Operating Manual English - en - US
Operating Manual English - en - US
SA 07.2 – SA 16.2
SAR 07.2 – SAR 16.2
Control unit - electromechanical
with actuator controls
AC 01.2 Intrusive
Control
Parallel
→ Profibus DP
Profinet
Modbus RTU
Modbus TCP/IP
Foundation Fieldbus
HART
Reference documents:
●
Manual (Operation and setting ) of actuator controls AC 01.2 Profibus DP
●
Manual (Fieldbus device integration) of actuator controls AC 01.2 Profibus DP
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
2
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Table of contents
3
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Table of contents AC 01.2 Intrusive Profibus DP
4
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Safety instructions
1. Safety instructions
1.1. Basic information on safety
Standards/directives Our products are designed and manufactured in compliance with recognised
standards and directives. This is certified in a Declaration of Incorporation and an
EU Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others:
● Applicable configuration guidelines for fieldbus applications.
Safety instructions/warn- All personnel working with this device must be familiar with the safety and warning
ings instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves, and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
5
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Safety instructions AC 01.2 Intrusive Profibus DP
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive
2014/34/EU.
To comply with all requirements of the ATEX directive, observe the following points:
● Actuators are marked with the explosion protection designation II3D... for use
in ZONE 22.
● Maximum surface temperature of actuators
- T150 °C for ambient temperatures up to +60 °C or
- T190 °C for ambient temperatures up to +80 °C.
Increased dust deposit on the equipment was not considered for the determin-
ation of the maximum surface temperature.
● The following conditions must be fulfilled to respect the maximum permissible
surface temperatures at the actuator:
- Respecting types of duty and technical manufacturer data
- Correct connection of thermal motor protection (thermoswitches or PTC
thermistor)
6
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Safety instructions
Information The term Information preceding the text indicates important notes and information.
7
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Identification AC 01.2 Intrusive Profibus DP
2. Identification
2.1. Name plate
Figure 1: Arrangement of name plates
8
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Identification
9
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Identification AC 01.2 Intrusive Profibus DP
AUMA power class for The switchgear used in the actuator controls (reversing contactors/thyristors) are
switchgear classified according to AUMA power classes (e.g. A1, B1, ....). The power class
defines the max. permissible rated power (of the motor) the switchgear has been
designed for. The rated power (nominal power) of the actuator motor is indicated in
kW on the motor name plate. For the assignment of the AUMA power classes to the
nominal power of the motor types, refer to the separate electrical data sheets.
For switchgear without assignment to any power classes, the actuator controls name
plate does not indicate the power class but the max. rated power in kW.
Control Table 2:
Control examples (indications on actuator controls name plate)
Input signal Description
Profibus DP Control via Profibus DP interface
Profibus DP/24 V DC Control via Profibus DP interface and control voltage for OPEN - CLOSE
control via digital inputs (OPEN, STOP, CLOSE)
10
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Identification
Data Matrix code When registered as authorised user, you may use our AUMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
Figure 6: Link to AUMA Assistant App:
11
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Transport, storage and packaging AC 01.2 Intrusive Profibus DP
Hovering load!
Risk of death or serious injury.
→ Do NOT stand below hovering load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
→ Respect total weight of combination (actuator, actuator controls, gearbox, valve)
→ Secure load against falling down, sliding or tilting.
→ Perform lift trial at low height to eliminate any potential danger e.g. by tilting.
Table 3:
Weights for multi-turn actuators SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
with 3-phase AC motors
Type designation Motor type1) Weight2)
Actuator approx. [kg]
SA 07.2/ VD... 19
SAR 07.2 AD... 20
SA 07.6/ VD... 20
SAR 07.6 AD... 21
SA 10.2/ VD... 22
SAR 10.2 AD... 25
SA 14.2/ VD... 44
SAR 14.2 AD... 48
12
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Transport, storage and packaging
Weights for multi-turn actuators SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
with 3-phase AC motors
Type designation Motor type1) Weight2)
Actuator approx. [kg]
SA 14.6/ VD... 46
SAR 14.6 AD... 53
SA 16.2/ VD... 67
SAR 16.2 AD... 83
Table 4:
Weights for multi-turn actuators SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
With 1-phase AC motors
Type designation Motor type1) Weight2)
Actuator approx. [kg]
SA 07.2/ VE... 25
SAR 07.2 AE... 28
SA 07.6/ VE... 25
SAR 07.6 AE... 28
AC... 37
SA 10.2/ VE...48-4... 28
SAR 10.2 VE...48-2... 31
AC... 56-4... 40
AC... 56-2... 43
SA 14.2/ VE... 59
SAR 14.2 VC... 61
AC... 63
SA 14.6/ VE... 63
SAR 14.6 VC... 66
Table 5:
Weights for multi-turn actuators SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
With DC motors
Type designation Motor type1) Weight2)
Actuator approx. [kg]
SA 07.2/ FN... 63-... 29
SAR 07.2 FN... 71-... 32
SA 07.6/ FN... 63-... 30
SAR 07.6 FN... 80-... 44
SA 10.2/ FN... 63-... 33
SAR 10.2 FN... 71-... 36
FN... 90-... 56
SA 14.2/ FN... 71-... / FN... 80-... 68
SAR 14.2 FN... 90-... 100
13
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Transport, storage and packaging AC 01.2 Intrusive Profibus DP
Weights for multi-turn actuators SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
With DC motors
Type designation Motor type1) Weight2)
Actuator approx. [kg]
SA 14.6/ FN... 80-... / FN... 90-... 76
SAR 14.6 FN... 112-... 122
SA 16.2/ FN... 100-... 123
SAR 16.2
Table 6:
Weights for output drive type A 07.2 – A 16.2
Type designation Flange size [kg]
A 07.2 F07 1.1
A 10.2 F10 2.8
A 14.2 F14 6.8
A 16.2 F16 11.7
3.2. Storage
Long-term storage For long-term storage (more than 6 months), observe the following points:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
3.3. Packaging
Our products are protected by special packaging for transport when leaving the
factory. The packaging consists of environmentally friendly materials which can easily
be separated and recycled. We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
14
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Assembly
4. Assembly
The product described in this document can be operated in any mounting position.
Restriction: When using oil instead of grease within the actuator gear housing, the
hollow shaft mounting position must be perpendicular, with the flange pointing
downward. The type of lubricant used is indicated on the actuator name plate (short
designation F...= grease; O...= oil).
Figure 8: Handwheel
[1] Spacer
[2] Input shaft
[3] Handwheel
[4] Retaining ring
15
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Assembly AC 01.2 Intrusive Profibus DP
Information To adapt the actuators to available output drive types A with flanges F10 and F14
(year of manufacture: 2009 and earlier), an adapter is required. The adapter can be
ordered from AUMA.
✔ This working step is only required if stem nut is supplied unbored or with pilot
bore.
Figure 10: Output drive type A
16
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Assembly
1. If the output drive type A is already mounted to the multi-turn actuator: Loosen
screws [3] and remove output drive type A [2].
2. Check if the flange of output drive type A matches the valve flange [4].
3. Apply a small quantity of grease to the valve stem [1].
4. Place output drive type A on valve stem and turn until it is flush on the valve
flange.
5. Turn output drive type A until alignment of the fixing holes.
6. Screw in fastening screws [5], however do not completely tighten.
7. Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
➥ The flanges are flush with each other if properly engaged.
8. Adjust multi-turn actuator until alignment of the fixing holes.
9. Fasten multi-turn actuator with screws [3].
17
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Assembly AC 01.2 Intrusive Profibus DP
11. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
and output drive A are firmly placed together.
12. Tighten fastening screws [5] between valve and output drive type A crosswise
applying a torque according to table.
4.3.2. Output drive types B and E
Application ● For rotating, non-rising valve stem
● Not capable of withstanding thrust
Design Connection between hollow shaft and valve or gearbox via output drive sleeve fixed
to the hollow shaft of the multi-turn actuator via retaining ring.
When exchanging the output drive sleeve, later retrofitting to a different output drive
type is possible
● Output drive types B and E: Output drive sleeve with bore according to DIN
3210
● Output drive types B1 – B4: Output drive sleeve with bore according to EN ISO
5210
Figure 12: Output drive type B
18
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Assembly
19
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Assembly AC 01.2 Intrusive Profibus DP
1. Seal all threads with hemp, Teflon tape, or thread sealing material.
2. Screw stem protection tube [2] into thread and tighten it firmly.
Information: For stem protection tubes made of two or more segments, all
parts have to be thoroughly screwed together.
Figure 15: Protection tube made of segments with threaded sleeves (>900 mm)
20
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Assembly
The mounting position of the local controls is implemented according to the order.
If, after mounting the actuator to the valve or the gearbox on site, the local controls
are in an unfavourable position, the mounting position can be changed at a later
date. Four mounting positions shifted by respectively 90° are possible (by maximum
180° into one direction).
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
21
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Electrical connection AC 01.2 Intrusive Profibus DP
5. Electrical connection
5.1. Basic information
Wiring diagram/terminal The pertaining wiring diagram/terminal plan (in German or English) is attached to
plan the device in a weather-proof bag, together with these operation instructions. It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks Actuator controls (actuators) are suitable for use in TN and TT networks with directly
(supply networks) earthed star point for mains voltage up to maximum 690 V AC. Use in IT networks
for nominal voltages up to maximum 600 V AC are permissible. For IT network, a
suitable, approved insulation monitor measuring the pulse code is required.
Current type, mains Type of current, mains voltage and mains frequency must match the data on the
voltage, mains fre- actuator controls and motor name plates. Also refer to chapter <Identification>/<Name
quency plate>.
Figure 17: Motor name plate (example)
External supply of the For external electronics supply with 24 V DC and simultaneous use of DC motors
electronics (24 V DC, 48 V DC, 60 V DC, 110 V DC, 220 V DC), the 24 V DC controls’ voltage
supply should be ensured via the XK25/26 terminals, separately from the power
supply (U1, V1). In case of common supply using a single cable (links from U1, V1
with XK25/26, for 24 V DC only !!!), short-term excess or falling below the permissible
voltage limits can be the consequence during switching (24 V DC +10 %/–10 %).
Any possibly incoming operation commands are not executed outside the admissible
limit values. The actuator controls briefly signal a fault condition.
Protection and sizing on For short-circuit protection and for disconnecting the actuator from the mains, fuses
site and disconnect switches have to be provided by the customer.
The current values for sizing the protection can be derived from the current
consumption of the motor (refer to motor name plate) plus the current consumption
of actuator controls.
We recommend adapting the switchgear sizing to the max. current (Imax) and selecting
and setting the overcurrent protection device in compliance with the indications in
the electrical data sheet.
22
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Electrical connection
Table 9:
Current consumption of actuator controls
Mains voltage Max. current consumption
Permissible variation of the mains voltage ±10 % –30 %
100 to 120 V AC 750 mA 1,000 mA
208 to 240 V AC 400 mA 750 mA
380 to 500 V AC 250 mA 400 mA
515 to 690 V AC 200 mA 400 mA
Table 10:
Maximum permissible protection
Switchgear Rated power max. protection
(switchgear with power class)1)
Reversing contactor A1 up to 1.5 kW 16 A (gL/gG)
Reversing contactor A2 up to 7.5 kW 32 A (gL/gG)
Reversing contactor A3 up to 15 kW 63 A (gL/gG)
Thyristor B1 up to 1.5 kW 16 A (g/R) I²t<1,500A²s
Thyristor B2 up to 3 kW 32 A (g/R) I²t<1,500A²s
Thyristor B3 up to 5.5 kW 63 A (g/R) I²t<5,000A²s
1) The AUMA power class (A1, B1, ...) is indicated on the actuator controls name plate
Consider the motor starting current (IA) (refer to electrical data sheet) when selecting
the circuit breaker. We recommend tripping characteristics D or K for circuit breakers
in accordance with IEC 60947-2. For controls with thyristors, we recommend safety
fuses instead of circuit breakers.
We recommend refraining from using residual current devices (RCD). However, if
an RCD is used within the mains, the residual current device must be of type B.
For actuator controls equipped with a heating system and external electronics power
supply, the fuses for the heating system have to be provided by the customer (refer
to wiring diagram F4 ext.)
Table 11:
Fuse for heating system
Designation in wiring diagram = F4 ext.
External power supply 115 V AC 230 V AC
Fuse 2AT 1AT
If actuator controls are mounted separately from actuator (actuator controls on wall
bracket): Consider length and cross section of connecting cable when defining the
protection required.
Potential of customer All input signals (control inputs) must be supplied with the same potential.
connections All output signals (status signals) must be supplied with the same potential.
Safety standards Safety measures and safety equipment must comply with the respectively valid
national on site specifications. All externally connected devices shall comply with
the relevant safety standards for the place of installation.
Connecting cables ● We recommend using connecting cables and connecting terminals according
to rated current (IN) (refer to motor name plate or electrical data sheet).
● For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
● Use connecting cable with appropriate minimum rated temperature.
● For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
● For the connection of position transmitters, screened cables must be used.
23
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Electrical connection AC 01.2 Intrusive Profibus DP
Cable installation in ac- Signal and fieldbus cables are susceptible to interference. Motor cables are
cordance with EMC interference sources.
● Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
● The interference immunity of signal and fieldbus cables increases if the cables
are laid close to the earth potential.
● If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
● Avoid parallel paths with little cable distance of cables being either susceptible
to interference or interference sources.
Fieldbus cable Table 12:
Cable recommendation
Only cables complying with IEC 61158 or IEC 61784, cable type A, may be used for Profibus DP wiring.
Impedance 135 to 165 Ohm, at a measurement frequency between 3 and 20 MHz
Cable capacity < 30 pF per metre
Wire diameter > 0.64 mm
Cross section > 0.34 mm², corresponds to AWG 22
Loop resistance < 110 Ohm per km
Screening CU shielding braid or shielding braid and shielding foil
24
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Electrical connection
Information For some special motors, the connection of the power terminals (U1, V1, W1, U2,
V2, W2) is not performed via the AUMA plug/socket connector but via a terminal
board directly at the motor.
25
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Electrical connection AC 01.2 Intrusive Profibus DP
Information Fieldbus operation is not interrupted when removing the connection housing [1].
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
4. Seal unused cable entries [6] with suitable blanking plugs [7].
Information Fieldbus connection can be accessed separately from the mains connection (refer
to <Fieldbus terminal compartment: open>.
26
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Electrical connection
Table 14:
Terminal cross sections and terminal tightening torques
Designation Terminal cross sections Tightening torques
2
Power contacts 1.0 – 6 mm (flexible) 1.2 – 1.5 Nm
2
(U1, V1, W1, U2, V2, W2) 1.5 – 10 mm (solid)
2
Protective earth connection (PE) 1.0 – 6 mm (flexible) with ring lugs 1.2 – 2.2 Nm
2
1.5 – 10 mm (solid) with loops
2
Control contacts 0.25 – 2.5 mm (flexible) 0.5 – 0.7 Nm
2
(1 to 50) 0.34 – 2.5 mm (solid)
27
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Electrical connection AC 01.2 Intrusive Profibus DP
1. Insert the socket carrier [5] into the connection housing [1] and fasten with
screws [4].
2. Clean sealing faces of connection housing [1] and housing.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit connection housing [1] and fasten screws [2] evenly crosswise.
6. Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
28
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Electrical connection
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
29
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Electrical connection AC 01.2 Intrusive Profibus DP
Table 16:
Functions of switches [S1] and [S2]1)
[S1] ON Fieldbus termination channel 1 ON
OFF Fieldbus termination channel 1 OFF
[S2] ON Fieldbus termination channel 2 ON (option)
OFF Fieldbus termination channel 2 OFF (option)
1) Upon delivery, the switches [S1] and [S2] are set to position OFF.
Cable connection 1. Always link A connections to green wire and B connections to red wire.
2. If the actuator is the final fieldbus device in the fieldbus segment:
2.1 Switch on the termination resistor for channel 1 using switch [S1] (position
ON).
2.2 For redundancy: Switch on the termination resistor for channel 2 using
switch [S2] (position ON).
Information: As soon as the termination resistors are switched on, the
connection to the next fieldbus device is automatically interrupted to avoid
multiple terminations.
3. Connect cable shield largely to shielding clamp [X].
30
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Electrical connection
31
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Electrical connection AC 01.2 Intrusive Profibus DP
32
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Electrical connection
Explosion hazard!
Risk of death or serious injury.
→ Prior to opening the device (removing the plug) ensure that the device is free
of gas and voltage!
→ Do NOT switch on voltage in potentially explosive atmospheres.
33
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Electrical connection AC 01.2 Intrusive Profibus DP
Table 17:
Terminal cross sections and earth connection tightening torques
Conductor type Terminal cross sections Tightening torques
Solid wire and stranded 2.5 mm² to 6 mm² 3 – 4 Nm
Fine stranded 1.5 mm² to 4 mm² 3 – 4 Nm
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.
34
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Operation
6. Operation
35
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Operation AC 01.2 Intrusive Profibus DP
➥ The actuator can now be operated using the push buttons [1 – 3]:
- Run actuator in direction OPEN: Press push button [1] .
- Stop actuator: Press push button STOP [2].
- Run actuator in direction CLOSE: Press push button [3] .
Information OPEN and CLOSE operation commands can be given either in push-to-run or in
self-retaining operation mode. In self-retaining mode, the actuator runs to the defined
end position after pressing the button, unless another command has been received
beforehand. For further information, please refer to Manual (Operation and setting).
36
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Operation
6.3. Menu navigation via push buttons (for settings and indications)
Menu navigation for display and setting is made via the push buttons [1 – 4] of the
local controls.
Set the selector switch [5] to position 0 (OFF) when navigating through the menu.
The bottom row of the display [6] serves as navigation support and explains which
push buttons [1 – 4] are used for menu navigation.
Figure 34:
37
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Operation AC 01.2 Intrusive Profibus DP
38
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Operation
● the push buttons on the local controls have not been operated within 10 minutes
● or by briefly pressing C
Direct display via ID When entering the ID within the main menu, screens can be displayed directly (without
clicking through).
Figure 38: Direct display (example)
Password A password must be entered to allow parameter modification. The display indicates:
Password 0***
A specific password is assigned to each user level and permits different actions.
Table 19:
User levels and authorisations
Designation (user level) Authorisation/password
Observer (1) Verify settings
No password required
Operator (2) Change settings
Default factory password: 0000
Maintenance (3) Reserved for future extensions
Specialist (4) Change device configuration
e.g. type of seating, assignment of output contacts
Default factory password: 0000
Service (5) Service staff
Change configuration settings
AUMA (6) AUMA administrator
1. Select desired menu and hold down push button for approx. 3 seconds.
➥ Display indicates the set user level, e.g Observer (1)
2. Select higher user level via Up ▲ and confirm with Ok.
➥ Display indicates: Password 0***
39
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Operation AC 01.2 Intrusive Profibus DP
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display...
Change passwords 3. Select parameter Change passwords either:
→ click via the menu to parameter, or
→ via direct display: press and enter ID M0229
- Display indicates: ▶ Change passwords
- The user level is indicated in the top row (1 – 6), e.g.:
- For user level 1 (view only), passwords cannot be changed. To change pass-
words, you must change to a higher user level. For this, enter a password via
a parameter.
4. For a user level between 2 and 6: Press push button Ok.
➥ The display indicates the highest user level, e.g.: For user 4
5. Select user level via push buttons Up ▲ Down ▼ and confirm with Ok.
➥ Display indicates: ▶ Change passwords Password 0***
6. Enter current password (→ enter password).
➥ Display indicates: ▶ Change passwords Password (new) 0***
7. Enter new password (→ enter password).
➥ Display indicates: ▶ Change passwords For user 4 (example)
8. Select next user level via push buttons Up ▲ Down ▼ or cancel the process
via Esc.
6.5. Language in the display
The AUMATIC actuator controls display is multilingual.
6.5.1. Language change
Display... M0009
Language M0049
40
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Operation
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display...
Change language 3. Press Ok.
➥ Display indicates: ▶ Language
4. Press Ok.
➥ Display indicates the selected language, e.g.: ▶ Deutsch
5. The bottom row of the display indicates:
→ Save → continue with step 10
→ Edit → continue with step 6
6. Press Edit.
➥ Display indicates: ▶ Observer (1)
7. Select user level via Up ▲ Down ▼ resulting in the following significations:
→ black triangle: ▶ = current setting
→ white triangle: ▷ = selection (not saved yet)
8. Press Ok.
➥ Display indicates: Password 0***
9. Enter password (→ enter password).
➥ Display indicates: ▶ Language and Save (bottom row)
Language selection 10. Select new language via Up ▲ Down ▼ resulting in the following significations:
→ black triangle: ▶ = current setting
→ white triangle: ▷ = selection (not saved yet)
11. Confirm selection via Save.
➥ The display changes to the new language.The new language selection is saved.
41
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Indications AC 01.2 Intrusive Profibus DP
7. Indications
7.1. Indications during commissioning
LED test When switching on the power supply, all LEDs on the local controls illuminate for
approx. 1 second. This optical feedback indicates that the voltage supply is connected
to the controls and all LEDs are operable.
Figure 40: LED test
Language selection During the self-test, the language selection can be activated so that the selected
language is immediately indicated in the display. For this, set selector switch to
position 0 (OFF).
Activate language selection:
1. Display indicates in the bottom row: Language selection menu? 'Reset'
2. Press push button RESET and hold it down until the following text is displayed
in the bottom line: Language menu loading, please wait.
Figure 41: Self-test
If the language selection feature has been activated during the self-test, the menu
for selecting the display language will now be indicated. For further information on
language setting, please refer to chapter <Language in the display>.
Figure 43: Language selection
If no entry is made over a longer period of time (approx. 1 minute), the display
automatically returns to the first status indication.
7.2. Indications in the display
Status bar
The status bar (first row in the display) indicates the operation mode [1], the presence
of an error [2] and the ID number [3] of the current display indication.
42
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Indications
Reaching the preset end positions is additionally indicated via (CLOSED) and
(OPEN) symbols.
Figure 47: End position CLOSED/OPEN reached
43
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Indications AC 01.2 Intrusive Profibus DP
Torque (S0002)
The indication is only available if the actuator is equipped with an MWG (magnetic
limit and torque transmitter).
● S0002 on the display indicates the torque applied at the actuator output.
● The bar graph display appears after approx. 3 seconds.
Figure 48: Torque
Select unit The push button allows to select the unit displayed (percent %, Newton metre Nm
or "foot-pound" ft-lb
Figure 49: Units of torque
Display in percent 100 % indication equals the max. torque indicated on the name plate of the actuator.
Example: SA 07.6 with 20 – 60 Nm.
● 100 % corresponds to 60 Nm of nominal torque.
● 50 % corresponds to 30 Nm of nominal torque.
Operation commands (S0003)
The display S0003 indicates:
● active operation commands, like e.g.: Operation in direction CLOSE or in direc-
tion OPEN
● the actual value E2 as bar graph indication and as value between 0 and 100
%.
● for setpoint control (positioner): setpoint E1
● for stepping mode or for intermediate positions with operation profile: pivot
points and operation behaviour of pivot points
The navigation support (bottom row) is faded out after approx. 3 seconds and the
axis/axes for pivot point display are shown.
OPEN - CLOSE control Active operation commands (OPEN, CLOSE, ...) are shown above the bar graph
display. The figure below shows the operation command in direction CLOSE.
Figure 50: Display for OPEN - CLOSE control
44
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Indications
Setpoint control If the positioner is enabled and activated, the bar graph indication for E1 (position
setpoint) is displayed.
The direction of the operation command is displayed by an arrow above the bar
graph indication.The figure below shows the operation command in direction CLOSE.
Figure 51: Indication for setpoint control (positioner)
E1 Position setpoint
E2 Actual position value
Pivot point axis The pivot points and their operation behaviour (operation profile) are shown on the
pivot point axis by means of symbols.
The symbols are only displayed if at least one of the following functions is activated:
Operation profile M0294
Timer CLOSE M0156
Timer OPEN M0206
Figure 52: Examples: on the left pivot points (intermediate positions); on the right
stepping mode
These indications are available if the parameter Diagnostic classific. M0539 is set
to AUMA.
Warnings (S0005)
If a warning has occurred, the display shows S0005:
● the number of warnings occurred
● a blinking question mark after approx. 3 seconds
45
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Indications AC 01.2 Intrusive Profibus DP
These indications are available, if the parameter Diagnostic classific. M0539 is set
to NAMUR.
Out of Specification (S0008)
The S0008 indication shows out of specification indications according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows S0008:
● the number of indications occurred
● a blinking triangle with question mark after approx. 3 seconds
Figure 56: Out of specification
46
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Indications
47
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Indications AC 01.2 Intrusive Profibus DP
48
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Indications
49
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Signals (output signals) AC 01.2 Intrusive Profibus DP
Feedback signals via fieldbus can be configured. Configuration is possible for both
data structure and data contents.
Configuration is defined via the GSD file only.
Information If required, download the GSD file (General Station Description) from the Internet:
www.auma.com
For information on the feedback signals via fieldbus and the configuration of the
parameters via fieldbus interface, refer to Manual (Device integration fieldbus) Profibus
DP.
8.2. Status signals via output contacts (digital outputs)
Conditions Output contacts are only available if a parallel interface is provided in addition to the
fieldbus interface.
Characteristics Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
8.2.1. Assignment of outputs
The output signals Coding DOUT 1 – Coding DOUT 6 can be set either to high active
or low active.
● High active = output contact closed = signal active
● Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1 = Low active
Coding DOUT 2–Coding DOUT 6 = High active
50
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Signals (output signals)
51
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Commissioning (basic settings) AC 01.2 Intrusive Profibus DP
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display...
Select parameter 3. Select parameter either:
→ click via the menu to parameter, or
→ via direct display: Press and enter ID M0086 or M0087
➥ Display indicates: End position CLOSED
CLOSE or OPEN 4. Use Up ▲ Down ▼ to select:
→ ▶ End position CLOSED
→ ▶ End position OPEN
➥ The black triangle ▶ indicates the current selection.
5. Press Ok.
➥ Display indicates the current setting: Limit or Torque
➥ The bottom row of the display indicates either:
- Edit → continue with step 6
- Save → continue with step 10
6. Press Edit.
➥ Display indicates: ▶ Specialist (4)
52
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Commissioning (basic settings)
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display...
Set fieldbus address 3. Select parameter either:
→ (by clicking through the menu)
→ or press and enter IDs M0098 or M0295 (direct selection)
➥ Display indicates: DP1 slave address
4. Select via Up ▲ Down ▼:
→ ▶ DP1 slave address
→ ▶ DP2 slave address
➥ The black triangle ▶ indicates the current selection.
5. Press Ok.
➥ Display shows the set address.
6. The bottom row of the display indicates:
→ Edit→ continue with step 7
→ Up ▲ Down ▼ → continue with step 11
7. Press Edit.
➥ Display indicates: Observer (1)
53
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Commissioning (basic settings) AC 01.2 Intrusive Profibus DP
1. Loosen screws [2] and remove cover [1] from the switch compartment.
54
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Commissioning (basic settings)
55
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Commissioning (basic settings) AC 01.2 Intrusive Profibus DP
Black section:
[1] Setting spindle: End position CLOSED
[2] Pointer: End position CLOSED
[3] Mark: End position CLOSED is set
White section:
[4] Setting spindle: End position OPEN
[5] Pointer: End position OPEN
[6] Mark: End position OPEN is set
56
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Commissioning (basic settings)
Black section:
[1] Setting spindle: Running direction CLOSE
[2] Pointer: Running direction CLOSE
[3] Mark: Intermediate position CLOSED is set
White section:
[4] Setting spindle: Running direction OPEN
[5] Pointer: Running direction OPEN
[6] Mark: Intermediate position OPEN is set
Information After 177 turns (control unit for 2 – 500 turns/stroke) or 1,769 turns (control unit for
2 – 5,000 turns/stroke), the intermediate switches release the contact.
9.6.1. Running direction CLOSE (black section): set
57
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Commissioning (basic settings) AC 01.2 Intrusive Profibus DP
3. Press down and turn setting spindle [4] with screw driver in direction of the
arrow and observe the pointer [5]: While a ratchet click is felt and heard, the
pointer [5] moves 90° every time.
4. As soon as the pointer [5] is 90° from mark [6]: Continue turning slowly.
5. As soon as the pointer [5] moves to mark [6]: Stop turning and release setting
spindle.
➥ The intermediate position setting in running direction OPEN is complete.
6. If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
9.7. Test run
Only perform test run only once all settings previously described have been
performed.
The direction of rotation can be checked at the position indicator if available. (Chapter
<Direction of rotation at mechanical position indicator: check>)
The direction of rotation must be checked at the hollow shaft/stem if no mechanical
position indicator is available. (Chapter <Direction of rotation at hollow shaft/stem:
check>)
9.7.1. Direction of rotation at mechanical position indicator: check
58
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Commissioning (basic settings)
59
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Commissioning (basic settings) AC 01.2 Intrusive Profibus DP
→ Operate actuator electrically (via the push buttons OPEN and CLOSE of the
local controls) once to end position OPEN and once to end position CLOSED.
If no reference operation is performed after changing the limit switching, the feedback
signal via the bus is not correct. The bus signals the missing reference operation as
a warning.
9.8. Switch compartment: close
✔ If options (e.g. potentiometer, position transmitter) are available: Only close switch
compartment once all optional equipment has been successfully set.
60
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Commissioning (optional equipment settings)
1) Power supply possible via: AC, AM actuator controls or external power supply
2) Depending on temperature range of the actuator: Refer to name plate
Setting elements The EWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
All settings are made via the two push buttons [S1] and [S2].
Figure 68: View on control unit when switch compartment is open
Table 22:
Short overview on push button functions
Push but- Function
tons
[S1] + [S2] → press simultaneously for 5 s: Activate setting mode
[S1] → press in setting mode for 3 s: Set 4 mA
→ press in setting mode for 6 s: Set 0 mA
→ press in operation for 3 s: Switch on/off LED end position signalling.
→ touch in end position: Reduce current value by 0.02 mA
[S2] → press in setting mode for 3 s: Set 20 mA
→ press in operation for 3 s: Switch on/off LED end position signalling.
→ touch in end position: Increase current value by 0.02 mA
61
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Commissioning (optional equipment settings) AC 01.2 Intrusive Profibus DP
For measuring range setting, voltage must be applied at the position transmitter.
For output current verification, connect a test device for 0 – 20 mA to measurement
points (+/–) (for 2-wire systems, connecting a test device is imperatively required).
Information ● Both measuring ranges 0/4 – 20 mA and 20 – 0/4 mA (inverse operation) can
be set.
During setting process, the measuring range (normal or inverse operation) is
assigned to the end positions by push button S1/S2 assignment.
● For 2-wire systems, switch off <LED end position signalling> prior to setting the
measuring range.
● Setting mode activation clears the settings in both end positions and sets the
output current to a value of 3.5 mA. After activation, both end values (0/4 mA
and 20 mA) need to be reset.
● In case of inadvertent incorrect adjustment, the settings can always be reset
by renewed activation of the setting mode (simultaneous pressing of [S1] and
[S2]).
Activate setting mode 1. Press both push buttons [S1] and [S2] and hold down for 5 seconds:
➥ By pulsing double flashes, the LED indicates that the setting mode is correctly
activated:
➥ For any other LED flash sequence (single/triple flashing): Refer to <Faults
during commissioning>.
Set measuring range 2. Operate valve in one of the end positions (OPEN/CLOSED).
3. Set desired output current (0/4 mA or 20 mA):
→ for 4 mA: Hold down push button [S1] for approx. 3 seconds,
until LED is blinking slowly .
→ for 0 mA: Hold down push button [S1] for approx. 6 seconds,
until LED is blinking fast .
→ for 20 mA: Hold down push button [S2] for approx. 3 seconds,
until LED is illuminated .
Information: For 2-wire systems read current values at test device.
4. Operate valve into opposite end position.
➥ The value set in end position (0/4 mA or 20 mA) does not change during travel
in setting mode.
5. Perform setting in the second end position following the same steps.
6. Approach both end positions again to check the setting.
→ If the measuring range cannot be set:
Refer to <Faults during commissioning>.
→ If the current values (0/4/20 mA) are incorrect:
Refer to <Current values: adjust>.
→ If the current value fluctuates (e.g. Between 4.0 – 4.2 mA):
Switch off LED end position signalling.
Refer to <LED end position signalling: switch on/off>.
10.1.2. Current values : adjust
The current values (0/4/20 mA) set in end positions can be adjusted at any time.
Common values are e.g. 0.1 mA (instead of 0 mA) or 4.1 mA (instead 4 mA).
62
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Commissioning (optional equipment settings)
Information If the current value fluctuates (e.g. between 4.0 – 4.2mA), the <LED end position
signalling> must be switched off for current adjustment.
→ Operate valve in desired end position (OPEN/CLOSED).
→ Reduce current value: Press push button [S1]
(the current is reduced by 0.02 mA every time the push button is
pressed)
→ Increase current value: Press push button [S2]
(the current is increased by 0.02 mA every time the push button is
pressed)
10.1.3. LED end position signalling: switch on/off
The LED behaviour for end position reached can be set as follows: blinking/continuous
illumination or no illumination. During setting mode, end position signalling is switched
on.
Switching on and off 1. Operate valve in one of the end positions (OPEN/CLOSED).
2. Hold down push buttons [S1] or [S2] for approx. 3 seconds.
➥ End position signalling is switched on or off.
Table 23:
LED behaviour when end position signalling is switched on
Set output current LED behaviour in end position
4 mA
LED is blinking slowly
0 mA
LED is blinking fast
20 mA
LED is illuminated
10.2. Potentiometer
The potentiometer is used as travel sensor and records the valve position.
Setting elements The potentiometer is housed in the actuator switch compartment. The switch
compartment must be opened to perform any settings. Refer to <Switch compartment:
open>.
Setting is made via potentiometer [1].
Figure 69: View on control unit
[1] Potentiometer
Information Due to the ratio of the reduction gearing, the complete resistance range/stroke is not
always covered. Therefore, external adjustment (setting potentiometer) must be
provided.
1. Move valve to end position CLOSED.
63
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Commissioning (optional equipment settings) AC 01.2 Intrusive Profibus DP
1) Power supply possible via: AC, AM actuator controls or external power supply
2) Depending on temperature range of the actuator: Refer to name plate
Setting elements The RWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
Setting is made via three potentiometers [1], [2] and [3].
Figure 70: View on control unit when switch compartment is open
For measuring range setting, voltage must be applied at the position transmitter.
64
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Commissioning (optional equipment settings)
65
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Corrective action AC 01.2 Intrusive Profibus DP
Table 25:
Faults during operation/commissioning
Fault Description/cause Remedy
Mechanical position indicator cannot Reduction gearing is not suitable for turns/stroke Set gear stage of the reduction gearing.
be set. of the actuator.
In spite of correct setting of mechan- The overrun was not considered when setting the ● Determine overrun: Overrun = travel covered
ical limit switching, actuator operates limit switching. from switching off until complete standstill.
into the valve or actuator end position. The overrun is generated by the inertia of both the ● Set limit switching again considering the over-
actuator and the valve and the delay time of the run. (Turn handwheel back by the amount of
actuator controls. the overrun)
Measuring range 0/4 – 20 mA or Reduction gearing is not suitable for turns/stroke Set gear stage of the reduction gearing.
maximum value 20 mA at position of the actuator.
transmitter cannot be set or supplies
an incorrect value.
The measuring range 0/4 – 20 mA at The LED on the EWG either flashes in setting mode Call service.
EWG position transmitter cannot be a) single flash or b) triple flash:
set.
Switch check
The red test buttons [1] and [2] are used for manual operation of the switches:
1. Turn test button [1] in direction of the TSC arrow: Torque switch CLOSED trips.
3. Turn test button [2] in direction of the TSO arrow: Torque switch OPEN trips.
If the actuator is equipped with a DUO limit switching (option), the intermediate
position switches (LSA and LSB) will be operated at the same time as the torque
switches.
1. Turn test button [1] in direction of the LSC arrow: Limit switch CLOSED trips.
2. Turn test button [2] in direction of the LSO arrow: Limit switch OPEN trips.
11.2. Fault indications and warning indications
Faults interrupt or prevent the electrical actuator operation. In the event of a fault,
the display backlight is red.
Warnings have no influence on the electrical actuator operation. They only serve
for information purposes. The display remains white.
Collective signals include further indications. They can be displayed via the
Details push button. The display remains white.
66
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Corrective action
Table 26:
Faults and warnings via status indications in the display
Indication on display Description/cause Remedy
S0001 Instead of the valve position, a status text is dis- For a description of the status texts, refer to Manual
played. (Operation and setting).
S0005 Collective signal 02: For indicated value > 0: Press push button De-
Warnings Indicates the number of active warnings. tails.
For details, refer to <Warnings and Out of specific-
ation> table.
S0006 Collective signal 04: For indicated value > 0: Press push button De-
Not ready REMOTE Indicates the number of active signals. tails.
For details, refer to <Not ready REMOTE and
Function check> table.
S0007 Collective signal 03: For indicated value > 0: Press push button Details
Fault Indicates the number of active faults. to display a list of detailed indications.
The actuator cannot be operated. For details, refer to <Faults and Failure> table.
S0008 Collective signal 07: For indicated value > 0: Press push button De-
Out of specification Indication according to NAMUR recommendation tails.
NE 107 For details, refer to <Warnings and Out of specific-
Actuator is operated outside the normal operation ation> table.
conditions.
S0009 Collective signal 08: For indicated value > 0: Press push button De-
Function check Indication according to NAMUR recommendation tails.
NE 107 For details, refer to <Not ready REMOTE and
The actuator is being worked on; output signals are Function check> table.
temporarily invalid.
S0010 Collective signal 09: For indicated value > 0: Press push button Details
Maintenance required Indication according to NAMUR recommendation to display a list of detailed indications.
NE 107
Recommendation to perform maintenance.
S0011 Collective signal 10: For indicated value > 0: Press push button Details
Failure Indication according to NAMUR recommendation to display a list of detailed indications.
NE 107 For details, refer to <Faults and Failure> table.
Actuator function failure, output signals are invalid
Table 27:
Warnings and Out of specification
Indication on display Description/cause Remedy
Config. warning Collective signal 06: Press push button Details to display a list of indi-
Possible cause: vidual indications.
Configuration setting is incorrect. For a description of the individual signals, refer to
The device can still be operated with restrictions. Manual (Operation and setting).
Internal warning Collective signal 15: Press push button Details to display a list of indi-
Device warnings vidual indications.
The device can still be operated with restrictions. For a description of the individual signals, refer to
Manual (Operation and setting).
24 V DC external The external 24 V DC voltage supply of the controls Check 24 V DC voltage supply.
has exceeded the power supply limits.
Wrn op.mode run time Warning on time max. running time/h exceeded ● Check modulating behaviour of actuator.
● Check parameter Perm. run time M0356, re-set
if required.
Wrn op.mode starts Warning on time max. number of motor starts ● Check modulating behaviour of actuator.
(starts) exceeded ● Check parameter Permissible starts M0357, re-
set if required.
Failure behav. active The failure behaviour is active since all required Verify signals:
setpoints and actual values are incorrect. ● Setpoint E1
● Actual value E2
● Actual process value E4
● Check connection to master.
● Check (clear) status of master.
67
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Corrective action AC 01.2 Intrusive Profibus DP
68
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Corrective action
Table 28:
Faults and Failure
Indication on display Description/cause Remedy
Configuration error Collective signal 11: Press push button Details to display a list of indi-
Configuration error has occurred. vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Config. error REMOTE Collective signal 22: Press push button Details to display a list of indi-
Configuration error has occurred. vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Internal error Collective signal 14: AUMA service
Internal error has occurred. Press push button Details to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Torque fault CLOSE Torque fault in direction CLOSE Perform one of the following measures:
● Issue operation command in direction OPEN.
● Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
● Execute reset command via fieldbus.
Torque fault OPEN Torque fault in direction OPEN Perform one of the following measures:
● Issue operation command in direction CLOSE.
● Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
● Execute reset command via fieldbus.
Phase fault ● When connecting to a 3-ph AC system and with Test/connect phases.
internal 24 V DC supply of the electronics:
Phase 2 is missing.
● When connecting to a 3-ph or 1-ph AC system
and with external 24 V DC supply of the elec-
tronics: One of the phases L1, L2 or L3 is
missing.
Incorrect phase seq The phase conductors L1, L2 and L3 are connected Correct the sequence of the phase conductors L1,
in the wrong sequence. L2 and L3 by exchanging two phases.
Only applicable if connected to a 3-ph AC system.
Mains quality Due to insufficient mains quality, the controls cannot ● Check mains voltage.
detect the phase sequence (sequence of phase For 3-phase/1-phase AC current, the permiss-
conductors L1, L2 and L3) within the pre-set time ible variation of the mains voltage is ±10 %
frame provided for monitoring. (option ±30 %). The permissible variation of the
mains voltage is ±5 %
● Check parameter Tripping time M0172, extend
time frame if required.
Thermal fault Motor protection tripped ● Cool down, wait.
● If the fault indication display persists after cool-
ing down:
- Set selector switch to position Local con-
trol (LOCAL) and reset fault indication via
push button RESET.
- Execute reset command via fieldbus.
● Check fuses.
Fault no reaction No actuator reaction to operation commands within Check movement at actuator.
the set reaction time.
Poti Out of Range Potentiometer is outside the permissible range. Check device configuration:
Parameter Low limit Uspan M0832 must be less
than parameter Volt.level diff. potent. M0833.
LPV not ready LPV: Lift Plug Valve function
The master actuator signals a fault
Wrn input AIN 1 Loss of signal analogue input 1 Check wiring.
Wrn input AIN 2 Loss of signal analogue input 2 Check wiring.
69
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Corrective action AC 01.2 Intrusive Profibus DP
Table 29:
Not ready REMOTE and Function check (collective signal 04)
Indication on display Description/cause Remedy
Wrong oper. cmd Collective signal 13: ● Check operation commands (reset/clear all op-
Possible causes: eration commands and send one operation
● Several operation commands (e.g. OPEN and command only).
CLOSE simultaneously, or OPEN and SET- ● Set parameter Positioner to Function active.
POINT operation simultaneously) ● Check setpoint.
● A setpoint is present and the positioner is not Press push button Details to display a list of indi-
active vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Sel. sw. not REMOTE Selector switch is not in position REMOTE. Set selector switch to position REMOTE.
Service active Operation via service interface (Bluetooth) and Exit service software.
AUMA CDT service software.
Disabled Actuator is in operation mode Disabled. Check setting and status of function <Local controls
enable>.
EMCY stop active The EMERGENCY stop switch has been operated. ● Enable EMERGENCY stop switch.
The motor control power supply (contactors or ● Reset EMERGENCY stop state by means of
thyristors) is disconnected. Reset command.
EMCY behav. active Operation mode EMERGENCY is active (EMER- ● Detect cause for EMERGENCY signal.
GENCY signal was sent). ● Verify failure source.
0 V are applied at the EMERGENCY input. ● Apply +24 V DC at EMERGENCY input.
I/O interface The actuator is controlled via the I/O interface (par- Check I/O interface.
allel).
Handwheel active Manual operation is activated. Start motor operation.
FailState fieldbus Fieldbus connection available, however no process Verify master configuration
data transmission by the master.
Local STOP A local STOP is active. Release push button STOP.
Push button STOP of local controls is operated.
70
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Corrective action
11.3. Fuses
11.3.1. Fuses within the actuator controls
Fuses used
F3 Internal 24 V DC supply
Table 31:
Secondary fuses F3 (internal 24 V DC supply)
G fuse according to IEC 60127-2/III F3 AUMA art. no.
Size 5 x 20 mm
Voltage output (power supply unit) = 24 V 2.0 A T; 250 V K006.106
Voltage output (power supply unit) = 115 V 2.0 A T; 250 V K006.106
F4 Table 32:
Secondary fuses F4 (internal AC supply)1)
G-fuse according to IEC 60127-2/III F4 AUMA art. no.
Size 5 x 20 mm
Voltage output (power supply unit) = 24 V 1.25 A T; 250 V K001.184
Voltage output (power supply unit) = 115 V — —
1) Fuse for: Switch compartment heater, reversing contactor control, PTC tripping device (at 24 V AC
only), at 115 V AC also control inputs OPEN, STOP, CLOSE
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
71
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Corrective action AC 01.2 Intrusive Profibus DP
2. Pull fuse holder [3] out of pin carrier, open fuse cover and replace old fuses by
new ones.
Test/replace fuses F3/F4
1. Loosen screws [1] and remove cover [2] on the rear of the actuator controls.
Figure 72:
The power supply unit has measurement points (solder pins) allowing to perform
a resistance (continuity) measurement:
Table 33:
Verifying Measuring points
F3 MTP5 – MTP6
F4 MTP7 – MTP8
2. To replace defective fuses: Carefully loosen power supply unit [3] and pull out.
(The fuses are on the equipped part of the power supply board).
72
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Corrective action
73
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Servicing and maintenance AC 01.2 Intrusive Profibus DP
AUMA
AUMA offers extensive service such as servicing and maintenance as well as
Service & Support customer product training. For the relevant contact addresses, please refer to
<Addresses> in this document or to the Internet (www.auma.com)
After submersion:
● Check actuator.
● In case of ingress of water, locate leaks and repair. Dry device correctly and
check for proper function.
74
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Servicing and maintenance
12.2. Maintenance
75
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Technical data AC 01.2 Intrusive Profibus DP
76
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Technical data
Service conditions
Use Indoor and outdoor use permissible
Mounting position Any position
Installation altitude ≤ 2 000 m above sea level
> 2,000 m above sea level, on request
Ambient temperature Standard: –30 °C to +70 °C
Options: –40 °C to +70 °C
–40 °C to +80 °C (multi-turn actuators for open-close duty with 3-phase/1-phase AC motors)
–60 °C to +60 °C (with 3-phase/1-phase AC motors)
0 °C to +120 °C (multi-turn actuators for open-close duty with 3-phase AC motor)
0 °C to +100 °C (multi-turn actuators for modulating duty with 3-phase AC motor)
For exact version, refer to actuator name plate.
Humidity Up to 100 % relative humidity across the entire permissible temperature range
77
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Technical data AC 01.2 Intrusive Profibus DP
Service conditions
Enclosure protection according to Standard: IP68 (with AUMA 3-phase/1-phase AC or DC motor)
EN 60529 For special motors differing enclosure protection available (refer to motor name plate)
Option: DS Terminal compartment additionally sealed against interior (double sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
● Depth of water: Maximum 8 m head of water
● Duration of continuous immersion in water: Maximum 96 hours
● Up to 10 operations during flooding.
● Modulating duty is not possible during continuous immersion.
For exact version, refer to actuator name plate.
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 2 g, from 10 to 200 Hz (for actuators in AUMA NORM version)
IEC 60068-2-6 1 g, from 10 to 200 Hz (for actuators with mounted AUMA actuator controls)
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Indications apply to actuators with AUMA 3-phase AC motor and AUMA plug/socket
connector. They are not valid in combination with gearboxes.
Corrosion protection Standard: KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
KX-G : same as KX, however aluminium-free version (outer parts)
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Other colours are possible on request.
Lifetime AUMA multi-turn actuators meet or exceed the lifetime requirements of EN 15714-2. For further details,
please contact AUMA
Noise level < 72 dB (A)
Further information
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
78
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Technical data
79
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Technical data AC 01.2 Intrusive Profibus DP
Control voltage and current con- Standard: 24 V DC, current consumption: approx. 10 mA per input
sumption of optional, digital addition-
Options: 48 V DC, current consumption: approx. 7 mA per input
al inputs
60 V DC, current consumption: approx. 9 mA per input
115 V DC, current consumption: approx. 15 mA per input
100 – 120 V AC, current consumption : approx. 15 mA per input
All input signals must be supplied with the same potential.
Status signals Via Profibus DP interface
Fieldbus interface with additional Additional, binary output signals (only available in combination with additional input signals (option)
output signals (option) ● 6 programmable output contacts:
- 5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive load)
Default configuration: End position CLOSED, end position OPEN, selector switch REMOTE,
torque fault CLOSE, torque fault OPEN
- 1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
Default configuration: Collective fault signal (torque fault, phase failure, motor protection tripped)
● 6 programmable output contacts:
- 5 potential-free change-over contacts with one common, max. 250 V AC, 1 A (resistive load)
- 1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
● 6 programmable output contacts:
- 6 potential-free change-over contacts without one common, max. 250 V AC, 5 A (resistive load)
● 6 programmable output contacts:
- 4 mains failure proof potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive
load), 1 potential-free NO contact, max. 250 V AC, 1 A (resistive load), 1 potential-free change-
over contact, max. 250 V AC, 5 A (resistive load)
● 6 programmable output contacts:
- 4 mains failure proof potential-free NO contacts, max. 250 V AC, 5 A (resistive load), 2 potential-
free change-over contacts, max. 250 V AC, 5 A (resistive load),
All binary output signals must be supplied with the same potential.
● Analogue output signal for position feedback
- Galvanically isolated position feedback 0/4 – 20 mA (load max. 500 Ω)
Voltage output Standard: Auxiliary voltage 24 V DC: max. 100 mA for supply of control inputs, galvanically isolated
from internal voltage supply.
Option: Auxiliary voltage 115 V AC: max. 30 mA for supply of control inputs, galvanically isolated
from internal voltage supply
(Not possible in combination with PTC tripping device)
Profibus DP-V1 (option) Access to parameters, the electronic name plate and the operating and diagnostic data with acyclic
write/read services
Profibus DP-V2 (option) Redundancy behaviour according to Profibus DP-V2 specification no. 2.212 (Primary and Backup with
RedCom)
Synchronisation of time between actuator controls and Profibus master with subsequent time stamp of
the most important events such as malfunctions, end position and torque signals from actuator controls
80
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Technical data
Bluetooth Bluetooth class II chip, version 2.1: With a range up to 10 m in industrial environments, supports the
Communication interface SPP Bluetooth profile (Serial Port Profile).
Required accessories:
● AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
● AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices)
Application functions Standard: ● Selectable type of seating, limit or torque seating for end position OPEN and end po-
sition CLOSED
● Torque by-pass: Adjustable duration (with adjustable peak torque during start-up time)
● Start and end of stepping mode as well as ON and OFF times can be set individually
for directions OPEN and CLOSE, 1 to 1,800 seconds
● Any 8 intermediate positions: can be set between 0 and 100 %, reaction and signal
behaviour programmable
● Running indication blinking: can be set
● Positioner
- Position setpoint via Profibus DP interface
- Programmable behaviour on loss of signal
- Automatic adaptation of dead band (adaptive behaviour selectable)
- Split range operation
- Change-over between OPEN-CLOSE control and setpoint control possible via
Profibus DP interface
Options: ● PID process controller: with adaptive positioner, via 0/4 – 20 mA analogue inputs for
process setpoint and actual process value
● Multiport valve: Up to 16 positions, signals (pulse or edge)
● Automatic deblocking: Up to 5 operation trials, travel time in opposite direction can be
set
● Static and dynamic torque recording for both rotation directions with torque measure-
ment flange as additional accessory
81
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Technical data AC 01.2 Intrusive Profibus DP
Options: ● Release of local controls via fieldbus interface.Thus, actuator operation can be enabled
or disabled via push buttons on local controls.
● Local STOP
- The actuator can be stopped via push button Stop of local controls if the selector
switch is in position REMOTE. (Not activated when leaving the factory.)
● Interlock for main/by-pass valve: Enabling the operation commands OPEN or CLOSE
via fieldbus interface
● EMERGENCY Stop push button (latching): interrupts electrical operation, irrespective
of the selector switch position.
● PVST (Partial Valve Stroke Test): programmable to check the function of both actuator
and actuator controls: Direction, stroke, operation time, reversing time
Monitoring functions ● Valve overload protection: adjustable, results in switching off and generates fault signal
● Motor temperature monitoring (thermal monitoring): results in switching off and generates fault indic-
ation
● Monitoring the heater within actuator: generates warning signal
● Monitoring of permissible on-time and number of starts: adjustable, generates warning signal
● Operation time monitoring: adjustable, generates warning signal
● Phase failure monitoring: results in switching off and generates fault signal
● Automatic correction of rotation direction upon wrong phase sequence (3-ph AC current)
Diagnostic functions ● Electronic device ID with order and product data
● Logging of operating data: A resettable counter and a lifetime counter each for:
- Motor running time, number of starts, torque switch trippings in end position CLOSED, limit
switch trippings in end position CLOSED, torque switch trippings in end position OPEN, limit
switch trippings in end position OPEN, torque faults CLOSE, torque faults OPEN, motor protection
trippings
● Time-stamped event report with history for setting, operation and faults
● Status signals according to NAMUR recommendation NE 107: "Failure", "Function check", "Out of
specification", "Maintenance required"
● Torque characteristics (for version with MWG in actuator):
- 3 torque characteristics (torque-travel characteristic) for opening and closing directions can be
saved separately.
- Torque characteristics stored can be shown on the display.
Motor protection evaluation Standard: Monitoring the motor temperature in combination with thermoswitches within actuator
motor
Options: ● Thermal overload relay in controls combined with thermoswitches within actuator
● PTC tripping device in combination with PTC thermistors within actuator motor
Overvoltage protection (option) Protection of the actuator and control electronics against overvoltages on the fieldbus cables of up to 4
kV
Electrical connection Standard: AUMA plug/socket connector with screw-type connection
Option: Gold-plated control plug (sockets and plugs)
Threads for cable entries Standard: Metric threads
Options: ● Pg-threads, NPT-threads, G-threads
● Terminals or crimp-type connection
Wiring diagram Refer to name plate
82
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Technical data
Device types DP master class 1, e.g. central controllers such as PLC, PC, ...
DP master class 2, e.g. programming/configuration tools
DP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors
Number of devices 32 devices without repeater, with repeater expandable to 126
Fieldbus access Token-passing between masters and polling for slaves. Mono-master or multi-master systems are pos-
sible.
Supported Profibus DP functions Cyclic data exchange, sync mode, freeze mode, fail safe mode
Profibus DP ident no. 0x0C4F: Standard applications with Profibus DP-V0 and DP-V1
0x0CBD: Applications with Profibus DP-V2
Service conditions
Use Indoor and outdoor use permissible
Mounting position Any position
Installation altitude ≤ 2 000 m above sea level
> 2,000 m above sea level, on request
Ambient temperature Refer to name plate of actuator controls
Humidity Up to 100 % relative humidity across the entire permissible temperature range
83
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Technical data AC 01.2 Intrusive Profibus DP
Service conditions
Enclosure protection according to Standard: IP68
EN 60529
Option: Terminal compartment additionally sealed against interior of actuator controls (double
sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
● Depth of water: Maximum 8 m head of water
● Duration of continuous immersion in water: Maximum 96 hours
● Up to 10 operations during continuous immersion
● Modulating duty is not possible during continuous immersion.
For exact version, refer to actuator controls name plate.
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 1 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. (Not valid in combination with gearboxes)
Corrosion protection Standard: KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Accessories
Wall bracket For actuator controls mounted separately from the actuator, including plug/socket connector.
Connecting cable on request.
Recommended for high ambient temperatures, difficult access, or in case of heavy vibration during
service.
Cable length between actuator and actuator controls is max. 100 m (Not suitable for version with poten-
tiometer in the actuator). Instead of the potentiometer, the actuator has to be equipped with an electronic
position transmitter. (MWG requires a separate data cable.)
Programming software AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices)
Torque measurement flange DMF Accessory for torque measurement for SA/SAR 07.2 – SA/SAR 16.2
Further information
Weight Approx. 7 kg (with AUMA plug/socket connector)
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
84
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Spare parts
85
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Spare parts AC 01.2 Intrusive Profibus DP
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary
from actual delivery.
86
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Spare parts
87
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Spare parts AC 01.2 Intrusive Profibus DP
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary
from actual delivery.
88
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Certificates
15. Certificates
Information Certificates are valid as from the indicated date of issue. Subject to changes without
notice. The latest versions are attached to the device upon delivery and also available
for download at http://www.auma.com.
89
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Index AC 01.2 Intrusive Profibus DP
E
Index Earth connection 34
Electrical connection 22, 77
A Electronic position transmitter 61, 64
Accessories (electrical con- 32 EMC 24
nection) Enclosure protection 8, 9, 9, 78, 84
Accessories for assembly 20 End position signalling 63
Actual value - indication on 44 Error - indication on display 42
display EU Declaration of Conformity 89
Actuator controls terminal 9 EWG 61
plan EWG position transmitter 61
Actuator operation at the local 36
controls F
Actuator operation from re- 37 Failure - indication on display 47
mote Fault 66
Actuator terminal plan 9, 10 Fault - indication on display 46
Ambient temperature 8, 9, 77, 83 Features and functions 82
Analogue signals 51 Fieldbus address 53
Applications 5 Fieldbus cable 24
Assembly 15 Fieldbus cables 30
Assistant App 11 Flange size 10
AUMA Assistant App 11 Frequency range 22
Function check - indication on 47
C display
Cable entries 77 Fuses 71
Cables 23
Cable set 32 G
Certificates 89 GSD file 50
Coating 84
Colour 84 H
Commissioning 5 Handwheel 15
Commissioning (indications 42 Heating system 23
on display) Hollow shaft 59
Commission number 8 Humidity 77
Connecting cable 32
I
Connecting cables 23
Identification 8
Control 9, 10
Indication lights 48
Control inputs Potential 23
Indications 42
Control voltage 10
Indications on display 42
Corrective action 66
Indicator disc 65
Corrosion protection 14, 78, 84
Indicator mark 49
Cross section (fieldbus cable) 24
Input current 10
Current consumption 22
Input signal 10
Current type 9, 22
Input signals Potential 23
D Inspection certificate 10
Data Matrix code 11 Installation altitude 83
Declaration of Incorporation 89 Insulation class 9, 76
Device type 10 Intermediate frame 33
Digital outputs 50 Intermediate position indica- 48
Direct display via ID 39 tion via LEDs
Direction of rotation 58, 59 Intermediate positions 57
Directives 5 Intrusive 11
Display (indications) 42 Inverse operation (0/20 – 4 62
Disposal 75 mA)
Double sealed 33
DUO limit switching 57
90
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Profibus DP Index
L P
Language in the display 40 Packaging 14
LED end position signalling 63 Parking frame 33
LEDs (indication lights) 48 Password 39
Lifetime 78 Password change 40
Limit switching 55, 59 Password entry 39
Local actuator operation 36 Positioner - indication on dis- 45
Local control 36 play
Local controls 36 Position indicator 49, 65
Local setting 37 Position transmitter 10
Lubrication 75 Position transmitter (EWG) 61
Position transmitter (RWG) 64
M Potentiometer 63
Main menu 38 Power class 9
Mains frequency 9, 9, 76 Power class for switchgear 10
Mains voltage 9, 9, 22, 76 Power factor 9
Maintenance 5, 74, 75 Power supply of electronics 22
Maintenance required - indic- 47 Production, year 10
ation on display Protection on site 22
Manual operation 35, 76 Protective measures 5
Mechanical position indicator 49, 65 Push-to-run operation 36
Menu navigation 37
Motor heater 76 Q
Motor operation 36 Qualification of staff 5
Motor protection 9, 76
Motors 76 R
Motor type 9 Range of application 5
Mounting position 83 Recycling 75
Reference operation 60
N Remote actuator operation 37
Name plate 8 Residual current device 23
Nominal current 9 (RCD)
Nominal power 9 Running indication 49
Non-Intrusive 11 RWG 64
Not ready REMOTE - indica- 46
tion on display
O
Operation 5, 35
Operation commands - indic- 44
ations on display
Order number 8, 9, 10
Out of specification - indica- 46
tion on display
Output contacts 50
Output drive type A 15
Output drive types B 18
Output signals 50
Output signals Potential 23
Output speed 8, 9
Overvoltage category 76, 79
91
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit - electromechanical
Index AC 01.2 Intrusive Profibus DP
S W
Safety instructions 5 Wall bracket 32
Safety instructions/warnings 5 Warnings - indication on dis- 45
Safety measures 23 play
Safety standards 23 Wire diameter (fieldbus cable) 24
Screening (fieldbus cable) 24 Wiring diagram 10, 22
Self-locking 76
Self-retaining 36 Y
Serial number 8, 9, 10 Year of production 10
Service 74
Servicing 74
Setpoint - indication on dis- 45
play
Short-circuit protection 22
Signals 50
Signals (analogue) 51
Size 10
Slave address 53
Spare parts 85
Standards 5
Status menu 38
Status signals 50
Status signals Potential 23
Stem 59
Stem nut 16
Stem protection tube 20
Storage 14
Supply networks 22
Support 74
Switch check 66
T
Technical data 76
Technical data for switches 78
Temperature protection 9
Terminal plan 22, 77
Test run 58
Torque - indication on display 44
Torque range 8
Torque switching 54
Transport 12
Type (device type) 10
Type designation 8, 9
Type of duty 9, 76
Type of lubricant 8
Type of networks 22
U
User level 39
V
Valve attachment 77
Valve position - indication on 43
display
Valve stem 20
Vibration resistance 84
Voltage range 22
92
AUMA worldwide
93
AUMA worldwide
B & C Biosciences Ltda. ITG - Iranians Torque Generator AUMA ACTUATORS (Singapore) Pte Ltd.
CO Bogotá D.C. IR 13998-34411 Teheran SG 569551 Singapore
Tel +57 1 349 0475 +982144545654 Tel +65 6 4818750
[email protected] [email protected] [email protected]
www.bycenlinea.com www.auma.com.sg
Trans-Jordan Electro Mechanical Supplies
AUMA Región Andina & Centroamérica JO 11133 Amman NETWORK ENGINEERING
EC Quito Tel +962 - 6 - 5332020 SY Homs
Tel +593 2 245 4614 [email protected] +963 31 231 571
[email protected] [email protected]
www.auma.com AUMA JAPAN Co., Ltd.
JP 211-0016 Kawasaki-shi, Kanagawa Sunny Valves and Intertrade Corp. Ltd.
Corsusa International S.A.C. Tel +81-(0)44-863-8371 TH 10120 Yannawa, Bangkok
PE Miraflores - Lima [email protected] Tel +66 2 2400656
Tel +511444-1200 / 0044 / 2321 www.auma.co.jp [email protected]
[email protected] www.sunnyvalves.co.th
www.corsusa.com DW Controls Co., Ltd.
KR 153-702 Gasan-dong, GeumChun-Gu,, Top Advance Enterprises Ltd.
Control Technologies Limited Seoul TW Jhonghe City, Taipei Hsien (235)
TT Marabella, Trinidad, W.I. Tel +82 2 2624 3400 Tel +886 2 2225 1718
Tel + 1 868 658 1744/5011 [email protected] [email protected]
www.ctltech.com www.actuatorbank.com www.auma-taiwan.com.tw
94
AUMA worldwide
95
AUMA Riester GmbH & Co. KG
P.O. Box 1362
DE 79373 Muellheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 1250
[email protected]
www.auma.com
Y004.762/003/en/1.18