PROFIBUS®-PA (Process Automation) uses synchronous transfer mode technology, as defined in IEC 61158-2, to
communicate between field devices and the RS 485 backbone of PROFIBUS®-DP. A segment coupler, or gateway is
installed to bridge PROFIBUS®-DP with PROFIBUS®-PA. Otherwise, the protocols are identical, allowing transparent
communication between general purpose automation systems and decentralized field devices.
PROFIBUS®-PA is a master-slave bus. Transmitters used in the process industry are typically slave devices or passive
stations which only communicate at the request of the master.
44
InterlinkBT™ 3000 Campus Drive Plymouth, MN 55441 Phone: (763) 694-2300 Fax: (763) 694-2399 Application Assistance: 1-888-546-5880
Visit InterlinkBT on the Internet: http://www.interlinkbt.com
The Home Run cable is considered the main trunk line of communication. Each device that is connected to the junction
brick is called a spur. In other industrial networks spurs are called drops off the trunk line.
3
Figure 4 - Star Topology Example
Transmitters
Figure 5 - Daisy Chain Layout
In many fieldbus installations it makes sense to mix both Star and Daisy Chain topology layouts. Remember that one of the
benefits to fieldbus is reduced wiring of devices, leading to faster start-up times.
45
InterlinkBT™ 3000 Campus Drive Plymouth, MN 55441 Phone: (763) 694-2300 Fax: (763) 694-2399 Application Assistance: 1-888-546-5880
Fieldbus Cable Specifications
The specifications for PROFIBUS®-PA physical media are defined by IEC 1158-2 and the ISA-S50.02 Part 2 Physical
Layer Standards. There are essentially four types of cable designations for fieldbus. Type A cable is the most preferred
for new installations because it allows for the most versatile lengths. The other types of cable are for installations where
cable already exists from 4-20 mA systems. See Table 1.
InterlinkBT offers both a three conductor and two conductor with the third conductor available for a centralized ground
of devices if needed. InterlinkBT cables meet or exceed the specifications of ANSI/ISA-SP50.02-1992, the fieldbus
standard for use in industrial control systems.
Cable Specifications
Type A Cable
- Designed for harsh environments
- Temperature range of -50 to 105°C(-58 to +221F)
- Governed by: ISA SP50.02 specification
- Sunlight resistant per test
- PLTC and ITC rated (CSA FT4)
- Impedence[Z0 at f r (31.25 kHz)] = 100Ω ± 20%
- Maximum attenuation at 1.25 fr (39 kHZ) = 3.0 dB/km
- Maximum capacitive unbalance to shield = 2 nF/km
- Maximum DC resistance (per conductor) = 24 Ω/km
- Maximum propagation delay change 0. 25 fr to 1.25 fr = 1.7 µs/km
- Conductor cross-sectional area (wire size) = nominal 0.8 mm2 (#18 AWG)
- Minimum shield coverage shall be 90%
46