NATIONAL GRID SA
Title: Index Number:
WI-NG-6460-002-006
SAS Ethernet Switches testing Page Number:
2 of 3
3.2 CSD Engineer /Technician
a. Witnessing all related test conducted by the testing engineer .
b. Verifying the test results with respect to the acceptance criteria wherever
applicable
c. Dually signing the test formats prepared by the testing engineer
d. Archiving the completed test results as per the approved archiving system.
3.3 Contractor Testing Engineer
The contractor testing engineer shall Follow the instructions below for
conducting the SAS Ethernet switches testing.
Check as per the hardware specification the switches have the correct number
of following:
Switch model
Number of ports
Type of all ports
Power supply type (AC/DC)
Burden (VA)
Archiving System Website: http://AMAS TP-NG-6250-001-007
NATIONAL GRID SA
Title: Index Number:
WI-NG-6460-002-006
SAS Ethernet Switches testing Page Number:
3 of 3
4.0 REFERENCES
Index Number Title
PR-NG-6460-002 Project Commissioning Procedure
CL-NG-6460-002-001 SAS Prerequisites Check List
DS-NG-6460-002-006 SAS Ethernet Switches Test Formats
CL-NG-6460-002-002 Check List of SAS–Substation Automation System
5.0 REVISION HISTORY
Version Date Brief Description of Change / Annual Review
00 2018-02-26 Initial issue of National Grid Work Instruction
This document shall comply in accordance with the existing Company’s Rules and Regulations.
Any modifications therein found not conformance with the document shall be declared invalid.
For clarification and verification on this document, contact the following:
Engr. Khalid Ali Habiballah
Technical Support and Coordination Division
Commissioning Services Department
Technical Services Business Unit
Extension No. 77476 Email:
[email protected]Archiving System Website: http://AMAS TP-NG-6250-001-007
Commissioning Services Department
Company Name: Contract No : SAS Ethernet Switches Test Formats
Project Title:
Indix DS-NG-6460-002-006 Date: Page:1
1.0 Equipment General Data and Information
Substation
SAS Panel Name
Ethernet Switch Name Serial No
2.0 Ethernet Switch Communication Panel Inspection
2.1 Installed Equipment
Visual inspections of all the equipment installed in the cubicle are checked
according to corresponding drawings.
2.2 Cabinet arrangement
Mechanical construction of the related cabinet/ cubicle will be checked and
ticked off if considered ok.
2.3 Terminals and Wiring
Main attention has to be focused on the related SAS-device i.e.
communication switches within the cubicles and the SAS-network-
connections (mainly for fiber-optics).
Not
Test Checked N.A Remarks
Checked
Labels and Markings
Panel Dimensions, Color, Selection, Locking
System, etc.
Visual inspection (Units, and individual
modules) are undamaged.
Visual inspection of correct wiring practices
Proper earthling of cubicle and devices
Proper wiring in cable channel
MCB rating
All modules mounted according to general
arrangement
Terminal blocks & MCBs are mounted properly
Illumination within the panel is adequate
Ventilation system is adequate
Fibre Optics ferrules (Source & Destination)
Tested By Contractor Representative Witnessed By Commissioning Services Dept. Representative
_____________________ __________________________ ______________________ __________________________
Name in block letters Signature Name in block letters Signature
__________________ __________________
Date Date
Commissioning Services Department
Company Name: Contract No : SAS Ethernet Switches Test Formats
Project Title:
Indix DS-NG-6460-002-006 Date: Page:2
20% Spare Ports available for each Ethernet
Switch
Ping test
AC sockets
Fibre Optics Ferrules
Watchdog Contacts
Permanent DC/AC Supply for all Ethernet
switches equipment
3.0 Ethernet Switch Hard and Software Configuration
Hard-and software components are checked to ensure required functionalities.
Versions are recorded for later support purposes.
Not
Checke
Hardware components Checke N.A. Remarks
d
d
Device ID/Bay No:
Device type:
Order Number
Activated Function:
Number of Ports
ST
Type Of Ports LC
RJ45
Software and Module Interface components
Firmware:
Network Name
IP Address
Subnet Mask
Number of ports
Used
Communication IEC61850
Module Checked: ……………..
Burden (VA)
Tested By Contractor Representative Witnessed By Commissioning Services Dept. Representative
_____________________ __________________________ ______________________ __________________________
Name in block letters Signature Name in block letters Signature
__________________ __________________
Date Date
Commissioning Services Department
Company Name: Contract No : SAS Ethernet Switches Test Formats
Project Title:
Indix DS-NG-6460-002-006 Date: Page:3
4.0 Network Devices Communication Redundancy
The Reliability and security of the redundant LAN configuration will be checked.
Remove the FO/Link from Ethernet-Switch, Control and protection device. Check if
the Alarm appears in the Event/Alarm List.
Expected Not
Checked Approved Remarks
Time Approved
Ethernet Ring
Checking functionality in case of
disconnecting and connecting the
Terminal ring at several points
Interruption of the Ethernet link at
port A forming the ring.
Interruption of the Ethernet link at
port B forming the ring
Check redundancy
Check fault indication from
Ethernet ports
Check appearance on HMI 1 & 2
Check execution of command
Ethernet Process connections
Checking functionality in case of
disconnecting and connecting the
IEC61850 Process connection from
device
Check redundancy
Check fault indication from
Ethernet port
Check appearance on HMI 1 & 2
Check execution of command
Power Supply Redundancy
Interruption by failing AC supply
Interruption by failing DC supply
5.0 SAS Architecture Verification
Each IED has two active channels connected to two different Ethernet switch in
LAN-A & B for PRP Protocol. The test has to verify available connection when any
Ethernet Switch is OFF.
Tested By Contractor Representative Witnessed By Commissioning Services Dept. Representative
_____________________ __________________________ ______________________ __________________________
Name in block letters Signature Name in block letters Signature
__________________ __________________
Date Date
Commissioning Services Department
Company Name: Contract No : SAS Ethernet Switches Test Formats
Project Title:
Indix DS-NG-6460-002-006 Date: Page:4
The Procedure is to be repeated for each Ethernet switch for LAN-A & B and all
architecture connection shall be verified in form of alarms at HMI and SAS
Overview.
DC-1 DC-2
MCB MCB HMI Alarm
Ethernet Switch
____OFF ___OFF
MCB OFF
#_______
DC-1 & 2
ES Faulty
become Fail
Connected
FO to ES
No No All
All
Effect Effect Connected
on on FO Fails
system system Alarm
Note: There should not be any effect when DC-1 or DC-2 got fail except DC fail
alarm at HMI but if both redundant supply OFF then ES should become faulty and
all FO connected to that ES should be fail and Modify the above format for each
Ethernet Switch.
6.0 Cyber Security
Sr.
No Test Checked
.
1. Blocking of all the Unused Ethernet Switches port .
Configuration of the Ethernet Switches should be password
2.
protected.
Tested By Contractor Representative Witnessed By Commissioning Services Dept. Representative
_____________________ __________________________ ______________________ __________________________
Name in block letters Signature Name in block letters Signature
__________________ __________________
Date Date