0% found this document useful (0 votes)
434 views21 pages

TVR II All Inverter - Water-Cooled - 220V-60Hz-3ph - Technical Service Manual

Uploaded by

felipe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
434 views21 pages

TVR II All Inverter - Water-Cooled - 220V-60Hz-3ph - Technical Service Manual

Uploaded by

felipe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

Technical Service Manual

TVR II Systems All Inverter


Water-Cooled
220V/60Hz/3ph

May 2015
1. Specifications .......................................................................................... 2
2. Dimensions .............................................................................................. 4
3. Piping diagrams ...................................................................................... 4
4. Electric Characteristics .......................................................................... 6
5. Electric wiring .......................................................................................... 7
6. Capacity Tables ..................................................................................... 13
7. Accessories ........................................................................................... 19
8. Functional parts and safety devices .................................................... 20

1
1. Specifications
Model 4TWH0086B6000AA 4TWH0096B6000AA 4TWH0115B6000AA
Power supply V-Ph-Hz 220V 3Ph ~ 60Hz
W 25200 28000 33500
Capacity
Btu/h 86000 95500 114300
Cooling (*1)
Input W 4800 6100 8000
EER W/W 5.25 4.59 4.19
W 27000 31500 37500
Capacity
Btu/h 92100 107500 128000
Heating (*2)
Input W 4450 5830 7800
COP W/W 6.07 5.40 4.81
IPLV© 5.9 5.8 5.8
Max. input consumption W 9454 9454 11188
Max. current A 37 37 37
Model E655DHD-65A2YG
Quantities 1
Type DC Inverter
Brand Hitachi
DC Inverter
Capacity Btu/h(W) 107800(31590)
compressor
Input W 10340
Operating frequency Hz 40~200
Crankcase W 40~80
Refrigerant oil gal.(ml) FVC68D /0.132(500)
Type Double-pipe heat exchanger
Rated water flow
m3/h 5.4 6 7.2
Heat volume
exchanger Pressure drop kPa 35 40 48
Max.pressure
MPa 1.98
of water pipe side
Drainage pipe outside diameter in.(mm) Ф25/64(Ф10)
Water side connecting pipe in.(mm) 1-1/4(DN32) inner groove
Outdoor sound level(*3) dB(A) 51 52 52
30-45/64×39-3/8×21-21/32
Dimension(W×H×D) in.(mm)
(780×1000×550)
Main unit 33-17/64×46-1/16×23-5/8
Packing (W×H×D) in.(mm)
(845×1170×600)
Net/Gross weight lbs(kg) 322/341(146/155)
Charged refrigerant type and volume lbs(kg) R410A 4.4(2)
Throttle type EXV
Excessive operating pressure MPa 4.4/2.6
Liquid side/ Gas side in.(mm) Ф3/8(9.53)/Ф7/8(22.2) Ф3/8(9.53)/Ф7/8(22.2) Ф1/2(12.7)/Ф1 (25.4)
Refrigerant
Oil balance pipe in.(mm) Ф1/4(Ф6.4)
piping
Total pipe length ft(m) 984(300)
The farthest pipe ft(m) 394

2
length(actual) (120)
The farthest pipe
ft(m) 492(150)
length (equivalent)
The farthest
equivalent pipe
ft(m) 131(40)/295(90)
length from the first
distributor (*4)
Max. Vertical pipe
length (When main ft(m) 164(50)
units is above)
Max. Vertical pipe
length (When main ft(m) 131(40)
units is below)
Max. drop between
ft(m) 98(30)
indoor units
Connection Power wiring mm2 4×10+10(L≤65.6ft.(20m)); 4×16+10(L≤164ft.(50m))
wiring Signal wiring mm2 3 core shielded wiring; wiring dia.≥0.75
Main unit water inlet temp. °F (°C) 44.6-113°F (7-45°C)
Main unit ambient temp. range °F (°C) 32-104°F (0-40°C)
Main unit ambient humidity Below 80%
Notes:
1. The cooling conditions: indoor temp.: 80.6°F (27°C DB), 66.2°F (19°C) WB, outdoor temp.: 95°F (35°C) DB, water inlet temp.:
86°F (30°C), equivalent pipe length: 16.4ft. (5m), drop length: 0ft. (0m).
2. The heating conditions: indoor temp.: 68°F (20°C) DB, 59°F (15°C) WB, outdoor temp.: 44.6°F (7°C) DB, 42.8°F (6°C) WB,
water inlet temp : 68°F (20°C), equivalent pipe length: 16.4ft. (5m) drop length: 0ft. (0m).
3. Sound level: Anechoic chamber conversion value, measured at a point 3.28ft. (1m) in front of the unit at a height of 3.28ft. (1
m). During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Connection piping diameter is based on the condition that the total equivalent liquid length is less than 295.2ft. (90m). When
the total equivalent liquid length is more than 295.2ft. (90m), please refer to installation manual to choose the connection piping
diameter.
5. The farthest equivalent pipe length should be equal to or shorter than 131.2ft. (40m), but it can be up to 295.2ft. (90m) if meet
the required conditions following part 4 installation sections.
The above data may be changed without notice for future improvement on quality and performance.

3
2. Dimensions
86, 96, 115 MBH (8HP/10HP/12HP) (unit: in.(mm))

3. Piping diagrams

Symbol Description TSC1


Electronic expansion valve

Electromagnetic valve TSC2


EXVA
Pressure relief valve TSJ
Way valve
EXVB
Filter

Pressure sensor
ST
Pressure Switch
Temperature probe
SV3

Oil separator
T7

SV2
Inverter
compressor

SV4

4
Remarks:

TSC1: water outlet temp. of upper pipe


TSC2: water outlet temp. of lower pipe
TSJ: water inlet temp. of double-pipe heat exchanger
T5: inverter module temp.
Pc: discharge pressure
Ps: suction pressure
T7: discharge temp. of inverter compressor
Each model has one inverter compressor and two EXVs at the high-pressure pipe side.
Key Components:
Oil Separator: used to separate oil from high pressure & temperature gas refrigerant, which is pumped out
from compressor. The separation efficiency is up to 99%, it makes the oil return back to each compressor very
soon.
Low pressure receiver: It is used to store the liquid refrigerant and oil, it can protect the compressor from
liquid hammer.
Four-way valve control (ST1): Closed in cooling mode and open in heating mode
EXV (electronic expansion valve) control:
1) Max. Open degree is 700 pulses.
2) When system power on, the EXV closes 700pulse first, then opens to 350 pulse and stand by. When then
the unit started, it opens to the right pulse.
3) When the running main unit receives OFF signal, the EXV of slave unit will stop, while master unit is running
and slave unit stopped at the same time. If all main units stopped, the EXV will close first, and then open to the
pulse of stand-by.
SV2: spray a little liquid refrigerant to cooling compressor. Open when any compressor discharge temperature
is higher than 100℃.
SV3: open when power on, closed after 60 seconds; open when discharge pressure is less than1.8MP in
cooling mode, open when discharge pressure is greater than 4.0MPa in heating mode.
SV4: oil returning valve. Opens after the DC inverter compressor has been run for 5 minutes and then closes
15 minutes later. (For the system has only one main unit).
Every 20 minutes, SV4 of each main unit opens for 3 minutes. (For the system has more than one main unit)
High pressure sensor: To supervisor the discharge pressure of the compressor and to control the water
temperature.

5
4. Electric Characteristics
Outdoor unit Power Current Compressor OFM
Capacity
Voltage Hz Min Max MCA TOCA MFA MSC RLA KW FLA
4TWH0086B6000AA 220 60 196 244 32.2 35 40 - 21.4 - -
4TWH0086B6000AA 220 60 196 244 33.4 35 40 - 23.8 - -
4TWH0086B6000AA 220 60 196 244 34.5 35 40 - 26.2 - -

Remarks:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (KW)

Notes:
1. The current value of combination unit is the total value of each basic model
For example: 34HP=10HP+12HP×2
Power supply: MCA=33.4+34.5×2=102.4
TOCA=35+35×2=105
MFA=40+40×2=120
Compressor: RLA=23.8+26.2×2=76.2
2. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB
3. TOCA means the total value of each OC set.
4. MSC means the Max. current during the starting of compressor.
5. Voltage range units are suitable for use on electrical systems where voltage supplied to unit terminals is not
below or above listed range limits.
6. Maximum allowable voltage variation between phase is 2%
7. Selection wire size based on the larger value of MCA or TOCA
8. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).

6
5. Electric wiring
5.1 Wiring diagram for 86, 96, 115 MBH (8,10,12HP)

7
5.2 Terminal base function

Communication
switching plate

XT1 powerline
terminal

Grounding
terminal

XT2 water flow switch XT3 water pump


ON/OFF signal input ON/OFF signal ouput
Electric control box diagram

Note: Never apply line voltage to communication switching plate and XT2 water flow switch ON/OFF signal input terminal.

XT2 water flow switch ON/OFF signal input terminal


(Must be connected to weak current control circuit !)

XT3 Water pump ON/OFF signal output terminals


(Dry contact )

8
5.3 Signal wire of indoor/main units
Signal wire of indoor/main unit adopts 3-core shielded wire (≥0.75mm2) which has polarity, please connect it
correctly.
Main unit Main unit Main unit
(master unit) (slave unit) (slave unit)

(All shield terminals of shield wires


connect to COMM terminal )

(H1 H2 E)
(P Q E)

(H1 H2 E) (H1 H2 E)

Signal wire between main units

To closed end of shield wire

(P Q E)

Signal wire of
indoor/main units

group control
matching

P
resisitor

Q (open)

5.4 Electric wiring of water pipelines


5.4.1 Water flow ON/OFF signal wiring
1) Water flow switch should be wired during the installation. Each unit must be configured a water flow switch,
and it cannot operate without a water flow switch.
2) The signal wire should apply 0.75mm2 shielding wire, and connected to the XT2 terminal in the electric
control box

XT2 XT3

Water flow ON/OFF signal input

9
5.4.2 Water pump ON/OFF signal wiring
1)Each unit has configured a dry contact terminal for central control of the water pump (see Fig.3-3),this
terminal cannot be connected to power terminal of the water pump directly, only should be connected to the
control terminal of the water pump starter.
2)When the water pump ON/OFF signal wire has been connected to strong current, it should be wired the
signal wires along with other strong current wires; when it has been connected to week current, it should be
wired the signal wires along with the week current wires.
3) When the water pipeline has a single system, the water pump ON/OFF signal wire should be connected to
the XT3 terminals in the main unit electric control box. When the water pipeline has several systems, the
water pump ON/OFF signal should be controlled by the main unit centralized controller. The wiring of main unit
centralized controller.

XT2 XT3

Water pump ON/OFF signal output


Main unit Main unit Main unit
(master unit) (slave unit) (slave unit)

(All shield terminals of shield wires


connect to COMM terminal )

(K1 K2 E)

(K1 K2 E) (K1 K2 E)

Main unit Main unit Main unit Main unit


(master unit) (slave unit) (slave unit) centralized controller

P P amplification

PUMP
(K1 K2 E)

(K1 K2 E) (K1 K2 E) (K1 K2 E)


Water pump starter
L
Water pump
N

Group control all the main units in the same water system

10
5.5 Example for power wire connection
5.5.1 A water circuit for single system wiring

11
5.5.2 A water circuit for several systems wiring

Note:
1. The signal connecting line between main units, indoor and main units and indoor units has polarity. When connecting, be
careful to prevent error connection.
2. Signal line shall adopt three-core shielded wire with an area above 0.75 mm2.
3. Do not bind signal line and copper pipe together with belting.
4. Make sure that the shield metal layer should be grounded well indoor control box in order to prevent interference.
5. It’s forbidden to connect 200V or above high-volt power to the communication terminal.

12
6. Capacity Tables
86MBH (8HP) cooling mode
Indoor temperature℃WB

Combination Water inlet Water 14 16 18 19 20 22 24

(%) temperature(℃) flow(L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

20 22.1 2.78 26.3 3.69 28.1 3.97 28.5 4.00 28.9 4.00 29.5 4.04 30.0 4.05

25 22.1 3.27 26.3 4.36 27.3 4.42 27.7 4.44 28.0 4.46 28.6 4.48 29.0 4.50
130% 90
30 22.1 3.87 25.5 4.82 26.3 4.86 26.6 4.89 27.0 4.90 27.5 4.93 27.8 4.94

35 22.1 4.62 24.4 5.27 25.1 5.32 25.5 5.34 25.8 5.36 26.1 5.37 26.4 5.37

20 20.4 2.44 24.4 3.24 27.7 3.95 28.0 3.97 28.4 3.99 29.1 4.02 29.6 4.04

25 20.4 2.88 24.4 3.82 26.8 4.39 27.2 4.42 27.7 4.43 28.2 4.47 28.7 4.48
120% 90
30 20.4 3.41 24.4 4.53 25.9 4.84 26.2 4.86 26.5 4.88 27.1 4.91 27.6 4.93

35 20.4 4.06 24.0 5.24 25.1 5.29 25.1 5.32 25.3 5.33 25.9 5.37 26.2 5.37

20 18.7 2.14 22.3 2.82 26.0 3.59 27.5 3.95 27.8 3.96 28.6 4.00 29.2 4.02

25 18.7 2.52 22.3 3.32 26.0 4.23 26.7 4.39 27.1 4.41 27.7 4.44 28.3 4.47
110% 90
30 18.7 2.97 22.3 3.93 25.4 4.81 25.8 4.83 26.0 4.86 26.7 4.89 27.2 4.92

35 18.6 3.55 22.3 4.70 24.3 5.75 24.6 5.29 24.9 5.31 25.5 5.34 26.0 5.37

20 17.0 1.85 20.3 2.42 23.6 3.07 25.2 3.43 26.8 3.80 29.8 3.97 28.6 4.00

25 17.0 2.17 20.3 2.85 23.6 3.62 25.2 4.04 26.5 4.38 27.2 4.42 27.7 4.44
100% 90
30 17.0 2.56 20.3 3.38 23.6 4.30 25.2 4.80 25.6 4.82 26.2 4.86 26.7 4.90

35 17.0 3.05 20.3 4.02 23.6 5.13 24.1 5.25 24.4 5.27 25.0 5.31 25.6 5.34

20 15.3 1.59 18.2 2.06 21.2 2.60 22.7 2.89 24.2 3.20 27.1 3.86 28.0 3.97

25 15.3 1.86 18.2 2.42 21.2 3.06 22.7 3.41 24.2 3.77 26.5 4.38 27.2 4.41
90% 90
30 15.3 2.19 18.2 2.86 21.2 3.80 22.7 4.04 24.2 4.47 25.6 4.82 26.1 4.86

35 15.3 2.60 18.2 3.40 21.2 4.32 22.7 4.82 23.9 5.23 24.5 5.28 25.0 5.31

20 13.6 1.35 16.2 1.73 18.9 2.17 20.2 2.40 21.4 2.65 24.1 3.18 26.7 3.77

25 13.6 1.58 16.2 2.03 18.9 2.55 20.2 2.83 21.4 3.12 24.1 3.76 26.5 4.38
80% 90
30 13.6 1.85 16.2 2.39 18.9 3.00 20.2 3.34 21.4 3.69 24.1 4.46 25.6 4.82

35 13.6 2.18 16.2 2.83 18.9 3.57 20.2 3.98 21.4 4.41 23.9 5.23 24.4 5.27

20 11.9 1.13 14.2 1.43 16.5 1.78 17.6 1.96 18.8 2.16 21.0 2.57 23.4 3.03

25 11.9 1.31 14.2 1.67 16.5 2.08 17.6 2.30 18.8 2.53 21.0 3.03 23.4 3.57
70% 90
30 11.9 1.54 14.2 1.97 16.5 2.45 17.6 2.71 18.8 2.99 21.0 3.59 23.4 4.24

35 11.9 1.81 14.2 2.32 16.5 2.89 17.6 3.22 18.8 3.89 21.0 4.28 23.4 5.07

20 10.2 0.92 12.2 1.16 14.2 1.42 15.1 1.56 16.1 1.71 18.0 2.03 20.0 2.38

25 10.2 1.07 12.2 1.35 14.2 1.66 15.1 1.83 16.1 2.01 18.0 2.39 20.0 2.80
60% 90
30 10.2 1.26 12.2 1.58 14.2 1.95 15.1 2.15 16.1 2.36 18.0 2.82 20.0 3.30

35 10.2 1.47 12.2 11.23 14.2 2.31 15.1 2.55 16.1 2.80 18.0 3.34 20.0 3.94

20 8.5 0.75 10.1 0.92 11.8 1.11 12.6 1.22 13.4 1.32 15.1 1.55 16.7 1.81

25 8.5 0.87 10.1 1.07 11.8 1.30 12.6 1.42 13.4 1.54 15.1 1.82 16.7 2.12
50% 90
30 8.5 1.00 10.1 1.24 11.8 1.51 12.6 1.66 13.4 1.81 15.1 2.14 16.7 2.49

35 8.5 1.17 10.1 1.46 11.8 1.78 12.6 1.96 13.4 2.14 15.1 2.53 16.7 2.96

Note:
1. is shown as reference
2. The above table shows the average value of conditions may operate
3. It is recommended to connect less than 130%
13
86 MBH (8HP) heating mode
Indoor temperature℃DB

Combination Water inlet Water 16 18 20 21 22 24

(%) temperature(℃) flow(L/min) TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW

20 28.5 3.61 28.3 3.70 28.2 3.81 28.0 3.87 28.0 3.94 27.7 4.09

25 31.3 3.79 31.2 3.91 30.9 4.03 30.8 4.10 30.6 4.17 30.4 4.33
130% 90
30 33.8 4.00 33.9 4.12 33.6 4.26 32.5 4.33 33.2 4.36 30.9 3.91

35 37.0 4.22 36.7 4.35 35.5 4.23 33.3 4.02 33.2 3.94 30.9 3.43

20 28.3 3.73 28.1 3.84 28.2 3.96 27.8 4.04 27.7 4.11 27.4 4.26

25 31.1 3.95 30.8 4.07 30.6 4.20 30.5 4.27 30.3 4.36 28.5 3.99
120% 90
30 33.8 4.17 33.5 4.30 32.7 4.27 31.7 4.07 30.6 3.86 28.5 3.47

35 36.5 4.40 34.8 4.12 32.7 3.74 31.7 3.56 30.6 3.39 28.5 3.05

20 28.0 3.90 27.9 4.02 27.6 4.15 27.5 4.22 27.4 4.30 26.1 4.09

25 30.7 4.13 30.5 4.26 30.0 4.32 29.0 4.11 28.0 3.90 26.1 3.50
110% 90
30 33.4 4.37 31.9 4.12 30.0 3.67 29.0 3.56 28.0 3.39 26.1 3.13

35 33.8 3.94 31.9 3.60 30.0 3.29 29.0 3.19 28.0 2.98 26.1 2.69

20 27.7 4.09 27.5 4.22 27.0 4.45 26.4 4.14 25.5 3.94 23.8 3.53

25 30.3 4.34 29.0 4.11 27.0 3.73 26.4 3.55 25.5 3.37 23.8 3.04
100% 90
30 30.7 3.89 29.0 3.56 27.0 3.24 26.4 3.09 25.5 2.94 23.8 2.66

35 30.7 3.41 29.0 3.13 27.0 2.86 26.4 2.73 25.5 2.60 23.8 2.36

20 27.4 4.32 26.1 4.08 24.6 3.71 23.7 3.53 22.9 3.35 21.4 3.02

25 27.7 3.82 26.1 3.50 24.6 3.19 23.7 3.04 22.9 2.89 21.4 2.62
90% 90
30 27.7 3.32 26.1 3.04 24.6 2.78 23.7 2.66 22.9 2.54 21.4 2.30

35 27.7 2.93 26.1 2.69 24.6 2.47 23.7 2.36 22.9 2.25 21.4 2.05

20 24.6 3.73 23.2 3.41 21.8 3.11 21.1 2.96 20.4 2.83 19.0 2.55

25 24.6 3.20 23.2 2.94 21.8 2.69 21.1 2.57 20.4 2.45 19.0 2.23
80% 90
30 24.6 2.76 23.2 2.57 21.8 2.36 21.1 2.27 20.4 2.16 19.0 1.97

35 24.6 2.51 23.2 2.29 21.8 2.10 21.1 2.02 20.4 1.93 19.0 1.77

20 21.6 3.06 20.3 2.80 19.1 2.57 18.4 2.46 17.8 2.34 16.6 2.13

25 21.6 2.64 20.3 2.44 19.1 2.23 18.4 2.14 17.8 2.05 16.6 1.87
70% 90
30 21.6 2.32 20.3 2.15 19.1 1.98 18.4 1.90 17.8 1.82 16.6 1.67

35 21.6 2.07 20.3 1.92 19.1 1.77 18.4 1.69 17.8 1.64 16.6 1.51

20 18.4 2.45 17.4 2.26 16.4 2.08 15.8 2.00 15.3 1.91 14.3 1.74

25 18.4 2.14 17.4 1.98 16.4 1.83 15.8 1.76 15.3 1.69 14.3 1.55
60% 90
30 18.4 1.90 17.4 1.76 16.4 1.64 15.8 1.57 15.3 1.51 14.3 1.39

35 18.4 1.70 17.4 1.59 16.4 1.48 15.8 1.42 15.3 1.37 14.3 1.27

20 15.4 1.92 14.5 1.79 14.5 1.65 13.2 1.59 12.7 1.53 11.9 1.41

25 15.4 1.69 14.5 1.58 14.5 1.47 13.2 1.41 12.7 1.36 11.9 1.26
50% 90
30 15.4 1.52 14.5 1.42 14.5 1.33 13.2 1.28 12.7 1.23 11.9 1.15

35 15.4 1.38 14.5 1.29 14.5 1.21 13.2 1.17 12.7 1.13 11.9 1.05

Note:
1. is shown as reference
2. The above table shows the average value of conditions may operate
3. It is recommended to connect less than 130%

14
96MBH (10HP) cooling mode
Indoor temperature℃WB

Combination Water inlet Water 14 16 18 19 20 22 24

(%) temperature(℃) flow(L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

20 24.5 3.53 29.3 4.69 31.3 5.05 31.7 5.08 32.1 5.09 32.8 5.13 33.3 5.15

25 24.5 4.16 29.3 5.54 30.3 5.61 30.7 5.64 31.1 5.67 31.8 5.70 32.2 5.72
130% 100
30 24.5 4.92 28.3 6.12 29.3 6.18 29.6 6.21 30.0 6.23 30.5 6.26 30.9 6.27

35 24.5 5.88 27.1 6.70 27.9 6.76 28.3 6.79 28.6 6.81 29.0 6.83 29.4 6.83

20 22.7 3.11 27.1 4.12 30.7 5.02 31.1 5.05 31.6 5.07 32.3 5.11 32.9 5.13

25 22.7 3.66 27.1 4.86 29.8 5.58 30.2 5.61 30.7 5.63 31.4 5.68 31.9 5.70
120% 100
30 22.7 4.33 27.1 5.76 28.7 6.15 29.2 6.18 29.5 6.20 30.1 6.24 30.6 6.26

35 22.7 5.16 26.6 6.66 27.9 6.73 27.9 6.76 28.1 6.78 28.7 6.82 29.2 6.83

20 20.8 2.72 24.7 3.58 28.8 4.56 30.5 5.02 30.9 5.04 31.8 5.08 32.4 5.11

25 20.8 3.20 24.7 4.22 28.8 5.38 29.7 5.57 30.1 5.60 30.8 5.64 31.5 5.68
110% 100
30 20.8 3.77 24.7 5.00 28.2 6.11 28.6 6.14 28.9 6.17 29.7 6.21 30.2 6.25

35 20.7 4.51 24.7 5.97 27.0 7.31 27.4 6.72 27.7 6.75 28.3 6.79 28.8 6.82

20 18.9 2.36 22.5 3.08 26.2 3.90 28.0 4.36 29.8 4.84 33.1 5.05 31.8 5.08

25 18.9 2.76 22.5 3.62 26.2 4.60 28.0 5.14 29.5 5.56 30.2 5.61 30.8 5.64
100% 100
30 18.9 3.26 22.5 4.29 26.2 5.46 28.0 6.10 28.4 6.13 29.2 6.18 29.7 6.22

35 18.9 3.87 22.5 5.11 26.2 6.52 26.7 6.67 27.2 6.70 27.8 6.75 28.4 6.79

20 17.0 2.02 20.2 2.62 23.6 3.30 25.2 3.67 26.8 4.07 30.1 4.91 31.1 5.05

25 17.0 2.37 20.2 3.08 23.6 3.88 25.2 4.33 26.8 4.80 29.5 5.56 30.2 5.60
90% 100
30 17.0 2.78 20.2 3.63 23.6 4.83 25.2 5.13 26.8 5.69 28.4 6.13 29.0 6.18

35 17.0 3.30 20.2 4.32 23.6 5.49 25.2 6.13 26.5 6.65 27.3 6.71 27.8 6.75

20 15.1 1.71 18.0 2.20 21.0 2.75 22.4 3.06 23.8 3.37 26.7 4.05 29.7 4.80

25 15.1 2.00 18.0 2.58 21.0 3.24 22.4 3.59 23.8 3.97 26.7 4.77 29.5 5.56
80% 100
30 15.1 2.35 18.0 3.03 21.0 3.81 22.4 4.25 23.8 4.69 26.7 5.67 28.4 6.13

35 15.1 2.77 18.0 3.60 21.0 4.54 22.4 5.06 23.8 5.60 26.5 6.65 27.2 6.70

20 13.2 1.44 15.7 1.82 18.4 2.26 19.6 2.49 20.9 2.74 23.4 3.27 26.0 3.85

25 13.2 1.67 15.7 2.12 18.4 2.64 19.6 2.92 20.9 3.22 23.4 3.85 26.0 4.54
70% 100
30 13.2 1.95 15.7 2.50 18.4 3.12 19.6 3.45 20.9 3.80 23.4 4.56 26.0 5.39

35 13.2 2.30 15.7 2.95 18.4 3.67 19.6 4.10 20.9 4.94 23.4 5.44 26.0 6.44

20 11.3 1.17 13.5 1.48 15.7 1.81 16.8 1.98 17.9 2.17 20.0 2.58 22.2 3.02

25 11.3 1.37 13.5 1.72 15.7 2.11 16.8 2.33 17.9 2.55 20.0 3.03 22.2 3.56
60% 100
30 11.3 1.60 13.5 2.01 15.7 2.48 16.8 2.73 17.9 3.00 20.0 3.58 22.2 4.20

35 11.3 1.87 13.5 14.27 15.7 2.93 16.8 3.24 17.9 3.56 20.0 4.25 22.2 5.01

20 9.4 0.95 11.2 1.17 13.1 1.42 14.1 1.55 14.9 1.68 16.8 1.97 18.6 2.30

25 9.4 1.10 11.2 1.36 13.1 1.65 14.1 1.80 14.9 1.96 16.8 2.32 18.6 2.69
50% 100
30 9.4 1.27 11.2 1.58 13.1 1.92 14.1 2.11 14.9 2.31 16.8 2.72 18.6 3.17

35 9.4 1.49 11.2 1.85 13.1 2.27 14.1 2.49 14.9 2.72 16.8 3.22 18.6 3.76

Note:
1. is shown as reference
2. The above table shows the average value of conditions may operate
3. It is recommended to connect less than 130%

15
96MBH (10HP) heating mode
Indoor temperature℃DB

Combination Water inlet Water 16 18 20 21 22 24

(%) temperature(℃) flow(L/min) TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW

20 33.2 4.73 33.0 4.84 32.9 5.00 32.7 5.07 32.6 5.16 32.3 5.35

25 36.6 4.97 36.4 5.12 36.1 5.28 36.0 5.37 35.8 5.47 35.5 5.68
130% 100
30 39.4 5.24 39.6 5.40 39.2 5.58 37.9 5.68 38.7 5.71 36.1 5.13

35 43.1 5.52 42.8 5.69 41.4 5.54 38.8 5.27 38.7 5.16 36.1 4.50

20 33.0 4.89 32.8 5.03 32.9 5.19 32.4 5.29 32.3 5.38 32.0 5.58

25 36.3 5.18 36.0 5.34 35.7 5.51 35.6 5.60 35.4 5.71 33.2 5.23
120% 100
30 39.5 5.47 39.1 5.64 38.2 5.60 37.0 5.33 35.8 5.06 33.2 4.54

35 42.6 5.76 40.6 5.39 38.2 4.90 37.0 4.67 35.8 4.44 33.2 3.99

20 32.7 5.11 32.5 5.26 32.2 5.44 32.1 5.53 31.9 5.63 30.5 5.35

25 35.9 5.41 35.6 5.58 35.0 5.66 33.8 5.38 32.7 5.11 30.5 4.59
110% 100
30 39.0 5.72 37.3 5.39 35.0 4.81 33.8 4.67 32.7 4.44 30.5 4.10

35 39.5 5.16 37.3 4.72 35.0 4.31 33.8 4.18 32.7 3.90 30.5 3.52

20 32.3 5.36 32.1 5.53 31.5 5.83 30.8 5.43 29.8 5.16 27.8 4.63

25 35.4 5.69 33.8 5.38 31.5 4.89 30.8 4.66 29.8 4.42 27.8 3.99
100% 100
30 35.9 5.10 33.8 4.67 31.5 4.25 30.8 4.05 29.8 3.85 27.8 3.48

35 35.9 4.47 33.8 4.10 31.5 3.75 30.8 3.58 29.8 3.41 27.8 3.09

20 31.9 5.67 30.5 5.35 28.7 4.85 27.7 4.63 26.8 4.39 24.9 3.96

25 32.3 5.01 30.5 4.58 28.7 4.17 27.7 3.99 26.8 3.79 24.9 3.43
90% 100
30 32.3 4.34 30.5 3.99 28.7 3.65 27.7 3.48 26.8 3.32 24.9 3.01

35 32.3 3.83 30.5 3.52 28.7 3.23 27.7 3.09 26.8 2.95 24.9 2.68

20 28.7 4.88 27.1 4.47 25.5 4.07 24.6 3.88 23.8 3.70 22.2 3.34

25 28.7 4.19 27.1 3.85 25.5 3.52 24.6 3.36 23.8 3.21 22.2 2.92
80% 100
30 28.7 3.62 27.1 3.37 25.5 3.10 24.6 2.98 23.8 2.83 22.2 2.58

35 28.7 3.29 27.1 2.99 25.5 2.76 24.6 2.64 23.8 2.53 22.2 2.31

20 25.1 4.00 23.7 3.67 22.3 3.36 21.5 3.22 20.8 3.07 19.4 2.79

25 25.1 3.46 23.7 3.19 22.3 2.93 21.5 2.80 20.8 2.68 19.4 2.45
70% 100
30 25.1 3.04 23.7 2.81 22.3 2.59 21.5 2.48 20.8 2.38 19.4 2.18

35 25.1 2.71 23.7 2.51 22.3 2.32 21.5 2.22 20.8 2.14 19.4 1.97

20 21.5 3.21 20.3 2.97 19.1 2.73 18.5 2.62 17.9 2.50 16.7 2.29

25 21.5 2.80 20.3 2.60 19.1 2.40 18.5 2.30 17.9 2.21 16.7 2.03
60% 100
30 21.5 2.48 20.3 2.30 19.1 2.14 18.5 2.06 17.9 1.97 16.7 1.82

35 21.5 2.23 20.3 2.08 19.1 1.94 18.5 1.86 17.9 1.79 16.7 1.66

20 18.0 2.52 17.0 2.34 17.0 2.16 15.4 2.09 14.8 2.00 13.8 1.84

25 18.0 2.22 17.0 2.07 17.0 1.93 15.4 1.85 14.8 1.78 13.8 1.65
50% 100
30 18.0 1.99 17.0 1.86 17.0 1.74 15.4 1.67 14.8 1.61 13.8 1.50

35 18.0 1.80 17.0 1.69 17.0 1.59 15.4 1.53 14.8 1.48 13.8 1.38

Note:
1. is shown as reference
2. The above table shows the average value of conditions may operate
3. It is recommended to connect less than 130%

16
115 MBH (12HP) cooling mode
Indoor temperature℃WB

Combination Water inlet Water 14 16 18 19 20 22 24

(%) temperature(℃) flow(L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW kW kW

20 29.4 4.63 35.0 6.16 37.4 6.62 37.9 6.66 38.4 6.67 39.3 6.73 39.9 6.75

25 29.4 5.45 35.0 7.27 36.3 7.36 36.8 7.40 37.3 7.43 38.0 7.47 38.5 7.50
130% 120
30 29.4 6.45 33.9 8.03 35.0 8.11 35.4 8.15 35.9 8.17 36.5 8.21 37.0 8.23

35 29.4 7.71 32.4 8.78 33.4 8.86 33.9 8.90 34.3 8.93 34.8 8.96 35.1 8.96

20 27.1 4.07 32.4 5.40 36.8 6.58 37.3 6.62 37.8 6.65 38.6 6.70 39.4 6.73

25 27.1 4.80 32.4 6.37 35.6 7.32 36.1 7.36 36.8 7.39 37.5 7.44 38.1 7.47
120% 120
30 27.1 5.68 32.4 7.55 34.4 8.07 34.9 8.11 35.3 8.13 36.0 8.19 36.6 8.21

35 27.1 6.77 31.9 8.73 33.4 8.82 33.4 8.86 33.6 8.89 34.4 8.94 34.9 8.96

20 24.8 3.57 29.6 4.70 34.5 5.98 36.5 6.58 37.0 6.61 38.0 6.66 38.8 6.70

25 24.8 4.19 29.6 5.53 34.5 7.06 35.5 7.31 36.0 7.35 36.9 7.40 37.6 7.44
110% 120
30 24.8 4.95 29.6 6.55 33.8 8.01 34.3 8.05 34.6 8.09 35.5 8.15 36.1 8.20

35 24.8 5.92 29.6 7.83 32.2 9.58 32.7 8.81 33.1 8.85 33.9 8.90 34.5 8.94

20 22.6 3.09 27.0 4.03 31.4 5.12 33.5 5.72 35.6 6.34 39.6 6.62 38.0 6.66

25 22.6 3.62 27.0 4.75 31.4 6.04 33.5 6.74 35.3 7.30 36.1 7.36 36.9 7.40
100% 120
30 22.6 4.27 27.0 5.63 31.4 7.16 33.5 8.00 34.0 8.04 34.9 8.11 35.5 8.16

35 22.6 5.08 27.0 6.70 31.4 8.56 32.0 8.74 32.5 8.78 33.2 8.85 34.0 8.90

20 20.3 2.65 24.2 3.44 28.2 4.33 30.1 4.82 32.1 5.33 36.0 6.43 37.3 6.62

25 20.3 3.10 24.2 4.03 28.2 5.09 30.1 5.68 32.1 6.29 35.3 7.30 36.1 7.35
90% 120
30 20.3 3.65 24.2 4.76 28.2 6.33 30.1 6.73 32.1 7.46 34.0 8.04 34.8 8.11

35 20.3 4.33 24.2 5.67 28.2 7.20 30.1 8.04 31.7 8.72 32.6 8.80 33.2 8.85

20 18.1 2.24 21.6 2.88 25.1 3.61 26.9 4.01 28.5 4.42 32.0 5.31 35.5 6.29

25 18.1 2.63 21.6 3.38 25.1 4.25 26.9 4.71 28.5 5.20 32.0 6.26 35.3 7.30
80% 120
30 18.1 3.08 21.6 3.98 25.1 5.00 26.9 5.57 28.5 6.16 32.0 7.43 34.0 8.04

35 18.1 3.64 21.6 4.72 25.1 5.96 26.9 6.63 28.5 7.35 31.7 8.72 32.5 8.78

20 15.8 1.88 18.8 2.39 22.0 2.96 23.5 3.26 25.0 3.60 28.0 4.29 31.1 5.05

25 15.8 2.19 18.8 2.79 22.0 3.46 23.5 3.83 25.0 4.22 28.0 5.05 31.1 5.96
70% 120
30 15.8 2.56 18.8 3.28 22.0 4.09 23.5 4.52 25.0 4.99 28.0 5.98 31.1 7.07

35 15.8 3.01 18.8 3.87 22.0 4.82 23.5 5.37 25.0 6.48 28.0 7.14 31.1 8.45

20 13.6 1.54 16.2 1.94 18.8 2.37 20.1 2.60 21.5 2.85 24.0 3.38 26.6 3.97

25 13.6 1.79 16.2 2.26 18.8 2.77 20.1 3.05 21.5 3.34 24.0 3.98 26.6 4.67
60% 120
30 13.6 2.10 16.2 2.64 18.8 3.25 20.1 3.58 21.5 3.94 24.0 4.70 26.6 5.51

35 13.6 2.45 16.2 18.72 18.8 3.85 20.1 4.25 21.5 4.67 24.0 5.57 26.6 6.57

20 11.3 1.25 13.4 1.54 15.7 1.86 16.8 2.03 17.8 2.20 20.1 2.59 22.2 3.01

25 11.3 1.45 13.4 1.78 15.7 2.16 16.8 2.36 17.8 2.57 20.1 3.04 22.2 3.53
50% 120
30 11.3 1.67 13.4 2.07 15.7 2.52 16.8 2.77 17.8 3.02 20.1 3.57 22.2 4.15

35 11.3 1.95 13.4 2.43 15.7 2.97 16.8 3.26 17.8 3.57 20.1 4.22 22.2 4.94

Note:
1. is shown as reference
2. The above table shows the average value of conditions may operate
3. It is recommended to connect less than 130%

17
115 MBH (12HP) heating mode
Indoor temperature℃DB

Combination Water inlet Water 16 18 20 21 22 24

(%) temperature(℃) flow(L/min) TC PI TC PI TC PI TC PI TC PI TC PI

kW kW kW kW kW kW kW kW kW kW kW kW

20 39.6 6.33 39.3 6.48 39.2 6.68 39.0 6.78 38.8 6.90 38.5 7.16

25 43.5 6.65 43.3 6.85 42.9 7.06 42.8 7.19 42.6 7.32 42.2 7.59
130% 120
30 46.9 7.01 47.1 7.23 46.7 7.47 45.2 7.59 46.1 7.64 42.9 6.86

35 51.3 7.39 51.0 7.62 49.3 7.42 46.2 7.05 46.1 6.90 42.9 6.01

20 39.3 6.54 39.1 6.73 39.2 6.95 38.6 7.08 38.5 7.20 38.1 7.47

25 43.2 6.92 42.8 7.14 42.4 7.37 42.3 7.49 42.1 7.64 39.6 7.00
120% 120
30 47.0 7.32 46.5 7.54 45.5 7.49 44.0 7.13 42.6 6.77 39.6 6.08

35 50.7 7.71 48.3 7.21 45.5 6.56 44.0 6.24 42.6 5.94 39.6 5.34

20 39.0 6.84 38.7 7.04 38.4 7.28 38.2 7.40 38.0 7.53 36.3 7.16

25 42.7 7.24 42.3 7.47 41.7 7.57 40.3 7.20 39.0 6.84 36.3 6.14
110% 120
30 46.4 7.66 44.4 7.21 41.7 6.43 40.3 6.24 39.0 5.94 36.3 5.48

35 47.0 6.90 44.4 6.32 41.7 5.76 40.3 5.60 39.0 5.22 36.3 4.71

20 38.5 7.18 38.2 7.40 37.5 7.80 36.7 7.26 35.5 6.90 33.1 6.19

25 42.1 7.61 40.3 7.20 37.5 6.54 36.7 6.23 35.5 5.91 33.1 5.33
100% 120
30 42.7 6.82 40.3 6.24 37.5 5.69 36.7 5.42 35.5 5.15 33.1 4.66

35 42.7 5.98 40.3 5.48 37.5 5.02 36.7 4.79 35.5 4.56 33.1 4.13

20 38.0 7.58 36.3 7.15 34.1 6.49 32.9 6.19 31.9 5.88 29.7 5.29

25 38.5 6.70 36.3 6.13 34.1 5.58 32.9 5.33 31.9 5.07 29.7 4.59
90% 120
30 38.5 5.81 36.3 5.33 34.1 4.88 32.9 4.66 31.9 4.45 29.7 4.03

35 38.5 5.13 36.3 4.71 34.1 4.32 32.9 4.13 31.9 3.94 29.7 3.59

20 34.1 6.53 32.2 5.98 30.3 5.45 29.3 5.19 28.4 4.95 26.5 4.47

25 34.1 5.61 32.2 5.15 30.3 4.71 29.3 4.50 28.4 4.30 26.5 3.90
80% 120
30 34.1 4.84 32.2 4.51 30.3 4.14 29.3 3.98 28.4 3.79 26.5 3.45

35 34.1 4.40 32.2 4.01 30.3 3.69 29.3 3.54 28.4 3.39 26.5 3.10

20 29.9 5.36 28.3 4.91 26.6 4.50 25.6 4.31 24.8 4.11 23.1 3.73

25 29.9 4.62 28.3 4.27 26.6 3.92 25.6 3.75 24.8 3.59 23.1 3.27
70% 120
30 29.9 4.07 28.3 3.77 26.6 3.46 25.6 3.32 24.8 3.18 23.1 2.92

35 29.9 3.63 28.3 3.36 26.6 3.11 25.6 2.97 24.8 2.87 23.1 2.64

20 25.6 4.30 24.2 3.97 22.7 3.65 22.0 3.50 21.3 3.35 19.8 3.06

25 25.6 3.75 24.2 3.47 22.7 3.21 22.0 3.08 21.3 2.96 19.8 2.72
60% 120
30 25.6 3.32 24.2 3.08 22.7 2.87 22.0 2.75 21.3 2.64 19.8 2.44

35 25.6 2.98 24.2 2.78 22.7 2.59 22.0 2.49 21.3 2.40 19.8 2.22

20 21.4 3.37 20.2 3.13 20.2 2.89 18.3 2.79 17.7 2.68 16.5 2.46

25 21.4 2.97 20.2 2.77 20.2 2.58 18.3 2.48 17.7 2.39 16.5 2.21
50% 120
30 21.4 2.67 20.2 2.49 20.2 2.32 18.3 2.24 17.7 2.16 16.5 2.01

35 21.4 2.41 20.2 2.26 20.2 2.12 18.3 2.05 17.7 1.98 16.5 1.84

Note:
1. is shown as reference
2. The above table shows the average value of conditions may operate
3. It is recommended to connect less than 130%

18
7. Accessories
7.1 Standard accessories
No Name Quantity Purpose
1 Main unit installation manual 1 /
2 Main unit owner’s manual 1 Be sure to deliver it to the customer
3 Indoor unit owner’s manual 1 Be sure to deliver it to the customer

4 User’s guideline 1 Be sure to deliver it to the customer

5 Bolts bag 1 Stone for service

6 Toggling flathead screw 1 For toggling of indoor and main units

7 Water outlet connector 1 For draining the internal condensed water of the unit

Block a drainage port of the unit chassis which do


8 Water outlet plug 1
not need to drainage
9 Seal ring 2 For avoiding water leakage of the chassis

10 Y-shape water filter 1 Connect to the side of water inlet pie

11 Indoor unit branch pipes 1


installation manual
12 Main unit branch pipes installation 1
manual
13 Seal plug 8 For pipe cleaning
14 Connective pipe accessory 1 Connect to the side of liquid pipe

15 Air side connective pipe 1 or 2 Connect to the air pipe side(8/10HP 1pc,12HP 2pcs)

19
8. Functional parts and safety devices
Item Symbol Capacity 8HP 10HP 12HP
Inverter Inverter compressor E655DHD-65D2YG E655DHD-65D2YG E655DHD-65D2YG
Safety
Compressor Current protection board 50A(IR341)-1
OLP
CCH Crank case heater DJRD-520A-1500-27.6W
Water inlet temp. of double-pipe
TSJ B:4100,R(25℃):10KΩ
heat exchanger
TSC1 Water outlet temp. of upper pipe B:4100,R(25℃):10KΩ
Temperature
TSC2 Water outlet temp. of lower pipe B:4100,R(25℃):10KΩ
sensor
T7 Discharge temp. sensor B:3950,R(25℃):56104.8Ω
Temp. sensor of inverter
T5 B:3950,R(25℃):56104.8Ω
module
High pressure sensor Model: YLCGQ-NSK-BD046I-U289
HPS
(discharge) 0-5Mpa
Pressure
sensor Low pressure sensor YK-0.05/0.15-2000
LPS
(suction) 0.05MPa

D32MISZ-1R
PMV Electronic expansion valve
4.2MPa
Functional
4-W/V 4-way valve STF-01VN1
Parts
FDF6A-049-PK(ZB) or FDF6A11
SV Solenoid valve
4.2MPa

20

You might also like