BM 2023
BM 2023
Features: BM000
• Mounts easy on round & square shaft (with option –8) BM020
• External clutch for manual adjustments BM060
• Maintenance free BM080
• Position indicator
BM000F
BM020F
• Control signal fully programmable
BM060F
• The fastest actuator of the world (model BM_ _ _FF)
BM080F
• Fail safe by Enerdrive System1 (on model 060 & 080) BM000FF
• Auxiliary switches (on model 020 & 080) BM020FF
BM060FF
BM080FF
BM000FF
BM060FF
BM020FF
BM080FF
BM000F
BM060F
BM020F
BM080F
BM000
BM060
BM020
BM080
Technical
Data
Dimensions
Dimension Inches (in) Metric (mm)
A 1.50 38.1
B 3.64 92.5
C 6.60 167.5
model 000 & 060 3.02 76.8
D
model 020 & 080 3.81 96.8
1
Enerdrive System U.S.A. Patent #5,278,454
BM-210802 1
BM Series Actuators
Specification and Installation Instructions
Caution
We strongly recommend that all Neptronic® products be wired to a separate transformer and that transformer shall service only Neptronic® products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment. When multiple actuators are wired on a single transformer, polarity must be observed. Long
wiring runs create voltage drop which may affect the actuator performance.
Mechanical Installation
Wiring Diagrams
Analog PWM
1 2 3 4 5 1 2 3 4 5
FEEDBACK FEEDBACK
COMMON (-) COMMON (-)
4 to 20 mA 4 to 20 mA
SUPPLY (+) 2 to 10 Vdc SUPPLY (+) PWM CONTROL SIGNAL
For 4 to 20mA control signal, connect supplied 500 Ohm resistor between
pins 1 and 3.
For 2 to 10Vdc feedback signal, connect supplied 500 Ohm resistor
between pins 1 and 5.
3-wire/Digital 2 positions 4-wire/Digital 3 point floating
2.2K 2.2K
2.2K 2.2K
1 2 3 4 5 1 2 3 4 5
Note: In Digital Mode, the actuator is sensitive to induced electrical voltages from external sources. To prevent interference, install a
2.2k Ohm, 0.5 W resistor (included) between pins 1 and 3 and another between pins 1 and 4 of TB1 as shown above.
Note: In any of the above wiring configurations, connect a supplied 500 Ohm resistor between pins 1 and 5 for a 2-10Vdc feedback
signal.
www.neptronic.com 2
BM Series Actuators
Specification and Installation Instructions
PC Board
BM060 DIP Switch Settings
Rotation: CCW
1 2 3 1 2 3
ON
Rotation: CW
Reset ON
NOTE*: To use DIP switch #3 in other modes
button
1 2 3 (analog/digital), refer to Feedback Selection (CCW
Direction) on page 4.
1 2 3 4 5 Dip switch
www.neptronic.com 3
BM Series Actuators
Specification and Installation Instructions
Feedback selection (CCW direction)
To select the CCW direction, set DS #1 to ON, and if the actuator is in Analog or Digital mode, you can program the feedback signal
direction.
0º 90º 0º 90º
20 mA 4 mA 4 mA 20 mA
Note: The voltage difference between the minimum voltage and high voltage settings must be at least 3V. If not, the actuator
will ignore the values entered and use the previous values. For example, a minimum voltage of 5V and a maximum
voltage of 7V represent a difference of 2V.
Note: To reset zero and span to 2 to 10 Vdc (factory value), re-select the analog control signal mode, see Programming.
www.neptronic.com 4