Range Of Product Modicon M251
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
[Us] Rated Supply Voltage 24 V DC
Complementary
Maximum Number Of I/O 7 (local I/O-Architecture)
Expansion Module 14 (remote I/O-Architecture)
Inrush Current 50 A
Data Backed Up 128 MB built-in flash memory for backup of user programs
Execution Time For 1 Kinstruction 0.3 ms for event and periodic task
0.7 ms for other instruction
Integrated Connection Type USB port with mini B USB 2.0 connector
Non isolated serial link serial with RJ45 connector and RS232/RS485 interface
Dual-port Ethernet 1 with RJ45 connector
Ethernet port Ethernet 2 with RJ45 connector
Transmission Rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for bus length of 3 m for USB
21-May-2024 1
Communication Service Downloading
IEC VAR ACCESS
Modbus TCP client
Modbus TCP server
Modbus TCP slave device
Monitoring
NGVL
Programming
Updating firmware
SMS notifications
DHCP client (Eth1)
DHCP server (Eth2)
Ethernet/IP originator (Eth2)
Ethernet/IP target (Eth1, Eth2)
Ethernet/IP scanner (Eth2)
Modbus TCP I/O Scanner and Messaging (Eth2)
FDR
FTP client/server
SNMP client/server
SQL client
Send and receive email from the controller based on TCP/UDP library
Web server (WebVisu & XWeb system)
OPC UA server
DNS client
Electrical Connection removable screw terminal blockpower supply (pitch 5.08 mm)
Marking CE
Mounting Support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
Height 90 mm
Depth 95 mm
Width 54 mm
Environment
2 21-May-2024
Standards ANSI/ISA 12-12-01
CSA C22.2 No 142
CSA C22.2 No 213
IEC 61131-2:2007
Marine specification (LR, ABS, DNV, GL)
UL 508
Electromagnetic Emission Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz
conforming to IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz
conforming to IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz
conforming to IEC 55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500
kHz conforming to IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz
conforming to IEC 55011
Immunity To Microbreaks 10 ms
Pollution Degree 2
Packing Units
Unit Type Of Package 1 PCE
21-May-2024 3
Package 1 Weight 371.0 g
Package 2 Height 30 cm
Package 2 Width 30 cm
Package 2 Length 40 cm
Package 3 Weight 48 kg
4 21-May-2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Well-being performance
Mercury Free
Pvc Free
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins
21-May-2024 5
Product datasheet TM251MESE
Dimensions Drawings
Dimensions
6 21-May-2024
Product datasheet TM251MESE
Clearance
21-May-2024 7
Product datasheet TM251MESE
Mounting Position
Acceptable Mounting
Incorrect Mounting
8 21-May-2024
Product datasheet TM251MESE
21-May-2024 9
Product datasheet TM251MESE
USB Connection to a PC
10 21-May-2024
Product datasheet TM251MESE
Ethernet Connection to a PC
21-May-2024 11