DeltaV Distributed Control System Product Data Sheet

May 2024

DeltaV™ IS Electronic Marshalling


„ Intrinsically Safe I/O anywhere you need it
„ Integrated galvanic Isolation per channel
„ Reduces installed cost of system
„ Fully redundant architecture
„ Field mounted capable hardware
„ Plug and play I/O

The DeltaV™ CHARM I/O Card (CIOC) with IS CHARMS.

Introduction Integrated galvanic Isolation per channel: Each I/O


channel has a dedicated IS CHARM that provides both
DeltaV™ IS Electronic Marshalling delivers a new level of control
signal characterization and galvanic isolation for intrinsically
system I/O performance with unprecedented flexibility and
safe applications. IS barriers are integrated inside the IS
ease of use. The addition of Intrinsically Safe (IS) CHARMs
CHARM to provide single channel fault isolation as well as
provides significant savings in system design, installation cost
electrical isolation and energy limiting circuitry that meets
and ease of maintenance expected with Electronic Marshalling,
IEC Ex ia ratings.
with the added safety for field wiring to hazardous areas.
The reduced footprint and associated elimination of separate Reduces installed cost of system: DeltaV Electronic
barriers and the associated inter cabinet wiring makes for Marshalling helps reduce overall system cost by eliminating
a more robust installation with significant cost savings. internal cabinet cross wiring, reducing overall footprint,
simplifying I/O channel assignments, and reducing FAT
Benefits activities. Electronic Marshalling provides separation between
I&E hardware installation schedules and control strategy
Intrinsically Safe I/O anywhere you need it: DeltaV CHARM
development. Wiring can begin earlier knowing any late
I/O Card (CIOC) supports both conventional and IS CHARMs,
changes can be done without lifting a wire. Separation of
providing an unprecedented flexibility in control system I/O
the controller and I/O allows more efficient cabinet designs
topology. Using standard Ethernet infrastructure hardware
and accommodates late scope changes by adding I/O anywhere.
you can add I/O anywhere you need it. From a local I/O cabinet
Adding additional control capacity does not require re-wiring
to remote enclosures miles away, simply install the hardware
I/O. Simply assign the control modules and their I/O signals
and connect it to the DeltaV control network. Each I/O card
to the new controller, without lifting a wire.
can serve I/O signals to any of four controllers in the system
with 50 ms updates for fast, reliable control.
DeltaV Distributed Control System May 2024

Fully redundant communications: The CIOC architecture Field power is provided through a redundant 24V DC bus
is fully redundant. This starts with the two I/O cards on the to each IS CHARM. Each IS CHARM provides galvanically
carrier. The carrier has redundant communication modules isolated field power through an internal isolation transformer,
for primary and secondary network connections. There are eliminating external wiring to barriers.
two 24V DC input power connections. The carrier connects to
the IS CHARMs baseplates and provides redundant power and Product Description
communication buses to the CHARMs. Everything is redundant IS Electronic Marshalling hardware includes:
down to the individual channel.
„ CHARM I/O Carrier (DIN rail mounted and supports
Field mounted capable hardware: All components of the redundant pair of CHARM I/O Cards, redundant 24V DC
CIOC are rated for installation in Class 1/Div 2 or Zone 2 power connectivity, and redundant Ethernet
hazardous locations. The extended operating temperature communication modules).
ranges and G3 environment rating allows them to be installed
„ CHARM I/O Card (CIOC) provides communication between
in field mounted junction boxes. This further reduces the foot
CHARMs and the Ethernet I/O network to M-series, S-series,
print required in central equipment rooms, as well as reduces
and PK Controllers. The CIOC has Achilles Communications
the overall wiring infrastructure of traditional multi-core
Certification Level 1 and the redesigned CIOC2 has more
instrumentation cable.
computing power and Achilles Communications Certification
Plug and Play I/O: The DeltaV CIOC has been designed for Level 2. The CIOC2 is a drop-in replacement for the CIOC
ease of use, both in physical installation and its software tools. (v13.3.1 or later is required).
Components snap together with secure DIN-rail latches and
„ IS CHARM Baseplate (DIN rail mounted with interleaving
interlocking carrier connectors.
power and bus connectors. Supports 12 IS CHARMs and
Attach a series of 96 I/O channels to a DIN-rail in a matter their terminal blocks).
of minutes. Insert the IS CHARMs and auto sense the node
„ IS CHARM Terminal Block (removable terminal block
to create the I/O definition automatically in your DeltaV
providing terminal connections to field wiring and
configuration database. IS CHARMs using a self-keying system
physical latch for IS CHARM).
to automatically set a channel for a specific IS CHARM type
Users cannot mistakenly insert an IS CHARM into the wrong „ IS CHARMs (Characterization Module for each field signal.
terminal block. Assign all, one or any number of channels to Provides galvanic isolation, fault isolation and basic analog
a controller with a simple click or drag and drop. to digital conversion to the redundant communication bus).

IS CHARM and Terminal Block.


CHARM I/O Card (CIOC) with IS CHARMs and Baseplate Separator
in Place.

www.emerson.com/deltav 2
DeltaV Distributed Control System May 2024

„ Labeling features for baseplate and channel identification.

„ Cable Extenders that provide flexibility in carrier mounting.

„ I/O bus termination (provides bus terminations for redundant


I/O bus).

Intrinsically Safe CHARMs are designed to meet IEC EX ia level


of safety and are suitable for connecting to field devices
installed in Class 1 Division 1 Hazardous Locations or Zone 1/0
Hazardous Areas. The CHARM I/O Card and IS CHARMs are rated
for installation in a Class 1 Division 2 Hazardous location,
a Zone 2 hazardous area or in the safe area.

The CHARM I/O card carrier is mounted to the top of a vertical


DIN rail and up to eight CHARM Baseplates are mounted below
it. IS CHARM Baseplates and regular CHARM Baseplates can be
combined on the same CIOC, provided installation rules are
respected. The baseplates snap easily to the DIN rail as they
are connected to each other. The bus termination assembly is
IS CHARM Latch Mechanism.
attached at the bottom. A standard DIN-rail lock is used to keep
the entire assembly in place.
The CIOC communicates over a redundant Ethernet network
Each IS baseplate is ordered pre-loaded with 12 IS terminal with up to 4 controllers, allowing great flexibility and ease
blocks that are ready to receive field wires from 2, 3 and of system expansion. Additional controllers can be added
4-wire devices. Electronic Marshalling eliminates the need to accommodate increased control scope and I/O can be
to scramble the field wiring or to partition the I/O to match reassigned without changing the physical wiring.
signals to channel types of specific cards. Simply connect field
IS CHARMs can be added to any existing IS baseplate position
signal multi-cores in an orderly fashion as desired. Insert the
and autosensed online. Additional CIOC’s can be added online.
appropriate IS CHARM into each terminal block to complete
the field circuit and the signal is ready to be used by any one IS CHARM Types
of 4 controllers. No cross-wiring required.
A variety of analog and discrete IS CHARMs are available to
All IS CHARMs are energy limited devices that prevent the meet your specific requirements. The following IS CHARMs
possibility of an explosion, even if wires are accidently shorted are available starting with v11.3.1:
together. In addition, each IS CHARM acts as a circuit protection
„ IS AI 4-20 mA HART
device and field wiring disconnect. Each IS CHARM provides
surge protection to meet industry standards in the area of „ IS RTD
EMC. Under extreme over voltage conditions due to incorrect „ IS Thermocouple / mV
field wiring, the IS CHARM will act as a fuse to protect adjacent
channels. Signal faults are thus isolated to the single IS CHARM. „ IS AO 4-20 mA HART

IS CHARMS can be partially ejected to a locked position that „ IS DI NAMUR


disconnects the field wiring from the system to perform „ IS DO 45 mA
field maintenance actions or to remove power to a field device.

Activating the IS CHARM latch ejects the IS CHARM to the


detent position. Closing the latch locks the IS CHARM in
place and isolates the field wiring for field work.

www.emerson.com/deltav 3
DeltaV Distributed Control System May 2024

All IS CHARMs have a bi-color Power/Integrity LED that indicates


the health of the IS CHARM. The indications provide clear,
actionable instruction to the maintenance personnel.

„ Green Solid: Normal Operation

„ Green Blink: Normal awaiting configuration

„ Red Blink: Fault detected on wiring

„ Red Solid: Internal Fault detected

Discrete IS CHARMs have a Yellow LED to indicate the state


of the field signal.

All IS CHARMs meet ISA 71.04-1985 severity level G3 (harsh)


corrosion specifications.

The IS DI NAMUR CHARM supports a pulse counter with


a maximum frequency of 10 KHz.

I/O Terminal Block Options


IS CHARM Terminal Block.
IS CHARMs are designed to work with the IS Terminal Blocks,
which are light blue in color, designating the field wiring as IS CHARM Baseplates
intrinsically safe. IS CHARMs are mechanically different and
will not install in non-IS terminal blocks, ensuring there is IS CHARM baseplates are mechanically different than non-IS
no error in the installation. baseplates, ensuring there is no error in the installation of the
Terminal Blocks or CHARMs (non-IS). A baseplate separator
There are two different IS Terminal Blocks available to meet is needed on the beginning and on the end of any IS CHARM
the wiring needs of field signals. baseplate row, also in between any of the IS CHARM baseplates.
„ IS Terminal Block You can add IS CHARM baseplates to non-IS CHARM baseplates
and any of the other components, like the CIOC carrier,
„ IS Thermocouple/mV Terminal Block CHARM baseplate extenders and CHARM baseplate Terminators.
The IS Terminal Block has 4 terminals, supporting the
traditional discrete and analog 2 & 4 wire sensor/actor field ASCO Numatics 580 CHARM Node
instrumentation signals as well 2, 3 and 4 wire RTD Sensors The 580 CHARM node enables Easy solenoid valve integration
into DeltaV with Electronic Marshalling. The new 580 CHARM
The IS Thermocouple / mV Terminal Block is specially designed
node connects directly to the CIOC via redundant CHARM
for the usage with the IS Thermocouple / mV CHARM. The IS
Baseplate extender cables. DeltaV can autosense the I/O as DO
Thermocouple / mV Terminal Block and IS Thermocouple / mV
Solenoid Valve CHARMs the same way as any other CHARM is
CHARM can only be ordered as an Assembly.
autosensed in DeltaV. The ASCO Numatics 580 CHARM node
IS CHARM Keying Posts can be installed in Zone 2 hazardous areas and can be combined
with the DeltaV IS Electronic Marshalling.
The IS Terminal Blocks contain keying posts that are
automatically set and locked to the unique position of the
installed IS CHARM. The keys prevent the insertion of an
incorrect IS CHARM during maintenance activities. The IS
Terminal Blocks are shipped with the keys in a neutral position
and are set when an IS CHARM is inserted. If needed, the keys
can be manually reset to allow a channel to be re-tasked for a
different signal type.

The keying mechanism consists of two keying posts that rotate


and lock into the IS Terminal Block base. Each IS CHARM type
is assigned a unique key setting.

www.emerson.com/deltav 4
DeltaV Distributed Control System May 2024

Benefits of the new 580 CHARM Node include:

„ Redundant communications and power connections „ Expands the Electronic Marshalling I/O offering to include
to pneumatic valve manifolds. ASCO Numatics pilot valve manifolds, enhancing the concept
„ Eliminates the need for additional dedicated networks like of: “I/O Anywhere”.
Profibus-DP and simplifies system I/O mapping. „ Reduces programming and commissioning time dramatically.

Hardware Specifications
Common Environmental Specifications (all components)

Operating Temperature* -40 to 70°C (-40 to 158°F)**

Storage Temperature -40 to 85°C (-40 to 185°F)

Relative Humidity 5 to 95% , non-condensing

Protection Rating IP 20
Airborne Contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Conformal coating
Shock 10 g ½-sine wave for 11 ms
Vibration 1 mm peak-to-peak from 2 to 13.2 Hz;
0.7 g from 13.2 to 150 Hz

*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime,
see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.

**When used with copper Ethernet I/O Ports (Copper IOP). When used with the Fiber Optic I/O Ports (Fiber Optic IOP), the operating temperature range is limited to -40 to 60°C
(-40 to 140°F).

CHARM I/O Card and Carrier.

www.emerson.com/deltav 5
DeltaV Distributed Control System May 2024

Uplink Port Uplink Port

Cascade Port

Copper IOP Fiber Optic IOP

Operating Temperature -40 to 70°C (-40 to 158°F). Operating Temperature -40 to 60°C (-40 to 140°F).

CIOC Carrier Ethernet Communication Modules

IS CHARM Baseplate with Separator, IS CHARMs and Label Plates in Place.

www.emerson.com/deltav 6
DeltaV Distributed Control System May 2024

CHARM Baseplate Terminator, Top.

CHARM Baseplate Terminator, Bottom.

CHARM Baseplate Extender, Top.

CHARM Baseplate Extender, Bottom.

www.emerson.com/deltav 7
DeltaV Distributed Control System May 2024

IS CHARM.

IS CHARM Terminal Block.

www.emerson.com/deltav 8
DeltaV Distributed Control System May 2024

IS CHARM Thermocouple/mV Terminal Block.

Address Plug.

www.emerson.com/deltav 9
DeltaV Distributed Control System May 2024

Address Plug Terminal Block for IS Baseplate.

www.emerson.com/deltav 10
DeltaV Distributed Control System May 2024

CHARM I/O Card Hardware


Specifications for CHARM I/O Card Carrier

Number of I/O Cards per Carrier 2 (redundant pair)

Input Power (Redundant) 24V DC ±10% at 12 A maximum


Redundant Ethernet Connections Fiber-optic:
„ 100BASE-FX with MTRJ connectors; cable should have MTRJ
Female connector
„ Full duplex operation
„ Multi-mode - 2 km nominal distance

Copper twisted pair:


„ 10/100BASE-TX with RJ45 connectors
„ Half/Full duplex operation
„ 100 m distance

Mounting DIN rail Latch to T-type rail

Specifications for CHARM I/O Card (CIOC) and CHARM I/O Card 2 (CIOC2)

Number of I/O Channels 96 Channels, individually defined signal types

Number of I/O Clients 4 (Controllers)

Number of CIOC’s per Controller 16

Number of CIOC’s per System 300

I/O Update Rates 50ms, 100ms, 250ms, 500ms

User Memory N/A


CIOC Power (24V DC) 0.28A per redundant CIOC node
0.32A per redundant CIOC2 node
(includes two cards and two communication modules)
(individual CHARM power requirements are in addition)
CIOC Heat Dissipation 8 Watts max. per redundant CIOC node
9 Watts max. per redundant CIOC2 node
„ 2.0 Watts per CIOC
„ 2.5 Watts per CIOC2
„ 1.34 Watts per Copper Ethernet I/O Communication Port
„ 2.0 Watts per Fiberoptic I/O Communication Port

CIOC Output to CHARMs 6.3V DC redundant power, at 3.25 A maximum*

Fuse Protection (Internal) Internal Non-replaceable Fuse

Mounting 2-wide CHARM I/O Carrier

Communication Redundant Ethernet connections via CHARM I/O Carrier

Network Addressing Auto Assigned during commissioning

LED Indicators

Green – Power Indicates DC power is applied

Red – Error Indicates an error condition

Green – Active/Standby Indicates operating mode of each CIOC

Yellow Flashing – Pri./Sec. CN Indicates valid control network communication

*Actual CIOC Output to CHARMs is dependent on number of installed CHARMs.

www.emerson.com/deltav 11
DeltaV Distributed Control System May 2024

IS CHARMs Baseplate Hardware


Specifications for IS CHARM Baseplate

Number of Channels per Baseplate 12

Number of Base Plates per CIOC 8

Addressing One address plug (1 through 8)


Terminal Blocks „ Standard IS Terminal Block (Light Blue)
„ IS Thermocouple / mV Terminal Block (Light Blue)
Shield Connections 1 screw cage terminal per channel, plus 1 for cable shield
0.32 – 2.5 mm2 / 22 – 14 AWG
Gold plated connectors for shield continuity
Wire Strip Length 7 – 9 mm / 0.28 – 0.36 in.

Mounting DIN rail Latch to T-type rail


Specifications for IS Baseplate Termination, Top and Bottom
Shield Drain Wire Connections 2 screw cage terminals
0.32 – 2.5 mm2 / 22 – 14 AWG
Wire Strip Length 7 – 9 mm / 0.28 – 0.36 in.

Specifications for Baseplate Extenders, Top and Bottom


Primary Bus Connection 9-pin D-shell,
Primary RS-485 communications bus
Primary 24V DC field power
Primary CHARM power
Secondary Bus Connection 9-pin D-shell,
Secondary RS-485 communications bus
Secondary 24V DC field power
Secondary CHARM power
Specifications for Extender Cables
Maximum Bus Length A maximum of four extender pairs can be used and only one
extender pair can exceed 0.5 meters (1.64 feet).
Available Cable Lengths 2 m, 1 m, 0.5 m (6.7 ft, 3.3 ft, 1.6 ft )
Specifications for IS Terminal Block
Number of Connections 4 screw cage terminals
0.32 – 2.5 mm2 / 22 – 14 AWG
Strip Length 7 – 9 mm / 0.28 – 0.36 in.

Maximum Current 45 mA at 28V DC max.

Color Light blue

www.emerson.com/deltav 12
DeltaV Distributed Control System May 2024

Specifications for IS Thermocouple / mV Terminal Block


Number of Connections 2 screw cage terminals
0.32 – 2.5 mm2 / 22 – 14 AWG
Strip Length 7 – 9 mm / 0.28 – 0.36 in.

Maximum Current 45 mA at 28V DC max.*

Color Light blue

Specifications for Address Plug Terminal Block

Number of Connections None

Color Black

*Actual Current draw is determined by type of CHARM and associated field devices.

IS Analog Input CHARM


Specifications for IS AI 4-20 mA HART CHARM
Sensor Types 4-20 mA with or without HART
Supports 2-wire and 4-wire device types
Nominal Signal Range (Span) 4-20 mA, (0-20 mA optional)

Full Signal Range 0 to 22 mA

Input Impedance 360 Ω

Field Power (2-Wire) 16.0V (min) at 20 mA


Accuracy Over Temperature Range 0.1% of span (0-60°C)
0.25% of span (over -40 -70°C)
Repeatability 0.05% of span

Resolution 16bit A/D converter

Calibration None required

DC/50/60 Hz Common Mode Rejection N/A


Isolation Galvanically isolated according to EN 60079-11
Voltage peak value 375V DC
CHARM Power Req. 60 mA max @ 24V DC ±10%

CHARM Heat Dissipation 0.86 W


HART Support HART v7 pass-through for AMS
HART v7 variable and device status available to control
HART Data Update Rates Typically less than one second but dependent on HART
communication loading and the capability of the HART device

www.emerson.com/deltav 13
DeltaV Distributed Control System May 2024

Simplified Circuit and Connection Diagrams for IS AI-CHARM4 to 20 mA HART Two Wire and Four Wire transmitters.

www.emerson.com/deltav 14
DeltaV Distributed Control System May 2024

IS RTD CHARM
Specifications for IS RTD Input CHARM

Sensor Types RTD input (Types listed in Table)

Sensor Configuration 2 wire, 3 wire, or 4 wire

Full Scale Signal Range See table below

Accuracy See table below

Repeatability 0.05% of span

Resolution 24 bit A/D converter / depends upon the sensor type

Calibration None required


Sensor Excitation Current 0.5 mA in 2-wire and 4 wire configurations
0.25 mA in 3-wire
DC/50/60 Hz Common Mode Rejection 90dB typical
Isolation Galvanically isolated according to EN 60079-11
Voltage peak value 375V DC
Open Sensor Detection Yes

CHARM Power Req. 23 mA max @ 24V DC

CHARM Heat Dissipation 0.60 W

RTD, ohms Sensor Type Specifications


Sensor Operating 25° Reference Temperature Drift
Resolution
Type Range Accuracy (4-wire) (4-wire)
Pt100 -200 to 850°C ± 0.50°C ± 0.015°C/°C ~0.02°C
Pt200 -200 to 850°C ± 0.40°C ± 0.014°C/°C ~0.02°C
Pt500 -200 to 850°C ± 0.34°C ± 0.014°C/°C ~0.02°C
Pt1000 -200 to 260°C ± 0.14°C ± 0.006°C/°C ~0.01°C
Ni120 -80 to 260°C ± 0.18°C ± 0.003°C/°C ~0.01°C
Ni100 -80 to 260°C ± 0.12°C ± 0.003°C/°C ~0.01°C
Ni200 -80 to 260°C ± 0.11°C ± 0.003°C/°C ~0.01°C
Ni500 -80 to 260°C ± 0.08°C ± 0.003°C/°C ~0.01°C
Ni1000 -80 to 140°C ± 0.06°C ± 0.003°C/°C ~0.01°C
Cu10 -200 to 260°C ± 0.70°C ± 0.020°C/°C ~0.01°C
Resistance/User Defined* 0 to 2,000 Ω ± 0.50 Ω ± 0.020 Ω/°C ~0.031 Ω
*The Callendar-Van Dusen linearization equation can be used with user defined Pt RTDs. Refer to Recommended I/O Practices in DeltaV Books online for usage information.

www.emerson.com/deltav 15
DeltaV Distributed Control System May 2024

Simplified Circuit and Connection Diagrams for IS RTD CHARM.

www.emerson.com/deltav 16
DeltaV Distributed Control System May 2024

IS Thermocouple/mV CHARM
Specifications for IS Thermocouple/mV Input CHARM
Sensor Types
„ Thermocouple B, E, J, K, N, R, S, T, uncharacterized
„ mV Low level voltage source (±20 mV, ±50 mV, and ±100 mV)
Full Scale Signal Range See table below

Accuracy See table below

Repeatability 0.05% of span

Resolution 24 Bit A/D converter / depends upon the sensor type

Calibration None required


Cold Junction Compensation(CJC)
„ Accuracy ± 0.7°C
„ Range -40 to 85°C
Temperature Drift 0.03°C/°C
Isolation Galvanically isolated according to EN 60079-11
Voltage peak value 375V DC
Open sensor Detection Yes

CHARM Power Req. 23 mA max @ 24V DC

CHARM Heat Dissipation 0.60 W

Sensor Type Specifications


Sensor 25° Reference Temperature Nominal Full Operating
Type Accuracy1 Drift Resolution Scale Range
B ± 2.50°C ± 0.07 °C/°C ~0.024°C 0 to 1820°C 250 to 400°C
± 1.70°C ± 0.05 °C/°C 400 to 1820°C
E ± 0.60°C ± 0.03°C/°C ~0.018°C -270 to 1000°C -200 to 1000°C

J ± 0.70°C ± 0.03°C/°C ~0.022°C -210 to 1200°C -200 to 1200°C


K ± 1.20°C ± 0.05°C/°C ~0.025°C -270 to 1372°C -200 to 1370°C

N ± 1.10°C ± 0.04°C/°C ~0.024°C -270 to 1300°C -200 to 1300°C

R ± 1.70°C ± 0.06°C/°C ~0.028°C -50 to 1768°C -50 to 1767°C

S ± 1.90°C ± 0.07°C/°C ~0.028°C -50 to 1768°C -50 to 1767°C

T ± 0.70°C ± 0.02°C/°C ~0.01°C -270 to 400°C -200 to 400°C

± 100 mV 50 μV ± 2.5 μV/°C ~0.0031mV -100 to 100 mV -100 to 100 mV

± 50 mV 40 μV ± 1.7 μV/°C ~0.0015mV -50 to 50 mV -50 to 50 mV

± 20 mV 20 μV ± 0.8 μV/°C ~0.0006mV -20 to 20 mV -20 to 20 mV


1
Total error is made up of the 25°C reference accuracy value, plus the CJC accuracy value, plus the sensor accuracy value.

www.emerson.com/deltav 17
DeltaV Distributed Control System May 2024

Simplified Circuit and Connection Diagram for IS Thermocouple/mV CHARM with IS Thermocouple/mV Terminal Block.

www.emerson.com/deltav 18
DeltaV Distributed Control System May 2024

IS Analog Output CHARM


Specifications for IS AO 4-20 mA HART CHARM

Sensor Types 4 to 20 mA with or without HART

Nominal Signal Range (Span) 4-20 mA, (0-20 mA optional)

Full Signal Range 0 to 22 mA

Load Resistance 750 Ohm max.

Voltage to Load 15V (min) @ 20 mA


Accuracy Over Temperature Range 0.25% of span (0 to 60°C)
0.5% of span (-40 to 70°C)
Resolution 16 bit A/D converter

Calibration None required


Isolation Galvanically isolated according to EN 60079-11
Voltage peak value 375V DC
CHARM Power Req. 56 mA max @ 24V DC ±10%

CHARM Heat Dissipation 1.1 W


HART Support HART v7 pass-through for AMS
HART v7 variable and device status available to control
HART Data Update Rates Typically less than one second but dependent on HART
communication loading and the capability of the HART device

Simplified Circuit and Connection Diagram for IS AO HART CHARM.

www.emerson.com/deltav 19
DeltaV Distributed Control System May 2024

IS Discrete Input CHARM


Specifications for IS DI NAMUR CHARM

Sensor Types NAMUR sensors, dry contacts

Detection Level for On >2.1 mA

Detection Level for Off <1.2 mA

Channel Impedance 1kOhm ± 10%

Wetting Voltage 8V DC ± 1V DC
Fault detection capable with NAMUR sensor or with an optional „ Guaranteed short circuit: <100 Ω
field resistor pack* as shown on Option 2 in diagram below „ Guaranteed good status: 360 Ω to 20 kΩ
(Option 1 in diagram below is not fault detection capable) „ Guaranteed open circuit: > 75 kΩ
Configurable Channel Types:
„ Discrete Input Dry contact or discrete state sensor changing <2 Hz
„ Pulse Count Pulse train 0.1 Hz to 10 KHz, 50 µsec min pulse width
Isolation Galvanically isolated according to EN 60079-11
Voltage peak value 375V DC
CHARM Power Req. 28 mA max @ 24V DC ±10%

CHARM Heat Dissipation 0.57 W

*VS6904 End of Line Resistance Module can be used for option 2, see DeltaV SIS Conditioning Components PDS for more info.

Simplified Circuit and Connection Diagram for IS DI NAMUR CHARM.

www.emerson.com/deltav 20
DeltaV Distributed Control System May 2024

IS Discrete Output CHARM


Specifications for IS DO 45 mA CHARM

Device Type Solenoid Coils

On State Output Rating 22V to 25V (open circuit); 11V at 45 mA

Off State Leakage Current 230μA


Line Fault Detection „ Guaranteed short circuit: <100 Ω load
„ Guaranteed good status: 150 Ω to 20 kΩ load
„ Guaranteed open circuit: >25 kΩ load
Configurable Output Behavior „ Momentary output
„ Continuous pulse output
„ Line fault testing
Line Fault Test Timing 180 to 220 µsec
Isolation Galvanically isolated according to EN 60079-11
Voltage peak value 375V DC
CHARM Power Req. 78 mA max @ 24V DC ±10%

CHARM Heat Dissipation 1.4 W

Simplified Circuit and Connection Diagram for IS DO 45 mA CHARM.

www.emerson.com/deltav 21
DeltaV Distributed Control System May 2024

ASCO Numatics 580 CHARM Node


Specifications for ASCO Numatics 580 CHARM Node

Bus Power 6.3V DC at 100mA

Valve Power 24V DC at 1.07A

Power and Bus Connector A-Coded 5 Pin M12 Male

LEDs Module Status and Network Status

Operating Temperature Range -10 to 115°F (-23 to 46°C)

Operating Humidity 95% Relative Humidity, Non-condensing

Vibration Shock EC 60068-2-27, IEC 60068-2-6

Moisture IP65 Certified

Maximum Valve Solenoid Outputs 48

Diagnostics Power, short, open load conditions are monitored

More Information https://www.emerson.com/en-gb/catalog/aventics-580-charm-en-gb*

*For hazardous area installations, please refer to installation instructions from ASCO.

580 CHARM Node.

www.emerson.com/deltav 22
DeltaV Distributed Control System May 2024

CIOC
Carrier

Address Address
Plug 1 Plug 3

CHARM CHARM
Baseplate 1 Baseplate 3

Address Address
Plug 2 Plug 4

CHARM CHARM
Baseplate 2 Baseplate 4

Bottom
CHARM
Column
Extenders

Connection to DeltaV IS Electronic Marshalling.

System Compatibility Control modules can be assigned to any controller and


inter-controller references are fully supported between
DeltaV IS CHARM I/O hardware requires:
different types of controllers.
„ SD Plus Controllers with DeltaV v11.3.1 or later software „ CHARM I/O Card: IS CHARMs installed on IS CHARM
„ SX Controllers with DeltaV v11.3.1 or later software baseplates can be connected to a CHARM I/O Card carrier,
„ SQ Controllers with v11.3.1 or later software using a baseplate separator and a special fuse in each of
the two power supply lines of the CHARM I/O carrier.
„ MD Plus Controllers with DeltaV v14.3 or later software
„ Non-IS CHARM Baseplates: Non-IS CHARM baseplates
„ MQ Controllers with DeltaV v14.3 or later software
can be extended with CHARM baseplates, using a
„ MX Controllers with DeltaV v14.3 or later software baseplate separator.
„ PK Controllers with DeltaV v14.3 or later software „ IS CHARM Baseplates: IS CHARM baseplates cannot
When assigning CHARMs to MD Plus and SD Plus controllers, be extended with non-IS CHARM Baseplates but can be
make sure to evaluate the Time Utilization Chart on the extended with the ASCO Numatics 580 CHARM Node.
controller in DeltaV Diagnostics to ensure the additional „ Baseplate Extender: IS CHARM baseplates can be connected
communication load can be handled by the controller. to CHARM baseplate extenders using baseplate separators
S-series and M-series controllers can be installed on the „ Baseplate Terminator: IS CHARM baseplates can be
same DeltaV Area Control Network in v11.3 and beyond. connected to CHARM baseplate terminators using
PK Controllers can be installed on the same DeltaV Area baseplate separators.
Control network in v14.3 and beyond. Refer to installation instructions for rules governing IS wiring.

www.emerson.com/deltav 23
DeltaV Distributed Control System May 2024

Certifications Hazardous Area/Location


The following certifications are available for DeltaV IS Electronic DeltaV IS Electronic Marshalling can be installed and used based
Marshalling (see actual certificates for exact certifications for on the following Standards (see actual certificates for exact
each product): product markings for each product):

„ CE „ FM (USA)

EMC - EN 61326-1 Installation:

„ FM Class I, Division 2, Groups A, B, C, D, T4

FM 3600 Class I, Zone 2 AEx ec IIC T4 Gc

FM 3610
Field Circuits:
FM 3611
Class I, II, III, Division 1, Group A-G, T4
ANSI/ISA 60079-0
Class I, Zone 2:
ANSI/ISA 60079-7
AEx ec [ia Ga] IIC T4 Gc
ANSI/ISA 60079-11
AEx ec [ia IIIC Da] IIC T4 Gc
„ CSA
„ cFM (Canada)
CSA C22.2 No. 213
Installation:
CSA-C22.2 No. 61010-1
Class I, Division 2, Groups A, B, C, D, T4
CSA-C22.2 No. 60079-0
Class I, Zone 2 Ex ec IIC T4 Gc
CSA-C22.2 No. 60079-7
Field Circuits:
CSA-C22.2 No. 60079-11
Class I, II, III, Division 1, Group A-G, T4
„ ATEX
Class I, Zone 2:
EN60079-0
Ex ec [ia Ga] IIC T4 Gc
EN60079-7
Ex ec [ia IIIC Da] IIC T4 Gc
EN60079-11
„ ATEX
„ IEC-Ex
II 3(1) G Ex ec [ia Ga] IIC T4 Gc
IEC60079-0
II 3 G (1D) Ex ec [ia IIIC Da] IIC Gc
IEC60079-7

IEC60079-11 „ IEC-Ex
„ Marine Certifications: IACS E10 II 3(1) G Ex ec [ia Ga] IIC T4 Gc
DNV Marine Certificate II 3 G (1D) Ex ec [ia IIIC Da] IIC Gc
„ Achilles Communications Certification
Regarding the Installation instructions please refer to the following Documents:
CIOC: Level 1 (v13.3.1, v14.FP1) ATEX/IECEx Installation Instructions IS-CHARM Subsystem 12P6523
Control Drawing DeltaV IS-CHARMs Subsystem 12P6122
CIOC2: Level 2 (v14.3, v14.FP1) Control Drawing DeltaV IS-CHARMs 12P6123

www.emerson.com/deltav 24
DeltaV Distributed Control System May 2024

Ordering Information
CHARM I/O CARD

Description Model Number


Redundant CIOC2 with Copper Ethernet, includes redundant pair of CHARM I/O Card 2, CHARM I/O SE6505T01*
Carrier with Screw Terminals, Copper I/O Ports, a Baseplate Identifier and a Baseplate Separation Wall
Redundant CIOC2 with fiber optics Ethernet, includes redundant pair of CHARM I/O Card 2, CHARM I/O SE6505T02
Carrier with Screw Terminals, Fiberoptic I/O Ports, a Baseplate Identifier and a Baseplate Separation Wall
Redundant CIOC Carrier Assembly with Copper Ethernet, includes CHARM I/O Carrier with SE6501T05*
Screw Terminals, Copper I/O Ports, a Baseplate Identifier and a Baseplate Separation Wall
Redundant CIOC Carrier Assembly with fiber optics Ethernet, includes CHARM I/O Carrier with SE6501T06
Screw Terminals, Fiber-Optic I/O Ports, a Baseplate Identifier and a Baseplate Separation Wall
Redundant CIOC2, includes 2 CHARMs I/O Card 2, (Order these with standard cabinets) SE6504

IS CHARM Baseplates
Description Model Number
IS CHARMS Baseplate Assembly with Standard IS CHARM Terminal Blocks, includes IS CHARMS SE4608T01
Baseplate, IS CHARM Address Terminal Block, 12 IS CHARM Standard Terminal blocks and a Baseplate
Separation Wall
CHARM I/O Baseplate Address Plugs

Description Model Number

Addressing Plugs, includes Address Plugs 1 through 8 SE4602

Addressing Plugs, includes Address Plugs 1 through 4 SE4613

CHARM I/O Baseplate Extender, Terminator & Cables

Description Model Number


CHARMs Baseplate Extender with Cable Connectors, Top (Male) SE4603T05
includes a Baseplate Identifier and a Baseplate Separation Wall
CHARMs Baseplate Extender with Cable Connectors, Bottom (Female) SE4603T06
includes a Baseplate Identifier and a Baseplate Separation Wall
CHARMs Baseplate Terminator, Top (Male) SE4604T03
includes a Baseplate Identifier and a Baseplate Separation Wall
CHARMs Baseplate Terminator, Bottom (Female) SE4604T04
includes a Baseplate Identifier and a Baseplate Separation Wall
CHARMs Baseplate Cables, includes two 0.5m cables SE4605T02

CHARMs Baseplate Cables, includes two 1m cables SE4605T03

CHARMs Baseplate Cables, includes two 2m cables SE4605T04

*The copper IOPs in this bundle are only supported in v13.3.1 and later and doesn’t have marine certifications yet. If marine certification is required or
if it is intended to be used for earlier versions, please request KL1601X1-BA1 and order the CIOC Carrier as KL4101X1-BA1.

Each vertical DIN rail requires a DIN Rail stop to lock baseplates in position. Order VE4054DRS, which is a box of 5.

www.emerson.com/deltav 25
DeltaV Distributed Control System May 2024

Ordering Information
IS CHARMs

Description Model Number

IS DI NAMUR SE4305T01

IS DO 45 mA SE4306T01

IS AI 4-20 mA HART SE4307T01

IS AO 4-20 mA HART SE4308T01

IS Thermocouple/mV SE4309T01

IS RTD SE4310T01

IS CHARMs and IS Terminal Block Assembly’s

Description Model Number

IS Thermocouple/mV CHARM with IS Thermocouple/mV Terminal Block SE4309T51

Additional Ordering Information for IS CHARM Protection Cover


IS CHARM Protection Cover

Description Model Number

IS CHARM Protection Cover; Package of 12 SE6104

Simplified Circuit and Connection Diagram for IS CHARM Protection Cover.

When the I.S. CHARM Protection Cover is installed, all terminals on the I.S. CHARM Terminal Block are shortened! The shortened
Terminals can be connected to Chassis Ground, while allowing the ground to be Daisy chained to the next I.S. CHARM Terminal
block, where the next I.S. CHARM Protection Cover got installed.

www.emerson.com/deltav 26
DeltaV Distributed Control System May 2024

Prerequisites
DeltaV IS Electronic Marshalling hardware requires DeltaV v11.3.1 or later software. Assigning CHARMs to MD Plus, MQ, MX,
and PK Controllers is supported in DeltaV v14.3 and later, but is not supported on M-series Controller Interfaces to PROVOX
and RS3.

CHARM I/O Card 2 (CIOC2) requires DeltaV v13.3.1 or later software. Hotfix is required for v13.3.1 and v13.3.2.

Electronic Marshalling requires use of DeltaV Smart Switches between controllers and CIOCs, please refer to Network
Considerations for M-series with Electronic Marshalling White Paper when adding Electronic Marshalling to M-series systems.

IS CHARM FUSE

Description Model Number

Fuse Holder and Fuse Assembly for 24V DC Power Supply of CHARM I/O CARD SE4610T01*

*Two of these Fuse Assemblies have to be ordered with any SE6505T01 or SE6505T02, when used with IS CHARM baseplates.

Outside Dimensions of the Fuse Holder.

www.emerson.com/deltav 27
DeltaV Distributed Control System May 2024

CHARM I/O Spare Part Ordering Information


CHARM I/O Spare Parts

Description Model Number

Power Terminal Plug for CHARM I/O Carrier KJ4005X1-BF1

I/O Port Switch Module; Copper; for CIOC Carriers KL1601X1-BB1*

I/O Port Switch Module; Fiber; for CIOC Carriers KL1602X1-BA1**

*Doesn’t have marine certification yet and is only supported on v13.3.1 and later. If marine certifiation is required or replacement is needed for earlier versions,
please request KL1601X1-BA1.
** Fiber Optic Ethernet I/O Ports are not cascade able.

IS CHARM I/O Labeling Ordering Information


IS CHARM I/O Labeling Parts

Description Model Number

Channel Identifier Labels for Intrinsically-Safe CHARM Baseplates; Package of 8 SE4609T01

IS Charm Baseplate Separation Wall; Package of 9 SE4609T02

Replacement Fuse for SE4610T01 Fuseholder Assembly KL4510X1-FA1

Replacement Fuseholder for SE4610T01 Fuseholder Assembly KL4510X1-GA1

©2024, Emerson. All rights reserved.


The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
a mark of one of the Emerson family of companies. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while
diligent efforts were made to ensure their accuracy, they are not to be construed as warranties
or guarantees, express or implied, regarding the products or services described herein or their
use or applicability. All sales are governed by our terms and conditions, which are available on
Contact Us request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/contactus at any time without notice.