Sinteso™

Fire control panel


FC2020

Compact, pre-assembled fire control panel with integrated, user-friendly


operating unit.
● Fire control panel for a maximum of 252 addresses
● Optional, integrated single-sector extinguishing
● Can be used as a standalone version or networked with up to 64 stations, such as
control panels and terminals
● Redundant network node with degraded mode operation according to EN 54
● Option to connect to Siemens 'Cloud for Buildings'
● Emergency power supply for emergency operating time of up to 72 hours
● Recognition, automatic read-in and immediate operational readiness of all FDnet
devices with auto-configuration
● Flexible configuration of complex applications and controls
● Configuration data can be uploaded/downloaded via remote access
● Time and situation-dependent changeover of detector parameter sets
● Extensions: Printer, key switches, LED indicators

009383_x_en_-- Smart Infrastructure


2023-07-06
Features and Functions
System

The diagrams have been simplified and do not include additional network hardware or
security components. Permissible applications are described in the A6V101039125
Network Security Guidelines document. Contact your Siemens IT security expert for more
information.

System overview

Fig. 1: System overview

2
Smart Infrastructure 009383_x_en_--
2023-07-06
1 Remote access with SintesoView
2 'Cloud for Buildings'
3 Customer network
4 Management platform
5 Remote access to management platform
6 Remote access with Sinteso Mobile
7 Router + firewall + virtual private network
8 Fire damper with actuator
Transmission of a fault signal

Transmission of an alarm signal

You will find a detailed labeled version of the diagram above along with further information in
the A6V10906627 planning guide, see chapter 'Product documentation'.

Networking of fire control panels

The diagrams have been simplified and do not include additional network hardware or
security components. Permissible applications are described in the A6V101039125
Network Security Guidelines document. Contact your Siemens IT security expert for more
information.

Up to 32 control panels and terminals can be linked to form one FCnet network. If the FCnet
network is connected to a danger management system via BACnet, up to 16 control panels
and terminals can be networked.

3
Smart Infrastructure 009383_x_en_--
2023-07-06
Fig. 2: Sub-net

1 Management platform
2 Remote access to management platform
Transmission of a fault signal

Transmission of an alarm signal

An optical FCnet/LAN network allows up to 14 sub-nets with up to 16 stations to be operated


in one network. A maximum of 64 stations is supported in total.

4
Smart Infrastructure 009383_x_en_--
2023-07-06
Fig. 3: Backbone

1 Remote access with SintesoView


2 'Cloud for Buildings'
3 Customer network
4 Management platform
5 Remote access to management platform
6 Remote access with Sinteso Mobile
7 Router + firewall + virtual private network
Transmission of a fault signal

Transmission of an alarm signal

You will find a detailed labeled version of the diagram above along with further information in
the A6V10906627 planning guide, see chapter 'Product documentation'.

5
Smart Infrastructure 009383_x_en_--
2023-07-06
Control panels

General features and functions


● Fast Ethernet interface for a heterogeneous network
● Processes the signals of the Sinteso detector series FD20
● Floor repeater displays, terminals and alarm devices on the FDnet detector line with
power supply via FDnet
● Interface to Siemens danger management system
● Slots for RS232 and RS485 serial interfaces
● All detector lines are monitored for ground faults
● Integrated degraded mode function
● Freely configurable, time-dependent controls with optional weekly, monthly, and yearly
switching programs
● Time and situation-dependent changeover of detector parameter sets
● Controls for synchronous activation of sounder bases/sounders (acoustic, optical,
language)
● The control panel and the fire detection system are custom-configured using the
'SintesoWorks' software
● Firmware for all processor-controlled control panel components can be updated
● Customer texts can be adapted directly on the operating unit of the control panel or with
the 'SintesoWorks' software
● Up to 13000 events can be called up from the event memory and filtered based on
various criteria
● Automatic summer/normal time changeover

Control panel-specific features

From MP8, the fire control panels can be ordered with a periphery board with a 0.5 A or
1.5 A output current per FDnet line.
To convert existing fire control panels, the periphery board with 1.5 A per FDnet line can be
ordered separately.

You will find information on the integrated extinguishing system and the individual
extinguishing components that are available in a separate data sheet with the document ID
'A6V10880701'.

FC2020-AZ Housing (Standard)


Detector line (FDnet)
● 252 addresses
● 2 loops/4 stubs
Properties
● Operating unit
● 70 W power supply
● Max. battery capacity 12 Ah
Options of the operating unit
● Event printer FTO2001-A1
● Key switch (Kaba) FTO2005-C1
● Key switch (nordic) FTO2006-B1

6
Smart Infrastructure 009383_x_en_--
2023-07-06
FC2020-EZ Housing (Standard)
Detector line (FDnet)
● 252 addresses
● 2 loops/4 stubs
Properties
● Operating unit (+LED indicator)
● 70 W power supply
● Max. battery capacity 12 Ah
Options of the operating unit
● Key switch (Kaba) FTO2005-C1
● Key switch (nordic) FTO2006-B1

FC2020-AA Housing (Comfort)


Detector line (FDnet)
● 252 addresses
● 2 loops / 4 stubs
Properties
● Operating unit
● Operating add-on (empty)
● 150 W power supply
● Max. battery capacity 25 Ah
● 1 flooding zone (optional)
Options of the operating unit
● Event printer FTO2001-A1
● Key switch (Kaba) FTO2005-C1
● Key switch (nordic) FTO2006-B1
● Operating add-on (2xLED indicator) FCM2038-A2
● Operating add-on (4xLED indicator) FCM2036-A2
● Exting. terminal (1 sector) XCM2002-A2

FC2020-AE Housing (Comfort)


Detector line (FDnet)
● 252 addresses
● 2 loops/4 stubs
Properties
● Operating unit
● Operating add-on (2xLED indicator)
● 150 W power supply
● Max. battery capacity 25 Ah
Options of the operating unit
● Event printer FTO2001-A1
● Key switch (Kaba) FTO2005-C1
● Key switch (nordic) FTO2006-B1

7
Smart Infrastructure 009383_x_en_--
2023-07-06
Extensions

You will find information on the integrated extinguishing system and the individual
extinguishing components that are available in a separate data sheet with the document ID
'A6V10880701'.

FCM2036-A2 Operating add-on (4xLED indicator)


● Optional operating add-ons with 96 indicator groups and two LEDs each:
1x red/green LED and 1x yellow LED

FCM2038-A2 Operating add-on (2xLED indicator)


● Optional operating add-ons with 48 indicator groups and two LEDs each:
1x red/green LED and 1x yellow LED

FH2002-A1 Housing (Standard)


● Empty housing for free use
● 443 x 404 x 188 mm
● E.g., for extra batteries, operating add-ons, or event printers
● Space for the following battery configuration:
– 2x FA2004-A1 (12 Ah)

FH2003-A1 Housing (Comfort)


● Empty housing for free use
● 443 x 802 x 188 mm
● E.g., for extra batteries, operating add-ons, or event printers
● Space for the following battery configurations:
– 2x FA2005-A1 (17 Ah) or
– 2x BAT12-25 (25 Ah)
● The mounting kit for the batteries FHA2061-A1 must be ordered separately.

8
Smart Infrastructure 009383_x_en_--
2023-07-06
FH2004-A1 Housing (Large Extension)
● Empty housing for free use
● 443 x 404 x 288 mm
● E.g., for extra batteries, operating add-ons, or event printer
● Space for the following battery configurations:
– 2x FA2007-A1 (45 Ah) or
– 2x FA2008-A1 (65 Ah)
● The mounting kit for the batteries FHA2061-A1 must be ordered separately.

FH2005-A1 Housing (Large)


● Empty housing for free use
● 443 x 802 x 288 mm
● E.g., for extra batteries, operating add-ons, or event printers
● Space for the following battery configurations:
– 2x BAT12-25 (25 Ah) or
– 2x FA2007-A1 (45 Ah) or
– 2x FA2008-A1 (65 Ah)
● The mounting kit for the batteries FHA2061-A1 must be ordered separately.

FH2007-A1 Housing (Standard + plan compartment)


● Empty housing for A4 documents
● 443 x 404 x 188 mm
● Plan compartment depth 150 mm

FTO2001-A1 Event printer


● Thermal printer for installation in operating units or operating add-ons
● Can be controlled via the RS232 module FCA2001-A1 (order separately)
● Logs all important events, such as alarms, faults, isolations, and test functions

DL3750+ Matrix printer (external)


● External matrix printer recommended by Siemens
● Supports monitoring for printing faults
● Can be controlled via the RS232 module FCA2001-A1 (order separately)
● Can be controlled via Ethernet via the print server PS104 from SEH

9
Smart Infrastructure 009383_x_en_--
2023-07-06
Use
For smaller-scale applications, e.g., workshops or hotels.
Also suitable for more comprehensive systems thanks to flexible networking options.

10
Smart Infrastructure 009383_x_en_--
2023-07-06
Design
Function elements

Operating unit
The following elements are available on the operating unit:
● CPU module and electronics
● Ethernet connection
● Slots for RS232 and RS485 modules and network modules (SAFEDLINK)
● Space for 'Kaba' or 'nordic' key switch
● Space for event printer (depending on version)
● Peripheral data bus connection for optional LED modules

Periphery board

From MP8, the fire control panels can be ordered with a periphery board with a 0.5 A or
1.5 A output current per FDnet line.
To convert existing fire control panels, the periphery board with 1.5 A per FDnet line can be
ordered separately.

The following elements are available on the periphery board:


● Connection terminals for:
– FDnet lines
– Remote transmission (alarm, fault)
– Horn output
– Configurable control inputs and outputs
– Monitored alarm and fault output
– Power supply and emergency supply
● 1x slot for loop extension (FDnet)

70 W or 150 W power supply, emergency power supply


The power supply feeds the hardware and charges the batteries.
In the event of a power cut, the batteries provide emergency current.

Housing
An FHA2007-A1 pivoting mounting plate can be fitted for the following elements above the
periphery board on the rear housing panel:
● 1x fire brigade periphery module (for Germany)
● 1x sounder module (as an alternative to mounting on U-rail TS35)
● 1x Connect X200 Gateway

Configuration
The following software allows the system to be customized:
● SintesoWorks
Operation
Each control unit has an integrated operating unit. The control panel can also be operated
via a separate FT2040 or FT2080 (Touch) fire terminal.
You will find details and more information in the product data sheet 009386 or
A6V10378271.

11
Smart Infrastructure 009383_x_en_--
2023-07-06
Setup

FC2020 inside housing (Standard)

Fig. 4: FC2020 Standard

Position Designation Type Comment


Basic equipment
1 Housing (Standard) FHA2002-A1 Items 1-5: Basic equipment for each
2 Periphery board (2 loops) FCI2002-A1 FC2020‑xx in housing (Standard).
The periphery board (2 loops, P) can be
Periphery board (2 loops, P) FCI2023-A1
ordered separately to convert the station to
3 Power supply (70 W) FP2015-A1 the 1.5 A FDnet line.
4 Mains terminals on TS35 DIN rail - Space for socket, relay modules, etc.
5 Operating unit FCM20xx-xx Operating unit with CPU
6 Space for batteries - 2x 12 V, 12 Ah
Extensions
7 Relay module Z3B171 Relay for fire controls
8 Event printer FTO2001-A1 For logging events
9 Key switch (Kaba) FTO2005-C1 For operating access authorization
Key switch (nordic) FTO2006-B1
10 Mounting plate FHA2007-A1 e.g., for fire brigade periphery module
or Connect X200 Gateway
11 Loop extension (FDnet) FCI2003-A1 For loop extension of the periphery board
(2 loops) FCI2002-A1 from two to four loops,
number of addresses remains the same
Loop extension (FDnet/C-NET, P) FCI2025-A1 For loop extension of the periphery board
(2 loops, P) FCI2023-A1 from two to four
loops, number of addresses remains the
same.
12 RS485 module (isolated) FCA2002-A1 For peripheral devices with RS485 interface

12
Smart Infrastructure 009383_x_en_--
2023-07-06
Position Designation Type Comment
13 RS232 module (isolated) FCA2001-A1 For devices with an RS232 interface
14 Network module (SAFEDLINK) FN2001-A1 For networking several stations
15 Connect X200 Gateway CXG3.X200 For connecting an FS20 station to Cloud for
Buildings
The mounting plate FHA2007-A1 and the
accessory set + ACDC (X200) FCA2056-A1
must be ordered separately.
16 Sounder module FCA2005-A1 For splitting one conventional sounder into
four
17 Battery (12 V, 12 Ah, VdS) FA2004-A1 For the emergency power supply
18 Fire brigade periphery module FCI2001-D1 For Germany (FBF, FSD, ÜE, FSE, ÖA, KL)
19 19" mounting kit FHA2016-A1 For installation in 19" third-party housing
20 FM blind 1HE FHA2017-A1 For recessed mounting of housing
21 License key Sx FCA20xx For special functions
22 Cable kit (communication) FCA2014-A1 For flexible connections running to the
modules on the operating unit
Repeater (SAFEDLINK) FN2002-A1 Not in overview, as not an installation part.
For extending the system bus FCnet from
1000 m to 2000 m between two stations. Max.
1x repeater (SAFEDLINK) between two
stations.

13
Smart Infrastructure 009383_x_en_--
2023-07-06
FC2020 inside housing (Comfort)

Fig. 5: FC2020 Comfort

Position Designation Type Comment


Basic equipment
1 Housing (Comfort) FHA2003-A1 Items 1-5: Basic equipment for each
2 Periphery board (2 loops) FCI2002-A1 FC2020‑xx in housing (Comfort).
The periphery board (2 loops, P) can be
Periphery board (2 loops, P) FCI2023-A1
ordered separately to convert the station to
3 Power supply (SV 24 V-150 W) V24230-Z6- the 1.5 A FDnet line.
A5
4 Mains terminals on TS35 DIN rail - Space for socket, relay modules, etc.
5 Operating unit FCM20xx-xx Operating unit with CPU
6 Space for batteries - 2x 12 V, 25 Ah
Extensions
7 Relay module Z3B171 Relay for fire controls
8 Event printer FTO2001-A1 For logging events
9 Key switch (Kaba) FTO2005-C1 For operating access authorization
Key switch (nordic) FTO2006-B1
10 Mounting plate FHA2007-A1 E.g., for fire brigade periphery module
or Connect X200 Gateway

14
Smart Infrastructure 009383_x_en_--
2023-07-06
Position Designation Type Comment
11 Loop extension (FDnet) FCI2003-A1 For loop extension of the periphery board
(2 loops) FCI2002-A1 from two to four loops,
number of addresses remains the same
Loop extension (FDnet/C‑NET, P) FCI2025-A1 For loop extension of the periphery board
(2 loops, P) FCI2023-A1 from two to four
loops, number of addresses remains the
same.
12 RS485 module (isolated) FCA2002-A1 For peripheral devices with RS485 interface
13 RS232 module (isolated) FCA2001-A1 For devices with an RS232 interface
14 Network module (SAFEDLINK) FN2001-A1 For networking several stations
15 Connect X200 Gateway and CXG3.X200 For connecting an FS20 station to Cloud for
mounting plate (X200) Buildings
FHA2063‑A1 The mounting plate FHA2007‑A1 and the
accessory set + ACDC (X200) FCA2056‑A1 or
the mounting plate (X200) FHA2063‑A1 and
the accessory set + ACDC (X200)
FCA2056‑A1 must be ordered separately.
16 Sounder module FCA2005-A1 For splitting one conventional sounder into
four
17 Battery (12 V, 25 Ah, VdS) BAT12-25 For the emergency power supply
18 Fire brigade periphery module FCI2001-D1 For Germany (FBF, FSD, ÜE, FSE, ÖA, KL)
19 19" mounting kit FHA2016-A1 For installation in 19" third-party housing
20 FM blind 2HE FHA2015-A1 For recessed mounting of housing
21 License key Sx FCA2xx For special functions
22 Cable kit (communication) FCA2014-A1 For flexible connections running to the
modules on the operating unit
23 Power supply kit (150 W, B) FP2005-A1 For extra power supply
Repeater (SAFEDLINK) FN2002-A1 Not in overview, as not an installation part.
For extending the system bus FCnet from
1000 m to 2000 m between two stations. Max.
1x repeater (SAFEDLINK) between two
stations.

15
Smart Infrastructure 009383_x_en_--
2023-07-06
Type Overview

Housing (Standard) Housing (Comfort)

Type FC2020-AZ FC2020-EZ FC2020-AA FC2020-AE


Number of FDnet 252
addresses
Number of lines:
Loops 2 (4)
(with loop
extension) or
Stubs 4 (8)
(with loop
extension)
Power supply 70 W 150 W
Battery size 12 Ah 25 Ah
Indicator groups - 24 - 48
with one red/
green and one
yellow LED each

16
Smart Infrastructure 009383_x_en_--
2023-07-06
Details for ordering

Control panels

Type Designation Weight Order number


FC2020-AZ Fire control panel (2-loop) 8.537 kg A5Q00015550
FC2020-AZ Fire control panel (2 loops, P) 8.600 kg S54400-C33-A1
FC2020-EZ Fire control panel (2-loop) 8.657 kg A5Q00016827
FC2020-EZ Fire control panel (2 loops, P) - S54400-C33-A3
FC2020-AA Fire control panel (2-loop) 14.869 kg A5Q00016829
FC2020-AA Fire control panel (2 loops, P) 14.928 kg S54400-C33-A6
FC2020-AE Fire control panel (2-loop) 15.124 kg A5Q00016851
FC2020-AE Fire control panel (2 loops, P) - S54400-C33-A7

Extensions

You will find information on the integrated extinguishing system and the individual
extinguishing components that are available in a separate data sheet with the document ID
'A6V10880701'.

Type Designation Weight Order number


FCA2001-A1 RS232 module (isolated) 0.033 kg A5Q00005327
FCA2002-A1 RS485 module (isolated) 0.027 kg A5Q00009923
FCA2005-A1 Sounder module 0.100 kg A5Q00014866
FCA2014-A1 Cable kit (communication) 0.126 kg A5Q00023027
FCI2001-D1 Fire brigade periphery module 0.207 kg A5Q00013100
FCI2003-A1 Loop extension (FDnet) 0.030 kg A5Q00010136
FCI2023-A1 Periphery board (2-Loop, P) 0.119 kg S54400-A183-A1
FCI2025-A1 Loop extension (FDnet/C-NET, P) 0.030 kg S54400-A185-A1
FCM2036-A2 Operating add-on (4xLED 3.905 kg S54400-B147-A1
indicator)
FCM2038-A2 Operating add-on (2xLED 2.516 kg S54400-B146-A1
indicator)
FH2002-A1 Housing (Standard) 7.193 kg A5Q00018931
FH2003-A1 Housing (Comfort) 11.051 kg A5Q00009906
FH2004-A1 Housing (Large Extension) 11.367 kg A5Q00018778
FH2005-A1 Housing (Large) 17.900 kg A5Q00019543
FH2007-A1 Housing (Standard + plan 9.430 kg A5Q00022369
compartment)
FHA2007-A1 Mounting plate 0.800 kg A5Q00010151
FHA2015-A1 FM blind 2HE 5.050 kg A5Q00024621
FHA2016-A1 19" mounting kit 3.000 kg A5Q00020179
FHA2017-A1 FM blind 1HE 3.020 kg A5Q00024719
FN2001-A1 Network module (SAFEDLINK) 0.022 kg A5Q00012851
FN2002-A1 Repeater (SAFEDLINK) 0.105 kg S24236-B2502-A1
FN2006-A1 Fiber network module (SM) 0.792 kg S54400-A109-A1
FN2007-A1 Fiber network module (MM) 0.792 kg S54400-A110-A1
FTO2001-A1 Event printer 0.141 kg A5Q00010126
- Spare printer reels (10 reels) 0.090 kg A5Q00017619

17
Smart Infrastructure 009383_x_en_--
2023-07-06
Type Designation Weight Order number
FTO2005-C1 Key switch (Kaba) 0.083 kg A5Q00010113
FTO2006-B1 Key switch (nordic) 0.046 kg A5Q00010129
Z3B171 Relay module 250 V AC / 10 A 0.042 kg 4843830001
(1 relay)

Auxiliary power supply

Type Designation Weight Order number


FP2004-A1 Power supply kit (150 W, A) for 1.286 kg A5Q00020825
EN-compliant installation in empty
housing
FP2005-A1 Power supply kit (150 W, B) for 1.181 kg A5Q00018779
extension
FP2015-A1 Power supply (70 W) for EN- 1.300 kg S54400-B121-A1
compliant installation in empty
housing

Network (backbone)

Type Designation Weight Order number


FCA2031-A1 Connection module (MoNet) 0.081 kg S54400-A153-A1
incl. cable
FHA2029-A1 Mounting kit (switch) 1.261 kg S54400-B79-A1
FN2012-A1 Ethernet switch (modular) 0.600 kg S54400-B152-A1
VN2002-A1 Ethernet module (MM) 0.026 kg S54400-A43-A1
VN2003-A1 Ethernet module (SM) 0.026 kg S54400-A44-A1

Cloud Gateway

Type Designation Weight Order number


CXG3.X200 Connect X200 Gateway 0.300 kg S55842-Z131-A100
FHA2063-A1 Mounting plate (X200) 0.269 kg S54400-B116-A1
FCA2056-A1 Accessory kit + ACDC (X200) 0.200 kg S54400-S115-A1

Batteries

Type Designation Weight Order number


FA2004-A1 Battery (12 V, 12 Ah, VdS) 3.750 kg A5Q00019354
FA2005-A1 Battery (12 V, 17 Ah, VdS) 5.700 kg A5Q00019677
BAT12-25 Battery (12 V, 25 Ah, VdS) 7.8 kg S54302-Z102-A1
FA2007-A1 Battery (12 V, 45 Ah, VdS) 14.500 kg A5Q00022897
FA2008-A1 Battery (12 V, 65 Ah, VdS) 21.300 kg A5Q00019357
FHA2061-A1 Mounting kit for batteries ‒ S54400-B91-A1
FHA2062-A1 Cable tie for batteries ‒ S54400-B92-A1

License keys

Type Designation Weight Order number


FCA2033-A1 License key (S1) 0.010 kg S54400-P154-A1
FCA2034-A1 License key (S2) 0.010 kg S54400-P155-A1
FCA2035-A1 License key (S3) 0.010 kg S54400-P156-A1

18
Smart Infrastructure 009383_x_en_--
2023-07-06
Type Designation Weight Order number
FCA2036-A1 License key (S4) 0.010 kg S54400-P157-A1

External printer

Type Designation Weight Order number


DL3750+ Matrix printer (external) 7.300 kg A5Q00023962
- Color ribbon for matrix printer 0.078 kg A5Q00023963
DL3750+

19
Smart Infrastructure 009383_x_en_--
2023-07-06
Product documentation

Title Document ID
System documentation
System description 008836
Product data 008837
Planning 008843
Mounting/Installation 008851
System data sheet
FS20 – Fire detection system 008955
Data sheets
FC2020 - fire control panel 009383
FC2030 - fire control panel for modernization A6V10087532
FC2040 - fire control panel 009384
FC2060 - fire control panel (modular) A6V10087844
FC2080 - fire control panel (19", modular) A6V10275515
FT2040 - fire terminal 009386
FT2080 - fire terminal (Touch) A6V10378271
Fire detection system with integrated single A6V10880701
or multi-sector extinguishing
Network Security Guidelines A6V101039125
Planning overview A6V10906627

Related documents such as the environmental declarations, CE declarations, etc., can be


downloaded from the following Internet address:
www.siemens.com/bt/download

Guarantee

The application-specific technical data is guaranteed only in combination with the Siemens
products listed in the 'Device combinations' section. If third-party products are used, any
guarantee provided by Siemens will be invalidated.

20
Smart Infrastructure 009383_x_en_--
2023-07-06
Technical data

Fire control panel (2 loops)/(2 loops, P) FC2020 in housing (Standard)


Supply Mains voltage AC 97…127 V / AC 196…253 V
Power supply 70 W
Operating voltage DC 20.5…28.6 V
Operating current Max. 2.5 A
Battery capacity 2x 12 V, max. 12 Ah
Battery monitoring Yes
Network monitoring Yes
Inputs / outputs Connectable detector series Sinteso (FDnet)
Number of addresses Max. 252
Number of integrated line cards 1
Number of lines:
● Loops (with loop extension) or 2 (4)
● Stubs 4 (8)
Integrated inputs/outputs:
● Alarm RT relay output 1
● Fault RT relay output 1
● Monitored alarm outputs 1
● Monitored fault outputs 1
● Monitored horn outputs 1
● Freely configurable inputs/outputs 8
Interfaces Operating unit Integrated
Slots for serial interfaces RS232, 2
RS485
Slots for network modules 2
Slot for loop extension 1
Mounting space for cable kit 1
(communication)
Sounder module Max. 1
Ethernet port RJ45 1
Ambient conditions Operating temperature -8…+42 °C
Storage temperature -20…+60 °C
Air humidity (no condensation ≤95 % rel.
permitted)
Maximum height above sea level 4000 m
Mechanical data Dimensions (W x H x D):
● Without cover cap 430 x 398 x 165 mm
● With cover cap 443 x 404 x 188 mm
Protection category (IEC 60529) IP30
Color:
● Housing ~RAL 7035 light gray
● Cover cap ~RAL 9010
Approvals VdS G206109
LPCB 126bn/01
FM 3048514

21
Smart Infrastructure 009383_x_en_--
2023-07-06
Fire control panel (2 loops)/(2 loops, P) FC2020 in housing (Comfort)
Supply Mains voltage AC 115 / 230 V +10/-15 %
Power supply 150 W
Operating voltage DC 21…28.4 V
Operating current Max. 5 A
Battery capacity 2x 12 V, max. 25 Ah
Battery monitoring Yes
Network monitoring Yes
Inputs / outputs Connectable detector series Sinteso (FDnet)
Number of addresses Max. 252
Number of integrated line cards 1
Number of lines:
● Loops (with loop extension) or 2 (4)
● Stubs 4 (8)
Integrated inputs/outputs:
● Alarm RT relay output 1
● Fault RT relay output 1
● Monitored alarm outputs 1
● Monitored fault outputs 1
● Monitored horn outputs 1
● Freely configurable inputs/outputs 8
Interfaces Operating unit Integrated
Slots for serial interfaces RS232, 2
RS485
Slots for network modules 2
Slot for loop extension 1
Mounting space for cable kit 1
(communication)
Sounder module Max. 1
Ethernet port RJ45 1
Ambient conditions Operating temperature -8…+42 °C
Storage temperature -20…+60 °C
Air humidity (no condensation ≤95 % rel.
permitted)
Maximum height above sea level 3,700 m
Mechanical data Dimensions (W x H x D):
● Without cover cap 430 x 796 x 165 mm
● With cover cap 443 x 802 x 188 mm
Protection category (IEC 60529) IP30
Color:
● Housing ~RAL 7035 light gray
● Cover cap ~RAL 9010
Approvals VdS G206109
LPCB 126bn/01
FM 3048514
DNV GL (marine) MEDB00003UW
see document A6V10400920

22
Smart Infrastructure 009383_x_en_--
2023-07-06
23
Smart Infrastructure 009383_x_en_--
2023-07-06
Issued by © Siemens 2007
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

Document ID 009383_x_en_--
Edition 2023-07-06

You might also like