Red670 M1
Red670 M1
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© Copyright 2022 HITACHI ENERGY
CUSTOMER
MUNDRA SOLAR TECHNOPARK PVT. LTD.
MUNDRA, GUJARAT
CHECKLIST
MEASUREMENT
1. LINE DIFFERENTIAL
2. ZONE 1,2,3,4
3. SOTF
4. VT FUSE FAIL
5. BRC
6. POWER SWING DETECTION
7. O/V
8. DIR. O/C
9. DIR. E/F
1. DIFFERENTIAL PROTECTION:
Idmin : 0.20 IB
EndSection1 : 1.25 IB
EndSection2 : 3.00 IB
SlopeSection2 : 30.0%
SlopeSection3 : 80.0%
IdUnre : 10.0 IB
I2/I1Ratio : 15.0%
I5/I1Ratio : 20.0%
b. DIFFERENTIAL STABILITY:
c. DIFFERENTIAL UNSTABILITY:
d. SLOPE TEST:
e. HARMONICS RESTRAINT:
2. DISTANCE PROTECTION
ZONE TEST FOR ALL ZONES 1, 2, 3, 4 (AS PER THE RELAY SETTINGS).
FAULT LOCATOR CHECKED OK.
TRIP CONTACTS & LEDS CHECKED OK.
BLOCKING OF DISTANCE PROTECTION FOR VT FUSE FAIL CHECKED OK.
BLOCKING OF DISTANCE PROTECTION FOR PSB CHECKED OK.
3. SOTF
4. VT FUSE FAIL
6. POWER SWING
7. O/V PROTECTION
8. DIR.O/C PROTECTION
I Start : 1.0 x In
Directional mode : Non-directional
Time multiplier : 0.2
Timer delay : 1.0 Sec
Operating curve type : IEC Norm. Inv.
Characteristic angle : 55 deg
9. DIR.E/F PROTECTION
I Start : 0.20 x In
Directional mode : Non-directional
Time multiplier : 0.31
Timer delay : 1.0 Sec
Operating curve type : IEC Norm. Inv.
Characteristic angle : 45 deg