turbine sensor, with the frequency from 1Hz to

Manual of Intelligent Flow 5000Hz (V low ≤ 1V, v high ≥ 3V).


2、 Wiring instructions
2Temperature sensor can be connected with PT100 2.1 terminal Description:
Totalizer resistance signal or 0-10mA or 4-20mA standard
current signal.
3. the pressure sensor can be connected with 0-10mA
or 4-20mA signal.
4. signal output: variable output 4 ~ 20mA (load
100 ~ 500 Ω), relay contact normally open or
normally closed (AC250V, 10a). Terminal Description: (in the order shown above)
1.2Display function: it can display the
accumulated flow, instantaneous flow, accumulated heat, 113, 14: external supply of 24VDC power input terminal.
instantaneous heat, differential pressure, frequency, 2, 3, 4: relay output, 2, 3 are normally open, 3, 4 are
density, pressure, temperature, etc., and call the
display at any time through the panel key. normally closed (AC250V, 10a).
1.3 Various protection measures.Communication, 5, 6, 7: pulse / frequency flow input (vortex street,
sensor input and current output have lightning
protection. turbine, etc.), GND: negative power supply, fr:
1.4 High precision acquisition.The analog quantity frequency, 24V +: positive power supply.
is better than 0.2% FS and the frequency quantity is
better than 0.1%.The internal operation accuracy is 2 89:4-20ma transmission output (active output).
This flow totalizer can be matched with vortex × 10-5%. 10, 11, 12:485 communication interface ground, a +, B
flowmeter, throttling device, turbine flowmeter, 1.5 Communication function: it has RS485
communication interface and conforms to Modbus -.
electromagnetic flowmeter, elliptical gear flowmeter
protocol. 1521: internal 24V power supply ground of integrator.
and other flowmeter.The flow totalizer adopts high 1.6 It has a variety of flow calculation modes and
performance processor and standard equation density compensation functions, and can be programmed 1617: pressure transmitter 4-20mA current input (no
calculation, which solves the problem of imprecise and combined.
external power supply required).
1.7 Power off protection function: the calculation
compensation algorithm of traditional totalizer.The 2019: flow / differential pressure transmitter 4-20mA
results in the machine and the data set by the user
high integrated and high-performance device is used to will not be lost in case of unexpected power off, and
current input (no external power supply required).The
solve the problem of measurement drift and realize wide the storage time is more than ten years.
temperature range and high-precision acquisition.The 1.8 Working conditions: temperature: - 20 ~ 55 active signal is connected to terminals 19 and 20 (such
℃.Humidity: 10% - 85% RH (no condensation).
product is designed with LCD Chinese character display, as electromagnetic flowmeter).
1.9 Power supply: AC 85 ~ 265vac, 50Hz; DC 24V.
Chinese and English optional, the keyboard operation is 1.10 Power: less than 10W 1618: temperature transmitter 4-20mA input (no external
intuitive, simple and user-friendly.Signal input and 1.11 Installation mode: horizontal.
1.12 Opening size: 152 ± 0.5 × 76 ± 0.5 (width power supply required).
output with lightning protection makes the equipment
× height, unit: mm). 22, 23, 24: PT100 temperature three wire system input.
more secure, which can be applied to various
1.13 Boundary dimension: 160 × 80 × 100 (width
measurement sites.And wireless GPRS wireless remote × height × depth, unit: mm). Two point two Cable selection: the input and output
transmission function can be attached. 1.14 Weight: about 1.0kg signal wires of the integrator shall be shielded wires,
1、 Main performance and index and the cross-sectional area of the core wire shall be
1.1It can be connected to various types of 0.5 ~ 2 mm2.
sensors.
1. the flow sensor can be connected to standard 3、 Panel display and key operation
throttling device and electromagnetic flowmeter, and 3.1 main page parameter display:
the signal can be 0-10mA or 4-20mA.It can also be
connected to the frequency output vortex street or The main page parameter display consists of the
following pages. The first power on parameter is
displayed as the instantaneous flow interface, which is After entering the setting item, the parameter 0: kg (kg); 1: t (T); 2: l (L); 3: Nm3 (standard
displayed by pressing the up key and the down key in setting value will be displayed.Press up key value plus condition m3); 4: condition m3.
sequence: one, press down key minus one, cycle display.Press the 5. Density in working state density in working state unit: kg / m3.
return key to cancel the parameter setting, and press 6. Standard state density standard state density value unit: kg /
the confirm key to make the setting effective. m3 (used to calculate gas standard state flow)
② Data entry: 7. Enthalpy setting the unit of enthalpy value of input fluid: kJ /
Unsigned data entry: press the left and right kg (kJ / kg) (not set in case of automatic compensation);
buttons to select the setting bit, and the selected bit 8. The small signal cutoff setting value is the percentage of the
will be displayed in reverse.Press the up key or the upper range of the output flow.
down key to display the value cycle, including the 9. Frequency 1-5 pulse output sensor frequency (different
decimal point. After setting, press the OK key to frequency values can be set for sectional compensation)
confirm that the value input is valid, and press the unit: Hz.
Note: this interface shows back key to cancel the setting. 10. Pulse instrument coefficient the instrument coefficient of 1-5
that the pressure value is pulse output sensor (different flow coefficient can be set
gauge pressure. 3.4 function introduction of each setting item for sectional compensation) unit: pulse / m3.Note: if there
3.2 record query: Press 3.4.1 flow: is no need for sectional compensation, only pulse meter
the confirm key on the main 1. Fluid selection coefficient is required.1 is OK, frequency 1-5 is set to 0
page to enter the main menu, and the selected items 0: water vapor; 1: other gases; 2: ideal gas; 3: by default
will be displayed in reverse.When the record query is liquid; 11. Corresponding unit of upper limit of differential pressure
selected, press the confirm key to enter the record 2. Compensation mode selection and upper limit of differential pressure of differential
query. 0: no compensation (the density is calculated pressure transmitter: kPa
3.3 parameter setting: In the main operation menu, according to the set working density); 1: 12. The lower limit of differential pressure corresponds to the
when you point to the setting parameters, press the temperature and pressure compensation (used for lower limit of differential pressure of differential
confirm key. Before entering the setting, first enter superheated steam measurement or gas pressure transmitter (generally 0), unit: kPa
the password (the default password is 0000). Set the measurement); 2: saturated steam temperature 13. The corresponding unit of flow upper limit and flow upper
value size through the up and down keys. Shift the left compensation; 3: saturated steam pressure limit of flowmeter is flow upper limit unit (item 15
and right keys. After entering the password, press the compensation. below)
confirm key to enter the function selection interface. 3. Flow sensor selection 14. The lower flow limit corresponds to the lower flow limit of
Press up and down to select.The selected item is 0: pulse flow sensor (vortex street, turbine, the flowmeter
highlighted.Press the Enter key to enter each setting etc.); 1:4-20ma throttle (orifice, nozzle, 15. Flow upper limit unit is set as the unit of flow upper and
item. Each setting item is divided into the following venturi, etc.); 2:0-10ma throttle; 3:4-20ma flow lower limit
two setting forms: (vortex street, turbine, electromagnetic, etc.); 3.4.2 temperature:
① Select class settings: 4:0-10ma flow. 1. Temperature sensor type selection
4. Unit selection:
0: not connected; 1:4-20ma temperature 2. Damping coefficient setting: it can be selected in 1-16 1. Remote transmission interval data upload
transmitter; 2:0-10ma temperature seconds. interval
transmitter; 3: PT100 temperature sensor; 3. Password setting: parameter setting password can be set. 2. IP address and port number server address and port number
2. The working temperature sets the temperature value of 4. Restore factory settings: press OK when you are instructed 3.5 quantitative control
common working state. If the temperature sensor fails, to restore factory settings. The basic quantitative
control function can be
the display and compensation temperature will be 5. Language setting: Chinese and English are optional. completed in this
calculated according to this value automatically. 3.4.5 communication: interface.First set the
batch set value (the
3. Standard state temperature standard state temperature unit: 1. The baud rate can be set as 1200, 2400, 4800, 9600, 19200. lowest flashing), press
℃ 2. The address range is 0-127. the confirm key to start
the batch accumulation,
4. Gas critical temperature setting gas critical temperature 3.4.6 alarm: and "start" will cancel
unit: ℃ 1. Upper limit setting of instantaneous flow alarm: output alarm the backlight display. When the batch accumulation
reaches the set value, the internal relay acts (2,
5. Zero point setting of temperature transmitter and lower limit when the instantaneous flow exceeds this set value. 3, 4 terminals), and the valve or pump action can be
temperature of 4-20 mA or 0-10 Ma temperature 2. Lower limit setting of instantaneous flow alarm: output controlled by connecting the relay and the AC
contactor.When the return key is pressed, the
transmitter unit: ℃ alarm when the instantaneous flow is less than this quantitative control interface will exit and the
6. Temperature transmitter range setting and 4-20 mA or 0-10 set value. internal relay will reset.

Ma temperature transmitter upper limit temperature 3. Upper limit of cumulative flow alarm: output alarm when 4、 Sensor algorithm description
corresponding unit: ℃ cumulative flow exceeds this value. Pulse / frequency output flow sensor:
7. Temperature compensation coefficient this parameter is the 4. Upper limit of temperature alarm: when the temperature Qm=F/K*ρ*3600
liquid temperature compensation coefficient. exceeds this value, an alarm will be output; when it is QM: flow (kg / h) f: frequency (Hz); K: instrument coefficient (n /
3.4.3 pressure: set to 0, an alarm will not be given if the temperature m3); ρ: density (kg / m3).
1. Select 0: not connected; 1:4-20ma pressure transmitter; 2:0- exceeds the limit. Differential pressure transmitter for throttling
10ma pressure transmitter. 5. Lower limit of temperature alarm: output alarm when the device:
2. The working pressure is set to the gauge pressure value in temperature is lower than this value.
common working state. If the pressure sensor fails (the 6. Upper limit of pressure alarm: output alarm when the Qm =k*

current value exceeds the range of 3-20ma), the pressure is higher than this value. When it is set to 0, QM: flow (kg / h); K: constant of throttling instrument; Pmax: upper
compensation pressure will be calculated automatically it will not alarm if the pressure exceeds the limit. limit of differential pressure (kPa); I: actual current value; IMAX:
according to this value, in MPa. 7. Pressure alarm lower limit setting: output alarm when the maximum current value; Imin: minimum current value; ρ: density
3. Local atmospheric pressure value of standard state pressure pressure is lower than this value. (kg / m3).
setting unit: MPa; 3.4.7 output: Calculation method of throttling instrument constant:
4. Critical pressure set critical pressure unit: MPa. 1. Upper limit of output flow range 4-20 mA upper limit
5. Pressure transmitter range setting transmitter range value of flow transmission output K=Qmax/

unit: MPa. 2. Lower range of output flow 4-20 mA lower output limit of Qmax: upper limit of flow (kg / h); Pmax: upper limit of differential
3.4.4 system: flow transformation pressure (kPa); ρ: density (kg / m3).
1. Cumulative reset: operation method reset. 3.4.8 remote transmission:
Standard current output flow sensor: 6、 Precautions for use
Qm =[(Lmax-Lmin) *(I- Imin)/(Imax-Imin) + Lmin ]*ρ 3. read this manual carefully. The wiring should be Although the instrument has undergone strict
QM: flow (kg / h); Lmax: flow upper limit; lmin: flow lower limit; accurate to avoid damaging the instrument. Pay special quality management, manufacturing and delivery, please
I: actual current value; IMAX: current maximum; Imin: current attention to 220 V AC to avoid electric shock; inform the company's business personnel, technical
minimum; ρ: density (kg / m3). 4. the place of use shall be indoors to avoid direct service department or the nearby company's agent
5、 Examples sunlight, rain and strong electromagnetic of any abnormal matters or accidents.
1The integrator is connected to the vortex flowmeter interference;. 8、 Packing list
with frequency output to measure steam, with PT100 and This product has been packed to prevent falling
pressure transmitter. See the right figure for wiring 7、 Ordering precautions before leaving the factory. Please open the instrument
mode Main settings: Thank you for purchasing this instrument. Please packing box and carefully check the items in the
read the "operation manual" carefully in advance for packing box. If you find any missing parts or damages
Flow rate
proper use. caused by human handling negligence or serious impact,
Fluid selection Steam
Please understand that this product will be please contact the manufacturer in time.
Compensation mode Temperature and
pressure compensation changed without notice due to improvement.If there is There are:
Sensor selection Pulse sensor any unknown, please contact our technical service 11 set of flow totalizer; 2. One manual; 3. One
Company Tons or kilograms department. certificate.
Meter coefficient Coefficient of vortex
flowmeter

2The integrator is connected with orifice flowmeter to


measure gas, with PT100 and pressure transmitter.
See the right figure for wiring mode
Main settings:

Flow rate
Fluid selection ideal gas
Compensation mode Voltage stabilizing
compensation
Sensor selection 4-20mA throttling
Company Standard cubic meter
Working density See the statement of
calculation
Standard density See calculation sheet
or check data
Upper and lower limit See the statement of
of differential calculation
pressure
Upper and lower limits See the statement of
and units of flow calculation