ONP STP Analysis
ONP STP Analysis
b) Steel
Grade 40 : 280 N/mm2
2.LOADS kN/m3
Density of Concrete Үc : 25 kN/m3
Density of Water Үw : 10
3.SOIL PARAMETERS kN/m2
Safe Bearing Capacity of soil SBC : 250
4.CONCRETE PARAMETERS
Q= σcbt/6 = 0.333 say = 0.350
280
m :
3*σcbc
= 9.34
n 10/(190/9.34+10) *d
= 0.384
j = 0.872
5.00 CAPACITY CALCULATIONS :
14.1 m
36.6 m
Lx = 4 m
Ly = 4 m
Type of Panel : Interior Panel
Loading :
Self weight = 0.12*25 = 3 KN/sqm
Live load = 1.5 KN/sqm
Finishings = 0.5 KN/sqm
Total Load w = 5 KN/sqm
Ly/Lx = 1
The slab is designed as two way slab
Moment Coefficient as per Table 26 of IS 456 - 2000 -αx = -0.032
+αx = 0.024
-αy = -0.032
+αy = 0.024
Moments along short span :
Support moment = 5*-0.032*4^2 = -2.56 kNm
Span moment = 5*0.024*4^2 = 1.92 kNm
Moments along longer span :
Support moment = 5*-0.032*4^2 = -2.56 kNm
Span moment = 5*0.024*4^2 = 1.92 kNm
Depth required 'D' 2.56 x 10^6
= = 85.523597412 mm
0.350
Provided depth d = 120 mm
= 120-(25+5)
= 90 mm
= ok
Area of Reinforcement (-ve) in shorter direction (Ast) = M.R
σst*j*d
= 2.56 x10^6
150*0.872*90
= 217.465 sqmm
Min Area of reinforcement (Ast min) = (0.24*1000*120)/100/2 = 144 sqmm
Shorter span :
Mid span : 8 @180c/c with alternare bars cranked at supports
Provided : 279.253 sqmm OK
Supports : 8 extra @ 360 W2 at supports
Longer span :
Reinforcement Details :
= 36.8 kN/m 2
Force on the wall F = (1/2 p H)
= 67.712 kN
Moment at base M = (1/2 x p x H) x (H/3)
= 73.00 kNm
Thickness of wall required T = M/(QB)
= 456.702 mm
Effective thickness d = 549 mm
= < 600 mm
Effective average thickness = 399 mm
Vertical reinforcement Ast = M/(σst j d)
546.0
3.45 m
3.15 m
0.6
0.5
0.6 3.3 m
p = 163.61884 6 x 0.461
1 +/-
3.3 3.3
Loads :
Load from slab = 4*4*5 = 80 kN
Weight of beam = 1.3225*2*4 = 10.58 kN
Self weight of column = 300/1000*300/1000*(3.45)*25 = 7.7625 kN
Total = 98.3425 kN
Providing 4no.s of - 16mm dia with 8dia ties @ 200 mm c/c
Carrying capacity of column P = Ac * σcc + Asc * σsc
= 90000 sqmm
Asc = 452.389 sqmm
Ac = 89547.611 sqmm P
= 13518.0960 kN
> 98.343 kN
5.07 FLOOR SLAB :
Assumed thickness of floor slab Th = 300 mm
As the floor slab is resting directly on ground provide min slab
Minimum % of reinforcement as per code = 720 sqmm
12 dia at @150mm mm c/c in b mm c/c in bothways = 628.319 mm2
5.06 COLUMN FOOTING : 1300 X 1300 mm
Thickness : 500 mm
Assumed cover to beam = 25 mm
Assumed dia of bar in beam = 12 mm
Loads :
Load on column = 98.3425 kN
Water load = 3.45*1.3*1.3*10 = 58.305 kN
Total = 98.3425+58.305 = 156.6475 kN
b) Steel
Grade : Fe-500
Permissible Stresses :
• Direct Tension : 130 N/mm2
• Tensile stress :
on liquid retaining face : 130 N/mm2
on face away from liquid
less than 225mm : 130 N/mm2
more than 225mm : 130 N/mm2
• Axial Compression : 140 N/mm2
2.LOADS
Density of Concrete γc : 25 kN/m3
Density of Soil γs : 18 kN/m3
Density of Water γw : 10 kN/m3
3.SOIL PARAMETERS
n 10/(130/9.34+10) *d
= 0.418
j = 0.861
Distribution factors
L/H = 2.5 B/H = 2.5
x/a line CD, y=0 line AB, y=b/2 line AB, y=0 line AB, y=b/2
Mx My Mx My Mx My Mx My
0 0 0.027 0 -0.074 0.000 0.027 0.000 -0.074
0.25 0.012 0.022 -0.013 -0.066 0.012 0.022 -0.013 -0.066
0.5 0.011 0.014 -0.011 -0.053 0.011 0.014 -0.011 -0.053
0.75 -0.021 -0.001 -0.005 -0.027 -0.021 -0.001 -0.005 -0.027
1 -0.108 -0.022 0 0 -0.108 -0.022 0.000 0.000
Joint A
Member AC AE
D.F 0.55 0.45
F.E.M (my) 0.044 0.066
Balance Moment -0.061 -0.05
Final Moment -0.017 0.016
Mid Span Moment (my) 0.027 0.027
Final Moment -0.034 -0.023
Maximum moment coefficients
AC AE
y=0 y=b/4 y=b/2
b/a x/a
Mx My Mx My Mx My
1 301 0 0.000 0.025 0.000 0.014 0.000 -0.082
b) Steel
Grade : Fe-500
Permissible Stresses :
• Direct Tension : 130 N/mm2
• Tensile stress :
on liquid retaining face : 130 N/mm2
on face away from liquid
less than 225mm : 130 N/mm2
more than 225mm : 130 N/mm2
• Axial Compression : 140 N/mm2
2.LOADS
Density of Concrete γc : 25 kN/m3
Density of Soil γs : 18 kN/m3
Density of Water γw : 10 kN/m3
3.SOIL PARAMETERS
n 10/(130/9.34+10) *d
= 0.418
j = 0.861
Distribution factors
L/H = 2.5 B/H = 2.5
x/a line CD, y=0 line AB, y=b/2 line AB, y=0 line AB, y=b/2
Mx My Mx My Mx My Mx My
0 0 0.027 0 -0.074 0.000 0.027 0.000 -0.074
0.25 0.012 0.022 -0.013 -0.066 0.012 0.022 -0.013 -0.066
0.5 0.011 0.014 -0.011 -0.053 0.011 0.014 -0.011 -0.053
0.75 -0.021 -0.001 -0.005 -0.027 -0.021 -0.001 -0.005 -0.027
1 -0.108 -0.022 0 0 -0.108 -0.022 0.000 0.000
Joint A
Member AC AE
D.F 0.49 0.51
F.E.M (my) 0.044 0.066
Balance Moment -0.054 -0.056
Final Moment -0.010 0.01
Mid Span Moment (my) 0.027 0.027
Final Moment -0.027 -0.029
Maximum moment coefficients
AC AE
Support -0.010 0.010
My
Mid Span -0.027 -0.029
Support -0.108 -0.108
Mx
Mid Span -0.013 -0.013
= 8 kN/m3
k x γ' = 3.12
Vertical Moment at base Mx*(γw+γ')*He3 Mv1 = -58.19 kN/m2
Vertical Moment at mid span Mx*(γw+γ')*He 3
Mv2 = -7.00 kN/m2
3
Thrust on long wall due to shear on short wall 0.3905 x wa2 T = 60.981 kN
Thickness of wall required D = M/(Q*B)
= 418 mm
Effective thickness d = 455 mm
= < 500 mm
Ast = M/(σst j d)
3
kN/m2
3
3
kN/m2
pull on long wall due to shear on short wall 0.3905 x wa2 T = 35.15 kN
Eccentricity of pull d-D/2 x = 205.00
mm
Net Horizontal moment at support Mh1 Mh1-x*T Mh1 = 4.51 kN/m2
Net Horizontal moment at support Mh1 Mh2-x*T Mh2 = -14.50 kN/m2
Thrust on short wall due to shear on long wall 0.3905 x wa2 T = 14.502 kN
pull on short wall due to shear on long wall 0.3905 x wa2 T = 60.980 kN
Eccentricity of pull d-D/2 x = 205 mm
Net Horizontal moment at support Mh1 Mh1-x*T Mh1 = -9.801 kN/m2
Net Horizontal moment at support Mh1 Mh2-x*T Mh2 = -20.331 kN/m2
Provide 750 mm slab projection in base slab 750 Size of base slab Ly = 5.10 m
Lx = 5.00 m
Design NUP = 129.46 kN/mm2
Say = 130.00 kN/mm2
Loads :
Cover slab Weight 3.60X3.50x6.25 = 85 kN
Beam Weight 0 = 0
kN Weight of Horizontal walls 2x3.60x5.10x25 = 918
kN Weight of Vertical walls 2x3.50x5.10x25 = 893
kN weight of base slab 5.1x5x450x25/1000 = 287
kN Water load 5.10x5.0x3.00x10 765
kN Total = 2947 kN
FORCE ANALYSIS;
Solve for Weight Normal and Tangential
Self wt 1.2DL+1.6LL Wind load
Therefore use, LC 75x38x15x2.0mm thck C-Channel space @ 0.6m. Provide sag rod @ every one-third betwee truss.
TRUSS COMPUTATION
L50x50x6mm
Input Parameters:
COMPRESSION AND TENSION MEMBERS COMPUTATION
Angle Type - Single.Angle Metal specs - A36 Welding Rod, Fexx - E70xx
Section - L51X51X6.4 Fy - 248 Mpa Weld Length, Lw - 75 mm
Section Properties, Ag - 609 mm² Max Compressive Force - 1.7 KN Weld thickness, t - 5 mm
Radius of gyration, ry - 15 Max Tension Force - 1.7 KN Eccentricity, x - 15.03 mm
Radius of gyration, rz - 10 Max Length, Lm - 1 m
b/t - 8 , b - 51 Effective length Factor, K - 1
CONDITION;
If KL/r ≤ Cc use, Fcr = [0.658^(Fy/Fe)]Fy
If KL/r > Cc use, Fcr = 0.877 Fe
* Where KL/r shall not be greater than to 200
CHECK ALLOWABLE TENSILE FORCE AISC Specs Sec. D
Ø = 0.90
Pu = Ø Fy Ag
Pu = 135.93 > 1.7 Pass
CHECK SECTION COMPACTNESS AISC Specs Table B4.1a
0.45 √(E/Fy) = 12.78
0.71 √(E/Fy) = 20.16
b/t = 8.0
b/t < 0.45 √(E/Fy), Therefore Nonslender Section
b/t < 0.71 √(E/Fy), Flexural-Torsional Buckling does not Apply
CHECK CRITICAL SLENDERNESS RATIO AISC Specs Sec. E
L/ra = 101.73, L/ra > 80; Therefore use KL/ra = 32+1.25L/r
Cc = 4.71 √(E/Fy) = 133.76
KL/r = 32+1.25L/r = 159.16
159.16 > 133.76, Therefore use Fcr = 0.877 Fe
Fe = π² E/(KL/r)² = 77.92
Fcr = 0.877 Fe = 68.34
COMPRESSIVE STRENGTH OF SECTION; AISC Specs Sec. E CHECK WELDING CONNECTION,
Pn = Fcr Ag = 41.62 Fillet Welds Fexx = 482 Mpa
ØPn = 0.90 Fcr Ag = 37.46 Fnw = 0.60 Fexx (1.0) = 289.2
ØPn = 37.46 > 1.7 Pass! Awe = 0.707 t 2Lw = 530.25
L = (L1 + L2) /2 = 75
U = 1 - (x/L) = 0.80
Rn = U Fnw Awe = 122.62
ØRn = 91.966 > 1.7 Pass!
Therefore use, L51X51X6.4mm Single Angle Bar, with 5 mm thck fillet welds at 75mm length
in all Connections.
Design of Pedestal:
Design Load :
Load transmitted by girt = 23.0 KN
Load due to GI Pipe 6” dia sch.60 = 54.0 KN
Load due to self weight (0.10 DL) = 5.4 KN
Total Design Load = 82.4 KN
Using Trial Section: 300mm x 300mm rectangular column reinf. by 6 -16mmØ RSB tied by 10mm Ø RSB spaced at 3
@ 0.05m, 3 @ 0.10m, rest @ 0.15m
Pg = 0.00502
Pu = Ø(0.80)Ag[0.85F’c{(1-Pg)} + Fy(Pg)]
Therefore the Section is suitable to carry the Pedestal Load and recommended to adopt the section.
N2 = A = 62,500mm2
N = 250mm
n = (250 – 72.39)/2
n = 88.805mm
- Therefore use 300mm x 300mm with Plate Area of 90,000mm2 and thickness of 15mm with
anchor bolt of 4-16mmØx 8”
DESIGN AND BUILD OF EXISTING SEWAGE
TREATMENT PLANT UPGRADING
Structural Analysis
220 Malvar St., ONP Compound Puerto Princesa City
DESIGNED BY:
ROCKY M. SIORES
Civil Engineer
PRC Reg. No. 0111516
PTR No. 1925073
TIN No. 408-875-292
Issued on: January 08, 2024
Issued at: Puerto Princesa City