Solcon Istart Manual 2
Solcon Istart Manual 2
iStart
This manual must be read thoroughly and
always stored near the softstarter.
II
Table of contents
4. Installation ....................................................................................................... 28
20160415_Rev03 III
4.1 Prior to Installation ................................................................................ 28
4.2 Mounting............................................................................................... 28
4.3 Temperature Range & Heat Dissipation ............................................... 30
4.3.1 Calculating the Enclosure Size, for Non-Ventilated Metallic Enclosure 31
4.3.2 Additional Ventilation ............................................................................ 31
4.4 Installing an Option Card ...................................................................... 32
4.4.1 Preinstallation Instructions for Installing an Option Card ...................... 32
4.4.2 Opening the Control Panel ................................................................... 32
4.4.3 Removing the Connector Cover ........................................................... 32
4.4.4 Inserting the Option Card and Closing the Unit .................................... 33
4.5 Setting the Thermistor In and Analog Out Option Card (Option 5) ....... 35
4.6 Setting the Analog Option – 3XRTD Thermal Sensor Option Card
(Option 6) ............................................................................................. 36
4.7 PT100 [C°/Ω] Table .............................................................................. 38
IV 20160415_Rev03
5.6.4 Fault Parameters – Page 3 of Basic (
page 5 of Professional and page 7 of Expert) ...................................... 68
5.6.5 AUTORESET PARAMS – Page 4 of Basic
(page 6 of Professional and page 8 Expert) ......................................... 75
5.6.6 I/O Programming Parameters – Page 5 of Basic
(7 of Professional and 9 of Expert) ....................................................... 77
5.6.7 Global Parameter ................................................................................. 81
5.6.8 Statistical Data – page 11..................................................................... 82
5.7 Event Logger – page 8 for Basic
(page 11 for Professional, page 12 for Expert) ..................................... 83
5.7.1 Event Summary .................................................................................... 83
5.7.2 Event Details ........................................................................................ 85
5.8 Actual Data View .................................................................................. 86
5.8.1 Default Data View ................................................................................. 86
7. Communication ............................................................................................... 94
20160415_Rev03 V
7.3.2 Start Parameters (First Adjust) ........................................................... 107
7.3.3 Stop Parameters (First Adjust) ........................................................... 108
7.3.4 Special Features Parameters ............................................................. 109
7.3.5 Fault Parameters ................................................................................ 109
7.3.6 Auto Reset Parameters ...................................................................... 111
7.3.7 I/O Programming Parameters ............................................................. 113
7.3.8 Global Parameters.............................................................................. 119
7.3.9 Communication Parameters ............................................................... 120
7.3.10 Example 2: Read Setting Parameters ................................................ 122
7.3.11 Example 3: Write a Single Setting Parameter .................................... 123
7.3.12 Example 4: Write Multiple Setting Parameters ................................... 125
7.4 Control Register Write (Write Word Register) ..................................... 126
7.4.1 Example 5 - Control Register Write .................................................... 127
7.5 Diagnostics ......................................................................................... 129
7.6 Exception Responses ......................................................................... 130
7.6.1 Exception Code Response Frame ...................................................... 130
7.6.2 Exception Codes Supported by the iStart........................................... 130
7.6.3 Example 6: Exception Response ........................................................ 131
7.7 Profibus Communication .................................................................... 133
7.7.1 Global Parameters.............................................................................. 133
7.7.2 Operation Mode in Profibus ................................................................ 133
7.7.3 Description of the DPV0 (Cyclic) Frame ............................................. 134
7.7.4 Operations that are Available in DPV1 ............................................... 139
7.7.5 Configure PROFIBUS in the iStart...................................................... 141
7.7.6 Watch Dog Definition .......................................................................... 141
7.7.7 Actual Data Register Numbers (Decimal) ........................................... 142
7.7.8 Default Order of Register Numbers .................................................... 147
7.7.9 Setting Parameters for Data Request ................................................. 148
VI 20160415_Rev03
8. Installing a Fan on Size A, B and C ............................................................. 153
20160415_Rev03 VII
VIII
Safty & Warnings
1.1 Safety
1.2 Attention
20160415_Rev03 9 / 180
Safty & Warnings
1.3 Warnings
10 / 180 20160415_Rev03
Product Presentation
2. Product Presentation
2.1 Introduction
The iStart is a highly sophisticated and reliable three -phase starter.
It can operate both three phase and two-phase mode. iStart is de-
signed for simple maintenance and maximum flexibility in the field.
You can connect motors with different mains voltages to
iStart:
Frame size A, B and C: 208V to 400V
208V to 600V
20160415_Rev03 11 / 180
Product Presentation
Select the starter according to motor's Full Load Ampere (FLA) that is
indicated on its nameplate (even if the motor will not be fully loaded).
The iStart is designed to operate under the following maximum con-
ditions:
12 / 180 20160415_Rev03
Product Presentation
40 400%xIn 30
50 350%xIn 20
Note:
For very frequent starts (inching applications) the inching current
should be considered as the Full Load Current (FLC) (consult factory).
20160415_Rev03 13 / 180
Product Presentation
D to I 208V to 400V,
50/60Hz, +10% -
15% Fan is required
14 / 180 20160415_Rev03
Recommended Wiring Scheme
20160415_Rev03 15 / 180
Recommended Wiring Scheme
Terminal 22 (NC) Programmable aux- Same as terminals 12, 11, and 14 for relay 2.
iliary output relay 2
Terminal 21 (C)
Terminal 24 (NC)
Terminal 1,2,3 24V Input – START The terminals can be programmed to operate
command. in the following modes:
INACTIVE
START
STOP
EXTERNAL TRIP
RESET
1ST ADJUST START
Start command to the 1st motor.
2ND ADJUST START
Start command to the 2nd motor.
3RD ADJUST START
Start command to the 3rd motor.
4TH ADJUST START
Start command to the 4th motor.
1ST ADJUST STOP
Soft Stop command to the 1st motor.
2ND ADJUST STOP
Soft Stop command to the 2nd motor.
3RD ADJUST STOP
Soft Stop command to the 3rd motor.
4TH ADJUST STOP
Soft Stop command to the 4th motor.
16 / 180 20160415_Rev03
Recommended Wiring Scheme
20160415_Rev03 17 / 180
Recommended Wiring Scheme
Notes:
1. Use fuses for type 2 coordination. Mains voltage of 208-
600V available to all models. Mains voltage 208-690V
available to 210-1100A.
2. Refer to ordering information for available control voltages.
3. Control inputs are shown in their default setting.
4. Applicable only when optional fans are installed in frame
sizes A-C.
18 / 180 20160415_Rev03
Recommended Wiring Scheme
Notes:
6. Use fuses for type 2 coordination. Refer to section
7. Mains voltage of 208-600V available to all models. Mains
voltage 208-690V available to 210-1100A.
8. Refer to ordering information for available control voltages.
9. Control inputs are shown in their default setting.
10. Applicable only when optional fans are installed in frame
sizes A-C.
20160415_Rev03 19 / 180
Recommended Wiring Scheme
20 / 180 20160415_Rev03
Recommended Wiring Scheme
Notes:
When installing the iStart INSIDE DELTA. it is highly recommended
to use a line contactor (C1) or contactor (C2) in order to avoid a
de-struction of the motor in case of a shorted SCR in the iStart.
If a contactor is connected Inside the Delta (C2) only, motor terminals
are „live” (full voltage) even when contactor is open.
20160415_Rev03 21 / 180
Recommended Wiring Scheme
22 / 180 20160415_Rev03
Recommended Wiring Scheme
Thermal Inputs
The iStart can accept inputs from the RTD - Platinum 100 Ohm
(Pt100) type of thermal sensors. This is a three-wire measurement
system that is used to compensate for cable resistance.
Notes:
11. AWG#18 wires must be used. Do not exceed the maxi-
mum length of 100m.
12. Shielded cables must be used. Connect shield to external
ground.
13. For RTD, the maximum cable resistance allowed is 25
Ohm.
14. LCD displays temperature in degrees Celsius for RTD.
15. If one or more sensors are not used, leave the relevant
terminals open.
The Actual Data display for this sensors will be “---“ (Three
dashes).
20160415_Rev03 23 / 180
Recommended Wiring Scheme
General Information
When the iStart is installed „Inside Delta”, the individual phases of
the Starter are connected in series with the individual motor windings
(6 conductor connections as with the star-delta starter). The soft starter
must only conduct about 67 % (=1\1.5) of the rated motor current. This
ensures the use of a significantly smaller device.
For example:
For a motor with a rated current of 1050A motor, a 1100A starter will
be selected to operate „In-Line”. For „Inside Delta” starter, we calcu-
late (1050 x 67% = 703A) and select a 720A starter.
Less heat dissipates in the cabinet vs. the standard „In-Line” connec-
tion.
24 / 180 20160415_Rev03
Recommended Wiring Scheme
Note :
For a high starting torque process, it is recommended to use the starter
in the „In Line” connection.
20160415_Rev03 25 / 180
Recommended Wiring Scheme
Beware!
26 / 180 20160415_Rev03
Recommended Wiring Scheme
1. C1 is a line contactor.
2. C2 is an „Inside Delta” contactor.
3. U1-U2, V1-V2, W1-W2 are motor’s windings.
4. L1-U, L2-V, L3-W are iStart controlled phases.
Note:
Motor terminals are marked as follows:
T1 - T4 A1-A2 U-X U1 - U2
T2 - T5 B1-B2 V-Y V1 - V2
T3 - T6 C1-C2 W-Z W1 - W2
20160415_Rev03 27 / 180
Installation
4. Installation
4.2 Mounting
The starter must be mounted vertically. Allow sufficient space (at least
100mm) above and below the starter for suitable airflow.
It is recommended to mount the starter directly on the rear metal plate
for better heat dissipation.
28 / 176 20160415_Rev03
Installation
Note:
Do not mount the iStart directly on the rear metal plate in case a
ventilation fan or ventilation opening is on the back side of the iStart.
Do not mount the starter near heat sources.
Surrounding air temperature in the cabinet should not exceed 50ºC.
Protect the starter from dust and corrosive atmospheres.
Note:
For harsh environments (sewage treatment plants, etc.), it is recom-
mended to order the starter with printed circuit board coating. Remote
Keypad Installation
20160415_Rev03 29 / 180
Installation
Starter’s heat dissipation while motor is running and the internal by-
pass relays are closed is typically less than 0.4 x In (in watts). During
soft start and soft stop, heating is approximately three times the actual
starting current (In watts).
30 / 180 20160415_Rev03
Installation
Important note:
If motor is frequently started, cabinet should be designed for the higher
heat dissipation.
Internal enclosure heating can be reduced through the use of addi-
tional ventilation.
Where: Area [m2]] - Surface area that can dissipate heat (front, sides,
top).
Total heat dissipation [Watt] – The total heat dissipation of the
starter and other control devices in the enclosure. If starter is fre-
quently started, average power should be used.
Fan Air
Air Outlet
Inlet
SST
Air
Inlet
20160415_Rev03 31 / 180
Installation
Step 1: Remove the 4 screws that hold the plastic housing of the
iStart control panel to the power unit.
Step 2: Ground yourself with ESD protection.
Step 3: Remove the 6 screws that hold the PCB card to the plastic
housing of the control panel.
Before you insert the option card, you must cut off the part of the hous-
ing that covers option card connections. For analog cards, cut off the
covering at the top of the plastic housing. For communication cards,
cut off the covering at the bottom of the plastic housing.
32 / 180 20160415_Rev03
Installation
20160415_Rev03 33 / 180
Installation
Step 10: Reconnect all cables and connectors that you removed.
Step 11: Add the connections to the relevant option card. Option
Card Connections
34 / 180 20160415_Rev03
Installation
Voltage (0 – 10V)
Step 3: Make sure that control power and mains voltage are off.
Step 4: Install the analog card.
Step 5: Set the parameters:
20160415_Rev03 35 / 180
Installation
19. Turn on control power, press the DATA key once, followed
by the down key.
This will take you to the following menu:
ANALOG OPTION
THERMISTOR IN-
PUT
21. Select the desired analog ouput. The next parameter will
be the CURRENT RANGE.
22. Set the CURRENT RANGE. The options are:
23. 0-20mA
24. 4-20mA
Important: When using the card in VOLTAGE mode, you must set
this parameter to 0-20mA.
25. The next parameter is THERMISTOR TYPE. Set the PTC
(default) or NTC.
26. The next parameter is LIMIT RESISTANCE. If the re-
sistance exceeds the max/min resistance defined, the
iStart will trip.
You can set this parameter from 100 Ohm to 30000 Ohm.
36 / 180 20160415_Rev03
Installation
Step 3: Turn on control power, press the DATA key once, followed
by the down key. This will take you to the following menu:
ANALOG OPTION
TEMP.RELAY-3IN
Step 4: Press ENTER.
This will take you to the following menu:
MAX TEMPERA-
TURE
120 C
Step 5: Set the maximum temperature. This parameter determines
the maximum measured temperature allowed. If the temperature
ex-ceeds the max/min temperature defined, the iStart will trip You
can set this parameter from -20°C to 200°C.
Step 6: Connect the PT100 between P1.1 and P1.2, and connect
P1.2 and P1.3 without any resistance (short-circuit). If P2 and P3 are
in use, do the same for them.
Step 7: In order to see the RTD reading, press DATA and use the
arrows until you see the RTD TEMPERATUR screen as in the exam-
ple below:
<RTD TEMPERATUR>
<54C 54C 54C>
If all three inputs are not connected, the missing sensor(s) will dis-
play as --- as in the example below:
<RTD TEMPERATUR>
<--- --- 54C>
20160415_Rev03 37 / 180
Installation
−5 98.04 85 132.8
0 100 90 134.7
5 101.95 95 136.6
35 113.61
38 / 180 20160415_Rev03
Settings – Control Keypad
The control keypad is the link between the iStart and the user.
The iStart control keypad features:
1. Indication LEDs (On, Ramp, Run, Fault, Comm)
2. Two lines of 16 alphanumeric characters each with selectable languages –
English, French, German, Spanish and Turkish. Russian and Chinese charac-
ters are optional and must be pre-ordered. By default the display shows actual
data.
3. Push-buttons (esc, reset, mode, store, ok, up (▲) and down (▼) keys).
1.
2.
3.
20160415_Rev03 39 / 180
Settings – Control Keypad
5.2 Push-Buttons
Table 6 Control elements
Exits the current menu and returns to the previous menu without
Esc
save.
Toggles between the view of actual data and parameter settings.
Actual data appears inside arrow brackets as shown below.
< Actual Data Type >
Data
< Actual Data Value >
Parameters are shown without arrow brackets. After a one mi-
nute timeout, the display returns to the actual data view.
Scrolls to the previous menu.
Allows the operator to increment adjusted values shown in the
▲ display.
Press this button once to increment one value, or continuously to
rapidly increment values up to the maximum value.
Allows the operator to decrement adjusted values shown in the
display.
▼
Press this button once to decrement one value, or continuously
to rapidly decrement values up to the minimum value.
When a menu name is displayed, pressing this button drills
down to the parameters for that menu.
When a parameter is displayed, pressing this button makes the
Enter parameter value editable (value blinks). Use the up/down arrows
to change the value.
When the parameter value blinks, pressing Enter saves the pa-
rameter value.
Resets the iStart after a fault has been dealt with and the start
command has been removed (except for UNDERCURR. TRIP).
Reset
This cancels the fault displayed and allows you to restart the mo-
tor.
40 / 180 20160415_Rev03
Settings – Control Keypad
20160415_Rev03 41 / 180
Settings – Control Keypad
Press the Data key to toggle from actual data view to the pa-
rameter menus.
Press Esc twice to get to the Main Parameters menu.
Press and hold the ▼ key until you reach the last menu
(TEST/MAINTENANCE).The LCD will display:
TEST/MAINTENANCE
- **** -
Press the Data key to toggle from actual data view to the pa-
rameter menus.
Press Esc twice to get to the Main Parameters menu.
Press and hold the ▼ key until you reach the last menu
(TEST/MAINTENANCE).The LCD will display:
TEST/MAINTENANCE
- **** -
Press Enter.
Use the ▼ key to navigate to the RESET SETTING!!! menu.
The LCD will display:
RESET SETTING!!!
ENTER TO DEFAULT
Press Enter to enter the menu. The LCD will display
RESET SETTING!!!
* * * N O * * *
Press the ▲ key. The LCD will display:
RESET SETTING!!!
* * * Y E S * * *
Press Enter. For a short interval, the LCD will display:
42 / 180 20160415_Rev03
Settings – Control Keypad
Press the Data key to toggle from actual data view to the pa-
rameter menus.
Press Esc twice to get to the Main Parameters menu.
Press the ▼ key until you reach the STATISTICAL DATA
menu. The LCD will display:
STATISTICAL DATA
- **** -
Press Enter.
Use the ▼ key to navigate to the RESET STATISTICS!!! menu.
The LCD will display:
RESET STATISTICS
ENTER TO RESET
Press Enter to enter the menu. The LCD will display:
RESET SETTING!!!
* * * N O * * *
Press the ▲ key. The LCD will display:
RESET SETTING!!!
* * * Y E S * * *
Press Enter. For a short interval, the LCD will display:
RESET STATISTICS
SETTING DEFAULT
20160415_Rev03 43 / 180
Settings – Control Keypad
44 / 180 20160415_Rev03
Settings – Control Keypad
20160415_Rev03 45 / 180
Settings – Control Keypad
GLOBAL
FAULT PA- AUTORESET I/O PRO- COMM. PA-
PARAME- STATISTICAL
RAMETERS PARAMS GRAMMING RAMETERS
TER DATA*** -
- **** - - **** - - **** - - **** -
- **** -
Display
Display Display and Display and Display and
and Display and
and default default va- default va- default va-
default default values
values lues lues lues
values
HS OVR GLOBAL AU- IN1 PRO-
PROTOCOL SET TIME TOTAL ENERGY
TMP TORESET GRAMMING
MODBUS 00:00:00
TRIP DISABLE ALL STOP
SHORT HS OVR TMP IN1 STATE LAST STRT PE-
BAUD RATE SET DATE
CIRC A.RESET DIS- MAINTAIN RIOD
115200 BPS 01/01/2000
IGNORE ABLE OPEN
DEFAULT
SHORT CIR IN1 MIN AC-
OVERLOAD STOP BIT DATA LAST STRT MAX I
A.RESET DIS- TIVE
TRIP 1.0 BITS V/I/COS
ABLE 0.1 SEC
PHI
UNDER OVERLOAD IN1 MIN INAC- PARITY LCD CON-
TOTAL RUN TIME
CURR A.RESET DIS- TIVE CHECK TRAST
TRIP ABLE 0.1 SEC NONE [********]
UNDER
UNDER IN2 PRO- LCD IN-
CURR SERIAL LINK TOTAL # OF STRTS
VOLT GRAMMING TENSITY
A.RESET DIS- NO.
TRIP SOFT STOP [********]
ABLE
UNDER VOLT IN2 STATE COM
OVER VOLT LAST TRIP
A.RESET MAINTAIN CHANGE
TRIP
DISABLE OPEN PARAM
PHASE OVER VOLT IN2 MIN AC- CMD VIA
TRIP CURRENT
LOSS A.RESET DIS- TIVE COMM
TRIP ABLE 0.1 SEC NO
PHASE LOSS IN2 MIN INAC- CMD VALID
PHASE SEQ
A.RESET DIS- TIVE FOR TOTAL # OF TRIPS
TRIP
ABLE 0.1 SEC 1.0 SEC
SHORTED PHASE SEQ IN3 PRO- RESET CMD
SCR A.RESET DIS- GRAMMING VALID PREVIOUS TRIP -1
TRIP ABLE START NO
LNG STRT SHORT SCR IN3 STATE COMM
TM A.RESET DIS- MAINTAIN TIMEOUT PREVIOUS TRIP -2
TRIP ABLE CLOSE 10.0SEC
LNG STRT UPD COMM
SLOW SPD IN3 MIN AC-
TM STEPS
TM TIVE PREVIOUS TRIP -3
A.RESET DIS- 1ST ACK
TRIP 0.1 SEC
ABLE THEN UPD
SLW SPD TM IN3 MIN INAC-
COMM T/O
A.RESET DIS- TIVE PREVIOUS TRIP -4
TRIP
ABLE 0.1 SEC
COMM T/O
EXT FAULT INPUT POLICY
A.RESET DIS- PREVIOUS TRIP -5
TRIP VIA PRIORITY
ABLE
INPUT PRIOR-
WRNG EXT FAULT
ITY
PARAMS A.RESET DIS- PREVIOUS TRIP -6
IN1,IN2,IN3,C
TRIP ABLE
OM
COMM
WRNG RLY1 ACTION
FAILED PREVIOUS TRIP -7
PARAMS FAULT
TRIP
46 / 180 20160415_Rev03
Settings – Control Keypad
A.RESET DIS-
ABLE
COMM RLY1 ON
TOO MANY FAILED STATE
PREVIOUS TRIP -8
TRIP A.RESET DIS- ON=NO /
ABLE OFF=NC
TOO MANY RLY1 ON DE-
MTOR INSUL
A.RESET DIS- LAY PREVIOUS TRIP -9
TRIP
ABLE 0.0 SEC
MTOR INSUL RLY1 OFF DE-
M OVR TMP RESET STATISTI-
A.RESET DIS- LAY
TRIP CAL DATA
ABLE 0.0 SEC
WRONG M OVR TMP
RLY2 ACTION
FREQ A.RESET DIS-
END OF ACC
TRIP ABLE
WRONG RLY2 ON
M.UNBAL-
FREQ STATE
ANCE
A.RESET DIS- ON=NO /
TRIP
ABLE OFF=NC
NO VOLTAGE RLY2 ON DE-
GND FAULT
A.RESET DIS- LAY
TRIP
ABLE 0.0 SEC
M.UNBAL-
NO CUR- RLY2 OFF DE-
ANCE
RENT LAY
A.RESET DIS-
TRIP 0.0 SEC
ABLE
NO CTR GND FAULT
PWR A.RESET DIS-
TRIP ABLE
NO CUR-
OVER CURR RENT
TRIP A.RESET DIS-
ABLE
NO CTR PWR
SHEAR PIN
A.RESET DIS-
TRIP
ABLE
OVER CURR
A.RESET DIS-
ABLE
SHEAR PIN
A.RESET DIS-
ABLE
20160415_Rev03 47 / 180
Settings – Control Keypad
MAIN PARAME-
TERS
- **** -
Display and de-
Range Description Remarks
fault values
SPANISH
GERMAN
SET LAN- FRENCH
GUAGE: Sets Starter’s
ENGLISH
ENGLISH language
TURKCE
RUSSIAN (Op-
tional)
Displays the
STARTER FLC
N/A FLC (Full load This parameter is not configurable.
44 AMP
current)
Factory preset – features and functions
when „INSIDE DELTA” mode is config-
Sets Starter’s ured:
CONNECTION LINE, INSIDE connection No Pulse Start.
TYPE
DELTA type. No Curve selection (CURVE 0!!).
LINE
No slow speed.
No phase sequence „off” mode.
48 / 180 20160415_Rev03
Settings – Control Keypad
100%-400%
Note:
The range of Operational during run time only.
Sets OVER-
the INITIAL Note:
O/C SHEAR PIN CURRENT
VOLTAGE can This protection is not intended to replace
400% FLA SHEAR PIN
be extended to fast acting fusser to protect from short
protection.
850% by using current!
the EXTEND
SETTING.
UNDER CUR- Sets minimum Operational during run time only.
RENT 0%-90% allowed cur- If the current drops to this level a trip will
20 % FLA rent. occur.
Sets OVERLOAD CLASS characteristics
Sets OVERLOAD PROTECT functional-
ity.
IEC CLASS 5/
The iStart allows motor protection ac-
IEC CLASS 10/
cording to IEC class 5 or 10 or according
IEC CLASS 20/
to NEMA class 10, 20 or 30.
IEC CLASS 30/
Tripping curves are shown in section
NEMA CLASS
5.5.1on page 42ff.The OVERLOAD pro-
OVERLOAD 5/
Sets OVER- tection incorporates a THERMAL CA-
CLASS NEMA CLASS
LOAD curve. PACITY register that calculates heating
IEC CLASS 10 10/
minus dissipation of the motor.
NEMA CLASS
The iStart trips when the register fills up.
20/
(THERMAL CAPACITY=100%)
NEMA CLASS
The time constant, in seconds, for cool
30/
down after overload trip is:
Class 10 20 30
IEC 320 640 -
NEMA 280 560 840
The overload protection can be set to
protect the motor as set in the OVER-
LOAD PROTECT parameter:
DISABLE/
OVERLOAD ENABLE ALWAYS – motor is protected
ENABLE
PROTECT at all time.
WHILE RUN/
DISABALE ENABLE WHILE RUN – motor is pro-
ENABLE AL-
tected only when in Run.
WAYS
DISABLE – motor is not overload pro-
tected by the soft starter.
Note:
20160415_Rev03 49 / 180
Settings – Control Keypad
50 / 180 20160415_Rev03
Settings – Control Keypad
Then if the starter’s current is 450% of FLA, then the multiple of pickup
current will be :
450%FLA / 150%FLA = 3.
According to the “U1 Curves” chart below – with Time Dial of 8.00 and
multiple of pickup of 3 – the O/C trip will occur after 4 seconds.
20160415_Rev03 51 / 180
Settings – Control Keypad
U1 Curves
10
TD = 15.00
Time [Sec]
TD = 12.00
1 TD = 10.00
TD = 8.00
TD = 6.00
TD = 5.00
TD = 4.00
0,1 TD = 3.00
TD = 2.00
TD = 1.00
TD = 0.50
0,01
1 10 100
Multiples of Pickup
Figure 16 U.S. Class OVERCURRENT curves – U1 curves
U2 Curves
100
10 TD = 15.00
TD = 12.00
Time [Sec]
TD = 10.00
TD = 8.00
1 TD = 6.00
TD = 5.00
TD = 4.00
TD = 3.00
0,1 TD = 2.00
TD = 1.00
TD = 0.50
0,01
1 10 100
Multiples of Pickup
Figure 17 U.S. Class OVERCURRENT curves – U2 curves
52 / 180 20160415_Rev03
Settings – Control Keypad
U3 Curves
100
TD =
10 15.00
Time [Sec]
TD =
12.00
TD =
1
10.00
TD = 8.00
0,1 TD = 6.00
0,01
1 10 100
Multiples of Pickup
Figure 18 U.S. Class OVERCURRENT curves – U3 curves
100
U4 Curves
TD = 15.00
TD = 12.00
10 TD = 10.00
Time [Sec]
TD = 8.00
TD = 6.00
TD = 5.00
1
TD = 4.00
TD = 3.00
TD = 2.00
0,1 TD = 1.00
TD = 0.50
0,01
1 10 100
Multiples of Pickup
20160415_Rev03 53 / 180
Settings – Control Keypad
U5 Curves
10
Time [Sec]
TD = 15.00
1 TD = 12.00
TD = 10.00
TD = 8.00
TD = 6.00
TD = 5.00
0,1 TD = 4.00
TD = 3.00
TD = 2.00
TD = 1.00
TD = 0.50
0,01
1 10 100
Multiples of Pickup
Figure 20 U.S. Class OVERCURRENT curves – U5 curves
C1 Curves
10
TD = 15.00
Time [Sec]
TD = 12.00
1 TD = 10.00
TD = 8.00
TD = 6.00
TD = 5.00
TD = 4.00
0,1 TD = 3.00
TD = 2.00
TD = 1.00
TD = 0.50
0,01
1 10 100
Multiples of Pickup
Figure 21 IEC Class OVERCURRENT curves – C1 curves
54 / 180 20160415_Rev03
Settings – Control Keypad
C2 Curves
10
Time [Sec]
TD =
1 15.00
TD =
12.00
0,1 TD =
10.00
TD = 8.00
0,01 TD = 6.00
0,001
1 10 100
Multiples of Pickup
Figure 22 IEC Class OVERCURRENT curves – C2 curves
100
C3 Curves
10
TD =
Time [Sec]
1 15.00
TD =
0,1 12.00
TD =
10.00
0,01
TD =
8.00
0,001 TD =
6.00
0,0001
1 10 100
Multiples of Pickup
Figure 23 IEC Class OVERCURRENT curves – C3 curves
20160415_Rev03 55 / 180
Settings – Control Keypad
1000
C4 Curves
100
TD =
15.00
Time [Sec]
10 TD =
12.00
TD =
1 10.00
TD = 8.00
0,1 TD = 6.00
0,01
1 10 100
Multiples of Pickup
Figure 24 IEC Class OVERCURRENT curves – C4 curves
10
C5 Curves
Time [Sec]
TD =
1 15.00
TD =
12.00
TD =
10.00
0,1 TD =
8.00
TD =
6.00
0,01
1 10 100
Multiples of Pickup
Figure 25 IEC Class OVERCURRENT curves – C5 curves
56 / 180 20160415_Rev03
Settings – Control Keypad
Time [sec.]
1000
1000
100
Cold 100
10
Cold
10
1
Hot Hot
0.1 1
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
Current [I/FLA]
Current [I/FLA]
10000 10000
1000 1000
10 10
Hot
Hot
1 1
0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8
Current [I/FLA] Current [I/FLA]
10000 10000
1000 1000
Cold
100 Cold 100
10 10
Hot Hot
1 1
0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8
Current [I/FLA] Current [I/FLA]
20160415_Rev03 57 / 180
Settings – Control Keypad
START/STOP
MOTOR
Display and
Range Description Remarks
default values
Should be programmed as shown
on the motor’s name plate.
Sets iStart's
MOTOR FLA 50%-100% of Note:
FLA (Full Load
44 AMP STARTER FLC When the iStart is installed Inside
Ampere)
Delta, set MOTOR FLA = <rated
motor current>/1.73.
9 !! - DOL - !!
5 !! TORQUE !!
4 !! PUMP 3 !!
SOFT START Sets starter’s
3 !! PUMP 2 !! When iStart is connected „Inside-
CURVE SOFT START
2 !! PUMP 1 !! Delta”, only CURVE 1 is applied.
1(STANDARD) CURVE.
1 – STANDARD -
0 !! GENERA-
TOR !!
CURRENT
PULSE E.
PULSE TYPE VOLTAGE
Expert only.
PULSE DISABLE PULSE E.
VOLTAGE
DISABLE
PULSE VOLT 50-99% RATED
Expert only.
0% RATED VOLT VOLT
PULSE CURRENT 0-700% FLA Expert only.
0% FLA
PULSE RISE TIME
0 – 5.0 SEC. Expert only.
0.1 SEC
Expert only.
Sets starter’s Intended to start high friction loads,
PULSE START requiring high starting torque for a
PULSE CONST TIME. short time.
TIME 0 – 10.0 SEC.
PULSE START Note:
0.0 SEC
level is 80% When iStart is connected „Inside-
Un. Delta”, PULSE START can not be
activated.
PULSE FALL TIME
0 – 5.0 SEC. Expert only.
0.1 SEC
58 / 180 20160415_Rev03
Settings – Control Keypad
20160415_Rev03 59 / 180
Settings – Control Keypad
1-30sec.
Note:
Sets ACCEL-
ACCELERATE Range can be ex-
ERATION
TIME tended to 1-
TIME of the
10 SEC 90sec. by using
motor. Notes:
the EXTEND
SETTING. Since CURRENT LIMIT overrides
ACCELERATE TIME, when CUR-
RENT LIMIT is set low, starting
time will be longer than the preset
ACCELERATE TIME.
When motor reaches full speed be-
fore voltage reaches nominal, AC-
CELERATE TIME setting is overrid-
den, causing voltage to quickly
ramp-up to nominal.
Using starting curves 2, 3, 4 pre-
vents quick ramp up.
The maximum allowable start time,
1-30sec. from Start signal to end of accelera-
Note: tion process. If voltage does not
Range can be ex- Sets MAXI- reach full voltage/speed during this
MAX START TIME tended to 1- MUM START time (e.g. because of too low CUR-
30 SEC
250sec.by using TIME RENT LIMIT setting), the starter will
the EXTEND trip the motor.
SETTING. LCD displays „LONG START
TIME” message.
60 / 180 20160415_Rev03
Settings – Control Keypad
9 !! - DOL - !!
5 !! TORQUE !!
4 !! PUMP 3 !!
SOFT STOP Sets starter’s
3 !! PUMP 2 !!
CURVE SOFT STOP .
2 !! PUMP 1 !!
1(STANDARD) CURVE.
1 – STANDARD -
0 !! GENERA-
TOR !!
Used for controlled deceleration of
high friction loads. Determines mo-
0 – 30sec. tor’s voltage ramp down time.
Note: Sets DECEL-
DECELERATE Range can be ex- ERATION
TIME
tended to 90sec. TIME of the
30 SEC
by using the EX- motor.
TEND SETTING.
Sets FINAL
STOP FINAL TORQUE
TORQUE 0(MIN) - 10(MAX)
during Soft
0 (MIN)
Stop.
20160415_Rev03 61 / 180
Settings – Control Keypad
62 / 180 20160415_Rev03
Settings – Control Keypad
Start Curve 9 (DOL) – Direct Online closes the bypass and connects
the motor directly.
Note:
Always start with Start Curve 1. If towards end of acceleration, peak
torque is too high (pressure is too high), proceed to Curve 2, 3, 4 or 5.
20160415_Rev03l 63 / 180
Settings – Control Keypad
the speed, thus correct control of voltage reduction reduces torque ad-
equately to smoothly decelerate to a stop.
Note:
It is recommended that you use Stop Curve 1 for all standard applica-
tions (not pumps).
To reduce Water Hammer, select STOP CURVE 2, than 3 or 4.
Curve 9 (DOL) – Direct Online closes the bypass and connects the
motor directly.
64 / 180 20160415_Rev03
Settings – Control Keypad
SPECIAL FEA-
TURES PARAME-
TERS
Display and
Range Description Remarks
default values
SLOW SPEED Sets SLOW
1(MIN) –
TORQ SPEED TOR-
10(MAX)
0 MIN QUE.
1–30sec. Note:
Note: When iStart is con-
Sets maximum
Range can be nected „Inside-Delta”
time for SLOW
MAX SLOW TIME extended to SLOW SPEED
SPEED
30 SEC 250sec. by us- TORQUE is not
TORQUE opera-
ing the EX- available.
tion.
TEND SET-
TING.
SAVING ADJUST YES/
NO NO
For use in very special
occurrences.
Do not set to ENABLE
EXTEND Enables wider
DISABLE/ unless starter is signifi-
SETTING range of parame-
ENABLE cantly larger then mo-
DISABLE ter settings.
tor!
See the detailed explana-
tion on the next page.
3 PHASE
If there is a problem with
START
one of the phases, you
IGNOR PHASE
can short-circuit the prob-
3 OR 2 PHASE 1 Defines which
lematic phase and set
3 PHASE START IGNOR PHASE phases to use.
iStart to ignore that
2
phase (operate in 2-
IGNOR PHASE
phase mode).
3
20160415_Rev03 65 / 180
Settings – Control Keypad
Extend Setting
Notes:
1. See PHASE LOSS protection and refer to the warning below.
2. See O/C or WRONG CON protection.
3. In order to avoid OVERLOAD TRIP in special cases (very high inertia
loads), where at the end of the acceleration process, although motor is
at full voltage (the Run LED is lit) and the current does not reduce to
nominal, set EXTEND SETTING to ENABLE causing the OVERLOAD
TRIP to be active only afterMAX. START TIME has elapsed.
66 / 180 20160415_Rev03
Settings – Control Keypad
28.
2 Phase Operation
To move to 2 phase operation, you must perform the following actions:
Short between mains and the motor the phase that you want to
short as follows:
20160415_Rev03 67 / 180
Settings – Control Keypad
FAULT PARAME-
TERS
- **** -
Display and
Range Description
Default Values
IGNORE
This parameter determines what to do if the tempera-
HS OVR TMP FLT TRIP
ture of the heat sink in the iStart exceeds the maxi-
TRIP WARNING
mum allowed.
TRIP + WARNING
HS OVR TMP DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
HS OVR TMP
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
SHORT CIRC FLT TRIP This parameter determines what to do if there is a
IGNORE WARNING short circuit.
TRIP + WARNING
SHORT CIRC DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
SHORT CIRC
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
OVERLOAD FLT TRIP This parameter determines what to do if there is an
TRIP WARNING overload.
TRIP + WARNING
OVERLOAD DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
OVERLOAD AFTR
0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
UNDER CURR FLT TRIP This parameter determines what to do if there is an
TRIP WARNING under current state.
TRIP + WARNING
UNDER CURR DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
5.0 SEC
UNDER CURR
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
68 / 180 20160415_Rev03
Settings – Control Keypad
IGNORE
UNDER VOLT FLT TRIP This parameter determines what to do if there is an
TRIP WARNING under volt state.
TRIP + WARNING
UNDER VOLT DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
5.0 SEC
UNDER VOLT
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
OVER VOLT FLT TRIP This parameter determines what to do if there is an
TRIP WARNING over volt state.
TRIP + WARNING
OVER VOLT DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
OVER VOLT AFTR
0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
This parameter determines what to do if 1 or 2 phases
are missing.
Notes:
If iStart trips on PHASE LOSS do the following:
(1) Verify that phase voltages are within the re-
quired range of the voltages.
(2) If you are sure that no real phase loss exists,
IGNORE
you can set PHASE LOSS to WARNING or IGNORE.
PHASE LOSS FLT TRIP This situation can occur in rare cases when there is
TRIP WARNING no real fault but the iStart recognizes unusual be-
TRIP + WARNING haviour like when Total Harmonic Distortion in Volt-
age (THDV) in the network is high.
(3) If this is a true case of PHASE LOSS, then after
setting PHASE LOSS to WARNING or IGNORE, the
motor will single phase and most likely be tripped by
the over load protection mechanism.
(4) Phase loss might not be detected in a motor
oper-ating under a light load.
PHASE LOSS DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
PHASE LOSS
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
PHASE SEQ FLT TRIP This parameter determines what to do if there is a
TRIP WARNING fault with the sequence of the phases.
TRIP + WARNING
PHASE SEQ DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
PHASE SEQ AFTR
0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
20160415_Rev03 69 / 180
Settings – Control Keypad
SHORTED SCR
DLY 0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
SHORTED SCR
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
LNG STRT TM FL TRIP This parameter determines what to do if there is a
TRIP WARNING long start.
TRIP + WARNING
LNG STRT TM
DLY 0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
LNG STRT TM
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
SLOW SPD TM TRIP This parameter determines what to do if the motor
FLT
TRIP WARNING speed is too slow.
TRIP + WARNING
SLOW SPD TM
DLY 0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
SLOW SPD TM
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
COMM T/O FLT TRIP This parameter determines what to do if a communi-
TRIP WARNING cation timeout causes a fault.
TRIP + WARNING
COMM T/O DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
COMM T/O
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
EXT FAULT FLT TRIP This parameter determines what to do if there is an
TRIP WARNING external trip.
TRIP + WARNING
EXT FAULT DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
70 / 180 20160415_Rev03
Settings – Control Keypad
EXT FAULT
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
This parameter determines what to do if one of the
IGNORE values for an iStart parameter is outside of the de-
WRNG PARAMS TRIP fined limits for that parameter.
FLT
TRIP WARNING To solve this problem, return iStart to the default
TRIP + WARNING settings, then reprogram it with all of the settings that
you had before the fault occurred.
WRNG PARAMS
DLY 0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
WRNG PARAMS
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
COMM FAILED TRIP This parameter determines what to do if there is a
FLT
TRIP WARNING communication failure.
TRIP + WARNING
COMM FAILED
DLY 0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
COMM FAILED
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
TOO MANY FLT TRIP This parameter determines what to do if there are too
TRIP WARNING many starts within the defined time period.
TRIP + WARNING
TOO MANY DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
TOO MANY AFTR
0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
This parameter determines what to do if the wiring in-
MTOR INSUL FLT TRIP
sulation causes a fault.
TRIP WARNING
TRIP + WARNING
20160415_Rev03 71 / 180
Settings – Control Keypad
72 / 180 20160415_Rev03
Settings – Control Keypad
TRIP WARNING
TRIP + WARNING
M.UNBALANCE
DLY 1.0 – 60.0 SEC The time needed to enter the fault state.
1.0 SEC
M.UNBALANCE
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
GND FAULT FLT TRIP This parameter determines what to do if there is a
TRIP WARNING ground fault.
TRIP + WARNING
GND FAULT DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
GND FAULT
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
NO CURRENT TRIP This parameter determines what to do if there is an
FLT
TRIP WARNING over current state
TRIP + WARNING
NO CURRENT
DLY 0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
NO CURRENT
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
NO CTR PWR TRIP This parameter determines what to do if there is a
FLT
TRIP WARNING short circuit.
TRIP + WARNING
NO CTR PWR
DLY 0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
NO CTR PWR
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
OVER CURR FLT TRIP This parameter determines what to do if there is a
TRIP WARNING short circuit.
TRIP + WARNING
OVER CURR DLY
0.1 – 60.0 SEC The time needed to enter the fault state.
0.1 SEC
OVER CURR
AFTR 0.1 – 60.0 SEC The time needed to exit the fault state.
0.1 SEC
IGNORE
SHEAR PIN FLT This parameter determines what to do if over current
TRIP
TRIP may have broken or weakened the virtual shear pin.
WARNING
20160415_Rev03 73 / 180
Settings – Control Keypad
TRIP + WARNING
74 / 180 20160415_Rev03
Settings – Control Keypad
AUTORESET PA-
RAMS
- **** -
Display and Default
Range Description
Values
DISABLE ALL = The Autoreset feature is disa-
bled for all faults, regardless of what is defined
GLOBAL AUTORESET DISABLE ALL for the fault.
DISABLE ALL ENABLE ALL
ENABLE ALL = The Autoreset feature is ena-
bled. It is defined for each fault separately.
AUTORESET PA-
RAMS
- **** -
Display and Default
Range Description
Values
{FaultName} A.RESET DISABLE iStart will not automatically reset after the
MODE
AUTO RESET OFF fault occurs.
20160415_Rev03 75 / 180
Settings – Control Keypad
76 / 180 20160415_Rev03
Settings – Control Keypad
I/O PROGRAMMING
PARAMETERS
Display and Default
Range Description
Values
IN1 PROGRAMMING
INACTIVE This input is ignored.
STOP
Start the motor.
START
20160415_Rev03 77 / 180
Settings – Control Keypad
78 / 180 20160415_Rev03
Settings – Control Keypad
(increments of 0.1
SEC)
IN3 PROGRAMMING Same as IN1 PRO-
Same as IN1 PROGRAMMING for input 3.
START GRAMMING
MAINTAIN CLOSE
MAINTAIN OPEN
IN3 STATE MOMENTARY
Same as IN1 STATE for input 3.
MAINTAIN CLOSE CLOSE
MOMENTARY O-
PEN
0.1 – 0.5 SEC
IN3 MIN ACTIVE
(increments of 0.1 Same as IN1 MIN ACTIVE for input 3.
0.1 SEC
SEC)
0.1 – 0.5 SEC
IN3 MIN INACTIVE
(increments of 0.1 Same as IN1 MIN INACTIVE for input 3.
0.1 SEC
SEC)
When commands arrive from different inputs,
INPUT POLICY
LAST CMD ACTIVE the last command is one that is implemented.
FIRST CMD ACTIVE Note: If commands from more than one input
arrive at the same time, the input with the
higher priority is implemented. Refer to the IN-
PUT PRIORITY parameter
When commands arrive from different inputs,
the command coming from the input with the
VIA PRIORITY highest priority is the one that is implemented.
The priority is determined by the INPUT PRIO-
RITY parameter.
INPUT PRIORITY
Priority goes from left (highest) to right (lowest).
IN1,IN2,IN3,COM
STOP
20160415_Rev03 79 / 180
Settings – Control Keypad
80 / 180 20160415_Rev03
Settings – Control Keypad
GLOBAL PARAME-
TER
- **** -
Display and default Range Description
values
SET TIME Time in 24 hour hh:mm:ss for-
00:00:00
mat.
SET DATE Date in DD/MM/YYYY format.
01/01/2014
DEFAULT DATA ACTUAL TRIP Sets the default actual data dis-
V/I/POWER FACTOR
ACTUAL WARNING play.
RTD TEMPERATUREi
PTC TEMPERATURE
ii
NTC TEMPERATURE
iii
INTERNAL TEMP
3PH VOLTAGE
3PH CURRENT
V/I/POWER FACTOR
LCD CONTRAST 1-8 Sets the contrast of the LCD
[****** ]
display.
LCD INTENSITY 1-8 Sets the intensity of LCD dis-
[********]
play.
20160415_Rev03 81 / 180
Settings – Control Keypad
STATISTICAL DATA
- **** -
Display and default va-
Range Description
lues
TOTAL ENERGY
Displays total energy drawn by the motor in KWH.
0 KWH
Displays last starting time in seconds.
LAST STRT PERIOD
Starting time is the duration until motor’s current
0SEC
reaches nominal.
LAST STRT MAX I
Displays last starting maximum starting current.
0 % FLA
TOTAL RUN TIME
Displays Motor’s total run time.
0 HOURS
TOTAL # OF STRTS
Displays total number of starts.
0
LAST TRIP
Displays motor’s last trip cause.
NO FAULT
TRIP CURRENT Displays motor’s current when motor was tripped by
0 % FLA the iStart.
TOTAL # OF TRIPS
Displays total number of trips.
0
PREVIOUS TRIP -1
Displays the motor’s trip history.
NO FAULT
PREVIOUS TRIP -9
NO FAULT
PREVIOUS TRIP -9
NO FAULT
PREVIOUS TRIP -9
NO FAULT
PREVIOUS TRIP -9
NO FAULT
PREVIOUS TRIP -9
NO FAULT
PREVIOUS TRIP -9
NO FAULT
PREVIOUS TRIP -9
NO FAULT
PREVIOUS TRIP -9
NO FAULT
RESET STATISTICA
82 / 180 20160415_Rev03
Settings – Control Keypad
20160415_Rev03 83 / 180
Settings – Control Keypad
START 1 Start
START 2 Start
START 3 Start
START 4 Start
STOP 1 Stop
STOP 2 Stop
STOP 3 Stop
STOP 4 Stop
Clock
Control Power On
Motor Idle
Run
Trip
84 / 180 20160415_Rev03
Settings – Control Keypad
1 OPER: Operation
2 FAULT
20160415_Rev03 85 / 180
Settings – Control Keypad
< - TRIP - > When there is a trip, the - TRIP - view dis-
< - NO FAULT - > plays as the default data view.
Syntax:
XX refers to the order of the faults
<WARNING 02/03> shown on the second line. 01 is the <WARNING XX/YY>
< OVERLOAD > least recent fault. The highest num- < ZZZZZZ >
ber is the most recent fault.
YY refers to the total number of
warnings that are active at that mo-
ment.
ZZZZZZ represents the name of
the fault. Refer to for details on
each warning.
Displays the line voltage and frequency.
< V1: V2: V3:>
Frequency is displayed after start com-
< 0% 0% 0%>
mand only.
Displays the operating current in each of
< I1: I2: I3:> the three phases as a percentage of motor
< 0% 0% 0%>
FLA (Full Load Ampere).
<Vrms:Irms:PwrF:>
< 0% 0% 0.00>
You can set any of the views to be the default when there is no trip. To
do this, select the view and press the Enter key. Alternately, you can
set the default in the GLOBAL PARAMETERS > DEFAULT DATA pa-
rameter setting.
86 / 180 20160415_Rev03
Starting Procedure
6. Starting Procedure
Note:
It is necessary to connect a motor to load terminals otherwise S.SCR
or WRONG CONNECTION Protection is activated. Other loads such
as light bulbs, resistors, etc. may also cause WRONG CONNECTION
Fault.
20160415_Rev03 87 / 180
Starting Procedure
Motor starts to No
turn shortly after Increase „Initial Voltage” and
Start signal? start again
Ye
No
Ye Ye No
Slightly increase Initial Voltage and Current Limit settings to allow for
load changes.
88 / 180 20160415_Rev03
Starting Procedure
Yes
Check total starting time and set Max. Start Time to approx. 5 seconds
longer than the maximum time required to complete the starting pro-
cess.
20160415_Rev03 89 / 180
Starting Procedure
90 / 180 20160415_Rev03
Starting Procedure
Starting Curve
Adjust MAIN PARAMETERS as necessary (FLA, FLC, etc.)
Set STARTING CURVE, ACCELERATION TIME, CURRENT
LIMIT, and INITIAL VOLTAGE to their default values (curve 1, 10
sec., 400% and 30% respectively).
Start the pump while watching the pressure gauge as the pump
starts and look for overshooting ( „Pressure Surge”) of the gauge
needle above the target pressure. In case of over pressure,
choose a peak torque reduction curve (Pump Control curve 2!).
Set START CURVE 2!, increase ACCELERATION TIME to 15
seconds and reduce CURRENT LIMIT to 350%. Start the pump
and watch the pressure gauge while the pump starts.
In most cases, overshooting is reduced. If the overshoot persists,
increase ACCELERATION TIME to 25 seconds (confirm with
motor manufacturer) and try again.
If the overpressure persists, increase START CURVE setting to
3!, or 4!. Each increase in START CURVE setting will reduce the
Peak Torque, thus, reducing the overpressure and preventing
the „Pressure Surge” during start.
To increase starting time above these maximums, employ „Spe-
cial Starting” for these techniques (Consult factory).
20160415_Rev03 91 / 180
Starting Procedure
Stopping Curve
Adjust MAIN PARAMETERS as necessary (FLA, FLC, etc.)
Set STOP CURVE and DECELERATION TIME, to their default
values (curve 0, 10 sec., respectively).
Stop the pump, watching the pressure gauge and check valve as
the pump stops. Look for overshooting ( „Water Hammer”) of the
gauge (abruptly stops the pump and the motor).
Select STOP CURVE 2, increase DECELERATION TIME to 15
seconds. Stop the pump and watch the pressure gauge and the
rate of closing of the check valve as the pump stops. Abrupt stop-
ping of the pump and motor will cause a loud audible noise emit-
ted from the check valve.
In most cases, „Water Hammer” is reduced. If the „Water Ham-
mer” persists, increase the time to 25 seconds (confirm with mo-
tor manufacturer) and try again.
If the „Water Hammer” persists, increase STOP CURVE setting
to 3!, or 4!. Each increase in STOP CURVE will reduce the abrupt
stop of the pump, thus, preventing the „Water Hammer” phe-
nomenon.
92 / 180 20160415_Rev03
Starting Procedure
20160415_Rev03 93 / 180
Communication
7. Communication
7.1.1 Features
RS485 Hardware.
Asynchronous serial link.
Half duplex.
Format: Modbus RTU Mode (Remote Terminal Unit Mode).
০ Binary.
০ Each character includes from 9.5 to 12 bits:
1 start bit.
8 data bits, LSB sent first.
1 Parity bit, Even/Odd/No can be selected.
0.5, 1, 1.5 or 2 Stop bits can be selected.
০ Cyclical Redundancy Check (CRC) for the entire frame, 16
bits.
Baud Rates: 1200 up to 115200 bits per second can be se-
lected.
Response time of the iStart:
০ Normally, 1ms <= time response <= 40mS.
০ For a long response, time response <= 100mS.
Setting Parameters cannot be set during Start, Soft Stop
operations and when the motor is running.
Notes:
You must connect the control panel earth to the iStart earth screw
before connecting serial link wires. Ignoring this instruction may
result in permanent damage to the serial link hardware.
94 / 180 20160415_Rev03
Communication
Modbus RTU frames have the same structure for both the "Query"
transmissions from the Master to the Slave (iStart) and the response
transmissions from the Slave to the Master:
20160415_Rev03 95 / 180
Communication
Note:
Address 0 that is normally used for broadcast is not supported by the
iStart.
Function
The function code informs the iStart of the requested action to take.
The function is used as the second byte in both the "Query" transmis-
sion from Master to Slave and in the “Response” transmission from
Slave to Master.
The function code informs the iStart of the requested action to take.
The function is used as the second byte in both the "Query" transmis-
sion from Master to Slave and in the “Response” transmission from
Slave to Master.
96 / 180 20160415_Rev03
Communication
Data
The Data field includes information that is transferred to and from the
iStart. The specific data format changes according to the function.
When Word data parameters are transmitted, the high byte is trans-
mitted first, followed by the low byte.
CRC
The CRC (Cyclic Redundancy Check) has two bytes (16 bit) that are
used to check the entire frame bytes. It is generated in the master de-
vice and transmitted as the last two bytes of the frame. The low byte
is appended first, followed by the high byte.
The slave device regenerates the CRC bytes and compares them to
the CRC bytes received. If the CRC bytes are not identical, the frame
is flushed and no response is transmitted to the master.
20160415_Rev03 97 / 180
Communication
98 / 180 20160415_Rev03
Communication
20160415_Rev03 99 / 180
Communication
The parameter addresses for all actual data have an offset of –1.
For example: In order to read parameter # 5, the user should call ad-
dress 304
Notes:
1. Use function 3 to read the setting parameters.
2. Use functions 6 and 16 to write the setting parameters.
3. Each of these parameters must set with care. Incorrect settings
of some parameters can damage both the motor and the ISA-
SL.
Note:
Start Parameters (second, third and fourth Adjust) have the same pa-
rameters. Their addresses are shifted from first adjust by: ((Adjust
Number – 1) * 40).
For example: the “Pulse Rise Time” for third adjusts has the address:
(# Pulse Rise Time First Adjust) + ((Adjust – 1) * 40) + offset of – 1 =
61 + 2*40 = 140.
Note:
Stop Parameters (second, third and fourth Adjust) have the same pa-
rameters. Their addresses are shifted from first adjust by: ((Adjust
Number – 1) * 20).
For example: the “Deceleration Time” for forth adjusts has the address:
(#Deceleration Time First Adjust) + ((Adjust – 1) * 20) + offset of –1 =
213 + 3*20 = 272.
Notes:
The next fault parameters are the same as the ones above except for
a few exceptionsviii. Their addresses are shifted from first set (Trip,
Active & Inactive time) by: ( (Fault Number –1)*3).
For example: the “Too Many Starts Inactive Time” has the address:
(# Over Temperature Inactive Time) + ((Fault Number – 1) * 3) + offset
of –1 = 313 + 15*3 = 4357.
Faults List
# Fault # Fault
01 Over Temperature 17 Motor Insulation (Op-
tional)
02 Short Circuit Current 18 Thermistor (Optional)
03 Overload 19 Wrong Frequency
04 Under Current 20 No Voltage
05 Under Voltage 21 Over 7p5 FLA current
06 Over Voltage 22 Over 7p5 FLC current
07 Phase Loss 23 Motor Unbalance
08 Phase Sequence 24 Ground Fault
09 Shorted SCR or 25 No Current
Wrong Connection.
10 Long Start Time 26 No Control power
11 Slow Speed Time 27 Over Current (Inverse)
12 MODBUS Timeout 28 Shear Pin Current
13 External Fault 29 Wrong VZC
14 Wrong Parameters 30 Welded Contactor
15 COM Port Failed 31 No Calibrationix
16 Too Many Starts
Notes:
1. The next Auto-Reset parameters are the same as the ones
above. Their addresses are shifted from first set (When Active,
Number of Tries… after Start Enable) by: ((Fault Number – 1) *
7).
For example: the “No Control Power Wait for solved” has the ad-
dress:
(#Over Temperature Wait for solved) + ((Fault Number – 1) * 3)
+ offset of –1 = 506 + 25*7 = 680.
2. The complete list of fault parameters is listed on page 110.
3. The last fault (No Calibration) does not have an autoreset param-
eters group.
Notes:
29. Parameter # is "1 based". The address is 1 lower than the
parameter #. For example address of parameter #1 is 0.
30. When the Write Multiple Register function (16) is used to
adjust one or more setting parameters, then if one or more
setting parameters are out of range, or if it is beyond the
To read the Adjust Soft Start Setting parameters #173 – 175 (ad-
dressed at 172 – 174) (Init Volt, Init Current and Current Limit) for
mo-tor number 4 attached to the iStart # 1, the host computer
should send following frame:
Note:
After setting iStart parameters, the user is responsible for reading
and testing all setting parameters. When Preset Multiple Register
Function (16) is used to adjust one or more setting parameters, an
Illegal_Data_Address (exception code 0x02) error response will be re-
turned if one of the following conditions exist:
One or more setting parameters are out of range
Preset Multiple Register Function (16) is outside the allowed
range.
Notes:
1. It is not possible to read the function of the control register. To
read the iStart status, read the Logic Status (actual parameter #
1 – address 0).
2. Bytes 2 - 8 of the control frame must be exactly as in Example 5
- Control Register Write on page 127e. Otherwise, an error mes-
sage will be returned.
3. Warning: Before applying Start Command via Comm. – make
sure you have at least one I/O Logic Input that is set to stop and
have higher priority than Comm.
36.
To start iStart # 1, the host computer should send the following query
frame:
7.5 Diagnostics
Modbus function 08, as implemented in the iStart, tests the commu-
nication serial link between the master and the iStart only supports
return query data (subfunction 0x00).
To request iStart with serial link # 1 to return query data, the master
should send the following query frame:
Exception response frame holds fix number of 5 Bytes. The first one,
the Slave Address field is the Serial link number (transmitted in query
and identical to iStart Serial Link No.). The second byte, the Function
field returns the echo of the transmitted query function, but with the
MSB set to 1 (adding 0x80 to the transmitted function code). The third
Byte is the Exception Code informing about the type of error. Last two
bytes are the CRC bytes.
Exception Response:
Note:
There are cases where the iStart returns a normal response, but the
requested action cannot be performed, or is modified by the table be-
low.
33: ;=============================================
34: ;==== General DP Keywords ====================
35: ;=============================================
36:
37: GSD_Revision = 5
38: Vendor_Name = "IGEL Ltd"
39: Model_Name ="iStart"
40: Revision ..."1.00"
=
41: Ident_Number
42: Protocol_Ident = 0xAFFE
43: Station_Type = 0
44: FMS_supp = 0
45: Hardware_Release = 0
46: Software_Release = "V1.00"
47: Redundancy = "V1.00"
48: Repeater_Ctrl_Sig = 2
0
49: 24V_Pins = 0
From the Profibus controller to the iStart, two bytes (16 bits) are
transferred.
From the iStart to the controller, 40 bytes are transferred.
Sending
from the
iStart
4 LSB
0 = normal speed
5 Slow Speed
1 = slow speed
0 = forward direction
6 Slow Spd Reverse
1 = reverse direction
7 Reset 1 = reset
Example:
To send a Reset, send 0x5A followed by 0x80.
Code Sample 2: GSD file, the part that responsible to the registers that
show at DPV0 (cyclic)
Write
Also, it easy to read this list by reading from Slot number 1 and Index
number 2 through Data Request (by DPV1).
Read
Write to
Slot: 2
Index: 2
Register num-
ber 80 hex
Read from
Slot: 3
Index: 2
8 byte – (4
Registers)
2. Press the Enter key once to cause the following message to ap-
pear:
SERIAL LINK NO.
ENABLE
3. Press the Down key once to cause the following message to ap-
pear:
COM CHANGE PARAM
YES
Regis-
ter Parameter Name Description
Number
Logic status of iStart. 1 indi-
cates:
d15: iStart Tripped.
d14: Motor Stopped.
d13: Motor in Soft Stop Pro-
cess.
d12: Motor in Start Process.
d11: Motor is Running.
1 Logic Status
d10: Adjust number LSB
d9: Adjust number MSB
d8: Motor is running at Slow
Speed forward.
d7: Motor is running at Slow
Speed reverse.
d6: Insulation Alarm (Optional)
d5..d0: Reserved
2 Current Current, % FLA
3 Voltage Line voltage, Volts
1: Correct phase seq. 0:
4 Phase Sequence
Wrong phase seq.
Discrete Hardwired control in-
puts:
d15..d3: Reserved.
d2: Logic input #3 status – 1:
5 Hardwired inputs Active, 0: Inactive.
d1: Logic input #2 status – 1:
Active, 0: Inactive.
d0: Logic input #1 status – 1:
Active, 0: Inactive.
Regis-
ter Parameter Name Description
Number
Relays status
d15..d2: Reserved.
6 Relays d1: Relay #2 status – 1: Ac-
tive, 0: Inactive.
d0: Relay #1 status – 1: Ac-
tive, 0: Inactive.
Insulation Re- Motor insulation, Kohm (Op-
7
sistance tional).
8 I Zero Current Ground leakage current, % FLA
I Motor Unbal- Max current deviation between
9
anced Current phases, %
10 Frequency Main frequency, Hz
Thermistor Re- Thermistor resistance, tenth
11
sistance Kohm (Optional).
Power [Watt] – Low
12 Power modulo 64K (65536)
word
Power [Watt] – Power divided by 64K (65536)
13
High word without residue
14 Power Factor Power Factor * 100
Total run time [Sec] Total Motor runtime modulo 64K
15
– Low word (65536)
Total run time [Sec] Total Motor runtime divided by
16
– High word 64K (65536) without residue
Logic status at Logic status at control power
17
power fail supply turns off.
18 Total run time Total hours of running motor.
19 Total starts Total number of starts
20 Last start period Duration of last start, Seconds
Peak current during last starting
21 Last start peak I
process
Time to Re-Enable Wait time until next start com-
22
start [Sec] mand will be allowed
Regis-
ter Parameter Name Description
Number
23 Total trips Total number of trips
Regis-
ter Parameter Name Description
Number
30: Welded contactor
31: By pass fault
25 Pre trip I Current at trip time, Amp.
26 Logic Input Status
The uniqe CRC16 Calculation of
27 Version CRC16
each SW Version
28 Phase Sequence 1: Positive, 0: Negative
Time to Over Cur- Time left until “Over Current” trip
29
rent Trip occurs in seconds
30 Cos Phi Cos Phi * 100
Phase 1 voltage, % Rated Line
31 Phase 1 Voltage
Voltage * 10
Phase 1 voltage, % Rated Line
32 Phase 2 Voltage
Voltage* 10
Phase 1 voltage, % Rated Line
33 Phase 3 Voltage
Voltage* 10
34 Phase 1 Current Phase 1 current, % FLA * 10
35 Phase 2 Current Phase 1 current, % FLA * 10
36 Phase 3 Current Phase 1 current, % FLA * 10
Energy [KWH] – Total Energy modulo 64K
37
Low word (65536)
Energy [KWH] – Total Energy divided by 64K
38
High word (65536) without residue
Energy per cycle –
39
first word – MSB
Energy per cycle –
40
second word
Energy per cycle in Watts
Energy per cycle –
41
third word
Energy per cycle –
42
forth word – LSB
43 Reserved
Regis-
ter Parameter Name Description
Number
44
45
46
47
Thermistor or phase 1 RTD Tem-
Analog option card
48 perature (Analog option cards)
– Temperature 1
[Kelvin]
Thermistor or phase 2 RTD Tem-
Analog option card
49 perature (Analog option cards)
– Temperature 2
[Kelvin]
Thermistor or phase 3 RTD Tem-
Analog option card
50 perature (Analog option cards)
– Temperature 3
[Kelvin]
51
Reserved
52
Phase 1 Tempera- Phase 1 internal temperature.
53
ture [Kelvin]
Phase 2 Tempera- Phase 2 internal temperature.
54
ture [Kelvin]
Phase 3 Tempera- Phase 3 internal temperature.
55
ture [Kelvin]
Trip number of 10 last trips –
111-120 Previous Trips
from last to earliest.
Main Parameters
4
Reserved
5
O/C Shear Pin 6 100..850 (% of FLA) 400 (% of FLA)
Reserved 7
Overload Class 8 IEC5..NEMA60 IEC10
0 – Disable
Overload Pro-
9 1 – Enable while run 0 – Disable
tect
2 – Enable always
Under Current
10 0..90 (% of FLA) 20 (% of FLA)
Level
M.Unbalance
11 10..100 (% of FLA) 20 (% of FLA)
Current Level
Ground Fault
12 1..60 (% of FLA) 20 (% of FLA)
Current Level
Under Voltage 50..90 (% of Rated 75 (% of Rated
14
Level Line) Line)
Start Parameters
Stop Parameters
Fault Parameters
I/O Programming
De-
Parameter # Range fau
lt
2
(En
Prog. Input #7 (ther- 7 0..2(0=En.Save,1=S.Spd,2=Rs erg
mal7) 2 t) y
Sav
er)
0
(Du
Prog. Input #8 (ther- 7 al
0..2(0=D.Adj.,1=Rvrs,2=Rst)
mal8) 3 Ad-
just
)
0
7 0..1 (0=Fault, 1=Fault-Fail
Fault_Relay_Type (Fa
4 Safe)
ult)
0
(Im
Immedi- 7 0..1 (0=Immediate, 1=shear
me-
ate_Realy_Type 5 pin)
di-
ate)
0
Imm._Realy_On_De- 7 (Se
0..3600
lay 6 con
ds)
0
Imm._Realy_Off_De- 7 (Se
0..3660
lay 7 con
ds)
0
Analog Output Param- 7 0 - Current, 0..200% of mo- (Cu
eter 8 tor_fla rre
nt)
7
Reserved
9
Step 1: Disconnect the mains and control power from the iStart.
Step 2: Remove the iStart unit from the wall.
Step 3: Mount the fan on the wall instead of the iStart unit. Use
the same holes.
Step 4: Mount the iStart unit on fan using the same screws that
you removed in step 2.
9. Troubleshooting
Upon fault – motor stops, Fault LED lights and Fault Relay operates.
The LCD shows TRIP: and fault description. (for example: TRIP: UN-
DER CURRENT).
Wait until motor and starter cool down – according to START IN-
HIBIT setting.
For more information on adjusting START PERIOD and START IN-
HIBIT refer to section 5.6.2 on page 58.
LONG Trips the starter if output voltage does not reach nominal at the pre-
START TM sent MAX. START TIME.
Check FLA, FLC, and MAX START TIME settings. Increase INI-
TIAL VOLTAGE, CURRENT LIMIT & MAX. START TIME or de-
crease ACCELERATION TIME as necessary.
For more information on FLC & FLA refer to section 5.6.1 on page
36 (MAIN PARAMETERS).
For more information on adjusting START PARAMETERS refer to
section 5.6.2 on page 58.
OVERLOAD Trips the starter when current exceed the OVERLOAD TRIP level
and thermal register has filled up.
Check FLA, FLC and Overload settings, check motor current, wait
15 minutes to let motor and starter cool down before restarting.
For more information on FLC, FLA & OVERLOAD settings refer to
section 5.6.1 on page 48 (MAIN PARAMETERS).
UNDER Trips the starter when line current drops below the preset level for
CURRENT the preset time.
UNDER Trips the starter when line voltage drops below the preset level for
VOLTAGE the preset time.
or
NO VOLT- Check UNDER VOLTAGE TRIP and TIME DELAY settings, check
AGE line voltages on L1, L2, L3. When voltage drops to zero, the starter
trips immediately with no delay.
For more information on UNDER VOLTAGE settings refer to sec-
tion 5.6.1 on page 48 (MAIN PARAMETERS).
OVER VOL- Trips the starter when line voltage increases above a preset level
TAGE for a preset time.
SHORT Trips the soft iStart when connected Inside Delta and Wrong con-
CIRCUIT nection or if over current is detected by the iStart.
Verify that the motor is not stalled or shorted and check cables and
wiring.
Verify that motor and iStart are connected exactly as shown in
section 0 page 25.
S. SCR OR Trips the starter when one or more motor phases are not properly
WR. CON- connected to starter’s load terminals, in case of internal disconnec-
NECTION tion in motor winding or if any SCR is short-circuited or when motor
windings are shorted.
EXTERNAL Trips the starter when a N.O contact between Aux. input terminals
FAULT 13, 14 closes for over two seconds.
Equipment Model:
Equipment Serial no.:
Report date
Date of equipment sale Date of installation
Representing Firm
Contact person
Telephone number Fax number
Email address
Application
Starter Rating
Motor current rating (motor Label)
Number of starts per hour
Special installation / ambient factors (°C)
Type of Fault Reported & time of occur-
rence (during start, after start, during soft
stop, end of soft stop, ON B.P. closing,
when …
Last Start Period Total Number Of Trips
Last Start Max. I Starter FLC
Total Run Time Motor FLC
Total Number Of Starts Initial Voltage
Last Trip Acceleration Time
Trip Current Current Limit
Remarks
By Distributor: We declare that product has been correctly ap- Warranted repair/replacement
plied, installed and operated, in accordance with esco
antriebstechnik gmbh written instructions, appropriate codes,
regulations and good practice, within the limits of rated
capacity and normal usage.
Date
Authorized by
10. Dimensions
Supply Voltage Line to Line 208-600V (to be specified) + 10%-15% for all
models
Frequency 45 – 65 Hz (Fixed or variable frequency source)
Control Supply 115V or 230V (to be specified) +10% - 15%
Load Three phases, three wires, squirrel cage induction motor.
Start-Stop Parameters:
Motor Protection:
Too Many Starts Maximum number of starts, range: Off or 1-10, during a time
period 1-60 min.
Starts inhibit Period of 1-60 min, during which starting is prevented, after
Too Many Start fault.
Long Start Time (Stall protection) Maximum allowable starting time 1-30 sec. (1-250sec. in EX-
TEND SETTING)
Over Current (Shear-pin) Two operation functions: during starting trips the starter at
850% and during running at 100-850% In, both within 1 Cycle
(after internal delay).
Electronic Overload (I2t) Adjustable IEC and MEMA curves.
Under Current Trips when current drops below 20-90% In, time delay 1-40
sec.
Under Voltage* Trips when main voltage drops below 50-90%, time delay 1-10
Sec
Over Voltage Trips when main voltage increase above 110-125%, time de-
lay 1-10 sec.
Phase Loss, Under/Over Frequency* Trips when one or two phases are missing and frequency is
45Hz. or 65Hz.
Phase Sequence Trips when phase sequence is wrong
Shorted SCR or Wrong connection Prevents starting, trips if motor is not connected / incorrectly
connected to the starter, or in case one or more SCRs have
been shorted
Heat Sink Over temp Trips when heat-sink temperature rises above 85˚C.
Control:
Standards:
Fan Module
Model Elektronic Consump-
tion
85 35VA 50VA
170 35VA 50VA
230 95VA 110VA
310 95VA 110VA
350 95VA 110VA
430 95VA 110VA
515 95VA 110VA
590 95VA 110VA
690 95VA 110VA
720 95VA 110VA
850 95VA 110VA
960 95VA 110VA
1100 95VA 110VA
Mains Voltage
Specify Description
480 208 – 480 VAC, 50/60Hz , +10% -15% R1
600 208 – 600 VAC, 50/60Hz , +10% -15% R1
208 – 690 VAC, 50/60Hz , +10% -15%. Only available with 230A and
690 R2
above.
Options
Specify Description
0 No options
3M Communication RS-485 Board (MODBUS) (1) (3) R1
3R Communication RS-232 Board (MODBUS) (1) (3) R1
3P Communication Profibus (1) (3) (D type connector) R2
3E Communication ProfiNet (1) (3) (RJ-45 connector) R?
3D Communication Device Net (1) (3) (terminal connectors) R2
2P 2 phase control(5) R1
D Remote Keypad (3) R1
4 Insulation tester (2) (3) R2
5 Analog card – Thermistor in and Analog out (2) (3) R2
6 3XRTD Thermal sensors (2) (3) R2
8 Harsh environment treatment R1
F115 Fan unit (4) 115VAC fan unit R2
F230 Fan unit (4) 230VAC fan unit R1
ROC Chinese language LCD R2
RU Russian language LCD R1
(1) Only one option from 3M, 3R, 3P, 3D, 3E.
(2) Only one option from: 4, 5, 6.
(3) You can install these options on site.
Notes: (4) You can install these options on site for frame sizes A, B and C only.
Front Panel
Specify Description
S Standard
13. Attachment
Figure 35 iStart Size B: 58A, 72A, 85A (Fan box included) .................162
Figure 36 iStart Size B: 58A, 72A, 85A (Without fan box)... .............163
Figure 37 iStart Size C: 105A, 145A, 170A (Fan box included) ..........164
Figure 38 iStart Size C: 105A, 145A, 170A (Without fan box).... ..........165
Table 22 LSB and MSB values for bits 3 and .................................. 135
Table 23 Number of the registers for the sample parameters ......... 137
13.3 Notes
Version18a02057
Information:
Tel.: +49 (0) 22 41 / 48 07 0
Internet: www.esco-antriebstechnik.de