PRESSURE TANKS

FEATURES

• Mild steel shell


• Interchangeable EPDM/Butyl membrane
• Maximum operating pressure 10 bar
(16 bar optional)
• Working temperature -10°C to 100ºC
• Suitable for drinking water applications
• Requires no maintenance

BENEFITS

• Compensates for pressure variation due


to water volume changes with
temperature variations in HVAC
Systems
• Maintains constant water flow even at
the most weak points in water supply
PRESSURE TANKS systems
• Reduces stress on hydronic system
components
• Prevents water hammering, stabilizes
pressure variation
• Reduces pump cycling

TECHNICAL DATA

Materials
Shell : MS
Membrane : EPDM/Butyl
Sizes : 24 - 5000 Liters
Pre loading pressure : 2 Bar
Max operating pressure : 10 Bar (16 Bar optional)
Working temperature : -10 °C to 100 °C
INSTALLATION AND COMMISIONING

1. Tank is generally installed at the suction side of the


pump.
2. Instal two isolation valves on either side of the tank. P2 = P1+0.5 bar
3. Install the drain valve at the bottom of the tank.
4. Install the safety valve on the pipe connecting
expansion tank to the system.
5. Close valves V1 & V2, open V3 and drain water
form the expansion tank.
6. Check standing pressure PI at the 1.
7. If the standing pressure is P1, then per-charge the
tank, though the air -valve provide, with nitrogen to Safety
0.5 bar above it, i.e. P2 = P1 + 0.5 bar. Valve Isolation
Isolation V2
V1 Valve
8. Close valve V3 and open valves V1 and V2. 1 Valve
N

System Check Valve Make-up


Connection Water
V3 Drain Valve Connection

DIMENSIONS
All dimensions are in mm

MODEL CAPACITY Conn. Approx.


H h D Weight
TYPE Litres Size (C)
Kgs. (empty)

CET 24 24 1” 470 - 280 5


C
CET 50 50 1” 420 180 409 10

CET 100 100 1” 720 250 480 20

CET 300 300 11 4 ” 980 250 634 50

CET 500 500 11 4 ” 1250 300 740 80

CET 750 750 2” 1650 300 740 130

CET 1000 1000 2” 1900 300 800 200


H
CET 1500 1500 2” 2100 300 960 250

CET 2000 2000 2” 1900 300 1200 600

CET 3000 3000 2” 1700 300 1500 900


h C
CET 4000 4000 2” 2550 300 1500 1200

CET 5000 5000 2” 3250 300 1500 1500


06/11

Subject to technical alteration