Data sheet 6AG1321-1BL00-2AA0
SIPLUS S7-300 SM 321 40-pole based on 6ES7321-1BL00-0AA0 with conformal
coating, -40…+70 °C, digital input isolated 32 DI, 24 V DC, 1x 40-pole
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 15 mA
Power loss
Power loss, typ. 6.5 W
Digital inputs
Number of digital inputs 32
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
— up to 40 °C, max. 32
— up to 60 °C, max. 16; 12 @ > 60 °C
Input voltage
● Type of input voltage DC
● Rated value (DC) 24 V
● for signal "0" -30 to +5 V
● for signal "1" 13 to 30V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable No
— at "0" to "1", min. 1.2 ms
— at "0" to "1", max. 4.8 ms
— at "1" to "0", min. 1.2 ms
— at "1" to "0", max. 4.8 ms
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA
Interrupts/diagnostics/status information
Alarms No
Diagnostics function No
6AG13211BL002AA0 Subject to change without notice
5/14/2024
Page 1/3 © Copyright Siemens
Alarms
● Diagnostic alarm No
● Hardware interrupt No
Diagnostics indication LED
● Status indicator digital input (green) Yes
Potential separation
Potential separation digital inputs
● between the channels No
● between the channels, in groups of 16
● between the channels and backplane bus Yes; Optocoupler
Isolation
Isolation tested with 500 V DC
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Railway application
● EN 50155 Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class
A/B, EN 50155:2007 (see SIOS entry 109755985)
Ambient conditions
Ambient temperature during operation
● min. -40 °C; = Tmin
● max. 70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated
temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use
applies
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax
- 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K)
at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068- 100 %; RH incl. condensation/frost (no commissioning under condensation
2-38, max. conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna);
60721-3-3 Class 3B3 on request
— to chemically active substances according to EN Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
60721-3-3 degree 3); *
— to mechanically active substances according to EN Yes; Class 3S4 incl. sand, dust, *
60721-3-3
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna);
60721-3-5 Class 5B3 on request
— to chemically active substances according to EN Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); *
60721-3-5
— to mechanically active substances according to EN Yes; Class 5S3 incl. sand, dust; *
60721-3-5
Use on ships/at sea
— to biologically active substances according to EN Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on
60721-3-6 request
— to chemically active substances according to EN Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
60721-3-6 degree 3); *
— to mechanically active substances according to EN Yes; Class 6S3 incl. sand, dust; *
60721-3-6
Usage in industrial process technology
— Against chemically active substances acc. to EN Yes; Class 3 (excluding trichlorethylene)
60654-4
— Environmental conditions for process, measuring Yes; Level GX group A/B (excluding trichlorethylene; harmful gas
and control systems acc. to ANSI/ISA-71.04 concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level
LC3 (salt spray) and level LB3 (oil)
6AG13211BL002AA0 Subject to change without notice
5/14/2024
Page 2/3 © Copyright Siemens
Remark
— Note regarding classification of environmental * The supplied plug covers must remain in place over the unused interfaces
conditions acc. to EN 60721, EN 60654-4 and during operation!
ANSI/ISA-71.04
connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 260 g
last modified: 5/13/2024
6AG13211BL002AA0 Subject to change without notice
5/14/2024
Page 3/3 © Copyright Siemens