Click here for more information:
elandcables.com | A2XS(FL)2Y HDPE High Voltage 76/132 (145) kV Cable
A2XS(FL)2Y HDPE High Voltage
76/132 (145) kV Cable
Eland Product Group: H9D
APPLICATION STANDARDS
High Voltage cables for distribution networks; also for IEC 60840
connection to generation units and plant and process
connection. For installation in ground, in water outdoors,
indoors and in cable ducts for power stations, industry and THE CABLE LAB®
distribution networks. The water blocking tape avoids water AN ISO/IEC 17025 AND IECEE CBTL ACCREDITED FACILITY
propagation inside the cable. Our world-class testing facility assures the quality and compliance of this cable
through a continuous and rigorous testing regime.
CHARACTERISTICS
Voltage Rating Uo/U
76/132 (145) kV
SUSTAINABILITY COMMITMENT
CONSTRUCTION We are on a journey to Net Zero.
Conductor We've committed to near-term emissions reductions and a net-zero target with the
Aluminium conductor (optional watertightness – WTC) Science Based Targets initiative and we're a signatory to the United Nations Global
Compact Sustainable Development Goals.
Conductor Screen Learn more about embodied carbon and our carbon emissions reduction actions,
Semi-conductive screen extruded on the phase conductor our comprehensive recycling services, and wider ESG activities for sustainable
operations at: www.elandcables.com/company/about-us/esg-sustainability
Insulation
XLPE (Cross-linked Polyethylene)
Insulation Screen
Semi-conductive screen extruded on insulation
Wrapping REGULATORY COMPLIANCE
Semi-conductive water swelling tape
This cable meets the requirements of the RoHS Directive 2015/65/EU and
Reach Directive EC 1907/2006. RoHS compliance has been tested and
Metallic Screen confirmed by The Cable Lab®.
Copper wires and equalising tape
Wrapping
Semi-conductive water swelling tape
Tape
Longitudinally applied aluminium tape coated with PE
copolymer
Sheath
HDPE (High Density Polyethylene)
Optional – semi-conductive layer
Sheath Colour
Black
UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com
International T +44 20 7241 8740 | F +44 20 7241 8700 |
[email protected] technicalspecification | 1 of 3
Click here for more information:
elandcables.com | A2XS(FL)2Y HDPE High Voltage 76/132 (145) kV Cable
DIMENSIONS
ELAND PART NO. NO. NOMINAL NOMINAL INSULATION METALLIC SCREEN NOMINAL NOMINAL MAXIMUM MINIMUM
OF CROSS DIAMETER OF mm OUTER WEIGHT PULLING BENDING
CORES SECTIONAL CONDUCTOR DIAMETER kg/km FORCE RADIUS
AREA mm OF CABLE mm m
mm2 mm
Nominal Nominal Nominal cross Nominal
thickness diamter over section diameter over
mm2 mm
H9D132KV010185 1 185RM 15.8 18.0 54.8 95 60.6 69 4600 6.5 1.7
H9D132KV010240 1 240RM 17.9 17.0 54.9 95 60.7 69 4710 8.4 1.7
H9D132KV010300 1 300RM 20.0 16.5 55.4 95 61.2 70 4850 10.5 1.7
H9D132KV010400 1 400RM 22.9 16.0 56.9 95 62.7 71 5140 14.0 1.8
H9D132KV010500 1 500RM 25.7 16.0 59.7 95 65.5 74 5640 17.5 1.9
H9D132KV010630 1 630RM 29.3 16.0 63.9 95 69.7 79 6370 22.1 2.0
H9D132KV010800 1 800RM 33.0 16.0 67.6 95 73.4 83 7090 28.0 2.1
H9D132KV011000 1 1000RM 38.0 16.0 72.6 95 78.4 88 8050 35.0 2.2
H9D132KV011200 1 1200RM 42.5 16.0 77.1 95 82.9 93 9010 42.0 2.3
H9D132KV011200R 1 1200RMS 43.0 16.0 79.2 95 85.0 95 9270 42.0 2.4
H9D132KV011400 1 1400RMS 45.1 16.0 81.3 95 87.1 97 9990 49.0 2.4
H9D132KV011600 1 1600RMS 48.5 16.0 84.7 95 90.5 101 10830 56.0 2.5
H9D132KV011800 1 1800RMS 52.7 16.0 88.9 95 94.7 105 11850 63.0 2.6
H9D132KV012000 1 2000RMS 54.5 16.0 90.7 95 96.5 107 12460 70.0 2.7
H9D132KV013000 1 3000RMS 67.0 16.0 104.2 95 110.4 122 16730 100.0 3.1
H9D132KV012500 1 2500RMS 59.0 16.0 96.2 95 102.4 114 14120 87.5 2.8
H9D132KV013000 1 3000RMS 67.0 16.0 104.2 95 110.4 122 16730 100.0 3.1
ELECTRICAL DATA
De – Cable diameter
Cables in flat formation, the distance between the cable axes = 2 × De
Cables in trefoil formation, the distance between the cable axes = De
ELECTRICAL CHARACTERISTICS
NOMINAL CROSS NOMINAL ELECTRICAL FIELD STRESS CAPACITANCE ZERO REACTANCE INDUCTANCE
SECTIONAL AREA RESISTANCE OF kV/mm μF/km Ω/km Ω/km
mm2 CONDUCTOR 90 OC
Ω/km
Conductor screen Insulation Flat formation Trefoil formation
185RM 0.2108 7.60 2.60 0.125 0.102 0.215 0.155
240RM 0.1610 7.55 2.90 0.140 0.094 0.205 0.145
300RM 0.1291 7.50 3.05 0.150 0.088 0.200 0.140
400RM 0.1009 7.40 3.25 0.165 0.080 0.190 0.135
500RM 0.0792 7.15 3.35 0.175 0.076 0.185 0.130
630RM 0.0622 6.90 3.45 0.195 0.072 0.180 0.125
800RM 0.0498 6.70 3.55 0.210 0.067 0.175 0.120
1000RM 0.0408 6.45 3.65 0.230 0.063 0.170 0.115
1200RM 0.0359 6.30 3.70 0.250 0.059 0.170 0.110
1200RMS 0.0319 6.25 3.75 0.260 0.060 0.170 0.110
UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com
2 of 3 | technicalspecification International T +44 20 7241 8740 | F +44 20 7241 8700 |
[email protected] Click here for more information:
elandcables.com | A2XS(FL)2Y HDPE High Voltage 76/132 (145) kV Cable
ELECTRICAL CHARACTERISTICS
NOMINAL CROSS NOMINAL ELECTRICAL FIELD STRESS CAPACITANCE ZERO REACTANCE INDUCTANCE
SECTIONAL AREA RESISTANCE OF kV/mm μF/km Ω/km Ω/km
mm2 CONDUCTOR 90 OC
Ω/km
Conductor screen Insulation Flat formation Trefoil formation
1400RMS 0.0275 6.20 3.75 0.270 0.059 0.165 0.110
1600RMS 0.0242 6.10 3.80 0.285 0.056 0.165 0.110
1800RMS 0.0216 6.00 3.85 0.300 0.054 0.160 0.105
2000RMS 0.0195 6.00 3.90 0.310 0.053 0.160 0.105
2500RMS 0.0168 5.90 3.95 0.330 0.052 0.160 0.100
3000RMS 0.0130 5.75 3.95 0.365 0.049 0.155 0.100
UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com
International T +44 20 7241 8740 | F +44 20 7241 8700 |
[email protected]