Lecture 6 - Rev 01 - Jan 2018 - Trafo - Diff
Lecture 6 - Rev 01 - Jan 2018 - Trafo - Diff
EE 442
Prepared by
Dr. Khaled El Bahrawy
Lecture #6
Transformer Protection
Contents
1 Differential Protection
2 Transformer protection
- During both normal conditions and external faults (Through fault conditions), the
protection system is balanced. The current vectors entering the Differential relay
I1 – I 2 = 0
Principle of circulating current Differential protection
Internal fault conditions
- During fault conditions, the protection system is unbalanced. The current vectors
entering the Differential relay I1 – I2 ≠ 0
2 – Transformer Protection
Transformers are one of the most important equipment in the electric network due to
the following facts:
- Maintenance of transformers may take a lot of time which affect the supply to the
consumers.
Transformer Faults
Transformer
Protection
1. Mechanical 2. Electrical
protection protection
A 3ph, 66/11kV Y/∆ transformer is protected by differential relays. The CTs of ∆ side is
420/5A. Find the CTs ratio on the Y side.
Solution 1
Solution 3
Example 4
3Ph, 42MVA, 69/12.5kV, ∆/YGrounded transformer has a load tap changer of ±10%. The
transformer is protected by a differential relay. The relay connection is as shown in the
below figure
The relay has a taps of 5.0, 5.5, 6.0, 6.6, 7.3, 8.0, 9.0 and 10.0. The relay is
nominally a 50% percentage differential relay which means that the
operating current must be at least 50% of the restraining current to cause
tripping. Determine the current transformer ratios and select an appropriate
tap setting of this relay.
Solution 4
Accordingly,
I69kV_Sec = 351 x (5/400) = 4.39 A
Accordingly,
I12.5kV_Sec = 1940 x (5*SQRT(3)/2000) = 8.4 A
Solution 4 (Cont.)
Assume tap #5 is used for 69kV side & tap x for 12.5kV side
Then,
X = 9.57