CURRENT TRANSFORMERS

Split core current Transformers


IAP - IAM - IAG

IAG IAM IAP

Application Design features


Split core current transformers convert an alternating current of high value - The current transformers can be opened
into a proportional, lower one, which is appropiate to be measured by stan- - Cases of self-extinguishing polycarbonate UL 94 - V0
dard instruments (ammeters, wattmeters, varmeters, power factor meters, re- - Double secondary terminals, for short circuiting the secondary winding
lays, measuring transducers...) of rated currents 5 or 1 A. Their split core before opening the measuring circuit
allows their installation in already existing networks without need to cut the - Mounting brackets for the panel mounting and fixing clamps for the
conductors. They are suitable for indoor use in low-voltage networks, and fixing to the primary bus bar are included
they are built according to IEC and EN 61869-2 standards.

Accuracy
Our current transformers fulfil the specifications of the accuracy classes 0.5, 1 and 3, for the rated burden indicated in the table, in the same instrument.

IAP, IAM, IAG Technical Data


Electrical Features (according to IEC-61869-2
Rated secondary current 5 or 1 A
Frecuency range 50 - 60 Hz
Hightest voltage for equipment 720 V
Rated insulation level 3kV, 50Hz 1 min.
Rated continuos thermal current 1.2x IN
Rated short-time thermal current (Ith) 60x IN
Rated dynamic current (Idyn) 2.5x Ith
Thermal class of insulation, according to IEC-6085 E (120ºC)
IAP: busbar 2x 50x10 mm, 3x 40x10 mm or round conductor Ø 40mm
Window IAM: busbar 4x 80x10 mm or round conductor Ø 80 mm
IAG: busbar 4x 125x10 mm or round conductor Ø 80 mm
IAP: 1040 g ... 1365 g
Weight: (depending on primary current) IAM: 1190 g ... 1640 g
IAG: 1640 g ... 2495 g

Celsa Messgerate España S.L.


www.celsamessgerate-spain.com
5.5/1 [email protected] / +34 96 130 93 78
CURRENT TRANSFORMERS

IAP - IAM - IAG Technical Daten, Executions


Primary rated Rated burdens VA (sec. .../5A , .../1A)
current IAP IAM IAG
A Cl. 0,5 Cl. 1 Cl. 3 Cl. 0,5 Cl. 1 Cl. 3 Cl. 0,5 Cl. 1 Cl. 3
60 – – 1,25 – – – – – –
75 – – 1,25 – – – – – –
100 – 1,25* 2,5 – – 1,25 – – –
125 – 1,25* 3,75 – – 2,5 – – –
150 – 2,5* 3,75 – – 3,75 – – –
200 – 3,75* 3,75 – 1,25* 3,75 – – –
250 – 3,75* 7,5 – 2,5* 3,75 – – –
300 – 5* 10 – 3,75* 5 – – –
400 – 7,5 20 – 5 10 – – –
500 5 10 30 1,25 5 15 – 2,5 15
600 10 15 30 2,5 7,5 20 1,25 5 15
750 10 20 45 7,5 15 30 1,25 10 20
800 10 30 60 10 20 30 2,5 10 20
1000 10 45 60 10 20 45 5 15 30
1200 15 45 60 10 30 60 7,5 20 45
1500 – – – 10 45 60 10 30 60
1600 – – – – – – 15 45 60
2000 – – – – – – 15 60 60
2500 – – – – – – 20 60 60
3000 – – – – – – 20 60 60
Remark: These current transformers meet the demands for the classes 0.5, 1 and 3 in the same instrument. / * only ammeters