DeltaV IS Electronic Marshalling Product Data Sheet (PDS)
DeltaV IS Electronic Marshalling Product Data Sheet (PDS)
May 2024
Fully redundant communications: The CIOC architecture Field power is provided through a redundant 24V DC bus
is fully redundant. This starts with the two I/O cards on the to each IS CHARM. Each IS CHARM provides galvanically
carrier. The carrier has redundant communication modules isolated field power through an internal isolation transformer,
for primary and secondary network connections. There are eliminating external wiring to barriers.
two 24V DC input power connections. The carrier connects to
the IS CHARMs baseplates and provides redundant power and Product Description
communication buses to the CHARMs. Everything is redundant IS Electronic Marshalling hardware includes:
down to the individual channel.
CHARM I/O Carrier (DIN rail mounted and supports
Field mounted capable hardware: All components of the redundant pair of CHARM I/O Cards, redundant 24V DC
CIOC are rated for installation in Class 1/Div 2 or Zone 2 power connectivity, and redundant Ethernet
hazardous locations. The extended operating temperature communication modules).
ranges and G3 environment rating allows them to be installed
CHARM I/O Card (CIOC) provides communication between
in field mounted junction boxes. This further reduces the foot
CHARMs and the Ethernet I/O network to M-series, S-series,
print required in central equipment rooms, as well as reduces
and PK Controllers. The CIOC has Achilles Communications
the overall wiring infrastructure of traditional multi-core
Certification Level 1 and the redesigned CIOC2 has more
instrumentation cable.
computing power and Achilles Communications Certification
Plug and Play I/O: The DeltaV CIOC has been designed for Level 2. The CIOC2 is a drop-in replacement for the CIOC
ease of use, both in physical installation and its software tools. (v13.3.1 or later is required).
Components snap together with secure DIN-rail latches and
IS CHARM Baseplate (DIN rail mounted with interleaving
interlocking carrier connectors.
power and bus connectors. Supports 12 IS CHARMs and
Attach a series of 96 I/O channels to a DIN-rail in a matter their terminal blocks).
of minutes. Insert the IS CHARMs and auto sense the node
IS CHARM Terminal Block (removable terminal block
to create the I/O definition automatically in your DeltaV
providing terminal connections to field wiring and
configuration database. IS CHARMs using a self-keying system
physical latch for IS CHARM).
to automatically set a channel for a specific IS CHARM type
Users cannot mistakenly insert an IS CHARM into the wrong IS CHARMs (Characterization Module for each field signal.
terminal block. Assign all, one or any number of channels to Provides galvanic isolation, fault isolation and basic analog
a controller with a simple click or drag and drop. to digital conversion to the redundant communication bus).
www.emerson.com/deltav 2
DeltaV Distributed Control System May 2024
www.emerson.com/deltav 3
DeltaV Distributed Control System May 2024
www.emerson.com/deltav 4
DeltaV Distributed Control System May 2024
Redundant communications and power connections Expands the Electronic Marshalling I/O offering to include
to pneumatic valve manifolds. ASCO Numatics pilot valve manifolds, enhancing the concept
Eliminates the need for additional dedicated networks like of: “I/O Anywhere”.
Profibus-DP and simplifies system I/O mapping. Reduces programming and commissioning time dramatically.
Hardware Specifications
Common Environmental Specifications (all components)
Protection Rating IP 20
Airborne Contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Conformal coating
Shock 10 g ½-sine wave for 11 ms
Vibration 1 mm peak-to-peak from 2 to 13.2 Hz;
0.7 g from 13.2 to 150 Hz
*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime,
see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.
**When used with copper Ethernet I/O Ports (Copper IOP). When used with the Fiber Optic I/O Ports (Fiber Optic IOP), the operating temperature range is limited to -40 to 60°C
(-40 to 140°F).
www.emerson.com/deltav 5
DeltaV Distributed Control System May 2024
Cascade Port
Operating Temperature -40 to 70°C (-40 to 158°F). Operating Temperature -40 to 60°C (-40 to 140°F).
www.emerson.com/deltav 6
DeltaV Distributed Control System May 2024
www.emerson.com/deltav 7
DeltaV Distributed Control System May 2024
IS CHARM.
www.emerson.com/deltav 8
DeltaV Distributed Control System May 2024
Address Plug.
www.emerson.com/deltav 9
DeltaV Distributed Control System May 2024
www.emerson.com/deltav 10
DeltaV Distributed Control System May 2024
Specifications for CHARM I/O Card (CIOC) and CHARM I/O Card 2 (CIOC2)
LED Indicators
www.emerson.com/deltav 11
DeltaV Distributed Control System May 2024
www.emerson.com/deltav 12
DeltaV Distributed Control System May 2024
Color Black
*Actual Current draw is determined by type of CHARM and associated field devices.
www.emerson.com/deltav 13
DeltaV Distributed Control System May 2024
Simplified Circuit and Connection Diagrams for IS AI-CHARM4 to 20 mA HART Two Wire and Four Wire transmitters.
www.emerson.com/deltav 14
DeltaV Distributed Control System May 2024
IS RTD CHARM
Specifications for IS RTD Input CHARM
www.emerson.com/deltav 15
DeltaV Distributed Control System May 2024
www.emerson.com/deltav 16
DeltaV Distributed Control System May 2024
IS Thermocouple/mV CHARM
Specifications for IS Thermocouple/mV Input CHARM
Sensor Types
Thermocouple B, E, J, K, N, R, S, T, uncharacterized
mV Low level voltage source (±20 mV, ±50 mV, and ±100 mV)
Full Scale Signal Range See table below
www.emerson.com/deltav 17
DeltaV Distributed Control System May 2024
Simplified Circuit and Connection Diagram for IS Thermocouple/mV CHARM with IS Thermocouple/mV Terminal Block.
www.emerson.com/deltav 18
DeltaV Distributed Control System May 2024
www.emerson.com/deltav 19
DeltaV Distributed Control System May 2024
Wetting Voltage 8V DC ± 1V DC
Fault detection capable with NAMUR sensor or with an optional Guaranteed short circuit: <100 Ω
field resistor pack* as shown on Option 2 in diagram below Guaranteed good status: 360 Ω to 20 kΩ
(Option 1 in diagram below is not fault detection capable) Guaranteed open circuit: > 75 kΩ
Configurable Channel Types:
Discrete Input Dry contact or discrete state sensor changing <2 Hz
Pulse Count Pulse train 0.1 Hz to 10 KHz, 50 µsec min pulse width
Isolation Galvanically isolated according to EN 60079-11
Voltage peak value 375V DC
CHARM Power Req. 28 mA max @ 24V DC ±10%
*VS6904 End of Line Resistance Module can be used for option 2, see DeltaV SIS Conditioning Components PDS for more info.
www.emerson.com/deltav 20
DeltaV Distributed Control System May 2024
www.emerson.com/deltav 21
DeltaV Distributed Control System May 2024
*For hazardous area installations, please refer to installation instructions from ASCO.
www.emerson.com/deltav 22
DeltaV Distributed Control System May 2024
CIOC
Carrier
Address Address
Plug 1 Plug 3
CHARM CHARM
Baseplate 1 Baseplate 3
Address Address
Plug 2 Plug 4
CHARM CHARM
Baseplate 2 Baseplate 4
Bottom
CHARM
Column
Extenders
www.emerson.com/deltav 23
DeltaV Distributed Control System May 2024
CE FM (USA)
FM 3610
Field Circuits:
FM 3611
Class I, II, III, Division 1, Group A-G, T4
ANSI/ISA 60079-0
Class I, Zone 2:
ANSI/ISA 60079-7
AEx ec [ia Ga] IIC T4 Gc
ANSI/ISA 60079-11
AEx ec [ia IIIC Da] IIC T4 Gc
CSA
cFM (Canada)
CSA C22.2 No. 213
Installation:
CSA-C22.2 No. 61010-1
Class I, Division 2, Groups A, B, C, D, T4
CSA-C22.2 No. 60079-0
Class I, Zone 2 Ex ec IIC T4 Gc
CSA-C22.2 No. 60079-7
Field Circuits:
CSA-C22.2 No. 60079-11
Class I, II, III, Division 1, Group A-G, T4
ATEX
Class I, Zone 2:
EN60079-0
Ex ec [ia Ga] IIC T4 Gc
EN60079-7
Ex ec [ia IIIC Da] IIC T4 Gc
EN60079-11
ATEX
IEC-Ex
II 3(1) G Ex ec [ia Ga] IIC T4 Gc
IEC60079-0
II 3 G (1D) Ex ec [ia IIIC Da] IIC Gc
IEC60079-7
IEC60079-11 IEC-Ex
Marine Certifications: IACS E10 II 3(1) G Ex ec [ia Ga] IIC T4 Gc
DNV Marine Certificate II 3 G (1D) Ex ec [ia IIIC Da] IIC Gc
Achilles Communications Certification
Regarding the Installation instructions please refer to the following Documents:
CIOC: Level 1 (v13.3.1, v14.FP1) ATEX/IECEx Installation Instructions IS-CHARM Subsystem 12P6523
Control Drawing DeltaV IS-CHARMs Subsystem 12P6122
CIOC2: Level 2 (v14.3, v14.FP1) Control Drawing DeltaV IS-CHARMs 12P6123
www.emerson.com/deltav 24
DeltaV Distributed Control System May 2024
Ordering Information
CHARM I/O CARD
IS CHARM Baseplates
Description Model Number
IS CHARMS Baseplate Assembly with Standard IS CHARM Terminal Blocks, includes IS CHARMS SE4608T01
Baseplate, IS CHARM Address Terminal Block, 12 IS CHARM Standard Terminal blocks and a Baseplate
Separation Wall
CHARM I/O Baseplate Address Plugs
*The copper IOPs in this bundle are only supported in v13.3.1 and later and doesn’t have marine certifications yet. If marine certification is required or
if it is intended to be used for earlier versions, please request KL1601X1-BA1 and order the CIOC Carrier as KL4101X1-BA1.
Each vertical DIN rail requires a DIN Rail stop to lock baseplates in position. Order VE4054DRS, which is a box of 5.
www.emerson.com/deltav 25
DeltaV Distributed Control System May 2024
Ordering Information
IS CHARMs
IS DI NAMUR SE4305T01
IS DO 45 mA SE4306T01
IS Thermocouple/mV SE4309T01
IS RTD SE4310T01
When the I.S. CHARM Protection Cover is installed, all terminals on the I.S. CHARM Terminal Block are shortened! The shortened
Terminals can be connected to Chassis Ground, while allowing the ground to be Daisy chained to the next I.S. CHARM Terminal
block, where the next I.S. CHARM Protection Cover got installed.
www.emerson.com/deltav 26
DeltaV Distributed Control System May 2024
Prerequisites
DeltaV IS Electronic Marshalling hardware requires DeltaV v11.3.1 or later software. Assigning CHARMs to MD Plus, MQ, MX,
and PK Controllers is supported in DeltaV v14.3 and later, but is not supported on M-series Controller Interfaces to PROVOX
and RS3.
CHARM I/O Card 2 (CIOC2) requires DeltaV v13.3.1 or later software. Hotfix is required for v13.3.1 and v13.3.2.
Electronic Marshalling requires use of DeltaV Smart Switches between controllers and CIOCs, please refer to Network
Considerations for M-series with Electronic Marshalling White Paper when adding Electronic Marshalling to M-series systems.
IS CHARM FUSE
Fuse Holder and Fuse Assembly for 24V DC Power Supply of CHARM I/O CARD SE4610T01*
*Two of these Fuse Assemblies have to be ordered with any SE6505T01 or SE6505T02, when used with IS CHARM baseplates.
www.emerson.com/deltav 27
DeltaV Distributed Control System May 2024
*Doesn’t have marine certification yet and is only supported on v13.3.1 and later. If marine certifiation is required or replacement is needed for earlier versions,
please request KL1601X1-BA1.
** Fiber Optic Ethernet I/O Ports are not cascade able.