Module 6 MV Dry Type Power Transformer
Module 6 MV Dry Type Power Transformer
SUBSTATION COMMISSIONING
COURSE
MODULE SIX
COMMISSIONING
DRY-TYPE POWER
TRANSFORMERS
Written by:
Raymond Lee, Technical Trainer
Copyright ©2011
Page 1 of 56
SUBSTATION COMMISSIONING COURSE
TABLE OF CONTENT
Headings Page
Introduction.............................................................................................................4
Objectives.................................................................................................................4
1. North American Dry-type Transformer Standards.........................................5
1. North American Dry-type Transformer Standards.........................................5
1.1 Canadian Standards......................................................................................5
1.2 US Standards..................................................................................................6
2. Nameplate Data.................................................................................................7
2.1 Serial number.................................................................................................7
2.2 Winding Temperature Class.........................................................................8
2.3 Temperature rise............................................................................................8
2.4 kVA Rating.....................................................................................................9
2.5 Voltage Rating..............................................................................................10
2.6 Cooling Class................................................................................................11
2.7 Polarity Markings........................................................................................12
2.8 Winding Designations..................................................................................12
2.9 Terminal markings......................................................................................13
2.10 Vector Diagrams........................................................................................13
2.11 Angular displacement between voltages of windings for three-phase
transformers.......................................................................................................13
2.12 Percent Impedance (%Z)..........................................................................15
2.13 Basic Impulse Insulation Level.................................................................16
3. Safety Consideration.........................................................................................18
3.1 High Voltage Safety.....................................................................................18
3.2 Electrostatic Charge....................................................................................18
4. Electrical Testing...............................................................................................19
4.1 Insulation Resistance Test...........................................................................20
Page 2 of 56
SUBSTATION COMMISSIONING COURSE
Page 3 of 56
SUBSTATION COMMISSIONING COURSE
Introduction
This module will detail the requirements for performing electrical and mechanical
tests on the MV dry-type power transformers. The purpose of the tests, testing
requirements and procedures are presented. Future module will be written on the
liquid-immersed transformers.
This module will introduce the NETA acceptance testing procedures for
transformer comprising of mechanical and visual inspections, electrical testing and
test data analysis. General guidelines for acceptance testing will be presented.
When equipment specific instructions are required the equipment
manufacturers/manuals should be consulted.
Objectives
By the end of this module the participants will have the basic skills to perform
acceptance testing on dry-type transformers, conduct visual and mechanical
inspections, perform insulation resistance tests, polarizing index test, applied
voltage tests, winding resistance tests, ratio test, polarity test, power factor test,
capacitance and dissipation test and completing the inspection / test forms and
conducting an assessment of the test data.
Page 4 of 56
SUBSTATION COMMISSIONING COURSE
Power transformers are used to convert and/or isolate power from one voltage level
to other voltage level(s). Power transformers are classified as having a rating
greater that 501 kVA for three-phase transformer and larger than 168 kVA for
single-phase transformer as per NETA standards and design for step-down
operation.
CSA C9-02 is the predominant standard for the design requirements of dry-type
transformers and reference the IEEE C57.12.91 for the testing requirement that is
not specifically noted within the document and also reference IEEE C57.96 for the
loading guidelines.
When transformers are not made to Canadian standards, the manufacturer must
declare that the unit has the equivalent safety performance as one made to
Canadian standards.
Page 5 of 56
SUBSTATION COMMISSIONING COURSE
Dry type transformers shall be tested as per IEEE C57.12.91 as specified in CSA
C9-2002 for Dry Type Transformer.
1.2 US Standards
The ANSI/IEEE standards which contain information on design and testing
requirements include but are not limited to:
IEEE C57.12.00 Standard General Requirements for Liquid- Immerse
Distribution, Power and Regulating Transformers
IEEE C57.12.01 Standard General requirements for Dry-Type Distribution
and Power Transformers Including Those with Solid-
cast and/or Resin Encapsulated Windings
IEEE C57.12.90 Standard Test Code for Liquid-Immersed Distribution,
Power and Regulating Transformers
IEEE C57.12.91 Standard Test Code for Dry-Type Distribution and Power
Transformers
Page 6 of 56
SUBSTATION COMMISSIONING COURSE
2. Nameplate Data
Page 7 of 56
SUBSTATION COMMISSIONING COURSE
Transformer temperature rise limits shall not be exceeded under the following
conditions:
For transformers with primary taps, delivery rated kVA at rated output
voltage with the primary energized on the lowest tap,
For any tap delivery rated output kVA at a lagging power factor of 80% or
higher, with 105% output voltage,
Energized at 110% output voltage, at no-load,
Operating with approximately sinusoidal load current with a harmonic
content less the .05 per unit.
Metallic parts in contact or adjacent to the insulation shall not attain a temperature
in excess of the figures in column 1 of Table 1.
Page 8 of 56
SUBSTATION COMMISSIONING COURSE
Full voltage taps are full-capacity taps and provisioned with two 2.5% taps above
and below rated voltage at rated kVA. Exceptions are for low voltage transformers
and units where the purchaser has specified the tap ratings.
Page 9 of 56
SUBSTATION COMMISSIONING COURSE
Page 10 of 56
SUBSTATION COMMISSIONING COURSE
The first letter designates the cooling medium surrounding the winding:
A – for air
G – for gas other than air
The second letter designates the method of circulating the cooling medium through
the winding:
N – for natural convection
F – for forced circulation
The third letter designates the manner of removing the heat from the cooling
medium:
Ventilated type:
N – for natural circulation of outside air that is in contact with the windings
F – for forced circulation of outside air that is in contact with the windings
Enclosed type:
C – for natural convection of outside air that is not in contact with the winding
P – for forced circulation of outside air that is in not in contact with the
windings
GNC: Gas-filled unit cooled by natural convection of the gas within the
enclosure and by natural convection of ambient air outside the enclosure
AFN: Air-filled cooled by forced circulation of the air within the open-
ventilated enclosure and by natural convection of ambient air outside the
enclosure
GNP: gas-filled unit cooled by natural convection of the gas within the
enclosure and forced flow of ambient air over the outside of the enclosure
Page 11 of 56
SUBSTATION COMMISSIONING COURSE
ANC / ANP: Air-filled unit cooled by natural convection of the air within the
enclosure and by natural convection of ambient air outside the enclosure and
emergency operation at higher kVA cooled by natural convection of the air
within the enclosure and by forced flow of ambient air over the outside of the
enclosure
The relative lead polarities are indicated by identification marks on the primary
and secondary leads of like polarity or by other appropriate identification.
Page 12 of 56
SUBSTATION COMMISSIONING COURSE
The highest voltage winding are identified in phase sequence order by H1, H2, H3
and the other winding in order of voltage rating by X1, X2, X3 and Y1, Y2, Y3, etc.
The vector lines of the diagram represent induced voltages using the recognized
counter-clockwise direction of rotation for phase sequence. The vector
representing any phase voltage of a given winding is drawn parallel to the other
phase voltages of the same winding that it is associated with.
Page 13 of 56
SUBSTATION COMMISSIONING COURSE
Winding Diagram
The winding diagram shows the internal winding connections for the various tap
positions and external bushing connection. Winding diagrams are normally
incorporated into the vector diagram.
Page 14 of 56
SUBSTATION COMMISSIONING COURSE
Page 15 of 56
SUBSTATION COMMISSIONING COURSE
The impulse level is the crest value of the impulse voltage during a lightning strike
that the transformer is required to withstand without failure. The impulse level is a
momentary withstand rating. The BIL ratings are shown in Table 5
Page 16 of 56
SUBSTATION COMMISSIONING COURSE
Table 5: Insulation Voltage Class and Dielectric Tests for Dry-type Transformer*
Insulation Voltage Nominal Voltage Applied Potential BIL, full and Chopped-wave
Class, kV Test, kV chopped-wave, kV minimum time to
crest flashover, µs
1.2 1,200 and less 4 ----- -----
2.5 2,400 10 20 1.0
5.0 4,160/2,400 12 30 1.0
4,160
4,800
8.7 8,320Y/4,800 19 45 1.25
7,200
8,320
15.0 12,470/7,200 31 60 1.5
13,860Y/8,000
12,470
13,860
18.0 24,940 GrdY/14,400 34 95 1.6
27,600 GrdY/16,000
25.0 35,500 GrdY/19,900 40 125 2.0
24,940Y/14,400
24,940
27,600Y/16,000
27,600
34.5 34,500 50 150 2.25
34,500Y/19,900
46,000 GrdY/26,600
* Higher voltage rating is available when specified
Notes:
1) Applied potential test levels are for application to windings that do not have reduced neutral terminal insulation.
2) Equipment having a voltage rating between listed values shall be tested at the higher values.
3) Transformer terminals that may be subjected to transient overvoltages exceeding 80% of their BIL should be protected by surge
arresters.
Page 17 of 56
SUBSTATION COMMISSIONING COURSE
3. Safety Consideration
Refer to IEEE Standard 510 – 1983, Recommended Practice for Safety in High
Voltage & High Power Testing.
Page 18 of 56
SUBSTATION COMMISSIONING COURSE
4. Electrical Testing
Electrical test
Electrical tests are required before energizing the transformer. The required basic
acceptance tests are:
Insulation resistance test
Applied-voltage test
Ratio test.
Page 19 of 56
SUBSTATION COMMISSIONING COURSE
Page 20 of 56
SUBSTATION COMMISSIONING COURSE
Note:
Table 6 was sourced from IEEE C57-94-1982 Recommended Practice for
Installation, Operation and Maintenance of Dry-type General Purpose Distribution
and Power Transformer. Table 6 differs from NETA Table 100.5 figures for
transformer Insulation Resistance Acceptance Testing values. There is no industry
consensus for satisfactory values.
Other references noted a general rule of thumb for acceptable insulation values at
1MΩ per 1kV of nameplate rating plus 1MΩ.
Note:
Under no condition should the test be made while the transformer is under vacuum.
Note:
The significance of values of insulation resistance test requires some interpretation
depending on design, dryness and cleanliness of the insulation involved. It is
recommended that the insulation resistance values be measured during periodic
maintenance shutdown and trended. Large variation in the trended values should be
investigated for cause.
Note:
Insulation resistance may vary with applied voltage and any comparison should be
made with the same measurements at the same voltage and as close as possible to
the same equipment temperature and humidity as practically possible.
Page 21 of 56
SUBSTATION COMMISSIONING COURSE
1. Isolate the equipment, apply working grounds to all incoming and outgoing
cables and disconnect all incoming and outgoing cables from the transformer
bushing terminals connections. Disconnected cables should have sufficient
clearance from the switchgear terminals greater that the phase spacing
distance. Use nylon rope to hold cable away from incoming and outgoing
terminals as required.
3. Disconnect all lightning arresters, fan system, meter or low voltage control
systems that are connected to the transformer winding.
4. Short circuit all winding terminals of the same voltage level together.
Page 22 of 56
SUBSTATION COMMISSIONING COURSE
Field dielectric test are conducted at 75% of the factory voltage test levels of the
test values listed in Table 8. When field test are made on a periodic basis, it is
recommended that the test voltages be limited to 65% of factory test.
Note: If dc test equipment is used, the test voltage should not exceed the factory
rms test voltage. Test equipment should be of the full-wave bridge design
with ripple content should be less than 1%.4
3
IEEE Standard C57.12.91-2001
Test Code for Dry-type Distribution and Power Transformers
4
ANSI/IEEE C57.94-1982
Recommended Practice for Installation, Application, Operation and
Maintenance of Dry-type General Purpose Distribution and Power
Transformers
Page 23 of 56
SUBSTATION COMMISSIONING COURSE
Note: Voltage levels may have to be reduced such that no winding need be
tested above its specified level to meet the test requirements of another
winding.
3. The voltage should be started at one-quarter or less of the full value and be
brought up gradually in not more than 15 seconds. After being held for the
specified duration, it should be gradually reduced in not les than 5 seconds to
one-quarter of the maximum value and then turned off.
Caution:
It is important to recognize that the neutral terminal of a wye-connected
transformer that is designed for a grounded wye connection may have an insulation
level lower than that of the line terminal. The insulation level of the neutral end of
the winding may differ from the insulation level of the highest voltage neutral
terminal. In such case, the dielectric test on the neutral shall be determined by
lower insulation value of the neutral terminal or the neutral end of the winding.
Page 24 of 56
SUBSTATION COMMISSIONING COURSE
Notes:
1) A single voltage of 4160 represents a delta-connected 3-phase transformer for
connection to a 3-wire system or a single-phase transformer for connection to a 2-wire
ungrounded system. A voltage such as 4160 GrdY / 2400 represents a wye-connected 3-
phase transformer having an effectively grounded neutral for connection to a 4-wire
multigrounded system. It also represents a 2400 V single-phase transformer with an
effectively grounded neutral end in the 2400 V winding. I may be connected line-to-
ground or as part of a 3-phase bank on a 4160 V 4-wire multigrounded system. A voltage
such as 4160Y / 2400 represents a 3-phase transformer with a fully insulated neutral for
connection to a 416 V 4-wire system.
2) Power frequency dielectric withstand test levels are for application to windings that do
not have reduced neutral terminal insulation.
3) Equipment having a voltage rating between listed values shall be tested at the higher
level.
4) See “Caution” above for windings that are grounded Y.
Page 25 of 56
SUBSTATION COMMISSIONING COURSE
Page 26 of 56
SUBSTATION COMMISSIONING COURSE
1. Isolate the equipment, apply working grounds to all incoming and outgoing
cables and disconnect all incoming, outgoing cables from the transformer
bushing terminals connections. Disconnected cables should have sufficient
clearance from the switchgear terminals greater that the phase spacing
distance. Use nylon rope to hold cable away from incoming and outgoing
terminals as required.
4. Short-circuit all low voltage bushing terminals and the neutral bushing
terminal together.
6. Attain the test voltage level at a constant rate of rise, to achieve the test
voltage level at the end of 15 seconds.
11.Remove all shorting jumpers after all tests are completed. Reconnect neutral
connection.
Page 27 of 56
SUBSTATION COMMISSIONING COURSE
The Transformer Turns Ratio tester (TTR) is used to measure the turns ratio
between the windings.. Voltage is applied on the H marked leads and measured of
the X marked lead by the test set. Ratio measurements are conducted on all tap
positions and calculated by dividing the induced voltage reading into the applied
voltage value
When ratio tests are being made on three-phase transformers, the ratio is taken on
one phase at a time with a three-phase TTR until the ratio measurements of all
three phases are completed. Measured ratio variations should be within .5% of the
nameplate markings.
Some TTR can perform transformer ratio measurement and also assess if on-load
tap changer contacts are making satisfactorily during its transition from one tap
position to the next position.
Page 28 of 56
SUBSTATION COMMISSIONING COURSE
1. Isolate the equipment, apply working grounds to all incoming and outgoing
cables and disconnect all incoming and outgoing cables from the transformer
bushing terminals connections. Disconnected cables should have sufficient
clearance from the switchgear terminals greater that the phase spacing
distance. Use nylon rope to hold cable away from incoming and outgoing
terminals as required.
2. Connect the H designated three-phase test lead with the military style
connector at one end to the mating connection on the test set marked with an
H. Ensure that the connector’s index notch lines up properly.
4. Connect the H1, H2, H3 designated test lead to the corresponding H1, H2,
H3 transformer terminal / bushing. Connect the H0 test lead if H0
terminal/bushing is present.
Refer to Figure 3.
5. Connect the X1, X2, X3 designated test leads to the corresponding X1, X2,
X3 transformer terminals / bushings. Connect the X0 test lead if X0
terminal/bushing is present.
7. Confirm that the measured ratios is within .5% of the calculated ratios.
Note:
Transformers that have wye connections but do not have the neutral of the wye
brought out shall be tested for ratio with three-phase power supply. Any inequality
in the magnetizing characteristics of the three phases will then result in a shift of
the neutral and thereby cause unequal phase voltages. When such inequality is
found, the connection should be changed, either to a delta or to a wye connection,
and the line voltages measured. When these are found to be equal to each other and
the proper values (1.732 times the phase voltages when connected in wye), the
ratio is correct.
Page 29 of 56
SUBSTATION COMMISSIONING COURSE
Where:
Polarisation Index = R10 / R1 R10 = megohms insulation resistance
at 10 minutes
R1 = megohms insulation resistance
at 1 minute
The 10 minute resistance is divided by the 1 minute resistance to give the PI value.
The PI indicates the relative dryness and level of moisture ingress into the
insulation.
Readings at every minute intervals are recorded for graphing purposes. A falling
off of the insulation value near the testing time could indicate insulation problems.
Page 30 of 56
SUBSTATION COMMISSIONING COURSE
Note: The polarizing index tests should be combined with the insulation resistance
test by extending the required test time to 10 minutes. This will minimize
testing time when both tests are combine versus performing two separate
tests.
1. Isolate the equipment, apply working grounds to all incoming and outgoing
cables and disconnect all incoming and outgoing cables from the transformer
bushing terminals connections. Disconnected cables should have sufficient
clearance from the switchgear terminals greater that the phase spacing
distance. Use nylon rope to hold cable away from incoming and outgoing
terminals as required.
3. Disconnect all lightning arresters, fan system, meter or low voltage control
systems that are connected to the transformer winding.
4. Short circuit all winding terminals of the same voltage level together.
Page 31 of 56
SUBSTATION COMMISSIONING COURSE
If all readings are within 1% of each other then they are acceptable.
The purpose of the test is to test for gross differences between the windings and for
checking if there are open circuits in the connections. Measuring the resistance of
the windings assures that the connections are correct and the resistance
measurement indicates that there are no severe mismatches or open.
Operating Principles
A DC current is passed through the transformer winding and an internal standard
current shunt in the test set. After both DC voltage drops are measured they are
ratioed and the display is read as resistance on the front panel meter.
Measurement of the voltage drop across the winding uses the standard formula for
a voltage drop across an inductor, where:
With zero ripple voltage, then di/dt is zero and the term L di/dt becomes zero.
Page 32 of 56
SUBSTATION COMMISSIONING COURSE
Caution:
When a DC current is flowing in an inductive element, opening the circuit will
be generate high voltages during kickback from the collapsing magnetic field in
the coil. DO NOT open the circuit during testing
When terminating the test, wait until the “charged” indicator on the test set goes
off before removing any leads. If it takes 30 second for the winding to charged, it
will take a longer time for the winding to discharge.
When transferring leads from one winding to another, the same relative polarity
should be maintained with regard to the measuring leads and the transformer
terminals.
Limitations
The transformer resistance test has several limitations which should be recognized
when performing the test and interpreting test data:
The resistance of the transformer's winding can limit the effectiveness of the test in
detecting problems. The lower the resistance of a winding the more sensitive the
test is with respect to detecting high resistance problems. Windings with high DC
resistance will mask problems.
The detection of shorted turns is not possible in all situations. Often shorted turns
at rated AC voltage cannot be detected with the DC test. If the fault is a carbon
path through the turn to turn insulation it is a dead short at operating potentials.
However, at test potential, 30 V DC, the carbon path may be a high resistance
parallel path and have no influence on the measured resistance.
Page 33 of 56
SUBSTATION COMMISSIONING COURSE
1. Isolate the equipment, apply working grounds to all incoming and outgoing
cables and disconnect all incoming and outgoing cables from the transformer
bushing terminals connections. Disconnected cables should have sufficient
clearance from the switchgear terminals greater that the phase spacing
distance. Use nylon rope to hold cable away from incoming and outgoing
terminals as required.
2. Select the correct winding metal type (aluminum or copper) on the test set if
provided. Resistivity of copper and aluminum is different.
3. For delta or wye connected windings, connect +ve DC current source lead to
the H1 (or X1) terminal and the –ve DC current source lead to the H2 (or
X2) terminal.
4. Connect the +ve DC voltage sensing lead to the H1 (or X1) terminal closer
toward the winding and the –ve DC voltage sensing lead to the H2 (or X2)
terminal closer toward the winding.
6. Repeat step 3 and 4 for H2-H3 (or X2-X3) and H3-H1 (or X3-X1) while
maintaining the relative polarity of the test leads.
7. For Wye connected windings, connect +ve DC current source lead to the H1
(or X1) terminal and the –ve DC current source lead to the H0 (or X0)
terminal.
8. Connect the +ve DC voltage sensing lead to the H1 (or X1) terminal closer
toward the winding and the –ve DC voltage sensing lead to the H0 (or X0)
terminal closer toward the winding.
10. Repeat step 7 and for H2-H0 (or X2-X0) and H3-H0 (or X3-X0) while
maintaining the relative polarity of the test leads.
Page 34 of 56
SUBSTATION COMMISSIONING COURSE
Watts = E x IT x Cosine Ө
Types of transformers that are normally subjected to the power factor test are:
- Two winding transformers
- Three winding transformer
- Auto-transformers
- Instrument transformers
Other test names synonymous with the PF test are Dielectric loss angle, dissipation
factor test, tan delta or Doble test.
Page 35 of 56
SUBSTATION COMMISSIONING COURSE
The power factor test typically applies a test voltage less than the stress working
levels of the equipment. Refer to Table 6.
The required tests are noted in Table 7 and its connection is shown in Figure 6 and
Figure 7. The difference between the high-voltage winding tests and the low-
voltage winding tests are the placement of the test leads and the test voltage levels.
Test 3 and test 8 of Table 7 should generate the same value as they both measure
the same capacitance between the windings.
1. Isolate the equipment, apply working grounds to all incoming and outgoing
cables and disconnect all incoming and outgoing cables from the transformer
bushing terminals. Disconnected cables should have sufficient clearance
from the switchgear terminals greater that the phase spacing distance. Use
nylon rope to hold cable away from incoming and outgoing terminals as
required.
4. Short-circuit all low voltage bushing terminals and the neutral bushing
terminal together.
Page 38 of 56
SUBSTATION COMMISSIONING COURSE
While the transformer preparation is identical to the power factor test procedure,
there is no requiremnts to make connection changes once the initial test set
connections are made. High-voltage winding and low-voltage winding test set
connection changes are made through a selector switch provided on the test set
which effect the test set connections akin to Table 7.
Winding capacitance and dissipation factor test values are obtained by balancing a
null meter for each variable at every the measured variable selector switch
positions.
Page 39 of 56
SUBSTATION COMMISSIONING COURSE
1. Isolate the equipment, apply working grounds to all incoming and outgoing
cables and disconnect all incoming and outgoing cables from the transformer
bushing terminals. Disconnected cables should have sufficient clearance
from the switchgear terminals greater that the phase spacing distance. Use
nylon rope to hold cable away from incoming and outgoing terminals as
required.
4. Short-circuit all low voltage bushing terminals and the neutral bushing
terminal together.
6. Record the capacitance and dissipation factor values once the null meter is
balance for both phasing position. Record values for the five test-variable
selector switch position.
Page 40 of 56
SUBSTATION COMMISSIONING COURSE
1. Isolate the equipment, apply working grounds to all incoming and outgoing
cables and disconnect all incoming and outgoing cables from the transformer
bushing terminals. Disconnected cables should have sufficient clearance
from the switchgear terminals greater that the phase spacing distance. Use
nylon rope to hold cable away from incoming and outgoing terminals as
required.
5. Measure the voltages between the various terminals as shown in Table 8 for
the respective winding group.
Page 41 of 56
SUBSTATION COMMISSIONING COURSE
Connect: H1 to X1
Measure: H1-H2,
H2-X2,
H2,X3,
H3-X2,
H3-X3
Page 42 of 56
SUBSTATION COMMISSIONING COURSE
Connect: H1 to X1
Measure: H1-H3,
H2-X2,
H2-X3,
H3-X2,
H3-X3
Page 43 of 56
SUBSTATION COMMISSIONING COURSE
Note: Many of the listed tests in the NETA standard are optional while optionally
indicate tests may be required to be performed; as such, those notes have
been excluded in this document. Any personnel responsible for performing
acceptance testing should determine which specific tests are required for
each specific projects.
4. Verify that resilient mounts are free and that any shipping brackets / bolts have
been removed.
6. Verify that control and alarm settings on temperature indicators are as specified.
7. Verify that cooling fans operate and that fan motors have correct overcurrent
protection.
8. Inspect bolted electrical connections for high resistance using one or more
of the following methods:
a. Use of a low-resistance ohmmeter.
b. Verify tightness of accessible bolted electrical connections by calibrated
torque-wrench method in accordance with manufacturer’s published data or
Table 2 of module 2 or Table 100.12 of NETA ATS-2009.
c. Perform thermographic.
Page 44 of 56
SUBSTATION COMMISSIONING COURSE
Page 45 of 56
SUBSTATION COMMISSIONING COURSE
Page 46 of 56
SUBSTATION COMMISSIONING COURSE
Page 47 of 56
SUBSTATION COMMISSIONING COURSE
5. Turns-ratio test results shall not deviate more than one-half percent from
either the adjacent coils or the calculated ratio.
6. The typical excitation current test data pattern for a three-legged core
transformer is two similar current readings and one lower current reading.
8. Core insulation-resistance values shall not be less than one megohm at 500
volts dc.
9. AC dielectric withstand test voltage shall not exceed 75 percent of factory test
voltage for one minute duration. If no evidence of distress or insulation failure
is observed by the end of the total time of voltage application during the
dielectric withstand test, the test specimen is considered to have passed the test.
Page 48 of 56
SUBSTATION COMMISSIONING COURSE
Page 49 of 56
SUBSTATION COMMISSIONING COURSE
7. Test Forms
Page 50 of 56
SUBSTATION COMMISSIONING COURSE
CUSTOMER DATA
Name: EITCA Date (mm/dd/yy):
Address: 4234 – 93 STREET City, Province: EDMONTON ALTA
Location: INDOOR Address: 4234 – 93 STREET
Substation: TRAINING LAB Postal code: T6E 5P5
Panel ID: Phone: 780-462-5729
Equipment ID: Contact person: MR. R. MATTHEWS
Tested by:
EQUIPMENT NAMEPLATE DATA
Make: HV Winding rating: kV
Type: LV Winding rating: kV
Load Rating: kVA BIL Rating; HV / LV / kV
Impedance: %
Number of taps: Temperature rise: / ºC
Manufactured Date: Cooling Class:
HV Winding material Total weight:
LV Winding material Winding configuration: /
VISUAL / MECHANICAL INSPECTION
Physical condition: Primary winding connection: Bushing Integrity:
Cleanliness: Sec. winding connection: Winding condition:
Anchorage: Core temperature sensors: Fan /fan motor condition:
Ground bus connections: Core grounding strap: Temp. controller integrity:
Comments:
Page 51 of 56
SUBSTATION COMMISSIONING COURSE
WINDING RATIO TEST
T HV H1-H3 / X1-X0 H2-H1 / X2-X0 H3-H2 / X3-X0
A WINDING CALC MEAS DIFF EXCIT RATIO DIFF EXCIT RATIO DIFF EXCIT
P RATING RATIO RATIO % mA % mA % mA
1 V
2 V
3 V
4 V
5 V
As found tap conn / rating: As left tap conn. / rating:
Test Equipment: Calibration Date:
Serial number: Test Equipment ID:
Comments:
Page 52 of 56
SUBSTATION COMMISSIONING COURSE
POLARIZING INDEX TEST / INSULATION RESISTANCE TEST
H to L & Gnd L to H & Gnd
TIME RESITANCE TIME RESITANCE
15 sec GΩ 15 sec GΩ
30 sec GΩ 30 sec GΩ
45 sec GΩ 45 sec GΩ
1 min GΩ 1 min GΩ
1.5 min GΩ 1.5 min GΩ
2 min GΩ 2 min GΩ
2.5 min GΩ 2.5 min GΩ
3 min GΩ 3 min GΩ
3.5 min GΩ 3.5 min GΩ
4 min GΩ 4 min GΩ
5 min GΩ 5 min GΩ
6 min GΩ 6 min GΩ
7 min GΩ 7 min GΩ
8 min GΩ 8 min GΩ
9 min GΩ 9 min GΩ
10 min GΩ 10 min GΩ
Test Voltage: Vdc Test Voltage: Vdc
P.I. Ratio P.I. Ratio:
Temperature: °C Humidity: % %
Test Equipment: Calibration Date:
Serial Number: Test Equipment ID:
Comments:
Page 53 of 56
SUBSTATION COMMISSIONING COURSE
VECTOR DIAGRAM
Page 54 of 56
SUBSTATION COMMISSIONING COURSE
4. ANSI/IEEE C57.94-1982
Recommended Practice for Installation, Application, Operation and
Maintenance of Dry-type General Purpose Distribution and Power
Transformers
© 1982 by the Institute of Elelctrical and Electronics Engineers, Inc.
345 East 47th Street, New York, NY 10017-2394, USA
Page 55 of 56
SUBSTATION COMMISSIONING COURSE
Page 56 of 56