1 Introduction 4
2 Smart Grid & Power Distribution 5
3 Auto Reclosing and Sectionalizing 6-7
4 Design and Technology 8-11
• Overview
• Pole Assembly
• Arc Interruption
• Control Panel
• Magnetic Actuator
• HT Circuit Breaker
NIKUM aims to provide customers with the latest technology combined with outstanding performance, affordable pricing, and
excellent service aimed at unparalleled customer satisfaction. Our products are all high quality and the natural option for you.
This is why they are all extensively type tested in independent laboratories as per IEC/ANSI standards
This is especially true when it comes to our feeder automation services and products, where years of information and modular
manufacturing techniques enable our outdoor vacuum reclosers to fulfil any need and schedule. Since 1991, NIKUM has been
manufacturing MV switchgear. With over two decades of experience in this field NIKUM, our team has extensive knowledge
and skills in this field.
All the technology available today has been indigenously developed by NIKUM in our in-house R&D facility
Smart Grid & Power Distribution
Functionally, a Smart Grid should be able to provide new abilities such as self-healing, high reliability, energy management,
and real-time pricing. From a design perspective, a Smart Grid will likely incorporate new technologies such as advanced me-
tering, automation, communication, distributed generation, and distributed storage
One of the important characteristic of smart grid from conventional grid is the self healing capacity. Auto recloser play a cru-
cial role in this characteristic.
While other characteristics such as cyber-security, real time monitoring and control, interoperability, development of demand
response can be realized with Nikum make smart Reclosers.
Sectionalizer are medium/low voltage protective devices which do not require fault interrupting capabilities. It is installed
downstream of a MV overhead feeder protected by a recloser/breaker. Sectionalizer count the operations of the backup
device during fault conditions. Counts are registered by the Sectionalizer only when fault current flow through the Sectional-
izer had been detected prior to the operation of the backup device. After a given number of counts, as selected as a part of
the Sectionalizer setting, the Sectionalizer opens to isolate the faulted section of the line when the backup device is in the
open position and the section of line where the Sectionalizer is located is in a deenergized state. The objective of the Section-
alizer to remain closed on temporary faults; the backup device will trip and reclose to restore the line to service for such
faults prior to the Sectionalizer opening.
For permanent faults, the Sectionalizer recognizes that one or more trips have occurred after the backup device reclosed,
and it subsequently opens to isolate the faulted portion of the line. NIKUM 'S Sectionalizer are programmed to sense the cur-
rent & voltage, decide as a fault feed; the upstream protective device operation (opening) is detected by the zero current
flow through it and then operates (opens). After the Sectionalizer opens, the backup device automatically recloses to restore
to service that portion of the line up to the Sectionalizer location. Application of sectionalizes requires that the backup inter-
rupting device be capable of detecting faults in the Sectionalizer zone of protection.
Normally
Substation Open / Tie
sending end Midpoint Point Sec-
Feeder 2 Recloser 2 Sectionalizer 2 tionalizer 3
Zone C Zone D
One of the practical application of Sectionalizer is shown in the above diagram. Two Feeders 1 and 2 and connected
through a Sectionalizer which is in normally open condition with voltage sensing provided on both incoming and outgoing
sides. Reclosers are provided for the fault interruption while a Sectionalizer is provided at midpoint location for fault isola-
tion. For better understanding, two case scenario are discussed below:
1) For any permanent Fault 1in Zone B, Sectionalizer 1 shall open after preset number of retries from Recloser 1. Finally,
Zone B get isolated automatically while supply in Zone A,C and D shall remain active.
2) For any permanent Fault 2 in Zone A, only Recloser 1 shall open and lockout after completing the duty cycle. It is here
when Sectionalizer 3 will sense the voltage outage on one of its side and it will close automatically to restore supply in
Zone B. Finally, Zone A will get isolated automatically while supply in Zone B, C and D shall remain active.
Design and Technology
The interface of the device has been tried to keep simple and convenient for the end user. The technology is developed indige-
Design Overview
nously by NIKUM 'S team. All the spare parts are procured to limit the manufacturing delays. Auto Recloser can withstand
30,000 close-open operations without maintenance.
The design of the product is all weather proof and can withstand extreme temperatures. The creepage of the breaker has
been maintained high to suit highly humid conditions.
The device primarily consist of three parts: HT Circuit Breaker (common for Auto Recloser and Sectionalizer), Control Panel
and Auxiliary Transformer (optional). A block diagram is shown below to realize the connection between these devices.
HT Circuit Breaker
Control Panel
The Control Cabinet houses the control and
power supply system of the HT Circuit Break-
er and is very easy to operate, enabling the
operator to work comfortably and a position
sensor is provided for the door position sens-
ing. Control Cabinet is located on the human
interface level and is connected with the unit
through a multi-core control cable which
comes as a part of the complete unit from
factory. Also, the cabinet includes a space
heater for moisture control.
An illumination LED is provide in the control
cabinet for the easier maintenance functions.
The control unit also houses a document
holder.
Use of magnetic actuation technology reduces the number of moving parts in the mechanism. As a result, we get a mainte-
Magnetic Actuator
nance free mechanism which can perform at least 30,000 operations. The design of the Recloser is bi-stable in nature i.e., it
does not need any external power to maintain the contact position.
All 3 phases are coupled to a single shaft which eliminates any chances of pole discrepancy.
Unlike conventional breakers, we have opted for magnetic actuators instead of motor-spring mechanism. The actuators are so
reliable that they can perform up to 1,00,000 operations.
Actuators are powered by Control unit of the Recloser.
HT Circuit Breaker
Incoming HT terminal
Current Transformer
Outgoing HT terminal
Trip Lever
The circuit breaker uses vacuum as interruption medium and solid dielectric HCEP as insulating medium. The mechanism
is sealed by a stainless steel metal tank while the HT parts are encapsulated in epoxy poles.
Copper terminals are provided as standard for both incoming and outgoing terminal. On the right side a position indicator
with detachable closing lever is provided. The indicator points over “0” and “I” to indicate circuit breaker position as
“Open” and “Closed” respectively. Below the indicator Tripping lever is provided.
The circuit breaker can be opened and closed manually i.e., without using Control Panel by an operator from ground level.
Inner Assembly of HT Circuit Breaker
Vacuum Interrupter
Current Transformer
Voltage Sensor
Opening actuator
Closing actuator
Inner engineering of the circuit breaker is explained in the image above. HCEP poles are mounted over a metal frame to
withstand the required closing forces applied to vacuum interrupters.
HT Circuit Breaker consist of 3 pole assembly which are connected by a common shaft. Each embedded pole consist of Vac-
uum Interrupter, Current Transformer and Voltage sensor.
Quality and Safety
NIKUM is committed to quality, environmental responsibility and safety in servicing
Our commitment and certifications
Manual Lockout
In addition to standard Auto Reclose lockout NIKUM's ACR is equipped with Manual Lockout Function. Once the ACR has been
set into Manual Lockout state, it can no longer be operated locally or remotely.
For setting the ACR in this mode, the operator has to pull down the trip lever provided the ACR tank with a hot stick. This mo-
tion does a dual function - Trip the ACR and set the ACR into Manual Lockout mode. Now, until the Trip Lever is set back into
its original state the unit remain in the Manual Lockout mode.
Over Current and Earth Fault (67, 50, 51, 67N, 50N, 51N)
Over current and Earth fault is applied to almost
every part of protection system. It protects the sys-
tem against over loading and short circuiting.
Follower or standard DTL can be added to In-
verse Time or Instantaneous protection
4 stage operation
IEC Curves - Normal Inverse, Very Inverse, Ex-
tremely Inverse
IEEE Curves - Moderately Inverse, Very Inverse,
Extremely Inverse
User Programmable non-standard curves
Under-Current (37)
Each element has settings for pickup level and Definite Time
Lag (DTL) delays. Operates if current falls below setting for
duration of delay.
Restraint and Supervision
It is often observed that creating sensitive protection scheme can lead to nuisance tripping in field conditions. Therefore, it is
very important to provide constraint to block any unwanted tripping of the unit,
At Nikum we pay a lot of attention to the user's comfort in device operation. With such sensitive protections, it is very much
possible that the ACR can get nuisance tripping. It causes loss of capital and man power.
Therefore, every possible effort has been taken by us to ensure the best customer experience by providing some restraints to
the protections.
Directional Blocking
Restricts tripping on faults to a designated side of the ACR. It prevents nuisance tripping if particular network conditions are
causing “false” ground faults. In radial systems, directional blocking prevents nuisance tripping by blocking faults in the source
direction and only responding to faults in the load direction
Inrush Restraint
High currents during line energization is a common phenomenon for reactive loads. Sometimes, the inrush currents can cre-
ate the false conditions of over loading causing the ACR to trip. Inrush restraint raises the phase and ground threshold cur-
rents for a short period of time to allow for short duration inrush currents when closing onto a load
High-set to Lockout
Repeated closure of line under high magnitude fault conditions can put severe stress on power lines and other line equipment
which may lead to failure. To restrict the number of reclosing attempts under severe fault conditions—High set to Lockout
function is provided.
It will resist the number of Reclosing attempts by the unit when the fault current is above a desired level. Number of high set
to lockout can be separately programmed (Range—0 to 4) in Recloser from the standard duty cycle.
Measurement
• Primary current phases and earth • Primary line and phase voltages
• Secondary current phases and earth • Apparent power and power factor
RTU provide two way communication between IED (Meter or Auto Recloser) and cloud server through secure VPN
tunneling.
Cloud server provide web based HMI which is accessible remotely.
PLC
Server
Auto Recloser
HMI Meter
Accessories
• Auxiliary Supply Transformer
A pole mounted transformer can be provided where ACR has to be
installed on isolated locations
• SS7 Modem
This modem can be applied in the areas with poor internet connec-
tivity. Through this, the user can control the ACR remotely
• RTU
A GPRS/3G/4G enabled modem can be incorporated inside the
control panel for wireless transmission of data
• Space Heater
A heater with thermostat can be installed in the control cabinet for
protection against moisture
• Electrical Isolator
Visual isolation is provided is provided on the out-
going side of the ACR for maximum safety
• Surge Arrestors
Surge Arrestors can be installed on Incoming or
Outgoing side of the ACR
950mm
800mm
425mm
Dimension
Digit Parameter Information
1 Model N: Solid Dielectric
RTU PT-H-6/830
Contact us