PCS – 9567

Integrated Medium Voltage Skid

Plug & Play power conversion system


adapted to client specifications and
standards

Designed for Grid Reliability and Resilience Investment with Higher Returns
 Compressed construction lead-times through factory integrated
 Full four-quadrant operation with bidirectional power conversion system
solution.
 State of the art three-level technology with max.conversion efficiency 99%.
 Reduced off-loading, on-site labor expense and transportation cost.
 Full power operation at 1500V and wide DC voltage operation range.
 Enhanced system reliability owing to reliable and qualified designs.
 Suitable for most local standards and severe environmental conditions.
 Endured extensive quality, safety and reliability.

Product Applications
Easy to Install and Service
 Typical applications - energy shifting, frequency regulation, peak shaving
 Fully monitored solution for online analysis and fast troubleshooting.
 Grid forming control, reactive power control, L/HVRT, L/HFRT, soft
 Convenient modular design provides easy access to all components for
start/stop, and specified power factor control.
maintenance purposes.
 Compliant with CE, TUV, ISO, UL1741, IEC62477 and G99 etc.
 40 feet container for ease of shipment and installation worldwide.
 Multiple communication interfaces such as CAN, RS485 and Ethernet
 Pre-assembled solution, configured & tested to reduce on-site labor and
project duration.
Technical Parameters | NR MEDIUM VOLTAGE SKID DATASHEET

PCS SKID GENERAL

Transformer
Transformer Model Oil type[1]

Transformer Vector Dy11-y11


● ○
Protection Level IP54 / IP55

Anti- corrosion Grade C4-H


● [2] ○ ○
/ C4-VH / C5-M / C5-H / C5-VH
○ ○

Cooling Method ●
ONAN / ONAF

Oil Retention Tank ●


None / Galvanized steel
○ [3]

● ○
Winding Material Aluminum / Copper
● ○
Transformer Oil 25# /45# mineral oil / Natural ester insulation oil

Transformer Efficiency ●
IEC standard / IEC Tier-2

MV Operating Voltage Range (V) 6.6~33kV±10%

Power Factor Range 0.9 (Leading) ~ 0.9 (Lagging)[4]

Nominal Frequency (Hz) 50 / 60 Hz

Operating Frequency (Hz) 45~55 / 55~65 Hz

Connection Phases Three-phase-three-wire

Switchgear
Switchgear Type Ring Main Unit, CCV [5]

Rated Operating Current 630A

Switchgear Short Circuit Rating 20kA 1s

Switchgear IAC A FL 20kA 1S

Protection
DC Input Protection Disconnector + Fuse inside of inverter

AC Output Protection Motorized Circuit breaker inside of Inverter

DC Overvoltage Protection Surge arrester, type II



/ I+II

AC Overvoltage Protection Surge arrester, type II



/ I+II

Ground Fault Protection Insulation monitoring for DC side

Transformer Protection Protection relay for pressure, temperature, gassing, dielectric level decrease with PT100

Fire Extinguishing System Smoke detector sensor (dry contact)

Communication Interface
Communication Method CAN / RS485 / RJ45 / Optical fiber

Supported Protocol CAN / Modbus / IEC60870-103 / IEC61850


Ethernet Switch Qty One for standard [6]

UPS 1kVA for 15min / 1h / 2h


● ○ ○

Skid General
Dimensions (W*H*D)(mm) 6058*2896*2438 mm (20ft) / 12192*2896*2438 mm (40ft)

Weight (kg) 23000kg (20ft) / 32000kg (40ft)

Protection Level IP54

Operating Temperature ( ) -35~60C, >45C derating

Storage Temperature ( ) -40~70C


NR Electric.Co.,Ltd.
Technical Parameters | NR MEDIUM VOLTAGE SKID DATASHEET
Maximum Altitude (above sea level) (m) 6000, ≥3000 derating [7]

Environment Humidity 0~ 100% ,No condensation


● ○
Type of Ventilation Nature air cooling / Forced air cooling

Auxiliary Power Consumption (w) 25kVA

Certificate IEC 62271-212, IEC 62271-200, IEC 60076, IEC 62477, IEC 6100, UL1741

Notes:
● Standard ○ Optional
1). If dry transformer is required, please contact with NR for more information
2). Lower protection level will be covered by C4-H
3). Standard for no supply of oil retention tank. If required to be integrated with PCS skid, please contact with NR
4). Typical value without any derating condition
5). If other type of switchgear is required, please contact with NR for more information
6). If more ethernet switch is required, please contact with NR for more information
7). When altitude is between 3000~4000m, the system LV AV voltage shall be less than 600V; When altitude is between 4000~4500m, the system LV AC voltage shall
be less than 550V; When altitude is between 4500~6000m, please contact with NR for more information.

NR Electric.Co.,Ltd.
Technical Parameters | NR MEDIUM VOLTAGE SKID DATASHEET

Type PCS-9567-2000 (20ft)

DC Side
PCS-9567TU-1000 PCS-9567TU-1250 PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

DC Input Voltage Range (V) 600~1500V 780~1500V 850~1500V 970~1500V 1050~1500V

Max. DC input Current (A) 1833A*2

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1000 PCS-9567TU-1250 PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

LV Nominal Operating Voltage (V) 400V 500V 550V 630V 690V

LV Operating Voltage Range (V) 360~440V 450~550V 500~600V 567~690V 630V~760V

PCS Efficiency 97.4% [1]


98.0% [1]
98.1% [1]
98.3% [1]
98.5%[1]

Max. AC Output Current (A) 1588A*2

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 2000kVA
Max. AC Power (kVA) 2200kVA

Type PCS-9567-2500 (20ft)

DC Side
PCS-9567TU-1250 PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

DC Input Voltage Range (V) 780~1500V 850~1500V 970~1500V 1050~1500V

Max. DC input Current (A) 1833A*2

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1250 PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

LV Nominal Operating Voltage (V) 500V 550V 630V 690V

LV Operating Voltage Range (V) 450~550V 500~600V 567~690V 630V~760V

PCS Efficiency 97.9% [1]


98.1% [1]
98.3% [1]
98.5%[1]

Max. AC Output Current (A) 1588A*2

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 2500kVA
Max. AC power (kVA) 2750kVA

Notes:
1). Typical discharge value for each PCS running at DC 1200V under IEC62933-2-1 environment condition

NR Electric.Co.,Ltd.
Technical Parameters | NR MEDIUM VOLTAGE SKID DATASHEET

Type PCS-9567-2750 (20ft)

DC Side
PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

DC Input Voltage Range (V) 850~1500V 970~1500V 1050~1500V

Max. DC input Current (A) 1833A*2

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

LV Nominal Operating Voltage (V) 550V 630V 690V

LV Operating Voltage Range (V) 500~600V 567~690V 630V~760V

PCS Efficiency 98.0% [1]


98.2% [1]
98.5%[1]

Max. AC Output Current (A) 1588A*2

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 2750kVA
Max. AC power (kVA) 3025kVA

Type PCS-9567-3150 (20ft)

DC Side
PCS-9567TU-1575 PCS-9567TU-1750

DC Input Voltage Range (V) 970~1500V 1050~1500V

Max. DC input Current (A) 1833A*2

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1575 PCS-9567TU-1750

LV Nominal Operating Voltage (V) 630V 690V

LV Operating Voltage Range (V) 567~690V 630V~760V

PCS Efficiency 98.2%[1] 98.4%[1]

Max. AC Output Current (A) 1588A*2

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 3150kVA
Max. AC power (kVA) 3465kVA

Notes:
1). Typical discharge value for each PCS running at DC 1200V under IEC62933-2-1 environment condition

NR Electric.Co.,Ltd.
Technical Parameters | NR MEDIUM VOLTAGE SKID DATASHEET

Type PCS-9567-3450 (20ft)

DC Side
PCS-9567TU-1750

DC Input Voltage Range (V) 1050~1500V

Max. DC input Current (A) 1833A*2

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1750

LV Nominal Operating Voltage (V) 690V

LV Operating Voltage Range (V) 630V~760V

PCS Efficiency 98.3%[1]

Max. AC Output Current (A) 1588A*2

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 3450kVA
Max. AC power (kVA) 3795kVA

Type PCS-9567-4000 (40ft)

DC Side
PCS-9567TU-1000 PCS-9567TU-1250 PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

DC Input Voltage Range (V) 600~1500V 780~1500V 850~1500V 970~1500V 1050~1500V

Max. DC input Current (A) 1833A*4

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1000 PCS-9567TU-1250 PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

LV Nominal Operating Voltage (V) 400V 500V 550V 630V 690V

LV Operating Voltage Range (V) 360~440V 450~550V 500~600V 567~690V 630V~760V

PCS Efficiency 97.4% [1]


98.0% [1]
98.1% [1]
98.3% [1]
98.5%[1]

Max. AC Output Current (A) 1588A*4

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 4000kVA
Max. AC power (kVA) 4400kVA

Notes:
1). Typical discharge value for each PCS running at DC 1200V under IEC62933-2-1 environment condition

NR Electric.Co.,Ltd.
Technical Parameters | NR MEDIUM VOLTAGE SKID DATASHEET

Type PCS-9567-5000 (40ft)

DC Side
PCS-9567TU-1250 PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

DC Input Voltage Range (V) 780~1500V 850~1500V 970~1500V 1050~1500V

Max. DC input Current (A) 1833A*4

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1250 PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

LV Nominal Operating Voltage (V) 500V 550V 630V 690V

LV Operating Voltage Range (V) 450~550V 500~600V 567~690V 630V~760V

PCS Efficiency 97.9% [1]


98.1% [1]
98.3% [1]
98.5%[1]

Max. AC Output Current (A) 1588A*4

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 5000kVA
Max. AC power (kVA) 5500kVA

Type PCS-9567-5500 (40ft)

DC Side
PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

DC Input Voltage Range (V) 850~1500V 970~1500V 1050~1500V

Max. DC input Current (A) 1833A*4

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1375 PCS-9567TU-1575 PCS-9567TU-1750

LV Nominal Operating Voltage (V) 550V 630V 690V

LV Operating Voltage Range (V) 500~600V 567~690V 630V~760V

PCS Efficiency 98.0%[1] 98.2%[1] 98.5%[1]

Max. AC Output Current (A) 1588A*4

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 5500kVA
Max. AC power (kVA) 6050kVA

Notes:
1). Typical discharge value for each PCS running at DC 1200V under IEC62933-2-1 environment condition

NR Electric.Co.,Ltd.
Technical Parameters | NR MEDIUM VOLTAGE SKID DATASHEET

Type PCS-9567-6300 (40ft)

DC Side
PCS-9567TU-1575 PCS-9567TU-1750

DC Input Voltage Range (V) 970~1500V 1050~1500V

Max. DC input Current (A) 1833A*4

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1575 PCS-9567TU-1750

LV Nominal Operating Voltage (V) 630V 690V

LV Operating Voltage Range (V) 567~690V 630V~760V

PCS Efficiency 98.2% [1]


98.4%[1]

Max. AC Output Current (A) 1588A*4

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 6300kVA
Max. AC power (kVA) 6930kVA

Type PCS-9567-6900 (40ft)

DC Side
PCS-9567TU-1750

DC Input Voltage Range (V) 1050~1500V

Max. DC input Current (A) 1833A*4

DC Voltage Ripple < 1%

DC Current Ripple < 3%

LV AC Side
PCS-9567TU-1750

LV Nominal Operating Voltage (V) 690V

LV Operating Voltage Range (V) 630V~760V

PCS Efficiency 98.3%[1]

Max. AC Output Current (A) 1588A*4

Total Harmonic Distortion Rate < 3%

Reactive Power Compensation Four quadrant operation

MV AC Side
Nominal Output Power (kW) 6900kVA
Max. AC power (kVA) 7590kVA

Notes:
1). Typical discharge value for each PCS running at DC 1200V under IEC62933-2-1 environment condition