Datasheet Digital LHDC D1137-13
Datasheet Digital LHDC D1137-13
1 D1137-13
Linear Heat Detection Cable - Monitor
Principles
The unit is operated in conjunction with a length of Digital (Non-resettable) Linear Heat Detection Cable (LHDC)
and an end of line (EOL) terminator. The Digital LHDC is a twisted pair twin core cable. When the trigger
temperature of the LHDC is reached the heat reactive polymer causes the cores to connect and a Fire alarm is
registered. The LDM-519-DDL units automatically determine the distance to the point of operation and displays
this by means of the LCD. The current loop output provides an analogue value of the ’distance’. This o/p is 0mA
when normal, and scaled 4mA = 0m to 20mA = 2000m on LHDC operation.
Reference should be made to the (separate) Sales Information Sheet D1179 on the Linear Heat Detection Cable
for the specification of their performance.
There are three principle modes of supply & signalling operation :-
Figure 1 shows a typical minimum system where a separate 24Vdc supply is employed.
The repeat contacts may be employed to signal an alarm panel and/or initiate control systems.
LDM-519-DDL
Figure 1 4 to 20mA
CURRENT LOOP
FIRE
REPEAT
CONTACTS
ALARM (2 SET)
LINEAR HEAT DETECTOR INTERPOSING FAULT
REPEAT
FAULT
CONTACTS
CABLE (2 SET)
EOL TERMINATOR JB 24Vdc
SUPPLY PSU
Figure 2 shows a simple configuration with the unit directly connected to a fire panel trigger circuit.
Note: Values of trigger and EOL resistors may vary depending on the Fire Panel.
Figure 2 LDM-519-DDL
CONVENTIONAL
CIRCUIT
FIRE
CONTROL
PANEL
ALARM
LINEAR HEAT DETECTOR INTERPOSING TRIGGER
CIRCUIT
FAULT EOL &
CABLE ALARM
EOL TERMINATOR JB SUPPLY
RESISTORS
Figure 3 shows the configuration when an ADDRESS LOOP interface / zone monitor unit (ZMU) module is
fitted.
Connection between the LDM-519-DDL and the addressable loop module is as the trigger circuit connection of
Figure 2.
Note: Values of trigger and EOL resistors may vary depending on the Fire Panel loop interface/Zone Monitor Unit.
Figure 3 LDM-519-DDL
ALARM
LINEAR HEAT DETECTOR INTERPOSING
FAULT 2 WIRE ADDRESS LOOP
CABLE
EOL TERMINATOR JB SUPPLY
ADDITIONAL ANALOGUE
LOOP ADDRESSABLE
INTERFACE FIRE ALARM
CIRCUIT CONTROL PANEL
2 D1137-13
Linear Heat Detection Cable - Monitor
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
LED's
SUPPLY
FIRE
LINEAR HEAT DETECTION CABLE FAULT LCD 3½ DIGIT
DISTANCE (m)
90 FIRE FAULT
TEST TEST
RESET
LDM-519-DDL
PUSH BUTTONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Enclosures
The LHDC Monitor can be mounted in a variety of enclosures.
For the example shown :- HEIGHT INCLUDING LID 115.6
Rating :- IP 65 82 164
190
DISTANCE (m)
FIRE FAULT
TEST TEST
Standard 700-451
M20
Operational Specification
<1.7mA
Current - Normal: <11.5mA - (with Fault Relay)
Plus user defined monitoring (EOL) current
<12mA <29mA - (with Both Relays)
Current - Fire:
Plus user defined Fire (Trigger) load Plus 4 to 20mA loop current if used
3 D1137-13
Linear Heat Detection Cable - Monitor
Figure 4 shows in more detail a typical minimum system where a 24Vdc supply is employed.
The repeat contacts may be employed to signal an alarm panel and/or initiate control systems.
REMOTE
Supply Fault Fire Trig. Cct. Trig. Cct. Calibrate Calibrate
Remote DISPLAY
Relay Relay Alarm EOL/Mon. Test Test Zero
0V 24V
Reset
Enable Enable Resistor Resistor Resistor Adjust OR PLC
- - + + - s c + c + s + s + s + Pot.
Figure 4
17/18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R
RELAY ENABLED
+24Vdc -
POWER
Details on how to install the calibration
SUPPLY + resistor are available in the Site
Adjustment section of this manual
Figures 5 shows in more detail a typical connection to a conventional panel or One Input Zone Monitor
similar to Hochiki CHQ-SZM, CHQ-SIM, CHQ-POM; Apollo 55000-812, 55000-845, 55000-833.
Other zone monitor manufacturers may also work .
1 INPUT
ZONE MONITOR
TYPICAL VALUES
470R
JUNCTION
4K7
EOL BOX
LHDC INTERPOSING CABLE 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35/36
A A
- + NO NC COM NO NC COM NO NC COM NO NC COM + - Cabling
M
4K7
REMOTE
Supply Fault Fire Trig. Cct. Trig. Cct. Calibrate Calibrate
Remote DISPLAY
Relay Relay Alarm EOL/Mon. Test Test
0V 24V
Reset
Enable Enable Resistor Resistor Resistor Not Used OR PLC
Figure 5 - - + + -
1 2 3 4 5
s
6
c
7
+
8
c
9
+ s + s
10 11 12 13 14 15 16
+ s +
17/18
R
RELAY ENABLED
+24Vdc -
POWER Details on how to install the calibration
SUPPLY + resistor are available in the Site
Adjustment section of this manual
4 D1137-13
Linear Heat Detection Cable - Monitor
Figures 6 shows in more detail a typical connection to a Two Input Zone Monitor similar to Hochiki CHQ
-DZM, CHQ-DIM, CHQ-POM
Other zone monitor manufacturers may also work .
2 INPUT
ZONE MONITOR
TYPICAL VALUES
INPUT 1 INPUT 2
470R
4K7
470R
JUNCTION
4K7
EOL BOX
LHDC INTERPOSING CABLE 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35/36
A A
- + NO NC COM NO NC COM NO NC COM NO NC COM + - Cabling
M
4K7
REMOTE
Supply Fault Fire Trig. Cct. Trig. Cct. Calibrate Calibrate
Remote DISPLAY
Relay Relay Alarm EOL/Mon. Test Test
Reset OR PLC
Figure 6 -
0V
- + + -
24V
s
Enable
c +
Enable
c +
Resistor Resistor Resistor Not Used
s + s + s +
17/18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R
RELAY ENABLED
+24Vdc -
POWER Details on how to install the calibration
SUPPLY + resistor are available in the Site
Adjustment section of this manual
Figure 7 shows in detail a typical Zener Barrier system where the LHDC is located in a Hazardous Area.
Hazardous Area principles used in the installation of Zener Barriers need to be closely adhered to. Those
principles will vary depending on the Hazardous Area, equipment, type of installation and site. As in the
examples above the repeat contacts may be employed to signal an alarm panel and or initiate control systems.
INTERPOSING CABLE
E E REMOTE
Supply Fault Fire Trig. Cct. Trig. Cct. Calibrate Calibrate
Remote DISPLAY
Relay Relay Alarm EOL/Mon. Test Test Zero
0V 24V
Reset
Enable Enable Resistor Resistor Resistor Adjust OR PLC
- - + + - s c + c + s + s + s + Pot.
I.S. EARTH 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17/18
Figure 7 R
RELAY ENABLED
+24Vdc -
POWER Details on how to install the calibration
SUPPLY + resistor are available in the Site
Adjustment section of this manual
5 D1137-13
Linear Heat Detection Cable - Monitor
Figure 8 shows in detail a typical Galvanic Isolator system where a length of LHDC is located in a
Hazardous Area. Hazardous Area principles used in the installation of Galvanic Isolator need to be closely
adhered to. Those principles will vary depending on the Hazardous Area, equipment, type of installation and site.
The main advantage in using a Galvanic Isolator over a Zener Barrier is that a special IS Earth is not required.
GALVANIC ISOLATOR
ALL CONTACTS ENABLED
JUNCTION 700-705
EOL BOX 700-706
LHDC INTERPOSING CABLE 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35/36
A A 470R A A
- + NO NC COM NO NC COM NO NC COM NO NC COM + - Cabling M
4K7
REMOTE
Supply Fault Fire Trig. Cct. Trig. Cct. Calibrate Calibrate
Remote DISPLAY
Relay Relay Alarm EOL/Mon. Test Test Zero
Figure 8. 0V
- - + + -
24V
Reset
s
Enable
c +
Enable
c +
Resistor Resistor Resistor Adjust
s + s + s + Pot.
OR PLC
17/18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Note:
For the Galvanic Isolator to work correctly with the R
RELAY ENABLED
LDM-519-DDL-G, a 470Ω, 250mW resistor is required +24Vdc -
in series with the positive terminal on the hazardous POWER Details on how to install the calibration
side of the Isolator and the LHDC connection in the
Junction Box.
SUPPLY + resistor are available in the Site
Adjustment section of this manual
As in the examples above the repeat contacts may be employed to signal an alarm panel and or initiate control
systems.
Figures 9 shows a typical connection to a conventional panel or Two Wire Mode Zone Monitor similar
to Hochiki CHQ-SZM, CHQ-POM; Apollo 55000-812, 55000-845, 55000-833
Other zone monitor manufacturers may also work .
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35/36
- + NO NC COM NO NC COM NO NC COM NO NC COM + - Cabling
A B 4 -20mA Site Zero
Loop Adjust
LHDC Fire Relay -Norm. De-energised Fault Relay -Norm. Energised Output Pot.
R
resistor are available in the Site
FIRE CONTROL PANEL Adjustment section of this manual
Figure 9. TRIGGER CIRCUIT INPUT
OR TYPICAL VALUES
ADDRESSABLE LOOP
INTERFACE MODULE INPUT
6 D1137-13
Linear Heat Detection Cable - Monitor
Operation
It should be noted that in order for the unit to operate at very low supply currents, as is necessary for connection to
Fire System trigger circuits, the Supply & Fault LEDs illuminate in a ‘flashing’ mode. The ‘flash’ cycle is
approximately 2s (0.5Hz) with an ON : OFF ratio of approximately 1:5.
The relay & resistor o/p conditions described in the following are appropriate to the configured mode detailed in
the previous section.
7 D1137-13
Linear Heat Detection Cable - Monitor
Disclaimer :-
The information contained in this document (D1137) is intended as guidance notes only, and do not take precedence over
any applicable on site policies or Hazardous Area regulations. We recommend that you always closely follow the
manufacture’s own applicable datasheets when installing any Hazardous Area Technology.
Notes.
Contact Details:
Patol Limited
Archway House
Bath Road
Padworth, Reading,
Berkshire.
RG7 5HR
Tel: +44 (0)1189 701 701
Fax: +44 (0)1189 701 700
Email: [email protected]
Web: www.Patol.co.uk
8 D1137-13