63, 100 Kva, 200 Kva LT Distribution Box With Mccbs For Urban Areas
63, 100 Kva, 200 Kva LT Distribution Box With Mccbs For Urban Areas
TECHNICAL SPECIFICATION
FOR
63, 100 kVA, 200 kVA LT DISTRIBUTION BOX with MCCBs for Urban Areas
FOR
DISTRIBUTION SYSTEM
IN
MSEDCL
1
MMC:MSC/LTDB/01/2018
INDEX
Clause No. Contents
2
MMC:MSC/LTDB/01/2018
2. SERVICE CONDITIONS:
The equipment to be supplied against this specification shall be suitable for satisfactory
continuous operation under the following tropical conditions.
2.1 Maximum ambient temperature (Degree C) 50
2.2 Maximum temperature in shade (Degree C) 45
2.3 Minimum Temperature (Degree C) 3.5
2.4 Relative Humidity (percent) 10 to 95
2.5 Maximum Annual rain fall (mm) 1450
2.6 Maximum wind pressure (kg/sq.m) 150
2.7 Maximum altitude above mean sea level ( Meter) 1000
2.8 Isoceranic level (days per year) 50
2.9 Siesmic level (Horizontal Acceleration) 0.3 g
Moderately hot and humid tropical climate conductive to rust and fungus growth ….
3. SYSTEM DETAILS:
Distribution Boxes are meant for control and protection of Distribution Transformers with
relevant parameters as under:-
4. Applicable Standards:
a. IS :13947/1993 (Part 3) for Isolator (Switch Disconnector)
b. IS: 13947/1993 (Part2)(amended upto date) for L.T. MCCBs.
c. IS: 8623/1993 (amended upto date) for enclosure Box & for degree of protection
provided by enclosures of electrical equipments.
d. IS:4237/1982, IS:8623/1993 (amended upto date) – for general requirement of L.T.
switchgears.
e. IS 13703/1993 ( Part I & II amended upto date) for HRC Fuse Base and HRC Fuse
Link.
f. IS:5 /2007 - Colours of Ready Mixed paints and Enamels.
g. IS: 13871/1993 – Powder coatings – specifications
h. IS : 6005/1998 – Code of Practice for phosphating of iron and steel.
5. MANUFACTURE/CONSTRUCTION OF BOXES:
a. Distribution Boxes shall have Isolator (Switch Disconnector) and HRC fuse base
with links on incoming circuit and single pole MCCBs & Link Disconnector on
outgoing circuits with necessary interconnecting Bus Bars/ Links.
b. Standard General Arrangement of Isolators, HRC fuse base with links, MCCBs,
Link Disconnector, Neutral Links, Bus Bars, connecting links, Cable termination
arrangement etc inside the Box is shown in the enclosed drawing No. Dist /DB/05
for 63/100 KVA and Drawing No. Dist / DB/ 02 for 200 kVA distribution boxes.
6. INCOMING CIRCUIT –
6.1 Isolator (Switch Disconnector) -
Each distribution box shall have one triple pole Isolator (Switch Disconnector), conforming
to relevant IS and MSEDCL specification. The bidder shall indicate makes and types of
offered isolator in GTP. The successful bidder shall submit Type Test Report of the
Isolator as specified in Cl. No. 12.3 (II) for approval of CE(MMC) before commencement
of supply. The Switch disconnector to be provided in the Distribution Box will be as per
MSEDCL’s approval as given in the detailed purchase order.
The Isolator should be front operated triple pole type. The casing of Isolator shall
be of Non –tracking and heat resistant insulating material of Dough Moulding
Compound (DMC) of D3 Grade as per IS:13411/1992, no separate enclosure is required.
Isolator Base should withstand the breaking capacity of 80 kA. To extinguish the arc
immediately in isolators, in each phase archutes with minimum 12 strips shall be
provided.
4
MMC:MSC/LTDB/01/2018
The isolator should be front operated triple pole type. The isolator shall be robust in
construction and easy for operation. The handle of the isolator should be detachable easily
for security purpose while working on L.T. circuits.
The characteristics of Isolator shall be as follows:
The terminal connector strips of the isolator shall be projecting out of isolator of 80
mm (minimum) in length on cable connection side and 60mm (minimum) on HRC fuse
base side as shown in the drawings. In 63 /100/200 KVA distribution box, the cross
section of the strips on outside of the isolator shall be provided as below:
63/100 KVA - 25X5 mm.
200 KVA - 50X 6 mm
The material of isolator strips shall be EC grade tin-plated copper. The terminal strips shall
be continuous from the point of contact separation inside the Isolator.
6.2 HRC FUSE
HRC Fuse of suitable capacity shall be provided between outgoing terminal of Switch
Disconnector (Isolator) and incoming Busbar as shown in the Drg.No. Dist/DB/08 to
facilitate electrical breaking of the circuit. Each Distribution Box shall have 3 Nos. of HRC
Fuse Base with HRC Fuse Links (Blade type Contacts).
The bidder shall indicate in GTP, the make, type and capacity of HRC Fuse Base and Fuse
Links offered.
5
MMC:MSC/LTDB/01/2018
6
MMC:MSC/LTDB/01/2018
MCCB shall have quick make quick break mechanism. Making of MCCB shall only be
manual but breaking of MCCBs shall be electrical as well as manual.
The detailed specification for MCCBs shall be as under.
S.N Particulars Details
1. KVA rating 63 KVA 100 KVA 200 KVA
2. Rated current 150 A 200 A
3. Fixed overload release setting ( A) 60 A 90 A 120 A
4. No. of poles Single pole
Rated service short circuit breaking capacity
5. ( kA) which is equal to ultimate breaking 10 KA at 0.4 p.f . ( lag)
capacity as per IS 13947 /1993
The sequence of operation for this test shall be, O - t - CO - t - CO, and t = 3 min.).
The test shall be done at 250V at 0.4 p.f. (lag). Voltage rating phase to phase 433 V
and phase to earth 250V.
6. Power factor for short circuit (Max.) 0.4 lag
7. Utilization category A
8. Rated Insulation Voltage 660 V
The Busbar dropper and Terminal connection strip of Link Disconnector shall be placed
in contact terminal of MCCB as shown in the drawing.
The rated service short circuit breaking capacity as specified in Sr. No. 5 above table,
shall be based on the rated service short circuit test carried out at specified power factors.
The MCCB should be front operated single pole type. The casing of MCCB shall be
of Non –tracking and heat resistant insulating material of Dough Moulding
Compound (DMC) of D3 Grade as per IS:13411/1992, no separate enclosure is
required. Isolator Base should withstand the breaking capacity of 80 kA. To extinguish
the arc immediately in MCCBs, archutes with minimum 8 strips shall be provided.
While the above stipulation regarding the test power factor and the sequence of operation
shall be binding, the other procedure for making the short circuit test and circuit etc. shall
generally be in accordance with the Indian Standard applicable to the type of circuit
breakers under test.
7
MMC:MSC/LTDB/01/2018
For above time/current characteristic, the reference calibration temperature of the breaker
shall be 50°C. Duration, if any, upto 60°C. ambient temperature shall not exceed 10% of
the current setting indicated above.
9 ENCLOSURE:
9.1 The Box & Doors shall be made up of CRCA MS sheet of 2mm thickness.
9.2 The manufacturing process of Box shall be either Deep Drawn process or Fabrication.
9.3 In case of Deep drawn type distribution boxes, the rounding of corners and slope on
Top shall be as shown in the drawing. No joints in the body of the Box are permitted
in Deep Drawn Process.
9.4 In case of fabricated box sharp corners & one side slope will be acceptable. The
fabrication boxes, involving welding, shall not have more than two joints.
9.5 The welding process of both type of distribution boxes shall be done by MIG (Metal
Inert Gas) welding and workmanship/finishing should be good enough.
9.6 A. For Fabrication Box : The general overall clear dimensions of 63 / 100 KVA
Distribution Box shall be 1000 x 1010 x 325 (LXHXW)mm. The height of distribution
boxes on front side shall be 1010 mm and backside shall be 990 mm. (Drg No.
Dist/DB/01/A) The general clear dimensions of 200 kVA Distribution Box shall be 1305
x 1060 x 325 (LXHXW) mm. The height of distribution boxes on front side shall be
9
MMC:MSC/LTDB/01/2018
9.7 The Base and doors of enclosure shall be individually in one piece without any welding,
except for fixing of the accessories like hinges, clamps, mounting clamps, bolts etc.
A) 63/100 kVA boxes shall have one door as shown in the drawing fixed on right side of
the box with four hinges provided from inside of box.
B) 200 kVA boxes shall have two doors as shown in drawing fixed on right side & left
side of the box with four hinges on both sides shall be provided from inside of box. On
closing of doors, right door shall rest on the left door.
Base and doors shall have flange / collars as shown in drawing. Collar of Base and doors
shall overlap by 10mm. Rubber gasket of suitable size shall be provided in between base
and doors, such that it provides proper sealing between the door and base of box to avoid
penetration of dust & ingress of water. Degree of protection shall be IP- 33 as per IS-
8623/1993 ( amended up to date ). Rubber Gasket shall be fixed with suitable adhesive.
Four hinges on each side shall be provided from inside of the box to fix the doors. Hinges
shall be minimum 50 mm in length & made from 2mm thick sheet. Hinge stainless steel
pin diameter shall be 4mm. The hinges shall not be visible from outside.
9.8 The MCCBs, Link Disconnector, Isolator and HRC fuse base with link shall be housed
inside the enclosure. Isolator operating handle shall be accessible only after opening of the
doors.
9.9 Four set of Louvers (two sets on each side) of suitable size shall be provided as shown in
drawing. The louvers shall be provided such that heat dissipation is proper. The perforated
sheet of 20 SWG with 2.5 mm holes shall be welded from inside of the louvers.
9.10 Mounting of components inside the enclosure shall allow free air circulation keeping the
clearances as per drawings No. Dist/DB/02 & Dist/Db/05 attached with specification.
9.11 Locking Arrangement to the Box:
The locking arrangements to boxes shall be such that the door (s) shall be automatically
closed without applying external force. The door should be front operated with a
common handle provided outside the door. In addition to this, C&R panel door locks
shall be provided to the door at top & bottom. Key way shall be provided on the door for
operating the lock from out side. Key way shall be provided with cover. A nylon
washer shall be provided between the handle and door to avoid penetration of
water.
10
MMC:MSC/LTDB/01/2018
9.12 A suitable cable termination arrangement with support insulators shall be provided on
Isolators and Link Disconnectors. The bimetallic lugs of adequate size, as per enclosed
specification & drawing, shall be provided. Clearances, Creepages and convenience in
making connections shall be ensured.
9.13 The electric grade aluminum Neutral Busbar of 300 x 30 x 8 mm for 63/100 KVA box
and 525 x 40 x 15 mm for 200 KVA Box capable of carrying for full load current. Neutral
Busbar shall be isolated with respect to body. The bimetallic lugs of adequate size, as per
enclosed specification & drawing, shall be provided. Neutral Busbar shall be as shown in
the drawing attached with the specifications.
9.14 Two galvanized earthing Bolts of M12 x 50 mm size shall be welded from inside and
projecting outside of the box as shown in the drawing. There should be no powder coating
on the earthing bolts. Two Nuts with washers shall be provided on each bolt.
9.15 Three bottom plates of the size 125mm x 125mm fixed with four screws from inside shall
be provided for incoming and outgoing cables. Bottom plates shall be provided with
suitable holes and rubber glands for the cables. Rubber glands shall be made such that
internal diameter of glands provided for cables should be closed with the rubber film of
minimum 1mm thickness. Cable will go through the glands by cutting the film of the
glands. Bottom plates shall also be provided with cable clamps as shown in drawing.
9.16 Necessary fixing arrangement shall be provided at the back of the enclosure to ensure
proper fixing on double pole structure by means of suitable clamps at 4 places.
9.17 Danger Board as shown in drawing no. Dist/DB/14 attached with specifications shall be
riveted on the box as per IS:2551. Danger board marking by painting shall not be
accepted.
9.18 All the components inside the Box shall be mounted on CRCA MS strips of 2mm
thickness. The mounting strips shall be provided with required bends or ribs to give the
extra strength and shall be powder coated or zinc plated.
9.19 All joints of current carrying parts shall be bolted with 8.8 grade High Tensile MS Nuts &
Bolts, Corrugated/spring & Plain Washers. The nuts & bolts should be of hexagonal type.
All the nuts, bolts & washers should be properly zinc plated.
9.20 Each distribution box shall be supplied with proper packing in five ply - corrugated box.
9.21 Name plate having details such as Month & year of manufacturing, Name of
manufacturer/Trade mark, Sr. No, and rating of Distribution box, shall be riveted on the
Distribution box door. The name plate should be of stainless steel of thickness 1 mm.
Mahavitaran logo in Marathi Language shall be embossed on the door of the distribution
box. Marathi slogans as per attached Annexure – I shall be painted in glowing colour
(Red/ Yellow/ Bright Green/Orange). The letter size, font, height & length shall be
suitable to the size of distribution boxes such that slogan can be clearly readable from 30
feet distance. There are total 15 nos Marathi slogans, out of them one slogan has to be
painted per box. All slogans shall be covered equally on the ordered quantity. All above
shall be so placed to give box good look.
9.22 Incoming and outgoing circuit should be duly highlighted with paint by stencil printing.
9.23 Adequate slope on the top of box shall be provided to drain out rainwater from the top.
11
MMC:MSC/LTDB/01/2018
9.24 3 Nos. MCCBs and 3 Nos. HRC fuse links in spare should be invariably provided with
each box.
9.25 Good-quality plastic sticker leaflet should be pasted inside of distribution box door. The
matter of instruction leaflet is given along with this specification. All the instructions in
leaflet should be in Marathi language.
10 CABLE TERMINATION:
Adequate size of Bimetallic lugs shall be provided for 3½ core, LT XLPE cable on
incoming side and out going side for 63/100/200 KVA boxes as below :
Incoming side Outgoing Side
63 KVA 120 sq.mm 50/ 70 sq.mm
100 KVA 120 sq.mm 50/70 sq.mm
200 KVA 185 sq.mm 120 sq.mm
11 FINISHING OF DISTRIBUTION BOX:
The outer side and inside surface of the box shall be properly Pre-treated / Phosphated
in seven tank process as per IS: 6005 and shall be applied powder coating of minimum
40 micron thickness. The Colour shade of smoke gray for 63 kVA box and light gray for
100 and 200 KVA box as per IS: 5/2007 (Colours of Ready Mixed paints and Enamels) shall
be applied inside & outside surface of the box. Powder coating shall be suitable for outdoor
use, conforming IS: 13871/1993 – Powder coatings. The process facility shall be in-house to
ensure proper quality for outdoor application.
12
MMC:MSC/LTDB/01/2018
For temperature rise test, a distribution box with all assembly of MCCBs / Link
Disconnectors / Isolator / HRC fuse base with link shall be kept in an enclosure such that
the temperature outside the box shall be maintained at 50 ° C.
20% more current than transformer secondary capacity i.e. for 63 KVA Distribution
Transformers full load current 84A, 20 % more is 100 A shall be kept in incoming circuit
keeping outgoing circuits short, till the temperature stabilizes and maximum temperature
rise should be recorded.
ii) Time-Current Characteristics
The MCCB should be tested for time current characteristics at 1.05 & 1.2 times of overload
release setting current and should pass the requirement given in clause- 7.2.
12.3. TYPE TESTS :
I ON COMPLETE BOX:
a. Temperature rise test:- The temperature rise test should be carried out as per
IS: 8623 -1993
b. High voltage test shall be carried out as per IS:8623/ 1993 amended upto date.
c. Short Time Withstand Current Test on Distribution Box shall be carried out as per IS
8623 or latest version.
d. The Distribution Box should be subjected to Short Time Withstand Current Test for 4KA
for 2 seconds for 63/100 KVA Box and 8 KA for 2 second for 200 KVA box) all the
circuits independently. The test should be carried out after by- passing MCCBs.
e. Degree of protection for IP- 33 on complete box shall be carried out as per IS: 13947/1993
or the latest version thereof.
f. Time /current characteristic test on MCCBs shall be carried out as per clause 7.2 of this
specification as stated above.
II) ON ISOLATOR (SWITCH DISCONNECTOR):
All type tests on Isolator (Switch Disconnector) as per IS: 13947/1993 (Part III) amended
up to date shall be carried out.
III) ON HRC fuses base and HRC fuse links :
All type tests on HRC fuses and HRC fuse links IS 13703/1993 ( Part I & II amended upto
date) for HRC Fuse Base and HRC fuse link shall be carried out.
IV) ON MCCB:
All type tests on MCCB as per IS-13947 amended upto date shall be carried out.
V) ON Link Disconnector:
Following tests shall be carried out on link disconnector as per IS:
1. Short Circuit Withstand Strength
2. Temperature rise Limits
3. Mechanical Operations
13
MMC:MSC/LTDB/01/2018
15. INSPECTION:
All routine & acceptance tests and inspection of material shall be carried out at the place
of manufacturer. The manufacturer shall offer the Inspector (representing the purchaser) all
reasonable facilities, free of charge at the time of Inspection.
The representative of the Chief Engineer (Distribution) and the Executive Engineer
(INSPECTION WING) shall jointly inspect the first lot of each rating of box.
14
MMC:MSC/LTDB/01/2018
16 . REJECTION:
The purchaser may select one box at random from a lot of 100 Distribution Boxes of each
type or part thereof as may be supplied to stores from time to time. The Box so selected
must pass all the Type Tests mentioned above otherwise the whole lot of 100 boxes or part
thereof, from which the box is selected, will be rejected. For this purpose, lots will be
made, consisting of 100 boxes per lot of each rating, at stores after supply.
The testing under this clause will be done in any Laboratory of the MSEDCL’s choice
including MSEDCL’s own Laboratory. Notice of such tests will be given by the MSEDCL
to supplier. The supplier is at liberty to be present during the testing.
17. SCHEDULES:
The tenderer shall fill in the following schedules which form part of the tender
specification and offer. If the schedules are not submitted duly filled-in with the offer, the
offer shall be liable for rejection.
Schedule ‘A’ – Guaranteed Technical Particulars
Schedule `B' - Tenderer's Experience.
The tenderer shall submit the list of orders for similar type of equipments, executed or
under execution during the last three years, with full details in the schedule of Tenderer's
experience (Schedule `B') to enable the purchaser to evaluate the tender.
18. DRAWINGS ENCLOSED:
i) Dist/DB/02/A ii) Dist/DB/02/B
iii) Dist/DB/02 iv) Dist/DB/03
v) Dist/DB/01/A vi) Dist/DB/01/B
vii) Dist./DB/05 viii) Dist./DB/07
ix) Dist./DB/08 x) Dist./DB/09
xi) Dist./DB/12 xii) Dist./DB/13
xiii) MMC/DB/14 xiv) Annexure –I
xvi) MMC/DB/17-A & 17B xvii) MMC/DB/15
xviii) MMC/DB/16-A,16-B and 16-C
The successful bidder shall submit set of all above drawings of the distribution box and its
components shall be submitted in triplicate to CE (Distribution) office and get approved
before commencement of supply.
15
MMC:MSC/LTDB/01/2018
SCHEDULE - `A'
16
MMC:MSC/LTDB/01/2018
SCHEDULE - `B'
Tenderer shall furnish here a list of similar orders executed/under execution by him to whom a
reference may be made by Purchaser in case he considers such a reference necessary.
--------------------------------------------------------------------------------------------------------------
Sr. Name of Client Value Period of supply Name & Address
No. & Description of order and commissioning to whom reference may be made.
--------------------------------------------------------------------------------------------------------------
1 2 3 4 5
--------------------------------------------------------------------------------------------------------------
DESIGNATION ______________________________________
DATE _____________________________________________
17
MMC:MSC/LTDB/01/2018
1) SCOPE:
Bimetallic terminal lugs are for use in Distribution Boxes/Distribution Transformer and other
O&M application for Crimping Copper and Aluminum Cables and termination on surface
namely Aluminum/Brass/Copper Plated terminals without the use of Bimetallic washers.
2) STANDARD:
Bimetallic lug crimped joint should conform to all tests laid down in IS-8337 e.g. clause 4.1.1
(6.2) for initial resistance and clause 4.1.3 (6.4) for Electrical Load Cycle test for 1000 Cycles
and Tensile Test clause 4.2 (6.5). Type Test certificate to this effect giving numerical values
obtained must be provided.
3) SERVICE CONDITION:
The Lugs to be supplied against this specification shall be suitable for satisfactory continuous
operation under the following tropical conditions.
3.1 Maximum ambient temperature ( Degree C) 50
3.2 Maximum temperature in shade (Degree C) 45
3.3 Minimum Temperature (Degree C) 3.5
3.4 Relative Humidity ( percent) 10 to 95
3.5 Maximum Annual rain fall (mm) 1450
3.6 Maximum wind pressure ( kg/ sq.m) 150
3.7 Maximum altitude above mean sea level ( Meter) 1000
3.8 Isoceranic level ( days per year ) 50
3.9 Siesmic level ( Horizontal Acceleration ) 0.3 g
3.10 Moderately hot and humid tropical climate conductive to rust and fungus growth.
4) MATERIAL SPECIFICATION:
Bimetallic lug should be made for electrolytic grade aluminum. Each lug should be copper
coated by electrolytic process and rich layer of tin should be mounted through out the lug to
protect from Galvanic Corrosion. The lugs shall be such that the rich layer of tin should not
peel of during operation. Individual lot should be pre filled with conductive inhibition
compound and lug should be duly capped to prevent oozing of compound. The ductility of
material should be such that flow ability of material be adequate to flow in to the strand of the
conductor and withstand on crimping pressure of 8500 PSI. The cut cross section of the joints
shall be homogeneous.
5) GENERAL REQUIREMENTS:
The minimum dimensions of the bimetallic lug in respect of barrel thickness and holes
diameter should conform to enclosed Drawing No.DIST/DB/13.
6) TESTS:
i) Initial resistance test of bimetallic crimped joint as per IS 8337.
ii) Heating cycle test for 1000 cycles of crimped joint of bimetallic lugs as per IS 8337.
iii) Tensile strength test of the crimped joint of bimetallic lug as per IS: 8337.
iv) Dimensional test as per drawing/offer.
18
MMC:MSC/LTDB/01/2018
7 TEST CERTIFICATES:
At present the following makes and types of bimetallic lugs are accepted by the MSEDCL.
Usha Martin Industries, Ismail, Chetna , Klippon, SRI, Alcon, NES , Hames and HB
In case any other equivalent make of bimetallic lugs, if bidder offer, they should indicate
makes and types of bimetallic lugs in E-tendering GTP. The bidders should submit complete
test reports of the bimetallic lugs as per this specification, clause No. 6 to C.E. (Dist) for
approval before commencement of supply. The Tests on lugs should be done in any reputed
independent laboratory.
19
MMC:MSC/LTDB/01/2018
20
MMC:MSC/LTDB/01/2018
21
MMC:MSC/LTDB/01/2018
22
MMC:MSC/LTDB/01/2018
23
MMC:MSC/LTDB/01/2018
24
MMC:MSC/LTDB/01/2018
25
MMC:MSC/LTDB/01/2018
26
MMC:MSC/LTDB/01/2018
27
MMC:MSC/LTDB/01/2018
28
MMC:MSC/LTDB/01/2018
29
MMC:MSC/LTDB/01/2018
30
MMC:MSC/LTDB/01/2018
31
MMC:MSC/LTDB/01/2018
32
MMC:MSC/LTDB/01/2018
33
MMC:MSC/LTDB/01/2018
34
MMC:MSC/LTDB/01/2018
35
MMC:MSC/LTDB/01/2018
36
MMC:MSC/LTDB/01/2018
37
MMC:MSC/LTDB/01/2018
38
MMC:MSC/LTDB/01/2018
39
MMC:MSC/LTDB/01/2018
40
MMC:MSC/LTDB/01/2018
41
MMC:MSC/LTDB/01/2018
43