and the lower channels for TC’s
Internal cold junction accuracy:
• Heat dissipated by nearby heat sources can cause errors in thermocouple measurements
by heating the IOM3.3 terminals to a different temperature than the cold-junction
compensation sensor. Thermal gradient across the terminals can cause the terminals of
different IOM3.3 channels to be at different temperatures, which creates accuracy errors
and affects the relative accuracy between channels.
• The temperature measurement accuracy specifications include errors caused by the
thermal gradient across the IOM3.3 terminals for configurations with the IOM3.3
terminals facing forward or upward.

Terminals: Standard 45° plug, 1.5 mm2


Terminal connections
Wiring: 0.1 to 1.5 mm2 (28 to 16 AWG), multi-stranded

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Connection of wiring to relay output terminals: 0.5 N·m (4.4 lb-in)
Torques and terminals
Connection of wiring to input terminals: 0.25 N·m (2.2 lb-in)
UL/cUL Listed: Wiring must be minimum 90 ºC (194 °F) copper conductors only

All 10 multi inputs have a common ground


Galvanic isolation
Galvanic isolation from rack: 600 V, 50 Hz for 60 s

Dimensions L×H×D: 28 × 162 × 150 mm (1.1 × 6.4 × 5.9 in)

Weight 164 g (0.4 lb)

3.3.11 Input/output module IOM3.4

The input output module has 12 digital outputs, and 16 digital inputs. These I/Os are all configurable.

4921240563U EN Page 48 of 58
IOM3.4 terminals
Module Count Symbol Type Name

12 Digital output Configurable


IOM3.4
16 Digital input Configurable
+

COM

COM

IOM3.4 technical specifications


Category Specification

Transistor type: PNP


Supply voltage: 12 or 24 V DC nominal, maximum 36 V DC (relative to common)
Maximum current (per output): < 55 °C: 250 mA; > 55 °C: 200 mA
Leak current: Typical 1 µA, maximum 100 µA (temperature-dependent)
Digital outputs Saturation voltage: Maximum 0.5 V
Non-replaceable 4 A fuse
Voltage withstand: ±36 V DC
Load dump protected by TVS diodes
Short circuit protection
Reverse polarity protection
Internal freewheeling diode

Bipolar inputs
• ON: -36 to -8 V DC, and 8 to 36 V DC
Digital inputs • OFF: -2 to 2 V DC
Minimum pulse length: 50 ms
Impedance: 4.7 kΩ
Voltage withstand: ±36 V DC

Terminals: Standard 45° plug, 1.5 mm2


Terminal connections
Wiring: 0.1 to 1.5 mm2 (28 to 16 AWG), multi-stranded

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Torques and terminals Connection of wiring to terminals: 0.25 N·m (2.2 lb-in)
UL/cUL Listed: Wiring must be minimum 90 ºC (194 °F) copper conductors only

Galvanic isolation Between groups: 600 V, 50 Hz for 60 s

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

4921240563U EN Page 49 of 58
Category Specification

Dimensions L×H×D: 28 × 162 × 150 mm (1.1 × 6.4 × 5.9 in)

Weight 175 g (0.4 lb)

3.3.12 Processor and communication module PCM3.1

The processor and communication module has the controller's main microprocessor, which contains and runs the controller
application software. It includes the Ethernet switch to manage the controller Ethernet connections, with five 100BASE-TX

Ethernet connections. It has a Self-check OK LED. It also has two sets of CAN bus terminals and SD card. The PCM3.1
performs time synchronisation with an NTP server.

PCM3.1 terminals
Module Count Symbol LED Type Name

5 Off : No communication Ethernet (RJ45) External network


PCM3.1 and DEIF network
Green : Communication connected
1 LEDs on the front
2
Green flash : Active communication of the hardware
H
module. Two
CAN-A

L
connections at
H the top of the
CAN-B

L
hardware module,
one on the front,
CAN-A

CAN-B and two at the


bottom.

2 H, CAN-A, L Off : No communication CAN bus CAN bus


H, CAN-B, L connection
Green : CAN connected
Green flash : Active CAN communication

1 Off : Self-check not OK


3
Green : Self-check OK
Green flash : In service mode
4

5 1 Off : No access SD card (industrial External memory


grade) *
Green flash : Read or write to SD card

NOTE * To meet the temperature and EMC specifications, you must use an industrial grade SD card.

PCM3.1 technical specifications


Category Specification

CAN terminals Voltage withstand: ±24 V DC

Between CAN A and other I/Os: 600 V, 50 Hz for 60 s


Galvanic isolation Between CAN B and other I/Os: 600 V, 50 Hz for 60 s
Between Ethernet ports and other I/Os: 600 V, 50 Hz for 60 s

RTC Real time clock with replaceable lithium battery (replacement recommended every 5 years).

CAN communication terminals: Standard 45° plug, 1.5 mm2


Communication Wiring: 0.5 to 1.5 mm2 (28 to 16 AWG), multi-stranded
connections DEIF network: RJ45. Use an Ethernet cable that meets or exceeds the SF/UTP CAT5e
specifications. 100BASE-TX.

Module faceplate screws: 0.5 N·m (4.4 lb-in)


Torques and terminals Connection of wiring to terminals: 0.5 N·m (4.4 lb-in)
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

4921240563U EN Page 50 of 58
Category Specification

Processor 400 MHz 32-bit PowerPC CPU

Memory 256 MB

Storage 512 MB

Unmounted: No protection rating


Ingress protection
Mounted in rack: IP20 according to IEC/EN 60529

Dimensions L×H×D: 36.8 × 162 × 150 mm (1.4 × 6.4 × 5.9 in)

Weight 214 g (0.5 lb)

3.3.13 Blind module

A blind module must be used to close off each empty slot in the rack.

Blind module technical specifications


Category Specification

Tightening torque Module faceplate screws: 0.5 N·m (4.4 lb-in)

Dimensions L×H×D: 28 × 162 × 18 mm (1.1 × 6.4 × 0.7 in)

Weight 44 g (0.1 lb)

4921240563U EN Page 51 of 58
3.4 Display unit DU 300 specifications
3.4.1 Display unit DU 300

218.2 mm (8.6 in)

52.4 mm
(2.1 in)

43.3 mm
(1.7 in)

157.9 mm (6.22 in)


173.4 mm (6.8 in)

233.4 mm (9.2 in)


8.0 mm
(0.3 in)

Dimensions and weight specifications


Category Specifications

L×H×D: 233.4 × 173.4 × 52.4 mm (9.2 × 6.8 × 2.1 in) (outer frame)
Dimensions
Panel cutout, L×H: 220 × 160 mm (8.7 × 6.3 in)

Weight 835 g (1.8 lb)

Technical specifications
Category Specifications

From the front: IP65 according to IEC/EN 60529


Ingress protection
From the back: IP20 according to IEC/EN 60529

UL/cUL Listed Type Complete Device, Open Type 1

Frame ground Voltage withstand: ±36 V DC to the power supply positive (terminal 1) and negative (terminal 2)

Input voltage: 12 or 24 V DC nominal (8 to 36 V DC continuously)


UL/cUL Listed: 10 to 32.5 V DC
Power supply 0 V DC for 50 ms when coming from at least 8 V DC (cranking dropout)
Consumption: Typical 4 W, maximum 12 W
Internal protection: 12 A slow-blow fuse (not replaceable) (fuse size determined by load dump
requirements)
Voltage withstand: ±36 V DC

4921240563U EN Page 52 of 58
Category Specifications

Load dump protected by TVS diodes

Start current
• Power supply current limiter
◦ 24 V: 2.1 A minimum
◦ 12 V: 4.2 A minimum
• Battery: No limit

Relay output Relay type: Electromechanical


Electrical rating and UL/cUL Listed: 30 V DC and 1 A, resistive
Voltage withstand: ±36 V DC

Relay output Relay type: Solid state


Electrical rating and UL/cUL Listed: 30 V DC and 1 A, resistive
Voltage withstand: ±36 V DC

Frame ground and power supply:


• Terminals: Standard plug, 2.5 mm2
• Wiring: 1.5 to 2.5 mm2 (16 to 12 AWG), multi-stranded
Terminal connections
Other connections:
• Terminals: Standard plug, 2.5 mm2
• Wiring: 0.5 to 2.5 mm2 (22 to 12 AWG), multi-stranded

Communication DEIF network: RJ45. Use an Ethernet cable that meets or exceeds the SF/UTP CAT5e
connections specifications, 100BASE-TX

Display unit fixing screw clamps: 0.15 N·m (1.3 lb-in)


Torques and terminals Connection of wiring to terminals: 0.5 N·m (4.4 lb-in)
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only

Galvanic isolation Between power supply, relay groups, and network plugs: 600 V, 50 Hz for 60 s

3.5 Accessory specifications


3.5.1 Ethernet cable

The Ethernet cable from DEIF meets the technical specifications below.

Category Specification

Cable type Shielded patch cable SF/UTP CAT5e

Fixed installation: -40 to 80 ºC (-40 to 176 °F)


Temperature
Flexible installation: -20 to 80 ºC (-4 to 176 °F)

Minimum bending radius Fixed installation: 25.6 mm (1.01 in)


(recommended) Flexible installation: 51.2 mm (2.02 in)

Length 2 m (6.6 ft)

Weight ~110 g (4 oz)

4921240563U EN Page 53 of 58
4. Ordering

4.1 PPU 300 controller ordering


Controller hardware configuration, standard controller
Each controller is always supplied with a PSM3.1, ACM3.1 and PCM3.1 module. Depending on the controller type ordered,
other modules are added. The factory selection of additional modules can be made when ordering.

A display unit can be ordered directly along with the controller (see type selection in table 4.4).

Standard controller without CODESYS


The standard controller can via display or PC software PICUS be selected to be one of the following types:
• Diesel generator controller.
• Shaft generator controller.
• Bus tie breaker controller.
• Shore connection controller.

Rack size: 7-slot Item number: 2912210060.01


Rack size: 4-slot Item number: 2912210060.07

Table 4.1 Controller configuration, standard controller without CODESYS

Rack Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7

IOM3.1/ GAM3.1/
R7.1 PSM3.1 ACM3.1 Selectable Selectable PCM3.1
Selectable Selectable
IOM3.1/
R4.1 PSM3.1 ACM3.1 PCM3.1 N/A N/A N/A
Selectable

Standard controller with CODESYS

Rack size: 7-slot Item number: 2912210060.06


Rack size: 4-slot Item number: 2912210060.09

Table 4.2 Controller configuration, standard controller with CODESYS

Rack Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7

R7.1 PSM3.1 ACM3.1 Selectable Selectable Selectable Selectable PCM3.1


R4.1 PSM3.1 ACM3.1 Selectable PCM3.1 N/A N/A N/A

Controller Hardware, Hybrid controller


The Hybrid controller can be used as a battery bank (ESS, Energy Storage System) controller, controlling the battery
inverter. It can also be used for a shaft generator, provided it is fitted with an inverter.

A display unit can be ordered along with the controller (see type selection in table 4.4).

Rack size: 7-slot Item number: 2912210060.13

4921240563U EN Page 54 of 58
Table 4.3 Controller configuration, Hybrid controller

Rack Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7

IOM3.1/ GAM3.1/
R7.1 PSM3.1 ACM3.1 Selectable Selectable PCM3.1
Selectable Selectable

Display unit selection


These selections are for standard unit displays. The Hybrid controller display always comes with the Hybrid folio.

Table 4.4 Display unit selection

Options Folio * Notes

Blank display unit folio.


Blank Used for: Read data only, no breaker feedback, no
control.

Display unit folio with application LEDs.


CB w/o CTRL Used for: Read data and see status and position, no
control.

Display unit folio with breaker push-buttons.


Used for:
CB CTRL • Shaft generator control.
• Bus tie breaker control.
• Shore connection control.

Display unit folio with full functionality.


DG + CB CTRL
Used for: Generator control.

Display unit folio with full functionality.


HYBRID
Used for: Inverter control.

NOTE * Only bottom part of display is shown, the top part is always the same.

4.2 Extension rack ordering


The Extension rack comes as standard with PSM3.2 module mounted.

Extension rack configuration

Rack size: 7-slot or 4-slot Item number: 2912990350.01

Table 4.5 Extension rack configuration

Rack Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7

R7.1 PSM3.2 Selectable Selectable Selectable Selectable Selectable Selectable


R4.1 PSM3.2 Selectable Selectable Selectable N/A N/A N/A

4921240563U EN Page 55 of 58
4.3 Modules for controller configuration
The following table lists parts/accessories/spare parts for a PPU 300 controller.

Module Terminals Comment Item no. Options

Blank

CB w/o CTRL

DU 300 - Display unit for PPU 300. 2912990240.01 CB CTRL

DG + CB CTRL

HYBRID

7-slot rack for use as


R7.1 - controller or extension 2912990240.09 -
rack.

4-slot rack for use as


R4.1 - controller or extension 2912990240.41 -
rack.

Power Supply Module (main rack)


• 1 × Power supply For use in controller
PSM3.1 2912990240.07 -
• 3 × Relay outputs (2 x configurable) rack.
• 2 × RJ45 EtherCAT communication ports

Power Supply Module (extension rack)


• 1 × Power supply For use in extension
PSM3.2 2912990240.42 -
• 3 × Relay outputs (2 x configurable) racks.
• 2 × RJ45 EtherCAT communication ports

A maximum of one
AC voltage and current module ACM3.1 module is
ACM3.1 • 2 × 3-phase voltage measurements allowed per controller 2912990240.03 -
• 1 × 3-phase and 4th current measurements (including extension
racks).

Differential current module


• 1 x 3-phase current measurement - A maximum of one
Consumer side ACM3.2 module is
2912990240.40
ACM3.2 allowed per controller -
• 1 x 3-phase current measurement - Neutral
(including extension
side
racks).

Input Output Module


IOM3.1 • 4 × Changeover relays 2912990240.05 -
• 10 × Digital inputs

Input Output Module


• 4 × Relay outputs
• 2 × Analogue multifunctional outputs (mA, V
DC, PWM)
2912990240.44
IOM3.2 • 2 × Analogue multifunctional outputs (mA, V -
DC)
• 4 x Digital inputs
• 4 x Analogue multifunctional inputs (mA, V
DC, RMI)

IOM3.3 Input Output Module 2912990240.45 -

4921240563U EN Page 56 of 58
Module Terminals Comment Item no. Options

• 10 x Analogue multifunctional inputs (mA, V


DC, RMI)

Input Output Module


IOM3.4 • 12 × Transistor outputs 2912990240.25 -
• 16 × Digital inputs

Engine Interface Module


• 1 × Power supply
• 4 × Relay outputs (1 with wire break A maximum of three
detection) EIM3.1 modules are
EIM3.1 allowed per controller 2912990240.04 -
• 4 × Digital inputs
(including extension
• 1 × MPU input units).
• 1 × W input
• 3 × Current/resistance analogue inputs

Governor and AVR Module


A maximum of three
• 4 × Relay outputs GAM3.1 and/or GAM3.2
GAM3.1 • 2 × Current/voltage analogue outputs modules are allowed per 2912990240.06 -
• 1 × PWM output controller (including
extension units).
• 2 × Current/voltage analogue inputs

Governor and AVR Module


• 1 × Power supply A maximum of three
GAM3.1 and/or GAM3.2
• 2 × Current/voltage analogue outputs
GAM3.2 modules are allowed per 2912990240.26 -
• 1 × PWM output
controller (including
• 5 × Digital inputs extension units).
• 5 × Relay outputs

Processor and Communication Module


• 5 × Ethernet communication ports 2912990240.46
PCM3.1 -
• 2 × CAN bus connections
• 1 × SD card slot

Not allowed between


Blind Blind module PSM3.1 and the optional 2912990240.08 -
modules.

Blind One needed for 2912990240.43


Small blind module -
small extension rack

Shielde
d patch - SF/UTP CAT5e 2912990240.14 -
cable

Terminal
Terminal blocks for Multi-line 300 2912990240.38 -
blocks

4921240563U EN Page 57 of 58
5. Legal information

5.1 Disclaimer and copyright


Open source software

This product contains open source software licensed under, for example, the GNU General Public License (GNU GPL) and
GNU Lesser General Public License (GNU LGPL). The source code for this software can be obtained by contacting DEIF at
[email protected]. DEIF reserves the right to charge for the cost of the service.

Trademarks

DEIF and the DEIF logo are trademarks of DEIF A/S.


Bonjour® is a registered trademark of Apple Inc. in the United States and other countries.
Adobe®, Acrobat®, and Reader®are either registered trademarks or trademarks of Adobe Systems Incorporated in the
United States and/or other countries.
CANopen® is a registered community trademark of CAN in Automation e.V. (CiA).
SAE J1939® is a registered trademark of SAE International®.
CODESYS® is a trademark of CODESYS GmbH.
EtherCAT®, EtherCAT P®, Safety over EtherCAT®, are trademarks or registered trademarks, licensed by Beckhoff
Automation GmbH, Germany.
Modbus® is a registered trademark of Schneider Automation Inc.
Windows® is a registered trademark of Microsoft Corporation in the United States and other countries.

All trademarks are the properties of their respective owners.

Copyright
© Copyright DEIF A/S. All rights reserved.

Disclaimer

DEIF A/S reserves the right to change any of the contents of this document without prior notice.

The English version of this document always contains the most recent and up-to-date information about the product. DEIF
does not take responsibility for the accuracy of translations, and translations might not be updated at the same time as the
English document. If there is a discrepancy, the English version prevails.