0% found this document useful (0 votes)
29 views44 pages

SolarEdge Firefighter Gateway Installation Guide v13

Uploaded by

j125131
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views44 pages

SolarEdge Firefighter Gateway Installation Guide v13

Uploaded by

j125131
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

Disclaimers

Disclaimers
Important Notice
Copyright © SolarEdge Technologies Inc. All rights reserved.
No part of this document may be reproduced, stored in a retrieval system or transmitted, in any form or
by any means, electronic, mechanical, photographic, magnetic or otherwise, without the prior written
permission of SolarEdge Technologies Inc. (also referred to herein as “SolarEdge”).
This document is solely for the use of SolarEdge customers and employees.
The material furnished in this document is believed to be accurate and reliable. However, SolarEdge
assumes no responsibility for the use of this material. SolarEdge reserves the right to make changes to the
material at any time and without notice. You may refer to the SolarEdge web site (www.solaredge.com)
for the most updated version of this and other documents.
All company and brand products and service names are trademarks or registered trademarks of their
respective holders.
Patent marking notice: http://www.solaredge.com/groups/patent
The general terms and conditions of purchase of SolarEdge products shall apply.
The content of these documents is continually reviewed and amended, where necessary. However,
discrepancies cannot be excluded. No guarantee is made for the completeness of these documents.
Please note: This product is intended to provide remote shutdown of the SolarEdge PV harvesting system,
to enable safer access to a building in the event of fire. This product DOES NOT reduce the risk of fire or
protect firefighters or others accessing a building in the event of a fire.
If the RS485 communication between the firefighter gateway and the SolarEdge inverter(s) is
disconnected for any reason (including fire), the firefighter gateway LCD will display "No
Communication" or "Partial Com.". In this case, the firefighter gateway cannot be relied upon to
disconnect the SolarEdge PV harvesting system.

FCC Compliance
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant
to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can
be determined by turning the equipment OFF and ON, you are encouraged to try to correct the
interference by one or more of the following measures:
 Reorient or relocate the receiving antenna.
 Increase the separation between the equipment and the receiver.
 Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
 Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for compliance may void the
user’s authority to operate the equipment.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 1


Contents

Contents
Disclaimers ......................................................................................................................... 1
Important Notice ...............................................................................................................1
FCC Compliance .................................................................................................................1
Contents............................................................................................................................. 2
About This Guide ................................................................................................................ 4
Support and Contact Information ....................................................................................... 5
Handling and Safety Instructions ........................................................................................ 6
Chapter 1: Introducing the SolarEdge Firefighter Gateway ................................................. 7
Overview ............................................................................................................................7
Firefighter Gateway User Interfaces ..................................................................................8
LCD and LCD-Menu Buttons...............................................................................................8
Communication Connectors ..............................................................................................9
Other Interfaces .................................................................................................................9
Chapter 2: Installing the SolarEdge Firefighter Gateway ................................................... 10
Safety ...............................................................................................................................10
Transport and Storage .....................................................................................................10
Package Contents ............................................................................................................10
Installation Equipment.....................................................................................................10
Installation Guidelines .....................................................................................................11
Installation Workflow ......................................................................................................11
Mounting the Firefighter Gateway ..................................................................................12
Connecting the Firefighter Gateway to AC ......................................................................13
Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control ............................... 14
Overview ..........................................................................................................................14
Connecting and Configuring an Emergency Stop Button to the Gateway .......................16
Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation ................... 18
Overview ..........................................................................................................................18
Connecting and Configuring the RS485 ...........................................................................19
Verifying the Connection .................................................................................................23
Troubleshooting the RS485 Communication ...................................................................23
Chapter 5: Emergency System Shutdown ......................................................................... 24
Chapter 6: LCD – Status Screens and Setup Options .......................................................... 26
Status Screens ..................................................................................................................26
Main Firefighter Gateway Status ............................................................................................. 26
ID Status .................................................................................................................................. 26
Server Communication Status ................................................................................................. 26
IP Status .................................................................................................................................. 27
ZigBee Status ........................................................................................................................... 27
Wi-Fi Status ............................................................................................................................. 28
Communication Ports Status ................................................................................................... 28

2 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Contents
Setup Menu Options ........................................................................................................29
Language ................................................................................................................................. 31
Communication ....................................................................................................................... 31
Remote Shutdown................................................................................................................... 33
Display ..................................................................................................................................... 33
Maintenance ........................................................................................................................... 33
Information ............................................................................................................................. 34
Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional) ................. 35
Communication Dataflow ................................................................................................35
Communication Types .....................................................................................................35
Creating an Ethernet (LAN) Connection ...........................................................................36
Overview ................................................................................................................................. 36
Ethernet Communication Configuration Options .................................................................... 36
Connecting and Configuring LAN ............................................................................................. 37
Troubleshooting Ethernet Communication ............................................................................. 39
Additional Connection Options ........................................................................................40
Creating a Wireless ZigBee Connection ................................................................................... 40
Creating a Wi-Fi Connection .................................................................................................... 40
Appendix A: Technical Specifications ................................................................................ 41

Firefighter Gateway Installation Guide MAN-01-00113-1.3 3


About This Guide

About This Guide


This user guide is intended for Photovoltaic (PV) installers, technicians, maintainers and integrators who
use the SolarEdge power harvesting system.
This guide describes the process of installing and configuring the SolarEdge Firefighter gateway (also
referred to herein as the "gateway").
This guide assumes that the SolarEdge power harvesting system is already installed and commissioned. For
additional information about how to install and commission the SolarEdge power harvesting system, refer
to the relevant inverter or Safety and Monitoring Interface (SMI) installation guide.
The guide includes the following chapters:
 Chapter 1: Introducing the SolarEdge Firefighter Gateway, page 7, introduces the SolarEdge
firefighter gateway.
 Chapter 2: Installing the SolarEdge Firefighter Gateway, page 10, describes how to install the
SolarEdge firefighter gateway.
 Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control, page 14, describes how to
connect and use an external emergency stop button.
 Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation, page 18, describes
how to connect the firefighter gateway to inverters or Safety and Monitoring Interface SMI using the
RS485 bus connection.
 Chapter 5: Emergency System Shutdown, page 24, describes how to use the emergency stop button
to stop the power production.
 Chapter 6: LCD – Status Screens and Setup Options, page 26, describes how to configure the
SolarEdge gateway and how to identify its status.
 Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional), page 35, describes
how to set up communication through the SolarEdge firefighter gateway to the SolarEdge
monitoring portal
 Appendix A: Technical Specifications, page 41, provides the electrical and mechanical specifications
of the SolarEdge Gateway device.
For further information, datasheets and the most up-to-date certifications for various products in different
countries, please visit the SolarEdge website: www.solaredge.com

4 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Support and Contact Information

Support and Contact Information


If you have technical queries concerning our products, please contact us:

Australia 1800 465 567 [email protected]


APAC (Asia Pacific) [email protected]
Belgium 080073041 [email protected]
France 0800917410 [email protected]
Germany +49 89-45459730 [email protected]
Italy 800 784 824 [email protected]
Japan +81.3.5530.9360 [email protected]
United Kingdom 0800 028 1183 [email protected]
US & Canada 1 877 360 5292 [email protected]
Greece 00800125574
Israel +972 73 240-3118
Netherlands 08000221089 [email protected]
Worldwide +972 73 240-3118
Fax +972 73 240-3117

 The communication method to the SolarEdge server


 The product serial number as appears on its label. The serial number can also be viewed in the
ID Status screen, as described on page 26.
 Your software version, which can be viewed in the ID Status screen, as described on page 26

Firefighter Gateway Installation Guide MAN-01-00113-1.3 5


Handling and Safety Instructions

Handling and Safety Instructions


During installation, testing and inspection, adherence to the following handling and safety instructions is
mandatory.

The following safety symbols may be used in this document. Familiarize yourself with the symbols and
their meaning before installing or operating the system.
WARNING!
Denotes a hazard. It calls attention to a procedure that, if not correctly performed or adhered to, could
result in injury or loss of life. Do not proceed beyond a warning note until the indicated conditions
are fully understood and met.
CAUTION:
Denotes a hazard. It calls attention to a procedure that, if not correctly performed or adhered to, could
result in damage or destruction of the instrument. Do not proceed beyond a caution sign until the
indicated conditions are fully understood and met.
NOTE:
Denotes additional information about the current subject.

IMPORTANT SAFETY FEATURE:


Denotes information about safety issues.

6 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 1: Introducing the SolarEdge Firefighter Gateway

Chapter 1: Introducing the SolarEdge


Firefighter Gateway
Overview
The firefighter gateway provides centralized safety management of SolarEdge systems: If the firefighter
gateway is properly installed and fully functional, firefighters can halt production of a SolarEdge
photovoltaic (PV) power harvesting system and have visual acknowledgement that the installation outputs
a safe DC voltage. The power production can be stopped either manually through an emergency stop
button or automatically through a Fire Alarm Control Panel system. This stops the AC production and
reduces string DC voltage to a safe voltage using the unique SafeDC™ feature.
The firefighter gateway can connect to SolarEdge inverters and to Safety and Monitoring Interfaces (SMIs).
Although DC voltage can be reduced directly from the inverter/SMI or by shutting off the AC voltage, using
the firefighter gateway provides a clear indication of DC voltage shutdown. The firefighter gateway
enables shutting off the installation from a distance of up to 1,000m, while getting visual feedback that the
PV installation is safe.

Figure 1: The SolarEdge Firefighter Gateway

Figure 2: The SolarEdge Firefighter Gateway Connections

Firefighter Gateway Installation Guide MAN-01-00113-1.3 7


Chapter 1: Introducing the SolarEdge Firefighter Gateway

Firefighter Gateway User Interfaces

Optional antenna1 Control RS485-1 SW1


(ZigBee, Wi-Fi)

LCD

Enter (3)
Down (2)
LEDs DC Micro SD Ethernet
Up (1)
(power
supply Esc
input) LCD User Buttons
Figure 3: Gateway interfaces

LCD and LCD-Menu Buttons


The LCD screen displays status information of the SolarEdge firefighter gateway and various menus for
configuration options. The LCD panel and buttons are used during the following processes:
 Operational Mode: The LCD panel allows checking that the gateway is working properly. Refer to
Status Screens on page 26 for a description of this option. Use the LCD user buttons to toggle
through the informative displays and select options.
 Setup: After mounting the gateway, the installer may perform basic gateway configuration, as
described in Setup Menu Options on page 29.
Four buttons are used for controlling the LCD menus (see Figure 3).
 Esc: Moves the cursor to the beginning of the parameter, goes to the previous menu, and cancels a
value change.
 Up (1), Down (2): Moves the cursor between menu options, moves among the characters of a
parameter, and toggles between possible characters when setting a value.
 Enter (3): Selects a menu option or accepts a value change. Also used to enable LCD backlight.

8 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 1: Introducing the SolarEdge Firefighter Gateway

Communication Connectors
The following connectors are available for the SolarEdge firefighter gateway:
 Antenna1: Used for optional wireless antenna connection – ZigBee or Wi-Fi (refer to Creating a
Wireless ZigBee Connection on page 40 and Creating a Wi-Fi Connection on page 40).
 RS485-1: Used for connecting external devices to the gateway (refer Chapter 4: Connecting the
Firefighter Gateway to the SolarEdge Installation on page 18).
 Ethernet: Enables connecting the SolarEdge gateway to the SolarEdge monitoring portal through an
Ethernet switch/router (refer to Creating an Ethernet (LAN) Connection on page 35). The Ethernet
switch/router should be connected to the Internet.

Other Interfaces
The following interfaces are available for the SolarEdge firefighter gateway:
 Control: Used for connection to an external emergency stop button (refer to Chapter 3: Connecting
Emergency Stop Button or Fire Alarm Control on page 14).
 SW1: RS485-1 termination
 DC: Used for the power supply input as described in Connecting the Firefighter Gateway to AC on
page 13
 Micro SD: Used for field software upgrade
 LEDs: All LEDs are ON while the SolarEdge gateway is powered up or configured.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 9


Chapter 2: Installing the SolarEdge Firefighter Gateway

Chapter 2: Installing the SolarEdge


Firefighter Gateway
Safety
CAUTION:
For North America only: The product’s communication with external devices must not use wires
that span more than one building, as per the UL 60950-2 standard.

Transport and Storage


Transport the SolarEdge gateway in its original packaging, without exposing it to unnecessary shocks. If the
original package is no longer available, use a similar box, which can be fully closed.
Store the SolarEdge gateway in a dry place where ambient temperatures are -40°C (-40°F) to
+60°C (140°F).

Package Contents
 Firefighter gateway
 100-240VAC to 12VDC power supply with an interchangeable AC plug (US, EU, AUS, UK)
 Accessory kit including:
 Three 3-pin terminal blocks
 One 6-pin terminal block

Installation Equipment
Standard tools can be used during the installation of the SolarEdge gateway. The following is a
recommendation of the equipment needed for installation:
 Emergency stop button (recommended: a button with a locking feature, which stays mechanically
locked in the off position until turning it clockwise to release it), or a fire alarm control system with
relay output interface
 Allen screwdriver for M5/M6 screw types
 Standard flat head screwdrivers set
 Voltage tester screwdriver
 Drill and 4mm diameter bits
 DIN rails
 Wire cutters
 Wire strippers
 Voltmeter
 Three twisted wires or four-wire twisted pair cable (wire cross-section area: 0.2- 1 mm²/ 24-18 AWG
(a CAT5 cable may be used); Maximum nodes: 32; Maximum distance between devices: 1 km /
3300 ft.
 For installing the communication options: CAT5/6 Ethernet cable

10 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 2: Installing the SolarEdge Firefighter Gateway

Installation Guidelines
The following requirements apply when locating and mounting the SolarEdge Gateway:
 The SolarEdge gateway is suitable for mounting indoors. For outdoor installation, use an external
outdoor enclosure (not provided by SolarEdge).
 The SolarEdge gateway must always remain in an ambient temperature of -20°C (-4°F) to
+60°C (140°F).
 Cable specifications:
Connection Type Cable Type Maximum Length
RS485 communication bus Three twisted wires or 4-wire twisted pair 1,000m (3,330 ft)
(per RS485 port) cable (two twisted pairs).
Recommended wire size: 20 AWG / 0.52 mm2
Ethernet CAT5/6 100m (325 ft).

 The SolarEdge gateway power supply requires a socket outlet with a grid voltage of 100 V - 240 V
(50 Hz/60 Hz).
 Protect the SolarEdge gateway from dust, wet conditions, corrosive substances and vapors.

Installation Workflow
The following provides an overview of the workflow for installing and setting up the firefighter gateway

Step 1 Mounting the firefigher safety gateway Page 12

Step 2 Connecting an emergency stop button or a fire Page 16


alarm control system

Step 3 Connecting the firefighter safety gateway to the Page 18


SolarEdge installation

Step 4 Configuring the Page 18


firefighter safey gateway and inverters/SMI

Step 5 Verifying PV system shutdown using the firefighter Page 24


gateway

Using the firefighter safety gateway to connect the


Step 6 installation to the monitoring server (optional) Page 26

Firefighter Gateway Installation Guide MAN-01-00113-1.3 11


Chapter 2: Installing the SolarEdge Firefighter Gateway

Mounting the Firefighter Gateway


The SolarEdge gateway can be installed on a wall or on a DIN rail.

► To mount the SolarEdge gateway on a wall:


1 Determine the mounting location. Leave clearance from all sides of the SolarEdge gateway for cover
opening, cable connection and routing.
2 Open the clips at the rear of the gateway by pushing the clips outwards.

Wall mount
holes

Press here Press here

Figure 4: Clips in Open Position

3 Position the device on the wall with the open clips, as shown in Figure 4. Mark points through the
holes of the clips and drill holes using a 4mm diameter drill bit.
4 Mount the unit using screw anchors and screws (use 3.5mm diameter screws, 20mm minimum
length, not provided by SolarEdge).

► To mount the SolarEdge gateway on a DIN rail:


1 Ensure that the clips are closed, as shown below:

Press here

Press here

Figure 5: Clips in Closed Position

12 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 2: Installing the SolarEdge Firefighter Gateway
2 Hook the two lower clips of the SolarEdge gateway onto the lower edge of the DIN rail.
3 Press the SolarEdge gateway upwards and snap it into the upper edge of the DIN rail. When on the
rail, the clip "grips" the rail on both the top and bottom lips of the rail.
To remove the DIN clip from the rail, simply push upwards on the DIN clip (thereby compressing the
springs in the bottom), pivot the top of the clip off of the rail, and then move the whole clip down to
also release the bottom of the clip. No screwdrivers or special tools are required.
4 The following figure shows the gateway’s rear side when mounted on a DIN rail.

DIN rail clips

Figure 6: Gateway Mounted on a DIN Rail

Connecting the Firefighter Gateway to AC


For connecting to power, use the supplied power supply:
1 Insert the power supply DC connector to the SolarEdge gateway (see Figure 3).
2 Connect the power supply to the AC mains. The LEDs are lit momentarily to indicate power
connection (see Figure 3)
CAUTION
If you use a non-SolarEdge power supply, check that it has 12Vdc/1A output ratings, and that it is
certified to UL/CSA/IEC60950-1 2ed standards. Limited Power Source output, NEC class 2.
Verify the power supply polarity as marked on the gateway.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 13


Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control

Chapter 3: Connecting Emergency Stop


Button or Fire Alarm Control
Overview
An external emergency stop button (not supplied by SolarEdge) should be connected to the firefighter
gateway, in order to shut down the PV system in case of emergency. Pressing the emergency stop button
starts the shutdown sequence of the PV system. Preferably, use a button with a locking feature that stays
mechanically locked in the off position until you turn it clockwise a quarter turn to unlock and release it.
The firefighter gateway can also be connected to a fire alarm control unit that has a relay output. The relay
output of the fire alarm control has the same functionality as the button. You can connect both a stop
button and a relay together to the same firefighter gateway, or two stop buttons or two relays.

Figure 7: Example: Emergency Stop Button and Fire Alarm System Connection

The emergency stop button(s) or relay(s) connect to the L1 or L2 ports on the Control connector of the
gateway, between 5V and L1 / L2/both. In the following sections, the instructions refer to L1, however
applies to L2 as well.

Figure 8: Emergency Stop Button Connection

14 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control
There are two types of contact states in Emergency Stop buttons/relays:
 Normally open (NO) – the contacts are open until closed by operation of the switch. This type of
switch should be connected in the following manner:

This installation is safe when L1/L2 has 5V input, and active with L1/L2 is not connected. This is
considered Normal polarity in the configuration screen.
 Normally closed (NC) – the contacts are closed until opened by operation of the switch. This type of
switch should be connected in the following manner:

This installation is safe when L1/L2 is not connected and active when L1/L2 is 5V. This is considered
Reverse polarity in the configuration screen.
 If you connect more than one firefighter gateways to the same emergency stop button, they should
connect to the same grounding, as in the following example:

 In some fire alarm control systems, the switch is grounded internally. This type of switch should be
connected in the following manner, sharing ground between the control system and the firefighter
gateway.

Fire Alarm Control System

In these cases, a Normally Open relay will connect L1/L2 to ground for safety, and when active, L1/L2
is 5V. This will be configured as a reverse polarity switch.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 15


Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control

Connecting and Configuring an Emergency Stop


Button to the Gateway
1 Depending on the button/relay type, connect L1/L2, 5V and Ground as described above. Use wire
size 20 AWG/ 0.52mm2: Insert the ends of wires into the ports of the supplied 6-pin terminal block.

G
5V
L1
L2

Figure 9: 6-pin Terminal Block

2 Insert the terminal block into the Control connector on the firefighter gateway.
3 Verify that the SolarEdge gateway is connected to a power outlet.
4 Press the Enter button until the following message is displayed:
P l e a s e e n t e r
P a s s w o r d
* * * * * * * *

The gateway is now in Setup mode and all its LEDs are lit.
5 Use the three-right-most LCD buttons to type in the following password: 12312312. The following
menu is displayed:
L a n g u a g e < e n g >
C o m m u n i c a t i o n
R e m o t e S h u t d o w n
D i s p l a y
M a i n t e n a n c e
I n f o r m a t i o n

6 Short-press the up/down buttons to scroll to the Remote Shutdown menu. Press the Enter key to
select it. The remote shutdown parameters are displayed:
L 1 P o l a r i t y < N o r m . >
L 2 P o l a r i t y < N o r m . >
S a f e V d c < 1 2 0 V >
C l r A l a r m M o d e < M >
C l e a r A l a r m

7 Set the following:


 L1/L2 Polarity: The lines polarity - Normal (default) or Reverse
 Normal – safety will be activated when L1/L2 has 5V
 Reverse – Safety will be activated when L1/L2 is connected to ground or not connected.
 Safe Vdc: Threshold value for safe Vdc: When the maximum DC voltage (of all connected devices)
reaches this threshold, the PV system will be considered safe and the display will show Safe DC in
the main gateway status screen. You may set the threshold in the range between 30 -120V (default
120V)

16 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control

 Clr Alarm Mode: Select the method to return to normal operation as soon as the emergency stop
button is released:
 Automatic (default) – when releasing the stop button or relay, the system immediately returns
to normal power production.
 Manual – when releasing the stop button or relay, the system will not return to normal
operation unless the user manually clears the alarm by selecting Clear Alarm (below). Use this
option if the button does not have the locking feature, the relay in the control system may
open unexpectedly, or if the user requires this added step.
 Clear Alarm: Used to allow normal operation. Appears only if the Clr Alarm Mode parameter (above)
is set to Manual, and the installation is in remote safety shutdown

Firefighter Gateway Installation Guide MAN-01-00113-1.3 17


Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation

Chapter 4: Connecting the Firefighter


Gateway to the SolarEdge Installation
Overview
The SolarEdge firefighter gateway connects to the PV system installation using the RS485 communication
option. The RS485 option enables creating a chain (bus) of up to 31 slave SolarEdge devices, connected to
one master, which can be another SolarEdge device or the SolarEdge firefighter gateway.
NOTE:
Only SolarEdge devices (inverters, Control and Communication Gateways (CCGs) and SMIs) are
allowed on the RS485 communication bus.

The following is an example of a slave gateway connected to a chain of slave inverters (one inverter is the
master).

Terminated Terminated

Figure 10: Example of RS485 Connection

The following sections describe how to connect the RS485 bus and how to configure its components.

18 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation

Connecting and Configuring the RS485


The RS485 bus uses a three-wire cable connecting the RS485-1 terminal block on the SolarEdge gateway to
the RS485 input of the inverters/SMI.
RS485 wiring specifications:
 Cable type: 4-wire shielded twisted pair
 Wire cross-section area: 0.2- 1 mm²/ 24-18 AWG (a CAT5 cable may be used)
 Maximum nodes: 32
 Maximum distance between devices: 1 km /3300 ft.
NOTE:
If the distance between devices is more than 10 m/33 ft, or in cases where there is a risk of induced
voltage surges, it is recommend to use external surge protection devices . For details refer to:
http://www.solaredge.com/files/pdfs/lightning_surge_protection.pdf

► To connect the RS485 communication bus between inverters/SMIs and


SolarEdge gateway:
1 Use one of the supplied 3-pin terminal blocks: Loosen the screws and insert the wire ends into the
A, B and G pins. For connections longer then 10m use twisted pair wires for A and B wires.

Screws

G
B
A
Figure 11: 3-pin Terminal Block

2 Connect the 3-pin terminal block to the RS485-1 port on the gateway.
NOTE:
RS485-1 is configured as SolarEdge device by default, therefore RS485-1 is used as the RS485
bus connection point.
3 If the gateway is at the end of the RS485 chain, terminate the gateway by switching a termination
dipswitch to ON. The switches in the SolarEdge gateway are marked SW1 for the RS485-1 port
termination (and SW2), as shown below:

On Off

A B G SW1 SW2 A B G

RS485- 2 RS485-1

Figure 12: RS485 Connectors and Termination Switches

Firefighter Gateway Installation Guide MAN-01-00113-1.3 19


Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation
4 Open the inverter/SMI cover as described in their manual.
5 Remove the seal from one of the openings in communication gland #2 of the inverter and insert the
cable through the opening.
6 Pull out the 9-pin RS485 terminal block connector, as shown below:

Figure 13: The RS485 terminal block in the inverter/SMI

7 Loosen the screws of pins B, A and G on the left-most of the RS485 terminal block.

RS485-2 (not used)

G
A RS485-1
B

Figure 14: RS485 terminal block

8 Insert the ends of wires into the G, A and B pins shown above. You can use any color wire for each of
the A, B and G connections, as long as the same color wire is used for all A pins, the same color for all
B pins and the same color for all G pins.

20 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation
9 Connect all B, A and G pins in all inverters/SMI. The following figure illustrates this connection
schema (the illustration applies to both inverters and SMI):

SolarEdge Gateway

Figure 15: Connecting SolarEdge Devices (Inverters or SMI) in a Chain

NOTE:
Do not cross-connect B, A and G wires.
Do not insert wires into RS485-2 pins.
10 Tighten the terminal block screws.
11 Push the RS485 terminal block firmly all the way into the communication board.
12 Terminate the inverters/SMIs at the two ends of the chain by switching a termination dipswitch
inside the inverter/SMI to ON (move the switch to the top). The switch is located on the
communication board and is marked SW7.

Use the left switch

Figure 16: RS485 Termination Switch

NOTE:
Only the first and the last SolarEdge devices in the chain should be terminated. The other
devices in the chain should have the termination switch OFF.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 21


Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation

► To configure the RS485 communication bus with SolarEdge inverters/SMI:


By default, all SolarEdge devices are pre-configured as slaves. Slaves can be further configured using the
RS485-x Conf option in the Communication menu.
One device must be set as the master on the RS485 bus. Any one of the SolarEdge devices may be the
master (firefighter gateway, inverter, or SMI). If you connect the installation to the SolarEdge monitoring
portal, the device used to connect to the server must be the master.
The following describes how to configure the master device.
1 Press the Enter button until the following message is displayed:
P l e a s e e n t e r
P a s s w o r d
* * * * * * * *

The gateway is now in Setup mode and all its LEDs are lit.
2 Use the three-right-most LCD buttons to type in the following password: 12312312. The following
menu is displayed:
L a n g u a g e < e n g >
C o m m u n i c a t i o n
R e m o t e S h u t d o w n
D i s p l a y
M a i n t e n a n c e
I n f o r m a t i o n

3 Short-press the arrow buttons to scroll to the Communication menu. Press the Enter key to select it.
4 Select Server  RS485-X Conf (X=1 or 2 depending on the specific physical port connection).
5 To configure the master , select the following in the LCD menu:
 Communication  RS485-1 Conf  Device Type  SolarEdge
 RS485-1 Conf  Protocol  Master
 RS485-1 Conf  Slave Detect
The system starts automatic detection of the SolarEdge slave inverters connected to the master
gateway. The gateway should report the correct number of slaves. If not, verify the connections and
terminations. Verify that only one master is configured on the bus.
6 Close the inverter/SMI cover and start power production.
7 On the firefighter gateway main status screen, verify that "Dev. On", "Dev. Safe" and "Max Vdc"
values are set according to your setup. That is, if you connected three slaves:
 Dev. On = 3/3
 Dev. Safe = 0/3
 Max Vdc = Voltage of the slave with highest DC voltage
P V N o r m a l O p e r a t i o n
0 0 3 / 0 0 3 D e v . O N
0 0 0 / 0 0 3 D e v . S a f e
M a x . V D C : 1 5 0 V

The PV installation is now connected to the firefighter gateway. Power production can now be
stopped at emergencies.
8 Test the Emergency system shutdown as described in Chapter 5: Emergency System Shutdown on
page 24.

22 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation

Verifying the Connection


1 After connection, a message similar to the following appears in the main status screen (see also Main
Firefighter Gateway Status on page 26):
P V N o r m a l O p e r a t i o n
X X X / Y Y Y D e v . O N
Z Z Z / Y Y Y D e v . S a f e
M a x . V D C : 7 5 0 V

2 Assuming that the system is producing power, check:


 XXX - number of devices that are connected to the gateway
 YYY - number of devices (inverters and SMIs) that are connected and ON
 ZZZ=0 - number of devices in Safe mode, that is, disconnected or shut down.
3 If No Communication or Partial Com. appear in the first line, refer to Troubleshooting the RS485
Communication, below.

Troubleshooting the RS485 Communication


1 If No Communication is displayed on the firefighter gateway, perform the following:
 Verify that the RS485 cable is connected to all inverters. Check the connections between the
first inverter in the chain and the other inverters.
 Verify that one of the devices is defined as the master and that slaves were detected, as
described in Step 5 above.
2 If Partial Com. is displayed on the firefighter gateway, one or more inverters are disconnected from
the bus. Perform the following:
 Verify that the RS485 cable is connected to all inverters.
 Check the Server Communication Status screen of all the inverters. The following should
appear:
S e r v e r : R S 4 8 5
S t a t u s : O K

If the message Master Not Found, check the connections to the master device and fix if required.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 23


Chapter 5: Emergency System Shutdown

Chapter 5: Emergency System Shutdown


In emergencies, use the emergency stop button to stop power production.
Use this procedure also to test the PV system shutdown using the firefighter gateway.

► To stop PV harvesting system power production:


1 On the firefighter gateway, press the Enter button to light up the LCD and display the main status
screen. Check that a message similar to the following appears, and that the first line does NOT
display No Communication or Partial Com.:
P V N o r m a l O p e r a t i o n
0 0 3 / 0 0 3 D e v . O N
0 0 0 / 0 0 3 D e v . S a f e
M a x . V D C : 1 5 0 V

WARNING!
If the RS485 communication between the firefighter gateway and inverters is disconnected for
any reason (including damage to cables caused by a fire), the firefighter gateway LCD will
display "No Communication" or "Partial Com". In this case, the firefighter gateway CANNOT
be relied upon to disconnect the SolarEdge PV harvesting system.
3 Press the emergency stop button. The PV system starts the shutdown sequence.
4 On the firefighter gateway LCD, check the main status screen. A message similar to the following
should appear:
P V S h u t t i n g D o w n
0 0 1 / 0 0 3 D e v . O N
0 0 2 / 0 0 3 D e v . S a f e
M a x . V d c : 1 5 0 V

The status changes to PV Reducing Voltage. The shutdown is immediate but safe indication will
take 3 to 5 minutes until the inverter capacitors are discharged.
Upon reaching safety voltage (default: 120V), the following message appears on the firefighter gateway
LCD:

P V S y s t e m s a f e

WARNING!
If the communication between the firefighter gateway and the inverters / SMIs is not available
during the shutdown sequence, the following message appears on the LCD:
System Failed
to Shutdown
If this occurs:
1. Shutdown the AC power to the inverters / SMIs
2. Wait 3 to 5 minutes until the capacitors are discharged.
On the inverters/SMIs LCD display, the following message appears upon reaching safe voltage:
F i r e f i g h t e r
R e m o t e S h u t d o w n

NOTE
The Maintenance submenu in the inverters/SMIs LCD includes a Clear Alarm option that appears
only in remote shutdown. This enables clearing the remote shutdown state for a specific device if
required.

24 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 5: Emergency System Shutdown
5 Disconnect the AC power to the inverters/SMIs.

► To regain system normal operation:


1 Release the emergency stop button.
2 Turn ON the AC power.
3 Do one of the following:
 If you set the Clear Alarm Mode in the firefighter gateway to Automatic (refer to Connecting and
Configuring an Emergency Stop Button to the Gateway on page 16), check the firefighter gateway
main status screen displays the status PV Normal Operation.
 If you set the Clear Alarm Mode in the firefighter gateway to Manual, do the following:
a. Enter Setup mode, as described in Setup Menu Options on page 29.
b. Select Fire Safety  Clear Alarm  Yes. the following is displayed:
C l e a r i n g A l a r m …

c. If the alarm was cleared, the following is displayed:


A l a r m C l e a r e d

If Failed is displayed, check that you have unlocked the emergency stop button.
4 On the firefighter gateway LCD, check the main status screen. A message similar to the following
should appear:
P V N o r m a l O p e r a t i o n
0 0 3 / 0 0 3 D e v . O N
0 0 0 / 0 0 0 D e v . S a f e
M a x . V D C : 1 6 4 V

5 If there is no communication between slave inverters and the master gateway, clear the alarm from
the inverter, as follows:
a. Enter Setup mode in the inverter LCD menu.
b. Select Maintenance > Clear Alarm.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 25


Chapter 6: LCD – Status Screens and Setup Options

Chapter 6: LCD – Status Screens and Setup


Options
This chapter describes the LCD display of the SolarEdge firefighter gateway. The LCD screen displays status
information of the gateway and various menus for configuration options.

Status Screens
During normal operation, pressing the Enter button turns the LCD backlight ON. Additional presses on the
Enter button display the following screens one after the other. The backlight is active for 30 seconds by
default. This duration is configurable, as described on page 33.
Main Firefighter Gateway Status
This window displays the communication and safety status of components in the system
< S t a t u s >
X X X / Y Y Y D e v . O N
Z Z Z / Y Y Y D e v . S a f e
M a x . V D C : 0 0 0 V

 Status: can be one of the following system stages:


 PV Normal Operation
 PV Shutting Down – appears when pressing the emergency stop button
 PV Reducing Voltage - appears during emergency stop
 PV System Safe – appears when the system reaches 120 V after pressing the emergency stop
button
 No Communication – indicates that the slave devices are disconnected from the master
 Partial Com. – indicates the number of communicating devices (inverters or SMIs) out of the
total number of devices in the installation
 XXX/YYY Dev. ON: The number of operational inverters or SMIs out of the total number of
inverters/SMIs in the installation
 ZZZ/YYY Dev. Safe: Number of inverters or SMIs that reached the safety threshold voltage or below,
out of the total number of inverters/SMIs in the installation
 Max. Vdc: Real-time maximum DC voltage for the entire installation
ID Status
This window displays the ID of the gateway and the software version.
I D : # # # # # # # # # #
C P U : 0 0 0 2 . 0 4 1 1

Server Communication Status


S e r v e r : L A N < S _ O K >
S t a t u s : < O K >
x x x x x x x x
< E R R O R M E S S A G E >

 Server: The method of connection to the SolarEdge monitoring server.


 LAN
 RS232
 RS485 (only applicable for slave SolarEdge devices on the RS485 bus)
 ZigBee (only applicable for slave ZigBee devices)

26 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 6: LCD – Status Screens and Setup Options
 Wi-Fi
 None
 S_OK: The connection to the SolarEdge monitoring portal is successful (appears only if the inverter is
connected to the portal).
 Status: Displays OK if the gateway established a successful connection and communication with the
specified server port/device (LAN, RS485, ZigBee transceiver or)
If the OK status is not displayed, an error has occurred.
 xxx…:Eight-bit Ethernet Communication Connection Status: When Ethernet communication is used,
an additional row with a string of 1s and optionally 0s is displayed. 1 indicates OK, 0 indicates an
error. For a list of possible errors and how to troubleshoot them, refer to Troubleshooting Ethernet
Communication on page 39. The following is a list of bits description, ordered left-to-right:
 Bit 1: The Ethernet link, physical Ethernet cable connection and WLAN link connection are all
OK.
 Bit 2: The DHCP IP is OK. The IP was successfully obtained from DHCP (if set to static IP =1).
 Bit 3: The ping gateway is OK. The ping to the local switch/router passed or the ping to APN was
OK.
 Bit 4: The ping to google.com was OK.
 Bit 5: The ping to server1 was OK.
 Bit 6: The ping to server2 was OK.
 Bit 7: The ping to server3 was OK.
 Bit 8: Communication to the SolarEdge server is OK.
 Error message: Refer to Troubleshooting Ethernet Communication on page 39.
IP Status
This window describes the Ethernet configuration: IP, Mask, TCP gateway and MAC address of the
gateway.
I P 1 9 2 . 1 6 8 . 2 . 1 1 9
M S K 2 5 5 . 2 5 5 . 2 5 5 . 0
G W 1 9 2 . 1 6 8 . 2 . 1
M A C 0 - 2 7 - 0 2 - 0 0 - 3 9 - 3 6

ZigBee Status
This window describes the ZigBee configuration:
P A N : X X X X X
C H : X X / X X X X R S S I : < L >
I D : X X X X X X X X X X X X X X X X
Z i g B e e R e a d y

 PAN: The ZigBee transceiver pan ID.


 CH: The ZigBee transceiver channel
 RSSI: The receive signal strength of the neighboring ZigBee transceiver. L = low, M = medium, H =
high and - = no signal.
 ID: The ZigBee transceiver ID.
 ZigBee Ready: This field is shown only in devices with ZigBee router transceivers (slaves), in a multi-
point (MP) protocol configuration. If a ZigBee transceiver is not physically connected, a No ZigBee
message is displayed.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 27


Chapter 6: LCD – Status Screens and Setup Options

Wi-Fi Status
This window describes the Wi-Fi configuration:
I P : 1 9 2 . 1 6 8 . 2 . 1 1 9
G W : 1 9 2 . 1 6 8 . 2 . 1
S S I D : x x x x x x x x
R S S I : < L / M / H / - >

 IP: The DHCP provided address


 GW: The gateway IP address
 SSID: Service Set Identifier - the name of a wireless local area network (WLAN). All wireless devices
on a WLAN must employ the same SSID in order to communicate with each other.
 RSSI: The receive signal strength indication of the closest Wi-Fi in the SolarEdge system. L = low,
M = medium, H = high and (-) = no signal.

Communication Ports Status


D e v P r o t # #
R S 4 8 5 - 1 < S E > < M > < 0 0 >
R S 4 8 5 - 2 < - - - > < - - > < - - >
Z i g B e e < S E > < M P S > < - - >

This window presents the communication port (RS485-1/2 or ZigBee), and the devices connected to them,
with details about the number, type, and protocol.
 DEV: The type of device that was configured to the specific port ( based on the port’s functionality),
as follows:
 SE: SolarEdge device (default)
 ---: None
 PROT: The protocol type to which the port is set:
For a SolarEdge device:
 S: SolarEdge slave
 M: SolarEdge master
 P2P: ZigBee point-to-point
 MPM: ZigBee multipoint master (for a ZigBee coordinator module)
 MPS: ZigBee multipoint slave (for a ZigBee router module)
For a non-SolarEdge logger:
 SS: SunSpec
For non-SolarEdge inverter readers and electricity meters, refer to
http://www.solaredge.com/articles/se-supported-devices.
 ##: The total number of slaves detected on the specific port

28 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 6: LCD – Status Screens and Setup Options

Setup Menu Options


This section describes basic gateway configuration options.
1 Verify that the SolarEdge gateway is connected to a power outlet.
2 Press the Enter button until the following message is displayed:
P l e a s e e n t e r
P a s s w o r d
* * * * * * * *

The gateway is now in Setup mode and all its LEDs are lit. The gateway automatically exits Setup
mode if no buttons are pressed for more than 2 minutes.
3 Use the three-right-most LCD buttons to type in the following password: 12312312. The following
message is displayed:
L a n g u a g e < e n g >
C o m m u n i c a t i o n
R e m o t e S h u t d o w n
D i s p l a y
M a i n t e n a n c e
I n f o r m a t i o n

Firefighter Gateway Installation Guide MAN-01-00113-1.3 29


Chapter 6: LCD – Status Screens and Setup Options

The following shows a hierarchical tree of the menu options:

L a n g u a g e < e n g >
C o m m u n i c a t i o n
R e m o t e S h u t d o w n
D i s p l a y
M a i n t e n a n c e
I n f o r m a t i o n

Language:
E n g l i s h
G e r m a n
S p a n i s h
F r e n c h
I t a l i a n

Communication1:
S e r v e r < L A N >
L A N C o n f
R S 4 8 5 – 1 C o n f < M >
R S 4 8 5 – 2 C o n f < >
Z i g B e e C o n f < >
W i - F i C o n f < >
R S 2 3 2 C o n f

Remote Shutdown
L 1 P o l a r i t y < N o r m . >
L 2 P o l a r i t y < N o r m . >
S a f e V d c < 1 2 0 V >
C l r A l a r m M o d e < A >

Display:
L C D O n T i m e < 3 0 >

Maintenance:
D a t e a n d T i m e
F a c t o r y R e s e t
S W U p g r a d e - S D C a r d

Information:
V e r s i o n s
E r r o r L o g
W a r n i n g l o g

This section describes how to use the LCD menus for configuring the SolarEdge gateway.

1 If Wi-Fi is connected, the ZigBee item is not displayed, and vice versa.

30 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 6: LCD – Status Screens and Setup Options

Language
Select the Language option to set the language in which the LCD should display. The default setting is
English.
Communication
1 Select the Communication option to define and configure:
 The communication option used by the gateway to communicate with the SolarEdge
Monitoring portal
 The communication option used to communicate between multiple SolarEdge devices or other
external non-SolarEdge devices, such as electricity meters or loggers.
2 Set the communication options as described in Connecting and Configuring the RS485 on page 18 and
Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional) on page 35.

The following shows a hierarchical tree of the menu options in the Communication menu. For detailed
information of commonly used the configuration options, refer to the Communication Options application
note, available on the SolarEdge website http://www.solaredge.com/files/pdfs/solaredge-
communication_options_application_note_v2_250_and_above.pdf.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 31


Chapter 6: LCD – Status Screens and Setup Options
Communication2:
S e r v e r < L A N >
L A N C o n f
R S 4 8 5 – 1 C o n f < S >
R S 4 8 5 – 2 C o n f < >
Z i g B e e C o n f < S >
W i - F i C o n f < N / A >
R S 2 3 2 C o n f

Server:
L A N
R S 2 3 2
R S 4 8 5
Z i g b e e
N o n e

LAN Conf:
I P C o n f i g
S e t D H C P < e n >
S e t I P
S e t M a s k
S e t G a t e w a y
S e t D N S
S e t S e r v e r A d d r
S e t S e r v e r P o r t

RS485-1/2 Conf:
D e v i c e T y p e < S E >
P r o t o c o l < S >
D e v i c e I D < 1 >
S l a v e D e t e c t < 0 >

ZigBee Conf (enabled only if the ZigBee .module is connected):


D e v i c e T y p e < S E >
P r o t o c o l < M P S >
D e v i c e I D < 1 >
P A N I D
S c a n C h a n n e l
L o a d Z B D e f a u l t s
S l a v e D e t e c t < 0 >

Wi-Fi Conf (enabled only if the internal module is connected):


S c a n N e t w o r k s
S e t k e y
L o a d D e f a u l t s

RS232 Conf:
D e v i c e T y p e < S E >
P r o t o c o l < D R C T >

2 If Wi-Fi is connected, the ZigBee item is not displayed, and vice versa.

32 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 6: LCD – Status Screens and Setup Options

Remote Shutdown
Select Remote Shutdown to set the following:
L 1 P o l a r i t y < N o r m . >
L 2 P o l a r i t y < N o r m . >
S a f e V d c < 1 2 0 V >
C l r A l a r m M o d e < M >
C l e a r A l a r m

 L1/L2 Polarity: The lines polarity - Normal (default) or Reverse


 Safe Vdc: Threshold value for safe Vdc: When the maximum voltage (of all connected devices)
reaches this threshold, the display will show Safe DC in the main gateway status screen. Select
either:
 Safe Vdc. – sets the threshold to the default 120V
 Setting the threshold in the range between 30 -120V (default 120V)
 Clr Alarm Mode: Enables clearing the alarms of emergency stop. Select either:
 Automatic (default) – when releasing the stop button, the system returns to normal opertaion
 Manual - when releasing the stop button, clear the alarm manually (select Clear Alarm below)
in order to return the system to normal operation
 Clear Alarm: Appears only if Clr Alarm Mode is set to Manual and a stop command has already been
sent. After releasing the stop button, select this option to return to normal operation.
For more information, refer to Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control on
page 14.
Display
Select Display to set the following:
L C D O n T i m e < 3 0 >

 LCD On Time <30>: The number of seconds that the LCD backlight is ON after the LCD button is
pressed. Set to 0 if you want the LCD to be lit at all times.
Maintenance
Select Maintenance to set the following options:
D a t e a n d T i m e
F a c t o r y R e s e t
S W U p g r a d e S D C a r d

 Date and Time: Set the internal real-time clock. If connected to the SolarEdge monitoring portal, the
date and time are set automatically and only time zone should be set.
 Factory Reset: Perform a general reset to the gateway default settings.
 SW Upgrade SD Card: Perform a software upgrade using an SD card.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 33


Chapter 6: LCD – Status Screens and Setup Options

Information
Select Information to display the following options:
V e r s i o n s
E r r o r L o g
W a r n i n g l o g

 Versions: Displays inverter firmware versions :


I D : # # # # # # # # # #
C P U : 0 0 0 2 . 0 3 3 6 . 0 0 0 0

 ID: The SolarEdge gateway ID. 10 last digits of the S/N


 CPU: The communication board firmware version.
NOTE:
Please have these numbers ready when you contact SolarEdge support.

 Error Log: Displays the last five errors.


 Warning Log: Displays the last five warnings.

34 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional)

Chapter 7: Setting Up Monitoring through the


Firefighter Gateway (Optional)
Communication Dataflow
The SolarEdge site information can be accessed remotely using the SolarEdge monitoring portal, as
described in the SolarEdge Monitoring Portal User Guide. In order to transfer monitoring data from a
SolarEdge site to the SolarEdge monitoring portal, a communication connection must be set up.
Communication setup is not required for power harvesting or for the safety control of the firefighter
gateway, however is needed when using the monitoring portal.
This chapter describes how to set up this connection when the gateway is the connection point to the
monitoring portal.
The connection point can be any SolarEdge device. If it is the firefighter gateway, the gateway should be
the master on an RS485 bus. Otherwise, it should be a slave.

Communication Types
The following types of communication can be used to transfer the monitored information from the
inverter to the SolarEdge monitoring portal through the SolarEdge gateway:
 Ethernet: Used for a LAN connection
 RS485: Enables connection of external devices, such as other SolarEdge inverters, non-SolarEdge
loggers or electricity meters, and transferring their information through the SolarEdge gateway to
the SolarEdge monitoring portal using Ethernet or ZigBee. The RS485-1 enables connection of
multiple SolarEdge devices (inverters/SMIs/gateways) through the same bus to the SolarEdge
gateway, such that connecting only one gateway to the server is sufficient to provide communication
services for all the devices on the bus.
 ZigBee (optional): Enables wireless connection of one or more SolarEdge devices through a ZigBee
transceiver (sold separately).
 Wi-Fi (optional): Enables wireless connection of one or more SolarEdge devices through Wi-Fi (sold
separately).
 The Mini-USB: enables PC/laptop connection for software upgrade using the SolarEdge configuration
tool. Use a USB to mini-USB adapter cable for this connection.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 35


Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional)

Creating an Ethernet (LAN) Connection


Overview
This communication option enables using an Ethernet connection to connect the SolarEdge gateway to the
SolarEdge monitoring portal through a LAN. The SolarEdge gateway has an RJ45 connector for Ethernet
communication.

Figure 17: Example of Ethernet Connection

Ethernet Communication Configuration Options


The following is a description of the options to configure the Ethernet (LAN) port settings.
Communication:
S e r v e r < L A N >
L A N C o n f
R S 4 8 5 – 1 C o n f < S >
R S 4 8 5 – 2 C o n f < >
Z i g B e e C o n f < >
R S 2 3 2 C o n f

LAN Conf
I P C o n f i g
S e t D H C P < e n >
S e t I P
S e t M a s k
S e t G a t e w a y
S e t D N S
S e t S e r v e r A d d r
S e t S e r v e r P o r t

 IP Config: Displays the current IP configuration of the gateway, as shown below. If DHCP is used, this
screen reflects the parameters retrieved from the DHCP server. If manual settings are used, the
screen shows the last manually input configurations.
I P 0 . 0 . 0 . 0
M S K 2 5 5 . 2 5 5 . 2 5 5 . 0
G W 1 9 2 . 1 6 8 . 0 . 1
D N S 0 . 0 . 0 . 0

 Set DHCP <En>: If the LAN connection between the gateway and the SolarEdge Monitoring Portal has
a DHCP server, enable this option by setting it to Enable (default). If this option is enabled, then the
DHCP server automatically configures the IP, Subnet Mask, gateway and DNS. If not, set them
manually.

36 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional)

 Set IP: Enables setting the IP of the gateway according to the LAN settings:
 Use the Up and Down buttons to adjust the value of each IP address octet.
 Press the Enter button to move to the next IP address octet.
 Long press the Enter button (until Applied message appears) – apply the value
 Long press the Esc button (until Aborted message appears) – erase all characters
S e t u p I P
1 9 2 . 1 6 8 . 2 . 7

 Set Mask: Set the subnet mask of the SolarEdge gateway according to the LAN settings.
 Set Gateway: Set the gateway address of the SolarEdge gateway according to the LAN settings.
 Set DNS: Set the DNS of the SolarEdge gateway according to the LAN settings.
 Set Server Addr: Set the IP address of the SolarEdge monitoring portal. This option is predefined in
the SolarEdge gateway to specify the SolarEdge monitoring portal IP address and does not normally
need configuration.
 Set Server Port: Set the port through which to connect to the SolarEdge monitoring portal. This
option is predefined in the gateway to specify the SolarEdge monitoring portal IP port and normally
does not need configuration.
NOTE:
If your LAN has a firewall, you must verify that the address and port configured in the Set Server
Addr and the Set Server Port fields are not blocked.
You may need to configure it to enable the connection to the following address:
Destination Address: prod.solaredge.com
Port: 22222
Connecting and Configuring LAN
► To connect the Ethernet port to the router/switch:
1 Use a pre-crimped cable or use a crimper to prepare an RJ45 communication connector on both ends
of a standard CAT5/6 cable: Insert the eight wires into the RJ45 connector.

CAT5/6 standard cables have eight wires (four twisted pairs), as shown in the diagram below. Wire
colors may differ from one cable to another. You can use either wiring standard, as long as both sides
of the cable have the same pin-out and color-coding.
Wire Color3 10Base-T Signal
RJ45 Pin #
T568B T568A 100Base-TX Signal
1 White/Orange White/Green Transmit+
2 Orange Green Transmit-
3 White/Green White/Orange Receive+
4 Blue Blue Reserved
5 White/Blue White/Blue Reserved
6 Green Orange Received-
7 White/Brown White/Brown Reserved
8 Brown Brown Reserved

3 The firefighter gateway connection has a 568A layout and does not support RX/TX polarity change. Supporting crossover
Ethernet cables depends on the switch capabilities.

Firefighter Gateway Installation Guide MAN-01-00113-1.3 37


Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional)

Figure 18: Standard cable wiring

1 Connect one end of the Ethernet cable to the RJ45 plug at the router or Ethernet gateway that
is connected to the Internet.
2 Connect the other end to the SolarEdge gateway Ethernet connector.
3 Verify that the yellow communication LED turns ON.

► To configure Ethernet communication to the SolarEdge monitoring portal:


The device connected to the monitoring portal has to be defined as the master device.
The server communication method is configured by default to LAN with DHCP enabled. If a different
setting is required, follow the steps below:
1 Enter Setup mode, as described in Setup Menu Options on page 29.
4 Set the gateway as the master of the RS485 bus and perform slave detection as described in To
configure the RS485 communication bus with SolarEdge inverters/SMI: on page 21.
5 To configure the LAN to Static IP select the following in the LCD menus on the gateway:
 Communication  Server  LAN
 LAN Conf  Set DHCP  <Dis>
6 Set the IP, mask, gateway DNS, server address, and server port as necessary using the LCD User
buttons. Refer to the Ethernet Communication Configuration Options on page 36.
7 Verify the that the status field in the Server Communication Status window displays S_OK:
S e r v e r : L A N < S _ O K >
S t a t u s : < O K >

8 Exit the Setup mode.

38 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional)

Troubleshooting Ethernet Communication


The Server Communication Status window can be used to identify errors.
S e r v e r : L A N < S _ O K >
S t a t u s : < O K >
x x x x x x x x
< E r r o r M e s s a g e >

1 If S_OK is not displayed, use a method independent of the SolarEdge gateway to check whether the
network and modem are operating properly. For example, connect a laptop to the Ethernet router
and connect to the Internet.
2 xxxxxxxx is a string of 1s and 0s showing an eight-bit communication connection status. 1 indicates
OK and 0 indicates an error. The possible errors and their troubleshooting are detailed in the
following table:
Bit Error Error Description Troubleshooting
Location Message
1st LAN An Ethernet physical cable Check the cable pin-out assignment
Disconnected connection fault: The Ethernet and cable connection
link or physical Ethernet cable
are not connected properly
2nd DHCP Failed, The inverter failed to get a valid Check the router and gateway
or IP address from the DHCP configuration
Invalid DHCP server, or
Config The DHCP/static IP settings in
the gateway are not the same as
those of the router.
3rd Gateway Ping The connection to the router is Check the physical connection to the
Failed not available: Ping to the first switch/router. Check that the link LED
hop switch/router failed (LAN at the router /switch is lit (indicating
error) phy-link). If OK - contact your network
IT, otherwise replace the cable or
change it from cross to straight
connection
4th G Server Ping The connection to the Internet is Connect a laptop and check for internet
Failed not available: Ping to connection.
google.com failed If internet access is unavailable, contact
your IT admin or your internet provider.
For WIFI networks, ensure that
username and password are as defined
in the internet provider AP/router.
5th Server x Ping Ping to redundant server #x Check the SolarEdge server address,
Failed failed as described on page 27.
6th
7th
8th Tcp Connect. The connection to the SolarEdge
Failed server was not established:
Communication with the server
failed

Firefighter Gateway Installation Guide MAN-01-00113-1.3 39


Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional)

Additional Connection Options


Creating a Wireless ZigBee Connection
This communication option enables using a ZigBee wireless connection for one of the following:
 To wirelessly connect the SolarEdge gateway to other SolarEdge devices, and to the monitoring
portal through the Ethernet
 To create a master/slave bus of connected SolarEdge devices
The ZigBee kit is purchased separately and provided with a user manual, which should be reviewed prior to
connection. It is available on the SolarEdge website at
http://www.solaredge.com/groups/products/communication (under ZigBee-Home gateway).
Creating a Wi-Fi Connection
This communication option enables using a Wi-Fi connection for connecting the inverter to the SolarEdge
monitoring portal.
The Wi-Fi kit can be purchased separately and assembled during system installation. The Wi-Fi kit is
provided with a user manual, which should be reviewed prior to connection. It is available on the
SolarEdge website at http://www.solaredge.com/groups/products/communication (under Wi-Fi).

40 Firefighter Gateway Installation Guide MAN-01-00113-1.3


Appendix A: Technical Specifications

Appendix A: Technical Specifications


Power Description Units
Power Supply – DIN Rail 100–240 VAC, EU/UK/US/AU
Supply Voltage 9-14 Vdc
Connector Type terminal block
Power Consumption <2 W
Communication Interfaces Type
Ethernet Interface 10/100-BaseT

Wireless Connections ZigBee module(*), Wi-Fi(*) (**)

Fire Alarm Control Panel Alarm input, 5V, GND (***)


SolarEdge Inverters RS485
Environmental
Operating Temperatures -20 to 60 / -4 to 140 °C / °F
Protection Rating IP20 Indoor
Mechanical
Mounting Type DIN rail/ Wall mount
Dimensions (L x W x H) 161.6 x 90 x 62 / 6.36 x 3.54 x 2.44 mm / inch
Weight 0.5 / 1.1 kg / lbs
Standard Compliance
Safety UL60950-1, IEC-60950-1
EMC FCC Part 15 class B, IEC61000-6-2, IEC61000-6-3

* Sold separately. See individual product specifications for supported locations.


** EU only
***Emergency stop button is not supplied by SolarEdge

Firefighter Gateway Installation Guide MAN-01-00113-1.3 41


Appendix A: Technical Specifications

Mechanical specifications:

161.6mm/6.36 in

90mm/3.54 in

62mm/2.44 in

90mm/3.54 in

Figure 19: SolarEdge Gateway Mechanical Specifications

42 Firefighter Gateway Installation Guide MAN-01-00113-1.3

You might also like