Dr.majid Albana مذكرة حسابية لمركز تجاري
Dr.majid Albana مذكرة حسابية لمركز تجاري
November 2022
1
District Baghdad government see fig1.
1 2 3 4 5
1.20
A 5.36
GUARD
3.70
2.05 2.00
7.10
L
IF
T
7.5000
4.70
1.20
0.95
1.50
B
7.0000
7.5000
7.6000
fig1.
2
1.50
14.50
4.00
2.00
L
IF
T
7.40
10.00
4.70
8.10
10.00 1.50
3.15
1.50
W1
3
COLUMNS & WALL KEY PLAN
2.0 CALCULATION UNTE
Force Unite Kn
Length Unite mm, m
Stress Unite Mpa ,n/mm2
3.0 REFERENCES
3.1 Codes of Practice
The building was designed in accordance with the design requirements of
relevant government gazettes and latest relevant codes. The following is a list of
codes and standards proposed to be used in the checked of this project.
a) ACI 318M-19
b) IBC 2009
c) IRAQ SEISMIC CODE 20017
d) ASCE-16
3.2 SOIL DATA
a) ALLOWABLE BEARING CAPACITY = 110 Kn/m2 F.S =3
b) WATER TABLE LEVEL AT (2.0) M below the existing ground surface
4
L : live load due to intended use and occupancy , including loads due to
movable objects and movable partitions and loads temporarily supported
by the structure during maintenance.
W : wind load ( X- direction & Y- direction)
E : Earthquake load ( X- direction & Y- direction)
4.2 Description of load
The structure will be controlled against construction loads.
4.2.1 Dead loads (D)
Dead weight of structural components is determined on the basis of
geometrical characteristics and material density.
The following unit masses will be used :
-reinforced concrete = 24 Kn/m3
-Waterproofing and roof insulation = 0.3 Kn/m2
- wall part ion = 7 Kn/m3
-Concrete pavers = 22 Kn/m3
-Mortar = 20 Kn/m3
-Plaster = 10 Kn/m3
-Rendering = 22 Kn/m3
-Tile = 24 Kn/m3
-False ceiling =0.3 Kn/m2
-Lightweight partition (per unit area of floor) = 1.0 Kn/m2
Roofing finishes:
-Paving tiles (50 mm) = 1.2 Kn/m2
-waterproofing membrane extruded polystyrene = 0.1 Kn/m2
5
-Earth fill = 20 Kn/m3
6
Windwazrd coefficient (figure 6-6, ASCE 7-16)., leeward coeff. (figure 6-6,
ASCE 7-16)
B) Seismic loading parameters:
The following information related to analysis and design for the lateral
force-resisting system of the building according to Iraq seismic map.
1. Seismic hazard zoning coefff. (clause 3.2.1),Z=I=0.05
2. Seismic importance factor (clause 3.2.2),Z=I
3. Dynamic coeff. Related to soil category (clause 3.2.3),S=I,soil type II
4. Structural system coeff. Specified for various type of structure.
5. Analysis procedure used: Equivalent static force procedure Analysis
according to ASCE 7-16.
7
9. 0.6DL-WIND
10. 0.6DL+1.3EQ
4.3.2 Loadin combination for STRENGTH design (ASCE 7-16and IBC-09)
DL= Dead load , LL= Live Load
1. 1.4DL
2. 1.2DL+1.6LL+1.2T
3. 1.2DL+0.8WIND
4. 1.2DL-0.8WIND
5. 1.2DL+1.0LL+1.6WIND
6. 1.2DL+1.0LL-1.6WIND
7. 0.9DL+1.6WIND
8. 0.9DL-1.6WIND
9.1.1DL+1.3LL+1.4EQ
10. 1.3DL+1.3EQ
8
-Plain mild steel (if any) = 250 Mpa
9
Slab thickness = 200 mm (see fig. below)
Column = 450x850 mm ( see fig. below)
Column = 850x 850 mm (see fig. below)
Column = 0x 00 mm ( see fig. below)
Walls =300 mm (see fig. below)
W1
10
11
14 - ?25 16 - ?25
?10@200 ?10@200
Roof Floor 2Ties/Set 2Ties/Set
Main Bar
Ties
Column Reinf.
Rest See
C 50
Section
3 rd Floor
C 50
Section
Ground Level
foundation
level
job title
(A)
drawing title
SCHEDULE OF COLUMN
Typ. Sec. For Column
designed project manager
ENG : DR-Majid Albana
checked scale date
1-100 3 /2023
drawn job no. sheet no.
12
13
?12@150 B&T MESH
W1
SEC. 2-2
?12@150 B. MESH ?12@150 B. MESH ?12@150 B. MESH
?12@150 B. MESH
?12@200 T. MESH
?12@200 T. MESH
@
H
B
E
S
?
1
6
2
0
0
.
?12@200 . MESH
?12@150 B. MESH
colum Reinf.
MINIMUM LAP LENGTH (UNLESS NOTED ON DRAWINGS) SHOULD BE AS TABLE BELWO :- job title
TOP REINFORCEMENT
Slab Reinf. (A)
drawing title
PLAN OF SLAB
BOTTOM REINFORCEMENT
REINFORCEMENT&SEC.
designed project manager
ENG : DR-Majid Albana
approved
12 ST/D/11
14
B
W1
B
?25@200 B. MESH
?25@200 T. MESH
ADDITIONAL ADDITIONAL
?25@200 mm ?25@200 mm
BOTTOM L=3m BOTTOM L=3m
CONCRETE COVERS
-SLABS = 25 mm
-BEAMS = 40 mm
?25@200 T. MESH
-COLUMNS = 40 mm
?25@200 B. MESH
0 O
B ? A
D
D
L mN
= mA
ADDITIONAL ADDITIONAL
T @ IT
L
O 2 I
?25@200 mm ?25@200 mm
O 2
T 5
M 0
-SLAB ON GRADE = 50 mm
-RAFT FOUNDATION = 75 mm
A ADDITIONAL
?25@200mm
BOTTOM L=3m
(A)
drawing title
Foundation Plan
PLAN OF FOUNDATION
REINFORCEMENT&SEC.
designed project manager
ENG : DR-Majid Albana
checked scale date
1-100
all dim. from ARCH D.W.G. 3 /2023
approved
job no.
4
sheet no.
ST/D/04
15
16
Column size 300x1000 mm
λ=1,(normal concrete)
Maximum column factored load (interior span)= 9300Kn, load case UDL.
17
(B.C.) = 110 KN / m2 ,F.S = 3
18
Fig. Base ppressure app
plied on the soil
19
- Maximum drift X =0.0005906 m at story no. 4 load case 0.9DL+1.4EQ
- Maximum drift Y = 0.006239 m at story no.5 load case 0.9DL+1.4QE
- Drift limitation h/600 = 21000/600 = 35 mm=0.035m
So lateral drift under control
20
21