PA C KA G E D E L E C T R I C / e l e c t r i c
KCA
Landmark® Rooftop Units
50 HZ
Bulletin No. 490186
P R O D U C T S P E C I F I C AT I O N S May 2018
Supersedes December 2017
Nominal Capacity - 10.5 to 21 kW (3 to 6 Tons)
Net Cooling Capacity − 9.1 to 17.4 kW (31 000 to 59 400 Btuh)
Optional Electric Heat − 5.7 to 23 kW
MODEL NUMBER IDENTIFICATION
K C A 060 S 4 B N 1 M
Brand/Family Voltage
K = Landmark® Product Line M = 380/420V-3 phase-50hz
Unit Type Minor Design Sequence
C = Packaged Electric Cooling w/ optional Electric Heat 1 = 1st Revision
2 = 2nd Revision
Major Design Sequence 3 = 3rd Revision
A = 1st Generation
Factory Installed Electric Heat
Nominal Cooling Capacity - Tons
N = No Heat
036 = 10.5 kW (3 Ton)
048 = 14 kW (4 Ton)
060 = 17.5 kW (5 Ton) Blower Type
072 = 21 kW (6 Ton) B = Belt Drive
Cooling Efficiency Refrigerant Type
S = Standard Efficiency 4 = R-410A
FEATURES AND BENEFITS
E
H
J
D
L
C
M
B
G K
F
I
(Cooling with Optional Electric Heat)
Shown With Optional Electric Heat, Economizer, Power
Exhaust and Hinged Access Panels
Landmark® rooftop units from Lennox are the new standard for reliable, efficient rooftop units built for long-lasting
performance that can significantly improve indoor environments. Landmark® rooftop units feature:
• R-410A Refrigerant - Environmentally friendly.
• Single Speed Scroll Compressor - Furnished on all models.
• Lennox’ Environ™ Coil System (072 models only) - Smaller, lighter condenser coil.
• High Pressure Switches - Protect compressor.
• Isolated Compressor Compartment - Allows performance check during normal compressor operation without
disrupting airflow.
• Belt Drive Blower Motors - Belt drive motors to maximize air performance.
• Independent Motor Mounts - Allows for easy and efficient service access without removing the top panel.
• Downflow or Horizontal Airflow - Easy field conversion.
• Two Fork Lift Slots on Three Sides - Easy to pick up and transport units from almost any angle.
• Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and improved
serviceability.
• Common Components - Many maintenance items are standard throughout the entire product line, reducing the
need to carry different parts to the job or maintain in inventory.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 2
FEATURES AND BENEFITS
CONTENTS Compressor Crankcase Heater
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 (072 Models)
Dimensions - Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 32 Protects against refrigerant
Dimensions - Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 migration that can occur during
low ambient operation.
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Refrigerant Metering Orifice
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . .1 Accurately meters refrigerant in
Optional Conventional Temperature Control Systems . . . . . . . . . . . 29 system.
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Refrigerant control is accomplished
Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 by exact sizing of refrigerant
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 metering orifice.
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 C Lennox’ Environ™ Coil System
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 (072 Models)
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Condenser
coil features
lightweight,
all aluminum
TESTING COOLING SYSTEM brazed fin
Components bonded for grounding Designed to maximize sensible construction.
to meet safety standards for and latent cooling performance at Constructed
servicing required by Underwriters design conditions. of three
Laboratories (UL) and the System can operate from −1°C components:
International Electrotechnical to 52°C without any additional a flat extrusion tubes, fins in-
Commission (IEC). controls. between the flat extrusion tubes
Cooling performance is rated and two refrigerant manifolds.
at test conditions included in R-410A Refrigerant Environ™ Coil System Features:
Air-Conditioning, Heating and Non-chlorine,
ozone friendly, • I mproved heat transfer
Refrigeration Institute (AHRI) performance due to high
Standard 210/240-2008 while R-410A.
primary surface area (flat
operating at rated voltage and air Unit pre-charged with refrigerant. tubes) versus secondary
volumes. See Specification table. surface (fins).
International Organization for • S maller internal volume
Standardization (ISO) 9001 B Scroll Compressor
Scroll compressors for high (reduced refrigerant charge).
Registered Manufacturing Quality
performance, reliability and quiet • High durability (all aluminum
System.
operation. construction).
Resiliently mounted on rubber • Fewer brazed joints.
grommets for quiet operation. • Compact design (reduces unit
weight).
• Easy maintenance/cleaning.
Mounting brackets with rubber
inserts secure coil to unit providing
vibration dampening and corrosion
protection.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 3
FEATURES AND BENEFITS
COOLING SYSTEM Options/Accessories G Exterior Panels
(continued) Constructed of heavy-gauge,
Field Installed
Conventional Fin/Tube Coil galvanized steel with a two-layer
(Condenser Coil for 036 thru 060 Condensate Drain Trap enamel paint finish.
models) and Evaporator Coil (all Field installed only.
models) Available in copper or polyvinyl H Insulation
All panels adjacent to conditioned
Copper tube construction, chloride (PVC).
air are fully insulated with non-
enhanced rippled-edge aluminum
Compressor Crankcase Heater hygroscopic fiberglass insulation.
fins, flared shoulder tubing
connections, silver soldered (Optional for 036 thru 060 Unit base is fully insulated. The
construction for improved heat Models) insulation also serves as an air
transfer. Factory leak tested. Protects against refrigerant seal to the roof curb, eliminating
Cross row circuiting optimizes migration that can occur during low the need to add a seal during
both sensible and latent cooling ambient operation. installation.
capacity. Drain Pan Overflow Switch Access Panels
High Pressure Switch Monitors condensate level in Access panels are provided for
Protects the compressor from drain pan, shuts down unit if drain the economizer/filter section,
overload conditions such as becomes clogged. heating/blower section, and the
dirty condenser coils, blocked compressor/controls section.
Low Ambient Kit
refrigerant flow, or loss of outdoor NOTE - 072 models include a
Cycles the outdoor fan while
fan operation. filler panel for proper cabinet
allowing compressor operation in
Filter/Drier the cooling cycle. This intermittent fit for optional accessories
High capacity filter/drier protects fan operation allows the system (Economizers, Power Exhaust,
the system from dirt and moisture. to operate without icing the Outdoor Air Dampers and
evaporator coil and losing capacity. Barometric Relief Dampers).
Freezestat
Designed for use in ambient Options/Accessories
Protects the evaporator coil from
temperatures no lower than −18°C.
damaging ice build-up due to Factory Installed
A crankcase heater must be
conditions such as low/no air flow,
installed on the compressor. Corrosion Protection
or low refrigerant charge.
CABINET A completely flexible immersed
Condensate Drain Pan coating with an electrodeposited
Plastic pan, sloped to meet E Construction dry film process (AST ElectroFin
drainage requirements of American Heavy-gauge steel panels and full E-Coat). Meets Mil Spec
Society of Heating Refrigeration perimeter heavy-gauge galvanized MIL-P-53084, ASTM B117
and Air Conditioning Engineers steel base rail provides structural Standard Method Salt Spray
62.1. integrity for transportation, Testing.
handling, and installation.
Side or bottom drain connections. Indoor Corrosion Protection:
Reversible to allow connection at Base rails have rigging holes.
Three sides of the base rail have • Coated coil
back of unit.
fork slots. • Painted blower housing
D Outdoor Coil Fan Motor Raised edges around duct and • Painted base
Thermal overload protected, totally power entry openings in the bottom Outdoor Corrosion Protection:
enclosed, permanently lubricated of the unit provide additional
sleeve (036 and 048 models) • Coated coil
protection against water entering
or ball bearings (060 and 072 the building. • Painted base
models), shaft up, wire basket
mount. Airflow Choice
Units are shipped in downflow
Outdoor Coil Fan (vertical) configuration, can be field
Polyvinyl chloride (PVC) coated converted to horizontal air flow
fan guard furnished. configuration without the need of
Required Selections a kit.
Cooling Capacity F Power Entry
Specify nominal cooling capacity of Electrical lines can be brought
the unit. through the unit base or through
horizontal access knock-outs.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 4
FEATURES AND BENEFITS
CABINET (continued) J BLOWER Healthy Climate® UVC
A wide selection of supply air Germicidal Lamps
I Hinged Access Panels blower options are available
Large access panels are hinged
to meet a variety of air flow
and have quarter-turn latches
requirements.
for quick and easy access to
maintenance areas (economizer Motor
/ filter, compressor / controls, Overload protected, equipped with
heating / blower). ball bearings.
Field Installed Single Speed belt drive motors
are offered on all models and are Helps eliminate mold and bacterial
Combination Coil/Hail Guards available in several different sizes growth on the evaporator and drain
Heavy gauge steel frame painted to maximize air performance. pans. Improves indoor air quality
to match cabinet with expanded
metal mesh to protect the outdoor Supply Air Blower and maintains efficiency of system
coil from damage. Forward curved blades, blower by reducing fouling of evaporator
wheel is statically and dynamically coil.
CONTROLS
balanced. Indoor Air Quality (CO2) Sensor
Unit Control Motors have adjustable pulley for Monitors CO2 levels adjusts
All control voltage is provided via a speed change. economizer dampers as needed
24V (secondary) transformer with
for Demand Control Ventilation.
built-in circuit breaker protection. Ordering Information
Specify drive kit number when ELECTRICAL
Heat/Cool Staging - Capable of base unit is ordered. Marked & Color-Coded Wiring
up to 2 heat / 2 cool staging with a
third party DDC control system or Required Selections All electrical wiring is color-coded
thermostat. and marked to identify which
Supply Air Blower components it is connecting.
Low Voltage Terminal Block - Order one drive kit, see Drive Kit
Provides screw terminal Electrical Plugs
Specifications Table.
connections for thermostat or Positive connection electrical plugs
controller wiring. INDOOR AIR QUALITY are used to connect common
Air Filters accessories or maintenance parts
Night Setback Mode - Saves for easy removal or installation.
energy by closing outdoor air Disposable 51 mm filters furnished
dampers and operating supply fan as standard. Unit Sub-Fuse Blocks
on thermostat demand only. Furnished as standard on all units.
Options/Accessories
Options/Accessories Required Selections
Field Installed
Field Installed Healthy Climate® High Efficiency Voltage Choice
Air Filters Specify when ordering base unit.
Smoke Detector
Photoelectric type, installed in Disposable MERV 8 or MERV 13 Options/Accessories
supply air section, return air (Minimum Efficiency Reporting
section or both sections. Available Value based on ASHRAE 52.2) Field Installed
with power board and single efficiency 51 mm pleated filters. K Electric Heat
sensor (supply or return) or power Electric Heat is CE marked.
board and two sensors (supply and Helix wound nichrome elements,
return). Power board located in unit individual element limit controls,
control compartment. wiring harness. Unit fuse block is
Thermostats furnished as standard.
Control system and thermostat
options, see page 29.
Aftermarket unit controller options,
see Options/Accessories table.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 5
OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS Economizer Controls: Module automatically detects
• Damper Minimum Position sensors by polling to determine
Factory or Field Installed which sensors are installed in
- Can be set lower than
L Economizer traditional minimum air system.
(Standard and High Performance requirements resulting in cost Module displays any alarm
Common Features) savings. messages (fault detection
Outdoor Air Hood is furnished. and diagnostics) as an aid in
• IAQ Sensor - Signals
Factory installed Economizer dampers to modulate and troubleshooting.
can be ordered with two exhaust maintain 13°C when CO2 is Non-volatile memory retains
options: higher than the CO2 setpoint. parameter settings in case of
• Barometric Relief Dampers • Demand Control Ventilation power failure.
and Exhaust Hood. (DCV) LED - A steady green Keypad with four navigation
• No Exhaust. Demand Control Ventilation buttons and LCD screen is
Field installed Economizer includes LED indicates the IAQ reading furnished for setting economizer
Barometric Relief Dampers with is higher than setpoint and parameters.
Exhaust Hood. requires more fresh air. • Menu Up/Exit button
Barometric Relief Dampers allow • Free Cool LED - A steady returns to the main menu.
relief of excess air, aluminum blade green LED indicates outdoor • A rrow Up button moves
dampers prevent blow back and air is suitable for free cooling. to the previous or next
outdoor air infiltration during off Free Cooling runs when outdoor parameter within the selected
cycle, bird screen furnished. air temperature is lower than menu.
Occupied/Unoccupied mode with the set temperature on the • Arrow Down button moves
field furnished setback thermostat. economizer control. to the next parameter within
Demand Control Ventilation (DCV) NOTE: The Free Cooling the selected menu.
ready using optional CO2 sensors. default setting for outdoor air • Select (enter) button
temperature sensor is 13°C. confirms parameter selection.
Mixed Air Sensor is furnished for
field installation in the rooftop unit. High Performance Main Menu Structure:
Sensor is factory installed when Economizer Features • STATUS (economizer and
Economizers are factory installed. Gear-driven action, high torque system operation status)
Single sensible sensor is furnished 24-volt fully-modulating spring
• SETPOINTS (settings for
with Economizer and enables return damper motor, return air
various setpoint parameters)
economizer operation if the and outdoor air dampers, plug-in
outdoor temperature is less than connections to unit, nylon bearings, • SYSTEM SETUP (settings/
the setpoint of the control. enhanced neoprene blade edge information about the system)
seals and flexible stainless steel • ADVANCED SETUP (freeze
Horizontal Economizer Conversion
jamb seals to minimize air leakage. protection, CO2 settings,
kit is available for field installation.
High Performance stage 3 delay and additional
Standard Economizer Features Economizer Control Module calibration settings)
Gear-driven action, return air Module • CHECKOUT (damper
and outdoor air dampers, plug- provides inputs positions)
in connections to unit, neoprene and outputs • ALARMS (output signal that
seals, 24-volt, fully-modulating to control can be configured for remote
spring return motor. economizer alarm monitoring)
Standard Economizer based on Refer to Installation Instructions
Control Module parameter settings. for complete setup information
The Standard and menu parameters available.
Economizer
Control Module
can be adjusted
to operate based
on outdoor air
temperatures.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 6
OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS EXHAUST OPTIONS ROOF CURBS
(continued) Nailer strip furnished, mates to unit,
Field Installed
US National Roofing Contractors
Factory or Field Installed
M Power Exhaust Fan Approved, shipped knocked down.
Single Enthalpy Temperature Installs internal to unit for downflow
Hybrid Roof Curbs, Downflow
Control applications only with Economizer
Roof curb can be assembled using
Outdoor air enthalpy sensor option. Provides exhaust air
interlocking tabs to fasten corners
enables Economizer if the outdoor pressure relief. Interlocked to
together. No tools required.
enthalpy is less than the setpoint of run when supply air blower is
the control. operating, fan runs when outdoor Curb can also be fastened together
air dampers are 50% open with furnished hardware.
Field Installed
(adjustable), motor is overload Available in 203, 356, 457, and
Differential Enthalpy Control protected. 610 mm heights.
Order two Single Enthalpy Fan is 406 mm diameter with 4 fan
Controls. One is field installed in Adjustable Pitch Curb
blades and a 0.25 kW motor.
the return air section, the other in Fully adjustable pitch curb provides
the outdoor air section. Allows the NOTE - If Power Exhaust is field a level platform for rooftop units
economizer control board to select installed with a factory installed allowing flexible installations on
Economizer, the Economizer must roofs with uneven or sloped angles.
between outdoor air or return air,
be ordered with the “No Exhaust”
whichever has lower enthalpy. Maximum slope is 19 mm per
option and the Barometric Relief
Horizontal Economizer Dampers with Exhaust Hood must 300 mm in any direction.
Conversion Kit also be ordered separately for field Uses interlocking tabs to fasten
Insulated panel covers the bottom installation. corners together. No tools required.
return air opening on the unit base OUTDOOR AIR OPTIONS Hardware is furnished to connect
to convert downflow Economizer to upper curb with lower curb.
horizontal airflow. Factory or Field Installed
Available in 356 mm height.
Outdoor Air Dampers -
Downflow or Horizontal Adaptor Curbs (not shown)
Single blade damper, 0 to 25% Curbs are regionally sourced.
(fixed) outdoor air adjustable, Dimensions will vary based
installs in unit. upon the source. Contact your
local sales representative for a
Automatic model features fully
detailed cut sheet with applicable
modulating spring return damper
dimensions.
motor with plug-in connection.
Manual model features a slide CEILING DIFFUSERS
damper. Maximum mixed air Ceiling Diffusers (Flush and
temperature in cooling mode: 38°C. Step-Down)
Outdoor Air Hood is furnished. Diffuser face and grilles with white
powder coat finish, insulated (UL
listed duct liner), diffuser box
with collars for duct connection,
fixed blades (flush diffusers) and
double deflection blades (step-
down diffusers), provisions for
suspending, internally sealed
(prevents recirculation), removable
return air grille, adapts to T-bar
ceiling grids or plaster ceilings.
Transitions (Supply and Return)
Used with diffusers, installs
in roof curb, galvanized steel
construction, flanges furnished for
duct connection to diffusers, fully
insulated.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 7
OPTIONS / ACCESSORIES
Unit Model Number
Item Model Catalog KCA KCA KCA KCA
No. No. 036 048 060 072
COOLING SYSTEM
Compressor Crankcase Heater 380/420V-3ph - K1CCHT012A-2G 14D87 X X
380/420V-3ph - T1CCHT01AN2G 14D84 X
Condensate Drain Trap Polyvinyl Chloride (PVC) - C1TRAP20AD2 76W26 X X X X
Copper - C1TRAP10AD2 76W27 X X X X
Drain Pan Overflow Switch K1SNSR71AB1- 74W42 X X X X
Low Ambient Kit K1SNSR33AN2 14D89 X X X X
Efficiency Standard O O O O
Refrigerant Type R-410A O O O O
BLOWER - SUPPLY AIR
Motors Belt Drive - 1.5 kW Standard Efficiency Factory O O O 1
O
Drive Kits Kit A01 - T1DRKT001-1 - 561 - 842 rev/min Factory O
See Blower Data Tables Kit A02 - T1DRKT002-1 - 621 - 931 rev/min Factory O
for selection
Kit A03 - T1DRKT003-1 - 694 - 1042 rev/min Factory O
Kit A04 - T1DRKT004-1 - 804-1117 rev/min Factory 1
O
Kit A05 - T1DRKT005-1 - 748 - 1122 rev/min Factory O
Kit A06 - T1DRKT006-1 - 893 - 1191 rev/min Factory O
Kit A07 - T1DRKT007-1 - 1010 - 1290 rev/min Factory O
Kit A08 - T1DRKT008-1 - 994 - 1326 rev/min Factory 1
O
Kit A09 - T1DRKT009-1 - 1193 - 1594 rev/min Factory 1
O
Kit AA02 - T1DRKT002AP1 - 527 -729 rev/min Factory 2
O
Kit AA03 - T1DRKT003AP1 - 665 - 921 rev/min Factory 2
O
Kit AA04 - T1DRKT004AP1 - 768 - 1023 rev/min Factory 2
O
CABINET
Hinged Access Panels Factory O O O O
Combination Coil/Hail Guards C1GARD51A-1 13R98 X X X
C1GARD51AT1 13T03 X
Corrosion Protection Factory O O O O
CONTROLS
BACnet® K0CTRL31A-2 16X70 OX OX OX OX
BACnet® Thermostat with Display K0SNSR01FF1 97W23 X X X X
BACnet Thermostat without Display
®
K0SNSR00FF1 97W24 X X X X
Novar® 2051 K0CTRL30A-1 96W11 OX OX OX
K0CTRL30AP1 12B98 OX
Plenum Cable - 23 m K0MISC00FF1 97W25 X X X X
Smoke Detector - Supply or Return C1SNSR44AP1 53W78 X X X X
(Power board and one sensor)
Smoke Detector - Supply and Return C1SNSR43AP1 53W79 X X X X
(Power board and two sensors)
1
072S Single Speed Belt Drive models only.
2
072H Single Speed Belt Drive.
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 8
OPTIONS / ACCESSORIES
Unit Model Number
Item Model Catalog KCA KCA KCA KCA
No. No. 036 048 060 072
ECONOMIZER
Standard Economizer With Outdoor Air Hood (Sensible Control)
Standard Economizer - Includes Barometric Relief Dampers K1ECON30A-3- 14D90 OX OX OX OX
and Exhaust Hood
Standard Economizer - No Exhaust Factory O O O O
Standard Economizer Controls
Single Enthalpy Control C1SNSR64FF1 53W64 OX OX OX OX
Differential Enthalpy Control (order 2) C1SNSR64FF1 53W64 X X X X
High Performance Economizer With Outdoor Air Hood
High Performance Economizer - Includes Barometric Relief K1ECON32A-3 16X75 OX OX OX OX
Dampers and Exhaust Hood
High Performance Economizer Controls
Single Enthalpy Control C1SNSR60FF1 10Z75 OX OX OX OX
Differential Enthalpy Control (order 2) C1SNSR60FF1 10Z75 X X X X
Economizer Accessories
Horizontal Economizer Conversion Kit T1HECK00AN1 17W45 X X X X
OUTDOOR AIR
Outdoor Air Dampers With Outdoor Air Hood
Motorized C1DAMP21A-1 15D17 OX OX OX OX
Manual C1DAMP11A-2 15D18 OX OX OX OX
Power EXhaust FAN
Standard Static 380/420V-3ph - C1PWRE10A-1M 79W93 X X X X
NOTE - Order Barometric
Relief Dampers with Exhaust
Hood below if unit is ordered
with factory installed Standard
Economizer with “No Exhaust”
option
1
BAROMETRIC RELIEF
Barometric Relief Dampers with Exhaust Hood C1DAMP50A-1- 74W38 X X X X
ELECTRICAL
Voltage 50 hz with neutral 380/420V − 3 phase O O O O
2
ELECTRIC HEAT
5.7 kW K1EH0057AN1M 67W92 X X X X
11.5 kW K1EH0115AN1M 67W93 X X X X
17.2 kW K1EH0172AN1M 67W94 X X
23 kW K1EH0230N-1M 67W95 X
1
Required when Economizer is factory installed (no exhaust option) with field installed Power Exhaust Fan option.
2
Nominal kW at 420V-3ph-50hz.
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 9
OPTIONS / ACCESSORIES
Item Unit Model Number
Model Catalog
KCA KCA KCA KCA
No. No.
036 048 060 072
Indoor Air Quality
Air Filters
Healthy Climate® High Efficiency MERV 8 (406 x 508 x 51) - C1FLTR15A-1- 54W20 X X X
Air Filters MERV 13 (406 x 508 x 51) - T1FLTR40A-1- 52W37 X X X
Order 4 per unit
MERV 8 (508 x 508 x 51) - C1FLTR15D-1- 54W21 X
MERV 13 (508 x 508 x 51) - C1FLTR40D-1- 52W39 X
Indoor Air Quality (CO2) Sensors
Sensor - Wall-mount, off-white plastic cover with LCD C0SNSR50AE1L 77N39 X X X X
display
Sensor - Wall-mount, black plastic case, no display, rated C0SNSR53AE1L 87N54 X X X X
for plenum mounting
CO2 Sensor Duct Mounting Kit - for downflow C0MISC19AE1- 85L43 X X X X
applications
Aspiration Box - for duct mounting non-plenum rated CO2 C0MISC16AE1- 90N43 X X X X
sensor (77N39)
UVC Germicidal Lamps
1
Healthy Climate® UVC Light Kit (220V-1ph) E1UVCL10AN1- 50W90 X X X X
ROOF CURBS
Hybrid Roof Curbs, Downflow
203 mm height C1CURB70A-1 11F50 X X X X
356 mm height C1CURB71A-1 11F51 X X X X
457 mm height C1CURB72A-1 11F52 X X X X
610 mm height C1CURB73A-1 11F53 X X X X
Adjustable Pitch Curb, Downflow
356 mm height C1CURB55AT1 43W27 X X X X
CEILING DIFFUSERS
Step-Down - Order one RTD9-65S 13K60 X X X
RTD11-95S 13K61 X
Flush - Order one FD9-65S 13K55 X X X
FD11-95S 13K56 X
Transitions (Supply and Return) - Order one T1TRAN10AN1 17W53 X X X
T1TRAN20N-1 17W54 X
1
amps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 380/420V primary to 220V secondary units. Alternately,
L
220V power supply may be used to directly power the UVC ballast(s).
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (Factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 10
SPECIFICATIONS 10.5 - 21 KW
General Data Nominal Size 10.5 kW (3 Ton) 14.0 kW (4 Ton) 17.5 kW (5 Ton) 21 kW (6 Ton)
Model No. KCA036S4B KCA048S4B KCA060S4B KCA072S4B
Efficiency Type Standard Standard Standard Standard
Blower Type Single Speed Single Speed Single Speed Single Speed Belt
Belt Drive Belt Drive Belt Drive Drive
Cooling Gross Cooling Capacity - kW (Btuh) 9.5 (32 500) 12.7 (43 300) 15.8 (53 900) 18.4 (62 500)
Performance 1
Net Cooling Capacity - kW (Btuh) 9.1 (31 000) 12.1 (41 200) 15.0 (51 100) 17.4 (59 400)
Rated Air Flow - L/s (cfm) 565 (1200) 755 (1600) 850 (1800) 1156 (2450)
3
Sound Rating Number (dB) 75 75 82 79
Total Unit Power - kW 3 3.9 4.7 5.2
1
SEER (Btuh/Watt) 13.0 13.0 13.0 11.3
1
EER (Btuh/Watt) at 35°C (95°F) 10.9 11.1 11.3 8.3
2
EER (Btuh/Watt) at 46°C (115°F) 8.5 8.7 9.6 12.3
Refrigerant Type R-410A R-410A R-410A R-410A
Charge Furnished 3.52 kg 3.97 kg 5.67 kg 3.20 kg
(7 lbs. 12 oz.) (8 lbs. 12 oz.) (12 lbs. 8 oz.) (7 lbs. 1 oz.)
Compressor Type (one per unit) Scroll Scroll Scroll Scroll
Outdoor Coil Net face area - m (sq. ft.)
2
1.45 (15.6) 1.45 (15.6) 1.45 (15.6) 1.65 (17.8)
Tube diameter - mm (in.) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8) 1
Number of rows 1 1.5 2 ---
Fins per meter (Fins per inch) 788 (20) 788 (20) 788 (20) 905 (23)
Outdoor Motor W (hp) 187 (1/4) 187 (1/4) 249 (1/3) 249 (1/3)
Coil Fan
Motor rev/min 690 690 900 900
Total motor watts 190 190 280 280
Diameter - mm (in.) / No. of blades 610 (24) - 3 610 (24) - 3 610 (24) - 3 610 (24) - 3
Total air volume - L/s (cfm) 1465 (3100) 1370 (2900) 1700 (3600) 1850 (3920)
Indoor Coil Net face area - m (sq. ft.)
2
0.72 (7.78) 0.72 (7.78) 0.72 (7.78) 0.90 (9.7)
Tube diameter - mm (in.) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8)
Number of rows 3 3 4 4
Fins per meter (Fins per inch) 551 (14) 551 (14) 551 (14) 551 (14)
Drain Connection (no.and size) - in. (1) 1 NPT (1) 1 NPT (1) 1 NPT (1) 1 NPT
Expansion device type Refrigerant Metering Orifice (RFC)
4
Indoor Nominal Motor Size kW (HP) 1.5 (2) 1.5 (2) 1.5 (2) 1.5 (2)
Blower
Maximum Usable Motor Size kW (HP) 1.7 (2.3) 1.7 (2.3) 1.7 (2.3) 1.7 (2.3)
& Drive
Selection Drive Kit (rev/min range) A01 - (561 - 842) A02 - (621 - 931) A03 (694 - 1042) A08 (994 - 1326)
A05 - (748 - 1122) A06 - (893 - 1191) A07 (1010 - 1290) A09 (1193 - 1594)
Wheel nominal diameter x width - mm (in.) 254 x 254 (10 x 10) 254 x 254 (10 x 10) 254 x 254 (10 x 10) 254 x 254 (10 x 10)
Filters Type Disposable Disposable Disposable Disposable
Number and size - mm (in.) (4) 406 x 508 x 51 (4) 406 x 508 x 51 (4) 406 x 508 x 51 (4) 508 x 508 x 51
(16 x 20 x 2) (16 x 20 x 2) (16 x20 x 2) (20 x 20 x 2)
Electrical Characteristics - 50 Hz 380/420V - 50 hertz - 3 phase with neutral
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
Tested at conditions which are based on AHRI Standard 210/240; 35°C (95°F) outdoor air temperature and 27°C (80°F) dry bulb/19°C (67°F) wet bulb entering evaporator
air; minimum external duct static pressure while operating at rated voltage and air volumes.
2
Rated at 46°C (115°F) outdoor air temperature and 27°C (80°F) db/19°C (67°F) wb entering evaporator air (T3 Conditions).
3
Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270.
4
Using total air volume and system static pressure requirements determine from blower performance tables rev/min and motor size required. Maximum usable size of
motors furnished is shown. If motors of comparable size are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 11
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
10.5 KW - KCA036S4
Outdoor Air Temperature Entering Outdoor Coil
Entering Total 26.7°C 35°C 43.3°C 46°C
Wet Air
Bulb Volume Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T)
Temper-
ature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
455 9.4 1.82 0.78 0.91 1 8.5 2.21 0.8 0.94 1 7.6 2.68 0.83 0.98 1 7.2 2.87 0.8 0.98 1
17.2°C 565 9.9 1.83 0.84 0.98 1 9 2.22 0.85 1 1 8.1 2.7 0.89 1 1 7.8 2.87 0.88 1 1
680 10.4 1.84 0.88 1 1 9.5 2.23 0.91 1 1 8.6 2.71 0.95 1 1 8.2 2.89 0.95 1 1
455 10 1.83 0.61 0.75 0.89 9.1 2.22 0.61 0.77 0.91 8.1 2.7 0.62 0.8 0.95 7.7 2.87 0.6 0.78 0.95
19.4°C 565 10.5 1.84 0.65 0.82 0.95 9.5 2.23 0.66 0.84 0.98 8.5 2.7 0.67 0.87 1 8.1 2.88 0.65 0.86 1
680 10.8 1.85 0.68 0.87 1 9.8 2.24 0.7 0.9 1 8.8 2.71 0.72 0.93 1 8.4 2.89 0.7 0.93 1
455 10.5 1.84 0.45 0.6 0.73 9.6 2.23 0.45 0.61 0.75 8.6 2.71 0.44 0.61 0.78 8.2 2.89 0.42 0.6 0.76
21.7°C 565 11 1.86 0.48 0.64 0.8 10.1 2.25 0.46 0.65 0.82 9 2.72 0.46 0.66 0.86 8.6 2.89 0.45 0.65 0.84
680 11.4 1.87 0.49 0.67 0.85 10.4 2.25 0.48 0.69 0.88 9.3 2.73 0.49 0.71 0.92 8.9 2.9 0.48 0.7 0.91
Outdoor Air Temperature Entering Outdoor Coil
Entering Total 48°C 50°C 51.7°C
Wet Air
Bulb Volume Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T)
Temper-
ature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
455 7 3.01 0.84 1 1 6.7 3.17 0.86 1 1 6.5 3.31 0.87 1 1
17.2°C 565 7.5 3.02 0.91 1 1 7.3 3.17 0.93 1 1 7.1 3.32 0.94 1 1
680 8 3.03 0.97 1 1 7.7 3.19 0.99 1 1 7.5 3.33 0.99 1 1
455 7.4 3.02 0.62 0.82 0.97 7.2 3.17 0.62 0.83 0.98 6.9 3.31 0.63 0.85 0.99
19.4°C 565 7.8 3.03 0.68 0.9 1 7.5 3.18 0.69 0.91 1 7.3 3.32 0.69 0.92 1
680 8.1 3.03 0.73 0.96 1 7.8 3.19 0.74 0.97 1 7.5 3.33 0.75 0.98 1
455 7.9 3.03 0.43 0.62 0.8 7.6 3.18 0.43 0.62 0.8 7.4 3.32 0.43 0.62 0.82
21.7°C 565 8.3 3.04 0.45 0.68 0.88 8 3.19 0.45 0.68 0.89 7.7 3.33 0.45 0.69 0.9
680 8.6 3.05 0.48 0.73 0.94 8.3 3.2 0.49 0.74 0.96 8 3.34 0.49 0.75 0.96
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 12
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
14 KW - KCA048S4
Outdoor Air Temperature Entering Outdoor Coil
Entering Total 26.7°C 35°C 43.3°C 46°C
Wet Air
Bulb Volume Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T)
Temper-
ature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
605 12.7 2.34 0.77 0.91 1 11.3 2.85 0.79 0.94 1 10 3.43 0.81 0.98 1 9.5 3.64 0.79 0.98 1
17.2°C 755 13.4 2.34 0.83 0.98 1 12 2.86 0.85 1 1 10.7 3.46 0.88 1 1 10.3 3.67 0.88 1 1
905 14 2.35 0.87 1 1 12.7 2.88 0.91 1 1 11.3 3.47 0.95 1 1 10.8 3.69 0.95 1 1
605 13.4 2.34 0.6 0.75 0.88 12.1 2.87 0.6 0.77 0.91 10.7 3.46 0.6 0.79 0.95 10.2 3.66 0.59 0.77 0.96
19.4°C 755 14.1 2.35 0.64 0.81 0.95 12.7 2.88 0.64 0.84 0.98 11.2 3.47 0.65 0.87 1 10.7 3.68 0.64 0.86 1
905 14.7 2.35 0.68 0.86 1 13.1 2.89 0.69 0.89 1 11.6 3.49 0.7 0.93 1 11.1 3.7 0.69 0.94 1
605 14.2 2.35 0.44 0.59 0.72 12.8 2.88 0.43 0.59 0.75 11.3 3.48 0.41 0.6 0.77 10.8 3.68 0.41 0.59 0.76
21.7°C 755 14.9 2.35 0.47 0.63 0.79 13.5 2.9 0.46 0.64 0.82 11.8 3.49 0.43 0.65 0.85 11.4 3.7 0.43 0.64 0.84
905 15.4 2.35 0.48 0.67 0.85 13.9 2.9 0.48 0.68 0.88 12.3 3.51 0.47 0.7 0.91 11.7 3.72 0.46 0.69 0.92
Outdoor Air Temperature Entering Outdoor Coil
Entering Total 48°C 50°C 51.7°C
Wet Air
Bulb Volume Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T)
Temper-
ature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
605 9.2 3.82 0.83 1 1 8.8 4 0.84 1 1 8.6 4.16 0.85 1 1
17.2°C 755 9.9 3.84 0.9 1 1 9.6 4.02 0.92 1 1 9.3 4.18 0.93 1 1
905 10.5 3.86 0.97 1 1 10.1 4.04 0.98 1 1 9.8 4.2 0.99 1 1
605 9.8 3.84 0.6 0.81 0.97 9.5 4.02 0.61 0.82 0.98 9.1 4.18 0.61 0.83 0.99
19.4°C 755 10.3 3.85 0.66 0.89 1 9.9 4.03 0.67 0.9 1 9.5 4.19 0.67 0.91 1
905 10.7 3.87 0.72 0.96 1 10.3 4.04 0.72 0.97 1 9.9 4.21 0.73 0.98 1
605 10.5 3.86 0.41 0.6 0.79 10.1 4.03 0.4 0.6 0.8 9.7 4.19 0.4 0.61 0.8
21.7°C 755 11 3.88 0.44 0.66 0.87 10.6 4.05 0.43 0.67 0.88 10.2 4.21 0.43 0.67 0.9
905 11.3 3.89 0.46 0.72 0.94 10.9 4.06 0.46 0.72 0.96 10.5 4.22 0.46 0.73 0.97
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 13
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
17.5 KW - KCA060S4
Outdoor Air Temperature Entering Outdoor Coil
Entering Total 26.7°C 35°C 43.3°C 46°C
Wet Air
Bulb Volume Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T)
Temper-
ature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
755 15.9 2.72 0.72 0.9 1 14.6 3.26 0.74 0.94 1 13.2 3.92 0.76 1 1 12.8 4.16 0.82 1 1
17.2°C 945 16.6 2.74 0.78 1 1 15.4 3.29 0.81 1 1 14.1 3.96 0.87 1 1 13.7 4.2 0.92 1 1
1135 17.5 2.77 0.86 1 1 16.1 3.32 0.91 1 1 14.8 3.99 0.98 1 1 14.3 4.23 1 1 1
755 16.9 2.75 0.56 0.7 0.85 15.5 3.29 0.57 0.72 0.9 14 3.96 0.57 0.74 0.96 13.5 4.19 0.61 0.8 0.99
19.4°C 945 17.5 2.77 0.59 0.76 0.97 16.1 3.32 0.61 0.79 1 14.6 3.98 0.62 0.84 1 14.1 4.22 0.67 0.9 1
1135 18 2.79 0.63 0.83 1 16.5 3.34 0.65 0.88 1 15 3.99 0.67 0.95 1 14.4 4.23 0.72 0.99 1
755 17.8 2.79 0.42 0.55 0.67 16.4 3.33 0.41 0.56 0.7 14.9 3.99 0.41 0.57 0.72 14.4 4.23 0.42 0.6 0.78
21.7°C 945 18.5 2.81 0.43 0.58 0.74 17 3.36 0.44 0.6 0.76 15.4 4.02 0.43 0.63 0.81 14.8 4.25 0.45 0.66 0.88
1135 19 2.83 0.45 0.63 0.81 17.4 3.37 0.45 0.64 0.86 15.8 4.03 0.46 0.67 0.93 15.2 4.26 0.48 0.72 0.97
Outdoor Air Temperature Entering Outdoor Coil
Entering Total 48°C 50°C 51.7°C
Wet Air
Bulb Volume Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T)
Temper-
ature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
755 12.5 4.36 0.79 1 1 12.2 4.57 0.8 1 1 11.9 4.76 0.81 1 1
17.2°C 945 13.3 4.4 0.91 1 1 13 4.6 0.93 1 1 12.6 4.78 0.95 1 1
1135 14 4.43 1 1 1 13.6 4.63 1 1 1 13.2 4.81 1 1 1
755 13.2 4.39 0.59 0.76 1 12.8 4.59 0.6 0.78 1 12.4 4.76 0.6 0.78 1
19.4°C 945 13.7 4.41 0.64 0.88 1 13.2 4.61 0.65 0.91 1 12.8 4.79 0.65 0.92 1
1135 14 4.42 0.7 0.99 1 13.6 4.63 0.71 1 1 13.2 4.8 0.72 1 1
755 14 4.43 0.42 0.57 0.74 13.5 4.63 0.41 0.59 0.76 13.1 4.8 0.42 0.6 0.77
21.7°C 945 14.4 4.44 0.43 0.64 0.86 14 4.64 0.45 0.64 0.88 13.6 4.82 0.45 0.65 0.9
1135 14.8 4.46 0.46 0.7 0.98 14.3 4.66 0.47 0.71 0.99 13.9 4.84 0.47 0.72 1
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 14
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
21 KW - KCA072S4
Outdoor Air Temperature Entering Outdoor Coil
Entering Total 26.7°C 35°C 43.3°C 46°C
Wet Air
Bulb Volume Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T)
Temper-
ature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
905 18.5 3.39 0.77 0.93 1 16.4 4 0.8 0.97 1 14.2 4.76 0.84 1 1 13.6 5.05 0.84 1 1
17.2°C 1135 19.5 3.42 0.84 1 1 17.5 4.04 0.88 1 1 15.4 4.81 0.92 1 1 14.7 5.1 0.94 1 1
1360 20.6 3.46 0.91 1 1 18.4 4.08 0.94 1 1 16.2 4.85 1 1 1 15.5 5.14 1 1 1
905 19.8 3.43 0.6 0.75 0.9 17.5 4.04 0.61 0.78 0.94 15.2 4.81 0.61 0.81 0.99 14.5 5.09 0.61 0.82 1
19.4°C 1135 20.7 3.46 0.64 0.82 0.98 18.3 4.07 0.66 0.86 1 15.8 4.84 0.67 0.9 1 15.1 5.12 0.68 0.92 1
1360 21.3 3.49 0.68 0.89 1 18.8 4.1 0.7 0.93 1 16.3 4.86 0.74 0.98 1 15.6 5.14 0.74 1 1
905 21 3.47 0.44 0.56 0.73 18.7 4.09 0.44 0.6 0.76 16.3 4.85 0.42 0.61 0.79 15.5 5.14 0.41 0.6 0.79
21.7°C 1135 22 3.51 0.46 0.64 0.8 19.5 4.13 0.45 0.65 0.84 16.9 4.89 0.44 0.67 0.89 16.1 5.17 0.44 0.67 0.9
1360 22.7 3.54 0.48 0.68 0.87 20 4.15 0.48 0.7 0.91 17.4 4.91 0.48 0.74 0.97 16.6 5.19 0.48 0.74 0.99
Outdoor Air Temperature Entering Outdoor Coil
Entering Total 48°C 50°C 51.7°C
Wet Air
Bulb Volume Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T)
Temper-
ature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
905 13.2 5.29 0.86 1 1 12.7 5.54 0.87 1 1 12.3 5.78 0.88 1 1
17.2°C 1135 14.2 5.33 0.96 1 1 13.7 5.59 0.98 1 1 13.3 5.82 0.99 1 1
1360 14.9 5.37 1 1 1 14.4 5.63 1 1 1 14 5.86 1 1 1
905 14 5.33 0.62 0.84 1 13.4 5.57 0.62 0.86 1 12.9 5.8 0.62 0.87 1
19.4°C 1135 14.5 5.35 0.69 0.94 1 14 5.6 0.7 0.96 1 13.5 5.83 0.71 0.97 1
1360 15 5.37 0.76 1 1 14.4 5.62 0.77 1 1 14 5.85 0.78 1 1
905 15 5.37 0.4 0.62 0.82 14.4 5.62 0.41 0.63 0.83 13.8 5.85 0.41 0.62 0.85
21.7°C 1135 15.6 5.4 0.45 0.69 0.93 15 5.65 0.45 0.7 0.94 14.4 5.88 0.45 0.71 0.95
1360 16 5.43 0.48 0.76 1 15.3 5.68 0.48 0.77 1 14.8 5.9 0.48 0.78 1
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 15
BLOWER DATA - BELT DRIVE - KCA036 - DOWNFLOW
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 24 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - Pa (in. w.g.)
Air Volume
25 (0.10) 50 (0.20) 75 (0.30) 100 (0.40) 125 (0.50) 150 (0.60) 175 (0.70) 200 (0.80)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
425 900 486 0.09 0.12 554 0.12 0.16 623 0.15 0.20 695 0.16 0.22 767 0.17 0.23 836 0.19 0.25 897 0.21 0.28 953 0.22 0.30
472 1000 508 0.11 0.15 576 0.14 0.19 643 0.16 0.22 713 0.18 0.24 783 0.19 0.26 848 0.21 0.28 907 0.22 0.30 961 0.25 0.33
519 1100 533 0.13 0.18 599 0.16 0.22 665 0.19 0.25 733 0.20 0.27 800 0.21 0.28 863 0.23 0.31 919 0.25 0.34 971 0.27 0.36
566 1200 560 0.16 0.21 625 0.19 0.25 689 0.21 0.28 755 0.22 0.30 820 0.24 0.32 879 0.25 0.34 932 0.28 0.37 983 0.30 0.40
613 1300 591 0.18 0.24 654 0.21 0.28 716 0.23 0.31 779 0.25 0.33 841 0.26 0.35 897 0.28 0.38 948 0.31 0.41 996 0.33 0.44
661 1400 631 0.19 0.26 690 0.22 0.30 748 0.25 0.34 807 0.27 0.36 864 0.29 0.39 916 0.31 0.42 964 0.34 0.46 1011 0.37 0.49
708 1500 676 0.21 0.28 729 0.25 0.33 782 0.27 0.36 835 0.30 0.40 887 0.32 0.43 935 0.35 0.47 981 0.37 0.50 1028 0.40 0.54
External Static - Pa (in. w.g.)
Air Volume
225 (0.90) 250 (1.00) 275 (1.10) 300 (1.20) 325 (1.30) 350 (1.40) 375 (1.50) 400 (1.60)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 16
min min min min min min min min
425 900 1004 0.25 0.33 1055 0.26 0.35 1106 0.28 0.37 1152 0.30 0.40 1193 0.32 0.43 1232 0.34 0.46 1269 0.37 0.49 1305 0.39 0.52
472 1000 1011 0.27 0.36 1062 0.28 0.38 1111 0.31 0.41 1157 0.32 0.43 1199 0.35 0.47 1238 0.37 0.50 1276 0.40 0.53 1311 0.42 0.56
519 1100 1020 0.29 0.39 1070 0.31 0.41 1118 0.33 0.44 1163 0.35 0.47 1206 0.38 0.51 1245 0.40 0.54 1282 0.43 0.58 1318 0.46 0.61
566 1200 1031 0.32 0.43 1079 0.34 0.45 1127 0.36 0.48 1171 0.39 0.52 1213 0.41 0.55 1252 0.44 0.59 1289 0.46 0.62 1324 0.49 0.66
613 1300 1044 0.35 0.47 1091 0.37 0.49 1137 0.40 0.53 1181 0.42 0.56 1221 0.45 0.60 1259 0.48 0.64 1296 0.51 0.68 1330 0.53 0.71
661 1400 1058 0.38 0.51 1105 0.40 0.54 1150 0.43 0.57 1191 0.46 0.61 1231 0.48 0.65 1268 0.51 0.69 1303 0.54 0.73 1337 0.57 0.77
708 1500 1074 0.42 0.56 1120 0.44 0.59 1163 0.47 0.63 1203 0.50 0.67 1241 0.53 0.71 1277 0.56 0.75 1312 0.59 0.79 1345 0.61 0.82
BLOWER DATA - BELT DRIVE - KCA036 - HORIZONTAL
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 24 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - Pa (in. w.g.)
Air Volume
25 (0.10) 50 (0.20) 75 (0.30) 100 (0.40) 125 (0.50) 150 (0.60) 175 (0.70) 200 (0.80)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
425 900 485 0.08 0.11 554 0.10 0.14 627 0.12 0.16 703 0.13 0.18 780 0.16 0.21 841 0.17 0.23 888 0.20 0.27 935 0.22 0.30
472 1000 509 0.10 0.13 578 0.12 0.16 649 0.14 0.19 722 0.16 0.21 796 0.17 0.23 854 0.19 0.26 900 0.22 0.29 947 0.25 0.33
519 1100 537 0.12 0.16 605 0.14 0.19 674 0.16 0.21 744 0.18 0.24 813 0.19 0.26 868 0.22 0.29 913 0.25 0.33 959 0.27 0.36
566 1200 567 0.14 0.19 633 0.16 0.22 700 0.18 0.24 768 0.20 0.27 833 0.22 0.30 884 0.25 0.33 928 0.28 0.37 974 0.30 0.40
613 1300 599 0.16 0.22 664 0.19 0.25 729 0.21 0.28 793 0.22 0.30 853 0.25 0.33 902 0.28 0.37 945 0.31 0.41 990 0.33 0.44
661 1400 634 0.19 0.26 697 0.22 0.29 758 0.23 0.31 819 0.25 0.34 875 0.28 0.38 921 0.31 0.42 964 0.34 0.46 1008 0.37 0.49
708 1500 669 0.22 0.30 730 0.25 0.33 789 0.27 0.36 846 0.29 0.39 897 0.31 0.42 941 0.35 0.47 983 0.38 0.51 1028 0.40 0.54
External Static - Pa (in. w.g.)
Air Volume
225 (0.90) 250 (1.00) 275 (1.10) 300 (1.20) 325 (1.30) 350 (1.40) 375 (1.50) 400 (1.60)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
425 900 986 0.24 0.32 1039 0.26 0.35 1090 0.28 0.37 1137 0.30 0.40 1177 0.32 0.43 1214 0.34 0.46 1248 0.37 0.49 1280 0.38 0.51
472 1000 997 0.26 0.35 1048 0.28 0.38 1098 0.31 0.41 1143 0.33 0.44 1184 0.35 0.47 1221 0.37 0.50 1255 0.40 0.53 1287 0.42 0.56
519 1100 1008 0.29 0.39 1059 0.31 0.41 1107 0.33 0.44 1150 0.35 0.47 1191 0.38 0.51 1228 0.40 0.54 1263 0.43 0.57 1295 0.45 0.6
566 1200 1022 0.32 0.43 1071 0.34 0.45 1117 0.36 0.48 1160 0.39 0.52 1200 0.41 0.55 1237 0.44 0.59 1271 0.46 0.62 1303 0.49 0.66
613 1300 1037 0.35 0.47 1085 0.37 0.50 1130 0.40 0.53 1171 0.43 0.57 1210 0.45 0.60 1246 0.48 0.64 1280 0.51 0.68 1312 0.53 0.71
661 1400 1054 0.39 0.52 1100 0.40 0.54 1144 0.43 0.58 1183 0.46 0.62 1221 0.49 0.66 1256 0.52 0.70 1290 0.54 0.73 1321 0.57 0.77
708 1500 1073 0.43 0.57 1117 0.45 0.60 1159 0.48 0.64 1197 0.50 0.67 1234 0.53 0.71 1268 0.56 0.75 1301 0.59 0.79 1332 0.62 0.83
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 17
BLOWER DATA - BELT DRIVE - KCA048 - DOWNFLOW
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 24 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - Pa (in. w.g.)
Air Volume
25 (0.10) 50 (0.20) 75 (0.30) 100 (0.40) 125 (0.50) 150 (0.60) 175 (0.70) 200 (0.80)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
566 1200 560 0.16 0.21 625 0.19 0.25 689 0.21 0.28 755 0.22 0.30 820 0.24 0.32 879 0.25 0.34 932 0.28 0.37 983 0.30 0.40
613 1300 591 0.18 0.24 654 0.21 0.28 716 0.23 0.31 779 0.25 0.33 841 0.26 0.35 897 0.28 0.38 948 0.31 0.41 996 0.33 0.44
661 1400 631 0.19 0.26 690 0.22 0.30 748 0.25 0.34 807 0.27 0.36 864 0.29 0.39 916 0.31 0.42 964 0.34 0.46 1011 0.37 0.49
708 1500 675 0.21 0.28 729 0.25 0.33 782 0.27 0.36 835 0.30 0.40 887 0.32 0.43 935 0.35 0.47 981 0.37 0.50 1028 0.40 0.54
755 1600 718 0.23 0.31 766 0.26 0.35 814 0.30 0.40 862 0.33 0.44 910 0.36 0.48 955 0.39 0.52 1000 0.41 0.55 1046 0.44 0.59
802 1700 756 0.25 0.34 799 0.29 0.39 843 0.33 0.44 887 0.37 0.49 932 0.40 0.53 976 0.43 0.57 1020 0.46 0.61 1066 0.48 0.64
849 1800 787 0.30 0.40 828 0.34 0.45 870 0.37 0.50 912 0.41 0.55 955 0.44 0.59 999 0.47 0.63 1043 0.50 0.67 1089 0.52 0.70
897 1900 815 0.34 0.46 855 0.38 0.51 897 0.43 0.57 939 0.46 0.62 981 0.49 0.66 1024 0.51 0.69 1068 0.54 0.73 1113 0.57 0.76
944 2000 843 0.40 0.53 884 0.44 0.59 925 0.48 0.64 968 0.51 0.68 1009 0.54 0.72 1052 0.57 0.76 1095 0.59 0.79 1138 0.62 0.83
External Static - Pa (in. w.g.)
Air Volume
225 (0.90) 250 (1.00) 275 (1.10) 300 (1.20) 325 (1.30) 350 (1.40) 375 (1.50) 400 (1.60)
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 18
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
566 1200 1031 0.32 0.43 1079 0.34 0.45 1127 0.36 0.48 1171 0.39 0.52 1213 0.41 0.55 1252 0.44 0.59 1289 0.46 0.62 1324 0.49 0.66
613 1300 1044 0.35 0.47 1091 0.37 0.49 1137 0.40 0.53 1181 0.42 0.56 1221 0.45 0.60 1259 0.48 0.64 1296 0.51 0.68 1330 0.53 0.71
661 1400 1058 0.38 0.51 1105 0.40 0.54 1150 0.43 0.57 1191 0.46 0.61 1231 0.48 0.65 1268 0.51 0.69 1303 0.54 0.73 1337 0.57 0.77
708 1500 1074 0.42 0.56 1120 0.44 0.59 1163 0.47 0.63 1203 0.50 0.67 1241 0.53 0.71 1277 0.56 0.75 1312 0.59 0.79 1345 0.61 0.82
755 1600 1092 0.46 0.61 1137 0.48 0.65 1178 0.51 0.68 1216 0.54 0.72 1253 0.57 0.76 1288 0.60 0.80 1321 0.63 0.84 1354 0.66 0.88
802 1700 1112 0.50 0.67 1155 0.52 0.70 1193 0.56 0.75 1230 0.59 0.79 1265 0.62 0.83 1299 0.65 0.87 1332 0.68 0.91 1364 0.71 0.95
849 1800 1133 0.54 0.73 1174 0.57 0.77 1209 0.60 0.81 1244 0.63 0.85 1278 0.67 0.90 1311 0.70 0.94 1343 0.73 0.98 1375 0.76 1.02
897 1900 1156 0.60 0.80 1193 0.63 0.84 1226 0.66 0.89 1260 0.69 0.93 1293 0.72 0.97 1325 0.75 1.01 1356 0.79 1.06 1388 0.82 1.1
944 2000 1178 0.65 0.87 1213 0.69 0.92 1243 0.72 0.97 1275 0.76 1.02 1307 0.79 1.06 1339 0.82 1.10 1370 0.85 1.14 1402 0.88 1.18
BLOWER DATA - BELT DRIVE - KCA048 - HORIZONTAL
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 24 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - Pa (in. w.g.)
Air Volume
25 (0.10) 50 (0.20) 75 (0.30) 100 (0.40) 125 (0.50) 150 (0.60) 175 (0.70) 200 (0.80)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
566 1200 567 0.14 0.19 633 0.16 0.22 700 0.18 0.24 768 0.20 0.27 833 0.22 0.30 884 0.25 0.33 928 0.28 0.37 974 0.30 0.40
613 1300 599 0.16 0.22 664 0.19 0.25 729 0.21 0.28 793 0.22 0.30 853 0.25 0.33 902 0.28 0.37 945 0.31 0.41 990 0.33 0.44
661 1400 634 0.19 0.26 697 0.22 0.29 758 0.23 0.31 819 0.25 0.34 875 0.28 0.38 921 0.31 0.42 964 0.34 0.46 1008 0.37 0.49
708 1500 669 0.22 0.30 730 0.25 0.33 789 0.27 0.36 846 0.29 0.39 897 0.31 0.42 941 0.35 0.47 983 0.38 0.51 1028 0.40 0.54
755 1600 705 0.25 0.34 763 0.28 0.37 819 0.30 0.40 873 0.32 0.43 921 0.36 0.48 963 0.39 0.52 1004 0.42 0.56 1048 0.44 0.59
802 1700 741 0.28 0.38 796 0.31 0.41 850 0.34 0.45 900 0.37 0.49 945 0.40 0.53 985 0.43 0.58 1026 0.46 0.62 1070 0.48 0.65
849 1800 776 0.32 0.43 829 0.34 0.46 880 0.38 0.51 927 0.41 0.55 970 0.45 0.60 1009 0.48 0.64 1050 0.51 0.68 1093 0.53 0.71
897 1900 812 0.36 0.48 862 0.39 0.52 910 0.43 0.57 955 0.46 0.62 996 0.49 0.66 1035 0.53 0.71 1076 0.55 0.74 1118 0.58 0.78
944 2000 847 0.40 0.54 895 0.44 0.59 941 0.48 0.64 984 0.51 0.69 1023 0.55 0.74 1062 0.58 0.78 1103 0.60 0.81 1144 0.63 0.85
External Static - Pa (in. w.g.)
Air Volume
225 (0.90) 250 (1.00) 275 (1.10) 300 (1.20) 325 (1.30) 350 (1.40) 375 (1.50) 400 (1.60)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
566 1200 1022 0.32 0.43 1071 0.34 0.45 1117 0.36 0.48 1160 0.39 0.52 1200 0.41 0.55 1237 0.44 0.59 1271 0.46 0.62 1303 0.49 0.66
613 1300 1037 0.35 0.47 1085 0.37 0.50 1130 0.40 0.53 1171 0.43 0.57 1210 0.45 0.60 1246 0.48 0.64 1280 0.51 0.68 1312 0.53 0.71
661 1400 1054 0.39 0.52 1100 0.40 0.54 1144 0.43 0.58 1183 0.46 0.62 1221 0.49 0.66 1256 0.52 0.70 1290 0.54 0.73 1321 0.57 0.77
708 1500 1073 0.43 0.57 1117 0.45 0.60 1159 0.48 0.64 1197 0.50 0.67 1234 0.53 0.71 1268 0.56 0.75 1301 0.59 0.79 1332 0.62 0.83
755 1600 1093 0.46 0.62 1136 0.49 0.66 1175 0.52 0.70 1212 0.55 0.74 1247 0.58 0.78 1281 0.61 0.82 1313 0.64 0.86 1344 0.67 0.9
802 1700 1114 0.51 0.68 1155 0.54 0.72 1192 0.57 0.76 1227 0.60 0.80 1262 0.63 0.85 1295 0.66 0.89 1327 0.69 0.93 1358 0.72 0.97
849 1800 1136 0.56 0.75 1175 0.59 0.79 1210 0.62 0.83 1245 0.66 0.88 1278 0.69 0.92 1311 0.72 0.97 1342 0.75 1.01 1373 0.78 1.05
897 1900 1159 0.61 0.82 1197 0.64 0.86 1229 0.69 0.92 1263 0.72 0.97 1296 0.75 1.01 1328 0.79 1.06 1359 0.82 1.10 1390 0.85 1.14
944 2000 1183 0.67 0.90 1218 0.71 0.95 1249 0.75 1.01 1282 0.79 1.06 1314 0.83 1.11 1346 0.86 1.15 1377 0.90 1.20 1408 0.93 1.24
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 19
BLOWER DATA - BELT DRIVE - KCA060 - DOWNFLOW
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 24 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - Pa (in. w.g.)
Air Volume
25 (0.10) 50 (0.20) 75 (0.30) 100 (0.40) 125 (0.50) 150 (0.60) 175 (0.70) 200 (0.80)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
755 1600 738 0.24 0.32 785 0.27 0.36 831 0.31 0.41 878 0.34 0.45 923 0.37 0.49 969 0.40 0.53 1014 0.43 0.57 1061 0.44 0.59
802 1700 773 0.27 0.36 816 0.31 0.41 859 0.34 0.46 903 0.38 0.51 947 0.41 0.55 991 0.43 0.58 1036 0.46 0.62 1082 0.48 0.65
849 1800 803 0.31 0.42 844 0.35 0.47 886 0.39 0.52 929 0.43 0.57 972 0.46 0.61 1016 0.48 0.64 1060 0.51 0.68 1106 0.53 0.71
897 1900 831 0.36 0.48 872 0.40 0.54 915 0.44 0.59 957 0.47 0.63 1000 0.50 0.67 1043 0.53 0.71 1087 0.55 0.74 1131 0.58 0.78
944 2000 861 0.42 0.56 903 0.46 0.61 945 0.49 0.66 988 0.52 0.70 1030 0.55 0.74 1072 0.57 0.77 1115 0.60 0.81 1157 0.63 0.85
991 2100 893 0.47 0.63 935 0.51 0.69 978 0.54 0.73 1019 0.58 0.78 1060 0.60 0.81 1101 0.63 0.85 1143 0.66 0.89 1182 0.69 0.93
1038 2200 927 0.53 0.71 969 0.57 0.76 1011 0.60 0.81 1052 0.63 0.85 1091 0.66 0.89 1131 0.69 0.93 1170 0.72 0.97 1206 0.76 1.02
1085 2300 963 0.59 0.79 1004 0.63 0.84 1045 0.66 0.89 1084 0.69 0.93 1122 0.72 0.97 1159 0.76 1.02 1195 0.80 1.07 1228 0.84 1.13
1133 2400 999 0.66 0.88 1039 0.69 0.92 1078 0.72 0.97 1115 0.76 1.02 1151 0.79 1.06 1186 0.84 1.12 1219 0.88 1.18 1250 0.93 1.24
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 20
External Static - Pa (in. w.g.)
Air Volume
225 (0.90) 250 (1.00) 275 (1.10) 300 (1.20) 325 (1.30) 350 (1.40) 375 (1.50) 400 (1.60)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
755 1600 1107 0.46 0.62 1151 0.49 0.66 1190 0.52 0.70 1228 0.55 0.74 1264 0.58 0.78 1298 0.61 0.82 1332 0.64 0.86 1364 0.67 0.9
802 1700 1128 0.51 0.68 1169 0.54 0.72 1206 0.57 0.76 1242 0.60 0.80 1277 0.63 0.84 1310 0.66 0.88 1343 0.69 0.92 1375 0.72 0.96
849 1800 1150 0.55 0.74 1189 0.59 0.79 1223 0.62 0.83 1257 0.65 0.87 1291 0.68 0.91 1324 0.71 0.95 1356 0.74 0.99 1388 0.77 1.03
897 1900 1173 0.60 0.81 1208 0.64 0.86 1240 0.68 0.91 1273 0.71 0.95 1306 0.74 0.99 1338 0.77 1.03 1369 0.80 1.07 1401 0.84 1.12
944 2000 1195 0.66 0.89 1228 0.70 0.94 1257 0.74 0.99 1290 0.78 1.04 1321 0.81 1.08 1353 0.84 1.12 1384 0.87 1.16 1416 0.90 1.2
991 2100 1217 0.73 0.98 1247 0.78 1.04 1275 0.81 1.09 1306 0.85 1.14 1338 0.88 1.18 1369 0.91 1.22 1400 0.93 1.25 1432 0.96 1.29
1038 2200 1238 0.81 1.08 1265 0.85 1.14 1293 0.89 1.19 1324 0.93 1.24 1355 0.95 1.28 1387 0.98 1.31 1418 1.01 1.35 1450 1.04 1.39
1085 2300 1257 0.89 1.19 1284 0.93 1.25 1313 0.97 1.30 1344 1.00 1.34 1375 1.03 1.38 1406 1.05 1.41 1437 1.08 1.45 1470 1.10 1.48
1133 2400 1278 0.97 1.30 1305 1.01 1.36 1334 1.04 1.40 1364 1.07 1.44 1395 1.10 1.48 1427 1.13 1.51 1458 1.16 1.55 1492 1.18 1.58
BLOWER DATA - BELT DRIVE - KCA060 - HORIZONTAL
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 24 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - Pa (in. w.g.)
Air Volume
25 (0.10) 50 (0.20) 75 (0.30) 100 (0.40) 125 (0.50) 150 (0.60) 175 (0.70) 200 (0.80)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
755 1600 752 0.22 0.30 798 0.26 0.35 844 0.30 0.40 889 0.34 0.45 933 0.37 0.49 975 0.40 0.53 1018 0.43 0.57 1062 0.45 0.60
802 1700 785 0.26 0.35 827 0.30 0.40 871 0.34 0.46 914 0.38 0.51 957 0.41 0.55 999 0.44 0.59 1042 0.47 0.63 1085 0.49 0.66
849 1800 813 0.31 0.42 855 0.35 0.47 898 0.39 0.52 940 0.43 0.57 983 0.46 0.62 1025 0.49 0.66 1067 0.51 0.69 1110 0.54 0.72
897 1900 841 0.37 0.49 883 0.40 0.54 926 0.45 0.60 969 0.48 0.65 1011 0.51 0.69 1052 0.54 0.72 1094 0.57 0.76 1136 0.59 0.79
944 2000 871 0.42 0.56 914 0.46 0.62 957 0.50 0.67 1000 0.54 0.72 1040 0.57 0.76 1081 0.59 0.79 1122 0.62 0.83 1162 0.65 0.87
991 2100 903 0.48 0.64 946 0.52 0.70 990 0.56 0.75 1031 0.59 0.79 1071 0.62 0.83 1110 0.65 0.87 1150 0.68 0.91 1189 0.72 0.96
1038 2200 937 0.54 0.73 981 0.58 0.78 1023 0.62 0.83 1063 0.65 0.87 1102 0.68 0.91 1140 0.72 0.96 1178 0.75 1.01 1215 0.80 1.07
1085 2300 973 0.60 0.81 1015 0.64 0.86 1056 0.68 0.91 1095 0.72 0.96 1132 0.75 1.01 1170 0.79 1.06 1206 0.84 1.12 1242 0.89 1.19
1133 2400 1010 0.68 0.91 1051 0.72 0.96 1090 0.75 1.01 1127 0.79 1.06 1164 0.83 1.11 1200 0.88 1.18 1235 0.93 1.24 1269 0.98 1.31
External Static - Pa (in. w.g.)
Air Volume
225 (0.90) 250 (1.00) 275 (1.10) 300 (1.20) 325 (1.30) 350 (1.40) 375 (1.50) 400 (1.60)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
755 1600 1107 0.47 0.63 1149 0.50 0.67 1187 0.53 0.71 1223 0.56 0.75 1258 0.59 0.79 1291 0.62 0.83 1323 0.65 0.87 1354 0.68 0.91
802 1700 1129 0.51 0.69 1169 0.54 0.73 1204 0.58 0.78 1240 0.61 0.82 1274 0.64 0.86 1306 0.67 0.90 1338 0.71 0.95 1369 0.74 0.99
849 1800 1152 0.57 0.76 1190 0.60 0.80 1223 0.63 0.85 1258 0.67 0.90 1291 0.70 0.94 1323 0.74 0.99 1354 0.77 1.03 1385 0.80 1.07
897 1900 1176 0.62 0.83 1212 0.66 0.89 1243 0.70 0.94 1277 0.74 0.99 1309 0.77 1.03 1341 0.81 1.08 1372 0.84 1.12 1402 0.87 1.16
944 2000 1201 0.69 0.92 1234 0.73 0.98 1264 0.78 1.04 1296 0.81 1.09 1329 0.84 1.13 1360 0.88 1.18 1391 0.91 1.22 1422 0.94 1.26
991 2100 1225 0.76 1.02 1256 0.81 1.08 1285 0.85 1.14 1318 0.89 1.19 1349 0.93 1.24 1381 0.95 1.28 1412 0.98 1.32 1442 1.01 1.36
1038 2200 1249 0.84 1.13 1279 0.89 1.19 1308 0.93 1.25 1340 0.97 1.30 1372 1.00 1.34 1403 1.03 1.38 1434 1.06 1.42 1465 1.09 1.46
1085 2300 1273 0.93 1.25 1303 0.98 1.31 1332 1.01 1.36 1364 1.05 1.41 1396 1.08 1.45 1427 1.11 1.49 1458 1.14 1.53 1490 1.17 1.57
1133 2400 1300 1.02 1.37 1329 1.07 1.43 1359 1.10 1.47 1390 1.13 1.52 1422 1.16 1.56 1453 1.19 1.60 1484 1.22 1.64 1516 1.25 1.67
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 21
BLOWER DATA - BELT DRIVE - KCA072 - DOWNFLOW
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 24 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - Pa (in. w.g.)
Air Volume
25 (0.10) 50 (0.20) 75 (0.30) 100 (0.40) 125 (0.50) 150 (0.60) 175 (0.70) 200 (0.80)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
897 1900 826 0.27 0.36 859 0.31 0.41 894 0.34 0.45 928 0.37 0.50 964 0.42 0.56 1000 0.46 0.61 1036 0.49 0.66 1072 0.52 0.70
944 2000 857 0.31 0.42 889 0.35 0.47 920 0.39 0.52 952 0.43 0.57 986 0.46 0.62 1020 0.51 0.68 1055 0.54 0.73 1091 0.57 0.77
991 2100 878 0.37 0.49 909 0.40 0.54 940 0.44 0.59 973 0.48 0.64 1006 0.52 0.70 1041 0.56 0.75 1076 0.60 0.80 1112 0.63 0.85
1038 2200 897 0.41 0.55 929 0.46 0.61 961 0.49 0.66 994 0.54 0.72 1028 0.58 0.78 1063 0.62 0.83 1099 0.66 0.89 1134 0.69 0.93
1085 2300 918 0.46 0.62 950 0.51 0.68 983 0.55 0.74 1017 0.60 0.80 1052 0.64 0.86 1087 0.69 0.92 1122 0.72 0.97 1157 0.76 1.02
1133 2400 941 0.52 0.70 974 0.57 0.77 1008 0.62 0.83 1042 0.67 0.90 1077 0.72 0.96 1111 0.75 1.01 1146 0.79 1.06 1181 0.83 1.11
1180 2500 966 0.59 0.79 1000 0.64 0.86 1034 0.69 0.93 1068 0.75 1.00 1103 0.79 1.06 1137 0.83 1.11 1171 0.87 1.16 1205 0.90 1.20
1227 2600 994 0.67 0.90 1028 0.72 0.97 1062 0.78 1.04 1096 0.82 1.10 1130 0.87 1.16 1164 0.90 1.21 1197 0.94 1.26 1231 0.97 1.30
1274 2700 1023 0.75 1.01 1057 0.81 1.08 1091 0.86 1.15 1125 0.91 1.22 1159 0.95 1.27 1192 0.98 1.32 1225 1.02 1.37 1258 1.05 1.41
1321 2800 1053 0.84 1.13 1088 0.90 1.21 1122 0.95 1.27 1155 0.99 1.33 1188 1.04 1.39 1221 1.07 1.43 1253 1.10 1.48 1286 1.14 1.53
1369 2900 1085 0.94 1.26 1119 0.99 1.33 1153 1.04 1.40 1186 1.08 1.45 1218 1.13 1.51 1250 1.16 1.55 1281 1.20 1.61 1313 1.24 1.66
External Static - Pa (in. w.g.)
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 22
Air Volume
225 (0.90) 250 (1.00) 275 (1.10) 300 (1.20) 325 (1.30) 350 (1.40) 375 (1.50) 400 (1.60)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
897 1900 1109 0.56 0.75 1146 0.59 0.79 1183 0.61 0.82 1221 0.64 0.86 1260 0.67 0.90 1294 0.70 0.94 1323 0.73 0.98 1349 0.76 1.02
944 2000 1128 0.61 0.82 1164 0.64 0.86 1201 0.66 0.89 1239 0.69 0.93 1276 0.72 0.97 1310 0.75 1.01 1336 0.79 1.06 1362 0.82 1.1
991 2100 1148 0.66 0.89 1185 0.69 0.93 1221 0.72 0.97 1258 0.75 1.01 1294 0.78 1.05 1325 0.81 1.09 1351 0.85 1.14 1376 0.89 1.19
1038 2200 1170 0.72 0.97 1206 0.75 1.01 1242 0.78 1.05 1277 0.81 1.09 1311 0.85 1.14 1341 0.88 1.18 1365 0.92 1.23 1390 0.95 1.28
1085 2300 1193 0.79 1.06 1228 0.81 1.09 1262 0.85 1.14 1295 0.89 1.19 1327 0.93 1.24 1355 0.96 1.29 1380 0.99 1.33 1406 1.02 1.37
1133 2400 1216 0.86 1.15 1250 0.89 1.19 1282 0.93 1.24 1313 0.97 1.30 1343 1.01 1.36 1371 1.04 1.40 1396 1.07 1.44 1423 1.10 1.48
1180 2500 1240 0.93 1.24 1273 0.96 1.29 1302 1.01 1.36 1331 1.06 1.42 1360 1.10 1.48 1388 1.13 1.52 1414 1.16 1.55 1441 1.18 1.58
1227 2600 1265 1.00 1.34 1296 1.04 1.40 1324 1.10 1.47 1352 1.15 1.54 1381 1.19 1.60 1408 1.22 1.64 1434 1.25 1.67 1460 1.27 1.7
1274 2700 1291 1.09 1.46 1321 1.13 1.52 1347 1.19 1.60 1374 1.25 1.67 1403 1.28 1.72 1429 1.31 1.76 1455 1.34 1.79 1481 1.36 1.82
1321 2800 1317 1.18 1.58 1346 1.24 1.66 1372 1.30 1.74 1399 1.34 1.80 1426 1.38 1.85 1451 1.41 1.89 1477 1.43 1.92 1503 1.45 1.95
1369 2900 1343 1.28 1.72 1371 1.34 1.80 1397 1.40 1.88 1424 1.45 1.95 1450 1.48 1.99 1475 1.51 2.02 1500 1.53 2.05 1526 1.55 2.08
BLOWER DATA - BELT DRIVE - KCA072 - HORIZONTAL
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 24 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - Pa (in. w.g.)
Air Volume
25 (0.10) 50 (0.20) 75 (0.30) 100 (0.40) 125 (0.50) 150 (0.60) 175 (0.70) 200 (0.80)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
897 1900 853 0.31 0.41 886 0.34 0.46 919 0.37 0.50 952 0.41 0.55 986 0.45 0.60 1021 0.48 0.64 1056 0.51 0.69 1091 0.54 0.73
944 2000 883 0.36 0.48 913 0.40 0.53 944 0.43 0.57 976 0.46 0.62 1009 0.50 0.67 1043 0.53 0.71 1078 0.57 0.76 1112 0.60 0.80
991 2100 906 0.42 0.56 936 0.45 0.60 967 0.48 0.65 999 0.52 0.70 1033 0.56 0.75 1067 0.59 0.79 1101 0.63 0.84 1135 0.66 0.88
1038 2200 930 0.48 0.64 960 0.51 0.68 991 0.54 0.73 1024 0.58 0.78 1058 0.62 0.83 1092 0.66 0.88 1126 0.69 0.92 1160 0.72 0.96
1085 2300 954 0.54 0.72 985 0.57 0.77 1017 0.61 0.82 1051 0.65 0.87 1085 0.69 0.92 1119 0.72 0.96 1152 0.75 1.00 1186 0.78 1.04
1133 2400 981 0.60 0.81 1013 0.64 0.86 1046 0.68 0.91 1079 0.72 0.96 1113 0.75 1.00 1146 0.78 1.05 1180 0.81 1.09 1213 0.84 1.13
1180 2500 1010 0.68 0.91 1042 0.72 0.96 1075 0.75 1.00 1109 0.78 1.05 1142 0.81 1.09 1175 0.85 1.14 1207 0.88 1.18 1239 0.92 1.23
1227 2600 1040 0.75 1.01 1073 0.78 1.05 1106 0.82 1.10 1139 0.85 1.14 1171 0.89 1.19 1203 0.92 1.23 1235 0.95 1.28 1266 0.99 1.33
1274 2700 1072 0.82 1.10 1104 0.86 1.15 1137 0.90 1.20 1169 0.93 1.24 1201 0.96 1.29 1232 1.00 1.34 1263 1.04 1.40 1293 1.09 1.46
1321 2800 1105 0.90 1.21 1137 0.93 1.25 1168 0.97 1.30 1200 1.01 1.35 1231 1.04 1.40 1261 1.09 1.46 1291 1.13 1.52 1321 1.19 1.59
1369 2900 1138 0.98 1.32 1169 1.02 1.37 1200 1.06 1.42 1231 1.10 1.47 1261 1.14 1.53 1291 1.19 1.60 1321 1.24 1.66 1350 1.29 1.73
External Static - Pa (in. w.g.)
Air Volume
225 (0.90) 250 (1.00) 275 (1.10) 300 (1.20) 325 (1.30) 350 (1.40) 375 (1.50) 400 (1.60)
Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/ Rev/
L/s cfm kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP kW BHP
min min min min min min min min
897 1900 1126 0.57 0.77 1163 0.60 0.81 1200 0.63 0.85 1237 0.66 0.88 1273 0.69 0.92 1306 0.72 0.96 1339 0.75 1.00 1371 0.78 1.04
944 2000 1148 0.63 0.84 1183 0.66 0.88 1220 0.69 0.92 1257 0.72 0.96 1291 0.75 1.00 1323 0.78 1.04 1354 0.81 1.08 1385 0.84 1.12
991 2100 1170 0.69 0.92 1206 0.72 0.96 1242 0.75 1.00 1277 0.78 1.04 1310 0.81 1.08 1340 0.84 1.13 1371 0.87 1.17 1401 0.90 1.21
1038 2200 1195 0.75 1.00 1230 0.78 1.04 1265 0.81 1.08 1299 0.84 1.13 1330 0.88 1.18 1359 0.92 1.23 1388 0.95 1.27 1418 0.98 1.31
1085 2300 1220 0.81 1.08 1254 0.84 1.13 1288 0.87 1.17 1320 0.92 1.23 1350 0.95 1.28 1378 1.00 1.34 1406 1.03 1.38 1435 1.06 1.42
1133 2400 1245 0.88 1.18 1278 0.91 1.22 1311 0.95 1.28 1341 0.99 1.33 1370 1.04 1.40 1397 1.08 1.45 1425 1.12 1.50 1454 1.15 1.54
1180 2500 1271 0.95 1.28 1303 0.99 1.33 1334 1.04 1.39 1363 1.08 1.45 1391 1.13 1.52 1418 1.17 1.57 1446 1.21 1.62 1474 1.24 1.66
1227 2600 1297 1.04 1.39 1328 1.08 1.45 1357 1.13 1.52 1385 1.18 1.58 1412 1.22 1.64 1439 1.27 1.70 1467 1.30 1.74 1495 1.33 1.78
1274 2700 1323 1.13 1.52 1353 1.18 1.58 1382 1.23 1.65 1409 1.28 1.72 1435 1.32 1.77 1462 1.36 1.82 1490 1.39 1.86 1517 1.42 1.9
1321 2800 1351 1.23 1.65 1380 1.28 1.72 1407 1.33 1.78 1434 1.38 1.85 1460 1.42 1.90 1486 1.45 1.95 1513 1.48 1.99 1541 1.51 2.02
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 23
1369 2900 1379 1.34 1.79 1407 1.39 1.86 1434 1.43 1.92 1460 1.48 1.98 1485 1.52 2.04 1511 1.55 2.08 1538 1.58 2.12 1565 1.60 2.15
BLOWER DATA
BELT DRIVE KIT SPECIFICATIONS
Model Motor kW (HP) No. of Drive Kits and Rev/Min Range
No. Nominal Max Speeds A01 A02 A03 A04 A05 A06 A07 A08 A09
036 1.5 (2) 1.7 (2.3) 1 561 - --- --- --- 748 - --- --- --- ---
842 1122
048 1.5 (2) 1.7 (2.3) 1 --- 621 - --- --- --- 893 - --- --- ---
931 1191
060 1.5 (2) 1.7 (2.3) 1 --- --- 694 - --- --- --- 1010 - --- ---
1042 1290
072 1.5 (2) 1.7 (2.3) 1 --- --- --- --- --- --- --- 994 - 1193 -
1326 1594
NOTE − Using total air volume and system static pressure requirements determine from blower performance tables rev/min and motor kW required. Maximum usable kW
of motors furnished are shown. If motors of comparable kW are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
OPTIONS / ACCESSORIES AIR RESISTANCE
Air Volume Wet Indoor Coil Economizer Electric Heat Filters
036-048 060 072 MERV 8 MERV 13
L/s cfm Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g.
375 800 2 0.01 2 0.01 2 0.01 10 0.04 2 0.01 10 0.04 12 0.05
470 1000 5 0.02 5 0.02 2 0.01 10 0.04 7 0.03 10 0.04 17 0.07
565 1200 7 0.03 7 0.04 5 0.02 10 0.04 15 0.06 10 0.04 17 0.07
660 1400 10 0.04 12 0.05 7 0.03 10 0.04 22 0.09 10 0.04 17 0.07
755 1600 12 0.05 15 0.06 7 0.04 10 0.04 30 0.12 10 0.04 17 0.07
850 1800 15 0.06 17 0.07 12 0.05 12 0.05 37 0.15 12 0.05 17 0.07
945 2000 20 0.08 22 0.09 15 0.06 12 0.05 45 0.18 12 0.05 20 0.08
1040 2200 22 0.09 25 0.10 17 0.07 12 0.05 50 0.20 12 0.05 20 0.08
1130 2400 25 0.10 30 0.12 20 0.08 12 0.05 55 0.22 12 0.05 20 0.08
1225 2600 27 0.11 30 0.13 22 0.09 15 0.06 60 0.24 12 0.05 20 0.08
1320 2800 30 0.13 37 0.15 25 0.10 15 0.06 65 0.26 12 0.05 20 0.08
1415 3000 35 0.14 40 0.16 30 0.12 15 0.06 70 0.28 12 0.05 20 0.08
POWER EXHAUST FAN PERFORMANCE
Return Air System Static
Air Volume Exhausted
Pressure
Pa in. w.g. L/s cfm
0 0.00 787 1665
12 0.05 783 1660
25 0.10 757 1605
37 0.15 712 1510
50 0.20 654 1385
62 0.25 593 1255
75 0.30 531 1125
87 0.35 476 1010
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 24
BLOWER DATA
CEILING DIFFUSERS AIR RESISTANCE
Air Volume RTD9-65S Step–Down Diffuser FD9-65S RTD11-95S Step–Down Diffuser FD11-95S
Flush Flush
2 Ends 1 Side & All Ends & 2 Ends 1 Side & All Ends &
Diffuser Diffuser
Open 2 Ends Open Sides Open Open 2 Ends Open Sides Open
L/s cfm Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g.
375 800 37 0.15 32 0.13 27 0.11 27 0.11 --- --- --- --- --- --- --- ---
470 1000 47 0.19 40 0.16 35 0.14 35 0.14 --- --- --- --- --- --- --- ---
565 1200 62 0.25 50 0.20 42 0.17 42 0.17 --- --- --- --- --- --- --- ---
660 1400 82 0.33 65 0.26 50 0.20 50 0.20 --- --- --- --- --- --- --- ---
755 1600 107 0.43 80 0.32 50 0.20 50 0.24 --- --- --- --- --- --- --- ---
850 1800 139 0.56 99 0.40 75 0.30 75 0.30 32 0.13 27 0.11 22 0.09 22 0.09
945 2000 182 0.73 124 0.50 90 0.36 90 0.36 37 0.15 32 0.13 27 0.11 25 0.10
1040 2200 236 0.95 157 0.63 109 0.44 109 0.44 45 0.18 37 0.15 30 0.12 30 0.12
1130 2400 --- --- --- --- --- --- --- --- 52 0.21 45 0.18 37 0.15 35 0.14
1225 2600 --- --- --- --- --- --- --- --- 60 0.24 52 0.21 45 0.18 42 0.17
1320 2800 --- --- --- --- --- --- --- --- 67 0.27 60 0.24 52 0.21 50 0.20
1415 3000 --- --- --- --- --- --- --- --- 80 0.32 72 0.29 62 0.25 62 0.25
CEILING DIFFUSER AIR THROW DATA
Air Volume 1
Effective Throw
Model No. RTD9-65S FD9-65S
L/s cfm m ft. m ft.
375 800 3-5 10 - 17 4-5 14 - 18
470 1000 3-5 10 - 17 5-6 15 - 20
565 1200 3-5 11 - 18 5-7 16 - 22
660 1400 4-6 12 - 19 5-7 17 - 24
755 1600 4-6 12 - 20 5-8 18 - 25
850 1800 4-6 13 - 21 6-9 20 - 28
945 2000 4-7 14 - 23 6-9 21 - 29
1040 2200 5-8 16 - 25 7-9 22 - 30
Model No. RTD11-95S FD11-95S
1225 2600 7-9 24 - 29 6-7 19 - 24
1320 2800 8-9 25 - 30 6-9 20 - 28
1415 3000 8 - 10 27 - 33 6-9 21 - 29
1
Effective throw based on terminal velocities of 23 m per minute ( 75 ft. per minute).
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 25
ELECTRIC HEAT CAPACITIES
5.7 kW 11.5 kW 17.2 kW 23 kW
Input No of kW Btuh No of kW Btuh No of kW Btuh No of kW Btuh
Voltage Steps input Output Steps input Output Steps input Output Steps input Output
380 1 4.7 16 100 1 9.4 32 100 1 14.1 48 200 1 18.8 64 200
400 1 5.2 17 800 1 10.4 35 500 1 15.6 53 300 1 20.9 71 400
420 1 5.7 19 500 1 11.5 39 300 1 17.2 58 800 1 23.0 78 500
ELECTRICAL DATA
Model no. KCA036S4 KCA048S4
1
Voltage - 50hz with Neutral 380/420V - 3 Ph 380/420V - 3 Ph
Compressor Rated Load Amps 4 5.5
Locked Rotor Amps 31 37
Outdoor Fan Motor Full Load Amps 1.1 1.1
Power Exhaust Full Load Amps 1.3 1.3
(1) 0.25 kW
Indoor Blower kW 1.5 1.5
Motor
Full Load Amps 3.6 3.6
2
Maximum Unit Only 15 15
Overcurrent With (1) 0.25 kW
15 15
Protection Power Exhaust
3
Minimum Unit Only 10 12
Circuit With (1) 0.25 kW
11 13
Ampacity Power Exhaust
ELECTRIC HEAT DATA
Electric Heat Voltage 420 420
2
Maximum Unit+ 5.7 kW 15 15
Overcurrent 4
Electric Heat
11.5 kW 25 25
Protection
3
Minimum Unit+ 5.7 kW 15 15
Circuit 4
Electric Heat
11.5 kW 25 25
Ampacity
2
Maximum Unit+ 5.7 kW 20 20
Overcurrent Electric Heat
4
11.5 kW 30 30
Protection and (1) 0.25 kW Power Exhaust
3
Minimum Unit+ 5.7 kW 16 16
Circuit Electric Heat
4
11.5 kW 26 26
Ampacity and (1) 0.25 kW Power Exhaust
1
Extremes of operating range are plus and minus 10% of line voltage.
2
Heating, Air Conditioning, Refrigeration type breaker or fuse.
3
Refer to local electrical code to determine wire, fuse and disconnect size requirements.
4
Nominal kW based on 420V-3ph-50hz.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 26
ELECTRICAL DATA
Model No. KCA060S4 KCA072S4
1
Voltage - 50hz with Neutral 380/420V - 3 Ph 380/420V - 3 Ph
Compressor Rated Load Amps 8 9.7
Locked Rotor Amps 59 64
Outdoor Fan Motor Full Load Amps 1.3 1.3
Power Exhaust Full Load Amps 1.3 1.3
(1) 0.25 kW
Indoor Blower kW 1.5 1.5
Motor
Full Load Amps 3.6 3.6
2
Maximum Unit Only 20 25
Overcurrent With (1) 0.25 kW
20 25
Protection Power Exhaust
3
Minimum Unit Only 15 18
Circuit With (1) 0.25 kW
17 19
Ampacity Power Exhaust
ELECTRIC HEAT DATA
Electric Heat Voltage 420 420
2
Maximum Unit+ 5.7 kW 20 25
Overcurrent 4
Electric Heat
11.5 kW 25 25
Protection
17.2 kW 35 35
23 kW --- 45
3
Minimum Unit+ 5.7 kW 15 18
Circuit 4
Electric Heat
11.5 kW 25 25
Ampacity
17.2 kW 35 35
23 kW --- 44
2
Maximum Unit+ 5.7 kW 20 25
Overcurrent Electric Heat
4
11.5 kW 30 30
Protection and (1) 0.25 kW Power Exhaust
17.2 kW 40 40
23 kW --- 50
3
Minimum Unit+ 5.7 kW 17 19
Circuit Electric Heat
4
11.5 kW 26 26
Ampacity and (1) 0.25 kW Power Exhaust
17.2 kW 36 36
23 kW --- 46
1
Extremes of operating range are plus and minus 10% of line voltage.
2
Heating, Air Conditioning, Refrigeration type breaker or fuse.
3
Refer to local electrical code to determine wire, fuse and disconnect size requirements.
4
Nominal kW based on 420V-3ph-50hz.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 27
UNIT CLEARANCES - MM (INCHES)
OUTDOOR AIR
B
HOOD
1
Unit Clearance A B C D Top
mm in. mm in. mm in. mm in. Clearance
Service Clearance 914 36 914 36 914 36 914 36 Unobstructed
Minimum Operation Clearance 914 36 914 36 914 36 914 36
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
Service Clearance - Required for removal of serviceable parts.
Minimum Operation Clearance - Required clearance for proper unit operation.
OUTDOOR SOUND DATA
Unit Octave Band Linear Sound Power Levels dB, re 10-12 Watts - Center Frequency - Hz 1
Sound Rating
Model No. 125 250 500 1000 2000 4000 8000 Number (SRN)
(dBA)
KCA036 and 048 63 66 70 71 68 62 53 75
KCA060 67 72 77 76 73 68 61 82
KCA072 66 71 74 73 70 65 57 79
Note - The octave sound power data does not include tonal corrections.
1
Sound Rating Number according to ARI Standard 270-95 (includes pure tone penalty). “SRN” is the overall A-Weighted Sound Power Level, (LWA), dB (100 Hz to
10,000 Hz).
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 28
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS
Model Catalog
Item
No. No.
COMFORTSENSE® 7500 COMMERCIAL 7-DAY PROGRAMMABLE THERMOSTAT
• Four-Stage Heating / Two-Stage Cooling Universal Multi-Stage C0STAT06FF1L 13H15
• Intuitive Touchscreen Interface
• Remote Indoor Temperature Sensing with Averaging
• Outside or Discharge Air Temperature Display
• Full Seven-Day Programming
• Four Time Periods Per Day
• Occupancy Scheduling with Economizer Relay Control
• Away Mode
• Holiday Scheduling
• Smooth Setback Recovery (SSR)
• Performance Reports
• Notifications/Reminders
• Dehumidification/Humiditrol® Control for Split Systems and Rooftop Units
• Economizer Relay Control
• Backlit Display
• Wallplate Furnished
Optional Accessories
1
Remote non-adjustable wall mount 20k temperature sensor C0SNZN01AE2- 47W36
1
Remote non-adjustable wall mount 10k temperature sensor C0SNZN73AE1- 47W37
Remote non-adjustable discharge air (duct mount) temperature sensor C0SNDC00AE1- 19L22
Outdoor temperature sensor C0SNSR03AE1- X2658
Locking cover (clear) C0MISC15AE1- 39P21
1
Remote sensors can be applied in any of the following combinations:
One Sensor - (1) 47W36
Two Sensors - (2) 47W37
Three Sensors - (2) 47W36 and (1) 47W37
Four Sensors - (4) 47W36
Five Sensors - (3) 47W36 and (2) 47W37
COMFORTSENSE® 3000 COMMERCIAL 5-2 DAY PROGRAMMABLE THERMOSTAT
• Two-Stage Heating / Two-Stage Cooling Conventional Systems C0STAT05FF1L 11Y05
MAINT
• Intuitive Interface
• 5-2 Day Programming
• Program Hold
• Remote Indoor Temperature Sensing
Commercial
• Smooth Setback Recovery (SSR)
• Economizer Relay Control
• Maintenance/Filter/Service Reminders
• Backlit Display
• Wallplate Furnished
• Simple Up and Down Temperature Control.
Optional Accessories
Remote non-adjustable wall mount 10k averaging temperature sensor C0SNZN73AE1- 47W37
Optional wall mounting plate C0MISC17AE1- X2659
DIGITAL NON-PROGRAMMABLE THERMOSTAT
• One-Stage Heating / Cooling Conventional Systems C0STAT12AE1L 51M32
• Intuitive Interface
• Automatic Changeover
• Backlit Display
• Simple Up and Down Temperature Control.
Optional Accessories
Outdoor temperature sensor C0SNSR04AE1- X2658
Optional wall mounting plate C0MISC17AE1- X2659
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 29
WEIGHT DATA
Model Number Net Shipping
Base Max. Base Max.
kg lbs. kg lbs. kg lbs. kg lbs.
KCA036S 226 498 277 610 253 558 308 679
KCA048S 243 535 293 647 270 595 325 716
KCA060S 256 565 309 681 283 625 340 750
KCA072S 281 620 340 750 300 661 359 791
Base Unit - The unit with NO OPTIONS.
Max. Unit - The unit with ALL OPTIONS installed (Economizer, etc.).
OPTIONS / ACCESSORIES
Shipping Weights
kg lbs.
ECONOMIZER
Economizer
Economizer, Includes Barometric Relief Dampers and Exhaust Hood 59 131
OUTDOOR AIR
Outdoor Air Dampers
Motorized 18 40
Manual 14 30
POWER EXHAUST
Standard Static 16 35
ELECTRIC HEAT
5.7 kW 14 31
11.5 kW 14 31
17.2 kW 16 35
23 kW 16 35
ROOF CURBS
Hybrid Roof Curb, Downflow
203 mm height 23 50
356 mm height 32 70
457 mm height 36 80
610 mm height 45 100
Hybrid Curb, Full Perimeter, Downflow
203 mm height 26 57
356 mm height 27 60
457 mm height 41 91
610 mm height 52 114
Adjustable Pitch Curb, Downflow
356 mm height 51 113
CEILING DIFFUSERS
Step-Down RTD9-65S 36 80
RTD11-95S 54 118
Flush FD9-65S 36 80
FD11-95S 54 118
Transitions (Supply and Return) T1TRAN10AN1 10 22
T1TRAN20N-1 10 21
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 30
DIMENSIONS - UNIT - MM (INCHES)
Model CORNER WEIGHTS CENTER OF GRAVITY
No. AA BB CC DD EE FF
Base Max. Base Max. Base Max. Base Max. Base Max. Base Max.
kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. mm in. mm in. mm in. mm in.
036 39 86 50 110 48 105 56 124 77 169 91 200 63 139 80 177 978 38-1/2 1016 40 457 18 457 18
048 42 93 53 116 51 112 60 132 82 181 96 212 68 149 85 187 978 38-1/2 1016 40 457 18 457 18
060 44 98 56 122 54 119 63 138 87 191 101 223 72 157 90 197 978 38-1/2 1016 40 457 18 457 18
072 53 118 65 142 63 140 69 152 89 197 93 205 75 166 114 251 991 39 1137 44-3/4 495 19-1/2 508 20
Base Unit - The unit with NO INTERNAL OPTIONS.
Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to
unit or high static power exhaust.
279
143 (11)
413 457
(5-5/8) (16-1/4) (18)
AA BB
178 (7) BOTTOM 127 (5)
RETURN
AIR
OPENING
508
737 BOTTOM (20) CENTER
(29) SUPPLY OF
AIR GRAVITY
1194 (47)
OPENING
BASE 654 (25-3/4)
KCA036 thru 072
FF 241
168
(6-5/8) (9-1/2)
DD CC
673 BOTTOM
(26-1/2) EE
CONDENSATE
OUTLET BOTTOM POWER ENTRY
76 x 203 (3 X 8)
TOP VIEW (Base)
1143 (45) 2115 (83-1/4) KCA036 thru 072
899 (35-3/8) KCA036 thru 060
987 (38-7/8) KCA036 thru 060
1102 (43-3/8) KCA072
1191 (46-7/8) KCA072
ELECTRICAL
INLET
CONDENSATE
OUTLET
(EITHER SIDE)
140
25 (1) (5-1/2) 25 (1)
89 (3-1/2)
1194 (47) 673 LIFTING HOLES
BASE (26-1/2) (For rigging)
2165 (85-1/4) KCA036 thru 072 BASE
END VIEW
SIDE VIEW
495 467 279
(19-1/2) (18-3/8) (11) 51 (2)
737
(29)
508
(20)
FORKLIFT SLOTS 140 HORIZONTAL HORIZONTAL 140
(Front, Back and (5-1/2) SUPPLY AIR RETURN AIR (5-1/2)
Blower End) OPENING OPENING
(Without Economizer)
BACK VIEW
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 31
DIMENSIONS - ACCESSORIES - MM (INCHES)
OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Downflow Applications)
298
(11-3/4)
OPTIONAL OUTDOOR
AIR HOOD
(Furnished with Economizer)
441
(17-3/8)
OPTIONAL BAROMETRIC
RELIEF HOOD SIDE VIEW
(Furnished with Economizer )
OUTDOOR AIR HOOD FOR ECONOMIZER (Furnished) BAROMETRIC RELIEF HOOD FOR ECONOMIZER (Furnished)
298
441
(11-3/4) 889
(17-3/8)
889 (35)
(35)
505
330 (13) (19-7/8)
OUTDOOR AIR DAMPER HOOD DETAIL (Downflow or Horizontal Applications)
267
(10-1/2)
OUTDOOR AIR
DAMPER HOOD
(Furnished)
SIDE VIEW
MANUAL OUTDOOR AIR HOOD MOTORIZED OUTDOOR AIR HOOD
889 OPTIONAL 889
(35) OUTDOOR (35)
OPTIONAL AIR DAMPERS
OUTDOOR AND PANEL
AIR DAMPERS
AND PANEL
OUTDOOR AIR
DAMPER HOOD
(13-1/2)
OUTDOOR AIR
343
DAMPER HOOD
(13-1/2)
343
889 (35) 889 (35)
036 thru 048 267 036 thru 048
419
1092 (43) (10-1/2) 1092 (43)
060 / 072 (16-1/2) 060 / 072
419
(16-1/2) 267
(10-1/2)
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 32
DIMENSIONS - ACCESSORIES - MM (INCHES)
OUTDOOR AIR HOOD DETAIL WITH OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Horizontal Applications)
ECONOMIZER DAMPERS
Barometric Relief Hood
and Dampers
RETURN AIR DUCT
(Field Fabricated - Must be sized to
accommodate Barometric Relief
Hood and Return Air Requirements)
RETURN AIR
SUPPLY AIR DUCT DUCT TRANSITION
BAROMETRIC RELIEF HOOD DIMENSIONS
(Field Provided) (Field fabricated and
Width - 902 mm (35-1/2 in)
SUPPLY installed on unit) RETURN Height - 533 mm (21 in.)
AIR AIR
OUTLET INLET See previous page for details.
OUTDOOR AIR HOOD
TOP VIEW (Furnished with Economizer)
NOTE - Horizontal applications with Economizer require
Horizontal Economizer Conversion Kit.
See Options/Accessories table.
298
(11-3/4)
495 797
(19-1/2) (31-3/8)
BAROMETRIC RELIEF HOOD
(Furnished with Economizer and
Field Installed on Field fabricated
Return Air Duct) 22
OUTDOOR (7/8)
This opening AIR
not used in
Horizontal
Applications
HORIZONTAL with 57 476
508 Economizer HORIZONTAL
SUPPLY AIR RETURN AIR (2-1/4) (18-3/4) 57
(20) 773
OPENING OPENING (30-7/16) (2-1/4)
EXHAUST
AIR
22
140 RETURN AIR RETURN AIR DUCT INLET UNIT RETURN AIR DUCT
(5-1/ 2) DUCT TRANSITION (7/8) OPENING
(Field Fabricated - Must be sized to WITH ECONOMIZER
(Field fabricated and accommodate Barometric Relief INSTALLED
installed on unit) Hood and Return Air Requirements)
BACK VIEW END VIEW
NOTE - Return Air Duct and Transition must be supported.
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 33
DIMENSIONS - ACCESSORIES - MM (INCHES)
HYBRID ROOF CURBS - DOUBLE DUCT OPENING
965 1054
2026 1937 (38) (41-1/2)
(79-3/4) (76-1/4)
486 537
(19-1/8) (21-1/8)
203 (8)
384 356 (14)
(15-1/8) SUPPLY 457 (18)
OPENING 610 (24)
321
(12-5/8)
44
1-3/4
RETURN
OPENING
813
(32)
NOTE - Roof deck may be omitted within confines of curb.
TYPICAL FLASHING DETAIL FOR ROOF CURB DETAIL ROOF CURB
BASE BOTTOM PACKAGED 44
UNIT (1-3/4)
13 (1/2)
FIBERGLASS
INSULATION COUNTER FLASHING
(Furnished) (Field Supplied)
FACTORY INSTALLED
NAILER STRIP PERIMETER WOOD
(Furnished) NAILER STRIP
CANT STRIP 203 (8)
ROOF CURB
(Field Supplied) 356 (14)
(Extends around entire
perimeter of unit) 457 (18)
ROOFING 610 (24)
MATERIAL
RIGID INSULATION
(Field Supplied)
44
(1-3/4)
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 34
DIMENSIONS - ACCESSORIES - MM (INCHES)
ADJUSTABLE PITCH CURBS - DOUBLE DUCT OPENING
1937
(76-1/4) 965 1054
2026 (38) (41-1/2)
(79-3/4)
486 537
(19-1/8) (21-1/8)
384 356
(15-1/8) SUPPLY (14)
OPENING
321
(12-5/8)
RETURN
OPENING
813
(32)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
BOTTOM CURB
ASSEMBLY
NOTE - Maximum slope pitch is 19 mm per 305 mm (3/4 in. per 1 foot)
in any one direction.
TYPICAL FLASHING DETAIL FOR ROOF CURB DETAIL ROOF CURB
BASE BOTTOM PACKAGED 44
UNIT (1-3/4)
13 (1/2)
FIBERGLASS
INSULATION COUNTER FLASHING
(Furnished) (Field Supplied)
FACTORY INSTALLED
NAILER STRIP PERIMETER WOOD
(Furnished) NAILER STRIP
CANT STRIP
ROOF CURB
(Field Supplied)
(Extends around entire
perimeter of unit)
356
ROOFING (14)
MATERIAL
RIGID INSULATION
(Field Supplied)
44
(1-3/4)
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 35
DIMENSIONS - ACCESSORIES - MM (INCHES)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER FLUSH CEILING DIFFUSER
G H D G H D
E E
F H F H
G C G C
51 (2) 51 (2)
L A A
B
B
J
K
Model Number RTD9-65S RTD11-95S Model Number FD9-65S FD11-95S
A mm 1159 1159 A mm 1159 1159
in. 47-5/8 47-5/8 in. 47-5/8 47-5/8
B mm 600 752 B mm 600 752
in. 23-5/8 29-5/8 in. 23-5/8 29-5/8
C mm 289 365 C mm 343 422
in. 11-3/8 14-3/8 in. 13-1/2 16-5/8
D mm 546 699 D mm 533 686
in. 21-1/2 27-1/2 in. 21 27
E mm 1156 1158 E mm 1143 1143
in. 45-1/2 45-1/2 in. 45 45
F mm 572 572 F mm 572 572
in. 22-1/2 22-1/2 in. 22-1/2 22-1/2
G mm 292 292 G mm 286 286
in. 11-1/2 11-1/2 in. 11-1/4 11-1/4
H mm 273 349 H mm 267 343
in. 10-3/4 13-3/4 in. 10-1/2 13-1/2
J mm 1156 1156 Duct Size mm 457 round 508 round
in. 45-1/2 45-1/2 in. 18 round 20 round
K mm 546 699
in. 21-1/2 27-1/2
L mm 181 206
in. 7-1/8 8-1/8
Duct Size mm 457 round 508 round
in. 18 round 20 round
Landmark® KCA Packaged Electric / Electric 10.5 to 21 kW (3 to 6 Tons) - 50 hz / Page 36
REVISIONS
Sections Description of Change
Document Changed KC to KCA to differentiate between new KCB models (separate document).
BACNet and High Performance Economizer model numbers and catalog numbers
Optional Accessories
changed.
Visit us at www.lennox.com
For the latest technical information, www.lennoxcommercial.com
Contact us at 1-800-4-LENNOX
NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency. ©2018 Lennox Industries, Inc.