COMBUSTION MONITORING - MS9001FA+e
COMBUSTION MONITORING - MS9001FA+e
INTRODUCTION
Monitoring of the exhaust thermocouples to detect combustion problems is performed by the
SPEEDTRONIC micro processor based controllers coupled with solid state analog devices for
interfacing with the primary controls and protective devices. For operating instructions,
calibration, PROM constant listing and operational check procedures for a specific gas turbine,
refer to the Control Specifications. Refer to the control sequence program for details of algorithm
implementation and identification of selectable display lists and PROM constants.
ALLOWABLE SPREAD
The allowable spread is the sum of two values: a nominal spread and a bias. The nominal
allowable spread is the steady state spread limit. It varies, typically, between 30 and
125 degrees F as a function of average exhaust temperature and compressor discharge
temperature. The bias is an adder to the nominal allowable spread which accounts for the
temporary increase in actual spreads that occur during transient operational periods. It is a
temperature value which varies between 0 and, typically, 200 degree F.
During steady state operation, the bias value is 0 degree F. when a transient operational condition
occurs, such as rapid change in load, the bias value steps to 200 degree F. It remains at that value
until 2 minutes after the transient condition ends. Its value then decays exponentially to
0 degrees F on a 2 minute time constant. Refer Fig.
The transient conditions which cause the bias to step to 200 degrees F are:
- Fuel transfer
- Turbine startup and shutdown
- Load changes produced by a governor RAISE or LOWER signal (Either Manual or Auto)
- Load changes produced by a rapid change in FSR.
SPREAD TEST
The most advanced algorithm, which is standard for gas turbines with redundant sensors, makes
use of the temperature spread and adjacency tests to differentiate between actual combustion
problems and thermocouple failures. The behavior is summarized by the Venn diagram
(Figure CMFPR-2) where:
Sallow (TTXSPL) is the "Allowable Spread", based on average exhaust temperature and
compressor discharge temperature.
And:
SPREAD #1(S1): TTXSP1
The difference between the highest and the lowest thermocouple reading
The allowable spread must be between the limits TTKSPL7 and TTKSPL6 in degrees F, usually
about 30° and 125° F. The values of the combustion monitor program constants are listed in the
Control Specifications.
DISPLAY MESSAGES
The various monitor outputs to the control panel cause alarm message display as well as
appropriate control action. The combustion monitor outputs are given below.
2) If Exhaust temperature spread # 1 exceeds 5 times the allowable spread and the second
largest spread exceeds 0.8 times the allowable spread and the second and third lowest
thermocouples are adjacent
i.e TTXSP1 > 5 * TTXSPL & TTXSP2 > 0.8 * TTXSPL and the second and third
lowest T/C’s are adjacent
Or
3) If spread #3 exceeds the allowable spread (which means that spread 1 and 2 also exceeds
the allowable spread limit)
i.e All spreads exceeds the allowable spread limit
If any of these conditions exist for 9 seconds, the trip will latch and "HIGH EXHAUST TEMP
SPREAD TRIP" message will be displayed. The turbine will be tripped through the master
protective circuit. The alarm and trip signals will be displayed until they are acknowledged and
reset.
The best protection against shutdowns due to failed thermocouples is good thermocouple
maintenance. Replace failed thermocouples promptly during normal downtime so that the
likelihood of operation with more than one failed thermocouple is low.
The TC TROUBLE ALARM is intended to call attention to failed thermocouples so that they
will be promptly replaced (The TC TROUBLE ALARM will also be activated by the early
stages of some combustion problems).
The COMBUSTION TROUBLE ALARM is intended as an early warning of an actual
combustion malfunction. DO NOT OPERATE THE GAS TURBINE FOR A PROLONGED
TIME PERIOD WHEN THE COMBUSTION TROUBLE ALARM HAS BEEN ACTIVATED.
If black smoke is seen in the exhaust, trip the machine immediately. If there is no black smoke in
the exhaust, any period of operation with this alarm should be used to diagnose the trouble; as
failed thermocouples are much easier to detect when hot than at ambient temperature. In
addition, the fuel oil nozzle pressures can be read during operation to help diagnose poor fuel
distribution (See Combustion Alarm - Corrective Action). If the gas turbine has been tripped by
the monitor, it will be necessary to determine the cause.
Figures CMFPR-3 through 5 are Troubleshooting flowcharts to help in that determination.
Condition Figure
All possible problems though cannot be foreseen and initiative and judgment may be required to
troubleshoot.
Thermocouple Checking
The <HMI> station display and the printer, if available, can be used to check thermocouple
readings at any time. The combustion monitor will continue to protect the gas turbine while the
thermocouple readings are being displayed and printed.
Thermocouple malfunction may be detected by observing the <HMI> station display. An open
thermocouple will indicate a value of -40F. A thermocouple may be intermittently open if the
display is erratic or cyclic. With the turbine coasting down and the exhaust metal still hot, but the
exhaust air cooler, a thermocouple that reads significantly higher than the others is probably
shorted in its junction box.
Automatic Trip
If an automatic trip has occurred and a thermocouple has failed, the failed thermocouple may
have caused the trip. If not, assume a possible combustion or associated problem. Proceed in
accordance with Figure CMFPR-5
CAUTION
Follow the restart instructions carefully. It is impossible to be sure there is no combustion
problem from the tests referred to above. In case of doubt or if failed thermocouple patterns are
not found, it is recommended that the Bharat Heavy Electricals Limited Field Service
Representative be consulted.
Combustor
1. Failed Liner (Cracked or Burned)
2. Failed Transition Piece (Cracked or Burned)
3. Collapsed Liner
4. Hot Crossfire Tubes
Fuel System
1. Break in Liquid Fuel Line
2. Break in Gas Fuel Line
3. Plugged Check Valve
4. Check Valve Stuck Open/Closed
5. Liquid Fuel in Gas Manifold
6. Stuck Flow Divider
7. Failed Fuel Pump
Fuel Nozzle
1. Plugged Fuel Nozzle (Liquid or Gas)
2. Unscrewed Fuel Nozzle
3. Fuel Nozzle Erosion
4. Red Hot Fuel Nozzle
** WARNING **
Keep personnel away from the vicinity of the turbine and accessory compartments until the
problem has been identified.
A. Look for abnormal smoke from the exhaust. Trip the turbine if abnormal smoke is
observed.
CAUTION
During troubleshooting watch the displays of temperature spread closely and trip the turbine
in the event of a continuous or sudden increase.
B. Read and record the exhaust thermocouple temperatures using the display, and the
printer.
C. Record the "spread" displayed.
D. Proceed with a normal turbine shutdown.
E. If faulty exhaust thermocouples have been discovered, replace the thermocouples.
This fired condition, while the turbine is at low pressure, will permit personnel to read
and record the individual fuel nozzle pressure readings in the accessory compartment on
liquid fuel fired gas turbines.
I. If an abnormal condition is observed, trip the turbine and take corrective action.
J. If no abnormal condition can be discovered at this point, the turbine should be shutdown
and a combustion inspection performed.
K. Preliminary disassembly of the combustor end cover will permit inspection of the
combustion liner, a portion of the transition piece, the fuel nozzles and the crossfire
tubes. The extent of the inspection must be dictated by the nature of the problem.
L. The problem area discovered in the course of the combustion inspection should be
corrected and the turbine should be returned to normal operation.