USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

BRAGA MORO
SISTEMI DI ENERGIA S.p.A

VIA LUDWIG VAN BEETHOVEN N.24

20092 CINISELLO BALSAMO (MI)

Tel.: +39 02 51 67 22 01

Fax: +39 02 51 67 22 13

mailto:[email protected]

www.bragamoro.com

USER MANULA
“AQUARIUS PLUS”
Da 1KVA a 3KVA
Cosphi 0,9

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 1 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

1. DOCUMENT CHECK SECTION

Drawing

Written by Role Date

Alessandri David Technical Staff 29-03-17

Control

Control by Role Date

Alessandri David Technical Staff 29-03-17

Approved

Approved by Role Date

Abbondio Adelio Technical Staff 29-03-17

Revision

Rev. Author Description Date


B
C
D
E
F
G
H
I
L

References

Ref. Author Title Revision

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 2 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

1. Preface

Thank you for purchasing our UPS, it is safe and reliable, little maintenance is required.

Read this manual carefully and completely. It includes safety and operating installation instructions.
It will help your UPS get a longer service life. This manual explains the principle of internal
operation, and the related protection functions.

This manual also contains information on the use of the equipment.

Please respect the instructions and all the warnings indicated in the manual or on the machine. Do
not use the machine before completing the safety reading and the operating instructions.

Note: due to continuous improvements, our products may differ from the contents included in this
manual. You can contact the local office to get information when needed.

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 3 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

General index
1. DOCUMENT CHECK SECTION ............................................................................................................. 2
1. Preface .................................................................................................................................................... 3
1 Description ............................................................................................................................................... 5
2 Safety Instructions ................................................................................................................................... 7
3 Product presentation ............................................................................................................................... 8
4 Installation ............................................................................................................................................. 11
5 Display operation and management...................................................................................................... 15
6 Maintenance .......................................................................................................................................... 25
7 TROUBLESHOOTING .......................................................................................................................... 25
8 Reference standards ............................................................................................................................. 30
9 Electrical characteristics ........................................................................................................................ 30
10 Environmental conditions ...................................................................................................................... 31
11 Mechanical specifications Rack mounting 19” ...................................................................................... 31
12 Communication ports............................................................................................................................. 31

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 4 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

1 Description
UPS (Uninterruptible Power Supply) is a device that allows continuity in the supply of loads in
alternating current, but also has protection and monitoring functions. The UPS plays a very
important role in the supply of computers and the computer network to which the computer is
possibly connected. The fields of application of UPS are numerous: communication, finance,
electricity, transport, national defense, universities, scientific research institutes and so on.

The Aquarius series from 1KVA to 3kVA, are products designed with the advanced ON-LINE UPS
technology, which provide the user with multiple functions and good performance.

1.1 Functions and features

1. The latest generations of IGBTs have been used in our UPSs to provide reliability and high
performance. In general, the electronic components we have used are able to work normally for
more than 300,000 hours.
2. Using digital technology associated with reliable algorithms, we have been able to create a
powerful and easy-to-use product.
3. The self-test at the start-up of the apparatus, allows to find in advance, potential problems of the
UPS in order to be able to intervene and resolve the problem promptly.
4. The on-line double conversion topology means that in the UPS output there is a sine wave with
constant voltage and frequency, low noise and without any type of interruption of energy supplied
to the load. All this guarantees the correct functioning of the equipment powered by our UPSs.
5. The transfer time between the main source and the emergency source at the UPS exit is zero, when
the main power supply fails it is immediately replaced by the emergency power supply
6. With the bypass function incorporated in the UPS, the energy is transferred to the loads without
any interruption. This feature is very useful when you need to perform maintenance on the UPS.
7. Advanced voltage compensation technology leads to having the input voltage range from 115V to
295V, which reduces battery usage and improves the ability to adapt to changing network
conditions.
8. The AC input frequency is 50Hz / 60Hz. When the output frequency is 50Hz, the AC input frequency
range is 45Hz-55Hz, when the output frequency is 60Hz, the AC input frequency range is 55Hz-
65Hz. The UPS has good compatibility with generators. It is suitable for different types of single-
phase generators.
9. The advanced PFC (Power Factor Correction), a technology that leads to a power factor higher than
0.98 of the UPS, increasing its energy efficiency and removing harmonic distortion.
10. The UPS starts up in battery mode, to be able to power the loads even in the absence of the mains.
When the battery voltage is low, the UPS protects itself and turns off automatically. When the main
power is restored, the UPS will detect its presence, checking that the voltage and frequency are in
the ranges. Once the input voltage is considered good, the UPS will automatically turn on to supply
loads; if the network is not considered good, the UPS will still start the charger to recharge the

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 5 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

battery. In this case the group does not switch on to supply loads until the voltage and frequency of
the main source fall within the allowed ranges.
11. When there is no power supply, the UPS can be started by battery. This feature is called cold start
and is used to supply loads in emergencies. This feature can also be activated at full load.
12. The UPS intervenes to protect the load when the following events occur: When the main input or
output power is too high or too low, in case of overload, short circuit, high inverter stage
temperature, minimum voltage and battery overload.
13. The UPS can be installed in a Rack or Tower version. The viewing angle of the display can be easily
changed by pressing two buttons on the control panel of the apparatus. The content displayed on
the interface is rich in measurements. Alarms and statuses are easily controlled from the operator
panel.
14. It is possible to connect the UPS to a computer, through an RS232 serial port. A software must be
installed on the PC that allows the intelligent management of most of the functionalities of the
device.
15. If you want to connect the UPS to a computer network, you must have a kit called "SNMP adapter".
The connection can be internal or external to the UPS. Through these cards it is possible to monitor
the UPS from the internet or by evicting the various network protocols made available to the kit.
16. A further possibility to monitor the UPS is the USB port, present on the UPS. Also, in this case it will
be necessary to load a software on the PC to which the group is connected.
17. The ECO function saves electricity. When the input voltage is in an acceptable range, the load is fed
directly from the mains. In this case the inverter remains in stand-by. When the input voltage
comes out of the ranges, the load is powered by the inverter, which returns the output voltage in
the allowed ranges.

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 6 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

2 Safety Instructions

This chapter mainly introduces safety marks and notes on the 1KVA-3KVA online UPS series.
Read this chapter carefully before using the equipment.

2.2 Safety

There are dangerous voltages and high temperatures inside the UPS. During the installation
and maintenance operation, please follow the safety instructions in the interior and the relevant laws,
otherwise personal injury or damage to the equipment may occur. Safety instructions in this text are
like an additional manual for internal safety instructions. Our company does not assume the
responsibility caused by non-compliance with safety instructions. Please note the following:

1. Do not use the UPS when the actual load exceeds the nominal load.
2. There are high-capacity batteries in standard-type UPSs. Do not open the cover. There is
a danger of electric shock. In case of maintenance or replacement of the internal battery,
please send it to the nearest UPS service center.
3. A short circuit inside the UPS causes electric shock or possible fire. Therefore, do not place
containers with liquid on top of the UPS so as not to cause danger of electric shock.
4. Do not put the UPS in a place with high temperature or humidity, as well as corrosive gases
and a lot of dust.
5. Maintain good air circulation on the front panel and rear panel.
6. In case of smoke coming out of the UPS, please remove the power as soon as possible
and contact the assistance service.

2.3 Indication symbols

The safety symbols mentioned in this manual are shown in the following table. They are used to
inform the user of safety problems that must be respected during installation, operation and
maintenance.

Indication symbols Indication

Attention

Sensitive to electrostatic discharge

Electrocution

There are three levels of security: Dangerous, warning and attention. The meaning is to the right of
the safety symbol, the description is below, as shown below:

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 7 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Dangerous:

Indicates the risk of serious injury or death or serious damage to the equipment

Attention:

Indicates the risk of serious injury or damage to the equipment.

Warning:

Indicates risk of injury or equipment damage.

3 Product presentation

3.1 Product appearance

Illustration 1: front panel

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 8 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Illustration 2: Rear panel

3.2 The principle of the product

Illustration 3: Principle outline

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 9 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

1. Input filter: filters the AC mains input supply to supply clean energy for the UPS.

2. AC / DC converter: Converts the filtered mains voltage (AC) into DC voltage and elevates it
for the DC / AC inverter.

3. DC / DC booster: When the UPS is operating in battery mode, this circuit increases the DC
voltage for the inverter.

4. DC / AC inverter: Converts the direct voltage (DC) to a stable alternating voltage (AC)
output.

5. Bypass: When an overload or failure of the inverter occurs, the UPS goes into bypass
mode to supply loads.

6. Charger: the standard unit provides 1A, while the long-life charger provides 4A.

7. Battery: sealed lead acid batteries.

8. Output Filter: Completely filters the UPS output to provide clean energy for the loads.

3.3 Modell

UPS type MODEL NO Remark


1KVAS Internal battery charger 1A,2 batterie PCS 7AH
Standard unit 2KVAS Internal battery charger 1A,4 batterie PCS 7AH
3KVAS Internal battery charger 1A,6 batterie PCS 7AH

Table 1: Aquarius model


To request an expansion battery box, for long term backup contact the Braga Moro sales office, or
write to the following E-Mail address: [email protected]

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 10 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

4 Installation

4.1 Unpacking and inspection

1. Unpack the UPS and check that there is no damage caused during transport. If any parts
are damaged or missing, do not start the appliance and inform the carrier and report it to
the service center.
2. Check the attachment (please refer to the Appendix 1 table).

4.2 Note

 Please place the UPS in a clean environment and avoid vibration, dust, moisture, flammable
and corrosive gases and liquids.
 The ambient temperature must be in a range between 0 ° C ~ 40 ° C. If the ambient
temperature exceeds 40 ° C, the nominal power decreases by 12% as the ambient
temperature increases.
 The maximum working temperature cannot be higher than 50 ° C.
 The UPS must be placed in a sufficiently ventilated place.

4.3 Mounting the brackets for the Tower-mounted installation

The plastic brackets must be mounted as shown in illustration 5 and 6

Illustration 4: mounting brackets-1 Illustration 5: mounting brackets-2

As for the mounting of the brackets for the different UPS models, it is necessary to know that the
1KVA unit needs a space of 1 unit, so it is sufficient to follow the illustrations 5 and 6. For the other
models the space between the brackets it is 2 units and for a correct assembly the other
illustrations in this paragraph must also be considered.

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 11 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Illustration 6: mounting brackets for 2/3KVA

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 12 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

4.4 Mounting of rack mounting brackets

The following illustrations show how to fix the brackets on the groups, to perform a rack mount.
The screws (SCREW A and B) shown in illustration 9 are from M4.
The fixing of the brackets must be carried out on both sides of the UPS.

Illustration 3: Fixing brackets for rack Illustration 4: Fixing Illustration 5: Fixing bracket on
mounting bracket UPS

Illustration 6: Rack mounting

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 13 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

4.5 UPS output input connection

the UPS to the mains and to the loads with the supplied power cable.

4.6 Connection to the high autonomy battery box

Attention:

 Before installing the battery, make sure the UPS is turned off and its switch is open. Use all
the precautions dictated by the safety rules at work, in order to avoid accidents.
 Pay attention to the battery polarity. The red cable connects it with the positive of the
battery "+" and black cable connect it with the negative "-".
 Please use insulated tools that comply with the occupational safety directives. Do not place
instruments or metal objects on the battery.

Note:
 Before connecting the loads to the UPS, open the relevant switches, then connect the cable
to power supply and finally turn on the loads one at a time.
 To avoid damage, it is strictly forbidden to connect inductive loads such as motors,
fluorescent lamps and photocopiers to the UPS.
 Connect the UPS to a device with overcurrent protection. The socket used must have a
ground connection.

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 14 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

 The UPS can supply output voltage regardless of whether the power cord is connected to
the power outlet. If you want the UPS not to supply output voltage, first open the circuit-
breaker and then detach the network.
 When connecting the laser printer, select the pickup capacity at the UPS start according to
the UPS model in order to have more power at start-up.

5 Display operation and management


Operation is simple. operators must only read the manual and follow the operating instructions
contained in this without any special training.

5.1 Button operation:

Illustration 7: front buttons

Buttons ON ( + )

Press these two buttons for more than half a second to turn on the UPS.

Buttons OFF ( + )
Press these two buttons for more than half a second to turn off the UPS.

TEST/MUTE buttons ( + )

Press the keys for more than 1 second in line mode or in economic mode: the UPS will perform
the auto test function.
Press the keys for more than 1 second in battery mode: the UPS performs the mute function.

Search keys o

Consultation method:
Press the keys for more than half a second (less than 2 seconds): list in order of the items
of the LCD display.
Press and hold these keys for more than 2 seconds: the display rotates 90 ° displays the
items every 2 seconds, keeping the keys pressed for the same amount of time, turn back to
the initial position.
Mode setting function:
Press and hold the button for more than half a second (less than 2 seconds):
Select the option to be set.
File name Date Page PUT9I001 PUT9I1K5
Code PUT9I002
DF19009A 05/04/19 15 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Key setting function

Consultation mode:
Press and hold this key for more than 2 seconds: interface setting function.
Mode setting function:
Press the button for more than half a second (less than 2 seconds): Confirms the set option.
Press the button for more than 2 seconds to exit this interface with the setting function.

5.2 Function of the LED indicators

Illustration 8: Display

Warning Red LED is on: UPS is faulty. For example: overload beyond the allowed time,
inverter failure, BUS failure, high temperature, etc.

Bypass Yellow LED on: UPS is in alarm. For example: active bypass, etc.

Battery Yellow LED on: UPS is in alarm. For example: battery inverter power supply mode.

Inverter Green LED on: UPS is normally powered from the mains or in ECO mode or in battery
mode.

When the UPS starts up, the four LEDs light up and go off one at a time. This sequence
repeats several times until the UPS has finally started up.

NOTE: Regarding the indication of the LEDs in different modes, please refer to the LED
display panel and the warning table.

5.3 Functions of the LCD display

The LCD display appears as shown in the figure:

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 16 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Illustration 9: Example
screen
LCD display includes a section with numerical values, a graphic section of the power supplied, a
graphic section of the fan status and a graphic section of the battery status.

The numerical values section displays: the input voltage and frequency, the output voltage and
frequency, the output powers, the temperature, the voltage and the percentage of battery charge,
for example, as shown in the figure above, the output voltage is 220V, the output frequency is
50Hz.

Graphic section of battery capacity and load: each box represents 20% of capacity.

As shown in the figure above, the battery capacity is between 80% and 100% (5 panels), the load
is between 40% and 60% (3 panels). When the UPS is overloaded, the icon will flash, when the
battery capacity is too low or disconnected, the icon will flash.

Fan – Defines the fan status. In case the fan is working properly, the graph simulates the rotation
of a propeller. In the event of an anomaly, the fan symbol will begin to flash.

Charger – When the charger is working properly, its symbol will follow a pattern like that shown in
the following figure.

In the event of a malfunction, the symbol will start to flash. When the UPS is in battery mode, the
number of charging status icons will vary depending on the battery capacity. For example: if there
are five boxes (as in the figure below), the corresponding number of lines is five lines (like the
following image on the left).

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 17 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

5.4 operation

5.4.1 UPS start-up

Starting the UPS, the Line Mode.

Once the mains supply is connected, the UPS charges the batteries. The display will show that the
output voltage is 0, which means that UPS cannot yet power the load. If you plan to use the bypass,
you can set the bps "ON" from the LCD settings menu.

To start the UPS, hold down the ON button for more than half a second. When the time expires the
inverter will start up.

Once started, the UPS will perform a self-test. The LEDs will turn on and off in a circular and orderly
manner. At the end of the initial test the device will be active and the Line Mode, with the relative
LED lit.

Starting the UPS in battery mode.

To start the UPS even in the absence of mains, keep the ON key pressed for more than half a
second. When the time expires, the inverter will start up.

The start-up of the group is identical to the Line Mode, at the end of the self-test the Battery Mode
LED will light up.

5.4.2 Turn off the UPS

To turn off the UPS, press and hold the OFF button for more than half a second. When the time
expires, the UPS and inverter will shut down.
After switching off the inverter there will be no output voltage left. In this situation it is possible to
activate the by-pass (bps on) function to equally power the load.
The same shutdown procedure, it is possible to use it even when the group is in absence of network
in battery mode.

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 18 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

5.4.3 Self-test/Mute modality

By pressing the self-test / mute button for more than one second, the group will start the self-
checking sequence. The LEDs will turn on and off in sequence. During this phase the UPS will check
the quality of its circuits. At the end of the test it will automatically return to the pre-test mode.
In case of pressure of the self-test / Mute for more than one second, when the group is in Battery
Mode, the acoustic signal will be silenced.

5.5 Parameter setting

The UPS allows the modification of some parameters. The changes can be implemented in any
operating mode. The application of the changes made to the group parameters will be checked by
the software of the device before being saved

5.5.1 Change UPS parameters.

To access the modification of the UPS configuration parameters, keep the key pressed for two
seconds . Once the mode is activated, the word ECO will flash on the display.

Illustration 10: Display- ECO

To activate ECO mode, the key must be kept pressed for more than half a second (but not
beyond two seconds). When the time expires you will see ON flashing (see next illustration).

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 19 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Illustration 11: ECO ON

Press the button to choose which ECO function to activate. The activated functions have the
word ON, while the non-active functions the word OFF. To activate or deactivate the features, press

the button for two seconds. After confirming the message ON or OFF will stop flashing.

To exit parameter modification, keep the button pressed for at least two seconds .

5.5.2 Bypass configuration

Entering the parameter modification mode as described in the previous paragraph. Select the
function with the key , the Bypass message will flash after selection.

Illustration 12: Bypass

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 20 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

To activate or deactivate the Bypass function by keeping the button pressed for at least half a second
. The display will begin to flash.

Illustration 13: Bypass ON

To confirm the selection, keep the key pressed , for at least 2 seconds. The word ON or OFF

will stop flashing. Pressing the button for another two seconds you return to the main menu.

5.5.3 Output voltage setting (optional)

NOTE:

Before changing the output voltage, it is advisable to disconnect the load.

Entering the parameter modification mode as described in the previous paragraph. Press the button

for half a second and select the OPU option.

Illustration 14: OPU

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 21 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Press the button again for half a second . Numerical values will appear under the word OPU.
With the key choose the desired output voltage value. The selectable values are: 208V, 220V,
230V and 240V.

Illustration 15: OPU- Vout

to confirm the choice, press the key for two seconds . The numerical value of the voltage will

stop flashing. To return to the main menu press the key for two seconds .

5.6 Display of the parameters

To view the UPS parameters, simply press the key or for half a second. The parameters
related to the input, output, battery and temperature will appear on the display.
Regarding the input and the output, it will be possible to see the input voltage and frequency.

Illustration 16: Input

As far as the load measurements are concerned, the active and apparent power can be displayed

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 22 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Illustrazione 17:
Potenza

Finally, the measurement relating to the internal temperature of the group and those relating to the
battery will be available: available voltage and capacity.

5.7 Run mode

5.7.1 Bypass mode

The visual indications in Bypass mode are as follows:

The yellow LED on indicates that the UPS is in Bypass, the sound signal emits a sound every
two minutes, even the red LED that signals an attention situation is on. The display shows the
measurements related to the load and the battery capacity.
Bypass mode is activated in the following conditions:

 When the UPS is in line mode and the network fails.


 When the UPS is overloaded.

Attention: When the UPS operates in Bypass mode it is not possible to use the batteries as a
backup.

5.7.2 Line mode

The visual signals in Line mode are as follows:

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 23 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

The green LED of the inverter is on. This condition remains if the input voltage is present and remains
in the allowed ranges.

5.7.3 Battery mode

The visual signals in Battery mode are as follows:

The green LED of the inverter, the yellow LED of the battery and the red warning LED are on.
The buzzer emits an acoustic signal every 4 seconds.
The Battery mode status remains until the input voltage is absent or out of limits.

5.7.4 ECO mode

The visual indications in ECO mode are as follows

The green inverter LED and the yellow bypass LED are on.
The ECO mode status must first be activated, secondly it remains until the input voltage remains in
the ranges allowed by this mode. If the input voltage exceeds the range allowed by the ECO mode,
the load is automatically powered by the inverter.

5.7.5 Alarm condition

The following visual alarms are indicated:

The red LED is on and the UPS emits an acoustic signal. The display shows an alarm code.
In some fault situations it may happen that the group no longer feeds the load.

The buzzer can be silenced by pressing the MUTE button, or the UPS can be turned off by pressing
the OFF button.

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 24 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

NOTE: THE ALARM CODES ARE INCLUDED IN THE APPENDICES OF THIS MANUAL.

INFORMATION:

 This procedure must be carried out when a UPS with a generator (GE) is powered:
 Turns on the GE, after it has started up and its output is stable in both frequency and voltage,
turn on the UPS.
 After the UPS has turned on, connect the loads one at a time.
 The power of the GE must be twice the power of the UPS.
 Do not activate the ECO mode function if the GE output is not very stable.

6 Maintenance
Minimal maintenance is required for this series of UPSs. Battery batteries are hermetically sealed,
and only need to be charged properly in order to maintain the expected life. To charge the batteries,
simply connect the UPS to the network. The device will take care of protecting the batteries in case
of excessive charge, and in case of deep discharge.

6.1 Battery maintenance

1. It is a good rule to perform a deep discharge and relative recharge, every three or four
months.

2. If the batteries are placed in environments where high temperatures are present, the
discharge and recharge should be done every two months.

3. On average, the expected life of sealed lead batteries varies from three to five years. During
periodic discharges / recharges, check the discharge / recharging times, should the batteries
shorten dramatically, they must be replaced as soon as possible by specialized personnel.

4. It is advisable to replace all the batteries at once.

5. ATTENTION: ALL MAINTENANCE ACTIVITIES MUST BE DONE BY SPECIALIZED


PERSONNEL AND FOLLOWING SAFETY REGULATIONS.

7 TROUBLESHOOTING
This chapter will describe the alarm codes that the user might encounter in the event of a UPS failure.
Read the manual carefully before performing any operations on the UPS.

ATTENTION: DANGEROUS VOLTAGES ARE PRESENT INSIDE THE APPARATUS.


WHICH MAY CAUSE SERIOUS DAMAGES TO THINGS OR PEOPLE.

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 25 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

To understand the operating status of the device it is necessary to know the following information:

1. When the red LED on the front panel is lit, there is a potential problem.
2. If the acoustic signal is active, a critical state is present.
3. In the presence of one of the situations it is advisable to contact the Braga Moro customer service
by sending an E-mail to: [email protected]. Specifying the following data:
• Code and serial number of the device
• Date of production
• Date of failure
• Code and description of the fault
• Status of visual and acoustic signals

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 26 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

7.1 Alarm codes and related visual signals

Appendix 1 Error codes

Description Code
Bus KO 00-19
Inverter KO 20-39
overtemperature 40-44
Short-circuit 45-49
Overload 50-54
KO output relay 55-59
Input NTC KO 60-64
KO aux power supply 65-69
KO input fuses KO 70-74
Other 99

Appendices 2 Signalizing di state

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 27 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

Notifications
N Acoustic
N° Status Comments
o Bat Bps Fau warnings
r
1 Line mode

Voltage within the limits ● Nobody


Voltage out of bounds
● ● ★ Every 4 seconds
UPS in Battery mode
2 Battery mode
Voltage within the limits ● ● ★ Every 4 seconds
Battery voltage out of
● ★ ★ Every second
limits
3 Bypass mode
Voltage within the limits ● ★ Every 2 minutes Delete after starting UPS
Voltage above the limits ★ Every 4 seconds
Voltage below the limits ★ Every second
4 Battery disconnection alarm
Check if the battery switch is
Bypass mode ● ★ Every 4 seconds
closed.
Check if the battery switch is
Inverter mode ● ★ Every 4 seconds
closed.
Check if the battery switch is
Power on Six times
closed.
5 Overload protection
Overload (warning) in
● ★ 2 per second Disconnect less important loads
Line mode
Protection for overload in
● ● Long sound Disconnect less important loads
Line mode
Overload (warning) in
● ● ★ 2 per second Disconnect less important loads
Battery mode
Overload protection in
● ● ● Long sound Disconnect less important loads
battery mode
Overload (warning) in
6 ● ★ Every 2 seconds Disconnect less important loads
Bypass mode
7 Fan alarm (icon flashes) ▲ ▲ ▲ ★ Every 2 seconds Check the fan status

If the alarm code is displayed,


8 Failure ● Long sound
contact the service center.

● _indicator lights for a long time


★ _indicator flashes

▲ _the status of indicator depends on other conditions

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 28 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

7.2 Troubleshooting

Fault Cause Solution

Neutral and phase


The word "INPUT"
reversed or Input voltage Connect the cables correctly.
flashes on the display
out of range.

Battery capacity Minimum battery voltage


Check the connections or battery status
flashes. or battery disconnection

Input voltage present,


Open disconnector Press the disconnector to reactivate it
but no output voltage

Connect the UPS to the mains for at least


Battery not fully charged
8 hours.

Insufficient backup Check the loads and remove the least


UPS in overload
time significant ones.

Contact the Braga Moro service center


Dated battery
for battery replacement.

The keys were not pressed


Press the ON buttons simultaneously
correctly

After pressing the ON There is a problem with Check the battery connection, if the
buttons the UPS does the battery or there are too battery voltage is low, turn off the UPS
not start. many loads connected and remove loads and then start the UPS.

Fault in the UPS Contact the Braga Moro service center.

The charger icon


The charger is not
flashes on the display
working properly, or the Contact the Braga Moro service center.
and the buzzer makes
battery is dated
a sound every second

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 29 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

8 Reference standards
The Braga Moro uninterruptible power supplies have been manufactured according to the
regulations listed in the table in this paragraph and have obtained the CE mark in compliance with
European standards.
EMC standards Safety standards
IEC62040-2 IEC62040-1
IEC61000-4-2 GB4943-5
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5

9 Electrical characteristics
Model 1KVAS 1KVAH 2KVAS 2KVAH 3KVAS 3KVAH
Nominal capacity 900W/1000VA 1800W/2000VA 2700W/3000VA
Input Input type Single-phase + earth
Voltage range 115±5VAC-295±5VAC
Frequency range 45Hz-55Hz@50HZ/55Hz-65Hz@60HZ
Power factor ≥0.98
ECO range Output voltage variation ± 20VAC
Range Bypass 186VAC-252VAC
Harmonic current ≤7% (100% nonlinear load)
Output Output type Single-phase + earth
Nominal voltages 208/220/230/240VAC
Power factor 0.9
Voltage accuracy ±2%
Line mode 1) When the input frequency is within the limits, the output frequency is
the same as the input frequency.
Frequency 2) When the input frequency is not within the limits, the frequency is
(50/60 ± 0.2) Hz.
Exit
Battery mode (50/60±0.2) Hz
Crest factor 3-1
Transfer time Network ← → battery = 0ms
Network←→ bypass =4ms
Capacity Battery mode 108%±5%<load≤150%±5% >30s cut off output and warn,
overload
150%±5%<load<200%±5% > 300ms cut off output and warn
Line mode 108%±5%<load≤150%±5% > 30s transfer. al bypass e notice
150%±5%<load<200%±5% >300ms transfer. al bypass e notice

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 30 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

performance Line mode Full load≥86%


Full load≥88%
Battery mode Full load≥84%

ECO Full load≥94%


Output Voltage Distortion ≤3% (100% linear load)
≤5% (100% non-linear load)
Battery Battery voltage 24VDC 24VDC 48VDC 48VDC 72VDC 72VDC
Battery number 2 4 6
Tipo batterie 12V/7AH airtight lead (for standard UPS only)
Autonomy Full load 4 minutes. For standard UPS only.
Charge current (A) 1 4 1 4 1 4

10 Environmental conditions
Template 1KVA-3KVA
Temperature 0℃~40℃
Humidity 0-95% without condensation

Altitude 1500 m

Storage temperature -25℃ - 55℃

11 Mechanical specifications Rack mounting 19”

Dimension W*D*H (mm) Net / Gross Weight (kg)


Model
1KVAS 440*430*86,5 15,7
1KVAH
2KVAS 440*572*86,5 26,3
2KVAH
3KVAS 440*736*86,5 33
3KVAH

12 Communication ports

12.1 RS232

On the UPS there is a RS232 DB9 connector. To connect the unit to a PC it is necessary to have a
standard serial cable. The following table shows how to wire the serial cable:
File name Date Page PUT9I001 PUT9I1K5
Code PUT9I002
DF19009A 05/04/19 31 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
USER MANUAL

UNI EN ISO 9001-2015 n° 9115.BRMO “Aquarius Plus”

PIN 1(hole)to computer serial port PIN 2(needle)to UPS serial port
2 2
3 3
5 5

To acquire data from the group's serial port, the UPSILON2000 software must be installed on the
computer.

12.2 Smart Slot

The following smart cards can be installed in the UPS intelligent slot: USB intelligent card, SNMP
card and relay card. All these cards are hot plug and play.

USB intelligent card: Useful to monitor the UPS and its parameters through the computer's USB
port, it is necessary to load the UPSILON2000 software on the PC to use this option.

WARNING: If both the RS232 and the USB are installed on an UPS, it is not possible to use
the two communication ports at the same time.

SNMP Card: This option allows you to connect the UPS to a computer network, with the consequent
possibility to monitor the UPS through the internet and the SNMP protocol.
Relay Card: Provides the status of the UPS through the clean relay contacts.

File name Date Page PUT9I001 PUT9I1K5


Code PUT9I002
DF19009A 05/04/19 32 di 32
PUT9I003
MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.